Professional Documents
Culture Documents
Commissioning
&
Operation
FireFinder
SP Series
FIREFIGHTER FACILITY
POWER ON
ALARM
PRE-ALARM
FIREFINDER
AMPAC
PH: 08 9242 3333
SYSTEM IS NORMAL
FAULT
15/1/2003
14:00:00
AUX ALARM
WARNING
SYS FAULT
SUPPLY FAULT
ISOLATED
EARTH FAULT
EXTERNAL BELL
ISOLATE
WARNING SYS
ISOLATE
PREVIOUS
NEXT
ACKNOWLEDGE
RESET
ISOLATE
SYSTEM FAULT
TEST MODE
DE-ISOLATE
LOOP
ABC
DEF
FAULT
OUTPUT ISOLATE
SENSOR
JKL
AUXILIARY
FAULT / ISOLATE
ZONE
TUV
WXYZ
AIF
ACTIVE
DISPLAY
TO
SPACE
Isolate
Alarm Fault
MNO
GHI
CANCEL ENTRY
PQRS
SYMB
ENTER
MENU FUNCTION
Fire Finder
TM
Isolate
Alarm Fault
New
ConfigManager
Version
A
AS
S44442288
advanced
warning
Our aim is to provide Consistently Excellent Service in the eyes of our customers
MAN2744
INDICATION
ALARM
Loop X sensor X
LX SX ZX
STAT: ALARM
DATE & TIME
ZONE ALARMS X OF XX
2.
TYPE
NEXT
Loop X sensor X
LX SX ZX
STAT: ALARM
DATE & TIME
ACKED ZONE ALARMS X OF XX
ALARM
4.
5.
6.
ACKNOWLEDGE ALARM
ACKNOWLEDGE
3.
TYPE
ISOLATE BELL
EXTERNAL BELL
ISOLATE
RESET
RESET ALARMS
ACKNOWLEDGE RESET
ACKNOWLEDGE
ii
Table Of Contents
Page No
System Overview..........................................................................................................................3
6.9
Printer ..........................................................................................................................29
6.9.1
Indicators and Buttons ...............................................................................29
6.9.2
Maintenance.................................................................................................30
6.9.3
6.9.4
10
11
12
13
Fault Test......................................................................................................60
13.2.3
Lamp Test.....................................................................................................60
ii
14.9
14.8.2
14.8.3
14.8.4
14.8.5
14.8.6
Mismatch Detected......................................................................................67
15
16
17
18
19
20
21
22
Address Setting..........................................................................................................................80
23
24
Glossary of Terms......................................................................................................................86
25
Definitions...................................................................................................................................87
26
iii
This contract has been entered into by the person or company user of this document (hereafter called the
Trader) and AMPAC Technologies (hereafter called AMPAC) of 97 Walters Drive, Osborne Park Western
Australia 6017. Under terms and conditions as specified hereunder.
Whereas AMPAC and the Trader for their mutual benefit and pursuant to a working relationship which may
be established, anticipate that AMPAC will disclose in the form of this document, information of a secret, or
confidential or proprietary nature (hereinafter collectively referred to as Proprietary Information).
Whereas AMPAC desires to ensure that the confidentiality of any Proprietary Information is maintained in
accordance with the terms of this Agreement;
NOW, THEREFORE, in consideration of the foregoing premises, and the mutual covenants contained
herein, the Trader hereby agrees as follows:
1. The Trader shall hold in trust and confidence, and not disclose to any person outside its organisation,
any Proprietary information which is disclosed to the Trader by AMPAC under this Agreement.
Proprietary Information disclosed under this Agreement may be used by the Trader only for the
purpose of carrying out work on or with AMPAC supplied equipment and may not be used for any other
purpose whatsoever.
2. The Trader shall disclose Proprietary Information received by AMPAC under this Agreement to
persons within its organisation only if such persons are legally bound in writing to protect the
confidentiality of such Proprietary Information.
3. The undertakings and obligations of the Trader under this Agreement shall not apply to any Proprietary
Information which :
1. Is disclosed in a printed publication available to the public, is described in patent anywhere in the
world, or is otherwise in the public domain at the time of disclosure;
2. Is generally disclosed to third parties by AMPAC without restriction on such third parties;
3. Is shown by the Trader to have been in its possession prior to the receipt thereof from AMPAC;
4. Is approved for release by written authorisation of AMPAC; or
5. Is not designated by AMPAC in writing or by appropriate stamp or legend to be of a secret,
confidential or proprietary nature.
4. This Agreement will be binding upon and inure to the benefit of the parties hereto, and their respective
successors and assigns.
5. This Agreement, and all rights and obligations hereunder, shall expire on the 10th anniversary of the
date of issue of this document.
These terms are accepted by the Trader on receipt and retention of this document.
Page 1
2
2.1
This manual contains all the information required to install, commission and operate the FireFinder SP
series Fire Alarm Control Panel (FACP) fitted with Version 6 software and is only available to and for the
use of personnel engaged in its installation, commissioning and operation.
2.2
General Requirements
The FireFinder SP series FACP has been designed and manufactured from high quality commercial
components so as to comply with major world standards. To ensure these standards are not compromised
in any way installation staff and operators should;
2.3
1.
2.
be familiar with the contents of this manual prior to the installation, commissioning or
operation of a FireFinder control system;
3.
4.
be aware that if a problem is encountered or there is any doubt with respect to the
operational parameters of the installation the supplier should be contacted.
References
Fire
AS4428 - Fire Detection, Warning, Control and Intercom Systems Control and
Indicating Equipment. Part 1 and Part 4
2.4
Symbols
Note:
Configuration considerations
Page 2
System Overview
The FireFinder SP series is an Intelligent Analogue / Addressable and / or Conventional Fire Alarm
Control Panel capable of supporting:
Apollo Discovery and XP95 Intelligent Detectors, Multisensor, Photoelectric, Ionisation,
Thermal (heat) and CO detectors.
Addressable Initiating Devices: Modules that monitor any conventional normally open contact
such as supervisory switches and flow switches.
Conventional two wire zone detector circuits
Multiple input/outputs
High Level Interfaces
Graphical Interfaces
Remote LCD Repeaters
Remote LED mimics
Peer to Peer networking
Master Slave (Main - Sub) networking
Main panel plus Data Gathering Panels networking
AS 4428.1
NZ4512
EN54
MS1404
CP10
CONVENTIONAL ZONE
USING CONVENTIONAL DETECTORS
AND BASES
HIGH LEVEL
INTERFACE
PRESS HERE
TO BREAK
E.O.L
3K3
FIRE
ALARM
NOR MAL
ALARM
DEF ECT
P REVIOUS
NEXT
BUZZ ER
MUT E
I SOLATE
CONVENTIONAL ZONE
CIRCUIT
PRE- ALARM
MEN U
ANCILLARY
SERVICES
FLOW SWITCH
E.O.L 20K
MANUAL CALL
POINT ( MCP )
ANALOGUE DETECTORS
EXTERNAL
COMMUNICATION
LOOP
ION
OPTICAL
4K7
HEAT
PRESS HERE
ISOLATOR
TO BREAK
FIRE
ALARM
FIREFIGHTER FACILITY
PO WER ON
PRE-ALARM
ALARM
FIREFINDER
AMPAC
PH: 08 9242 3333
SYSTEM IS NORMAL
15/1/2003
14:00:00
EARTH FAULT
WARNING SYS
ISOLATE
PREVIOUS
ACKNOWLEDGE
RESET
ISOLATE
T EST MODE
DE-ISOLATE
LOOP
FAULT
OUTPUT ISOLATE
SENSOR
JKL
ZONE
TUV
WX YZ
DISPLAY
TO
SPACE
AUXILIARY
FAULT / ISOLATE
AIF
ACTIVE
Isolate
Alarm Fault
4
7
L2
SYSTEM FAULT
NEXT
ABC
L1
OUT
SUPPLY FAULT
DEF
M NO
8
0
G HI
IN
ADDRESSABLE
LOOP
NO
4K7
PQ RS
SY MB
ENTER
SINGLE INPUT
DEVICE
CANCEL ENTRY
MENU FUNCTION
FireFinder
TM
C1
IN-1
IN-2
NO
ISOLATOR
IN-3
RELAY
O/P 3
NC
C3
+ +24V DC
-
PRESS HERE
TO BREAK
N/O
RELAY
O/P 2
C2
NO
AS PER INPUT 1
E.O.L 10K
AUX OUTPUTS
NC
AS PER INPUT 1
SOUNDER
RELAY
O/P 1
NC
20K
EOL
N/O INPUT
SWITCH
Isolate
Alarm Fault
E.O.L 20K
EXTERNAL BELL
ISOLATE
AUX ALARM
WA RN IN G
SYS FAULT
ISOLATED
N/C
RELAY
OUTPUT
MONITORED
INPUT
4K7
FAULT
+
-
+24V DC
F I RE
A LAR M
FIREFINDER
FACP
HIGH LEVEL
INTERFACE
INPUT/OUTPUT
UNIT
SOUNDER
CONTROL
LOOP SOUNDER
ZONE MONITOR
CONVENTIONAL DETECTORS
MAXIMUM OF 20
E.O.L
6K2
Page 3
SPECIFICATIONS:
MAX LENGTH = 2KM
MAX RESISTANCE = 50ohms
MIN CABLE SIZE = 1.5mm
+ -
R N17
C H8
CH8 C H6
-V
-V
+V
+V
20 WAY
POWER
SUPPLY
UNIT
(AC)
L(AC) N(AC)
U11
U10
DANGER
240V
+VE
LOOP COMMS
SLAVE CPU
(302-6692)
SLAVE CPU
(302-6692)
CPU BOARD
(BRD85CPU)
CN1
CN1
U14
RN20
POWER
U13
CN1
SLAVE CPU
(302-6692)
U15
CN2
CN5
TB4 AUXILIARY
NO C NC
16 WAY
CN2
CH8
TB2
PSU MONITOR
BRIGADE I/F
27V IN
C N16
C 12
SERIAL RELAY
BRD (302-7320) OR
10 WAY
CN7
TB6
C N6
BZ1
EXPANSION LEDS
C N5
FRONT PANEL
PRINTER
CN2
26 WAY
TX1
POW ER
CN3
GENERAL INDICATOR, OR
X- PRINTER
(OEM1447)
C/W MOUNTING
PLATE.
(KIT = 159-0093)
FAN TERM
BRD (BRD25FTB)
MOUNTED ON CONVENTIONAL
OR LOOP TERMINATION BRD
VALVE MON
NO C NC
CN2
CN4
ALARM
NO C NC
ZD7
CN3
CN1
BRIGADE
O/P TERM
BOARD
(302-6732)
TB10
+ IN -
DOOR SW DBA/MCP
CN6 SGD II
+ BAT -
FAN CONTROL OR
AGENT RELEASE
COMMS OUT
D
C
B
CTS
COMMS IN
D
C
B
TXD
RXD
RTS
COM
TB1
TB1
TRX-
SCRN
TRX+
CTS
RXD
+27V
RTS
10 WAY
TXD
EXPANSION PANEL
3 WAY
BATT FAIL
C
C N3
CN1
ISOLATE
NO C NC
C H2
CN 4
0V
C N2
+ -
R17
MODEM
CN21
C N8
C H1
T H1
CN3
CN1
C N10
FAULT
NO C NC
CN3
TP3
D14
MAINS
SWITCH
TB3
-VE
C N18
CN2
CN1
CN2
EARTH
STUD
EXT
+35V
BELL2
-
L2+ L1-
EXT
+35V
CN2
a b
L2+ L1-
CN3
a b
EXT
+35V
C N14
C N15
C N11
L2+ L1-
BELL1
-
C N13
EXT
+35V
L2+ L1-
C N20
D13
GROUND
C H15
CH16
NEUTRAL
CN17
ACTIVE
TB3
TB2
TB3
TB2
CN3
OUT
302-7250
CN2
302-7240
CN1
CN1
TO BATTERIES
AGENT TERM
BRD OR
FAN TERM
BRD
RJ45/8 PIN
MAINS
INPUT
DANGER
240V
EARTH
STUD
CN2
CH15
MAINS
SWITCH
L(AC) N(AC)
CN10
PSU MONITOR
BRIGADE I/F
(AC)
+VE
-VE
CN1
GROUND
CN3
NEUTRAL
20 WAY
ACTIVE
16 WAY
SLAVE CPU 2
SLAVE CPU 3
SLAVE CPU 4
CPU BOARD
CH15
-V
-V
+V
+V
10 WAY
CN7
ZD7
CN6
CN8
CH2
CN1
PR INTER
BELL2
-
CN5
3 WAY
TB2
TB1
TB6
FAULT
NO C NC
CN1
CN2
COMMS OUT
D
C
B
ALARM
NO C NC
S
A
CTS
TB3
X- PRINTER
(OEM1447)
C/W MOUNTING
PLATE.
(KIT = 159-0093)
VALVE MON
NO C NC
RXD
RTS
BRIGADE
PSU MON.
BOARD
BATT FAIL
C
TB2
+
COM
TXD
ISOLATE
NO C NC
NETWORK
I/F CARD
BLANK
+ -
COMMS IN
D
C
B
CN2
TB10
CN6
TB3
+27V
0V
CN1
CONTROLLER
I/F CARD
TB2
COM
TXD
RXD
RTS
CTS
TRX+
TRXSCRN
TB1
CN3
OUT
CABINET (291-0076)
TO BATTERIES
Page 4
CN3
SLAVE CPU
6
SLAVE CPU
7
SLAVE CPU
8
SLAVE CPU
5
20 WAY
BLANK
TB3
+ -
ANCILLARIES or
HOUSING BLANKS
AGENT RELEASE
MODULE OR
FIRE FAN CONTROL
MODULE
POWER
SUPPLY
UNIT
BELL1
-
RJ45/8 PIN
GENERAL
INDICATOR
CARD
3 WAY
TB4 AUXILIARY
NO C NC
CN5
SGD II
DOOR SW DBA/MCP
+ IN -
+ BAT -
CN1
FireFinderTM Description
The following description does not relate to specific cabinets as the size of each cabinet will vary with the
amount of hardware fitted.
The heart of the FireFinder consists of two boards collectively known as the Controller. These boards
are the Main Board (BRD85MBA) and the CPU board (BRD85CPU). Combining these two boards with a
front panel (302-690) forms the basis for a FireFinder FACP. A single FireFinder Controller without an
expansion board has the capacity to interface to four (4) FireFinder Slave CPUs modules. Each of these
Slave CPUs can interface to 16 Zone Conventional Termination Boards, Loop Termination Boards or
Input/Output Boards as well as communicate with the Brigade / PSU Monitor Board (302-673).
The Main Board (BRD85MBA) has the Slave CPU Board for the first Loop Termination Board and the
provision for mounting of up to three additional FireFinder Slave CPUs. The FireFinder Slave CPUs all
have the same software installed and the manner in which they operate is automatically determined by the
type of termination or interface board onto which they connect.
If the system is to be expanded to have more than four Slave CPUs an Expansion Board (302-688) is
required. This board contains FireFinder Slave CPU No. 5 and expansion sockets for three more. This
configuration allows for a maximum number of 8 Slave CPUs that any one Controller can accommodate.
If a system is required to be expanded beyond eight Slave CPUs then either local networking using up to a
total of four controllers (max 32 Slave CPUs) within the one cabinet may be fitted or external networking
must be used.
The FireFinder has an internal ASPI ( Ampac Serial Peripheral Interface ) serial bus. This serial bus
provides interfacing to the Brigade /PSU Monitor Board and if required up to eight (8) Sounder Board/s
(302-7420/1).
FireFinder has a second serial interface that connects to ancillary boards that can be designed into a
system to control / monitor field plant / equipment and agent release .
Where the system design exceeds the capability of one FireFinder then other FireFinder panels can be
networked together to provide an expanded system containing multiple boards in a variety of applications.
Some of these applications include:
SmartGraphics
A Network FireFinder System supports a combination or all these options on a single network. Each
panel on the network is regarded as a node. The NETWORK BUS can be accessed using either a
Network Interface Card (NIC 302-724) and/or Controller Interface Card (CIC 302-725). Modules that are
supported on the network are Remote LED Mimic Board (302-715), Remote Liquid Crystal Display
Repeater (302-720, 302-721), remote FireFinder main panels and other FireFinder remote data
gathering panels. The network configuration determines whether a NIC or a CIC or a combination of both
is required.
Page 5
Page 6
CN1
CN1
CN21
CN2
CN2
KEY
TO FRONT KEYPAD
SW
(NOT USED IF THE
PANEL IS A DGP OR
SLAVE CONTROLLER)
CN1
+-
CN2
SLAVE CPU 8
302-6692
302-6880 JUN 98
CN2
TO CN5 OF THE
BRIGADE BOARD
OR SOUNDER
CONTROL BRD
IN CN1
NODE ADDRESS
LOOP COMMS
EXTERNAL LOOP
COMMUNICATION
CONNECTS TO
NIC OR CIC
RS485 COMMS TO
BACKPAN BORADS
UP TO 3 ADDITIONAL
SLAVE CPU's ( 6, 7 & 8 )
CAN BE SLOTTED INTO
THE EXP BOARD.
INTERNAL PRINTER
OUTPUT
PRINTER
CN5
CN7
SLAVE CPU 6
302-6692
CN2
INTERNAL SERIAL
COMMUNICATION
PORT
EXPANSION
LEDS
CN1
MODEM
I/O PORT
CN1
CN4
CN10
CN3
CN1
CN6
SW3
FRONT PANEL
BZ1
EXPANSION
PANEL
CN8
LK2
B U Z Z ER
ENABLE
SLAVE CPU 2
302-6692
CN2
SLAVE CPU 3
302-6692
#1 PANEL BOARDS
ARE CONNECTED
VIA A 20 WAY
RIBBON TO CN1
ON A SLAVE CPU
CN2
ON
RS485 COMMS TO
FRONT PANEL MODULES
SLAVE CPU 4
302-6692
CN2
CN18
27VDC
CN16 (CN16)
IN
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
BACKLIGHT
CN17
MAIN CPU
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
RESET
SW1
CN20
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
abc
C N 11
#2 UP TO 3 ADDITIONAL
SLAVE CPU's (302-6692)
CAN BE SLOTTED ONTO
THE MAIN BOARD.
+-
MAIN BOARD
Master / Sub FACP : Where there are one or more FACPs configured as local panels then each report
the status of their associated zones/devices to a MFACP. There is no control between local panels as the
MFACP is structured to have full control of the entire system.
Peer to Peer : Each FACP is regarded as a Master FACP and therefore a user can take control of the
entire fire system from any FACP.
Data Gathering Panel : The use of this type of panel may be installed where there is a need to have field
terminations only at one location and all control is performed by an FACP that is remotely located.
LCD Repeater Panel : The LCDRs are network compatible and provide the user with the ability to monitor
the status of designated areas or an entire site as well as execute specific interrogation tasks.
CN1
CN1
CN1
CN5
5
5.1
An Operators manual
003 keys
5.2
Anti-Static Precautions
To prevent damage to components, modules and boards, anti-static precautions MUST
be observed while performing any task within the FACP. The same applies to those
situated in the field
5.3
Prior to unplugging any connector, connecting or disconnecting any wiring, removing or replacing any
module or board ensure that both the Mains and Batteries have been isolated to prevent damage to panel
components.
5.4
The Cabinet
Features:
The cabinet is available in three different styles. Each style has the capability of being
either surface or flush mounted. With flush mounting though a surround is required.
Normally painted Arch White Ripple. Other colors are available on request.
The inner and outer door hinges are mounted on the left-hand side of the cabinet which
allow the doors open to an angle of 100. Locking is normally keyless though keyed entry
is available on request.
Knockouts are positioned at the top and rear of the cabinet to simplify cable entry.
5.5
Open the front door. Use the keyhole mounting holes in the top corners and in the lower middle of the unit to
mount it on the wall. Cables to connect the system to its external actuating devices are brought in through the
knockouts on the top or bottom of the cabinet.
12 mm
R 6mm.
Figure 5: Example SP1X Back Pan Mounting Hole & Removing Knockouts
Page 7
5.6
5.7
Operational Parameters
Temperature:
-5C to + 55C
Humidity:
25% to 75%
IP Rating
IP51
126
40
85 - 240V AC
450 mA (min)
19.2 V
Cabling Recommendations
Conventional Zones
Cabled in red Twin Plastic Sheath ( TPS ) or fire rated Radox or approved equivalent.
Analogue Loop
Two core cable. The minimum cable size is 0.75mm2, the maximum loop resistance is 50 ohms and the
maximum loop distance is 2km.
RS 422 Loop
Two twisted pair screened ( 4 core ) cable originating from FACP extending through the protected areas
and returning to the FACP.
Cable Specifications
Capacitance of 100 picofarads per metre or less
Resistance of 100 milliohms per metre or less
Impedance of loop typical 100 to 120 ohms
Maximum distances between modules 1.2km providing cable meets above specifications.
Recommended cable type
Belden 8132 or 9842 (non fire rated)
Radox FR Communication 0.75mm 1 pair (fire rated) x 2
LCD Repeater
Two by two twisted pair shielded cable (4 core) plus 2
Maximum distance between LCD mimic panel and FACP. is 1.2km.
Note:
core
power,
or
local
supply.
If the LCD operates in a redundant path mode the total cores including power is 10. The preferred
cabling method in this case is 1 X 2 pair twisted shielded cable ( 4 core ) and 1 X two pair twisted
shielded cable (4 core) plus 2 core power
Page 8
5.8
AC Mains will be connected to either a 2 Amp, 5 Amp or 18Amp 27 volt supply. These supplies will be
either mounted in the upper or lower right hand corner of the cabinet with the Brigade Board mounted
above or below. The wiring should enter the cabinet through the nearest knockout entry hole on that side.
See the following diagrams for the actual wiring and fusing details for each supply.
Input Voltage:
Input Freq
PFC
Tolerance at 27V
Load Regulation
Line Regulation
85 to 264 VAC
47 to 63Hz.
0.95~230VAC
+/- 1%
+/- 0.5%
+/- 0.5%
Output
27V @ 2.2A
Tolerance
1%
R&N
150mV
Efficiency
79%
SP-150-27
27V @ 5.6A
1%
150mV
84%
SP-500-27
27VDC @ 18A
1%
200mV
86%
POWER SWITCH
(LOOKING AT REAR)
BROWN
(ACTIVE)
1
C
LOOP
MAINS CORD
EARTH (GREEN)
TO CHASIS EARTH
TERMINAL
BLUE
(NEUTRAL)
NOTE:
Output Voltage is Set to
27.4Volts.
BROWN
(ACTIVE)
DC 27V TO PANEL
FUSE Rating
1 Amp 3AG Slow Blow
V ADJ
LED
V+
V-
GND
N(AC) L(AC)
Page 9
POWER SWITCH
(LOOKING AT REAR)
BROWN
(ACTIVE)
1
C
LOOP
MAINS CORD
BLUE
(NEUTRAL)
EARTH (GREEN)
TO CHASSIS EARTH
TERMINAL
27VDC TO BRIGADE
PSU MONITOR BOARD
BLACK
NOTE:
Output Voltage is Set to 27.4
Volts.
FUSE Rating
2 Amp 3AG Slow Blow
RED
L(AC) N(AC)
(AC)
-V
-V
+V
+V
+
V ADJ
BROWN
(ACTIVE)
1
C
EARTH (GREEN)
TO CHASSIS EARTH
TERMINAL
LOOP
MAINS CORD
BLUE
(NEUTRAL)
NOTE:
Output Voltage is Set to 27.4
Volts.
FUSE Rating
Amp 3AG Slow Blow
(AC)
(AC)
L
N
( AC )
(AC)
FG
NC NC
RC
RED
DC 27V TO PANEL
BLACK
+S
+27V 18A
-V
-S
V ADJ
Page 10
5.9
The Current Limiter, Fuse Board provides protection for the boards, cards and other 27VDC distribution
within the FACP when the 18Amp power supply is used. The four LEDs associated with the board indicate
that 27VDC is available at each of the outputs CN1 5.
BRD85CLFB1-A
U2
HS1
U1
RV1
Q1
Q3
Q2
N1236
F1
F2
1A
1A
F3
1A
F5
F4
1A
1A
TB1
TB4
CN1
CN2
CN3
CN4
CN5
0V+27V 0V
0V
+ OUTPUT -
+ BATT -
+ PSU I/P -
+BATT V
TO
302-6730
TB1
TO
302-6730
CN1
DISTRIBUTION
EV60 / 120 TONE GEN
All earth cabling shall be terminated to the panel Chassis Earth Terminal in a star configuration.
2.
The earth cable closest to the cabinet body shall have an M4 SPW beneath the lug then an M4 SPW
and M4 nut.
3.
Each additional earth cable shall be terminated with an M4 SPW and M4 nut.
4.
An additional M4 nut and M4 SPW are fitted to the Chassis Earth Terminal for installers to connect
their Mains Earth.
CHASSIS EARTH TERMINAL
M4 Nut *
M4 Shake Proof Washer *
M4 Nut
M4 Shake Proof Washer
Note:
M4 Nut
Earth Cable
Page 11
Function
Bell 1
Bell 2
Plant (Aux) Monitored
Plant (Aux) Non-Monitored
Warn Sys (Evac) Monitored
Warn Sys (Evac) Un-Monitored
Fault Monitored
Fault Non-Monitored
Isolate
Alarm
Valve Monitor
Batt Fail
( Relay Normally Energised )
Battery Output
Aux Power Output 1
Aux Power Output 1 EV40 use
Aux Power Output 2
Type of Output
2 Amp Fused
2 Amp Fused
1 Amp Fused
1 Amp Voltage Free Contacts
1 Amp Fused
1 Amp Voltage Free Contacts
1 Amp Fused
1 Amp Voltage Free Contacts
1 Amp Voltage Free Contacts
1 Amp Voltage Free Contacts
1 Amp Voltage Free Contacts
1 Amp Voltage Free Contacts
Thermistor Protected
1 Amp Fused Not Monitored
3 Amp Fused Not Monitored
1 Amp Fused Not Monitored
Fuse
F2
F3
F4
Relay
RL 1
RL 1
RL2
F5
RL3
F6
RL 4
RL6
RL 5
RL 8
RL 7
F7
F7
F8
Fuse Information
1. All fuses are of the Glass M205 style.
2. F1 is 6.3A
3. Voltage Free contacts are rated at 1A @ 30V
Inductive loads fitted to the Brigade PSU Monitor Board MUST be fitted with Flyback
diodes at the load for back EMF protection.
Transient Protection
Recognised transient line protection methodologies at the FACP and the load must also be
considered when connecting any control devices to the outputs be they in close or remote
proximity to the FACP.
Page 12
- + -
TB3
RL1
///
NC
Monitored
EOL
Required
EOL
10K
Ohms
NO
Bell 1
F2 2A
TB4
Bell
Un-monitored
or Sounder
Auxiliary
Monitored
EOL
Required
Warning System
Alarm
+ - NO C NC + - NO C NC
Bell 2
CN5
F3 2A
RL2
F4 1A
+ - + -
F5 1A
Monitored
EOL
Required
Isolate Relay
Alarm Relay
NO C NC NO C NC NO C NC NO C NC
Fault
+ - NO C NC
TB2
Un-monitored
Note: NC C NO
Denotes Voltage
Free Contacts
NC = Normally Closed
C = Common
NO = Normally Open
F8 1A
F7 1A
RL4
CN3
TB6
CN2
TB7
TB8
TB9
TB10
RL6
F6
1A
CN1
RL5
RL8
RL7
CN6
ASE
Fault
TB11
TB1
+ BAT -
DBA
Door MCP
Switch
Monitored
NO
CN1, 2, 3 Supplies
Regulated +27VDC
to Internal Boards
F1
6.3A
+ IN NC
Warning System
27VDC
* NOTE: When used
for the EV40 F7
MUST be changed
to 3 Amps
302-6730
EOL
Required
+27VDC
from PSU
Battery 1
12 Volts
- +
Battery 2
12Volts
Page 13
C14
M20
+ IN -
+ BAT -
Battery 1
12 Volts
+27VDC
FROM PSU
- +
Battery 2
12Volts
TB2
C27
+ -+ -
2 X LIMITED 1A
AUX POWER
OUTPUTS
F8
1A
F7
1A
Brigade/PSU
Monitor Board
5.13 Brigade / PSU Monitor Board DBA / MCP & Door Switch Connections
If used the DBA / MCP & Door Switch Connections are shown below.
Note: Door Switch is Open for
Normal Operation and not Monitored
4K7
DBA / MCP
Brigade/PSU
Monitor Board
TB11
DBA/MCP DOOR SW
Door Switch
EOL
10K
Ohms
TB11
5.14 Brigade PSU Monitor Board ASE Fault Brigade Box Connection
If an ASE Brigade Box is included in a system CN6 is used to convey a fault in the box to the FACP.
Brigade/PSU
Monitor Board
CN6
1
RL/1
NC
NO
Bell 2
EOL
10K
Ohms
TB3
+ - + -
Note:
Outputs are fused
@ 2Amps ( F2, F3 )
Brigade/PSU
Monitor Board
Bell 1
Note:
1. NO C NC are 1A voltage free contacts
2. + / - are monitored / fused 1A outputs
Un-used O/P's must be terminated in
10K Ohms EOL
Brigade/PSU
Monitor Board
EOL
10K
Ohms
Warning
System
EOL
10K
Ohms
Sounder
TB5
Figure 17: Use of Warning System Control for Sounder / Bell Wiring ( Diagram 2 )
Monitored
EOL
Required
Auxiliary
+ - NO C NC + - NO C NC
Note:
1. NO C NC are 1A voltage free contacts
2. + / - are monitored / fused 1A outputs
Un-used O/P's must be terminated in
10K Ohms EOL
Brigade/PSU
Monitor Board
EOL
10K
Ohms
TB5
Figure 18: EV20 / EV40 Warning System Cabling ( Alternate to Sounder / Bell Wiring )
BATT FAIL
NO C NC
M23
M27
TB10
NC
VALVE MON
ALARM
NO CC NC
NO CC NC
NC
NO
NC NO
M26
TB9
TB8
+ -
NO CC NC
NC
NO
M24
TB7
NO
Page 15
FAULT
ISOLATE
NO C
C NC
NO
NC
EOL
10K
Ohms
TB6
Brigade/PSU
Monitor Board
Up to 4 Slave CPUs
A printer
A Modem/Graphics Output
An Expansion Panel
An Internal serial bus
An External communication bus.
CN8 provides a serial data (RS232) port for interfacing to the outside world eg modems. This facility is
implemented via U15.
U21 provides the real time clock for the panel.
U19 provides non volatile memory in the form of an EEPROM.
The board also provides a data bus for the BRD85CPU processor.
RV1 LCD contrast adjust
Supply and Current = 27VDc @ 120mA
Connections
CONNECTOR
CN1
CN2
CN3
CN4
CN5
CN6
CN7
CN8
CN9
CN10
CN11
CN12
CN13
CN14
CN15
CN16
CN17
CN18
CN19
CN20
CN21
CONNECTS TO
Keyswitch Input
Expansion Panel
Serial Communication Port
Front Keypad
Printer
Misc
Brigade Output
Modem
External Buzzer Output
Slave CPU output 1
Main CPU
LCD Expansion Lead
Slave CPU connection
Slave CPU connection
Slave CPU connection
27VDC in
To LCD Backlight supply
External Loop Communication
LCD Characters
RS485 Communications Port 1
RS485 Communications Port 2
Page 16
CN17
LC
BACKLIGHT
RESET
SW 1
RS485
COMMS
CN13
CN14
CN15
SLAVE CPU4
SLAVE CPU3
SLAVE CPU2
CN20
CN11
abc
302-674E
27V IN
CN16
+-
8
7
6
4
ON BOARD
SLAVE CPU
CABLES TO
LOOP
TERMINATION
BOARD
CN6
CN21
BZ1
EXPANSION LEDS
CN3
TO BRIGADE
PSU MONITOR
BOARD OR
SOUNDER BOARD
INTERNAL PRINTER
FRONT PANEL
CN2
SW3
RS485 COMMS
EXPANSION BOARD
FOR 4 SLAVE CPU's
NODE
ADDRESS
CN9
MODEM
DEBUG
I/O PORT
CN8
C
N
1
8
NETWORKING
LCD CONTRAST
ADJUST
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
RV1
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
ON
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
CN4
C
N
1
0
C
N
7
CN5
CN1
NOT USED
Figure 20: Main Board Layout with no Main CPU or Slave CPUs
D1
D16
D15
U1
D2
U3
D8
D3
D9
D4
D10
D11
D6
U2
D7
U4
D5
D22
D23
U5
D12
D24
U6
D13
D14
Connections
CONNECTOR
CN2
CONNECTS TO
The Main Board BRDMBA CN11
Board Overlay
XL1
a b
U8
CN2
U9
U1
BRD85CPU306/01/2004
U6
U2
U3
Page 18
Connects to
302-670, 302-671 and 302-672
Main Connection Board (BRD85MBA)
1
CN2
1
Main Board
TLC542
U8
U5
U7
U6
302-696
U3
U2
X1
U9
CN1
U1
Page 19
U4
Plug in DB9
Connector
6
7
8
9
1
2
3
4
5
Rx Data
Tx Data
Signal
Ground
CN8
5
9
Rx Data
3 Tx
Data
2 Rx
Data
Tx Data
DB9F CONNECTOR
( Female Rear View )
DB9F CONNECTOR
( Female Rear View )
To Modem or PC
To facilitate safe maintenance of these services an option is available that allows for the isolation and
visual indication of the disablement of ancillary services that does not affect the normal operation of the fire
alarm system.
To ensure power to the fire alarm system is not prejudiced in any way, power for the ancillary services
must be included in the calculation of the power supply and battery capacity.
Page 20
TB4
+
_
Zone 1
+
_
+
_
+
_
+
_
Zone 2
Zone 3
TB3
Zone 4
Zone 5
+
_
+
_
+
_
Zone 6
Zone 7
Zone 8
To Slave
CPU
302-6692
3K3
EOL
3K3
EOL
4K7
MCP
3K3
EOL
3K3
EOL
3K3
EOL
L1
OUT
L1
IN
-R
L2
L2
3K3
EOL
3K3
EOL
OUT
L1
L1
IN
-R
L2
TB2
L2
+
_
Zone 9
+
_
+
_
+
_
+_
Zone 10
Zone 11
Zone 12
TB1
Zone 13
Zone 14
C1
CN1
+
+
_
+
_
+
_
To 27VDC Regulated
Output of the Brigade /
PSU Monitor Board
Zone 15
Zone 16
POWER
3K3
EOL
3K3
EOL
3K3
EOL
OUT
L1
L1
E
O
L
L2
IN
-R
L2
3K3
EOL
3K3
EOL
3K3
EOL
3K3
EOL
3K3
EOL
3K3
EOL
The Above
Shows a
Series 60
Monitored
Detector
Circuit
302-671B
27/2/01
Page 21
LOOP 2 ADDRESSABLE
DEVICES
IN
OUT
L1
L1
R+
TB1
TB2
B
IN
-R
L2
L2
OUT
LOOP NORMAL
LED A monitoring
each Loop is ON
L1
L1
LOOP IN FAULT
LED A & B ON
indicates a fault
on the Loop
( S/C, O/C ) and
the Loop is being
monitored in
both directions
R+
L2
-R
L2
L1
L1
R+
L2
-R
L2
C
N
3
T0 SLAVE CPU
302-6692 CN1
C
N
1
T0 SLAVE CPU
302-6692 CN1
Wiring Shown
Above is for a
XP95 Circuit
with one Detector
Having LED
Monitoring
REGULATED
27VDC In / Out
CN4
CN2
+
+
RV1
26V ADJ
POWER
Page 22
6
L
16 per Controller
15 per Controller
* 16
( SP1X: 159-0106 )
* Configuration dependant
( SP8X: 159-0089, SP16X: 159-0120 )
* 16
( SP1X: 159-0107)
* Configuration dependant
( SP8X: 159-0108, SP16X: 159-0121 )
General Indicator Card ( Amber LEDs ) ........................ SP1X: 159-0123, SP8X &16: 159-0124
Printer............................................................................. (TPUP-AT)
1 per Controller
( SP1X: 159-0084, SP8X: 159-0110 )
8 per Controller
8 per Controller
8 per Controller
(N/A)
1 per Controller
3 per Node
( Rack: 159-0067 )
1 per Controller
1 per Controller
Note # 2
( 159-0044 )
Note # 1 : This comprises 4 on the Main Controller and 4 on the Expansion Board.
Note # 2 : Depends on the configuration and the number of Panels in the System.
Page 23
6.1
The Input / Output Board is connected to the slave CPU via CN1 and acts as the interface between the
Slave CPU, 8 Way Relay Board and the 16 Way Opto Input Board.
Dependant on the panel configuration a maximum of 8 Input / Output boards can be daisy chained
together.
TO 16 WAY OPTO
INPUT BOARD
U2
U1
U7
CTRL
OUT
U8
U6
TO CN1 OF THE
SLAVE CPU
(302-6690)
U9
CN2
CONTROL OUT
TO CONTROL IN OF
NEXT
INPUT / OUTPUT BOARD
OR
FAN CONTROL BOARD
MAXIMUM OF 8
BOARDS PER
SLAVE CPU
+5V
U3
CN1
CN6
U5
0V
CN7
U4
POWER
+27V
IN
OUT
+
-
+V
+
-
CN2
302-6720 1/98
6.2
Relay Outputs: Each 8 Way Relay Board 302-676 is fitted with either eight 1A, RL1 to 8, (302-6760) or
5A, RL9 to 16, (302-6761) relays with voltage free contacts which can be used for control ( eg. releasing
doors ) or monitoring ( eg. driving indicators, door open / closed ) purposes.
O/P 1
O/P 2
O/P 3
O/P 4
O/P 5
O/P 6
O/P 7
O/P 8
N/0 C N/C N/0 C N/C N/0 C N/C N/0 C N/C N/0 C N/C N/0 C N/C N/0 C N/C N/0 C N/C
TB1
TB2
N/O
RL9
C
TO CN4
OR CN5
OR THE
1/0 BOARD
302-6720
N/O
N/C
RL1
RL10
N/C
RL2
RL11
N/O
C
N/C
RL3
N/O
RL12
N/O
RL13
C
N/C
RL4
C
N/C
RL5
N/O
RL14
C
N/C
RL6
N/O
RL15
C
N/C
RL7
RL16
N/C
RL8
N/O
RL9
C
N/C
RL1
5 Amp Version
Legend
1 Amp Version
Page 24
N/O
302-676x
CN1
6.3
Opto-Inputs: Up to 16 inputs can be connected to the 16 Way Input Board. These inputs are required to
be voltage free contacts as shown below.
AS AN EXAMPLE
INPUTS 1 AND 16 CONNECTED TO
VOLTAGE-FREE CONTACTS
COMCOM 1 2 3 4 5 6 7
TB2
U1
TB3
U3
U2
U5
U4
TB5
TB4
U6
U7
U9
U11
U8
U10
U12
TB6
U13
302-6770
TB1
8 9 10 1112 13 14 15 16
U15
U14
U16
CN1
TO CN3 OF
302-6720
6.4
Relay Outputs: Each Serial Relay Board 302-7320 communicates with the Main Controller via the Serial
Bus and is fitted with eight 1A relays with voltage free contacts. A maximum of 16 boards can be daisy
chained together per Controller.
Cabled to
CN3 of
302-674 or
CN2 of
Previous
Serial Board
O/P 1
N/0
O/P 2
C N/C N/0
O/P 3
C N/C N/0
O/P 4
C N/C N/0
O/P 5
C N/C N/0
O/P 6
C N/C N/0
C N/C N/0
O/P 7
O/P 8
C N/C N/0
TB2
TB1
IN
C N/C
CN1
10 Way Ribbon
RL1
OUT
Cabled to CN1
(IN) of next
Serial Board
RL2
RL3
RL4
RL5
RL6
RL7
RL8
CN2
CN3
CN4
U7
U6
U1
U5
302-7320
To 27VDC Regulated Output of Brigade / PSU Monitor Board
Page 25
6.5
The Fire Fan Module has four ( 4 ) separate fan controls each having an On, Auto and Off function switch
and a set of three (3) monitoring LEDs. The LEDs indicate the status of the equipment eg. Run, Fault or
Stop. The two ( 2 ) arrow head keys are used to step up and / or down through the three ( 3 ) conditions. A
slip in label can also be inserted into the hinged cover for identification purposes.
A loop driven version is also available (159-0105 )
Note#: As per AS 1668.1 1991, Clause 14.17.4 lettering on any of the slip in labels must be at least
5mm in height.
Quiescent Current: 13.5mA
Module & PCB Securing Tabs
( Top & Bottom )
WINDOWS
PCB
P la
s t ic
FOR SLIP
IN LABELS
Clip
In
C
N
1
La
be
l
WINDOWS
ON
C
N
2
1 2 3 4
C le
ar
Address
Switch
Set to 1
Out
In
K2 Termination Link
Slip In
Label
Clip On
Plastic Surround
( Push down here and pull
out to remove and insert labels )
Lettering on slip in
labels must be at
least 5mm in height.
6.6
The Fan Termination Board interfaces between the Fire Fan Module and the plant/equipment it controls via
the 24 volt 250mA Start, Stop, current limited, relay outputs and monitor inputs. Programmable monitoring
of the field equipment is achieved using 0 volts as an input level to indicate run, fault and stop conditions of
that equipment. Monitoring is programmed in the Function Menu for a 3, 4 or 5 Wire Start / Stop, Run,
Fault, Stop & Common functions. The inputs are protected by way of resetable transorbs and resistive /
capacitive networks.
Connectors
CN5
Is used for factory programming only and may not be available on all boards.
Terminal Blocks
TB2 5 Are used to connect the fan control and monitoring wiring to the board.
FAN 1
FAN 1
START STOP RUN FLT STOP COM
FAN 2
FAN 2
START STOP RUN FLT STOP COM
TB2
TB3
FAN 3
FAN 3
START STOP RUN FLT STOP COM
TB4
FAN 4
FAN 4
START STOP RUN FLT STOP COM
TB5
RUN
STOP
FAN MONITORING
RUN
STOP
CN1
CN3
CN4
COM
ON
1 2 3 4
0 V +27V
CN2
FLT
START
FAN CONTROL
SOLID STATE OR
RELAY INTERFACE
SW1
Address SW
+24V O/Ps
INPUTS 1, 2 & 3
0V
TB 2, 3, 4 or 5
1
Figure 34: Fan Termination Board Layout and Typical I/O Wiring
Page 26
6.7
The General Indicator Card (BRD85GIBB) comes in two versions each consisting of a front clip on
surround, decal, mounting frame, PCB and is clipped into the front panel of the FACP to provide visual
LED indication of; Zones in alarm x 32 [red], or Zones in alarm x 16 [red] / Zones in fault x 16 [yellow].
Each Indicator can identified by way of slip in labels.
Decal
Windows for
Slip in Label
Slip In Label
Windows for
Slip in Label
Slip In Label
Windows for
Slip in Label
Windows for
Slip in Label
Slip In Label
Slip In Label
Top OverLay
CN3
D1
D9
D17
D25
D2
D10
D18
D26
D3
D11
D19
D27
D4
D12
D20
D28
D5
D13
D21
D29
D14
D6
D15
D7
Bottom Overlay
D8
D16
D22
D30
D23
D31
D24
D32
Note #1: DO NOT USE excessive force to remove any component once it is clipped into position.
Note #2: If the indicator becomes illuminated it remains so until Reset is pressed.
Note #3: The indicators are tested by the Lamp Test control.
DEC2580-T1
BRD85GIBB2
050603
LED's
Windows for
Slip in Labels
RED
D1
D9
D17
D25
YELLOW
D2
D10
D18
D26
RED
D3
D11
D19
D27
YELLOW
D4
D12
D20
D28
RED
D5
D13
D21
D29
YELLOW
D6
D14
D22
D30
D7
D15
D23
D31
D16
D24
D32
RED
YELLOW
D8
Figure 38: 16 Zone Alarm / Fault Card Decal & PCB Layout
Page 27
6.8
The 8 way Sounder Monitor Board allow a larger number of bells and sounders to be connected to the
FireFinder System.
The 302-742 is built in two versions:
1. 302-7420: All outputs are monitored and provide 1 Amp per circuit.
2. 302-7421: The first 4 circuits are Voltage free contacts, the second 4 are as per the 302-7420.
Wiring to the Monitored sounder outputs is as per the 302-6730.
The Sounder/ Bell monitor board connects to the serial peripheral interface (SPI) bus. This is the same bus
that connects to the Brigade Output Board and a maximum of 8 boards can be daisy chained together.
Note: Output current is dependent on the capacity of the Power Supply
R10
D2
D33
R34
D3
R38
D34
D4
R35
R39
R13
C27
R22
R31
TB4
D35
F4
D5
R40
R36
RL4
F6
C20
R6
R26
R17
RL6
1A
TB6
D30
D7
F7
RL7
R27
R18
1A
D29
D6
C21
R7
TB5
1A
TB7
D31
R9
D8
C23
R28
R19
RL8
F8
10K EOL
F5
RL5
C22
R8
1A
Note:
If the O/P was configured
as a monitored O/P, as
below, NO is the +ve leg
while NC is the -ve leg.
D28
R25
R16
R23
1A
10K EOL
F3
RL3
R32
1A
TB3
R12
C26
R30
R21
F2
R37
R33
R11
RL2
U9
1A
TB2
C25
R29
R20
F1
C24
D32
RL1
10K EOL
10K EOL
10K EOL
1A
D9
X1
302-742
U7
U2
U1
AT90S8535-8JC
LK2
U3
LK1
NORMAL
U4
TB1
IN
OUT
CN1
CN2
D10
C5
+27V
To CN7 of the
Main Controller
D1
C4
To IN (CN1) of next
Sounder Monitor Board
or Output Brigade Board
CN5
0V
Page 28
6.9
Printer
Specifications
9 Printing method: directed impact dot matrix
9 Printing mechanism: 4/6 pin shuttle
9
9
TP
PUSH
Indicator
INDICATOR
Press and turn
to tighten ribbon
SEL Button
SEL
LF Button
LF
Ribbon
Cassette
Paper
Paper Cutter
Instructions
Figure 40: Printer Front Panel Layout ( Front Cover Closed / Open )
1.
Indicator
When the 3 colour LED indicator is illuminated;
SEL Button
a) On Line / Off Line State
The printer enters the On Line state automatically when power is applied or on exiting from the
Self-Test mode. ( LED is green ).
Press the SEL button, the LED is turned off and the printer goes Off Line.
Press the SEL button again, the LED turns on and the printer is On Line again.
Note : The printer will not receipt data when the printer is off line.
b) Pausing the Printer While It Is Printing.
Press the SEL button while the printer is printing, the printer will pause and enter the Off Line
mode after it finishes printing the row it was currently printing. The printer will continue to print
when the SEL button is pressed again.
c) Enter the HEX-DUMP mode
Remove power from the printer, press the SEL button, then reconnect the printer to the power
supply. The printer will enter the HEX-DUMP mode. In this mode any programs sent from the host
CPU will be printed out in Hexadecimal.
LF Button
While the printer is Off Line press the LF button, paper feed will be initiated press again to cancel.
4.
Self-Test Mode
With power applied (green LED illuminated ) push the SEL button. This will turn off the LED, press
and hold in the LF button then press the SEL button again and the printer will enter the Self Test
mode. Self-test will print out all the valid characters in the character sets.
Page 29
6.9.2 Maintenance
Installing The Ribbon Cassette
The printer has a factory loaded ink ribbon cassette.
Ribbon Replacement;
Mechanism
Release
Button
Hinges
PUSH
1.
2.
LED
3.
Push
Buttons
4.
Paper
Paper Cutter
The left end of the cassette can only be pressed in after the
right end has been correctly seated onto the drive axle. If
alignment is difficult it may be necessary to turn the knob on
the cassette slightly. Now check that the ribbon is tight
across the face of the cassette, that is on the inside of the
cassette and across the paper. Turn the knob clockwise
again if the ribbon is on the outside of the cassette.
Front Door
Locking Tab
Push back the mechanism head and lock it, close the cover of the printer and reconnect the power.
Loading the Paper Roll
1.
Disconnect the power, unlock and open the front cover.
2.
Push down on the mechanism release button in the top right corner to release the head.
3.
Lift the mechanism as shown below.
Mechanism
Release
Button
Hinges
PUSH
LED
Push
Buttons
Paper
Note:
Front Door
Removed
Ink Ribbon
Cassette
Note:
Front Door
Removed
Figure 42: Head Mechanism Rotation and Paper Roll Removal / Insertion
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
Note #1: Press only on the PUSH label to return the head mechanism back into position.
Note #2 :The above instructions are graphically displayed on the inside of the front cover..
C9
R2
R3
U3
U2
C6
C7
U8
U7
C19
R9
C21
D2
T4
C5
C18
C8
T1
U5
C16
T3
Connector to
Front Panel
LED & Switches
C17
R8
C4
T2
C20
U4
X1
C2
C15
U6
C3
U1
UP-ATHZP
VER:CC 2002.1
C14
R7
C1
U9
C12
R6
R1
R5
R4
D1
J1
C13
R10
J6
R11
J7
C22
Jumper State
NOT Inserted
Inserted
NOT Inserted
Function
Selects ESC Commands
Selects UP Commands
Selects ASCII Character Printing Mode
Inserted
NOT Inserted
Inserted
Insert the Shorting Clip Between
Pins 1 and 2
Insert the Shorting Clip Between
Pin 2 and 3
CN1
0.5A
F1
5V OUT
27VDC IN
CN2
IN: 18 -36VDC
OUT: 5VDC
OUT OUT +
- IN +
API-713
HY1
TO PRINTER
Page 31
Expanding the system can be achieved in various ways and requires the use of boards specifically
designed for communications purposes and boards that actually expand the system.
7.1
The Controller Interface Card ( CIC ) provides 1 X RS232 O/P for High Level Interfaces, Graphics etc., 1 X
half duplex RS485 O/P for external LED Mimics, High level Interfaces EWIS- , Graphics etc and option to
allow for multiple CIC interconnection.
27VDC IN
K1, K2:
Link Pins 1 & 2
on LAST CIC only
CN6
+ -
CN5
+ -
F1
2A
To Previous CIC
CN3 ( OUT )
IN
CN1
+ -
CN 5
+ -
F1
2A
+27V
0V
RS232 COMMS
OUTPUT
HLI / GRAPHICS
RTS
OR BMS
TXD
TB2
TB3
RXD
+27V
0V
C OM
CTS
TXD
TB2
To Loop Comms
( CN18 ) of the
Main Controller
R XD
RTS
K1
K2
CN2
TRX+
CTS
TRX+
TRX-
TRX-
1 2 3
O UT
AUX FUSED
( F1 )
27VDC OUT
COM
27VDC IN
CN 6
TB3
-----
SCRN
TB1
CN3
SCRN
TB1
CN16 302-422
IN EWIS SYSTEM
7.2
The Network Interface Card provides two communication buses, RS232 and RS422,
networking of multiple panels in different combinations, eg. from Data Gathering panels to
panels. Intercommunication can be via CN18 on the Main Controller (Loop Comms) or
Controller Interface Card connector CN3 (Out). Fitted to the rear of the NIC is the CPU
(BRD85CPU) with NIC software to control the flow of communications in and out of the NIC.
TO CN3 (OUT) OF
THE CONTROLLER
INTERFACE CARD
IF CIC IS INSTALLED
+27v
U1
+27v
CN1
1
0V
0V
RL1
TB1
U2
TO CN18 (LOOP
COMMS) OF THE
MAIN CONTROLLER
(STAND ALONE USE)
TB1
B
U3
RL2
U4
A
+27v
U5
RL3
U7
ON
CN3
U11
U9
U8
U10
TB2
5
6
7
8
U14
C OM
SW2
ISOLATE
TB3
ON
OFF
EC3A21H
HY1
c b a
D
B
S W3
TXD
+27v
RXD
U15
RTS
0V
CTS
F1
RESET
ON
+
CN4 -
+
-
TB2
2A
CN5
RS422
COMMS
IN
3
4
5
6
7
8
Note:
The ISOLATE Switch turns
OFF the board and
effectively S/C's the O/P's
TXD
TB3
RXD
RTS
CTS
+ -
+ -
2A
Page 32
RS422 COMMS
OUT
LCD Repeater
Other Panels
COM
ON
CN5
CN4
To Remote
Mimic
SW2 ISOLATE
OFF
F1 FUSED
27V OUT
To Remote
Mimic
U13
U12
RL4
SW1
ADDRESS
SETTING
D
C
0V
U6
F1 FUSED
27V OUT
D
C
CN 2
to allow the
Peer to Peer
by way of a
IO Controller
F1
RS232 COMMS
OUTPUT
Graphics or BMS
7.3
The Expansion Connection Board is used t increase the capacity of the controller from 4 Slave CPUs to 8.
Connection from the Controller to the Expansion Board, which must be mounted within 200mm of the
Controller, is made via a 20 way flat cable
Connections
Connector
CN1
CN2
CN3
CN4
CN5
Connects to
To Main Connection Board
Slave CPU 2
Slave CPU 3
Slave CPU 4
On board Slave CPU to 302-670. 302-671 and 302-672
Board Overlay
Slave CPU number 5 is an integral part of the Expansion Board, only Slave CPUs 6, 7 and 8 are plug ins.
To CN2 of the
Main Controller
CN2
U2
U4
R1
C5
C6
D2
RN2
TP1
D1
TP2
C7
U5
U6
C8
U8
U7
CN5
U9
C15
Slave CPU 5
C9
C11
C12
C13
C14
C17
C19
C21
C23
C25
RN3
RN4
RN5
C16
U10
C18
C20
C22
C24
L1
R3
D3
C29
C26
C27
C10
R2
Slave CPU
X1
C3
C4
C1
U3
RN1
CN4
Slave CPU
Slave CPU
CN1
U1
C2
CN3
U11
U12
C28
7.4
Expansion Controller
An Expansion Controller ( Fast Fit Kit Number 159-0077 ) can be described as a Main Controller without a
without a Front Panel. A maximum of 3 can be introduced into any one Node, that is into any one FACP
and require Controller Interface Cards ( CIC ) and Network Interface Cards in order to communicate with
the Main Board / Controller.
Connecting Controllers together ( Networking within the same cabinet ) expands the system beyond 8
Slave CPUs, that is the Main Board plus an Expansion Board.
Networking in this way enables the connection of up to 4 Expansion Controllers within the same FACP
cabinet. This requires the use of CICs and NICs but offers the added advantage that the RS422
communication bus is internal and all Controllers are physically and logically located at the same Node. It
is now possible to Network up to 32 Slave CPUs in one cabinet with each Slave CPU connected to an
Addressable Loop, 16 Conventional Zone Board or Digital I/O Board. With this configuration only one
Controller has a Front Panel Board.
Once the system has been expanded to this degree it is obviously quite large and some form of indication
at a point remote from the FACP may become necessary. This is achieved with the use of a Controller
Interface Card (CIC ) and a Remote LED Mimic or a CIC, a Network Interface Card ( NIC ) and a Remote
LCD Repeater.
Page 33
7.5
Networking
When FACPs are connected to each other they form a NETWORK . Individual FACPs in the Network
are referred to as NODES. The Network as defined by the limitations of the installation can consist of a
number of Nodes, the number of Nodes being dependant on the configuration of each Node. Typically an
entire Network could consist of 60 Slave CPUs connected to loops, zones and or input / output devices
spread over several nodes. The Network is Peer to Peer with the entire system configuration being stored
at each Node. The system is then programmed so that information can be made invisible to particular
Nodes or visible to all Nodes. Likewise system commands can be global or restricted to specific parts of
the network.
The entire system can be programmed from Node 1 in the Network and is connected as a data loop which
provides redundancy should there be a single cabling fault.
IMPORTANT
While it is important that proper documentation is kept and maintained for any installation it becomes even
more important as a system develops into the larger types described above.
FIREFINDER FACP
NODE 1 CONTROLLER 1
CN2
CN11
LOOP COMMS
SW3
NODE ADDRESS
LED DISPLAY
POWER ON
OFF
D4
CN5
D3
D2
ALM
PRE
ADDRESS
DBA
NOM
RST
SYSTEM
LT
LEDS FLASH
BM
BI
SW7
N/F
CPU RESET
CN1
CN1
CN1
NOTE:
ONLY RS485 OR RS422
NOT BOTH
EVC
REMOTE LED
REPEATER
302 - 715
BZ
2
3
4
5
6
TB4
SW5
LAMP
TEST
LAMP
RESET
SW4
CN2
16 WAY RIBBON
LED
1
SW3
CN7
CN10
BUZZER
MUTE
TB5
9
10
SW6
11
0V
P SU MONITOR
BRIGA DE I/F
LK2
CN16
NORMAL FAULT
ON
SW2
FLT
CONTROLLER
302-669
BRD85MBA
BRD85CPU
CN2
CN2
a b c
CN1
a b
FACTORY
USE ONLY
N/O
CN18
CN17
CN15
N/C
BACKLIGHT
CN13
12
GPI
13
27V IN
CN9
14
15
CN6
TB3
PR INTER
IN
CN2
+27V
0V
TB2
F1
2A
COM
TXD
CN1
RXD
CTS
20
FIT K1 ON
LAST MIMIC
ONLY
TB1
TRXSCRN
TB1
CN3
19
OUT
21
22
23
24
CN4
TRX+
1 2 3
K1
K2
16
18
RTS
RS485 MULTIDROP
(SINGLE PAIR SHIELDED)
CABLE TYPE BELDEN 9841
17
BZ1
CN5
FRONT PANEL
TB3
BZ1
EXPANSION LEDS
CN1
CN5
EX PANSION PANEL
CN4
CN6
CN3
OUT
CN7
CN2
MODEM
IN
RESET
SW1
CN8
26
27
29
30
31
32
EXPANSION CONTROLLER
NODE 1 C2
25
28
K2
CN6
LED AUX 5V
POW ER OUT
FIT K2
FOR BUZZER
BACK LIGHT
LED DISPLAY
OFF
CN18
CN17
10 WAY RIBBON
CN13
CN15
D4
CN5
D3
D2
ALM
PRE
ADDRESS
CN2
DBA
FLT
CN2
CN2
NORMAL FAULT
SW2
a b c
a b
POW ER ON
ON
NOM
RST
SYSTEM
CN11
LT
LOOP COMMS
LEDS FLASH
SW3
EVC
CN1
BZ
LED
1
2
3
4
SW3
CN7
5
6
TB4
N/O
SW5
LAMP
TEST
LAMP
RESET
SW4
CN2
N/C
CN1
BUZZER
MUTE
TB5
9
10
SW6
11
0V
CN1
16 WAY
RIBBON
CN10
PSU MONITOR
BRIGADE I/F
CN16
FACTORY
USE ONLY
NOTE:
ONLY RS485 OR RS422
NOT BOTH
1
CN1
REMOTE LED
REPEATER
302 - 715
CPU RESET
NODE ADDRESS
LK2
BM
BI
SW7
N/F
12
GPI
13
27V IN
CN9
14
15
CN6
TB3
PRINTER
CN2
IN
TB3
+27V
0V
TB2
F1
2A
COM
TXD
CN1
RXD
CTS
TRX+
1 2 3
20
FIT K1 ON
LAST MIMIC
ONLY
TB1
TRXSCRN
TB1
CN3
19
OUT
21
22
23
24
CN4
K1
K2
16
18
RTS
RS485 MULTIDROP
(SINGLE PAIR SHIELDED)
CABLE TYPE BELDEN 9841
17
BZ1
CN6
CN5
FRONT PANEL
BZ 1
EXPANSION LEDS
CN1
CN5
CN4
OUT
CN7
CN3
CN2
M ODEM
IN
RESET
SW 1
C N8
26
27
29
30
31
32
EXPANSION CONTROLLER
NODE 1 C3
25
28
K2
CN6
LED AUX 5V
POW ER OUT
FIT K2
FOR BUZZER
BACK LIGHT
LED DISPLAY
OFF
CN18
CN17
POWER ON
NORMAL FAULT
ON
D4
CN5
D3
D2
SW2
CN13
CN15
ALM
PRE
ADDRESS
c
CN2
DBA
FLT
CN2
CN2
a b c
NOM
10 WAY RIBBON
CN11
LOOP COMMS
RST
SYSTEM
LT
LEDS FLASH
SW3
SW7
N/F
CPU RESET
NOTE:
ONLY RS485 OR RS422
NOT BOTH
EVC
BZ
LED
1
3
4
5
6
7
SW5
LAMP
TEST
LAMP
RESET
SW4
CN2
BUZZER
MUTE
TB5
9
10
SW6
11
0V
LK2
CN16
BI
TB4
N/O
CN1
CN1
CN1
16 WAY
RIBBON
CN10
BM
SW3
CN7
N/C
PSU MONITOR
BRIGADE I/F
FACTORY
USE ONLY
NODE ADDRESS
REMOTE LED
REPEATER
302 - 715
CN1
4
a b
12
GPI
13
2 7V IN
CN9
14
15
TB3
CN6
CN6
CN4
CN1
FRONT PANEL
CN5
PRINTER
CN2
IN
TB3
+27V
2A
0V
TB2
F1
COM
TXD
CN1
RXD
CTS
TRX+
1 2 3
RS485 MULTIDROP
(SINGLE PAIR SHIELDED)
CABLE TYPE BELDEN 9841
SCRN
TB1
CN3
20
FIT K1 ON
LAST MIMIC
ONLY
TB1
TRX-
OUT
10 WAY RIBBON
19
21
22
23
24
CN4
K1
K2
18
RTS
16
17
BZ1
BZ 1
EXPANSION LEDS
CN5
25
26
27
28
29
30
31
32
K2
CN6
LED AUX 5V
POW ER OUT
TB1
FIT K2
FOR BUZZER
CN1
C OMMS IN
C
D
S
B
A
TB1
+
-
RESET
RTS
CN7
CTS
RXD
T XD
TOP LAYER
API 720
BACKLIGHT-
BACKLIGHT+
Jan 1999
BZ1
COM
RV1
OPTIONAL RS232
(AVAILABLE FOR
HIGH LEVEL INTERFACE OR
GRAPHICS OR
REMOTE SERIAL PRINTER)
SW3
P RINTER
SW2
TB3
COMMS OUT
REMOTE LCD
REPEATER
302 - 720
COMMS OUT
C
D
S
CN5
CN4
CN5
LCD
COMMS OUT
D
C
B
SW2
a
b
S W3
RESET
F1
RS232
NOT AVAILABLE
ON
OFF
S W1
RTS
CTS
COMMS IN
T XD
RXD
2A
TB2
TB2
COMMS OUT
COM
ISOLATE
DEB UG
CN2
CN2
POW ER
COMMS IN
D
C
B
SW1
OFF
27VDC POWER
ON
CN1
CN3
COMMS IN
CONTRAST
EXPANSION PANEL
OUT
CN7
CN3
CN2
M ODEM
IN
RESET
SW1
C N8
CN17
CN15
C18
CN2
CN2
a b c
a b
NOTES:
MAXIMUM DISTANCES BETWEEN PANELS = 1.2KM
IF GREATER DISTANCE ARE REQUIRED A RS422 REPEATER
(BLACK BOX 352A or 352A-F) TO BE FITTED EVERY 1.2KM
AFTER THE FIRST 1.2KM
CABLE TO BE USED = BELDEN 8132 OR 9842 TWO PAIR SHIELDED.
FIREFINDER
PANEL No1
BACKLIGHT
CN13
RV1
CN2
CN11
LOOP COMMS
SW3
RN17
NODE ADDRESS
CONTROLLER
1
CN1
CN1
CN1
CN10
PSU M ONITOR
BRIGAD E I/F
CN1
CN5
FRONT PANEL
CN1
SW1
CN4
PRINTER
CN2
BZ1
EXPANSION LEDS
OFF
CN7
CN3
CN2
ON
CN6
MODEM
POWER
27 V IN
CN9
RESET
SW1
CN8
DEBUG
LK2
CN16
COMMS IN
T B1
-
1
S
COMMS IN
D
C
B
COMMS IN
C
D
S
CN1
CN3
COMMS IN
A
+
-
CTS
OPTIONAL RS232
(AVAILABLE FOR
HIGH LEVEL INTERFACE OR
GRAPHICS OR
REMOTE SERIAL PRINTER)
CN18
CN17
c
CN2
CN2
CN2
a b
a b
RESET
FIREFINDER
PANEL No2
BACKLIGHT
CN13
RV1
COMMS OUT
RS422 COMMS LOOP
TWO PAIR SHIELDED
BELDEN 8132 OR 9842
SW3
CN5
F1
TB3
CN4
2A
PRINTER
a
b
c
SW3
RESET
27VDC POWER
SW2
A
RXD
RTS
COMMS OUT
C
D
S
COMMS OUT
D
C
B
T XD
S
COM
TB2
+
TB2
COMMS OUT
TB1
CN2
CN5
LCD
16 WAY RIBBON
CN11
LOOP COMMS
RTS
CN7
CTS
SW3
RN17
RXD
NODE ADDRESS
PSU M ONITOR
BRIGAD E I/F
2 7V IN
CN16
COM
TOP LAYER
CN10
TXD
BZ1
CONTROLLER
API 720
CN1
CN1
CN1
OPTIONAL RS232
(AVAILABLE FOR
HIGH LEVEL INTERFACE OR
GRAPHICS OR
REMOTE SERIAL PRINTER)
Jan 1999
CN6
CN1
CN5
FRONT PANEL
PR INTER
BACKLIGHT-
CN4
CONTRAST
BZ1
EXPANSION LEDS
RV1
CN7
CN3
EXPANSION PANEL
BACKLIGHT+
RESET
SW1
CN8
16 WAY RIBBON
TB1
+
-
CN1
CN3
1
S
COMMS IN
D
C
B
OUT
COMMS IN
CN2
+
TB2
COMMS OUT
COMMS OUT
D
C
B
IN
A
COM
T XD
RXD
c
a
b
SW3
RESET
RTS
CTS
2A
CN5
TB3
CN4
27VDC POWER
F1
EXTERNAL FIELD
FACP (INTERNAL)
LED DISPLAY
OFF
BACKLIGHT
ALM
PRE
2
CN2
CN2
CN2
DBA
FLT
16 WAY RIBBON
a b c
CN11
CN5
D3
ADDRESS
3
1
NOM
RST
SYSTEM
LT
LEDS FLASH
SLAVE
CPU's
2,3,4
SW7
N/F
SW3
MAIN CPU
BM
BI
LOOP COMMS
EVC
BZ
REMOTE
LED MIMIC 1
NODE ADDRESS
CN1
a b
NORMAL FAULT
D4
D2
CN14
POWER ON
ON
SW2
CN18
CN13
CN17
LED
1
2
3
CN1
CN1
CN1
4
5
6
TB4
MODEM
CN7
CN3
CN1
EXPANSION LEDS
FRONT PANEL
CN5
PRINTER
CN6
CN5
+27V
CN1
0V
CONTROLLER
INTERFACE
CARD
C
0V
GPI
16
18
19
20
21
22
TB1
23
24
OPTIONAL RS232
(AVAILABLE FOR
HIGH LEVEL
INTERFACE
OR GRAPHICS OR
REMOTE SERIAL
PRINTER)
TB3
14
15
RN3
27
29
30
31
32
LED DISPLAY
OFF
NORMAL FAULT
D4
D2
CN5
D3
ALM
PRE
ADDRESS
DBA
FLT
NOM
RST
SYSTEM
LT
LEDS FLASH
BM
BI
SW7
N/F
EVC
BZ
RXD
REMOTE
LED MIMIC 2
RS485 MULTIDROP
TRX+
TRXSCRN
2
3
4
5
6
7
N/O
CN2
N/C
OUT
9
10
TB5
11
0V
NOTES:
MAXIMUM DISTANCE BETWEEN PANELS = 1.2KM
CABLE = BELDEN 9841 OR SIMILAR
SINGLE PAIR SHIELDED.
LED
1
TB4
TB1
CN3
POWER ON
ON
SW2
COM
CTS
25
26
28
TXD
RTS
17
CN4
27VDC POWER
12
13
CN3
CN4
EXPANSION PANEL
10
11
CN1
CN2
TB3
OUT
CN6
12
GPI
13
14
15
OUT
16
CN3
TB3
19
20
21
22
23
IN
24
TO MAXIMUM OF
32 LED MIMICS
CN4
POWER REQUIREMENTS
27VDC CAN BE DERIVED FROM THE FIREFINDER OR
AN EXTERNAL APPROVED 27VDC SUPPLY CAN BE
USED AND WIRED INTO TB1 + AND - TERMINALS
17
18
TB1
+27 OV GND SCR TX- TX+
CN8
27V IN
CN16
N/C
N/O
TB5
IN
PSU MONITOR
BRIGADE I/F
CN2
2 CORE SHIELDED
CABLE TYPE BELDEN
9841 OR SIMILAR
CN10
25
26
27
28
29
30
31
32
7.6
The LCDR mimics all displays as those shown at the main panel, provides controls to interrogate the
system and would normally connect / communicate with the Network Interface Card using RS422
communication protocol. The controls function in the same way as those on the FACP.
.
NORMAL
FIRE
FAULT
ISOLATE
PRE-ALARM
FireFinder
16/12/2004 12:32:42
AMPAC TECHNOLOGIES AUSTRALIA
MENU
SYSTEM IS NORMAL
PREVIOUS
NEXT
ACKNOWLEDGE
CTS
TXD
RTS
RXD
COM
PRINTER
TB3
RS232 OUTPUT
HIGH LEVEL
INTERFACE
[ HLI ]
CONTRAST
RV1
C D
S 0V +27v
TB2
RS422 COMMS
IN TO TB1
NETWORK
INTERFACE
CARD [ NIC ]
CN7
PRINTER
OUTPUT
C D
S 0 V +27v
TB1
RS422 COMMS
OUT TO TB2
NETWORK
INTERFACE
CARD [ NIC ]
CN3
LCD
BACKLIGHT +
POWER
SW1
302-7200
BACKLIGHT -
ON
CN5
LCD
OFF
LCD Mounting
CN4
LCD
PRINTER
POWER
CN1
BZ1
CN2
RESET
CN9
DEBUG
Pin2 Rx Data
Pin3 Tx Data
Pin5 Shield
SW2
OOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOO
OOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOO
OOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOO
OOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOO
OOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOO
OOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOO
Agent Release control consists of a Agent Release Module, Termination Board and an optional Local
Control Station.
8.1
Operation
Introduction
The Agent Release Module and Termination Board communicate with the FACP via the RS485 multi-drop
bus.
The Local Control Station communicates only with the Termination Board via a separate RS485 bus. Up to
4 Local Control Stations can be connected to one termination board.
Agent discharge operates in two modes automatic and manual. The manual mode is selected by
pressing the Inhibit switch on any Local Control Station. To indicate the system is in manual the Inhibit LED
will be illuminated. Pressing Inhibit again will toggle or return the mode to automatic and extinguish the
Inhibit LED.
The Agent Released Pressure Switch ( PSW ) is wired to the PSW input on the Termination Board and
is used to confirm that the agent has been released. The circuitry involved in this process can be
configured to accept a normally open contact, normally closed contact, normally open mechanically
operated (manual) or is ignored ( not fitted ) and is selected via FACP on-site programming. If the
mechanical ( manually operated ) option is selected the module monitors the pressure switch input and
provides notification the agent has been released manually, initiates an alarm and illuminates the Agent
Released indicator.
Manual Mode
When the system is in manual mode, then;
The Local Control Station Inhibit indicator is lit at the FACP and all Local Control Stations.
The buzzer at all Local Control Stations will sound until the inhibit is released.
The System Inoperative output is turned on.
The Automatic discharge sequences are prevented from starting.
If an automatic discharge sequence was underway and the inhibit switch is activated
(switched to manual mode) the discharge sequence is aborted and the sequence is reset.
This means the Stage 1 and Stage 2 outputs are switched off.
To manually discharge the agent the Lock Off Valve must be open and the Manual Release switch on
the Local Control Station pressed. The manual discharge sequence is;
Manual Activation indicator is lit on the FACP and Local Control Station.
The FACP activates its brigade alarm output.
Stage 1 outputs are switched to +24VDC. [FIRE ALARM sign illuminated, aural alarm
sounds].
Stage 2 outputs are switched to +24VDC. [ FIRE ALARM, EVACUATE & DO NOT ENTER
signs illuminated, aural alarm sounds ].
The optional pre-release start delay is activated ( Selected via FACP on-site programming ),
time out and an ON Interlock signal will then operate the selected release circuitry.
The Agent Discharge LED on the Agent Release Module and Local Control Station will
illuminate when the Pressure Switch input on the Termination Board is activated.
Activate gas-fired output.
Note: The Interlock Input can be defaulted to the on position by placing a 10K EOL termination
resistor across the terminals TB2. 7 / 8 of the Agent Release Module and Local Control Station.
Auto Mode
Automatic discharge is when one or two zones going into alarm initiate the agent discharge sequence.
Note: A manual release can still be initiated in auto mode but the LCS Inhibit control WILL
NOT inhibit / abort the agent release sequence.
Page 37
Lock-Off Valve
When the manual lock-off valve is operated;
The agent is blocked from reaching the release valve.
The lock-off valve inhibit indicator LEDs on the Agent Release Module and Local Control
Station are illuminated.
The system inoperative output operates.
Fault Monitoring
Fault conditions are initiated by:
The Pressure Switch monitoring circuit.
The Low Pressure Switch monitoring circuit.
The Lock-off Valve monitoring circuit.
Activation circuitry.
Stage 1 outputs. ( Aural & visual discharge alarms ).
Stage 2 outputs. ( Aural & visual discharge alarms ).
A Zone Fault.
A Fault on the interlock input.
A Fault with a LCS.
Note #1:
The common fault indicator on the Agent Release Module and Local Control Station is
illuminated for any Fault condition.
Note #2:
For a pressure switch fault, low pressure switch fault, lock-off valve fault, stage 1 output
fault, stage 2 output fault and interlock fault, the FACP will signal the brigade.
Page 38
When there is a fault in the activation circuit or in the trigger zones, in addition to the
above, the system inoperative output is operated.
Note #4:
Note #5:
Isolation
If a trigger zone is isolated at the FACP the trigger zone isolated indicator at the Agent Release Module
and Local Control Station is illuminated, and the system inoperative output is operated.
System Inoperative Output
The system inoperative output is switched to +24VDC under the following conditions;
Operation of the Service Switch.
A Fault in the selected trigger circuit.
Operation of the Lock-off valve.
Operation of the Inhibit at an Local Control Station.
A Fault in any of the activation zones.
If any of the activation zones are isolated.
Manual Mechanical Release of the Agent
With agent release systems, a manual mechanical means can be provided to release the agent.
If the pressure switch is activated (indicating that the agent has been released), and the agent release
module has not activated the selected activation circuit, then the following will occur:
Stage 1 output is switched to +24VDC and stage 1 relay is output closed
Stage 2 output is switched to +24VDC and stage 2 relay output is closed
Light the agent release led on the ACC and LCSs
Activate gas-fired relay output
Monitoring of the Pressure Switch
Due to the requirements of Manual Mechanical Release of the Agent, the pressure switch input conveys
two pieces of information:
When the pressure switch input is active, it signals that the agent has been released. The
release can be as a result of the agent release module or due to a manual mechanical release.
1.
When the pressure switch is not active, it signals that there is a full bottle of agent
available to be discharged.
2.
In order for the agent release module to respond to a manual mechanical release, the pressure switch
must have been previously not active, to signify that a full bottle of agent is available
8.2
The Agent Release Module controls and monitors all the requirements for agent release and carries the
slide in label for identification of the agent and application area.
Manual Release
Switch
Quiescent
Current:
8mA
MANUAL
ACTIVATION
LOCK OFF
VALVE INHIBIT
AGENT LOW
PRESSURE
INTERLOCK
AUTOMATIC
ACTIVATION
LOCAL CONTROL
PANEL INHIBIT
TRIGGER ZONE
ISOLATED
INITIAL AGENT
OFF
PCB
SELECT
SERVICE INHIBIT
Keyswitch
AGENT
Page 39
AGENT
DISCHARGED
AGENT CIRCUIT
FAULT
COMMON FAULT
RESERVE AGENT
M
A
N
U
A
L
R
E
L
E
A
S
E
The FCP goes into service mode when the keyswitch is switched to SERVICE INHIBIT. This results in the
selected agent activation circuit being electrically isolated and a Common Isolate condition being indicated
at the FACP. This condition can also confirmed through the Status Menu. To remove the key it is
necessary for the switch to be in the OFF position.
SELECT
AGENT
Pressing Select toggles the selection of either the Main or Reserve release agent. Selection is
indicated by the Main and Reserve Agent LEDs
M
A
N
U
A
L
R
E
L
E
A
S
E
If activated the Manual Release will commence the discharge sequence of the selected
agent and an alarm condition is initiated. Progress of the release can be monitored through the Status
Menu. To prevent accidental operation this switch has a hinged clear plastic cover that has to be raised to
access the switch.
Lock Off
Valve Inhibit
Agent Low
Pressure
Local Control
Panel Inhibit
Trigger Zone
Isolated
Interlock
Initial Agent
Agent
Circuit Fault
Common
Fault
Reserve
Agent
CN7
CN6
TP9
Agent
Discharged
RS485
&
+/- 27v
Out
Address
Switch
RS485
&
+/- 27v
In
K1
Termination
Link
CN8
Select
Manual Release
SW2
CN2
Key Switch
Page 40
ON
Automatic
Activation
1 2 3 4
Manual
Activation
8.3
The LCS has the same indicators, Inhibit and Manual Release buttons as the Agent Release Module but
no Service Inhibit keyswitch or Agent Select button.
Quiescent
Current:
26mA
TB1 & 2
PCB
290-0270
MANUAL
ACTIVATION
LOCK OFF
VALVE INHIBIT
AGENT LOW
PRESSURE
INTERLOCK
AUTOMATIC
ACTIVATION
LOCAL CONTROL
PANEL INHIBIT
TRIGGER ZONE
ISOLATED
INITIAL AGENT
AGENT
Manual Release
Switch
INHIBIT
AGENT
DISCHARGED
AGENT CIRCUIT
FAULT
COMMON FAULT
RESERVE AGENT
M
A
N
U
A
L
R
E
L
E
A
S
E
M
A
N
U
A
L
Lifting the switch cover and pressing the push button starts the manual agent release
sequence and initiates an alarm. This two action safety feature prevents any accidental operation of the
control and should not be disabled.
AGENT
INHIBIT
When pressed places the system into manual mode and prevents the initiation of the automatic
discharge sequence.
8.4
Panel Indicators
There are 12 indicators on both the Agent Release Module and Local Control Station. They are;
MANUAL
ACTIVATION
AUTOMATIC
ACTIVATION
Blue Illuminated when the pressure switch indicates the agent has been
discharged. For pyrogen, feedback is from the thermal switch. If there is no pressure switch fitted, the
indicator will be illuminated as soon as the agent discharge signal is activated. ( Selected via FACP on-site
programming ).
LOCK OFF
VALVE INHIBIT
Yellow Illuminated when the Lock-Off valve has been physically activated.
LOCAL CONTROL
PANEL INHIBIT
Yellow Illuminated when the Inhibit switch is activated at any of the LCSs.
Page 41
Yellow Illuminated when the low pressure switch is activated. This could indicate
the agent is leaking from its container.
TRIGGER ZONE
ISOLATED
Yellow Illuminated when any of the programmed trigger zones on the FACP are
isolated.
INTERLOCK
Yellow Illuminated when the interlock input (eg from dampers, doors etc) is off
during the discharge sequence meaning the dampers, doors etc are not closed as they should be or a
fault exists.
Note: The Interlock is a Monitored Input and can be defaulted to the ON position by terminating
the input ( TB2 7 & 8 ) into a 10K EOL resistor.
COMMON FAULT
INITIAL AGENT
RESERVE AGENT
Buzzer
The Buzzer is activated under programmed control as per the appropriate Standard.
Assignment
RS485 + In
RS485 - In
RS485 Common
RS485 + Out
RS485 - Out
RS485 Common
Interlock+
Interlock-
TB1 Terminal
1
2
3
4
Page 42
Assignment
+27V In
0V In
+27V Out
0V Out
RS 485
IN from Agent
CO M Termination Brd.
10K
EOL
INTER
LOCK
0V
0V
+27VDC IN from
CN8
Term. Brd.
Manual
+27VDC OUT
Release
to Next LCS
1 2 3 4
+
2K2
Address
Switch
Set to 1
BUZZER
BZ1
CN2
Key
Switch
(Not Used)
TB1
LCS CABLE
27V to
Next Board
C
N
2
NC
NO
Contact
Rating
1A & 24V
U1
EOL
Termination
LK1
CN3 CN4
TB3 TB4
NC
NO
NO
RL4
-L
N/0 COM
TB5
+L
TB6
NC
NC
C
RL5
-L
RL6
+L
U4
RESV
+
-
TB7
NO
NO
Contact
Rating
1A & 24V
COMM
RELEASE
MAIN
N/0 COM +
-
NO
NO
Contact
Rating
1A & 24V
COMM
C
RL2
NC
NC
Contact
Rating
1A & 24V
C
RL1
U3
302-7870
03/09/02
C
N
1
TB2
///
27V In
TB1
N/0 COM
+ LOCK-
///
RS485 Control
Out to Next
Board or Link 1
EOL is Applied
+ L.PSW+ PSW -
STAGE2
STAGE1
///
RS485 Control
In From CN2 of
Previous Board
or CN21 of the
Main Control
Board
SIG+
0VDC
SCRN SIG+24VDC
GAS SYST.
FIRED INOP.
///
8.5
NC
COMM
RL7
C
RL3
-L
+L
U2
Q2
U5
U10
X1
Address Setting
ON
CN5
1 2 3 4
U9
U7
SW1
Page 43
ON
INTER
LOCK
ON
+
_
10K
EOL
SW2
1 2 3 4
RS 485
OUT to
CO M Next LCS
ON
+
_
RS 485
COMMS
BUS
LK1
Termination
Link
1 2 3 4
SCRN
SIG
SIG
ON
+
_
27VDC
0VDC
1 2 3 4
TB1
27VDC
TB2
2.
LCSs ( up to 4 ) via TB1. LK1 is inserted in the last board in the RS485 Bus
3.
Monitored Inputs: via TB2. ( EOL Resistance 22K, Series Resistance 4K7 )
(a)
Pressure Switch ( PSW ) agent released
(b)
Low Pressure Switch ( LPSW ) agent storage cylinder pressure has dropped to a predetermined level; and
(c)
Interlock, the manual lock-off valve has been operated.
4.
Gas Fired: Output via RL2 N/O contacts rated at 1A @ 24VDC wired to TB3. Used to indicate
to other monitoring devices the agent has been released.
5.
System Inoperative: via RL1 N/O contacts rated at 1A @ 24VDC wired to TB4. Used to warn
by way of signage / audible alarm and/or monitoring that the system is inoperative.
6.
Stage 1: Output; initiates the visual and audible Fire Alarm and Evacuate warnings.
(a)
Monitored; via RL4 C/O contacts wired to TB5 1 & 2 ( EOL required 10K ) and
(b)
un-monitored; via RL5 N/O contacts wired to TB5 3 & 4.
7.
Stage 2: output; initiates the visual and audible Fire Alarm and Do No Enter warnings
(a)
Monitored; via RL6 C/O contacts wired to TB6 1 &2; ( EOL required is 10K ) and
(b)
Un-monitored; via RL3 N/O contacts wired to TB6 3 & 4
8.
Release: Main actuating circuit, monitored (10K EOL required) via TB7 1 & 2 ( 2A current
limited ),
Release: Reserve actuating circuit, monitored (10K EOL required) via TB7 3 & 4 ( 2A
current limited )
(a)
To Pyrogen Igniter ( max of 10 )
(b)
Metron Igniters ( max of 10 a series 2watt 18 resister must be added to the circuit )
(c)
Solenoid valve ( max current of 2 amps & 27VDC )
Interface Wiring
Monitored Inputs TB2 1 & 2
Pyrogen,
This input relies on a thermal fuse used in conjunction with 22K EOL and 4K7 series resistors.
The type of agent release mechanism has to be set in the Programming Menu for the input to
function as per the manufacturers specifications and be in accordance with the relevant Standard.
To Next 302-740 if Applicable
Place 10K EOL Across Last Board.
Pyrogen Release
Board 302-740
C2
-VE
TB2
Pyrogen
Canister
FUSE
D1
R2
R1
302-7400
17/10/00
4K7
Pyrogen
Release
Point
To TB7
MAIN or
RESERVE
Release
10K
EOL
TB1
+VE
8.6
1.
C1
10K EOL
Solenoid
22K
EOL
- P SW
+
Termination Board
Alternative
Wiring to TB7
TB2
+ -
TB7
MAIN
Page 44
+ RESV
10K EOL
Solenoid
+ -
4K7
To TB7
MAIN or
RESERVE
Release
+ TB7
MAIN
22K EOL
22K
EOL
4K7
Termination
Board
+ - +
RESV
MAIN / RESERVE
RELEASE
22K EOL
4K7
- +
Agent
PSW
LPSW
LOCK
TB3
*
= MOV
*
35V
RL2A
1
2
To Monitoring
Interface / Device
TB4
RL1A
+
System Inoperative
+27V Current
Limited to1A
0V
0V
To Sys
Inop Mon
Stage 1, Stage 2
Stage 1
or
Stage 2
RL4A
RL6A
RL4B
RL6B
RL5A
TB5 / 6
1
+ve
-ve
3
*
RL3A
= MOV
35V
10K
EOL
-(+)
To audible / visual
device or interface
*
0V
Page 45
+(-)
1 or 2 Way
Signage
TB5 = Stage 1
TB6 = Stage 2
8.7
Warning Signs
Description
The warning signs are driven by a 2 wire system and may be configured for single or dual stage operation.
An on-board buzzer provides an audible warning which may be disabled by removing JP3.
External evacuation devices, eg sounders may be connected to TB3 of the input termination board. An
external mute push-button (N/O contacts) may also be connected to Term 3 on the warning sign PCB to
enable the user to silence the internal buzzer and evacuation device. Inserting JP4 disables this function.
Enclosures
The IP50 is a metal enclosure. The facia surround is fitted by removing the screw on the left hand side of
the enclosure and pulling it away to the left. The facia sign is fitted in place and the tabs bent over to hold it
in place. Two holes in the backpan of the chassis allow for mounting.
The IP65 ABS enclosure has 10 screws, tightened evenly but not over tightened, hold the facia in place.
Do not over tighten. 4 holes in the backpan allow for mounting.
Specifications:
Operational Voltage
IP Ratings
Environmental
28VDC
At 24VDC 55mA Stage 1
At 24VDC 140mA Stage 2 (100mA Muted)
IP50 ( Dim: 190H x 315W x 73D mm )
IP65 ( Dim: 200H x 295W x 65D mm )
-10C to +55C Dry heat
+40C @ 0 to 93% Relative Humidity
Installation
1.
2.
3.
4.
Remove the backpan from the enclosure to ensure it is not damaged while mounting the
enclosure.
Bring the cabling into the enclosure by removing the knockouts most appropriate for the
installation.
Mount the enclosure, remount thebackpan, set the configuration and then cable as per the
following diagram.
ENSURE THE AGENT IS ISOLATED and test from the Agent Release Module.
Cabling
Term 3 (Buzzer Mute)
BUZZER MUTE
INPUT
0V 24VDC
24VDC 0V
1-2 Continuous
2-3 Flashing (DEFAULT)
LED's Permanently ON
LED's flashing at 1.5Hz
Buzzer activates
both Stage 1 & 2
1-2 EXTERNAL
(DEFAULT)
JP 3 (Enable Buzzer)
1-2 ENABLE BUZZER
(DEFAULT)
MUTE
Page 46
INPUT
TERM
6
OUTPUT
OUTPUT
TERM
1
+
TONE 1
+
TONE 2
BUZZER
MUTE
NOT USED
NOT
USED
ROW
TERM
3
OUTPUT
EXTERNAL
SOUNDER
TP10
BACKPAN RETAINING
SCREWS IN EACH CORNER
BUZZER MUTE
TERM
2
COM +
LEVEL 2
+
TONE 1
+
TONE 2
LEVEL 1
COM +
LEVEL 2
GND
INPUT
TERM
4
TERM 5
LEVEL 1
TP1
TB2
CN1/2
+
+
-
IN
TB1
C OM+
OUT
VANTAGE
SOUNDER
(MAX 1)
TP11
JP"X"
TP12
ROW
NOT USED
1 2
3
JUMPER
NUMBERING
TP13
TP7
TP8
ROW
NOT USED
TP9
JP2
JP4
JP5 JP3
ENABLE
BUZZER
DISABLE
EXT-MUTE
BUZZER
ENABLE
SOUNDER
(NOT USED)
CONTINUOUS
FLASHING
DUAL LEVEL
GND
SINGLE LEVEL
TP14
JP1
4. (-) ALERT
STG1
3. (-) ALERT
STG2
2. (-) EVAC
BRD 42WTB2-A
1. (-) EVAC
BRD 42WTB1-A
C N1
CN 2
TB2
+
+
-
10K
TB1
IN
TB3
COM+
OUT
6. (+) POS
5. (+) POS
10K
SYST.
VANTAGE SOUNDER
( ORDER CODE 205-0062 )
TERM 4
WARNING
SIGN
( MAXIMUM
OF 6 IN
TOTAL )
INPUT
+
TONE 1
+
TONE 2
INOP
TB4
MAIN
+
N/0 C O M
- N/0 C O M
RESV
+
TB6
STAGE2
TB7
RELEASE
Figure 65: 2 Wire Cabling from the Agent Termination Board to the Warning Sign/s & Evacuation Device/s
Page 47
The EV20, EV40, EV60 and EV120 are compact single zone occupant warning devices that when
triggered produce Alert and Evacuation signals to meet the requirements of AS1670.4.
EV20
At the heart of an EV20 single zone occupant warning system is a microprocessor that generates the alert
and evacuation signals, controls timing and the input / output.
If an FACP warning system input is received when the rotary switch is in the AUTO position the EV20 will
begin to output the Alert signal for a duration determined by the setting of the 4 way DIL switch SW1. The
set duration is termed the changeover timeout and ranges from 0 seconds to a maximum of 300 seconds.
If the time out is set to 0 seconds then the alert signal is bypassed and the evacuation signal commences
immediately. The operator can manually stop the sequence by turning the rotary switch to the ISOLATE
position.
IC4 performs the task of an audio amplifier with TX1 providing the impedance matching to a 100 volt
speaker line. The alert and evacuation signal output Stages are set by adjusting RV1 and RV2
respectively.
Short or open circuit speaker faults are detected by the fault monitoring circuitry and will result in the
illumination of the FAULT indicator mounted on the front panel control module.
Public Address
A microphone and pre-amplifier (Order Code 222-0007) is used to provide the public address capabilities.
EV40
At the heart of an EV40 single zone occupant warning system is a microprocessor that generates the alert
and evacuation signals, controls timing and the input / output.
If an FACP warning system input is received when the rotary switch is in the AUTO position the EV40 will
begin to output the Alert signal for a duration determined by the setting of the 4 way DIL switch. The set
duration is termed the changeover timeout and ranges from 0 seconds to a maximum of 540 seconds. If
the time out is set to 0 seconds then the alert signal is bypassed and the evacuation signal commences
immediately. The operator can manually stop the signal sequence by turning the rotary switch to the
ISOLATE position.
Amplifier 1 & 2 provides 40watts of audio output at 8 ohms which feeds TX1 to provide the impedance
matching to a 100 volt speaker line. The ALERT and EVAC Stage controls adjust the output Stage of
each set of signals.
Short or open circuit speaker faults are detected by the fault monitoring circuitry and will result in the
illumination of the FAULT indicator mounted on the front panel control module and SPEAKER SHORT
(red) or SPEAKER OPEN (yellow) LEDs on the main board.
Public Address
A microphone (Order Code 294-0001) is used to provide the public address capabilities.
Page 48
Indicators
LINE FAULT
- In the event of an open or short circuit speaker line the LINE FAULT indicator (yellow)
will be illuminated
ISOLATE
- the LED will be illuminated (yellow) when the warning system is isolated
Signal Structures
ALERT SIGNAL
420Hz
420Hz
ON
AS1670.4:
420Hz pulsed on for 0.625 seconds
at 1.25 second intervals
0.625 0.625
sec
sec
OFF
2
3
Time in seconds
EVACUATION SIGNAL
0.5
0.5
0.5
500Hz
1.5
sec sec
sec
sec
sec
secs
0.5
OFF
2
3
Time in seconds
0.5
sec
AS1670.4:
0.5 second sweep signal 500-1200
Hz for 2.5 seconds at 4 second
intervals
0.5
0.5
0.5
0.5
1.5
0.5
sec sec
sec
sec
sec
secs
sec
0.5
OFF
"EMERGENCY
EVACUATE NOW"
Time in seconds
Page 49
TB2
4
2 1+
PSU
BRIGADE
MONITOR
BOARD
EVACUATION
SYSTEM
CN1
5
4
EV20 CONTROL
RED
PINK
BLACK
GREEN
ORANGE
COMMON 3
ISOLATE 2
MANUAL EVAC 1
CN3
GND 3
OUT 2
IN 1
302-604A
EV20
OUTPUT
TB1
TB5
2
1
WARNING
SYSTEM
222-0008
TB2
2
1
47K
TB2
+27V 3
COMMON 4
1
2
3 CN3
4
5
MIC PRE-AMP
TB1
1
1 CN1 2
3
1
CN1 2
3
1
2
CN2 3
4
5
302-475
3
CN2
302-718
+27V
TX1
Signal Pin 1
4
3
AMPAC
REC
LATCHING
30
S
60 E
C
120 O
N
180 D
S
240
4
0 ( EVAC ONLY )
2 Core Audio
1
D4
CN2
0V Pin1
C14
SW1
1 2 3 4
TO VERBAL MESSAGE
BOARD
PLAY
1 2 3 4
SW1 TIME
OUT TABLE
EXAMPLE OF
SETTING - 30SECS
( FACTORY SETTING "0" )
AND I/P SET TO
NON-LATCHING
TDA
2030
TONE
C6
C2
U3
C5
DC- DC+
ON
TB1
ON
TX1
TB5
+
+
2 1
TONE
VOLUME
CN3
VOICE
VOLUME
EV
C O M TIMER
FireFinder
BRIGADE
PSU MON
BOARD
WARNING
SYSTEM
( MONITORED )
+27V
-0V
AUDIO
RV2
RV1
+ IN -
3 4
TB2
SW 1
CTRL
O/P
+27
VDC
F1 1A
CN1
VOICE
RES1093
47K
GND
5 WAY PANDUIT
EVAC/ALERT
CONTROL
FAULT
SW1
FACP CONNECTIONS
+27V Pin 2
BRD42ETG-01
11
CN2
SHEILD
Shield Pin 3
8
C 9
10
+ -
IN
CN3
PUBLIC ADDRESS
PRE-AMP
OUT
ISOLATE
A
12
LINE FAULT
API-718
FRONT
PANEL
CN3 CN2 CN1
3
2
- +
Shield
MIC I/P
D090 PHILIPS
RL1
Signal
(Red)
LED1
CN1
AUTOMATIC
ISOLATE
PUBLIC ADDRESS
MANUAL EVACUATION
Shield
TB1 *
LINE FAULT
RV1
API-475/2
O/P
TB1
TX2
O/P
Note: WARNING SYSTEM is a monitored O/P. The EOL is on board the EV20 and is effectively made to
be O/C (at TB1) during an EV20 fault condition. This produces the fault condition at the FACP.
NON-LATCHING
SW1/4 MUST BE SET
TO NON-LATCHING.
OPTIONAL VERBAL
MESSAGE BOARD
ORDER No 222-0013
VERBAL MESSAGE BOARD IS
MOUNTED ON STANDOFFS
ONTO THE MAIN BOARD IN THE
POSITION INDICATED ABOVE
300
ALERT ONLY NO CHANGE OVER
Figure 68: EV20 Wiring to Control Module, FACP Cabling and Time Out Table
Page 50
8 OHM
o o o o o
o o o o o
SPARE
JUMPERS
EVACTRON
EV40
TB4
AMP2
40W LINE
TRANSFORMER
100V IN
TB5
R ED
100V IN
22K
AMP1
FUSE
3A
PA1
SPEAKER OPEN
(YELLOW)
FAULT
PA2
CONT
LINE FAULT
PINK
FAULT
COM FLT
- o o +
AUTOMATIC
ISOLATE
PUBLIC ADDRESS
MANUAL EVACUATION
NOCF
M/MAN
OFF
1 2 3 4
EV
- 27VDC IN
TB3
CCT FLT
RELAY
AL
ON
ON
4321
TIMER
MICRO
FRONT PANEL
ALARM
MESSAGE BRD
MOUNTING SOCKETS
TB2
AL
EV
ORANGE
AUTO
WHITE
GND
BLACK
PA1
M1
ALM
P WR
IN
ALERT EVAC
CN1
TB1
MIC2
MIC1
TB1
TERMINATION
BOARD
o
o
o
o
o
GN D
PAU P EV
+
+P WR
M2
GREEN
BLACK
PA2
PINK
-WARN
RED
CN1
302-718
o
o
o
o
o
o
CN2
302-718A
14/8/00
o
o
o
o
o
o
o
o
o
o
o
STATUS CONTROL
CN3
D09 0 PHILIPS
MIC - OPTIONAL
ORDER SEPARATELY
MIC
BLACK 0V
TB2
1 2
SYSTEM POWER
VERBAL
MESSAGE
BOARD
RED +27V
GREY
WHITE
1 2
WARNING SYSTEM
+27VDC
NOTE:
Ensure F7
is 3Amps
FireFinder
BRIGADE
PSU MON
BOARD
WARNING
SYSTEM
MONITORED
TB5
ON
ALERT
480
540
420
360
300
240
270
210
150
180
120
60
90
SECONDS
30
EVAC
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Page 51
9.1
EV60 / 120
The EV60 & 120 are essentially an EV20 MPU and driver but with 60 and 120 watt output amplifiers
powered from a Current Limit Fuse Board.
9.2
EV120
EV3000
EV3000
O/P 2
O/P 3
O/P 4
O/P 5
O/P 6
O/P 7
O/P 8
N/0 C N/C N/0 C N/C N/0 C N/C N/0 C N/C N/0 C N/C N/0 C N/C N/0 C N/C N/0 C N/C
TB1
F.I.P. INPUT
BOARD
TB5
INPUT
COMMON
INPUT
INPUT
16 15 14 13
TB2
O/P 1
RL10
RL11
N/O
RL12
N/O
RL13
N/O
RL14
N/O
RL15
RL16
TB1
TB2
TB4
IC37
IC39
N/O
INPUT
5
N/O
TO CN4
OR CN5
OR THE
1/0 BOARD
302-6720
N/O
N/O
RL9
CN1
INPUT
12 11 1 0 9
TB3
N/C
RL7
N/C
N/C
RL6
RL8
N/C
RL5
N/C
RL4
N/C
RL3
ON
N/C
RL2
302-676x
N/C
RL1
IC38
SW1
CN1
IC40
RS485 IN
N/O
RL9
5 Amp Version
Legend
1 Amp Version
C
N/C
RL1
CN2
IC41
IC36
IC27
IC18
IC9
RS485 OUT
CN4 POWER OUT
FIREFINDER
CN13
FireFinder
CN17
CH16
CN20
CN15
2
1
C N2
C N2
CN 2
SLAVE CPU
(302-6692)
RN20
CH8
CH8 CH6
CH8
CN2
CN21
27V IN
CN8
EXPANSION LEDS
TB2
302-7250
API-422B
CN17
CN15
CN16
TX D
RX D
T RX+
TRX-
OUT
CN3
CN3
SC RN
TB1
BRIGADE PSU
MONITOR
BOARD
TB5 1/2 (+/-)
WARN SYS
C N7
CN5
CN4
CN4
CN5
CN6
CN7
TIME OUT
SELECTION
SWITCH
CN8
CN9
CH2
CN1
FRONT PANEL
CN14
CN10
CN6
CN3
EXPANSION PANEL
CN13
CO M
RT S
CN1
RN17
CN16
M ODE M
CN1
0V
CT S
U11
U10
+2 7V
SW2
CN11
PRINTER
RESET
CN10
10K
302-673
EV3000 MASTER
CONTROL PANEL
EV3000
CN18
Figure 73: HLI & Common Fault Cabling To & From the FACP and EV3000
Page 52
ON
CN1
CN1
U14
CN18
TB3
1 2 3 4 5 6 7 8
U13
SLAVE CPU
(302-6692)
CN2
CN1
SLAVE CPU
(302-6692)
U15
CPU BOARD
(BRD85CPU)
a b
a b
LOOP
COMMS
CN11
CN26
CN12
CONTROLLER
I/F CARD
CN14
ON
D13
8 7 6 5 4 3 2 1
CH15
10
Brigade Devices
TB8
ALARM
TB7
ISOL
TB6
FAULT
COM
1 2 3
1 2 3
BLACK
BLUE
YELLOW
1A
RED
1 2 3
RED
BRIGADE
PSU
MONITOR
BRD
N/C
N/0
CN6
5 6
+ 27 VDC
COMMON
RL
1
+ 27 VDC
TERMINAL
BLOCK
ASE
FAULT
1
10
RL/1
CONTRACTOR
CONNECTIONS
ASE
BRIGADE
BOX
ASE BRIGADE
BOX MOUNTING CLIP
TB8
TB2
+
TB3
TB6
ISOL
FAULT
ALARM
N/C
N/0
TELEPHONE
CABLE IN
COM
1 2 3
1 2 3
1 2 3
C
O
M
M
O
N
2
7
V
D
C
1 2
CONTRACTOR
CONNECTIONS
BRIGADE
BOX CABLING
10
11
12
RED
+27V
BLACK
0V
BRIGADE
BOX
NOTE:
CABLE THE BRIGADE
BOX EARTH TO THE
CHASSIS EARTH IN A
STAR CONFIGURATION
BACKPAN
Page 53
FireFinderTM Operation
11
ALARM
FIREFINDER
AMPAC
PH: 08 9242 3333
SYSTEM IS NORMAL
FAULT
15/1/2003
14:00:00
34
ISOLATED
EXTERNAL BELL
ISOLATE
WARNING SYS
ISOLATE
PREVIOUS
NEXT
ACKNOWLEDGE
RESET
ISOLATE
10
19
DE-ISOLATE
23
LOOP
ABC
20
FAULT
OUTPUT ISOLATE
24
SENSOR
JKL
21
AUXILIARY
FAULT / ISOLATE
25
ZONE
TUV
WXYZ
SYMB
22
AIF
ACTIVE
26
DISPLAY
TO
SPACE
ENTER
DEF
4
7
GHI
MNO
27
28
CANCEL ENTRY
POWER ON
12
PRE-ALARM
13
AUX ALARM
14
WARNING
SYS FAULT
15
SUPPLY FAULT
16
EARTH FAULT
17
SYSTEM FAULT
18
TEST MODE
30
31
PQRS
11
32
MENU FUNCTION
33
29
FireFinder
TM
NOTE: The Italic numbers next to each of the Indicators and Keys / Buttons in the diagram above
relate to the explanations below.
FIRFIGHTER FACILITY
1.
2.
3.
4.
5.
ALARM
(Red): This LED will flash if any unacknowledged alarms are present on the system.
If all alarms have acknowledged it will light steady.
FAULT
(Yellow): This LED will light steady if there are any faults on the system, whether
they are loop faults, module faults, device faults etc.
ISOLATED
(Yellow): This LED will light steady if any detectors, devices or zones in the system
have been isolated.
EXTERNAL BELL
ISOLATE
(Yellow): Pressing this button will isolate any bells connected to the fire panel If the
bell is isolated the LED just above the button will glow steady yellow. Pressing the button again will
de-isolate the bell.
WARNING SYS
ISOLATE
Pressing this button will isolate the FACP output to the Warning System if it is
connected to one. Pressing the button again de-isolates the Warning System output. When the
Warning System is isolated the LED just above the button will be illuminated steady.
Page 54
Pressing this key scrolls the display backwards through the alarms, faults, or isolates.
6.
NEXT
7.
8.
9.
10.
Pressing this key scrolls the display forwards through alarms, faults, or isolates .
ACKNOWLEDGE
Pressing this key will acknowledge an alarm currently displayed on the LCD. It will
also silence the panel buzzer, which sounds whenever there is an alarm (optional) or fault.
RESET
Pressing this key will reset the panel, clearing any acknowledged alarms and taking
the LCD display back to its default screen, unless there are any uncleared faults or isolated
devices, these will continue to be displayed.
ISOLATE
Indicators
POWER ON
11.
12.
13.
14.
15.
PRE-ALARM
AUX ALARM
17.
18.
19.
20.
(Red): This LED will light when a sensor/detector is in the pre-alarm state.
(Yellow): This LED will light if the auxiliary alarm output has been activated.
WARNING
SYS FAULT
(Yellow): When a warning system is connected to the fire panel, this LED will
light if the connection to the warning system becomes faulty.
SUPPLY FAULT
supply.
16.
(Green): This LED will light when the mains power is turned on.
(Yellow): This LED will light if there is one of the following faults on the power
EARTH FAULT
(Yellow): This LED will light if there is an incorrect earth on any of the signal
cables of the system.
SYSTEM FAULT
TEST MODE
(Yellow) This LED will light if the main system CPU is in fault.
(Yellow): This LED will light when the panel is in any of the test modes.
DE-ISOLATE
If a detector currently displayed on the LCD has been isolated, pressing this
key will de-isolate it.
FAULT
OUTPUT ISOLATE
( Yellow ): Pressing this button will isolate the fault output relay on the brigade
board. If the relay is isolated the associated LED will light. Pressing the button again will de-isolate
the relay.
Page 55
21.
22.
23.
24.
25.
26.
AUXILIARY
FAULT / ISOLATE
( Yellow ): Pressing this button or if the FACP is fitted with a door switch and
the door is opened the auxiliary output relay on the brigade board will be isolated. If the auxiliary
fault / isolate is isolated the associated LED will light steady. Pressing the button again will deisolate the auxiliary fault / isolate relay.
The auxiliary output line is monitored, should it go into fault, the LED will flash.
AIF
ACTIVE
( Yellow ): Pressing this button will activate the Alarm Investigation Facility.
The LED just above the switch shall turn on.
LOOP
Press this key followed by a number to select the loop you wish to access eg LOOP 4.
SENSOR
After selecting the Loop number press this key to enter the sensor number for the device
to be interrogated.
ZONE
Press this key followed by a number eg ZONE 4 to select the required zone.
DISPLAY
Press this key after selecting the Zone number or the Loop and Sensor numbers to
display the state of the device.
9
27.
28.
29.
30.
SYMB
These keys are used to navigate around the panels menus and enter data. If entering a
descriptor, or some other data that contains characters as well as numbers, pressing the keys
multiple times will scroll through the available letters written on the button, in sequence. Eg 1,A,B,C
TO
ENTER
Press the ENTER key when using the panel, to enter data.
CANCEL ENTRY
The CANCEL ENTRY key is used to delete data in a current field or return to
the previously displayed menu.
31.
Used to move the cursor back and forth when entering data in a field.
32.
These keys are used to move between fields when entering data.
MENU FUNCTION
33.
Pressing the MENU key will display the main menu on the LCD. Similarly
pressing the FUNCTION key will display the function menu on the LCD.
34.
LCD DISPLAY - This screen can be configured with the servicing companies name and phone
number. It also displays the current date, time and that the system is normal (no faults and alarms).
If there are any faults or alarms the LCD will display the device in question, if multiple detectors or zones
are not in their normal state, the PREVIOUS and NEXT keys are used to scroll through them.
FIREFINDER
AMPAC
PH: 08 9242 3333
SYSTEM IS NORMAL
15/7/2005
Page 56
14:00:00
IMPORTANT NOTE:
It is strongly recommended that all field programming changes be properly recorded.
12
15/7/2005
14:00:00
NOTE: All menus are provided with screen prompts and a Quick Reference Guide ( see Section
24 ) guides the operator through the operation of the FAC .
From the DEFAULT DISPLAY, press MENU or FUNCTION. The FUNCTION
menu is password protected (actually a pass-number as it can only contain
numbers) to prevent unauthorised changes to the panel's configuration.
MENU FUNCTION
Level III: In addition to the Level I & II facilities, Add, Delete, Delete all passwords and Mode ( Zone /
Sensor ) onsite Programming.
12.3.1
Forgotten Passwords
NOTE: The temporary password becomes invalid if 9999 is entered again or if the panel is repowered after 9999 has been entered.
Page 57
13
MENU FUNCTION
1:PREALARMS
4: STATUS
2: FAULTS
5:TEST
n
o
PRE-ALARMS,
FAULTS; Pressing
m Zones
p Power
r Test
Sensors
Loops
Modules
Supply
Brigade
Failures
Bells
If there are no alarms, pre-alarms, faults or isolates, a message, eg. NO ZONES OR SENSORS IN
ALARM, will be displayed for 1 to 2 seconds and then the display will return to the Main menu.
1: MODULES
4:AVALUES
2: I/O
STATUS MENU
0: LOOPS
3: NETWORK
SELECT NO.
1: MODULES
4: SYSTEM
2: I/O
5:AVALUES
Press to print all devices on the loops ( Press RESET to stop printing )
Modules: Select the type of module, Slave m, P/S n, Brigade o or External LED Mimic p
and follow the screen prompts to display the status of the selected field.
I/O: The LCD will display the status of an input or output in a panel or on a loop.
Once the above is selected follow the prompts and enter the;
i)
I/O controller number then the input or output on that controller or,
ii)
loop, sensor and output number on that device.
The LCD will display if it is configured and if so a description of what that input or output does
and its current state.
Page 58
m Network Points:
DISPLAY NETWORK POINTS
0: STATUS
1: POWER SUPPLY
2: BRIGADE
SELECT NO.
or
o Brigade
LCD
Displays
Operational
Non- Op
VER: 6.2
STAT: NORMAL
q Is pressed to access SYSTEM STATUS.( If the system configuration is not networked Press p )
SYSTEM STATUS
ALARMS: 0000 PREALARMS: 0000
ISOLATES: 0000
SENSOR FAULTS: 0000 MOD FAULTS: 0000 WDOG: 00
LOOP FAULTS: 00
VERSION: 6.0.30/AS4428
Page 59
Loop 1 Sensor 1
SMOKE
L1 S1 Z2 STAT: NORMAL
AVALUE: 25 MODE: 0 1: 000 O: 000
2: LAMP
SELECT NO:
13.2.1
Alarm Test
Important: Ensure Alarm outputs are isolated / inhibited before commencing the test.
is pressed to initiate an Alarm Test: Alarm tests either a zone or a sensor on a loop or a range
TO
TO
ALARM TEST
ZONE
select ZONE NO. then ENTER or TO key
SELECT NO:
SELECT NO:
13.2.2
Fault Test
FAULT TEST
0: ALARM
1: SENSOR
SELECT NO:
and FAULT that was detected can be viewed by scrolling through them using the
and
PREVIOUS
keys. If an Alarm or Fault was not detected a short message displays this result and the
screen returns to the Fault Test default screen.
13.2.3
Lamp Test
is pressed to initiate a Lamp Test: The test will sequentially flash the LEDs on the front panel
and illuminate the various segments on the LCD display.
Page 60
14
Main Functions
LEVEL II MAIN FUNCTIONS
0: DATE 1: TIME 2: DAYNIGHT SETTINGS
4: TESTS 5: I/O 6: ACCESS
SELECT NO:
3: LOGS
3: LOGS
to select the set DATE SCREEN. The prompt will ask for the date to be entered in this format,
DD/MM/YYYY ( EG 18/08/2005 ), key in and press ENTER . The screen will then return to the MAIN
FUNCTIONS MENU.
n
o
ENTER .
ENTER .
Re-pressing
will
&
Once the type of log is selected, eg. FAULT above, each entry can be viewed by stepping through them
PREVIOUS
NEXT
using the
and
keys
Page 61
PRINT ENTRY will print out the displayed information if a printer is installed, or
SHOW OPTIONS allows the operator to select how the Logs are viewed.
Press
m to VIEW BY ENTRY NUMBER or n to VIEW BY DATE. In each case the screen
will ask for the appropriate information ( ENTRY NUMBER or DATE ) to be entered before
the selected option will be displayed.
NOTE: it is possible to scroll through the alarms by using the PREVIOUS and NEXT keys.
TESTS: prompts the operator to select either the WALK or LOOP test.
Press
m
WALK TEST; the operator will be prompted to select either ZONE or SENSOR test.
Press
This screen requires the operator to select a Zone or number of Zones to be tested, that is enter the
Zone number
press ENTER or enter the Zone number press TO then the next highest
Zone number to be tested EG. 2 TO 7 then ENTER.
The TEST MODE LED will be illuminated for the duration of the test and the test will run until the
operator RESETS the system.
Press
This screen requires the operator to select a Zone and then a Sensor
(using the TO key) to be tested then pressing ENTER to start the test.
or number of Sensors
The TEST MODE LED will be illuminated for the duration of the test and the test will run until the
operator RESETS the system.
Press
LOOP TEST requires the operator to select a LOOP for DIAGNOSTIC TESTING
NOTE: The LEDs on the Brigade Board will indicate which leg is being tested.
The tests displayed are;
TESTING SIDE A
TESTING SIDE B
Once the testing is completed the final screen will display the number of devices found and tested
on the LOOP and a Reset is requested to return the system to normal.
NOTE: If the data is not entered within 2 minutes the screen will time out and return to the
DEFAULT SCREEN.
Page 62
n Output Selected:
FUNCTIONS
PASSWORD
select PASSWORD then ENTER key
&
1: DELETE PASSWORD
3: SENSOR MODE
Press
s while in the Main Functions menu and enter the Level III Password if in Access Level II or, if in Access
Level III to display the Password Menu.
Add Password: Enter the new password, then press ENTER . The password is always a
4 digit number.
Delete Password: Enter the password that you want to delete, then press ENTER.
Delete All Passwords: This asks you to confirm that you want to delete all the passwords.
Press ENTER then ENTER again.
Zone / Sensor Mode: This sets the mode in which Alarms, Faults, Prealarms and Isolates
status information will be displayed. Zone is the default setting.
Page 63
14.8.1
Press
Zone:
Key in the zone number and enter or change the description ( DESC ) by pressing the numeric
buttons multiple times to access characters while at the same time using
buttons to move the flashing underline or curser.
EDIT Zx DESC AND TYPE SETTING
DESC < ZONE >
TYPE <
ALPHA KEYS ARE ACTIVE
Press
to move between fields use the reciprocal button
By going through all the fields a second screen can also be accessed to show the Output options.
Press
The keys
are used to set the Y/N field, that is the selected Zone that will activate
the Brigade Options ALRM, BELL etc and Config.
EDIT Z I/O GROUPS
GROUP 1: GROUP 2:
GROUP 4: GROUP 5:
Enter GROUP NO:
GROUP 3:
GROUP 6:
or
Configuration settings are Latching, Non-Latching, AVF, Self Reset ( 0 to 99 seconds ). After
setting the Configuration the ZONE I/O GROUPS are programmed.
ENTER Zx BRIGADE OPTIONS AND CONFIG
ALRM: Y/N BELL: Y/N AUX: Y/N SPK: Y/N AIF: Y/N
ALARM LED: Y/N CONFIG: LATCHING
use < or > to change setting
14.8.2
Device Programming
Press
DEVICE:
Screen:
keys to MOVE between fields ie: DESC & TYPE and next parameter
Enter the Loop and Sensor number then scroll through the following screens.
Press
or
Press
m to EDIT
or
n to DELETE
1. EDIT LxSx DESCRIPTION AND TYPE STRING.
eg:
DESC
Loop 1 Sensor 1
TYPE
SMOKE
2. Allocate / Edit the Sensor to a Zone and set the device type then press.
eg: XP95 Photo, XP95 Heat etc3. Set /Edit and display the Output Configurations or options then
eg: Latching, AVF, Non-latching etc
press.
press.
14.8.3
Input Programming
Press
INPUT:
By following the screen prompts as above Edit or Delete an INPUT in a panel or a loop.
Screen: PROGRAM MENU SELECTING AN INPUT
m IN A PANEL
I/O MODULE
ON A LOOP
LOOP
INPUT
SENSOR
INPUT
Select INPUT NO. then ENTER key
14.8.4
Output Programming
Press
p
OUTPUT:
By following the screen prompts as above Add, Edit or Delete an output in a panel or on a loop.
Page 65
14.8.5
Press
q
MCP:
The operator will be prompted to enter the NODE Number, that is the Node or panel on which the
MCP is mounted.
14.8.6
Sub Address
Press
Sub Address lets the operator EDIT or DELETE the address of an IO device on a Loop.
to EDIT or press
to DELETE.
Editing
If editing, the screen will display the Loop number, Sensor number and sub address followed by
DESC <
TYPE < INPUT > and advise the Alpha keys are active. Once edited and pressing
ENTER the message UPDATE TO MEMORY message will be displayed.
ENTER should not be pressed if the CONFIGURATION is to be edited, instead press to go
to the next screen where the output is configured to be latching (general alarm requiring a Reset to
be returned to normal ), NON-LATCHING ( hence self resetting ) or FAULT which clears when the
fault is cleared. )
14.8.7
Watchdog
This Function provides a counter to record any re-initialisation of the processor. If due to a
software failure the panel is automatically reset then the counter will increment by 1 The maximum
count is 99 after which the counter resets to 00. Pressing m will reset the counter. When the panel
is commissioned this counter MUST be reset to 0 as must be the Events Logs.
Note: If a change does occur the FACP will take 30seconds to register the event on the LCD and
illuminate the FAULT LED.
14.9.1
Extra Devices Detected
The FireFinder LCD will indicate extra devices have been detected by displaying the screen below
and the FAULT LED will be illuminated.
FIREFINDER
4/7/2005
08:05:45
EXTRA DEVICES DETECTED
GOTO PROGRAMMING MENU TO RESOLVE
SYSTEM IS NOT NORMAL
Page 66
PROGRAMMING MENU
0: RESOLVE EXTRA MODULES AND DEVICES
1: ON SITE PROGRAMMING
SELECT NO:
14.9.2
Mismatch Detected
If a mismatch is detected the Normal Default Screen will change to that shown below. Go to the
Programming Menu and select either m Resolve Extra Modules and Devices then o
( Device Type ) or p ( Mode ) to resolve the mismatch, OR On Site Programming to resolve manually.
Loop 1 Sensor 1
L1 S6 Z1 STAT: TYPE MISMATCH
ZONE FAULTS 1 OF 1
15
The LCD will always display the first fire alarm signal received in the top section of the LCD. The lower
section of the LCD will also permanently display the most recent zone in alarm. Other essential fire alarm
PREVIOUS
NEXT
DETECTOR 1
L1 S1 Z17 ALARM
5/7/2005 15:12:10
SENSOR ALARMS 1 OF 5
SMOKE
16
LOOP OR SENSOR
1. From the default display, press LOOP
2. Enter the loop number you wish to interrogate then press SENSOR.
3. Press the button for the sensor number.
4. Press the TO button if you wish to access a range of sensors on the loop,
5. Press the DISPLAY button if you wish to display the status of a sensor,
6. Press the ISOLATE button if you wish to isolate a sensor then ACKNOWLEDGE
7. Press the DE-ISOLATE button to de-isolate a sensor.
LOOP
SENSOR
ABC
JKL
ISOLATE
TUV
DISPLAY
ACKNOWLEDGE
17
Detectors
Isolator
Section B
Section A
Interface
Isolator
L+ L-
Isolator
LEDs A & B
Loop 1
Page 68
L-
L+
213-0015
213-0021
213-0022
213-0023
Page 69
201-0023
201-0024
201-0025
201-0026
201-0027
201-0028
201-0029
214-0001
223-0001
209-0019
201-0032
201-0033
201-0034
201-0035
201-0103
201-0104
201-0105
201-0106
201-0107
201-0108
220-0004
222-0020
222-0021
222-0022
222-0023
205-0062
205-0063
205-0066
205-0067
205-0064
205-0065
205-0077
205-0078
201-0110
201-0114
201-0113
Page 70
18
Certification Information
Manufactured to:
AS4428
Page 71
19
Statement of Compliance
Please PRINT
1. Name of building
2. Address
3. I/WE have installed in the above building
an
alteration
to
the
manufactured by,
OR
system
a system manufactured by
4. The system is connected to the
P,
non-permanent
5. Date of connection
Pconnection ( tick )
/
Manufacturer
AH
Yes
Yes
Yes
Yes
14. Portions of the building not protected by this system are; ( Please PRINT )
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
Page 72
P
P
P
P
No
No
No
No
P
P
P
P
I/We
1.
2.
3.
Print Name/s
hereby certify that the installation has been thoroughly tested from each actuating device and that a test of
the transmission of the alarm signal to the monitoring service provider has been satisfactorily carried out.
I/We further certify that the whole system and all components called up in Clause 1.3 in connection
therewith are installed entirely in accordance with the current requirements of AS 1670.l, except with regard to the following details which have already been approved", approval attached.
Strike out the bolded sentence if there have not been any exceptions.
Signature
Date
Installing Company
Please PRINT or Stamp
Page 73
#
*
Indicate with a number in brackets the number of actuating devices in concealed spaces.
Add addressable loop number in brackets where applicable.
Zone of
Protection
Alarm Zone
* No of
Actuating
Devices
per Zone
Smoke
D
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
Page 74
Ion
Photo
Flame
IR
UV
MCP
Other
20
Postcode
NEW
MODIFIED
ADDITION
UPGRADE
( Circle )
( in 'BLOCK LETTERS' )
Company Name
Street
Suburb
State / Country
Postcode
Commissioning Representative: Name ( Print )
Signature:
Page 75
20.1 Procedure
The following tests are the minimum that shall be performed when commissioning a system using the
FireFinder Fire Alarm Control Panel. Supplements to these test may be added by way of attachments or
notation ( using waterproof ink ) to this documentation. If supplements or tests are added reference to them
shall be made at an appropriate point on this document.
This Commissioning Record is to be completed in conjunction with the 1.
operator's manual;
2.
installer's statement(s);
3.
'as-installed' drawings; and
4.
detector test records,
The Record provides a complete description of the installed system and its tested performance at the time
of being commissioned.
ii
iii
iv
P
P
P
P
P
P
P
P
Not
Applicable
No
1.
Yes
System Information
20.2
P
P
P
P
2.
Check that the primary power source for the system has been provided in
accordance with AS 3000, and that the isolating switch disconnects the active
conductors.
PPP
3.
Check that the detector and the FIP locations are in accordance with the
appropriate clauses of Standard, AS 1670.
PPP
Measure each alarm zone circuit voltage, and ensure each is within the
equipment manufacturer's specifications.
ii
Page 76
PPP
PPP
6.
7.
Open circuit and short circuit the end of line device' on each alarm zone
circuit, or conduct other appropriate tests to ensure that fault and alarm
conditions are operating correctly on all alarm zone facilities on other sections
of the control and indicating equipment.
NA
PPP
Operate each alarm test, fault test, isolate and reset facility provided for
each alarm zone facility to determine correct operation.
ii
Operate the primary power source switch on and off at least five times to
check the system will not cause a false alarm from primary power source
interruptions.
PPP
PPP
PPP
Check the operation of each manual call point and all other actuating devices.
PPP
ii
iii
8.
PPP
PPP
iii
iv
v
vi
Page 77
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
Measure the response time of all sampling points using smoke placed
at each sampling point.
Check the back-up power supply capacity.
iii
iv
vi
vii
viii
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
NA
P
P
P
P
P
P
P
P
10.
Test each ancillary function by operating the alarm zone facility(ies), associated with the ancillary
function.
11.
Alarm signaling:
i
ii
12.
Check that the master alarm facility is able to receive the alarm signal
by operating each alarm zone facility.
Check that the master alarm facility initiates an alarm to the fire control
station equipment.
PPP
PPP
Battery supply:
i
ii
Check that both the primary and secondary power sources are of a
suitable type and capacity complying with Clause 8.2.
Perform a float voltage check according to the battery manufacturer's
recommendation to ensure that the charger type and setting is correct.
Type of battery.
Charger type.
PPP
PPP
13.
Check that all alarm zone facilities have been correctly labeled and that the
alarm zone is immediately apparent from the labeling.
PPP
14.
Check the 'as-installed' drawings are marked up, are consistent with the
installation and the operator's manual is relevant to the installation.
PPP
15.
Ensure the results of these tests are recorded in the system logbook.
PPP
Page 78
21
Troubleshooting Chart
Problem
Solution
No Mains Power
FireFinder
You must perform a loop test to clear the fault. This is a level 1
function.
Check for correct software installed in all communication boards.
Forgotten password
An Analogue Fault occurs when using a Zone Monitor A 1.8k Ohm resistor must be placed in series with the switch
to monitor a switch.
contacts.
Sounder Fault
Make sure you have a 10K Ohm EOL resistor fitted and a diode
(1N4004) in series with the sounder
Page 79
22
Address Setting
ADDRESS 1234567
01 = 1000000
02 = 0100000
03 = 1100000
04 = 0010000
05 = 1010000
06 = 0110000
07 = 1110000
08 = 0001000
09 = 1001000
10 = 0101000
11 = 1101000
12 = 0011000
13 = 1011000
14 = 0111000
15 = 1111000
16 = 0000100
17 = 1000100
18 = 0100100
19 = 1100100
20 = 0010100
21 = 1010100
22 = 0110100
23 = 1110100
24 = 0001100
25 = 1001100
26 = 0101100
27 = 1101100
28 = 0011100
29 = 1011100
30 = 0111100
31 = 1111100
32 = 0000010
33 = 1000010
34 = 0100010
35 = 1100010
36 = 0010010
37 = 1010010
38 = 0110010
39 = 1110010
40 = 0001010
41 = 1001010
42 0101010
43 = 1101010
44 = 0011010
45 = 1011010
46 = 0111010
47 = 1111010
48 = 0000110
49 = 1000110
50 = 0100110
51 = 1100110
52 = 0010110
53 = 1010110
54 = 0110110
55 = 1110110
56 = 0001110
57 = 1001110
58 = 0101110
59 = 1101110
60 = 0011110
61 = 1011110
62 = 0111110
63 = 1111110
64 = 0000001
65 = 1000001
66 = 0100001
67 = 1100001
68 = 0010001
69 = 1010001
70 = 0110001
71 = 1110001
72 = 0001001
73 = 1001001
74 = 0101001
75 = 1101001
76 = 0011001
77 = 1011001
78 = 0111001
79 = 1111001
80 = 0000101
81 = 1000101
82 = 0100101
83 = 1100101
84 = 0010101
85 = 1010101
86 = 0110101
87 = 1110101
88 = 0001101
89 = 1001101
90 = 0101101
91 = 1101101
92 = 0011101
93 = 1011101
94 = 0111101
95 = 1111101
96 = 0000011
97 = 1000011
98 = 0100011
99 = 1100011
100 = 0010011
101 = 1010011
102 = 0110011
103 = 1110011
104 = 0001011
105 = 1001011
106 = 0101011
107 = 1101011
108 = 0011011
109 = 1011011
110 = 0111011
111 = 1111011
112 = 0000111
113 = 1000111
114 = 0100111
115 = 1100111
116 = 0010111
117 = 1010111
118 = 0110111
119 = 1110111
120 = 0001111
121 = 1001111
122 = 0101111
123 = 1101111
124 = 0011111
125 = 1011111
126 = 0111111
ON
11
1
11
32
16 64
23
EN54
NZS4512
UL72
MS1404
GB4717
DESCRIPTION
Enter the number of units listed in the left hand column which go to make up the panel, complete
the multiplication to obtain the quiescent current then multiply by the standby and alarm hours
required by the standard.
1.
Amps
2.
Add
Amps
3.
Add
Amps
4.
Amps
Note: Where the fire control station will not receive the system's total power supply failure signal,
the battery should have sufficient capacity to maintain the system for 96 h.
Page 81
Iq Calculation
Iq
No Off X mA
240
254
360
1.8
156.2
27
= Iq
Interface Modules
Additional 3,5 loops add
Additional 2,4 loops add
16 zone
16/16 I/O
Fire Fan Control
32 Zone LED
Network I/F
Controller I/F
Valve or Pump Display
8 Way Bell Monitor
Agent Release
40 each
15 each
143
5
14
0
74
5.1
3.7
20
29
Loop Devices
XP95 Thermal A / B
Discovery Thermal C&D
XP95 Ion
XP95 Photo
Discovery Multisensor
Discovery Photo
Discovery Ion
XP95 Short cct isolator
XP95 I/O module
XP95 Sounder control
XP95 MCP
XP95 Zone Monitor
Ampac 3 I/O loop power
Ampac 3 I/O ext. power
Ampac SID / SIOD
0.25
0.5
0.28
0.34
0.5
0.4
0.5
0.11
1.2
1.9
0.35
6
2.1
1.5
1.7
Iq =
Devices activating when the system is in alarm
8 x Relays
60
Bell
30
Other
Ida=
Devices de-activating when the system goes into alarm
Aircon Relays
20
Electric locks
100
Other
Idd=
Page 82
Evac
Type
Iq in
mA
Ia in
mA
EV20
41
650
EV40
EV60
EV120
140
150
150
2500
3800
8500
NOTE:
Note:
=
=
1,000ma = 1 Amp
( Iq x 24 ) + Fc( Ia x 0.5 )
Note: The figure of 24 above
should be replaced with 96 if
Agent Release is used
=
=
Ah
=
=
Ah x 1.25
Ah
Ah
Ah Requirement
=
=
=
=
Ah above
24 x e
A
Ah
Page 83
EXAMPLE CALCULATION
Panel Configuration
Basic 1 loop panel
Basic 2 loop panel
Basic 16 Zone panel
Extender
LCD repeater
LED repeater
Evac Module
Iq Calculation
Iq
No Off X mA
1
240
254
360
1
1.8
156.2
2
27
= Iq
240
0
0
1.8
0
54
0
0
0
0
0
0
429
5
6.7
0
0
0
3.7
0
Interface Modules
Additional 3,5 loops add
Additional 2,4 loops add
16 zone
16/16 I/O
Fire Fan Control
32 Zone LED
Network I/F
Controller I/F
Valve or Pump Display
8 Way Bell Monitor
Agent Release
3
1
1
Loop Devices
XP95 Thermal A & B
Discovery Thermal C&D
XP95 Ion
XP95 Photo
Discovery Multisensor
Discovery Photo
Discovery Ion
XP95 Short cct isolator
XP95 I/O module
XP95 Sounder control
XP95 MCP
XP95 Zone Monitor
Ampac 3 I/O loop power
Ampac 3 I/O ext power
Ampac SID / SIOD
30
30
40 each
15 each
143
5
6
0
74
5.1
3.7
20
29
Evac
Type
Iq in
mA
Ia in
mA
EV20
41
650
EV40
EV60
EV120
140
150
150
2500
3800
8500
0
0
0
0.25
7.5
0.5
0
0.28
0
0.34
0
0.5
15
0.4
0
0.5
0
0.11
0
1.2
6
1.9
0
0.35
0
6
0
2.1
0
1.5
0
1.7
0
0
Iq = 768.7
Note:
1,000ma = 1 Amp
=
=
=
=
( Iq x 24 ) + Fc( Ia x 0.5 )
( 769ma x 24 ) + 2( 1049ma x 0.5 )
18456ma + 1050ma
19.506Ah
=
=
19.5 x 1.25
24.375 Ah
25 Ah
Ah Requirement
=
=
=
=
( 5x Iq ) + Fc( 0.5 x Ia )
( 5 x 769 ) + 2( 0.5 x 1049 )
3845 + 1050
4.895Ah
4.895
24 x e
0.26A ( rounded )
afp - 792
Power-Sonic
PS Series
afp - 1220
Matsushita
LCR Series
afp - 1228
B&B
BP Series
NPH1.3-12
NPH2-12
NPH3.2-12
NPH5-12
NPH16-12
NP0.8-12
NP1.2-12
NP1.9-12
NP2.3-12
NP2-12
NP2.6-12
NP4-12
NP7-12
NP12-12
NP24-12
NP24-12B
NP38-12
NP65-12
PS-1208
PS-1212
PS-1219
PS-1232
PS-1240
PS-1270
PS-12120
PS-12180
PS-12240
PS-12330
PS-12400
PS-12650
LCR12V4BP
LC-R125P
LC-RC1217P
LC-R127P
LC-R127R2P
BP 1.2-12
BP 1.9-12
BP 4 12
BP 7 12
BP 12-12
BP 17-12
BP 24-12
BP 40-12
afp - 1221
Matsushita
LCL Series
LC-LA12V33P
Afp - 1222
Matsushita
LCX Series
LC-X1224P9(AP)
LC-X1228P(AP)
LC-X1238P(AP)
LC-X1242P(AP)
LC-X1265P
LC-XA12100P
Page 85
24
Glossary of Terms
ACF :
ACKD :
ACKNOWLEDGED
AHU :
ALM :
ALARM
AVF :
AZF :
AZC :
C:
CIC :
CN :
CONNECTOR
CPU :
DGP :
EARTH :
BUILDING EARTH
EOL :
END OF LINE
FDS :
FACP :
FLT :
FAULT
GND :
I/O :
INPUT/OUTPUT
LCD :
MAF :
MCP :
MOV :
NIC :
N/C :
N/O :
N/W :
NETWORK
PCB :
P/S :
POWER SUPPLY
PSM :
REM :
REMOTE
SPOT :
TB :
TERMINAL BLOCK
VDC :
Page 86
25
Definitions
Addressable system - a fire alarm and detection system that contains addressable alarm zone facilities or
addressable control devices.
Alarm Verification Facility (AVF) - that part of the FACP, which provides an automatic resetting function
for spurious alarm signals so that they will not inadvertently initiate Master Alarm Facility (MAF), or ACF
functions. Using ConfigManager prior to downloading to the FireFinder sets this option
Alarm zone - the specific portion of a building or complex identified by a particular alarm zone facility.
Alarm Zone Circuit (AZC) - the link or path that carries signals from an actuating device(s) to an alarm
zone facility(s).
Alarm Zone Facility (AZF) - that part of the control and indicating equipment that registers and indicates
signals (alarm and fault) received from its alarm zone circuit. It also transmits appropriate signals to other
control and indicating facilities.
Alert signal - an audible signal, or combination of audible and visible signals, from the occupant warning
system to alert wardens and other nominated personnel as necessary to commence prescribed actions.
Ancillary Control Facility (ACF) - that portion of the control and indicating equipment that on receipt of a
signal initiates predetermined actions in external ancillary devices.
Ancillary equipment - remote equipment connected to FACP.
Ancillary relay - relay within FACP to operate ancillary equipment.
Ancillary output - output for driving ancillary equipment.
Approved and approval - approved by, or the approval of, the Regulatory Authority concerned.
Card-detect link - a link on a module connector to indicate the disconnection of the module.
Conventional System - is a fire detection system using a dedicated circuit for each alarm zone.
Distributed system - a fire alarm and detection system where sections of the control and indicating
equipment are remotely located from the FACP or where sub-indicator panel(s) communicate with a main
FACP.
Field connections - are connections made to FACP or ancillary equipment during installation.
Fire alarm system - an arrangement of components and apparatus for giving an audible, visible, or other
perceptible alarm of fire, and which may also initiate other action.
Fire detection system - an arrangement of detectors and control and indicating equipment employed for
automatically detecting fire and initiating other action as arranged.
Fire Alarm Control Panel (FACP) - a panel on which is mounted an indicator or indicators together with
associated equipment for the fire alarm or sprinkler system.
Fire resisting - an element of construction, component or structure which, by requirement of the
Regulatory Authority, has a specified fire resistance.
Indicating equipment - the part of a fire detection and or alarm system, which provides indication of any
warning signals (alarm and fault), received by the control equipment.
Interface - The interconnection between equipment that permits the transfer of data.
Main equipment - equipment essential to the operation of the system including, control equipment,
amplification equipment and power supply modules.
Master Alarm Facility (MAF) - that part of the equipment which receives alarm and fault signals from any
alarm zone facility and initiates the common signal (alarm and/or fault) for transmission to the fire control
station. Bells and other ancillary functions may be initiated from this facility.
Power Supply - that portion of the FACP which supplies all voltages necessary for its operation.
Regulatory Authority - an authority administering Acts of Parliament or Regulations under such Acts.
Page 87
26
MENU
FUNCTION
SPACE
ABC
DEF
ZONES/SENSORS
LOOP
MODULE
P/SUPPLY
BRIGADE
SPACE
( FAULT FIELDS )
ABC
DEF
GHI
JKL
MNO
TFAILS
BELLS
PQRS
(TEST FAILURES)
GHI
JKL
SPACE
PRINT TOTALS
SPACE
ABC
MODULES ( MODULE No )
ABC
SLAVE
P/S
BRIGADE
SPACE
ABC
DEF
GHI
DEF
I/O
SPACE
ABC
GHI
NETWORK
NETWORK POINTS
SPACE
ABC
DEF
( STATUS FIELDS )
( IF NETWORK IS ENABLED )
( IF NETWORK IS ENABLED )
SYSTEM
AVALUES
( ANALOGUE
VALUE OF DET )
JKL
MNO
MNO
NETWORK
NOT ENABLED
NETWORK
NOT ENABLED
GHI
JKL
SPACE
ZONE ( ZONE No )
SENSOR
( LOOP/SENSOR No )
SPACE
ABC
ABC
ZONE ( ZONE No )
SENSOR
( LOOP/SENSOR No )
SPACE
ABC
DEF
Page 88
LAMP
( TEST
FIELDS )
DATE ( DD/MM/YYYY )
TIME ( HH:MM )
SPACE
LEVEL 1
FUNCTIONS
FireFinder
FUNCTION
ABC
DEF
MENU
MNO
DEF
GHI
SPACE
ABC
ON ( TURN INPUT ON )
DEF
SPACE
ABC
DEF
IN A PANEL
( SELECT INPUT CONTROL No AND INPUT No )
SPACE
IN A PANEL
( SELECT I/O CONTROL NUMBER AND OUTPUT No )
ABC
SPACE
ABC
ABC
ABC
JKL
ABC
ON ( TURN OUTPUT ON )
DISABLED IF FACP
IS NETWORKED
ON ( TURN OUTPUT ON )
SPACE
ABC
GHI
SPACE
SPACE
AS FOR ALARM
SPACE
SPACE
SPACE
TUV
ON A LOOP
( SELECT LOOP No, SENSOR No, INPUT No )
DEF
AS FOR ALARM
VIEW BY DATE
AS FOR ALARM
JKL
GHI
ABC
ON ( TURN INPUT ON )
ABC
AS FOR ALARM
ABC
DEF
SPACE
SHOW OPTIONS
DEF
DEF
ABC
ABC
0
SPACE
DEF
IN A PANEL
( SELECT I/O CONTROL NUMBER AND INPUT No )
SPACE
ENABLE
ABC
PQRS
SPACE
DEF
PQRS
0
SPACE
ABC
LEVEL 3 FUNCTION
0
LOGS
SPACE
FUNCTION
LEVEL 2 FUNCTION
ABC
MENU
SPACE
0
SPACE
Quick Reference
FUNCTION
LEVEL 2
FUNCTIONS
TM
IN A PANEL
( SELECT OUTPUT CONTROL No AND OUTPUT No )
AS FOR INPUT
SPACE
SPACE
ABC
ABC
ABC
DEF
DEF
ABC
AS FOR INPUT
WATCHDOG RESET
JKL
MNO
PQRS
89
AUSTRALIA
AMPAC TECHNOLOGIES PTY LTD
EUROPE
AMPAC EUROPE LTD.
NEW ZEALAND
AMPAC INDUSTRIES LTD.
97 Walters Drive
Osborne Park 6017
Western Australia
UNCONTROLLED DOCUMENT
NOTE: Due to Ampacs commitment to continuous improvement specifications may change without notice.