Professional Documents
Culture Documents
Cracking
Staining/discolouration
Sealant failures
Efflorescence
Rising dampness/water penetration
Corrosion
Buckling/deflection
Tile/plaster delamination
The types of facades affected by each defects are shown in the table below.
Defects
Cracking
Straining/discolouration
Sealant defects
Efflorescence
Rising damp/Water penetration
Misalignment and chip off
Corrosion
Delamination
Surface appearance
(a) Erosion due to rain water
(b) Surface abrasion
(c) Surface etching
Cement
render
X
X
X
X
Tiles
Building facades
Aluminiu
Natural
m
X
X
X
X
X
X
X
X
stone
X
X
X
X
X
X
Glass
X
X
X
X
X
X
X
X
X
To avoid or minimize the defect to the facades, several things need to be considered in the
design and construction.
i.
A proper analysis of wind design should be made since cladding elements can be
affected by short duration high speed gusting, local wind pressure and suction
effects.
ii.
iii.
iv.
contractor or specialist.
Attention on the joint sealants.
- Proper joint design
- Appropriate choice of sealant
- Good surface preparation and workmanship in installation of the sealant
- Consideration on the thermal/moisture changes in the design
- Consideration on the ultraviolet radiation and high temperature and humidity
Obtain accurate information from manufacturers to avoid misuse or inappropriate
choice and use of materials
Smallest size apartment: C1, C4, C5, C6, C7, C1-G, C4-G, C5-G (14m x 11.6m)
Requirement
Rooms minimum area:
1st: 11.0m2
2nd: 9.3m2
Others: 6.5m2
Width of every habitable room shall not be < 2m
The area and width of kitchen shall not be < 4.5m2 and
1.5 m
Checked: sufficient
ii.
Smallest size apartment: C1, C4, C5, C6, C7, C1-G, C4-G, C5-G (14m x 11.6m)
Requirement
Water closet with pedestal-type: 1.5m x 0.75m
Water closet other than pedestal-type: 1.25m x
0.75m
Bathrooms: 1.5m2 (width not < 0.75m)
Bathrooms with close fittings: 2m2 (width not <
0.75m)
Checked: sufficient
iii.
Requirement
The height of any basement shall not < 3.0m
Height
Basement 1: 3.5m
Basement 2: 3.5m
The height of ground floor parking shall not <2.5 m Ground floor parking: 5m
The height of headroom shall not < 2m
The height of any verandah shall not < 3.0 m
-
Checked: sufficient
Rain Water down Pipe (RWDP)
During the construction, it is important to make sure the RWDP positions are aligned
accordingly. This is to avoid complication in installing the RWDP.
Columns Positioning
The column arrangement as proposed by the architect are to be amended where the C&S
consultant would like to introduce additional columns in certain location due to the fact that
the column arrangement made by the architect are unable to fully support the overall building
structure.
Hacking of slab for M&E services installation works shall be according to these:
i.
Holes next to the column should be small and limited to two and on opposite sides
rather than on adjacent sides of the column as this will affect the design shear
ii.
iii.
allow coordination.
Large services holes should be located away from the column strips and column
heads in the centre of the bays. Again, the location and size of the holes should be
agreed early in the design stage.
vi.
vii.
viii.
Fire safety
All installed M&E services especially electrical circuit and energy supply system should be
protected from fire. Therefore for this project, passive fire proofing such as calcium silicate
boards are recommended to encase M&E services lines before installation of ceiling board
Calcium silicate is commonly used for high temperature
insulation material and formed into cladding for passive fire
protection. Since this material is easily damaged by water,
silicon treated sheets should be fabricated to mitigate potential
harm from high humidity or general presence of water.