Professional Documents
Culture Documents
Impedance Protection
The year of Profitable Growth
Power Automation
Progress. Its that simple.
Generator Protection
Overcurrent and Impedance
Protection
Presenter: Dr. Hans-Joachim Herrmann
PTD PA13
Phone +49 911 433 8266
E-Mail: Hans-Joachim.Herrmann@siemens.com
Power Automation
Summary
The short circuit is a heavy fault for a generator. In that case the short-circuit protection is a standard protection for a
Power Automation
generator. The electromotive force (e.m.f.) supplies at the moment of a short circuit the following current :
Progress. Its that simple.
I K(3) ?
1,1?VN
3 ?X d "
This subtransient short-circuit current is reduced with the typical time constants of a generator. The type of the excitation has
an important influence on the magnitude of the short circuit current. In the case of a short circuit near the terminals the
voltage is low and the voltage regulator starts to increase the excitation. A higher current is the result.
Dimensioning the co-ordination of the voltage regulator and excitation system (including excitation winding) based on a short
circuit current for a time of 8-10s is appr. 1,8 of the nominal generator current.
The settings of an overcurrent time relay is appr. 1,3 - 1,4 x I N . If the short- circuit current can be lower after a time an
undervoltage seal-in must be activated.
The short-circuit current depends on the fault type.
The ratio is I SC(1) : I SC(2) : I SC(3) = 5:3:2. In the case of a no load field voltage and a full load field voltage the range of the
short-circuit current is appr. 1:2,5.
For a turbo generator the following steady state short-circuit currents are
typically:
three-phase fault:
I SC ??(0,8 ... 2)I N
phase-to-phase fault:
I SC ??(1,2 ... 3)I N
single-phase fault:
I SC ??(2 ... 5)I N
(grounding of the generator star point)
If the generator is grounded with a low ohmic resistor the short-circuit
current is limited to the nominal current.
Part 1:
Part2:
- Overcurrent Protection
- Impedance Protection
- Differential Protection
Power Automation
A) Internal Faults
1) Isolated star point
(or high ohmic)
L3
Interturn fault
Phase to phase short circuit
B) External Faults
Transformer
Grid
Power Automation
- t
2 ? ?' ' - ?' ?e T' 'd
- t
2 ? ?' - ? ?e T' d
2 ?? ' '
k
2 ??
- t
2 ??' 'k ?e Tg
Combinations:
Driving Voltages
V??p
<
V?p
<
Vp
Actual reactances
X??d
<
X?d
<
Xd
Time Constants
T??d
<
T?d
<
Td
ik ?
transient part
Steady state
short circuit current
DC - current
t
?
?
t
t
?
?
2 ? I ' ' ? I' ?e T' ' d sin?? t - ? ?? I ' - I ?e T' d sin?? t - ? ?? I sin?? t - ? ?? I' ' ?e T g sin? ?
k
k
k k
k
k
?
?
?
?
Power Automation
Data:
xd = 0,24
Td = 1,125s
xd = 0,16
Td = 0,05s
Vp
Vp
Vp
Turbo generator
2,25
1,11
1,07
1,8
1,2
1,13
.V
N
.V
N
IK ?
2,25
?I N ? 1,26 I N
Xd
I K ?
I K ?
1,11
? I N ? 4,6 I N
X?d
1,07
? I N ? 6,7 I N
X?d?
Without Dc offset (? = 0)
Power Automation
Ik
R, Xd
?
0,5
Short circuit near the star point has small short-circuit currents
Power Automation
I >, t
G
I >, t
I >, t
I >>, t
I > - Generator
?t
? t:grading time
(approx. 0,3 s)
I > - Network
I >>
l
? Protection is connected on the star-point-CT (proof against internal faults - at open
time (0,1 s)
? Busbar connection: reverse interlocking is recommended for radial network
? Unit transformer connection: Ipick-up > 1,5 I ??SC(3, G) t ? 0,1 s
Power Automation
Logic:
I>, t
U<
I>
G
>1
&
V<
?1
S
R
Pick-up
T-Seal-in
Attention:
In ANSI or English speaking regions are very often used the inverse time
overcurrent protection. The trip time depends on the amount of current. In
the applications different types of characteristics are available.
t
The same
characteristic
is used
Grading time
G
Example: Very Inverse (ANSI)
IP - Pick-up current
(General pickup is fix at 1,1 I P)
D - Time multiplier (0,5s to 15 s)
?
?
?
?
3.922
t??
? 0.0982 ? ? D
2
??
?
? -1
I
?? I ?
?
?
?? P ?
Power Automation
10
Factor
1,0
0,25
0,25
1,0
V/VNG
Note:
To avoid an overfunction in the case of an fuse failure (voltage circuit
interruption), there is recommended a blocking via an external m.c.b. or
the internal fuse - failure -monitor function.
Power Automation
11
Impedance Protection
Power Automation
I>
tNetz +? t
Z1 ? 0,7XT
Z<
0,1s
Z1
G
XG
XT
Z<
?
?
Z ? 0)
12
Three-phase fault
Additional Infeed
RatioTr
Z<
ZT
Z Meas ? Z T ?
1
?Z L
2
Ratio Tr
ZL
Z<
Z Meas ? Z T ?
IK2
IK1
ZT
1
Ratio 2 Tr
IK
? I K2
??1 ?
? I K1
?
?? ?Z L
?
1
ZL
Ratio 2 Tr
RatioTr : Transformer Ratio
Power Automation
13
Single-phase fault
Phase-to-phase fault
L1
L1
L2
L2
L3
L3
Accurate measurement:
ZMeas
V
V L2
? ph.-E ?
I ph,max
I L2
Z Meas ?
V ph.-ph.
I ph.-ph.
? ZT ? ZL ?
1
?Z 0T ? Z 0L ?
2
14
X
X2
t(I>)
X1B
t(Z2)
X1
t(Z1)
R1 R1B R2
Z 1 ? 0,7X T
No direction element is
necessary because the
star point CT is used.
t(Z1B)
Z1
Z2
Z1B
Power Automation
15
ZG
ZT
ZL
G
I > (ZG)
t
ZT (backward)
ZG
2. Stage (ZT)
ZG: Generator
Transformer
Line
ZL
Z
ZT
ZT: Transformer
Line
ZL: Line
16