POWER SUPPORT SYSTEM (PSS)

POWER SUPPLY CHARGER


12 or 24 VDC @: 2.5, 5, 7.5, or 10 Amp Power Limited
3, 6, 9, or 12 Amp Non-Power Limited
The AlarmSaf Uninterruptible Power Support Systems (PSS) contain a
multi-regulator, float mode power supply/battery charger in a vented locking
cabinet. These units are available with power limiting or non power limiting for
use as primary or backup DC power systems. The systems are offered in 12 or
24 volt outputs with capacities of 3, 6, 9 and 12 Amps in single output or 2.5,
5, 7.5, or 10 Amps in multi-output power limited systems for power distributed
or split load requirements.

DIMENSIONS
Cabinet Size
B03
11"H x 15"W x 4"D
28cm x 38cm x 10cm
B04
15"H x 18"W x 4"D
38cm x 46cm x 10cm

Cabinet Material
B03
18 Gauge Painted Steel
B04
16 Gauge Painted Steel
Battery Space (Units 6 Amps or lower)
B04
7"H x 18"W x 4"D
16.8cm x 46cm x 10.2cm

SPECIFICATIONS
Input Characteristics
Input Voltage: 120 VAC, 60 Hz., Single Phase
Input Current: 2 to 10 Amperes (Model Dependent)
Output Characteristics
Output Voltage: 13.8 or 27.6 VDC
Ripple: @ 50% Rated Load < 1%
Overcurrent Protection
AC Fuse
Battery Fuse
Electronically Limited Regulators
PTCs (Current Limiting Protection)*
Thermal Protection
Transformer Link
Electronically Limited Regulators
Battery Chemistry
Lead Acid/Gelled Electrolyte
*PLS Models only

Visual Indicators
AC Presence: Green LED
Normal Operation: Green LED
Tripped PTC*: Yellow LED
Fault Detection Conditions Reported
High Battery/Output
Low Battery/Output
Low AC/No AC/Blown AC Fuse
Blown Battery Fuse
Tripped PTC
Trouble Output
Form "C" Relay Contacts
1 A @ 26 VDC
.5 A @ 120 VAC
Temperature Range
32F to 120F
0C to 50C

FEATURES

Uninterruptible Power System


Thermal & Battery Reverse Polarity Protected
Vented Locking Cabinet
Interior Battery Space (Model Specific, B04)

Power Limited Outputs (Available)


Fault Detection
Available Matching Battery Cabinets
PLS Version Power Distributed
Continuous Current Ratings

UL294 Access Control System Units


UL603 Power Supplies for use with Burglar Alarm Units
UL1481 Power Supplies for Fire Protective
Signaling Systems (NPL Models)

Complies with NFPA72 - National Fire Alarm Code


CSFM Listed - # 7315 - 1214:102
MEA Accepted - #MEA - 14 - 93 - E

AlarmSaf 65A Industrial Way, Wilmington, MA 01887-3499, USA, Telephone: 978-658-6717, Fax 978-658-8638, www.alarmsaf.com

52-100, 7/1/97

LISTINGS

MAXIMUM BATTERY
PLUS Selection versus Maximum Battery Size

N-PLUS Selection versus Maximum Battery Size


160
Max. Battery

Max. Battery

100
80
60
40
20

120
80
40
0
NPL-xx030
NPL-xx090
NPL-xx060
NPL-xx120
Max battery at full current rating of the unit
Max battery at 50% current rating of the unit
Max battery at 3 A(NPL-xx120 only)

0
PLUS Unit
PLS-xx025
PLS-xx050

PLS-xx75
PLS-xx100

ORDER INFORMATION
PLS - Power Distributed Uninterruptible Systems
Order
Number
01601
01602
01605
01606
01608
01609
01612
01613
01615
01616
01617
01618

Model Number
AS/PLS-12025-B03-UL
AS/PLS-12025-B04-UL
AS/PLS-24025-B03-UL
AS/PLS-24025-B04-UL
AS/PLS-12050-B03-UL
AS/PLS-12050-B04-UL
AS/PLS-24050-B03-UL
AS/PLS-24050-B04-UL
AS/PLS-12075-B04-UL
AS/PLS-24075-B04-UL
AS/PLS-12100-B04-UL
AS/PLS-24100-B04-UL

System
Voltage
12 VDC
12 VDC
24 VDC
24 VDC
12 VDC
12 VDC
24 VDC
24 VDC
12 VDC
24 VDC
12 VDC
24 VDC

System
Current
2.5 A
2.5 A
2.5 A
2.5 A
5A
5A
5A
5A
7.5 A
7.5 A
10 A
10 A

Cabinet
B03
B04
B03
B04
B03
B04
B03
B04
B04
B04
B04
B04

Maximum
Battery
Capacity
34 Ah
34 Ah
34 Ah
34 Ah
50 Ah
50 Ah
50 Ah
50 Ah
80 Ah
80 Ah
100 Ah
100 Ah

Maximum
AC Input
Current
1.5 A
1.5 A
3.0 A
3.0 A
2.5 A
2.5 A
5.0 A
5.0 A
3.5 A
7.5 A
5.0 A
10 A

UL
Listing
A, B
A, B
A, B
A, B
A, B
A, B
A, B
A, B
A, B
A, B
A, B
A, B

Cabinet
B03
B04
B03
B04
B03
B04
B03
B04
B04
B04
B04
B04

Maximum
Battery
Capacity
40 Ah
40 Ah
40 Ah
40 Ah
70 Ah
70 Ah
70 Ah
70 Ah
120 Ah
120 Ah
160 Ah
160 Ah

Maximum
AC Input
Current
1.5 A
1.5 A
3.0 A
3.0 A
2.5 A
2.5 A
5.0 A
5.0 A
3.5 A
7.5 A
5.0 A
10 A

UL
Listing
A, C
A, C
A, C
A, C
A, C
A, C
A, C
A, C
A, C
A, C
A, C
A, C

NPL - Non-power Limited Uninterruptible Systems


Order
Number
01501
01502
01505
01506
01508
01509
01512
01513
01515
01516
01517
01518

Model Number
AS/NPL-12030-B03-UL
AS/NPL-12030-B04-UL
AS/NPL-24030-B03-UL
AS/NPL-24030-B04-UL
AS/NPL-12060-B03-UL
AS/NPL-12060-B04-UL
AS/NPL-24060-B03-UL
AS/NPL-24060-B04-UL
AS/NPL-12090-B04-UL
AS/NPL-24090-B04-UL
AS/NPL-12120-B04-UL
AS/NPL-24120-B04-UL

System
Voltage
12 VDC
12 VDC
24 VDC
24 VDC
12 VDC
12 VDC
24 VDC
24 VDC
12 VDC
24 VDC
12 VDC
24VDC

System
Current
3A
3A
3A
3A
6A
6A
6A
6A
9A
9A
12 A
12 A

UL Listings:
A= UL294 - Access Control Systems Units
B= UL603 - Power Supplies for use with Burglar-Alarm Units
C= UL1481 - Power Supplies for Fire Protective Signaling Systems

Cabinets:
B03= 11H x 15W x 4D
B04= 15H x 18W x 4D