You are on page 1of 20

Substation Automation Products

IIntroduction
d i to the
h R
Relion
li 670
6 0 series
i
Hardware
SA-T Training
1MRG004718

Section 03

Contents

SA-T Training
1MRG004718
Slide 2

Hardware - General

Hardware configuration

Modules

Hardware overview

Local HMI

Summary

Hardware modules

Communication

Time synchronization

Relion

670 series Hardware general

Platform based

Closed casings of common look

HMI unit with Ethernet PC port

Small or medium size


graphical display

Common modules

Easy
y future hardware addition
possibilities

Dimension

Section 03

1/2, 3/4 or 1/1 of 19 wide and 6U


high

Mounting flexibility

Flush-, semi-flush, wall- and rack


mounting

Side by side

Compression type or ring lug cable


termination

SA-T Training
1MRG004718
Slide 3

Relion 670 series Hardware general

SA-T Training
1MRG004718
Slide 4

I/O flexibility
y

0 - 12 - 24 analog inputs with


different input combinations

1A or 5A on the CT inputs

Up to 220V on the VT inputs

3 to 14 slot positions to be used for


binary inputs/outputs and transducer
inputs

Max 224 binary inputs

Max 96 binary outputs

Max 24 mA inputs

Binary input voltage 24-250


24 250 Vdc

LDCM (per LDCM and in each


direction)

4 currents and 8 binary signals


or

192 binary signals

Section 03

Relion 670 series Hardware general

Section 03

Time synchronization

TCP/IP, Ethernet

IEC 61850, DNP 3.0

LON, SPA

IRIG-B

GPS

Binary input

Communication

IEC 61850-8-1,
61850 8 1 DNP 3
3.0
0

LON, SPA

LDCM (C37.94, G.703 or X21)

SA-T Training
1MRG004718
Slide 5

Relion 670 series Hardware general


1/1 19
19 case,
case 6U high

ADM
Power
Supply

SA-T Training
1MRG004718
Slide 6

In- /
O t t
Outputs

NUM

TRM

Transformer Input Module TRM1


and TRM2 (none, one or two)

Analog Digital Conversion module


ADM1 and ADM2 (corresponds to
TRMx)

Central Processing Unit NUM


(always included)

Input / Output modules BIM, BOM,


SOM, IOM and MIM

Power supply module PSM (always


included)

Section 03

Section 03

Hardware configuration Backplane modules


UBM

1/1 19
19 rack

Universal Backplane Module


(UBM)

CBM

Slot no: P1, P3 P13

P30 - P32 P40, P41

UBM

1/2 19 rack

TRM1 and TRM2,, Slot 40,, 41

ADM1 and ADM2, Slot 31, 32

NUM, Slot P30 (always)

1/2 19 case

TRM1, Slot P40

ADM1, Slot P31

NUM, Slot P30 (always)

Combined Backplane Module


(CBM)

CBM
Slot no: P1, P3 P5

1/1 19 case (from right to left)

P30, P31 P40

1/1 19 case (from left to right)

PSM Slot 1 (always)


PSM,

11 CAN-bus slots, Slot 3-13

1/2 19 case

PSM, Slot 1 (always)

3 CAN-bus slots, Slot 3-5

SA-T Training
1MRG004718
Slide 7

Section 03

Hardware configuration 1/1 19 case

CAN-bus

PSM

NUM

TRM

ADM

3 cPCI positions

1
2

1
PMC
PC-MIP 2

CAN-master

1
PMC
PC-MIP 2

NUM
N

ADM
A

ADM
A

11*CAN-bus

TRM
T

TRM
T

UBM

1
2
View from the front side

SA-T Training
1MRG004718
Slide 8

I/O modules
d l like
lik BIM,
BIM BOM,
BOM SOM,
SOM
IOM and MIM connected to the
CAN-bus

CAN-bus

PSM
P

CBM

Section 03

Hardware configuration 1/1 19 case

1
PMC
PC-MIP
PC
MIP 2

CAN b
CAN-bus

PSM
P

NUM

A
ADM
1

TR
RM

2 cPCI positions

1
2
CAN-master
CBM

UBM

14*CAN-bus

I/O modules like BIM, BOM,


SOM IOM and MIM connected
SOM,
to the CAN-bus

View from the front side


SA-T Training
1MRG004718
Slide 9

Transformer input module (TRM)

Isolation barrier preventing


disturbances to enter into
670 series

Adapt measured values to static


circuitry

Up to 12 analog inputs can be


connected (settable 50 or 60 Hz)

SA-T Training
1MRG004718
Slide 10

0 - 6 U, 110-220V rated range

6 -12 I, 1A and/or 5A rated current

Connectors (same type for all I/Omodules)

Screw compression or

Ring lug

Section 03

Transformer input module (TRM1 or 2)


1A

1A

5A

metering

9I+3U

All except REB670

All except REB670

RET670 RED670

All except REB670

All except REB670

Customized

Customized

Customized

Customized

All except REB670

All exceptt REB670

REL670

3
4

6I+6U

110-220
110
220 V

metering

7I+5U

5A

Section 03

SA-T Training
1MRG004718
Slide 11

Transformer input module (TRM1 or 2)


1A

1A

5A

metering

12I

12

All except REL670


and REC670

All except REL670


and REC670
All except REB670

SA-T Training
1MRG004718
Slide 12

110-220
110
220 V

metering

12

6I

5A

All exceptt REB670

Section 03

Analog to digital conversion module (ADM1)

Section 03

Analog inputs (from TRM1)


P31

Mounting position for OEM


module (only on ADM1)

P31:1

cPCIbus
Possible
P
ibl mounting
ti position
iti ffor
LDCM, GTM or RS485 module

P31:2

Possible mounting position


for LDCM or GTM module

P31:3
Front
SA-T Training
1MRG004718
Slide 13

Analog to digital conversion module (ADM2)

Section 03

Analog inputs (from TRM2)


P32

cPCIbus
Possible mounting position for
LDCM or GTM modules

P32:2

P32:3
Front
SA-T Training
1MRG004718
Slide 14

Section 03

Numerical module (NUM)


P30
UBM interface
P30:1
Mounting
gp
position
for SLM module
P30 2
P30:2

Possible
P
ibl mounting
ti position
iti
for IRIG-B or LDCM modules

P30:3

Possible mounting position for


LDCM module
cPCIbus
F t
Front

SA-T Training
1MRG004718
Slide 15

Section 03

Optical Ethernet module (OEM)

Communication

P31:1

IEC 61850-8-1

IEC 61850-9-2LE

DNP 3.0

One or two channels

Connectors

SA-T Training
1MRG004718
Slide 16

Ethernet (100 Mbit/s)

Glass fiber
fiber, type ST

Max 1 module per IED

Mounted on ADM1

Serial communication module (SLM)

Section 03

Rear

P30:1

Communication

LON

SPA or

IEC 60870-5-103

Connectors

Glass fiber, type ST

Plastic fiber, type HFBR


p
snap-in

Combination of glass &


plastic fiber

M 1 module
Max
d l per IED

Mounted on NUM

SA-T Training
1MRG004718
Slide 17

Line data communication module (LDCM)

Rear

Up
p to 4 modules p
per IED ((option)
p
)

Application example

Line differential protection

Need to exchange large number of binary


information

Communication:

multiplexed, route switched or dedicated


fibre using C37.94

external modems for G


G.703
703 and G
G.703E1
703E1

Different ranges

Short range (SR), Multi-mode, 3 km

Medium range (MR), Single-mode, 80 km

Long range (LR), Single-mode, 120-150


km

Connectors

SA-T Training
1MRG004718
Slide 18

SR: Type ST; MR and LR: Type FC

Module mounted on ADM and/or on NUM


(depending if IRIG-B and RS485 are included
and the number of LDCMs)

Section 03

Section 03

Galvanic LDCM (X21-LDCM)

The optical ports in LDCM (C37


(C37.94)
94) may be replaced with galvanic
X21-port (option)

Up to 4 modules per IED (same as optical LDCM)

Connectors

Electrical 15-pole female mini D-sub

Module mounted on ADM and/or on NUM (depending if IRIG-B and RS485


are included and number of LDCMs)

SA-T Training
1MRG004718
Slide 19

GPS time synchronization module (GTM)


Rear

Time Synchronizing (option)

Number of channels

SA-T Training
1MRG004718
Slide 20

GPS:

PPS:

Connectors

Antenna 50 Ohm: SMA

Optical PPS: Type ST

Module mounted on ADM (1p2)

Section 03

Section 03

Time synchronizing module (IRIG-B)

R
Rear

P30:2

Time Synchronizing using


a station clock (option)

Number of channels

IRIG-B:

PPS:

Connectors

Electrical IRIG-B:
BNC

Optical PPS:
Type ST

Module mounted on NUM

SA-T Training
1MRG004718
Slide 21

Galvanic RS485 communication module (DNP 3.0)


Rear

SA-T Training
1MRG004718
Slide 22

Station Bus
Communication (option)

DNP 3.0

Serial communication,
alternative for Ethernet
communication

2400 19200 Bits/s

Connectors

RS 485 6-pole

Soft ground 2-pole


connector

Max 1 module per IED

Mounted on ADM1

Section 03

Section 03

Power supply module (PSM)

P1

DC/DC Converter providing full


isolation between IED and
external battery system

Input range: 24-60 V DC or

Input range: 90-250 V DC

I t
Internal
l fail
f il relay
l output
t t

Connectors (same type for all


I/O-modules))

Screw compression or

Ring lug

Front
SA-T Training
1MRG004718
Slide 23

Section 03

Binary input module (BIM)

16 Independent Binary Inputs

Debounce filter, T = 5 ms

Oscillation suppression detection within


1 s; > 0 - 40 Hz

Pulse counting at all inputs (option)

Auxiliary voltage

SA-T Training
1MRG004718
Slide 24

24/40 V DC (20%)

48/60 V DC (20%)

110/125 V DC (20%)

220/250 V DC (20%)

Connectors ((same type


yp for all I/Omodules)

Screw compression or

Ring
g lug
ug

Section 03

Binary output module (BOM)

24 Single Output Relays or

12 Double pole Command


Output Relays

Connectors (same type for


all I/O-modules)

Screw compression or

Ring lug

SA-T Training
1MRG004718
Slide 25

Static binary output module (SOM)

SA-T Training
1MRG004718
Slide 26

6 Fast Static Outputs

48-60 VDC or

110-250
110
250 VDC

Operating time < 1ms

6 Change
g over Output
p Relays
y

Connectors (same type for all


I/O-modules)

Screw compression or

Ring lug

Section 03

Binary input/output module (IOM)

Section 03

8 independent Binary Inputs and 12


Binary Output Relays (10 trip and
signal relays, 2 fast signal relays)

Fix filter time 5 ms

Auxiliary voltage

24/40 V DC (20%)

48/60 V DC (20%)

110/125 V DC (20%)

220/250 V DC (20%)

Connectors (same type for all I/Omodules)

Screw compression or

Ring lug

SA-T Training
1MRG004718
Slide 27

Section 03

mA input module (MIM)

SA-T Training
1MRG004718
Slide 28

6 independent input channels

Software selected input ranges

0-5,, 0-10,, 0-20,, 4-20 mA

5, 10, 20 mA

Resolution: 16 bit

Accuracy: 0,1%

Connectors (same type for all


I/O-modules)

Screw compression or

Ring lug

Section 03

Hardware overview, 1/1 19 case


11*CAN

3*PCI

SLM
OEM
PSM

LDCM
(4 pieces)
GTM
IRIG-B
RS485

I/O

NUM

TRM1 TRM2

ADM1 ADM2

SA-T Training
1MRG004718
Slide 29

Section 03

Hardware overview I/O modules, 1/1 case


MIM *)
(max 4)
IOM
(max 6)
SOM *)
(max 4)
BOM *))
(max 4)

1/1 Case
Option 1:
1 TRM
14 I/O modules
Option 2:
2 TRM
11I/O modules

12 binary outputs
and 8 binary inputs

BIM
(max 11/14)

6 static and 6 change


over binary outputs
24 binary outputs
16 binary inputs

SA-T Training
1MRG004718
Slide 30

6 Transducer inputs,
setting range + 20 mA

*)) Total number of MIM,, SOM and BOM must be 4

Section 03

Hardware overview I/O modules, 3/4 case


MIM *)
(max 1)
IOM
(max 5/6)
SOM *)
(max 4)
BOM *))
(max 4)

3/4 Case
Option 1:
1 TRM
8 I/O modules

6 Transducer inputs,
setting range + 20 mA
12 binary outputs
and 8 binary inputs

BIM
(max 5/8)

6 static and 6 change


over binary outputs

Option 2:
2 TRM
5 I/O modules

24 binary outputs
16 binary inputs

*) Total number of MIM, SOM and BOM must be 4

SA-T Training
1MRG004718
Slide 31

Section 03

Hardware overview I/O modules, 1/2 case


MIM
(n.a.)
IOM
(max 3)
SOM
(max 3)
BOM
(max 3)

1/2 Case
1TRM
3 I/O modules

6 Transducer inputs,
setting range + 20 mA
12 binary outputs
and 8 binary inputs

BIM
(max 3)

6 static and 6 change


over binary outputs
24 binary outputs
16 binary inputs
SA-T Training
1MRG004718
Slide 32

Hardware overview I/O modules, Ring lugs

1/1 Case

3/4 Case

Option 1:
1 TRM
7 I/O modules

Option 1:
1 TRM
4 I/O modules

Option 2:
2 TRM
5 I/O modules

Option 2:
2 TRM
2 I/O modules

Section 03

1/2 Case
1TRM
1 I/O modules

SA-T Training
1MRG004718
Slide 33

Section 03

Local HMI

Small or medium size screen

3 status indication LEDs indicate the


status of the IED

SA-T Training
1MRG004718
Slide 34

Graphical LCD display (80 x 240 or


320 x 240 pixels)

Ready, Start and Trip

15 indication LEDs

12 push buttons for navigation,


control etc.

Ethernet front port connection, RJ45

Summary Basic hardware modules

Universal Backplane
p
Module ((UBM))

Combined Backplane Module (CBM)

Main Processing Module (NUM)

Power Supply Module (PSM)

Section 03

SA-T Training
1MRG004718
Slide 35

Summary Specific hardware modules

Binary
y Input
p Module ((BIM))

Binary Output Modules

Relay outputs (BOM)

Static and relay outputs (SOM)

Binary I/O Module (IOM)

mA input Module (MIM)

Analog Input Module (TRM)

Analog to Digital conversion Module (ADM)

Data communication Module (LDCM)

SA-T Training
1MRG004718
Slide 36

Optical (C37.94) or galvanic (X21)

Serial communication Modules

LON, SPA or IEC 60870-5-103 (SLM)

DNP 3.0 galvanic (RS485)

Optical Ethernet Module (OEM)

Time Synchronization Modules

GPS (GTM)

IRIG B
IRIG-B

Section 03

Section 03

Summary Communication

OEM (TCP/IP, Ethernet, SA-system)


SA system)

IEC 61850-8-1

IEC 61850-9-2LE

DNP 3
3.0
0

SLM (Serial Communication Module)

LON (SA-system)

SPA or IEC 60870-5-103 (SMSsystem)

RS485 (SA-system)

DNP 3.0

LDCM (communication between IEDs)

IEEE/ANSI C37.94

G.703/G.703E1 optical to galvanic


conversion

X21-modem
ode connection
co ec o

SA-T Training
1MRG004718
Slide 37

Summary Time synchronization

OEM (TCP/IP, Ethernet)

IEC 61850-8-1

DNP 3.0

SLM (Serial Communication Module)

LON

SPA

RS485

GSM (GPS module)

IRIG-B

SA-T Training
1MRG004718
Slide 38

DNP 3.0

Electrical IRIG-B
IRIG B

Optical PPS

Binary input

Section 03

Section 03

SA-T Training
1MRG004718
Slide 39