Product

Data

50TJ008-014
Single-Package Rooftop Units
Electric Cooling
with Electric Heat Option
50 Hz, CE Units
Nominal Capacity: 21.5 kW to 35.9 kW
(6.1 to 10.2 Tons)

Single-Package Rooftop Units with:


European Community (CE) design
Galvanized steel cabinet with
Carrier Weather ArmorT coating
Fifty-one mm (2-in.) return-air
filters
Commercial strength base rails
Exclusive tool-less filter access
panel
Corrosion-resistant sloped condensate pan
Single power entry to unit
Commercial duty motors with permanently lubricated bearings
Standard cooling operation at outdoor ambient temperatures as low
as 4 C (25 F)
Meets ASHRAE Standard 62
(U.S.A.) for Indoor-Air Quality
(IAQ)

Features/Benefits
Compact, vertical discharge
units convert to horizontal
discharge, combining installation flexibility with efficient performance and easy
maintenance.
Easy installation and
conversion
All units are shipped in the vertical discharge configuration for fit-up to standard
roof curbs. The contractor can order
and install the roof curb early in the construction stage, before decisions on size
requirements are made.
All units feature roll-formed baserail
design with forklift slots on all 3 sides and
rigging holes for easier maneuvering.
Durable packaging protects all units during
shipment and storage.

Copyright 1995 Carrier Corporation

Form 50TJ-C4PD

The units can be easily converted from


a vertical to a horizontal discharge configuration by interchanging the panels supplied with the unit.
All units feature a non-corrosive sloped
condensate drain pan in accordance with
ASHRAE (American Society of Heating,
Refrigeration and Air Conditioning Engineers) Standard 62. Also, the new, sloped
condensate pan permits either an external side condensate drain (outside the roof
curb) or an internal bottom drain (inside
the roof curb). Both options require an
external, field-supplied P-trap. Plus, the
condenser coil grille (available as a
field-installed accessory) provides a metal
plate as an alternate location for the fieldsupplied disconnect, if desired.
In addition, the 50TJ units have a standard filter access door, which permits
tool-less filter changes and provides an
opening for outdoor air options and
accessories.
Field-installed electric heaters are available in a wide range of capacities. Single
point wiring kit makes installation simple.

Carriers exclusive Acutrol metering


device precisely controls refrigerant flow,
preventing slugging and flood-back, while
maintaining optimum unit performance.

Simple electrical connections

Integrated economizers and


outdoor air

Terminal boards, located in the base unit


control box, facilitate connections to room
thermostat, outdoor thermostat(s), economizer, and electric heat. Service panels are quickly removed, permitting easy
servicing.
Thru-the-bottom service connection
capability allows power and control wiring
to be routed through the unit basepan,
minimizing roof penetrations. Both power
and control connections are made on
the same side of the unit to simplify
installation.

Proven compressor reliability


Design techniques feature computerprogrammed balance between compressor,
condenser, and evaporator. Carrierspecified hermetic compressors are
equipped with compressor overcurrent and
overtemperature protection to ensure
dependability.

Durable, dependable
construction
Designed for durability in any climate, the
weather-resistant cabinets are manufactured using Carrier Weather Armort coating. The cabinet is constructed of
galvanized steel, is bonderized, and all
exterior panels are coated with a
prepainted baked enamel finish. The paint
finish is non-chalking, and is capable
of withstanding Federal (U.S.A.) Test
Method Standard No. 141 (Method 6061)
500-hour salt spray test. All internal
cabinet panels are primed, permitting
longer life and a more attractive appearance for the entire unit. In addition, the
50TJ units are designed with a single,
continuous top piece to eliminate any
possible leaks. Totally-enclosed condenser-fan motors and permanentlylubricated bearings provide additional unit
dependability.

During a first stage call for cooling, if the


outdoor-air temperature is below the
control set point, the leaving-air sensor
modulates the economizer outdoor-air
damper open to achieve the set point.
When second-stage cooling is called for,
the compressor is energized in addition to
the economizer. If the outdoor-air temperature is above the set point, the first
stage of compression is activated and the
economizer stays at minimum vent position. Economizer operation is controlled
by Accusensor I dry-bulb thermostat
that senses outdoor-air temperature.
Accessory upgrade kits include solid-state
enthalpy control and differential enthalpy
sensor.
The Durablade economizer has a reliable sliding plate damper which is easily adjusted for 100% outdoor air, 100%
return air, or any proportions of mixed air.

EURO-STYLE CONTROL BOX

Quiet, efficient operation and


dependable performance
Compressors have vibration isolators for
extremely quiet operation. Efficient fan
and motor design permits operation at
very low sound levels, and all units are
mounted on independent mounting rails.
Quiet and efficient operation is provided
by belt-driven evaporator fans (standard).
The belt-driven evaporator-fan motors
allow adjustment to available static pressure to meet the job requirements of even
the most demanding applications.

Indoor-air quality begins with


Carrier rooftops
Sloped condensate pans minimize biological growth in rooftop units in accordance
with ASHRAE Standard 62. Fifty-one mm
(2-in.) filters with optional dirty filter indicator switch provide for greater particle
reduction in the return air. The face-split
evaporator coils improve the dehumidification capability of the standard units, and
standard enthalpy controls provided with
the optional or accessory economizers
maximize building humidity control. The
units also have an accessory, 100% open,
two-position damper to meet all your
fresh outdoor air requirements.
For units without economizer, yearround ventilation is enhanced by a manual
outdoor-air damper (ordered as an accessory). The damper can be preset to admit up to 25% outdoor air.

Euro-style control box


Control box is designed in accordance
with IEC (International Electrotechnical
Commission) standards and complies
with harmonized European Standard
EN60335-2-40. The control box is factory
installed and features:
single-color, specially routed wiring with
supports
fully shrouded terminal blocks for field
power connection
no sharp edges on wire paths
earth bonding
transformer which meets IEC742

Table of contents
Page
Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1,2
Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4,5
Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6,7
Base Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Accessory Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10,11
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-25
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Typical Piping and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Typical Wiring Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28,29
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32-34

Model number nomenclature

LEGEND
Al
Aluminum
Cu
Copper
FIOP Factory-Installed Option

*Refer to 50TJ Product Ordering Data or contact your local Carrier


representative for 50TJ FIOP code table.
All coils have copper tubes. Contact your local Carrier representative for more details regarding coil fin options B, C, D, and V.
**50TJ007-014 only.

Physical data (SI)


UNIT SIZE
NOMINAL CAPACITY (kW)
OPERATING WEIGHT (kg)
Unit
Al/Al*
Economizer
Roof Curb
COMPRESSOR
Quantity
Oil (ml)
REFRIGERANT TYPE
Operating Charge (kg)
Circuit 1
Circuit 2
CONDENSER COIL
Rows...Fins/m
Total Face Area (sq m)
CONDENSER FAN
Nominal L/s
Quantity...Diameter (mm)
Motor BkW...r/s
EVAPORATOR COIL
Rows...Fins/m
Total Face Area (sq m)
EVAPORATOR FAN
Quantity...Size (mm x mm)
Type Drive
Nominal L/s
Motor kW
Maximum Continuous BkW
Motor Frame Size
Fan r/s Range
Motor Bearing Type
Maximum Allowable r/s
Motor Pulley Pitch Diameter Min/Max (mm)
Nominal Motor Shaft Diameter (mm)
Fan Pulley Pitch Diameter (mm)
Nominal Fan Shaft Diameter (mm)
Belt, Quantity...Type...Length (mm)
Pulley Center Line Distance (mm)
Speed Change per Full Turn of
Movable Pulley Flange (r/s)
Movable Pulley Maximum Full Turns
From Closed Position
Factory Setting
Factory Speed Setting (r/s)
Fan Shaft Diameter at Pulley (mm)
HIGH-PRESSURE SWITCH (kPa)**
Standard Compressor Internal Relief
(Differential)
Cutout
Reset (Auto.)
LOW-PRESSURE SWITCH (kPa)**
Cutout
Reset (Auto.)
FREEZE PROTECTION THERMOSTAT**
Opens (C)
Closes (C)
OUTDOOR-AIR INLET SCREENS

008
21.5

009
24.3

012
29.2

014
35.9

342
20
65

345
20
65

415
20
65

422
20
65

2
1479 ea

2
1479 ea

2
1479 ea

2
1922 ea

Hermetic
R-22
2.10
2.13

2.54
2.49
4.22
2.54
2.55
3.90
Enhanced Copper Tubes, Aluminum Lanced Fins
1...669
2...669
2...669
2...669
1.90
1.67
1.62
2.30
Propeller Type
2880
2880
3050
3050
2...559
2...559
2...559
2...559
.19...15.5
.19...15.5
.19...15.5
.19...15.5
Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Acutrol Feed Device
3...590
3...590
3...590
4...590
0.74
0.74
0.93
1.03
Centrifugal Type
1...381 x 381
1...381 x 381
1...381 x 381
1...381 x 381
Belt
Belt
Belt
Belt
1230
1420
1700
1980
1.12
1.12
1.50
2.24
1.79
1.79
2.16
3.13
56
56
56
56
10.33-14.67
10.33-14.67
11.50-15.00
11.83-14.83
Ball
Ball
Ball
Ball
26.7
26.7
26.7
26.7
61/86
61/86
86/112
102/127
16
16
16
22
140
140
178
203
25
25
25
25
1...A...1219
1...A...1219
1...A...1295
1...A...1448
406
406
495
495
.83
.83
.67
.58
5
5
10.33
25

Al
Bhp
BkW
Cu

LEGEND
Aluminum
Brake Horsepower
Fan Input Watts x Motor Efficiency
Copper

5
5
11.50
25

3103 345

5
5
11.83
25
3448 345

2951
2206
48 21
152 48

Quantity...Size (mm)
RETURN-AIR FILTERS
Quantity...Size (mm)

5
5
10.33
25

4...406 x 508 x 51

1
7
Cleanable
1...508 x 635 x 25
1...406 x 635 x 25
Throwaway
4...406 x 508 x 51
4...508 x 508 x 51

4...508 x 508 x 51

*Evaporator coil fins/condenser coil fins.


Weight of 356 mm roof curb.
**Requires the accessory/optional Controls Upgrade Kit.
NOTE: The 50TJ units have a loss-of-charge/low-pressure switch
(accessory/option) located in the liquid line.

Physical data (English)


UNIT SIZE
NOMINAL CAPACITY (tons)
OPERATING WEIGHT (lb)
Unit
Al/Al*
Economizer
Roof Curb
COMPRESSOR
Quantity
Oil (oz)
REFRIGERANT TYPE
Operating Charge (lb-oz)
Circuit 1
Circuit 2
CONDENSER COIL
Rows...Fins/in.
Total Face Area (sq ft)
CONDENSER FAN
Nominal Cfm
Quantity...Diameter (in.)
Motor Hp...Rpm
EVAPORATOR COIL
Rows...Fins/in.
Total Face Area (sq ft)
EVAPORATOR FAN
Quantity...Size (in.)
Type Drive
Nominal Cfm
Motor Hp
Maximum Continuous Bhp
Motor Frame Size
Fan Rpm Range
Motor Bearing Type
Maximum Allowable Rpm
Motor Pulley Pitch Diameter Min/Max (in.)
Nominal Motor Shaft Diameter (in.)
Fan Pulley Pitch Diameter (in.)
Nominal Fan Shaft Diameter (in.)
Belt, Quantity...Type...Length (in.)
Pulley Center Line Distance (in.)
Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Movable Pulley Maximum Full Turns
From Closed Position
Factory Setting
Factory Speed Setting (rpm)
Fan Shaft Diameter at Pulley (in.)
HIGH-PRESSURE SWITCH (psig)**
Standard Compressor Internal Relief
Differential)
Cutout
Reset (Auto.)
LOW-PRESSURE SWITCH (psig)**
Cutout
Reset (Auto.)
FREEZE PROTECTION THERMOSTAT**
Opens
Closes
OUTDOOR-AIR INLET SCREENS
Quantity...Size (in.)
RETURN-AIR FILTERS
Quantity...Size (in.)

Al
Bhp
BkW
Cu

LEGEND
Aluminum
Brake Horsepower
Fan Input Watts x Motor Efficiency
Copper

008
6.1

009
6.9

012
8.3

014
10.2

755
44
143

760
44
143

915
44
143

930
44
143

2
50 ea

2
50 ea

2
50 ea

2
65 ea

Hermetic
R-22
4-10
4-11

5-7
5-8
9-5
5-7
5-10
8-7
Enhanced Copper Tubes, Aluminum Lanced Fins
1...17
2...17
2...17
2...17
20.50
18.00
17.42
25.00
Propeller Type
6100
6100
6500
6500
2...22
2...22
2...22
2...22
14...930
14...930
14...930
14...930
Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Acutrol Feed Device
3...15
3...15
3...15
4...15
8.0
8.0
10.0
11.1
Centrifugal Type
1...15 x 15
1...15 x 15
1...15 x 15
1...15 x 15
Belt
Belt
Belt
Belt
2600
2600
3500
4200
112
112
2
3
2.40
2.40
2.90
4.20
56
56
56
56
620-880
620-880
690-900
710-890
Ball
Ball
Ball
Ball
1600
1600
1600
1600
2.4/3.4
2.4/3.4
3.4/4.4
4.0/5.0
5 8
5 8
5 8
7 8
5.5
5.5
7.0
8.0
1.0
1.0
1.0
1.0
1...A...48
1...A...48
1...A...51
1...A...51
16
16
19.5
19.5
50
50
41
35
5
5
620
1

5
5
620
1

5
5
690
1

450 50

5
5
710
1
500 50

428
320
73
22 7

4...16 x 20 x 2

30 5
45 5
Cleanable
1...20 x 25 x 1
1...16 x 25 x 1
Throwaway
4...16 x 20 x 2
4...20 x 20 x 2

4...20 x 20 x 2

*Evaporator coil fins/condenser coil fins.


Requires the accessory/optional Controls Upgrade Kit.
**Weight of 14-in. roof curb.
NOTE: The 50TJ units have a loss-of-charge/low-pressure switch
(accessory/option) located in the liquid line.

Options and accessories


ITEM
Unit-Mounted Disconnect
Durablade Integrated Economizer (Includes Hood)
Manual Outdoor-Air Damper
Controls Upgrade Kit
Condenser Coil Grille
Electric Heat
25% Open Two-Position Damper
100% Open Two-Position Damper
Roof Curbs (Vertical and Horizontal Discharge)
Remote Control Panel
Thermostats and Subbases
Time GuardT II Control Circuit
Thru-the-Bottom Service Connections
Accusensor II Enthalpy Control
Accusensor III Enthalpy Sensor
Condenser Coil Hail Guard Assembly
Fan/Filter Status
Salt Spray Protection Grille

OPTION*
X
X
X**

ACCESSORY
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X

*Factory installed.
Field installed.
**Includes high pressure, loss-of-charge/low pressure, and freeze protection switches.

HAIL GUARD AND CONDENSER COIL


SALT-SPRAY PROTECTION

THERMOSTAT

Zone thermostat (24 v) provides one- or 2-stage cooling for control


of unit. Matching subbases are available with or without tamperproof
switches and automatic changeover.

COIL GUARD GRILLE


Condenser coil hail guard accessory protects coil against damage
from hail and other flying debris.
Condenser coil salt spray protection accessory protects coils from
salt spray induced corrosion in coastal areas, and utilizes a cleanable filter.

Coil guard grille protects coils against large objects and vandalism.

ACCUSENSOR II

SO

TR

REV. B 1 9 8 8 1 8 A

MINIMUM 3
POSITION

OPEN

T1

P1

TR

24VAC

TR1

3 mA MIN. AT 11 VDC

B A

ENTHALPY CONTROL

CWSETPOINTSCCW

RUSH AT 24VAC

CONTACT RATINGS: 1.5A RUN, 3.5A IN

CONTACTS SHOWN IN HIGH ENTHALPY


OR UNPOWERED STATE

OUTDOOR TEMP.

% 90
H
DAMPER
U 70
CLOSED
M
I 60
DAMPER
D
OPEN
I 30
T
Y 10
50 55 60 65 70 75 80 85
REV.

ACCUSENSOR III

Accusensor economizer controls help provide efficient, economical economizer operation. The Accusensor I dry-bulb
sensor measures outdoor temperature and is standard with
the economizer.
The accessory Accusensor II solid-state enthalpy control senses both dry and wet bulb of the outdoor air to provide an accurate enthalpy reading. Accusensor II is available as a field-installed accessory for the economizer.
The accessory Accusensor III differential enthalpy sensor compares outdoor temperature and humidity to returnair temperature and humidity and determines the most
economical mixture of air. Accusensor III is available as a
field-installed accessory for the economizers.

97-3672

TIME GUARD II CONTROL

UNIT MOUNTED DISCONNECT

Time Guard II Control automatically prevents compressor from restarting for at least 5 minutes after a
shutdown. Field-installed accessory prevents short
cycling of compressor if thermostat is rapidly changed.
Time Guard II device mounts in the control compartment of unit.

DURABLADE ECONOMIZER

Factory-installed, internally-mounted, NEC and UL (U.S.A. Standards) approved non-fused switch provides unit power shutoff and
disconnect lockout protection capability. The switch is accessible from
outside the unit.

ELECTRIC HEATER

Electric heaters are available in a wide range of capacities for field


installation.

Exclusive Durablade economizer damper design saves energy while


providing economical and reliable cooling. A sliding plate on the face
of the economizer controls the amount of outdoor air entering the
system. When the sliding plate is closed, it provides a leakproof seal
which prevents ambient air from seeping in or conditioned air from
seeping out. It can be easily adjusted for 100% outdoor air or any
proportion of mixed air.

Base unit dimensions


UNIT
50TJ
008
009
012
014

STD UNIT
WEIGHT
Lb
Kg
755
342
760
345
915
415
930
422

CORNER
WEIGHT (A)
Lb
Kg
164
74
165
75
199
90
202
92

CORNER
WEIGHT (B)
Lb
Kg
140
64
141
64
170
77
172
78

CORNER
WEIGHT (C)
Lb
Kg
208
94
209
94
252
114
256
116

CORNER
WEIGHT (D)
Lb
Kg
243
110
245
111
294
134
300
136

H
Ft-in.
1-278
3-378
2-578
1-278

mm
378
1013
759

Ft-in.
3-5516
3-5516
4-1516

mm
1050
1050
1253

Ft-in.
2-91116
2-91116
3-038

mm
856
856
924

378

4-1516

1253

3-038

924

A
B
C
D
E
F

CONNECTION SIZES
1389 dia [35] field power supply hole
2129 dia [64] power supply knockout
1349 dia [44] charging port hole
789 [22] field control wiring hole
349-14 NPT condensate drain
29 dia [51] power supply knockout

BOTTOM POWER CHART: THESE HOLES


REQUIRED FOR USE WITH ACCESSORY PACKAGES
CRBTMPWR001A00 (12(, 34() OR
CRBTMPWR002A00 (12(, 114()
THREADED
CONDUIT SIZE
12(
34(
114(

WIRE USE
24 v
POWER*
POWER*

REQD HOLE
SIZES (MAX.)
789 [22.2]
1189 [28.4]
1349 [44.4]

*Select either 349 or 1149 for power, depending on wire size.

NOTES:
1. Dimensions in [
2.
3.

] are in millimeters.

Center of gravity.
Direction of airflow.

4. Ductwork to be attached to accessory roof curb only.


5. Minimum clearance (local codes or jurisdiction may prevail):
a. Bottom to combustible surfaces (when not using curb) 0 inches. On horizontal
discharge units with electric heat 1 in. clearance to ductwork for 1 ft.
b. Condenser coil, for proper airflow, 36 in. one side, 12 in. the other. The side
getting the greater clearance is optional.
c. Overhead, 60 in. to assure proper condenser fan operation.
d. Horizontal supply and return end, 0 inches.
6. With the exception of the clearance for the condenser section or combustibles as
stated in Notes 5a, b, and c, a removable fence or barricade requires no
clearance.
7. Units may be installed on combustible floors made from wood or class A, B, or C
roof covering material.
8. The vertical center of gravity is 18-7129 [495] for 008 and 009, 28-09 [610] for 012
and 014 up from the bottom of the base rail. Horizontal center of gravity is shown.

Accessory dimensions
ROOF CURB
A
18-29 [356]
28-09 [610]

ROOF CURB
ACCESSORY
CRRFCURB003A00
CRRFCURB004A00

CONNECTION SIZES
B

D ALT
DRAIN
HOLE

28-87169
[827]

18-1015169
[583]

1349 [45]

POWER
CONNECTION

CONTROL
CONNECTION

CONNECTOR
ACY PKG

9 NPT

CRBTMPWR001A00
(Thru-the-Bottom)
CRBTMPWR002A00
(Thru-the-Bottom)

9 NPT

34

1149 NPT

12

9 NPT

12

NOTES:
1. Roof curb accessory is shipped unassembled.
2. Insulated panels.
3. Dimensions in [ ] are in millimeters.
4. Roof curb: galvanized steel.
5. Attach ductwork to curb (flanges of duct rest on curb).
6. Service clearance 4 ft on each side.
7.

Direction of airflow.

8. Either accessory connector package can be used with


either accessory roof curb.

Selection procedure
(with 50TJ012 example) SI
I Determine cooling and heating requirements at
design conditions.
Given:
Required Cooling Capacity (TC) . . . . . . . . . . . 28 kW
Sensible Heat Capacity (SHC) . . . . . . . . . . . . . 19 kW
Required Heating Capacity . . . . . . . . . . . . . . . . 18 kW
Condenser Entering-Air Temp . . . . . . . . . . . . . . 36 C
Evaporator Entering-Air Temp . . . . . . . . 26.7 C edb,
20 C ewb
Evaporator Air Quantity . . . . . . . . . . . . . . . 1520 L/s
External Static Pressure (ESP) . . . . . . . . . . . . . 300 Pa
Electrical Characteristics (V-Ph-Hz) . . . . . . . 380-3-50
Edb Entering dry bulb
Ewb Entering wet bulb
II Select unit based on required cooling capacity.
Enter the 50TJ012 Cooling Capacities table on page 14
at condenser entering temperature of 36 C, evaporatorair entering at 1520 L/s, 26.7 C db and 20 C wb.
The 50TJ012 unit will provide cooling capacity of
30.1 kW and a sensible heat capacity of 21.2 kW.
For evaporator-air temperature other than 26.7 C edb,
calculate sensible heat capacity correction, as required,
using the formula found in the notes following the Cooling Capacities table on page 15.
NOTE: Unit ratings are gross capacities and do not include the effect of evaporator (indoor) fan motor (IFM)
heat. To calculate net capacities, see Step V.
III Select electric heat:
Heating load required is 18 kW.
Enter the Electric Heating Capacities table (page 25)
for the 50TJ012 at 400-3-50. The 19.3 kW heater at
400 v most closely satisfies the heating required. To
calculate kW at 380 v, use the Multiplication Factors
table on page 25.
19.3 x .902 = 17.4 kW gross capacity

10

IV Determine fan speed and power requirements


at design conditions.
Before entering the Fan Performance tables, calculate
the total static pressure required based on unit components. From the given and the Pressure Drop tables
(page 25), find:
External static pressure
300 Pa
Economizer
9 Pa
Electric Heat
14 Pa
Total static pressure
323 Pa
Enter the Fan Performance table for the 50TJ012
vertical discharge unit on page 20. Find the fan r/s
and kilowatts at 323 Pa and 1520 L/s. Note that the
fan speed is 14.5 r/s and power required is 1.56 kW
(interpolation required). The standard motor will adequately handle the job requirements.
V Determine net capacities.
Capacities are gross and do not include the effect of
evaporator-fan motor heat. Use IFM kW from Fan
Performance table on page 20.
Determine net cooling capacity as follows:
Net capacity = gross capacity 2 IFM kW
= 30.1 kW 2 1.56 kW
= 28.5 kW
Net sensible capacity = 21.2 kW 2 1.56 kW
= 19.6 kW
Determine net heating capacity as follows:
Net capacity = gross capacity 1 IFM heat
= 17.4 kW 1 1.56 kW
= 18.9 kW

Selection procedure
(with 50TJ012 example) English
I Determine cooling and heating requirements at
design conditions.
Given:
Required Cooling Capacity (TC) . . . . . . 96,000 Btuh
Sensible Heat Capacity (SHC) . . . . . . . 70,000 Btuh
Required Heating Capacity . . . . . . . . . . 62,000 Btuh
Condenser Entering-Air Temp . . . . . . . . . . . . . . . 95 F
Evaporator Entering-Air Temp . . . . . . . . . . 80 F edb,
67 F ewb
Evaporator Air Quantity . . . . . . . . . . . . . . . 3200 cfm
External Static Pressure (ESP) . . . . . . . . . 1.10 in. wg
Electrical Characteristics (V-Ph-Hz) . . . . . . . 380-3-50
Edb Entering dry bulb
Ewb Entering wet bulb
II Select unit based on required cooling capacity.
Enter the 50TJ012 Cooling Capacities table on
page 17 condenser entering temperature of 95 F,
evaporator-air entering at 3200 cfm, 80 F db and
67 F wb. The 50TJ012 unit will provide cooling capacity of 102,500 Btuh and a sensible heat capacity
of 76,000 Btuh. For evaporator-air temperature other
than 80 F edb, calculate sensible heat capacity correction, as required, using the formula found in the notes
following the Cooling Capacities table on page 17.
NOTE: Unit ratings are gross capacities and do not include the effect of evaporator-fan motor (IFM) heat. To
calculate net capacities, see Step V.
III Select electric heat:
Heating load required is 62,000 Btuh.
62,000 Btuh
= 18.2 kW of heat required
3413 Btuh/kW
Enter the Electric Heating Capacities table (page 25)
for the 50TJ012 at 400-3-50. The 19.3 kW heater at
400 v most closely satisfies the heating required. To
calculate kW at 380 v, use the Multiplication Factors
table on page 25.
19.3 x .902 = 17.4 kW
19.3 x .902 x 3413 = 59,416 Btuh gross capacity

IV Determine fan speed and power requirements


at design conditions.
Before entering the Fan Performance tables, calculate
the total static pressure required based on unit components. From the given and the Pressure Drop tables
(page 25) find:
External static pressure
1.10 in. wg
Economizer
0.03 in. wg
Electric Heat
0.06 in. wg
Total static pressure
1.19 in. wg
Enter the Fan Performance table for the 50TJ012
vertical discharge unit on page 23. Find the fan rpm
and watts at 1.19 in. wg and 3200 cfm. Note that the
fan speed is 842 rpm and power required is 1423 Watts.
(Interpolation is required.) The standard motor will adequately handle the job requirements.
V Determine net capacities.
Capacities are gross and do not include the effect of
evaporator-fan motor heat. Use IFM Watts from Fan
Performance table on page 23.
Determine net cooling capacity as follows:
Net capacity = gross capacity 2 IFM Watts
= 102,500 Btuh 1423 Watts x 3.413 Btuh
Watts
= 102,500 Btuh 4857 Btuh
= 97,643 Btuh
Net sensible capacity = 76,000 Btuh 2 4857 Btuh
= 71,143 Btuh
Determine net heating capacity as follows:
Net Capacity = gross capacity 1 IFM heat
= 59,416 1 4857
= 64,273 Btuh

11

Performance data
COOLING CAPACITIES SI
50TJ008 (21.5 kW)
Temp (C)
Air Entering
Condenser
(Edb)
20

24

28

32

36

40

44

48

52

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

Air Entering Evaporator L/s/BF


850/0.05
14
19.5
19.4
5.02
19.1
18.9
5.25
18.6
18.4
5.49
18.0
17.8
5.77
17.3
17.2
6.09
16.6
16.6
6.40
15.9
15.9
6.71
15.2
15.2
7.02
14.4
14.4
7.33

16
20.9
18.0
5.16
20.4
17.7
5.38
19.8
17.3
5.61
19.1
16.9
5.88
18.2
16.4
6.18
18.3
15.9
6.48
16.4
15.4
6.77
15.5
14.9
7.05
14.5
14.3
7.33

18
22.5
16.2
5.34
21.9
16.0
5.56
21.3
15.7
5.78
20.6
15.4
6.04
19.63
15.0
6.34
18.7
14.6
6.63
17.7
14.2
6.92
16.7
13.8
7.20
15.6
13.3
7.47

1130/0.075
Air Entering Evaporator Ewb (C)
20
22
14
16
24.3
26.0
21.6
22.3
14.3
12.3
21.4
20.5
5.54
5.72
5.28
5.37
23.7
25.4
21.0
21.7
14.1
12.1
21.0
20.2
5.76
5.96
5.51
5.58
23.0
24.8
20.5
21.1
13.9
11.9
20.5
19.8
5.98
6.19
5.74
5.8
22.2
23.9
19.9
20.3
13.6
11.6
19.8
19.4
6.25
6.47
6.03
6.07
21.3
23.0
18.2
19.4
13.2
11.3
19.1
18.9
6.55
6.77
6.33
6.37
20.3
22.0
18.4
18.6
12.8
10.9
18.4
18.3
6.84
7.07
6.65
6.67
19.4
21.0
17.7
17.7
12.5
10.6
17.7
17.6
7.13
7.36
6.97
6.97
18.3
19.9
16.9
16.9
12.1
10.2
16.9
16.9
7.41
7.64
7.27
7.27
17.3
18.8
16.1
16.1
11.7
9.9
16.1
16.1
7.67
7.91
7.56
7.57

18
23.7
18.5
5.52
23.1
18.3
5.74
22.4
18.0
5.96
21.5
17.7
6.22
20.6
17.3
6.61
19.6
16.9
6.81
18.7
16.4
7.10
17.7
15.8
7.39
16.8
15.2
7.67

20
25.3
16.1
5.70
24.7
15.9
5.92
24.1
15.7
6.15
23.2
15.4
6.43
22.3
15.0
6.73
21.3
14.7
7.02
20.2
14.3
7.30
19.1
13.9
7.57
18.0
13.5
7.85

22
27.0
13.4
5.88
26.4
13.3
6.12
25.9
13.1
6.36
25.0
12.9
6.64
24.0
12.5
6.94
23.0
12.3
7.24
21.9
11.9
7.53
20.7
11.5
7.81
19.6
11.2
8.08

20
26.1
17.7
5.83
25.4
17.5
6.05
24.7
17.3
6.28
23.8
17.0
6.54
22.8
16.6
6.84
21.7
16.3
7.12
20.6
15.9
7.41
19.5
15.5
7.69
18.3
15.1
7.95

22
27.7
14.5
5.99
27.0
14.3
6.22
26.4
14.1
6.46
25.6
13.9
6.74
24.6
13.6
7.05
23.4
13.3
7.34
22.3
13.0
7.64
21.2
12.7
7.92
19.9
12.3
8.18

50TJ008 (21.5 kW) (cont)


Temp (C)
Air Entering
Condenser
(Edb)
20

24

28

32

36

40

44

48

52

12

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

Air Entering Evaporator L/s/BF


1180/0.075
14
21.8
21.8
5.33
21.3
21.2
5.55
20.8
20.7
5.78
20.2
20.2
6.07
19.5
19.4
6.39
18.7
18.7
6.69
17.9
17.9
7.01
17.1
17.1
7.31
16.3
16.3
7.61

16
22.5
20.9
5.41
21.9
20.6
5.62
21.2
20.2
5.84
20.5
19.8
6.11
19.6
19.2
6.41
18.7
18.6
6.70
17.9
17.9
7.01
17.1
17.1
7.31
16.3
16.3
7.61

18
23.9
18.9
5.55
23.3
18.7
5.77
22.5
18.4
5.98
21.7
18.1
6.25
20.7
17.7
6.55
19.8
17.2
6.83
18.8
16.7
7.13
17.9
16.1
7.42
16.9
15.4
7.70

1400/0.095
Air Entering Evaporator Ewb (C)
20
22
14
16
25.5
27.1
22.9
23.1
16.4
13.6
22.8
22.4
5.73
5.91
5.49
5.51
24.9
26.5
22.4
22.5
16.2
13.5
22.3
22.0
5.96
6.14
5.72
5.73
24.2
25.9
21.8
21.9
16.0
13.3
21.8
21.7
6.17
6.38
5.94
5.96
23.4
25.2
21.2
21.2
15.7
13.0
21.2
21.0
6.45
6.66
6.23
6.23
22.4
24.1
20.4
20.4
15.3
12.7
20.4
20.4
6.75
6.96
6.54
6.54
21.3
23.1
19.6
19.6
15.0
12.4
19.6
19.6
7.04
7.26
6.86
6.86
20.3
22.0
18.8
18.8
14.6
12.1
18.8
18.8
7.33
7.55
7.16
7.16
19.2
20.8
17.9
17.9
14.2
11.7
17.9
17.9
7.59
7.83
7.46
7.47
18.0
19.6
17.1
17.1
13.9
11.4
17.1
17.1
7.87
8.1
7.76
7.77

18
24.3
20.5
5.65
23.7
20.2
5.86
23.1
20.0
6.08
22.2
19.5
6.36
20.7
19.0
6.66
20.4
18.4
6.95
19.4
17.8
7.25
18.5
17.2
7.54
17.4
16.5
7.82

COOLING CAPACITIES SI (cont)


50TJ009 (24.3 kW)
Temp (C)
Air Entering
Condenser
(Edb)
20

24

28

32

35

40

44

48

52

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

900/0.05
13
22.7
22.7
5.50
21.9
21.9
5.86
20.8
20.8
6.18
19.7
19.7
6.51
18.8
18.8
6.77
17.3
17.3
7.17
16.4
16.4
7.48
15.3
15.3
7.78
14.1
14.1
8.11

16
25.4
21.8
5.72
24.4
21.3
6.08
23.5
20.9
6.45
22.5
20.4
6.81
21.6
20.0
7.07
20.3
19.3
7.48
19.2
18.8
7.81
18.1
18.1
8.14
17.1
17.1
8.47

19
27.8
18.5
5.93
27.0
18.1
6.32
26.2
17.8
6.70
25.2
17.4
7.08
24.5
17.0
7.36
23.1
16.5
7.80
22.1
16.0
8.15
21.1
15.6
8.50
19.9
15.1
8.85

22
30.2
14.9
6.13
29.4
14.6
6.53
28.6
14.3
6.95
27.8
14.0
7.35
27.1
13.8
7.65
25.7
13.3
8.12
24.6
12.8
8.49
23.6
12.4
8.86
22.5
12.0
9.23

Air Entering Evaporator L/s/BF


1200/0.07
Air Entering Evaporator Ewb (C)
13
16
19
22
24.7
27.1
29.4
31.7
24.7
25.4
20.8
16.3
5.70
5.88
6.07
6.26
23.7
26.1
28.5
30.9
23.7
24.9
20.6
16.1
6.04
6.25
6.47
6.69
22.7
25.2
27.7
30.1
22.7
24.5
20.3
15.8
6.38
6.63
6.88
7.12
21.7
24.2
26.7
29.2
21.7
24.0
19.9
15.5
6.72
6.99
7.26
7.52
20.9
23.4
25.9
28.4
20.9
23.3
19.6
15.2
6.97
7.25
7.53
7.82
19.7
22.1
24.6
27.0
19.7
22.1
19.0
14.7
7.37
7.68
7.98
8.30
19.0
21.2
23.5
25.8
19.0
21.2
18.5
14.4
7.70
8.01
8.34
8.68
18.1
20.2
22.4
24.7
18.1
20.2
18.0
13.9
8.01
8.35
8.69
9.06
17.3
19.2
21.3
23.5
17.3
19.2
17.6
13.6
8.34
8.68
9.04
9.44

1500/0.10
13
25.9
25.9
5.79
24.8
24.8
6.15
23.9
23.9
6.52
23.1
23.1
6.87
22.5
22.5
7.13
21.7
21.7
7.62
21.1
21.1
8.02
20.6
20.6
8.41
20.0
20.0
8.79

16
28.1
28.1
5.97
27.2
27.2
6.36
26.3
26.3
6.74
25.3
25.3
7.11
24.6
24.6
7.40
23.6
23.6
7.86
22.7
22.7
8.24
21.9
21.9
8.62
21.0
21.0
9.00

19
30.4
23.1
6.17
29.5
22.8
6.58
28.7
22.5
6.98
27.7
22.1
7.38
26.9
21.7
7.66
25.5
21.1
8.12
24.4
20.5
8.49
23.3
19.9
8.85
22.2
19.4
9.22

22
32.5
17.8
6.35
31.8
17.5
6.78
31.0
17.1
7.21
30.1
16.8
7.64
29.3
16.6
7.94
27.8
16.1
8.42
26.6
15.7
8.80
25.4
15.3
9.17
24.1
14.9
9.55

LEGEND AND NOTES FOR COOLING CAPACITY TABLES SI


LEGEND
BF
Bypass Factor
Edb Entering Dry Bulb Temperature (C)
Ewb Entering Wet Bulb Temperature (C)
kW Compressor Input (kW)
ldb Leaving Dry Bulb
lwb Leaving Wet Bulb
SHC Sensible Heat Capacity (kW)
TC
Total Capacity (kW)
NOTES:
1. Ratings are gross, and do not account for the effects of the evaporatorfan motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. SHC is based on 26.7 C db temperature of air entering the unit. At any
other temperature, correct the SHC read from the table of cooling capacities as follows:
Corrected SHCkW
= SHC 1 [1.23 x 1023 x (1 2 BF) x (Cdb 2 26.7) x L/s]
Observe the rule of sign. Above 26.7 C, SHC correction will be positive;
add it to SHC. Below 26.7 C, SHC correction will be negative; subtract it
from SHC.

4. Formulas:
Cldb = Cedb 2

SHCkW x 1000
1.23 x L/s

Leaving wet bulb = wet bulb temperature corresponding to enthalpy of air


leaving coil (hlwb).
hlwb = hewb 2

TCkW x 1000
1.20 x L/s

Where hewb is enthalpy of air entering evaporator coil (kJ/kg).

13

Performance data (cont)


COOLING CAPACITIES SI (cont)
50TJ012 (29.2 kW)
Temp (C)
Air Entering
Condenser
(Edb)
20

24

28

32

36

40

44

48

52

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

Air Entering Evaporator L/s/BF


1140/0.08
14
26.6
26.4
6.82
25.8
25.6
7.20
24.7
24.6
7.61
23.6
23.5
8.03
22.4
22.3
8.47
21.1
21.1
8.95
20.0
20.0
9.40
19.1
10.1
9.89
18.3
18.3
10.37

16
28.2
24.8
6.98
27.0
24.2
7.34
25.8
23.5
7.93
24.5
22.7
8.13
23.0
21.8
8.53
21.5
20.9
8.97
20.1
19.9
9.40
19.1
19.1
9.89
18.3
18.3
10.37

18
30.5
22.8
7.17
29.4
22.3
7.54
28.2
21.7
8.11
26.6
21.1
8.31
25.0
20.3
8.73
23.4
19.6
9.15
21.7
18.7
9.60
20.3
17.9
10.06
19.1
17.2
10.52

1520/0.105
Air Entering Evaporator Ewb (C)
20
22
14
16
33.1
34.7
30.5
31.4
20.3
17.3
30.4
29.3
7.35
7.42
7.09
7.17
32.1
33.8
29.6
30.4
19.9
16.8
29.5
28.7
7.73
7.82
7.47
7.53
30.8
32.8
28.5
29.1
19.4
16.4
28.5
27.9
8.32
8.45
8.09
8.12
29.4
31.8
27.3
27.7
18.8
16.1
27.3
27.0
8.53
8.67
8.30
8.32
27.9
30.7
26.1
26.3
18.2
17.8
26.0
26.0
8.96
9.15
8.74
8.74
26.2
29.5
24.7
24.7
17.5
15.3
24.7
24.7
9.40
9.64
9.20
9.20
24.4
27.9
23.1
23.1
16.8
14.8
23.1
23.1
9.86
10.11
9.70
9.71
22.6
26.0
21.5
21.5
16.2
14.2
21.5
21.5
10.32
10.59
10.22
10.22
20.9
24.0
20.0
20.0
15.5
13.5
20.0
20.0
10.77
11.07
10.74
10.74

18
32.7
26.2
7.27
31.8
25.9
7.65
30.7
25.4
8.26
29.4
24.8
8.47
27.9
24.1
8.89
26.4
23.3
9.34
24.4
22.0
9.82
22.4
20.7
10.31
20.4
18.4
10.81

20
34.3
22.2
7.39
33.5
22.2
7.80
32.6
21.9
8.46
31.5
21.6
8.67
30.1
21.2
9.11
28.7
20.7
9.56
26.6
20.0
10.03
24.3
19.1
10.50
21.9
18.1
10.98

22
36.3
18.7
7.60
35.3
18.4
7.99
34.4
18.2
8.64
33.3
17.8
8.85
32.0
17.4
9.30
30.8
17.2
9.80
29.4
16.7
10.29
27.6
16.2
10.79
25.5
15.5
11.28

20
35.3
24.4
7.51
34.4
24.0
7.90
33.3
23.7
8.31
32.2
23.5
8.75
31.0
23.3
9.19
29.7
23.0
9.66
27.7
22.3
10.13
25.5
21.4
10.61
23.0
20.4
11.10

22
37.3
20.2
7.71
36.2
19.7
8.09
35.0
19.5
8.51
34.0
19.2
8.95
32.9
18.9
9.42
31.6
18.6
9.89
30.1
18.2
10.38
28.4
17.8
10.90
26.7
17.4
11.41

50TJ012 (29.2 kW) (cont)


Temp (C)
Air Entering
Condenser
(Edb)
20

24

28

32

36

40

44

48

52

14

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

Air Entering Evaporator L/s/BF


1800/0.125
14
31.5
31.4
7.12
30.8
30.8
7.53
30.0
30.0
7.95
29.1
29.1
8.40
28.1
27.9
8.87
26.5
14.7
9.37
24.8
24.8
9.87
23.0
23.0
10.39
21.3
21.3
10.93

16
31.9
30.6
7.16
31.0
30.1
7.54
30.1
29.6
7.97
29.1
29.0
8.41
28.0
28.0
8.87
26.5
26.5
9.36
24.8
24.8
9.87
23.0
23.0
10.39
21.3
21.3
10.93

18
33.3
27.8
7.30
32.4
27.4
7.68
31.4
27.2
8.11
30.3
26.7
8.54
29.1
26.1
8.89
27.7
25.1
9.46
25.7
23.8
9.96
23.7
22.4
10.45
21.6
21.0
10.95

1880/0.13
Air Entering Evaporator Ewb (C)
20
22
14
16
35.3
37.2
31.7
23.1
24.0
19.9
31.7
31.1
7.50
7.70
7.15
7.18
34.2
36.2
31.0
31.2
23.6
19.6
31.0
30.5
7.88
8.10
7.54
7.57
33.2
35.2
30.3
30.4
23.4
19.3
30.2
30.1
8.30
8.51
7.99
7.99
32.1
34.0
29.4
29.4
23.1
18.9
29.4
29.4
8.73
8.95
8.44
8.44
30.8
32.8
28.3
28.3
22.8
18.5
28.3
28.3
9.17
9.40
8.91
8.91
29.5
31.5
27.0
27.0
22.5
18.3
26.9
27.0
9.64
9.88
9.41
9.40
27.5
30.0
25.2
25.2
21.8
18.0
25.2
25.2
10.12
10.36
9.92
9.92
25.3
28.3
23.4
23.4
20.9
17.5
23.4
23.4
10.59
10.86
10.43
10.43
22.8
26.5
21.6
21.6
19.9
17.0
21.6
21.6
11.07
11.38
10.97
10.97

18
33.5
28.3
7.32
32.5
27.9
7.71
31.6
27.6
8.13
30.5
27.1
8.56
29.3
26.5
9.01
28.0
25.6
9.50
26.1
24.4
9.99
24.0
23.0
10.49
21.8
21.4
10.99

COOLING CAPACITIES SI (cont)


50TJ014 (35.9 kW)
Temp (C)
Air Entering
Condenser
(Edb)
20

24

28

32

35

40

44

48

52

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

1500/0.13
13
34.7
34.7
8.92
32.1
32.1
9.34
29.4
29.4
9.78
26.7
26.7
10.20
24.7
24.7
10.52
21.1
21.1
11.10
20.5
20.5
11.62
20.4
20.4
12.15
20.1
20.1
12.67

16
38.0
33.8
8.99
35.8
32.8
9.46
33.6
31.9
9.94
31.5
30.9
10.42
29.9
29.7
10.80
26.8
26.8
11.40
25.3
25.3
11.93
24.1
24.1
12.45
22.8
22.8
12.98

19
41.4
28.1
9.08
39.6
27.4
9.60
37.9
26.7
10.12
36.2
26.0
10.64
34.9
25.5
11.03
32.3
24.4
11.71
30.2
23.5
12.25
27.9
27.9
12.78
25.8
21.4
13.31

22
44.4
22.0
9.13
43.0
21.6
9.70
41.6
21.1
10.27
40.2
20.7
10.85
39.1
20.3
11.30
37.1
19.7
12.00
35.2
19.1
12.58
33.2
33.2
13.17
31.3
17.8
13.75

Air Entering Evaporator L/s/BF


2000/0.17
Air Entering Evaporator Ewb (C)
13
16
19
22
37.0
40.0
43.2
46.3
37.0
39.9
31.7
24.0
9.00
9.06
9.13
9.22
34.8
38.2
41.6
44.9
34.8
38.2
31.1
23.7
9.47
9.57
9.68
9.80
32.9
36.3
40.0
43.4
32.9
36.3
30.5
23.3
9.95
10.08
10.22
10.39
30.8
34.5
38.3
42.0
30.8
34.5
29.9
22.9
10.40
10.59
10.76
10.96
29.2
33.1
37.0
40.9
29.2
33.1
29.4
22.7
10.77
11.00
11.18
11.40
26.9
30.8
34.7
38.8
26.9
30.8
28.3
22.1
11.42
11.64
11.88
12.13
25.7
28.8
32.2
36.9
25.7
28.8
27.1
21.5
12.05
12.24
12.44
12.73
24.5
26.9
29.6
34.9
24.5
26.9
25.8
21.0
12.68
12.84
13.00
13.33
23.3
24.9
27.0
33.1
23.3
24.9
24.5
20.3
13.34
13.43
13.56
13.93

2500/0.22
13
36.7
36.7
8.85
35.8
35.8
9.40
35.0
35.0
9.98
34.0
34.0
10.53
33.3
33.3
10.95
32.0
32.0
11.73
30.5
30.5
12.35
29.0
29.0
12.96
27.5
27.1
13.56

16
40.1
40.1
8.97
38.9
38.9
9.55
37.8
37.8
10.11
36.7
36.7
10.68
35.8
35.8
11.10
34.1
34.1
11.86
32.0
32.0
12.44
29.9
29.9
13.03
27.8
27.7
13.63

19
43.7
34.2
9.12
42.3
33.7
9.69
40.9
33.3
10.26
39.5
32.8
10.84
38.4
32.4
11.27
36.3
31.6
11.99
33.9
30.4
12.56
31.3
29.1
13.14
28.7
27.7
13.71

22
46.9
25.4
9.26
45.6
25.2
9.85
44.3
25.1
10.43
43.0
24.9
11.03
42.0
24.8
11.50
39.9
24.4
12.23
37.9
23.9
12.82
35.7
23.3
13.41
33.6
22.8
13.99

LEGEND AND NOTES FOR COOLING CAPACITY TABLES SI


LEGEND
BF
Bypass Factor
Edb Entering Dry Bulb Temperature (C)
Ewb Entering Wet Bulb Temperature (C)
kW Compressor Input (kW)
ldb Leaving Dry Bulb
lwb Leaving Wet Bulb
SHC Sensible Heat Capacity (kW)
TC
Total Capacity (kW)
NOTES:
1. Ratings are gross, and do not account for the effects of the evaporatorfan motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. SHC is based on 26.7 C db temperature of air entering the unit. At any
other temperature, correct the SHC read from the table of cooling capacities as follows:
Corrected SHCkW
= SHC 1 [1.23 x 1023 x (1 2 BF) x (Cdb 2 26.7) x L/s]
Observe the rule of sign. Above 26.7 C, SHC correction will be positive;
add it to SHC. Below 26.7 C, SHC correction will be negative; subtract it
from SHC.

4. Formulas:
Cldb = Cedb 2

SHCkW x 1000
1.23 x L/s

Leaving wet bulb = wet bulb temperature corresponding to enthalpy of air


leaving coil (hlwb).
hlwb = hewb 2

TCkW x 1000
1.20 x L/s

Where hewb is enthalpy of air entering evaporator coil (kJ/kg).

15

Performance data (cont)


COOLING CAPACITIES ENGLISH
50TJ008 (6.1 TONS)
Temp (F)
Air Entering
Condenser
(Edb)
75
85
95
105
115
125

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

1950/0.06
62
71.9
56.3
5.47
69.0
59.7
5.77
64.9
57.9
6.32
60.4
55.7
6.59
55.9
53.2
6.99
51.1
50.4
7.37

67
80.1
46.6
5.73
77.1
50.5
6.04
72.7
48.8
6.61
68.1
47.2
6.86
63.4
45.4
7.26
58.4
43.5
7.63

72
88.3
55.1
6.02
85.4
40.6
6.34
80.8
39.1
6.54
76.2
37.5
7.19
71.1
35.9
7.58
65.8
34.1
7.95

62
74.9
62.3
5.60
71.7
66.6
5.90
67.4
64.6
6.45
63.0
62.2
6.71
59.0
59.0
7.13
55.1
55.0
7.54

Air Entering Evaporator Cfm/BF


2400/0.075
2500/0.075
Air Entering Evaporator Ewb (F)
67
72
62
67
83.0
90.9
75.3
83.6
50.5
57.0
63.6
51.2
5.86
6.14
5.64
5.90
79.8
88.2
72.2
80.2
55.6
43.6
68.0
56.6
6.17
6.47
5.93
6.19
75.2
83.5
67.8
75.6
54.0
42.1
65.8
55.1
6.75
6.60
6.48
6.76
70.4
78.6
63.5
70.8
52.4
40.8
63.2
53.4
7.00
7.32
6.74
7.02
65.4
73.2
59.7
65.6
50.6
39.0
59.7
51.6
7.39
7.71
7.17
7.41
60.0
67.7
55.8
60.3
48.6
37.3
55.8
49.8
7.75
8.08
7.58
6.77

3000/0.095
72
91.3
60.4
6.14
88.5
44.1
6.49
83.8
42.7
6.69
78.8
41.3
7.34
73.5
39.6
7.72
57.9
37.9
8.10

62
77.4
69.1
5.74
74.3
73.8
6.05
70.7
70.5
6.60
66.7
66.7
6.90
62.5
62.7
7.34
58.7
58.6
7.75

67
85.2
55.3
6.00
82.0
62.0
6.31
77.1
60.2
6.86
72.0
58.6
7.11
66.8
56.8
7.49
61.3
54.8
7.87

72
92.9
23.7
6.24
90.0
47.0
6.57
85.5
45.9
3.46
80.1
44.1
7.40
75.0
43.0
7.83
69.0
41.3
8.20

50TJ009 (6.9 TONS)


Temp (F)
Air Entering
Condenser
(Edb)
75
85
95
105
115
125

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

1950/0.06
62
88.6
72.7
6.09
81.6
69.5
6.65
76.2
66.9
7.15
71.2
64.4
7.62
66.2
62.0
8.08
65.2
61.3
8.36

67
96.5
61.7
6.29
89.9
59.2
6.90
85.3
57.3
7.42
80.3
55.3
7.91
75.3
53.2
8.40
72.5
51.9
8.70

72
104.4
50.5
6.51
97.8
48.1
7.12
93.5
46.5
7.70
88.3
44.5
8.22
83.2
42.6
8.74
79.9
41.3
9.09

Air Entering Evaporator Cfm/BF


2600/0.08
Air Entering Evaporator Ewb (F)
62
67
72
62
94.3
102.1
109.6
98.0
84.0
69.7
55.0
93.1
6.25
6.46
6.67
6.35
87.1
95.1
103.1
90.7
80.9
67.6
52.9
89.9
6.83
7.07
73.1
6.94
82.1
90.0
98.0
86.2
78.3
65.6
51.2
86.2
7.33
7.58
7.86
7.47
77.4
84.7
92.5
81.9
75.5
63.5
49.5
81.8
7.80
8.09
8.39
7.99
72.7
79.5
87.1
77.6
72.6
61.5
47.7
77.6
8.28
8.58
8.92
8.52
70.3
76.4
83.0
74.9
70.3
60.0
46.0
74.9
8.63
8.92
9.24
8.87

3250/0.10
67
105.7
77.0
6.57
98.3
75.0
7.17
93.1
73.4
7.71
87.6
71.2
8.22
81.9
69.1
8.71
78.5
67.0
9.04

72
112.6
59.1
6.76
105.7
57.0
7.39
100.9
55.7
7.98
95.1
53.9
8.51
89.4
52.0
9.03
85.3
50.3
9.38

LEGEND AND NOTES FOR COOLING CAPACITY TABLES ENGLISH


LEGEND
BF
Bypass Factor
Edb Entering Dry Bulb Temperature (F)
Ewb Entering Wet Bulb Temperature (F)
kW Compressor Motor Power Input
ldb Leaving Dry Bulb
lwb Leaving Wet Bulb
SHC Sensible Heat Capacity (1000 Btuh)
TC
Total Capacity (1000 Btuh)
NOTES:
1. Ratings are gross, and do not account for the effects of the evaporatorfan motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. SHC is based on 80 F db temperature of air entering the unit. At any other
temperature, correct the SHC read from the table of cooling capacities as
follows:
Corrected SHCBtuh
= SHC 1 [1.10 x (1 2 BF) x (Fdb 2 80) x cfm]
Observe the rule of sign. Above 80 F, SHC correction will be positive; add
it to SHC. Below 80 F, SHC correction will be negative; subtract it from
SHC.

16

4. Formulas:
Fldb = Fedb 2

SHCBtuh
1.09 x cfm

Leaving wet bulb = wet bulb temperature corresponding to enthalpy of air


leaving coil (hlwb).
hlwb = hewb 2

TCBtuh
4.50 x cfm

Where hewb is enthalpy of air entering evaporator coil (Btu/lb).

COOLING CAPACITIES ENGLISH (cont)


50TJ012 (8.3 TONS)
Temp (F)
Air Entering
Condenser
(Edb)
75
85
95
105
115
125

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

2500/0.09
62
95.1
77.4
7.39
88.9
79.9
7.91
81.8
76.4
8.64
74.2
72.1
9.06
67.4
67.3
9.71
63.2
63.2
10.37

67
108.3
64.2
7.69
102.3
69.3
8.24
94.7
66.2
8.94
86.4
62.8
9.42
77.2
59.1
10.04
69.2
56.0
10.68

72
116.7
77.2
7.83
112.0
55.1
8.42
107.2
53.8
8.85
101.8
51.8
9.74
94.2
49.5
10.42
84.4
46.0
11.09

62
104.5
87.6
7.55
98.5
93.5
8.08
91.2
89.5
8.77
83.4
83.4
9.26
75.6
75.6
9.97
68.5
68.5
10.69

Air Entering Evaporator Cfm/BF


3200/0.105
3800/0.12
Air Entering Evaporator Ewb (F)
67
72
62
67
112.8
121.4
106.2
114.9
70.1
82.0
101.9
74.6
7.74
8.00
7.5
7.81
108.3
116.9
101.8
110.3
77.7
60.0
100.3
83.4
8.34
8.60
8.10
8.39
102.5
110.9
96.8
104.4
76.0
58.1
96.7
82.1
9.08
8.96
8.8
9.15
95.2
105.3
89.7
98.2
73.4
56.9
89.7
80.5
9.56
9.88
9.4
9.65
83.8
99.0
81.3
87.4
68.9
55.1
81.2
76.3
10.19
10.59
10.1
10.28
71.8
88.8
73.1
75.0
64.3
51.9
73.0
70.9
10.85
11.27
10.9
10.95

4000/0.13
72
124.4
84.7
8.10
119.2
63.7
8.69
113.7
61.4
9.03
107.6
60.8
9.96
100.6
59.0
10.66
92.3
56.9
11.37

62
107.0
95.0
7.56
102.7
102.2
8.15
98.0
98.0
8.91
91.3
91.3
9.48
82.8
82.7
10.19
74.2
74.2
10.93

67
115.8
75.9
7.84
110.8
85.1
8.41
105.0
83.9
9.17
98.7
82.6
9.66
88.4
78.7
10.31
76.0
73.0
10.97

72
124.2
32.4
8.10
119.0
64.4
8.67
114.2
63.2
4.60
108.0
61.7
9.98
101.0
60.1
10.68
93.0
58.4
11.41

50TJ014 (10.2 TONS)


Temp (F)
Air Entering
Condenser
(Edb)
75
85
95
105
115
125

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

3150/0.13
62
125.1
107.5
9.48
115.4
103.1
10.15
105.5
98.9
10.83
94.1
92.7
11.54
86.9
86.8
12.26
79.9
79.9
13.00

67
137.3
90.6
9.60
129.6
87.7
10.33
122.0
84.8
11.06
112.2
81.2
11.83
100.4
76.4
12.55
88.5
71.7
13.29

Air Entering Evaporator Cfm/BF


4200/0.17
Air Entering Evaporator Ewb (F)
72
62
67
72
62
147.5
133.0
143.5
154.1
135.4
71.7
125.8
101.9
78.7
135.4
9.69
9.58
9.67
9.79
9.56
140.9
124.4
135.9
147.3
129.6
69.8
120.8
99.8
77.0
129.6
10.49
10.29
10.43
10.61
10.35
134.4
115.8
128.2
140.4
123.8
67.8
115.7
97.8
75.3
123.8
11.30
11.01
11.20
11.41
11.13
126.9
106.5
118.9
132.4
116.6
65.3
106.5
94.8
73.2
116.5
12.10
11.76
11.98
12.22
11.95
117.9
96.5
105.3
123.7
105.9
62.5
96.5
89.8
70.5
105.9
12.91
12.58
12.74
13.07
12.76
108.8
86.4
91.7
115.0
95.4
59.6
96.3
84.8
67.8
95.4
13.72
13.40
14.49
13.91
13.57

5250/0.22
67
145.9
111.0
9.69
139.0
110.1
10.49
132.0
109.2
11.28
123.2
107.4
12.07
109.9
102.2
12.85
96.7
96.2
13.64

72
156.4
83.8
9.84
150.3
83.0
10.67
144.1
82.2
11.48
136.4
80.4
12.33
126.6
78.3
13.15
116.8
76.0
13.97

LEGEND AND NOTES FOR COOLING CAPACITY TABLES ENGLISH


LEGEND
BF
Bypass Factor
Edb Entering Dry Bulb Temperature (F)
Ewb Entering Wet Bulb Temperature (F)
kW Compressor Motor Power Input
ldb Leaving Dry Bulb
lwb Leaving Wet Bulb
SHC Sensible Heat Capacity (1000 Btuh)
TC
Total Capacity (1000 Btuh)
NOTES:
1. Ratings are gross, and do not account for the effects of the evaporatorfan motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. SHC is based on 80 F db temperature of air entering the unit. At any other
temperature, correct the SHC read from the table of cooling capacities as
follows:
Corrected SHCBtuh
= SHC 1 [1.10 x (1 2 BF) x (Fdb 2 80) x cfm]
Observe the rule of sign. Above 80 F, SHC correction will be positive; add
it to SHC. Below 80 F, SHC correction will be negative; subtract it from
SHC.

4. Formulas:
Fldb = Fedb 2

SHCBtuh
1.09 x cfm

Leaving wet bulb = wet bulb temperature corresponding to enthalpy of air


leaving coil (hlwb).
hlwb = hewb 2

TCBtuh
4.50 x cfm

Where hewb is enthalpy of air entering evaporator coil (Btu/lb).

17

Performance data (cont)


FAN PERFORMANCE (SI) HORIZONTAL DISCHARGE UNITS
50TJ008,009 (21.5 AND 24.3 kW) STANDARD MOTOR (BELT DRIVE)
External Static
Airflow
50
100
150
200
250
(L/s)
R/s
kW
R/s
kW
R/s
kW
R/s
kW
R/s
kW
900
7.1 0.36
8.6 0.45
9.8 0.62 11.1 0.81 12.1 0.95
1000
7.5 0.43
9.0 0.55 10.2 0.73 11.4 0.92 12.4 1.09
1100
7.9 0.50
9.4 0.65 10.6 0.84 11.7 1.03 12.7 1.23
1200
8.3 0.57
9.8 0.75 11.0 0.95 12.0 1.14 13.0 1.37
1300
8.8 0.66 10.2 0.85 11.3 1.06 12.4 1.29 13.3 1.52
1400
9.2 0.76 10.6 0.97 11.7 1.19 12.7 1.45 13.7 1.69
1500
9.7 0.88 11.0 1.10 12.1 1.34 13.0 1.60 14.0 1.88
1600
10.1 1.00 11.3 1.24 12.5 1.52 13.4 1.77 14.3 2.07
LEGEND
BkW Fan Input kW x Motor Efficiency
kW
Kilowatt Input to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.

6.
7.

indicates field-supplied motor and drive required.

3. Factory-shipped drive range is 10.33 to 14.67 r/s. Other r/ss may require
a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors

8.
9.

Pressure (Pa)
300
350
R/s
kW
R/s
kW
13.0 1.23 13.6 1.45
13.3 1.36 13.9 1.59
13.6 1.49 14.4 1.73
13.9 1.62 14.8 1.87
14.2 1.77 15.0 2.04
14.5 1.93 15.3 2.21
14.8 2.14 15.6 2.41
15.2 2.36 15.9 2.63

400
R/s
kW
13.7 1.70
14.1 1.85
14.9 2.00
15.5 2.15
15.8 2.32
16.1 2.50
16.4 2.70

450
R/s
kW
13.9 1.95
14.3 2.11
15.1 2.27
16.0 2.43
16.5 2.60
16.9 2.78

500
R/s
kW
14.2 2.19
14.6 2.35
15.0 2.53
16.4 2.71
17.1 2.88

up to the kW ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See EvaporatorFan Motor Performance table on page 24 for additional information.
Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
To convert kW to bkW:
BkW = kW x Motor Efficiency
Motor Efficiency: .81
Maximum Continuous kW: 2.12
Interpolation is permissible. Do not extrapolate.
Static pressure losses (i.e., economizer, electric heater) must be added
to external static pressure before entering Fan Performance table.

50TJ012 (29.2 kW) STANDARD MOTOR (BELT DRIVE)


Airflow
(L/s)
1200
1250
1300
1400
1500
1600
1700
1800
1900
2000

50
R/s
7.4
7.6
7.6
8.0
8.4
8.8
9.1
9.5
9.9
10.3

100
kW
0.35
0.39
0.56
0.66
0.74
0.85
0.96
1.09
1.24
1.41

R/s
8.7
8.8
8.9
9.3
9.6
10.0
10.3
10.7
11.0
11.4

kW
0.46
0.49
0.67
0.78
0.87
0.96
1.06
1.18
1.31
1.47

150
R/s
9.9
10.0
10.2
10.5
10.7
11.1
11.3
11.7
12.0
12.3

kW
0.58
0.69
0.83
0.91
0.99
1.10
1.22
1.34
1.48
1.64

External Static
250
kW
R/s
kW
0.72 11.9 0.80
0.77 12.0 0.88
0.91 12.1 1.05
1.03 12.4 1.16
1.14 12.7 1.28
1.25 12.9 1.40
1.37 13.2 1.53
1.51 13.5 1.68
1.66 13.8 1.84
1.81 14.1 2.02

200
R/s
11.0
11.1
11.1
11.4
11.8
12.1
12.3
12.6
12.9
13.2

LEGEND
BkW Fan Input kW x Motor Efficiency
kW
Kilowatt Input to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.

7.

indicates field-supplied motor and drive required.

3. Factory-shipped drive range is 11.50 to 15.00 r/s. Other r/ss may require
a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors

18

6.

8.
9.

Pressure (Pa)
300
350
R/s
kW
R/s
kW
12.9 0.86 13.7 0.96
13.0 0.87 13.8 1.02
13.1 1.21 13.9 1.22
13.3 1.30 14.1 1.41
13.5 1.42 14.3 1.57
13.8 1.55 14.5 1.70
14.0 1.69 14.8 1.86
14.3 1.86 15.0 2.03
14.6 2.04 15.3 2.21
14.9 2.21 15.6 2.43

400
R/s
kW
13.8 1.02
13.9 1.08
14.0 0.79
14.6 1.25
15.1 1.67
15.3 1.88
15.5 2.02
15.8 2.21
16.0 2.42
16.3 2.64

450
R/s
kW
14.4 1.08
14.6 1.20
15.0 1.43
15.4 1.64
15.7 1.83
16.0 2.00
16.3 2.23
16.4 2.40
16.7 2.61
17.0 2.86

500
R/s
kW
14.7 1.23
15.0 1.45
15.6 1.64
16.0 1.75
16.4 1.88
16.7 2.09
17.0 2.36
17.2 2.62
17.3 2.82
17.6 3.08

up to the kW ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See EvaporatorFan Motor Performance table on page 24 for additional information.
Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
To convert kW to bkW:
BkW = kW x Motor Efficiency
Motor Efficiency: .83
Maximum Continuous kW: 2.60
Interpolation is permissible. Do not extrapolate.
Static pressure losses (i.e., economizer, electric heater) must be added
to external static pressure before entering Fan Performance table.

FAN PERFORMANCE (SI) HORIZONTAL DISCHARGE UNITS (cont)


50TJ014 (35.9 kW) STANDARD MOTOR (BELT DRIVE)
Airflow
(L/s)
1500
1550
1600
1650
1700
1750
1800
1850
1900
1950
2000
2050
2100
2150
2200
2250
2300
2350

50
R/s
9.0
9.2
9.4
9.7
9.9
10.1
10.4
10.6
10.8
11.1
11.3
11.6
11.9
12.0
12.4
12.6
12.9
13.2

100
kW
0.58
0.62
0.67
0.73
0.79
0.94
1.01
1.07
1.13
1.21
1.29
1.36
1.45
1.54
1.64
1.75
1.85
1.95

R/s
10.2
10.4
10.6
10.8
11.0
11.2
11.4
11.6
11.8
12.0
12.1
12.3
12.5
12.7
12.9
13.1
13.3
13.5

kW
0.73
0.79
0.84
0.89
0.96
1.11
1.17
1.22
1.29
1.35
1.43
1.51
1.58
1.67
1.76
1.85
1.95
2.06

150
R/s
11.3
11.5
11.7
11.9
12.1
12.2
12.4
12.5
12.7
12.9
13.1
13.2
13.4
13.6
13.8
14.0
14.2
14.4

kW
0.88
0.94
1.01
1.08
1.14
1.26
1.33
1.40
1.46
1.55
1.63
1.71
1.81
1.89
1.99
2.08
2.19
2.29

External Static
250
kW
R/s
kW
1.00 13.2 1.21
1.06 13.2 1.24
1.14 13.3 1.28
1.21 13.5 1.35
1.29 13.6 1.44
1.42 13.9 1.56
1.51 14.0 1.64
1.59 14.2 1.72
1.68 14.4 1.81
1.76 14.5 1.91
1.84 14.7 2.01
1.92 14.9 2.12
2.00 15.1 2.23
2.09 15.3 2.34
2.19 15.5 2.45
2.30 15.6 2.56
2.42 15.8 2.65
2.54 16.0 2.77

200
R/s
12.1
12.3
12.5
12.7
12.9
13.0
13.3
13.5
13.7
13.8
14.0
14.1
14.3
14.5
14.6
14.8
15.0
15.2

LEGEND
BkW Fan Input kW x Motor Efficiency
kW
Kilowatt Input to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.

6.
7.

indicates field-supplied motor and drive required.

3. Factory-shipped drive range is 11.83 to 14.83 r/s. Other r/ss may require
a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors

8.
9.

Pressure (Pa)
300
350
R/s
kW
R/s
kW
14.2 1.24 15.1 1.28
14.3 1.29 15.1 1.41
14.4 1.38 15.2 1.54
14.5 1.48 15.3 1.67
14.6 1.64 15.4 1.82
14.7 1.75 15.5 1.94
14.8 1.81 15.6 2.02
15.0 1.89 15.7 2.10
15.1 1.98 15.8 2.19
15.3 2.07 16.0 2.27
15.4 2.17 16.2 2.36
15.6 2.28 16.3 2.47
15.8 2.39 16.5 2.58
15.9 2.51 16.6 2.69
16.1 2.64 16.8 2.82
16.3 2.77 16.9 2.94
16.5 2.91 17.1 3.08
16.7 3.04 17.3 3.23

400
R/s
kW
16.0 1.44
16.0 1.59
16.1 1.73
16.1 1.86
16.2 1.94
16.2 2.12
16.3 2.21
16.5 2.32
16.6 2.40
16.7 2.51
16.8 2.60
17.0 2.70
17.1 2.80
17.3 2.90
17.4 3.02
17.6 3.14
17.7 3.29
17.9 3.44

450
R/s
kW
16.5 1.68
16.6 1.81
16.6 1.94
16.7 2.02
16.8 2.13
16.9 2.29
17.0 2.40
17.2 2.51
17.3 2.60
17.4 2.71
17.5 2.82
17.6 2.93
17.8 3.04
17.9 3.16
18.1 3.28
18.2 3.40
18.4 3.51
18.5 3.65

500
R/s
kW
17.3 1.80
17.3 1.93
17.4 2.06
17.4 2.15
17.5 2.29
17.4 2.44
17.6 2.56
17.8 2.68
18.0 2.80
18.1 2.92
18.2 3.04
18.3 3.15
18.4 3.29
18.6 3.41
18.7 3.55
18.8 3.67
19.0 3.80
19.1 3.92

up to the kW ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See EvaporatorFan Motor Performance table on page 24 for additional information.
Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
To convert kW to bkW:
BkW = kW x Motor Efficiency
Motor Efficiency: .85
Maximum Continuous kW: 3.78
Interpolation is permissible. Do not extrapolate.
Static pressure losses (i.e., economizer, electric heater) must be added
to external static pressure before entering Fan Performance table.

FAN PERFORMANCE (SI) VERTICAL DISCHARGE UNITS


50TJ008,009 (21.5 AND 24.3 kW) STANDARD MOTOR (BELT DRIVE)
External Static
Airflow
50
100
150
200
250
(L/s)
R/s
kW
R/s
kW
R/s
kW
R/s
kW
R/s
kW
900
7.5 0.37
9.3 0.55 10.1 0.66 11.4 0.84 12.3 1.02
1000
8.1 0.47
9.7 0.65 10.6 0.79 11.8 0.98 12.7 1.18
1100
8.7 0.57 10.1 0.75 11.1 0.92 12.2 1.12 13.1 1.34
1200
9.3 0.67 10.5 0.85 11.6 1.05 12.6 1.26 13.5 1.50
1300
9.8 0.80 11.0 0.99 12.1 1.21 13.0 1.43 13.9 1.67
1400
10.4 0.94 11.5 1.13 12.6 1.38 13.5 1.63 14.3 1.87
1500
11.0 1.11 12.0 1.31 13.0 1.58 13.9 1.85 14.7 2.11
1600
11.6 1.29 12.6 1.52 13.5 1.78 14.4 2.08 15.2 2.36
LEGEND
BkW Fan Input kW x Motor Efficiency
kW
Kilowatt Input to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.

6.
7.

indicates field-supplied motor and drive required.

3. Factory-shipped drive range is 10.33 to 14.67 r/s. Other r/ss may require
a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors

8.
9.

Pressure (Pa)
300
350
R/s
kW
R/s
kW
13.4 1.19 14.2 1.43
13.7 1.37 14.5 1.61
14.0 1.55 14.8 1.79
14.3 1.73 15.1 1.97
14.7 1.93 15.5 2.18
15.1 2.13 15.9 2.41
15.5 2.36 16.3 2.64
16.0 2.62 16.7 2.88

400
R/s
kW
15.3 1.86
15.5 1.98
15.7 2.10
15.9 2.22
16.2 2.34
16.6 2.66
17.0 2.91

450
R/s
kW
15.8 2.10
16.1 2.24
16.4 2.38
16.7 2.52
16.9 2.69
17.3 2.92

500
R/s
kW
16.8 2.55
17.0 2.65
17.2 2.75
17.4 2.85
17.6 2.97

up to the kW ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See EvaporatorFan Motor Performance table on page 24 for additional information.
Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
To convert kW to bkW:
BkW = kW x Motor Efficiency
Motor Efficiency: .81
Maximum Continuous kW: 2.12
Interpolation is permissible. Do not extrapolate.
Static pressure losses (i.e., economizer, electric heater) must be added
to external static pressure before entering Fan Performance table.

19

Performance data (cont)


FAN PERFORMANCE (SI) VERTICAL DISCHARGE UNITS (cont)
50TJ012 (29.2 kW) STANDARD MOTOR (BELT DRIVE)
Airflow
(L/s)
1200
1250
1300
1400
1500
1600
1700
1800
1900
2000

50
R/s
7.9
8.2
8.4
8.8
9.2
9.7
10.2
10.6
11.1
11.6

100
kW
0.39
0.42
0.56
0.66
0.74
0.85
0.96
1.09
1.24
1.41

R/s
9.3
9.5
9.6
10.0
10.4
10.8
11.2
11.7
12.1
12.5

kW
0.51
0.55
0.78
0.86
0.95
1.07
1.19
1.34
1.49
1.67

150
R/s
10.4
10.6
10.8
11.1
11.5
11.8
12.2
12.6
13.0
13.4

kW
0.63
0.69
0.88
0.98
1.09
1.22
1.35
1.51
1.67
1.86

External Static
250
kW
R/s
kW
0.75 12.8 0.86
0.80 12.9 1.92
0.96 12.6 1.09
1.10 12.9 1.22
1.23 13.2 1.35
1.37 13.6 1.49
1.51 13.9 1.66
1.67 14.3 1.85
1.86 14.7 2.04
2.05 15.0 2.25

200
R/s
11.4
11.5
11.7
12.0
12.4
12.8
13.1
13.5
13.9
14.3

LEGEND
BkW Fan Input kW x Motor Efficiency
kW
Kilowatt Input to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.

6.
7.

indicates field-supplied motor and drive required.

3. Factory-shipped drive range is 11.50 to 15.00 r/s. Other r/ss may require
a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors

8.
9.

Pressure (Pa)
300
350
R/s
kW
R/s
kW
13.0 0.90 13.9 1.02
13.1 1.02 14.2 1.14
13.3 1.18 14.3 1.34
13.7 1.33 14.5 1.47
14.0 1.49 14.8 1.57
14.4 1.65 15.1 1.79
14.7 1.81 15.4 1.98
15.0 2.01 15.7 2.18
15.4 2.23 16.1 2.40
15.8 2.46 16.5 2.67

400
R/s
kW
14.6 1.13
14.8 1.38
15.1 1.58
15.4 1.67
15.6 1.77
15.8 1.94
16.1 2.13
16.4 2.36
16.8 2.59
17.1 2.86

450
R/s
kW
15.4 1.38
15.6 1.65
15.9 1.81
16.2 1.90
16.4 1.97
16.5 2.09
16.7 2.29
17.1 2.54
17.4 2.80
17.7 3.08

500
R/s
kW
16.3 1.60
16.5 1.83
16.7 2.03
16.8 2.12
17.1 2.21
17.3 2.31
17.4 2.46
17.7 2.71
18.0 2.99

up to the kW ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See EvaporatorFan Motor Performance table on page 24 for additional information.
Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
To convert kW to bkW:
BkW = kW x Motor Efficiency
Motor Efficiency: .83
Maximum Continuous kW: 2.60
Interpolation is permissible. Do not extrapolate.
Static pressure losses (i.e., economizer, electric heater) must be added
to external static pressure before entering Fan Performance table.

50TJ014 (35.9 kW) STANDARD MOTOR (BELT DRIVE)


Airflow
(L/s)
1400
1450
1500
1550
1600
1650
1700
1750
1800
1850
1900
1950
2000
2050
2100
2150
2200
2250
2300
2350

50
R/s
9.2
9.5
9.7
9.9
10.2
10.4
10.7
10.9
11.1
11.4
11.6
11.9
12.1
12.4
12.6
12.8
13.1
13.3
13.6
13.8

100
kW
0.55
0.61
0.66
0.72
0.78
0.85
0.91
1.07
1.12
1.19
1.26
1.34
1.42
1.51
1.60
1.70
1.79
1.91
2.01
2.13

R/s
10.3
10.6
10.8
11.0
11.2
11.5
11.7
11.9
12.1
12.4
12.6
12.8
13.0
13.2
13.5
13.7
13.9
14.2
14.4
14.6

kW
0.72
0.78
0.84
0.89
0.95
1.01
1.08
1.22
1.29
1.36
1.45
1.53
1.62
1.71
1.81
1.92
2.02
2.14
2.26
2.38

150
R/s
11.3
11.5
11.7
11.9
12.1
12.4
12.6
12.8
13.0
13.2
13.4
13.7
13.9
14.1
14.3
14.5
14.7
15.0
15.2
15.4

kW
0.81
0.87
0.91
1.01
1.10
1.20
1.29
1.37
1.45
1.54
1.62
1.71
1.80
1.89
2.00
2.12
2.22
2.34
2.47
2.60

External Static
250
kW
R/s
kW
0.98 13.1 1.08
1.04 13.3 1.18
1.09 13.5 1.27
1.15 13.7 1.34
1.22 13.8 1.41
1.29 14.0 1.48
1.38 14.2 1.55
1.52 14.4 1.67
1.60 14.6 1.75
1.69 14.7 1.84
1.78 14.9 1.93
1.88 15.1 2.03
1.99 15.3 2.15
2.09 15.5 2.26
2.21 15.7 2.39
2.33 15.9 2.51
2.45 16.1 2.64
2.57 16.4 2.77
2.69 16.6 2.92
2.82 16.8 3.07

200
R/s
12.3
12.4
12.6
12.8
13.0
13.2
13.4
13.6
13.8
14.0
14.2
14.4
14.6
14.8
15.0
15.3
15.5
15.7
15.9
16.1

LEGEND
BkW Fan Input kW x Motor Efficiency
kW
Kilowatt Input to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.

7.

indicates field-supplied motor and drive required.

3. Factory-shipped drive range is 11.83 to 14.83 r/s. Other r/ss may require
a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors

20

6.

8.
9.

Pressure (Pa)
300
350
R/s
kW
R/s
kW
14.0 1.22 14.9 1.27
14.2 1.28 15.0 1.35
14.3 1.32 15.1 1.44
14.5 1.46 15.2 1.38
14.6 1.58 15.4 1.71
14.8 1.67 15.5 1.76
15.0 1.76 15.7 1.92
15.1 1.86 15.8 2.02
15.3 1.95 16.0 2.12
15.5 2.03 16.2 2.22
15.6 2.12 16.3 2.33
15.8 2.22 16.5 2.44
16.0 2.32 16.7 2.54
16.2 2.42 16.9 2.64
16.4 2.54 17.0 2.76
16.6 2.68 17.2 2.88
16.8 2.82 17.4 3.01
17.0 2.97 17.6 3.14
17.2 3.12 17.8 3.30
17.4 3.26 18.0 3.47

400
R/s
kW
15.8 1.41
15.9 1.48
16.0 1.55
16.1 1.71
16.2 1.79
16.3 1.89
16.4 2.01
16.5 2.20
16.7 2.29
16.8 2.40
17.0 2.52
17.2 2.64
17.3 2.76
17.5 2.88
17.7 3.01
17.8 3.14
18.0 3.25
18.2 3.39
18.4 3.52
18.6 3.67

450
R/s
kW
16.7 1.47
16.8 1.53
16.9 1.66
17.0 1.79
17.0 1.92
17.1 2.06
17.1 2.18
17.2 2.36
17.3 2.47
17.5 2.59
17.7 2.71
17.8 2.83
18.0 2.96
18.1 3.09
18.3 3.23
18.5 3.36
18.6 3.51
18.8 3.65
19.0 3.80
19.2 3.93

500
R/s
kW
17.4 1.63
17.4 1.78
17.5 1.88
17.5 2.02
17.6 2.15
17.6 2.28
17.7 2.36
17.7 2.51
17.9 2.64
18.1 2.77
18.3 2.90
18.4 3.03
18.6 3.16
17.7 3.30
18.9 3.44
19.1 3.59
19.2 3.75
19.4 3.90
19.5 4.06
19.7 4.22

up to the kW ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See EvaporatorFan Motor Performance table on page 24 for additional information.
Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
To convert kW to bkW:
BkW = kW x Motor Efficiency
Motor Efficiency: .85
Maximum Continuous kW: 3.78
Interpolation is permissible. Do not extrapolate.
Static pressure losses (i.e., economizer, electric heater) must be added
to external static pressure before entering Fan Performance table.

FAN PERFORMANCE (ENGLISH) HORIZONTAL DISCHARGE UNITS


50TJ008,009 (6.1 AND 6.9 TONS) STANDARD MOTOR (BELT DRIVE)
External Static Pressure (in. wg)
Airflow
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
(Cfm)
Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts
1950
429
410 424
538 600
659 671
843 736 1046 778 1252 800 1501
765 1735
2000
435
421 429
553 605
683 675
867 739 1071 783 1282 808 1532
795 1770
2100
447
443 439
584 615
731 683
916 746 1122 794 1343 825 1594
826 1840
2200
459
465 549
615 625
779 691
965 753 1173 805 1404 842 1656
857 1910
2250
465
473 554
630 630
803 695
989 757 1199 810 1439 850 1691
873 1945
2300
471
487 559
646 635
827 699 1014 760 1224 816 1465 859 1718
888 1980
2400
482
524 569
684 645
875 708 1064 768 1284 824 1526 872 1779
909 2050
2500
494
554 581
723 654
924 717 1123 776 1344 832 1587 882 1849
925 2119
2550
501
577 587
747 659
956 722 1156 780 1378 836 1621 887 1884
931 2162
2600
507
592 592
771 663
981 727 1182 784 1404 839 1656 891 1919
936 2197
2700
520
638 604
827 672 1031 737 1250 793 1473 846 1726 898 1997
946 2275
2800
533
684 615
875 683 1081 747 1327 802 1552 855 1805 906 2076
954 2352
2900
546
731 626
932 693 1140 756 1396 813 1630 863 1884 913 2154
961 2436
3000
559
779 637
989 704 1207 765 1473 823 1718 872 1962 921 2240
969 2529
3100
572
835 648 1056 715 1275 775 1543 832 1814 882 2058 930 2335
976 2620
3200
585
883 660 1114 727 1353 785 1321 841 1901 892 2162 939 2428
984 2710
3300
598
940 671 1182 739 1439 795 1691 851 1997 902 2266 948 2529
993 2799
3400
610
998 682 1258 750 1526 806 1779 860 2084 912 2369 958 2637 1002 2902
3500
623 1056 694 1335 761 1613 817 1866 870 2180 921 2479 968 2751

LEGEND
Bhp
Brake Horsepower
Watts Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.

6.
7.

indicates field-supplied motor and drive required.

3. Factory-shipped drive range is 620 to 880 rpm. Other rpms may require a
field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors

8.
9.

1.8
2.0
Rpm Watts Rpm Watts
736 1945
666 2060
759 1988
697 2123
805 2075
760 2250
851 2162
823 2377
863 2206
855 2445
897 2249
887 2504
931 2326
935 2595
955 2394
972 2678
964 2436
986 2718
973 2479
999 2759
987 2554 1019 2839
997 2637 1034 2917
1006 2727

1014 2807

1021 2902

up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See EvaporatorFan Motor Performance table on page 24 for additional information.
Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
To convert Watts to Bhp:
Watts x Motor Efficiency
Bhp =
746
Motor Efficiency: .81
Maximum Continuous Watts: 2120
Interpolation is permissible. Do not extrapolate.
Static pressure losses (i.e., economizer, electric heater) must be added
to external static pressure before entering Fan Performance table.

50TJ012 (8.3 TONS) STANDARD MOTOR (BELT DRIVE)


Airflow
(Cfm)
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200

External Static Pressure (in. wg)


0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts
437
333 517
440 590
566 653
692 712
755 770
827 805
881
811
944
448
369 526
476 597
602 660
746 717
836 778
881 815
926
822
989
460
404 534
512 605
638 668
791 723
908 779
944 825
980
835 1052
471
449 544
557 613
683 675
361 730
971 783 1052 830 1070
843 1150
483
494 553
593 620
728 682
881 738 1034 789 1150 840 1159
860 1195
484
562 560
677 631
810 690
940 747 1081 800 1233 850 1353
879 1233
495
607 570
723 638
851 699
998 755 1140 805 1284 857 1447
896 1473
505
646 579
763 646
899 708 1047 761 1199 812 1344 862 1517
908 1639
516
692 589
810 655
956 717 1106 767 1250 819 1413 867 1578
915 1753
527
739 599
859 664 1006 724 1165 775 1318 827 1482 873 1639
920 1831
537
795 609
907 672 1064 731 1216 784 1387 833 1552 880 1718
926 1901
548
851 619
956 680 1114 738 1275 794 1456 840 1621 888 1805
931 1971
560
916 629 1014 688 1173 747 1344 802 1534 847 1700 895 1884
938 2108
571
981 639 1072 698 1241 756 1422 810 1604 856 1788 901 1971
945 2203
582 1047 649 1140 708 1310 764 1499 816 1674 865 1875 908 2050
953 2300
593 1123 659 1207 717 1387 773 1578 823 1753 875 1962 915 2186
960 2389
605 1207 670 1284 727 1465 781 1648 832 1840 883 2050 924 2291
966 2487
616 1292 680 1361 737 1543 789 1726 841 1927 889 2177 934 2389
972 2587

LEGEND
Bhp
Brake Horsepower
Watts Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.

6.
7.

indicates field-supplied motor and drive required.

3. Factory-shipped drive range is 690 to 900 rpm. Other rpms may require a
field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors

8.
9.

1.8
Rpm Watts
830
998
843 1079
855 1186
868 1303
880 1429
925 1604
935 1709
944 1836
952 1920
963 2005
970 2134
976 2230
981 2309
986 2389
993 2478
1000 2587
1008 2698
1015 2819

2.0
Rpm Watts
883 1240
898 1357
910 1474
924 1546
942 1681
964 1761
975 1811
984 1903
993 2014
1001 2091
1007 2221
1017 2362
1024 2496
1029 2605
1034 2707
1039 2800
1046 2904
1053 3029

up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See EvaporatorFan Motor Performance table on page 24 for additional information.
Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
To convert Watts to Bhp:
Watts x Motor Efficiency
Bhp =
746
Motor Efficiency: .83
Maximum Continuous Watts: 2120
Interpolation is permissible. Do not extrapolate.
Static pressure losses (i.e., economizer, electric heater) must be added
to external static pressure before entering Fan Performance table.

21

Performance data (cont)


FAN PERFORMANCE (ENGLISH) HORIZONTAL DISCHARGE UNITS (cont)
50TJ014 (10.2 TONS) STANDARD MOTOR (BELT DRIVE)
Airflow
(Cfm)
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100

External Static Pressure (in. wg)


0.2
0.4
0.6
0.8
1.0
1.2
1.4
Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts
529
535 605
693 669
834 719
948 775 1158
815 1308
880 1352
541
579 615
746 680
886 729 1009 791 1211
827 1369
889 1448
553
632 626
790 692
948
40
1071 792 1237
832 1413
895 1571
566
685 636
843 702 1018 751 1141
98
1290
845 1510
903 1668
579
737 647
904 713 1080 763 1220
07
1352
856 1589
911 1747
593
790 659
957 722 1141 775 1290 817 1431
867 1624
920 1799
607
947 670 1113 732 1267 782 1423 833 1565
879 1751
927 1940
621 1010 681 1170 742 1332 795 1506 842 1641
889 1819
934 2018
636 1073 693 1226 751 1398 808 1590
51
1725
898 1897
942 2105
650 1137 705 1291 761 1464 819 1674 861 1811
908 1974
950 2193
665 1210 717 1357 772 1548 830 1759 871 1905
917 2070
960 2272
680 1283 728 1431 783 1632 839 1836
83
2009
925 2175
969 2370
696 1365 739 1506 794 1717 848 1914 896 2123
935 2281
979 2468
711 1456 750 1582 805 1811 857 2000 908 2237
945 2387
988 2575
727 1540 762 1666 817 1897 867 2096 919 2343
955 2512
996 2692
742 1641 774 1759 828 1992 877 2193 929 2450
967 2638 1005 2819
758 1742 786 1854 840 2088 888 2307 938 2557
980 2773 1015 2946
773 1845 799 1948 852 2193 899 2423 947 2656
992 2910 1025 3083
789 1958 812 2053 863 2290 910 2548 957 2773 1003 3047 1036 3230
805 2070 826 2166 875 2405 921 2665 966 2891 1014 3184 1049 3396
821 2202 840 2290 887 2521 932 2792 976 3019 1024 3322 1061 3553

LEGEND
Bhp
Brake Horsepower
Watts Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.

indicates field-supplied motor and drive required.

3. Factory-shipped drive range is 710 to 890 rpm. Other rpms may require a
field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors

6.
7.

8.
9.

1.6
Rpm Watts
911 1606
920 1676
929 1755
940 1826
952 1887
965 2010
973 2123
980 2210
987 2307
994 2405
1001 2503
1009 2602
1018 2701
1028 2801
1037 2901
1046 3019
1056 3147
1064 3285
1073 3433
1083 3590
1093 3748

1.8
Rpm Watts
940 1685
951 1747
965 1843
980 1940
989 2054
1000 2150
1013 2290
1022 2396
1030 2503
1037 2602
1045 2710
1051 2828
1058 2937
1066 3047
1074 3166
1084 3276
1093 3396
1103 3516
1112 3655
1121 3804
1129 3962

2.0
Rpm Watts
971 1826
985 1922
999 2027
1010 2133
1021 2229
1035 2308
1046 2432
1058 2557
1068 2683
1077 2801
1085 2919
1092 3037
1100 3157
1106 3285
1113 3414
1121 3544
1129 3674
1137 3795
1147 3925
1157 4055
1166 4204

up to the wattage ratings shown will not result in nuisance tripping or


premature motor failure. Unit warranty will not be affected. See EvaporatorFan Motor Performance table on page 24 for additional information.
Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
To convert Watts to Bhp:
Watts x Motor Efficiency
Bhp =
746
Motor Efficiency: .85
Maximum Continuous Watts: 3775
Interpolation is permissible. Do not extrapolate.
Static pressure losses (i.e., economizer, electric heater) must be added
to external static pressure before entering Fan Performance table.

FAN PERFORMANCE (ENGLISH) VERTICAL DISCHARGE UNITS


50TJ008,009 (6.1 AND 6.9 TONS) STANDARD MOTOR (BELT DRIVE)
External Static Pressure (in. wg)
Airflow
0.2
0.4
0.6
0.8
1.0
1.2
1.4
(Cfm)
Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts
1950
466
429 564
567 623
731 689
894 745 1041 799 1250
861 1616
2000
473
448 571
590 571
755 694
923 750 1079 804 1289
864 1638
2100
488
486 585
637 641
803 705
981 761 1156 814 1368
871 1682
2200
503
524 585
684 653
851 716 1039 772 1233 824 1447
878 1726
2250
511
539 592
708 659
875 722 1072 778 1275 829 1491
884 1744
2300
518
562 599
731 665
899 727 1097 783 1310 834 1526
885 1770
2400
534
607 613
787 677
965 738 1165 794 1378 844 1604
892 1840
2500
549
653 627
835 690 1031 750 1233 805 1456 855 1691
902 1927
2550
557
684 633
867 697 1064 756 1267 811 1499 861 1735
908 1980
2600
565
708 639
891 703 1097 761 1301 816 1543 866 1779
913 2023
2700
581
763 652
948 717 1173 773 1378 827 1621 878 1875
924 2128
2800
597
827 665 1014 713 1250 786 1473 839 1709 889 1971
935 2223
2900
613
891 679 1081 745 1335 799 1560 850 1805 900 2067
946 2335
3000
629
965 694 1156 759 1413 812 1665 862 1901 911 2171
957 2445
3100
646 1039 709 1241 772 1508 825 1761 875 2015 923 2275
968 2554
3200
662 1123 724 1335 785 1595 840 1866 887 2128 934 2386
980 2661
3300
679 1207 740 1430 798 1691 854 1980 900 2240 946 2504
991 2775
3400
696 1301 756 1534 811 1788 868 2093 914 2369 959 2629 1003 2886
3500
712 1396 771 1639 824 1892 881 2206 928 2495 971 2759 1014 3009
LEGEND
Bhp
Brake Horsepower
Watts Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.

7.

indicates field-supplied motor and drive required.

3. Factory-shipped drive range is 620 to 880 rpm. Other rpms may require a
field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors

22

6.

8.
9.

1.6
Rpm Watts
922 1902
924 1928
929 1980
934 2032
937 2058
939 2084
944 2119
949 2188
953 2232
957 2275
967 2377
978 2479
989 2595
1000 2702
1011 2832
1022 2933

1.8
Rpm Watts
759 2219
790 2246
853 2283
916 2326
947 2343
979 2369
987 2428
1002 2495
1003 2521
1004 2554
1010 2637
1019 2735
1030 2847
1040 2956

2.0
Rpm Watts
1004 2640
1007 2652
1013 2677
1019 2702
1022 2710
1025 2727
1039 2791
1041 2831
1045 2854
1050 2878
1056 2925
1061 3002

up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See EvaporatorFan Motor Performance table on page 24 for additional information.
Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
To convert Watts to Bhp:
Watts x Motor Efficiency
Bhp =
746
Motor Efficiency: .81
Maximum Continuous Watts: 2120
Interpolation is permissible. Do not extrapolate.
Static pressure losses (i.e., economizer, electric heater) must be added
to external static pressure before entering Fan Performance table.

FAN PERFORMANCE (ENGLISH) VERTICAL DISCHARGE UNITS (cont)


50TJ012 (8.3 TONS) STANDARD MOTOR (BELT DRIVE)
Airflow
(Cfm)
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200

External Static Pressure (in. wg)


0.2
0.4
0.6
0.8
1.0
1.2
1.4
Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts
471
369 552
494 617
611 679
719 740
818 757
881 765
944
483
404 562
530 627
656 685
773 754
881 765
944 775 1025
495
449 573
575 638
710 694
827 757
944 775 1007 793 1088
508
485 583
620 648
755 704
881 759 1007 791 1070 808 1186
521
530 594
665 659
809 714
944 766 1070 807 1150 823 1339
532
630 605
763 670
891 725 1014 778 1148 825 1275 874 1422
544
677 616
803 680
940 735 1081 787 1216 835 1353 880 1491
557
716 628
859 690
998 746 1148 796 1284 844 1430 888 1569
570
763 639
907 700 1064 757 1216 805 1353 854 1508 897 1648
583
818 651
965 711 1123 767 1284 815 1430 863 1587 907 1744
596
867 663 1031 721 1190 777 1353 826 1517 871 1665 916 1831
609
924 674 1097 732 1267 787 1430 836 1595 880 1753 926 1927
622
989 686 1165 744 1335 797 1508 847 1691 890 1849 934 2015
635 1047 698 1241 755 1413 808 1595 857 1779 901 1945 943 2160
649 1123 713 1318 767 1491 818 1683 867 1866 912 2050 952 2265
662 1190 722 1396 778 1578 829 1779 878 1962 922 2203 962 2371
675 1267 734 1482 790 1674 839 1875 888 2058 933 2309 973 2496
689 1353 746 1569 801 1761 851 1971 898 2212 943 2424 983 2624
LEGEND

Bhp
Brake Horsepower
Watts Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.

6.
7.

indicates field-supplied motor and drive required.

3. Factory-shipped drive range is 690 to 900 rpm. Other rpms may require a
field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors

8.
9.

1.6
Rpm Watts
811 1034
825 1097
848 1240
887 1357
918 1519
926 1613
933 1656
934 1718
940 1853
947 1946
956 2039
966 2134
976 2238
985 2344
994 2451
1003 2560
1011 2679
1021 2810

1.8
Rpm Watts
889 1321
907 1429
929 1528
954 1690
963 1834
974 1920
983 1963
988 1980
989 2031
991 2099
997 2195
1004 2291
1013 2397
1023 2514
1032 2633
1042 2763
1051 2895
1060 3029

2.0
Rpm Watts
946 1645
959 1771
975 1878
987 1959
999 2040
1012 2134
1017 2177
1025 2230
1032 2282
1038 2318
1043 2380
1045 2478
1051 2569
1059 2688
1068 2819
1078 2952
1087 3097
1090 3276

up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See EvaporatorFan Motor Performance table on page 24 for additional information.
Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
To convert Watts to Bhp:
Watts x Motor Efficiency
Bhp =
746
Motor Efficiency: .83
Maximum Continuous Watts: 2120
Interpolation is permissible. Do not extrapolate.
Static pressure losses (i.e., economizer, electric heater) must be added
to external static pressure before entering Fan Performance table.

50TJ014 (10.2 TONS) STANDARD MOTOR (BELT DRIVE)


Airflow
(Cfm)
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100

External Static Pressure (in. wg)


0.2
0.4
0.6
0.8
1.0
1.2
1.4
Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts
570
623 636
799 693
886
748 1044
800 1202
850 1281
901 1360
584
676 649
842 705
948
759 1097
809 1281
858 1352
907 1457
598
728 662
904 717 1027
769 1158
819 1342
867 1483
914 1536
612
781 675
957 729 1115
780 1229
829 1414
876 1589
922 1606
626
873 688 1018 741 1202
792 1299
840 1483
886 1676
930 1773
640
913 702 1080 754 1290
803 1378
851 1553
896 1755
940 1913
654 1065 714 1218 767 1373
815 1514
861 1666
906 1862
950 2027
668 1129 727 1291 780 1456
827 1598
873 1751
916 1948
959 2123
683 1194 741 1365 793 1540
839 1691
884 1836
927 2035
969 2228
697 1267 754 1448 806 1624
851 1785
895 1931
938 2123
979 2334
711 1340 767 1531 819 1708
864 1879
907 2035
949 2219
989 2441
726 1423 780 1624 832 1802
877 1983
919 2149
960 2316 1000 2548
741 1506 794 1717 845 1897
889 2096
931 2263
971 2423 1011 2647
755 1598 808 1819 858 2000
902 2210
943 2387
983 2548 1022 2764
770 1700 821 1923 871 2114
915 2325
955 2512
995 2683 1033 2882
784 1794 835 2027 884 2219
928 2450
968 2638 1006 2828 1044 3010
799 1905 849 2140 897 2343
941 2566
981 2773 1018 2964 1056 3147
814 2009 863 2254 910 2468
954 2692
993 2919 1030 3111 1067 3304
829 2131 877 2378 923 2602
967 2828 1006 3065 1043 3267 1079 3470
843 2246 892 2503 937 2746
980 2964 1019 3221 1055 3424 1091 3637
858 2378 906 2629 950 2891
993 3111 1032 3368 1068 3590 1103 3804
LEGEND

Bhp
Brake Horsepower
Watts Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.

6.
7.

indicates field-supplied motor and drive required.

3. Factory-shipped drive range is 710 to 890 rpm. Other rpms may require a
field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors

8.
9.

1.6
Rpm Watts
950 1474
960 1571
963 1668
968 1764
975 1826
983 1887
991 2202
1001 2299
1010 2405
1020 2521
1029 2638
1039 2764
1049 2882
1059 3010
1070 3138
1081 3258
1092 3387
1103 3525
1114 3674
1126 3822
1137 4009

1.8
Rpm Watts
989 1597
1001 1703
1010 1799
1018 1940
1021 2062
1026 2212
1030 2361
1040 2476
1049 2593
1059 2710
1068 2837
1077 2955
1087 3092
1097 3230
1107 3368
1117 3516
1127 3655
1138 3804
1149 3934
1160 4083
1171 4242

2.0
Rpm Watts
1000 1755
1006 1834
1018 1940
1022 2045
1039 2203
1051 2370
1064 2512
1075 2638
1085 2773
1095 2901
1105 3028
1114 3166
1124 3304
1133 3442
1143 3590
1152 3748
1162 3897
1172 4055
1182 4223
1193 4382
1204 4531

up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See EvaporatorFan Motor Performance table on page 24 for additional information.
Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
To convert Watts to Bhp:
Watts x Motor Efficiency
Bhp =
746
Motor Efficiency: .85
Maximum Continuous Watts: 3775
Interpolation is permissible. Do not extrapolate.
Static pressure losses (i.e., economizer, electric heater) must be added
to external static pressure before entering Fan Performance table.

23

Performance data (cont)


EVAPORATOR-FAN MOTOR PERFORMANCE
UNIT
50TJ

UNIT RATED
VOLTAGE

008
009
012
014

400
400
400
400

MAXIMUM
ACCEPTABLE
CONTINUOUS
BkW*
1.79
1.79
2.16
3.13

LEGEND
Bhp Brake Horsepower
BkW kW x Motor Efficiency

MAXIMUM
ACCEPTABLE
CONTINUOUS
BHP*
2.40
2.40
2.90
4.20

MAXIMUM
ACCEPTABLE
OPERATING
WATTS
2120
2120
2120
3775

MAXIMUM
AMP DRAW
2.7
2.7
2.7
5.7

*Extensive motor and electrical testing on these units ensures that the
full range of the motors can be utilized with confidence. Using your fan
motors up to the ratings shown in this table will not result in nuisance
tripping or premature motor failure. Unit warranty will not be affected.

FAN R/s AT MOTOR PULLEY SETTINGS (SI)


UNIT
50TJ
008,009
012
014

0
14.67
15.00
14.83

14.25
14.58
14.58
12

1
13.83
14.25
14.25

112
13.33
13.92
13.72

MOTOR PULLEY TURNS OPEN


2
212
3
12.92
12.50
12.08
13.58
13.25
12.92
13.67
13.33
13.08

312
11.67
12.58
12.75

4
11.25
12.25
12.50

412
10.83
11.92
12.17

5
10.33
11.50
11.83

4
675
735
750

4 1 2
650
715
730

5
620
690
710

FAN RPM AT MOTOR PULLEY SETTINGS (ENGLISH)


UNIT
50TJ
008,009
012
014

0
880
900
890

855
875
875
12

1
830
855
855

1 1 2
800
835
835

MOTOR PULLEY TURNS OPEN


2
212
3
775
750
725
815
795
775
820
800
785

DURABLADE ECONOMIZER BAROMETRIC


RELIEF DAMPER CHARACTERISTICS

24

312
700
755
765

ACCESSORY/FIOP STATIC PRESSURE DROP (Pa)


RATED
VOLTAGE

L/s

All

1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300

1 HEATER
MODULE
6
8
10
12
14
16
18
19
21
23
25
27
29

2 HEATER
MODULES
10
12
15
17
20
22
25
27
29
32
34
37
39

ECONOMIZER
5
6
7
8
9
10
11
12
13
14
15
16
17

FIOP Factory-Installed Option

ACCESSORY/FIOP STATIC PRESSURE DROP (in. wg)


RATED
VOLTAGE

CFM

All

2200
2500
3000
3500
4000
4500
5000
5500
6000

1 HEATER
MODULE
.02
.03
.05
.07
.08
.10
.12
.14
.16

2 HEATER
MODULES
.03
.05
.07
.09
.12
.14
.16
.19
.21

ECONOMIZER
.02
.02
.03
.04
.05
.06
.07
.08
.09

FIOP Factory-Installed Option

ELECTRIC HEATING CAPACITIES


UNIT
50TJ

UNIT ELECTRICAL
CHARACTERISTICS

008

400-3-50

009

400-3-50

012,
014

400-3-50

*Two heater packages are required to provide


kW indicated.
Available on 012 size units only.
**Available on 014 size units only.

ACCESSORY
kW
9.7
11.5
19.3
22.9
29.0*
9.7
11.5
19.3
22.9
29.0*
9.7
11.5**
19.3
22.9
29.0*
34.7*

PART NO.
CRHEATER-----123A00
120A00
121A00
122A00
121A00, 123A00
123A00
120A00
121A00
122A00
121A00, 123A00
123A00
120A00
121A00
122A00
123A00, 121A00
120A00, 122A00

NOTE: The kW ratings shown above are at 400 v. Use the


Multiplication Factors table below to determine heater capacity for other voltages.

MULTIPLICATION FACTORS
HEATER kW
RATING
(Nominal Voltage)
400

VOLTAGE
DISTRIBUTION
V-3-50
380
415
420

MULTIPLICATION
FACTOR
FOR CAPACITY
0.902
1.076
1.101

MULTIPLICATION
FACTOR
FOR FULL LOAD AMPS
0.949
1.037
1.050

EXAMPLE: 22.9 kW (at 400 v) heater on 380 v


= 22.9 (0.902 mult factor)
= 20.7 kW capacity at 380 v.
NOTE: Nominal volts are as marked on 50TJ base unit dataplate. Voltage distribution is the design power supply at
installation site.

25

Electrical data
UNIT
50TJ

NOMINAL
VOLTAGE
(50 Hz)

VOLTAGE
RANGE
Min

Max

COMPR
(ea)
RLA

LRA

OFM
(ea)

IFM

ELECTRIC HEAT*

POWER SUPPLY

FLA

FLA

Nominal
kW

9.7
11.5
19.3
22.9
29.0

9.7
11.5
19.3
22.9
29.0

9.7
19.3
22.9
29.0
34.7

11.5
19.3
22.9
29.0
34.7

FLA

MCA

MOCP**

13.9
16.5
27.8
33.1
41.8

13.9
16.5
27.8
33.1
41.8

16.5
27.8
33.1
41.8
50.1

16.5
27.8
33.1
41.8
50.1

17.8
20.7
23.9
38.1
44.6
55.5
20.5
20.7
23.9
38.1
44.6
55.5
24.0
24.9
39.1
45.6
56.5
66.9
29.4
29.4
40.8
47.3
52.8
68.6

20
25
25
40
45
60
25
25
25
40
45
60
30
30
40
45
60
70
35
35
45
50
60
70

008

400
(3 phase)

380

420

6.2

37.7

0.6

2.6

009

400
(3 phase)

380

420

7.4

46.0

0.6

2.6

012

400
(3 phase)

380

420

8.6

55.0

0.6

3.4

014

400
(3 phase)

380

420

10.4

72.0

0.6

4.8

LEGEND
CE
The Mark of the European Community
FLA
Full Load Amps
IFM
Indoor (Evaporator) Fan Motor
LRA
Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
OFM
Outdoor (Condenser) Fan Motor
RLA
Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 400 v. If power
distribution voltage to unit varies from rated heater voltage, heater kW
will vary accordingly.
Heaters are field installed only.
**Fuse or circuit breaker.
Fusing in single point box provides the required branch circuit
protection.
NOTES:
1. Unit total kW values are determined under test conditions stated in
European Standard EN60335-2-40.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent
of voltage imbalance.
% Voltage imbalance
max voltage deviation from average voltage
= 100 x
average voltage

26

UNIT
TOTAL
kW
9.5
11.1
12.9
20.8
24.4
30.4
10.3
11.1
12.9
20.8
24.4
30.4
11.2
13.4
21.3
24.9
30.9
36.6
15.9
15.9
21.8
25.2
31.2
36.9

MINIMUM
UNIT
DISCONNECT
FLA
19
19
22
35
41
57
21
21
22
35
41
51
25
25
36
42
52
62
31
31
38
44
54
63

LRA

99

115

133
133
133
133
134
134

190

EXAMPLE: Supply voltage is 400-3-50.


AB = 393 v
BC = 403 v
AC = 396 v
393 + 403 + 396
3
1192
=
3
= 397

Average Voltage =

Determine maximum deviation from average voltage:


(AB) 397 393 = 4 v
(BC) 403 397 = 6 v
(AC) 397 396 = 1 v
Maximum deviation is 6 v.
Determine percent voltage imbalance.
6
% Voltage imbalance = 100 x
397
= 1.5%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more
than 2%, contact your local electric utility company immediately.

Typical piping and wiring


VERTICAL DISCHARGE DUCTING

HORIZONTAL DISCHARGE DUCTING

CONDENSER-FAN
DISCHARGE AIR

EURO-STYLE
CONTROL BOX

FIELD-SUPPLIED
DISCONNECT
PER LOCAL
CODES*

OUTDOORAIR INLET

POWER WIRING

SLAB MOUNT

OPTIONAL FACTORY-INSTALLED
DISCONNECT SWITCH

CONTROL WIRING
COMPRESSOR

*Factory-supplied, internally mounted disconnect available as an option.

27

Typical wiring schematic

LEGEND
AHA
C
CAP
CB
CC
COMP
D
EC
ECON
EPS
ER
FPT
FSS
HPS
HR
IFC
IFM
LPS
LS
LSM
NC
NO
OAT
OFM
PE
PL
R
SAT
SEN
SW1
SW2

Adjustable Heat Anticipator


Contactor
Capacitor
Circuit Breaker
Cooling Compensator
Compressor Motor
Diode
Enthalpy Control
Economizer
Emergency Power Supply
Economizer Relay
Freeze-Up Protection Thermostat
Filter Status Switch
High-Pressure Switch
Heater Relay
Indoor (Evaporator) Fan Contactor
Indoor (Evaporator) Fan Motor
Low-Pressure Switch
Limit Switch
Limit Switch (Manual Reset)
Normally Closed
Normally Open
Outdoor-Air Thermostat
Outdoor (Condenser) Fan Motor
External Protective Conductor Terminal
Plug Assembly
Relay
Supply-Air Thermostat
Sensor
Switch Fully Open
Switch Fully Closed

NOTES:
1. If any of the original wire furnished must be replaced, it must be
replaced with type 90 C wire or its equivalent.
2. Three-phase motors are protected under primary single-phasing
conditions.
3. Thermostat:
HH07AT170,172,174 and P272-2783
Subbase:
HH93AZ176,178 and P272-1882,1883.
4. Set heat anticipator at 1 amp.
5. Use copper conductors only.

28

SW3
SW4
TB
TC
TH
TRAN

Switch Min. Vent Position


Switch Max. Vent Position
Terminal Block
Thermostat Cooling
Thermostat Heating
Transformer
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To Indicate Common Potential Only,
Not to Represent Wiring

29

Controls
Operating sequence
Cooling, units without economizer When thermostat calls for cooling, terminals G and Y1 are energized. The
indoor (evaporator) fan contactor (IFC), and compressor
contactor no. 1 (C1) are energized and evaporator-fan motor, compressor no. 1, and condenser fans start. The
condenser-fan motor runs continuously while unit is cooling. If the thermostat calls for a second stage of cooling by
energizing Y2, compressor contactor no. 2 (C2) is energized and compressor no. 2 starts.
Heating, units without economizer (If Accessory Heater
is Installed) Upon a call for heating through terminal
W1, IFC and heater contactor no. 1 (HC1) are energized.
On units equipped for 2 stages of heat, when additional
heat is needed, HC2 is energized through W2.
Cooling, units with economizer When the outdoorair temperature is above the outdoor-air thermostat (OAT)
setting and the room thermostat calls for cooling, compressor contactor no. 1 is energized to start compressor no. 1
and the condenser-fan motor. The evaporator-fan motor is
energized and the economizer damper moves to the minimum position. Upon a further call for cooling, compressor
contactor no. 2 will be energized, starting compressor
no. 2. After the thermostat is satisfied, the damper moves
to the fully closed position.
When the outdoor-air temperature is below the OAT setting and the thermostat calls for cooling, the economizer
dampers move to the minimum position. If the supply-air
temperature is above 13.9 C (57 F), the damper continues
to open until it reaches the fully open position or until the
supply-air temperature drops below 13.9 C (57 F).

30

When the supply-air temperature falls to between


13.9 C (57 F) and 11.1 C (52 F), the damper will remain at
an intermediate open position. If the supply-air temperature falls below 11.1 C (52 F), the damper will modulate
closed until it reaches the minimum position or until the
supply-air temperature is above 11.1 C (52 F). When the
thermostat is satisfied, the damper will move to the fully
closed position.
If the outdoor air alone cannot satisfy the cooling requirements of the conditioned space, economizer cooling is integrated with mechanical cooling, providing second-stage
cooling. Compressor no. 1 and the condenser fan will be
energized and the position of the economizer damper will
be determined by the supply-air temperature. Compressor
no. 2 is locked out.
When the second stage of cooling is satisfied, the compressor and condenser-fan motor will be deenergized. The
damper position will be determined by the supply-air
temperature.
When the first stage of cooling is satisfied, the damper
will move to fully closed position.
Heating, units with economizer (If Accessory Heater
is Installed) When the room thermostat calls for heat
through terminal W1, the evaporator-fan contactor and
heater contactor no. 1 are energized. On units equipped
for 2 stages of heat, when additional heat is needed, heater
contactor no. 2 is energized through W2. The economizer
damper moves to the minimum position during heating.
When the thermostat is satisfied, the damper moves to the
fully closed position.

Application data
Outdoor installation Units approved for outdoor installation only.
Ductwork Secure vertical discharge ductwork to roof
curb. For horizontal discharge applications, either attach
ductwork to unit, or use field-supplied flanges attached to
the horizontal discharge openings and attach all ductwork
to flanges.
Horizontal discharge To convert from vertical discharge to horizontal discharge:
1. Remove economizer or two-position damper to gain access to return duct opening.
2. Move the horizontal-discharge duct opening covers to
the vertical discharge openings.
3. Rotate economizer or two-position damper 90 degrees.
4. Remove screws along right side of barometric relief
damper and relocate them across top of damper so
damper opens freely at bottom.
5. Install block-off plate over the opening on the access
panel.
Thru-the-bottom service connections Power connections made through the bottom of the unit must utilize
an accessory Carrier roof curb and accessory thru-the-bottom
power connection accessory kit.
Thermostat Use of 2-stage heating and cooling thermostat is recommended for all units. A 2-stage cooling
thermostat is required on units with accessory economizer
to provide integrated cooling.

Heating-to-cooling changeover All units are automatic changeover from heating to cooling when automatic
changeover thermostat and subbase are used.
Airflow Units are draw-thru on cooling and blow-thru
on heating.
Maximum airflow To minimize the possibility of condensate blow-off from evaporator, airflow through units
should not exceed 236 L/s per kW (500 cfm/ton).
Minimum airflow For cooling, minimum airflow is
142 L/s per kW (300 cfm/ton). For units with electric heating, required minimum L/s (cfm) is 1062 (2250) for 50TJ008;
1203 (2550) for 50TJ009; and 1416 (3000) for 50TJ012
and 014.
Minimum ambient cooling operating temperature
The minimum temperature for size 008-014 standard units
is 4 C (25 F).
Internal unit design Due to Carriers internal unit
design (draw-thru over the motor), air path, and specially
designed motors, the full kW horsepower (maximum continuous bkW and bhp) listed in the Physical Data tables and
the notes following each Fan Performance table can be utilized with confidence.
Using Carrier motors with the values listed in the Physical and Fan Performance Data tables will not result in nuisance tripping or premature motor failure. The unit warranty will not be affected.

31

Guide specifications
Packaged Rooftop Cooling Unit with
Electric Heat Option Constant Volume
Application
HVAC Guide Specifications
Size Range: 21.5 to 35.9 kW (6.1 to 10.2 Tons)
Nominal Cooling
Carrier Model Number: 50TJ
Part 1 General
1.01 SYSTEM DESCRIPTION
A. Outdoor rooftop- or slab-mounted, electrically controlled cooling unit with optional heat utilizing a
hermetic compressor for cooling duty and electric
resistance coils for heating duty. Unit shall discharge
supply air vertically or horizontally as shown on contract drawings.
1.02 QUALITY ASSURANCE
A. Unit shall be designed in accordance with European
Standard EN60335-2-40, and shall be tested in accordance with Eurovent standards.
B. Unit shall be rated in accordance with ARI Standards
210/240 or 360 and 270 (U.S.A. Standards).
C. Unit shall be designed to conform to ASHRAE 15,
latest revision. Unit shall be designed in accordance
with UL 1995 (U.S.A. Standards) and shall be certified under Canadian Standards as a total package for
safety requirements.
D. Unit shall be manufactured in a facility registered to
ISO-9002/BS5750, Part 2.
E. Roof curb shall be designed to conform to NRCA
Standards (U.S.A. Standards).
F. Insulation and adhesive shall meet NFPA 90A requirements (U.S.A. Standard) for flame spread and smoke
generation.
G. Unit casing shall be capable of withstanding Federal
Test Method (U.S.A. Standard) Standard No. 141
(Method 6061) 500-hour salt spray test.
1.03 DELIVERY, STORAGE, AND HANDLING
A. Unit(s) shall be stored and handled per manufacturers recommendations.
Part 2 Products
2.01 EQUIPMENT (STANDARD)
A. General:
Factory-assembled, single-piece cooling unit with optional electric heat. Contained within the unit enclosure shall be all factory wiring, piping, controls, refrigerant charge (R-22), and special features required
prior to field start-up.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized steel,
bonderized and coated with a baked enamel finish
on all externally exposed surfaces.
2. Evaporator fan cabinet interior shall be insulated
with a minimum 13-mm (12-in.) thick flexible fiberglass insulation coated on the air side. Aluminum foil-faced fiberglass insulation shall be used
in the furnace compartment.
32

C.

D.

E.

F.

3. Cabinet panels shall be easily removable for


servicing.
4. Holes shall be provided in the base rails for
rigging shackles to facilitate overhead rigging,
and forklift slots shall be provided to facilitate
maneuvering.
5. Unit shall have a factory-installed, sloped condensate drain pan made of a non-corrosive material,
providing a minimum 19-mm (34-in.) connection
with both vertical and horizontal drains and shall
comply with ASHRAE 62 (U.S.A. Standard).
6. Unit shall have factory-installed filter access panel
to provide filter access with tool-less removal.
7. Unit shall have standard thru-the-bottom power
connection capability.
Fans:
1. Indoor blower (evaporator fan) shall be of the beltdriven, double inlet, forward-curved centrifugal
type. Drive shall include an adjustable-pitch motor
pulley.
2. Indoor blower (evaporator fan) shall be made from
steel with a corrosion-resistant finish and shall be
dynamically balanced.
3. Bearings shall be of the sealed, permanently lubricated, ball-bearing type for longer life and lower
maintenance.
4. Condenser fan shall be of the direct-driven propeller type and shall discharge air vertically.
5. Condenser fan shall have aluminum blades riveted
to corrosion-resistant steel spiders and shall be dynamically balanced.
Compressors:
1. Fully hermetic type, internally protected.
2. Factory spring-mounted and internally spring
mounted for vibration isolation.
3. On independent mounting circuits.
4. Shall comply with European Standard EN603352-34.
Coils:
1. Condenser coils shall have aluminum plate fins mechanically bonded to enhanced copper tubes with
all joints brazed.
2. Tube sheet openings shall be belled to prevent tube
wear.
3. Evaporator coil shall be of the full face active
design.
Refrigerant Components:
Refrigerant circuit components shall include:
1. Acutrol feed system.
2. Refrigerant strainer.
3. Service gage connections on suction, discharge,
and liquid lines.

G. Filter Section:
1. Standard filter section shall consist of factoryinstalled, low-velocity, throwaway, 51-mm (2-in.)
thick fiberglass filters of commercially available
sizes.
2. Filter face velocity shall not exceed 1.64 m/s
(320 fpm) at nominal airflows.
3. Filter section shall use only one size filter.
4. Filters shall be accessible through an access panel
with no-tool removal.
H. Controls and Safeties:
1. Unit Controls:
Unit shall be complete with self-contained lowvoltage control circuit.
2. Standard Safeties:
a. Unit shall incorporate compressor overtemperature and overcurrent safety devices to shut
off compressor.
b. Heating section shall be provided with the following minimum protections:
1) High-temperature limit switches.
2) Overcurrent protection.
I. Operating Characteristics:
1. Unit shall be capable of starting and running at
46.1 C (115 F) ambient outdoor temperature,
meeting maximum load criteria of ARI Standard
210/240 or 360 (U.S.A. Standards) at 10%
voltage.
2. Compressor with standard controls shall be capable of operation down to 25 F ambient outdoor
temperature.
J. Electrical Requirements:
All unit power wiring shall enter unit cabinet at a single
factory-predrilled location.
K. Motors:
1. Compressor motors shall be cooled by refrigerant
passing through motor windings and shall have line
break thermal and current overload protection.
2. Indoor blower (evaporator fan) motor shall have
permanently lubricated bearings and inherent
automatic-reset thermal overload protection.
3. Totally-enclosed condenser-fan motor shall have
permanently lubricated bearings and inherent
automatic-reset thermal overload protection.
L. Special Features:
Certain features are not applicable when the features
designated by * are specified. For assistance in amending the specifications, contact your local Carrier Sales
Office.
1. Roof Curbs: (Horizontal and Vertical)
a. Formed galvanized steel with wood nailer strip
and shall be capable of supporting entire unit
weight.
b. Allows for installing and securing ductwork
to curb prior to mounting unit on the curb.

2. Integrated Economizer:
a. Integrated integral-modulating type capable
of simultaneous economizer and compressor
operation.
b. Includes all hardware and controls to provide
cooling with outdoor air.
c. Equipped with low-leakage dampers not to
exceed 3% leakage, at 249 Pa (1 in. wg) pressure differential.
d. Capable of introducing up to 100% outdoor
air in both minimum and fully-open
positions.
e. Equipped with a gravity relief sliding plate
damper. Damper shall close upon unit shutoff.
f. Designed to close damper during loss-ofpower situations with emergency power
supply.
g. Dry bulb outdoor-air thermostat protection
shall be provided as standard.
h. Economizer has a guillotine-style damper.
3. Manual Outdoor-Air Damper:
Manual damper package shall consist of damper,
birdscreen, and rainhood which can be preset to
admit up to 50% outdoor air for year-round
ventilation.
4. 100% Two-Position Damper:
a. Two-position damper package shall include
single blade damper and motor. Admits up
to 100% outdoor air.
b. Damper shall close upon evaporator fan shutoff.
c. Designed to close damper during loss of power
situations.
d. Equipped with barometric relief damper.
5. 25% Two-Position Damper:
a. Two-position damper package shall include
single blade damper and motor. Admits up
to 25% outdoor air.
b. Damper shall close upon evaporator fan
shutoff.
c. Designed to close damper during loss of power
situations.
d. Equipped with barometric relief damper.
6. Solid-State Enthalpy Control:
Capable of sensing outdoor-air enthalpy content
(temperature and humidity) and controlling economizer cut-in point to have minimum heat content
air passing over the evaporator coil for most efficient system operation.
7. Differential Enthalpy Sensor:
a. For use with economizer only.
b. Capable of comparing enthalpy content (temperature and humidity) of outdoor and indoor air and controlling economizer cut-in
point at the most economical level.
33

Guide specifications (cont)


*

34

8. Electric Resistance Heaters:


a. Open wire nichrome elements with all necessary safety operating controls.
b. UL listed (U.S.A. Standard) and indicated on
basic unit informative plate.
c. Available in multiples to match heating
requirements.
9. Remote Control Panel:
Panel shall be a decorative, indoor, wall-mounted
panel consisting of:
a. Two-stage heat/2-stage cool thermostat.
b. Automatic changeover.
c. System switch with HEAT-COOL-AUTO.OFF settings.
d. Fan switch with ON-AUTO. settings.
e. Ventilation control for remote variation of the
amount of outdoor-air intake.
f. Indicator lights for HEAT-COOL-FAN
operation.
g. Three unused indicator lights for field use.
10. Thermostat and Subbase:
Provides staged cooling and heating, automatic
(or manual) changeover, fan control, and indicator light.
11. Thru-The-Bottom Service Connectors:
Kit shall provide connectors to permit electrical
connections to be brought to the unit through
the basepan.

12. Condenser Coil Hail Guard Assembly:


Hail guard shall protect against damage from hail
and flying debris.
13. Controls Upgrade Kit:
Kit shall contain high-pressure, loss-of-charge/
low-pressure, and freeze protection switches. It
shall mount on factory-installed Schrader fittings.
14. Condenser Coil Grille:
The grille protects the condenser coil from damage by large objects without increasing unit
clearances.
15. Compressor Cycle Delay:
Unit shall be prevented from restarting for a minimum of 5 min. after shutdown.
16. Salt Spray Protection Package:
Coil guard protects coil from corrosion in coastal
areas and in areas with high sulfur emissions.
17. Fan/Filter Status Switch:
Provides status of indoor fan (ON/OFF) or filter
(CLEAN/DIRTY). Status shall be displayed with
an indicator light at the thermostat.
18. Unit Mounted Disconnect Switch:
Option shall be a factory-installed, internallymounted, NEC and UL (U.S.A. Standards) approved, non-fused switch providing unit power
shutoff. Switch shall be accessible from outside
the unit.

Carrier Corporation Syracuse, New York 13221

11-95

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 1b 6b

Page 36

Catalog No. 005-044

Printed in U.S.A.

Form 50TJ-C4PD
Replaces: New