50TJ008-014
Single-Package Rooftop Units
Electric Cooling
with Electric Heat Option
50 Hz, CE Units
Nominal Capacity: 21.5 kW to 35.9 kW
(6.1 to 10.2 Tons)
Features/Benefits
Compact, vertical discharge
units convert to horizontal
discharge, combining installation flexibility with efficient performance and easy
maintenance.
Easy installation and
conversion
All units are shipped in the vertical discharge configuration for fit-up to standard
roof curbs. The contractor can order
and install the roof curb early in the construction stage, before decisions on size
requirements are made.
All units feature roll-formed baserail
design with forklift slots on all 3 sides and
rigging holes for easier maneuvering.
Durable packaging protects all units during
shipment and storage.
Form 50TJ-C4PD
Durable, dependable
construction
Designed for durability in any climate, the
weather-resistant cabinets are manufactured using Carrier Weather Armort coating. The cabinet is constructed of
galvanized steel, is bonderized, and all
exterior panels are coated with a
prepainted baked enamel finish. The paint
finish is non-chalking, and is capable
of withstanding Federal (U.S.A.) Test
Method Standard No. 141 (Method 6061)
500-hour salt spray test. All internal
cabinet panels are primed, permitting
longer life and a more attractive appearance for the entire unit. In addition, the
50TJ units are designed with a single,
continuous top piece to eliminate any
possible leaks. Totally-enclosed condenser-fan motors and permanentlylubricated bearings provide additional unit
dependability.
Table of contents
Page
Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1,2
Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4,5
Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6,7
Base Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Accessory Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10,11
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-25
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Typical Piping and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Typical Wiring Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28,29
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32-34
LEGEND
Al
Aluminum
Cu
Copper
FIOP Factory-Installed Option
008
21.5
009
24.3
012
29.2
014
35.9
342
20
65
345
20
65
415
20
65
422
20
65
2
1479 ea
2
1479 ea
2
1479 ea
2
1922 ea
Hermetic
R-22
2.10
2.13
2.54
2.49
4.22
2.54
2.55
3.90
Enhanced Copper Tubes, Aluminum Lanced Fins
1...669
2...669
2...669
2...669
1.90
1.67
1.62
2.30
Propeller Type
2880
2880
3050
3050
2...559
2...559
2...559
2...559
.19...15.5
.19...15.5
.19...15.5
.19...15.5
Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Acutrol Feed Device
3...590
3...590
3...590
4...590
0.74
0.74
0.93
1.03
Centrifugal Type
1...381 x 381
1...381 x 381
1...381 x 381
1...381 x 381
Belt
Belt
Belt
Belt
1230
1420
1700
1980
1.12
1.12
1.50
2.24
1.79
1.79
2.16
3.13
56
56
56
56
10.33-14.67
10.33-14.67
11.50-15.00
11.83-14.83
Ball
Ball
Ball
Ball
26.7
26.7
26.7
26.7
61/86
61/86
86/112
102/127
16
16
16
22
140
140
178
203
25
25
25
25
1...A...1219
1...A...1219
1...A...1295
1...A...1448
406
406
495
495
.83
.83
.67
.58
5
5
10.33
25
Al
Bhp
BkW
Cu
LEGEND
Aluminum
Brake Horsepower
Fan Input Watts x Motor Efficiency
Copper
5
5
11.50
25
3103 345
5
5
11.83
25
3448 345
2951
2206
48 21
152 48
Quantity...Size (mm)
RETURN-AIR FILTERS
Quantity...Size (mm)
5
5
10.33
25
4...406 x 508 x 51
1
7
Cleanable
1...508 x 635 x 25
1...406 x 635 x 25
Throwaway
4...406 x 508 x 51
4...508 x 508 x 51
4...508 x 508 x 51
Al
Bhp
BkW
Cu
LEGEND
Aluminum
Brake Horsepower
Fan Input Watts x Motor Efficiency
Copper
008
6.1
009
6.9
012
8.3
014
10.2
755
44
143
760
44
143
915
44
143
930
44
143
2
50 ea
2
50 ea
2
50 ea
2
65 ea
Hermetic
R-22
4-10
4-11
5-7
5-8
9-5
5-7
5-10
8-7
Enhanced Copper Tubes, Aluminum Lanced Fins
1...17
2...17
2...17
2...17
20.50
18.00
17.42
25.00
Propeller Type
6100
6100
6500
6500
2...22
2...22
2...22
2...22
14...930
14...930
14...930
14...930
Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Acutrol Feed Device
3...15
3...15
3...15
4...15
8.0
8.0
10.0
11.1
Centrifugal Type
1...15 x 15
1...15 x 15
1...15 x 15
1...15 x 15
Belt
Belt
Belt
Belt
2600
2600
3500
4200
112
112
2
3
2.40
2.40
2.90
4.20
56
56
56
56
620-880
620-880
690-900
710-890
Ball
Ball
Ball
Ball
1600
1600
1600
1600
2.4/3.4
2.4/3.4
3.4/4.4
4.0/5.0
5 8
5 8
5 8
7 8
5.5
5.5
7.0
8.0
1.0
1.0
1.0
1.0
1...A...48
1...A...48
1...A...51
1...A...51
16
16
19.5
19.5
50
50
41
35
5
5
620
1
5
5
620
1
5
5
690
1
450 50
5
5
710
1
500 50
428
320
73
22 7
4...16 x 20 x 2
30 5
45 5
Cleanable
1...20 x 25 x 1
1...16 x 25 x 1
Throwaway
4...16 x 20 x 2
4...20 x 20 x 2
4...20 x 20 x 2
OPTION*
X
X
X**
ACCESSORY
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
*Factory installed.
Field installed.
**Includes high pressure, loss-of-charge/low pressure, and freeze protection switches.
THERMOSTAT
Coil guard grille protects coils against large objects and vandalism.
ACCUSENSOR II
SO
TR
REV. B 1 9 8 8 1 8 A
MINIMUM 3
POSITION
OPEN
T1
P1
TR
24VAC
TR1
3 mA MIN. AT 11 VDC
B A
ENTHALPY CONTROL
CWSETPOINTSCCW
RUSH AT 24VAC
OUTDOOR TEMP.
% 90
H
DAMPER
U 70
CLOSED
M
I 60
DAMPER
D
OPEN
I 30
T
Y 10
50 55 60 65 70 75 80 85
REV.
ACCUSENSOR III
Accusensor economizer controls help provide efficient, economical economizer operation. The Accusensor I dry-bulb
sensor measures outdoor temperature and is standard with
the economizer.
The accessory Accusensor II solid-state enthalpy control senses both dry and wet bulb of the outdoor air to provide an accurate enthalpy reading. Accusensor II is available as a field-installed accessory for the economizer.
The accessory Accusensor III differential enthalpy sensor compares outdoor temperature and humidity to returnair temperature and humidity and determines the most
economical mixture of air. Accusensor III is available as a
field-installed accessory for the economizers.
97-3672
Time Guard II Control automatically prevents compressor from restarting for at least 5 minutes after a
shutdown. Field-installed accessory prevents short
cycling of compressor if thermostat is rapidly changed.
Time Guard II device mounts in the control compartment of unit.
DURABLADE ECONOMIZER
Factory-installed, internally-mounted, NEC and UL (U.S.A. Standards) approved non-fused switch provides unit power shutoff and
disconnect lockout protection capability. The switch is accessible from
outside the unit.
ELECTRIC HEATER
STD UNIT
WEIGHT
Lb
Kg
755
342
760
345
915
415
930
422
CORNER
WEIGHT (A)
Lb
Kg
164
74
165
75
199
90
202
92
CORNER
WEIGHT (B)
Lb
Kg
140
64
141
64
170
77
172
78
CORNER
WEIGHT (C)
Lb
Kg
208
94
209
94
252
114
256
116
CORNER
WEIGHT (D)
Lb
Kg
243
110
245
111
294
134
300
136
H
Ft-in.
1-278
3-378
2-578
1-278
mm
378
1013
759
Ft-in.
3-5516
3-5516
4-1516
mm
1050
1050
1253
Ft-in.
2-91116
2-91116
3-038
mm
856
856
924
378
4-1516
1253
3-038
924
A
B
C
D
E
F
CONNECTION SIZES
1389 dia [35] field power supply hole
2129 dia [64] power supply knockout
1349 dia [44] charging port hole
789 [22] field control wiring hole
349-14 NPT condensate drain
29 dia [51] power supply knockout
WIRE USE
24 v
POWER*
POWER*
REQD HOLE
SIZES (MAX.)
789 [22.2]
1189 [28.4]
1349 [44.4]
NOTES:
1. Dimensions in [
2.
3.
] are in millimeters.
Center of gravity.
Direction of airflow.
Accessory dimensions
ROOF CURB
A
18-29 [356]
28-09 [610]
ROOF CURB
ACCESSORY
CRRFCURB003A00
CRRFCURB004A00
CONNECTION SIZES
B
D ALT
DRAIN
HOLE
28-87169
[827]
18-1015169
[583]
1349 [45]
POWER
CONNECTION
CONTROL
CONNECTION
CONNECTOR
ACY PKG
9 NPT
CRBTMPWR001A00
(Thru-the-Bottom)
CRBTMPWR002A00
(Thru-the-Bottom)
9 NPT
34
1149 NPT
12
9 NPT
12
NOTES:
1. Roof curb accessory is shipped unassembled.
2. Insulated panels.
3. Dimensions in [ ] are in millimeters.
4. Roof curb: galvanized steel.
5. Attach ductwork to curb (flanges of duct rest on curb).
6. Service clearance 4 ft on each side.
7.
Direction of airflow.
Selection procedure
(with 50TJ012 example) SI
I Determine cooling and heating requirements at
design conditions.
Given:
Required Cooling Capacity (TC) . . . . . . . . . . . 28 kW
Sensible Heat Capacity (SHC) . . . . . . . . . . . . . 19 kW
Required Heating Capacity . . . . . . . . . . . . . . . . 18 kW
Condenser Entering-Air Temp . . . . . . . . . . . . . . 36 C
Evaporator Entering-Air Temp . . . . . . . . 26.7 C edb,
20 C ewb
Evaporator Air Quantity . . . . . . . . . . . . . . . 1520 L/s
External Static Pressure (ESP) . . . . . . . . . . . . . 300 Pa
Electrical Characteristics (V-Ph-Hz) . . . . . . . 380-3-50
Edb Entering dry bulb
Ewb Entering wet bulb
II Select unit based on required cooling capacity.
Enter the 50TJ012 Cooling Capacities table on page 14
at condenser entering temperature of 36 C, evaporatorair entering at 1520 L/s, 26.7 C db and 20 C wb.
The 50TJ012 unit will provide cooling capacity of
30.1 kW and a sensible heat capacity of 21.2 kW.
For evaporator-air temperature other than 26.7 C edb,
calculate sensible heat capacity correction, as required,
using the formula found in the notes following the Cooling Capacities table on page 15.
NOTE: Unit ratings are gross capacities and do not include the effect of evaporator (indoor) fan motor (IFM)
heat. To calculate net capacities, see Step V.
III Select electric heat:
Heating load required is 18 kW.
Enter the Electric Heating Capacities table (page 25)
for the 50TJ012 at 400-3-50. The 19.3 kW heater at
400 v most closely satisfies the heating required. To
calculate kW at 380 v, use the Multiplication Factors
table on page 25.
19.3 x .902 = 17.4 kW gross capacity
10
Selection procedure
(with 50TJ012 example) English
I Determine cooling and heating requirements at
design conditions.
Given:
Required Cooling Capacity (TC) . . . . . . 96,000 Btuh
Sensible Heat Capacity (SHC) . . . . . . . 70,000 Btuh
Required Heating Capacity . . . . . . . . . . 62,000 Btuh
Condenser Entering-Air Temp . . . . . . . . . . . . . . . 95 F
Evaporator Entering-Air Temp . . . . . . . . . . 80 F edb,
67 F ewb
Evaporator Air Quantity . . . . . . . . . . . . . . . 3200 cfm
External Static Pressure (ESP) . . . . . . . . . 1.10 in. wg
Electrical Characteristics (V-Ph-Hz) . . . . . . . 380-3-50
Edb Entering dry bulb
Ewb Entering wet bulb
II Select unit based on required cooling capacity.
Enter the 50TJ012 Cooling Capacities table on
page 17 condenser entering temperature of 95 F,
evaporator-air entering at 3200 cfm, 80 F db and
67 F wb. The 50TJ012 unit will provide cooling capacity of 102,500 Btuh and a sensible heat capacity
of 76,000 Btuh. For evaporator-air temperature other
than 80 F edb, calculate sensible heat capacity correction, as required, using the formula found in the notes
following the Cooling Capacities table on page 17.
NOTE: Unit ratings are gross capacities and do not include the effect of evaporator-fan motor (IFM) heat. To
calculate net capacities, see Step V.
III Select electric heat:
Heating load required is 62,000 Btuh.
62,000 Btuh
= 18.2 kW of heat required
3413 Btuh/kW
Enter the Electric Heating Capacities table (page 25)
for the 50TJ012 at 400-3-50. The 19.3 kW heater at
400 v most closely satisfies the heating required. To
calculate kW at 380 v, use the Multiplication Factors
table on page 25.
19.3 x .902 = 17.4 kW
19.3 x .902 x 3413 = 59,416 Btuh gross capacity
11
Performance data
COOLING CAPACITIES SI
50TJ008 (21.5 kW)
Temp (C)
Air Entering
Condenser
(Edb)
20
24
28
32
36
40
44
48
52
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
16
20.9
18.0
5.16
20.4
17.7
5.38
19.8
17.3
5.61
19.1
16.9
5.88
18.2
16.4
6.18
18.3
15.9
6.48
16.4
15.4
6.77
15.5
14.9
7.05
14.5
14.3
7.33
18
22.5
16.2
5.34
21.9
16.0
5.56
21.3
15.7
5.78
20.6
15.4
6.04
19.63
15.0
6.34
18.7
14.6
6.63
17.7
14.2
6.92
16.7
13.8
7.20
15.6
13.3
7.47
1130/0.075
Air Entering Evaporator Ewb (C)
20
22
14
16
24.3
26.0
21.6
22.3
14.3
12.3
21.4
20.5
5.54
5.72
5.28
5.37
23.7
25.4
21.0
21.7
14.1
12.1
21.0
20.2
5.76
5.96
5.51
5.58
23.0
24.8
20.5
21.1
13.9
11.9
20.5
19.8
5.98
6.19
5.74
5.8
22.2
23.9
19.9
20.3
13.6
11.6
19.8
19.4
6.25
6.47
6.03
6.07
21.3
23.0
18.2
19.4
13.2
11.3
19.1
18.9
6.55
6.77
6.33
6.37
20.3
22.0
18.4
18.6
12.8
10.9
18.4
18.3
6.84
7.07
6.65
6.67
19.4
21.0
17.7
17.7
12.5
10.6
17.7
17.6
7.13
7.36
6.97
6.97
18.3
19.9
16.9
16.9
12.1
10.2
16.9
16.9
7.41
7.64
7.27
7.27
17.3
18.8
16.1
16.1
11.7
9.9
16.1
16.1
7.67
7.91
7.56
7.57
18
23.7
18.5
5.52
23.1
18.3
5.74
22.4
18.0
5.96
21.5
17.7
6.22
20.6
17.3
6.61
19.6
16.9
6.81
18.7
16.4
7.10
17.7
15.8
7.39
16.8
15.2
7.67
20
25.3
16.1
5.70
24.7
15.9
5.92
24.1
15.7
6.15
23.2
15.4
6.43
22.3
15.0
6.73
21.3
14.7
7.02
20.2
14.3
7.30
19.1
13.9
7.57
18.0
13.5
7.85
22
27.0
13.4
5.88
26.4
13.3
6.12
25.9
13.1
6.36
25.0
12.9
6.64
24.0
12.5
6.94
23.0
12.3
7.24
21.9
11.9
7.53
20.7
11.5
7.81
19.6
11.2
8.08
20
26.1
17.7
5.83
25.4
17.5
6.05
24.7
17.3
6.28
23.8
17.0
6.54
22.8
16.6
6.84
21.7
16.3
7.12
20.6
15.9
7.41
19.5
15.5
7.69
18.3
15.1
7.95
22
27.7
14.5
5.99
27.0
14.3
6.22
26.4
14.1
6.46
25.6
13.9
6.74
24.6
13.6
7.05
23.4
13.3
7.34
22.3
13.0
7.64
21.2
12.7
7.92
19.9
12.3
8.18
24
28
32
36
40
44
48
52
12
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
16
22.5
20.9
5.41
21.9
20.6
5.62
21.2
20.2
5.84
20.5
19.8
6.11
19.6
19.2
6.41
18.7
18.6
6.70
17.9
17.9
7.01
17.1
17.1
7.31
16.3
16.3
7.61
18
23.9
18.9
5.55
23.3
18.7
5.77
22.5
18.4
5.98
21.7
18.1
6.25
20.7
17.7
6.55
19.8
17.2
6.83
18.8
16.7
7.13
17.9
16.1
7.42
16.9
15.4
7.70
1400/0.095
Air Entering Evaporator Ewb (C)
20
22
14
16
25.5
27.1
22.9
23.1
16.4
13.6
22.8
22.4
5.73
5.91
5.49
5.51
24.9
26.5
22.4
22.5
16.2
13.5
22.3
22.0
5.96
6.14
5.72
5.73
24.2
25.9
21.8
21.9
16.0
13.3
21.8
21.7
6.17
6.38
5.94
5.96
23.4
25.2
21.2
21.2
15.7
13.0
21.2
21.0
6.45
6.66
6.23
6.23
22.4
24.1
20.4
20.4
15.3
12.7
20.4
20.4
6.75
6.96
6.54
6.54
21.3
23.1
19.6
19.6
15.0
12.4
19.6
19.6
7.04
7.26
6.86
6.86
20.3
22.0
18.8
18.8
14.6
12.1
18.8
18.8
7.33
7.55
7.16
7.16
19.2
20.8
17.9
17.9
14.2
11.7
17.9
17.9
7.59
7.83
7.46
7.47
18.0
19.6
17.1
17.1
13.9
11.4
17.1
17.1
7.87
8.1
7.76
7.77
18
24.3
20.5
5.65
23.7
20.2
5.86
23.1
20.0
6.08
22.2
19.5
6.36
20.7
19.0
6.66
20.4
18.4
6.95
19.4
17.8
7.25
18.5
17.2
7.54
17.4
16.5
7.82
24
28
32
35
40
44
48
52
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
900/0.05
13
22.7
22.7
5.50
21.9
21.9
5.86
20.8
20.8
6.18
19.7
19.7
6.51
18.8
18.8
6.77
17.3
17.3
7.17
16.4
16.4
7.48
15.3
15.3
7.78
14.1
14.1
8.11
16
25.4
21.8
5.72
24.4
21.3
6.08
23.5
20.9
6.45
22.5
20.4
6.81
21.6
20.0
7.07
20.3
19.3
7.48
19.2
18.8
7.81
18.1
18.1
8.14
17.1
17.1
8.47
19
27.8
18.5
5.93
27.0
18.1
6.32
26.2
17.8
6.70
25.2
17.4
7.08
24.5
17.0
7.36
23.1
16.5
7.80
22.1
16.0
8.15
21.1
15.6
8.50
19.9
15.1
8.85
22
30.2
14.9
6.13
29.4
14.6
6.53
28.6
14.3
6.95
27.8
14.0
7.35
27.1
13.8
7.65
25.7
13.3
8.12
24.6
12.8
8.49
23.6
12.4
8.86
22.5
12.0
9.23
1500/0.10
13
25.9
25.9
5.79
24.8
24.8
6.15
23.9
23.9
6.52
23.1
23.1
6.87
22.5
22.5
7.13
21.7
21.7
7.62
21.1
21.1
8.02
20.6
20.6
8.41
20.0
20.0
8.79
16
28.1
28.1
5.97
27.2
27.2
6.36
26.3
26.3
6.74
25.3
25.3
7.11
24.6
24.6
7.40
23.6
23.6
7.86
22.7
22.7
8.24
21.9
21.9
8.62
21.0
21.0
9.00
19
30.4
23.1
6.17
29.5
22.8
6.58
28.7
22.5
6.98
27.7
22.1
7.38
26.9
21.7
7.66
25.5
21.1
8.12
24.4
20.5
8.49
23.3
19.9
8.85
22.2
19.4
9.22
22
32.5
17.8
6.35
31.8
17.5
6.78
31.0
17.1
7.21
30.1
16.8
7.64
29.3
16.6
7.94
27.8
16.1
8.42
26.6
15.7
8.80
25.4
15.3
9.17
24.1
14.9
9.55
4. Formulas:
Cldb = Cedb 2
SHCkW x 1000
1.23 x L/s
TCkW x 1000
1.20 x L/s
13
24
28
32
36
40
44
48
52
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
16
28.2
24.8
6.98
27.0
24.2
7.34
25.8
23.5
7.93
24.5
22.7
8.13
23.0
21.8
8.53
21.5
20.9
8.97
20.1
19.9
9.40
19.1
19.1
9.89
18.3
18.3
10.37
18
30.5
22.8
7.17
29.4
22.3
7.54
28.2
21.7
8.11
26.6
21.1
8.31
25.0
20.3
8.73
23.4
19.6
9.15
21.7
18.7
9.60
20.3
17.9
10.06
19.1
17.2
10.52
1520/0.105
Air Entering Evaporator Ewb (C)
20
22
14
16
33.1
34.7
30.5
31.4
20.3
17.3
30.4
29.3
7.35
7.42
7.09
7.17
32.1
33.8
29.6
30.4
19.9
16.8
29.5
28.7
7.73
7.82
7.47
7.53
30.8
32.8
28.5
29.1
19.4
16.4
28.5
27.9
8.32
8.45
8.09
8.12
29.4
31.8
27.3
27.7
18.8
16.1
27.3
27.0
8.53
8.67
8.30
8.32
27.9
30.7
26.1
26.3
18.2
17.8
26.0
26.0
8.96
9.15
8.74
8.74
26.2
29.5
24.7
24.7
17.5
15.3
24.7
24.7
9.40
9.64
9.20
9.20
24.4
27.9
23.1
23.1
16.8
14.8
23.1
23.1
9.86
10.11
9.70
9.71
22.6
26.0
21.5
21.5
16.2
14.2
21.5
21.5
10.32
10.59
10.22
10.22
20.9
24.0
20.0
20.0
15.5
13.5
20.0
20.0
10.77
11.07
10.74
10.74
18
32.7
26.2
7.27
31.8
25.9
7.65
30.7
25.4
8.26
29.4
24.8
8.47
27.9
24.1
8.89
26.4
23.3
9.34
24.4
22.0
9.82
22.4
20.7
10.31
20.4
18.4
10.81
20
34.3
22.2
7.39
33.5
22.2
7.80
32.6
21.9
8.46
31.5
21.6
8.67
30.1
21.2
9.11
28.7
20.7
9.56
26.6
20.0
10.03
24.3
19.1
10.50
21.9
18.1
10.98
22
36.3
18.7
7.60
35.3
18.4
7.99
34.4
18.2
8.64
33.3
17.8
8.85
32.0
17.4
9.30
30.8
17.2
9.80
29.4
16.7
10.29
27.6
16.2
10.79
25.5
15.5
11.28
20
35.3
24.4
7.51
34.4
24.0
7.90
33.3
23.7
8.31
32.2
23.5
8.75
31.0
23.3
9.19
29.7
23.0
9.66
27.7
22.3
10.13
25.5
21.4
10.61
23.0
20.4
11.10
22
37.3
20.2
7.71
36.2
19.7
8.09
35.0
19.5
8.51
34.0
19.2
8.95
32.9
18.9
9.42
31.6
18.6
9.89
30.1
18.2
10.38
28.4
17.8
10.90
26.7
17.4
11.41
24
28
32
36
40
44
48
52
14
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
16
31.9
30.6
7.16
31.0
30.1
7.54
30.1
29.6
7.97
29.1
29.0
8.41
28.0
28.0
8.87
26.5
26.5
9.36
24.8
24.8
9.87
23.0
23.0
10.39
21.3
21.3
10.93
18
33.3
27.8
7.30
32.4
27.4
7.68
31.4
27.2
8.11
30.3
26.7
8.54
29.1
26.1
8.89
27.7
25.1
9.46
25.7
23.8
9.96
23.7
22.4
10.45
21.6
21.0
10.95
1880/0.13
Air Entering Evaporator Ewb (C)
20
22
14
16
35.3
37.2
31.7
23.1
24.0
19.9
31.7
31.1
7.50
7.70
7.15
7.18
34.2
36.2
31.0
31.2
23.6
19.6
31.0
30.5
7.88
8.10
7.54
7.57
33.2
35.2
30.3
30.4
23.4
19.3
30.2
30.1
8.30
8.51
7.99
7.99
32.1
34.0
29.4
29.4
23.1
18.9
29.4
29.4
8.73
8.95
8.44
8.44
30.8
32.8
28.3
28.3
22.8
18.5
28.3
28.3
9.17
9.40
8.91
8.91
29.5
31.5
27.0
27.0
22.5
18.3
26.9
27.0
9.64
9.88
9.41
9.40
27.5
30.0
25.2
25.2
21.8
18.0
25.2
25.2
10.12
10.36
9.92
9.92
25.3
28.3
23.4
23.4
20.9
17.5
23.4
23.4
10.59
10.86
10.43
10.43
22.8
26.5
21.6
21.6
19.9
17.0
21.6
21.6
11.07
11.38
10.97
10.97
18
33.5
28.3
7.32
32.5
27.9
7.71
31.6
27.6
8.13
30.5
27.1
8.56
29.3
26.5
9.01
28.0
25.6
9.50
26.1
24.4
9.99
24.0
23.0
10.49
21.8
21.4
10.99
24
28
32
35
40
44
48
52
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
1500/0.13
13
34.7
34.7
8.92
32.1
32.1
9.34
29.4
29.4
9.78
26.7
26.7
10.20
24.7
24.7
10.52
21.1
21.1
11.10
20.5
20.5
11.62
20.4
20.4
12.15
20.1
20.1
12.67
16
38.0
33.8
8.99
35.8
32.8
9.46
33.6
31.9
9.94
31.5
30.9
10.42
29.9
29.7
10.80
26.8
26.8
11.40
25.3
25.3
11.93
24.1
24.1
12.45
22.8
22.8
12.98
19
41.4
28.1
9.08
39.6
27.4
9.60
37.9
26.7
10.12
36.2
26.0
10.64
34.9
25.5
11.03
32.3
24.4
11.71
30.2
23.5
12.25
27.9
27.9
12.78
25.8
21.4
13.31
22
44.4
22.0
9.13
43.0
21.6
9.70
41.6
21.1
10.27
40.2
20.7
10.85
39.1
20.3
11.30
37.1
19.7
12.00
35.2
19.1
12.58
33.2
33.2
13.17
31.3
17.8
13.75
2500/0.22
13
36.7
36.7
8.85
35.8
35.8
9.40
35.0
35.0
9.98
34.0
34.0
10.53
33.3
33.3
10.95
32.0
32.0
11.73
30.5
30.5
12.35
29.0
29.0
12.96
27.5
27.1
13.56
16
40.1
40.1
8.97
38.9
38.9
9.55
37.8
37.8
10.11
36.7
36.7
10.68
35.8
35.8
11.10
34.1
34.1
11.86
32.0
32.0
12.44
29.9
29.9
13.03
27.8
27.7
13.63
19
43.7
34.2
9.12
42.3
33.7
9.69
40.9
33.3
10.26
39.5
32.8
10.84
38.4
32.4
11.27
36.3
31.6
11.99
33.9
30.4
12.56
31.3
29.1
13.14
28.7
27.7
13.71
22
46.9
25.4
9.26
45.6
25.2
9.85
44.3
25.1
10.43
43.0
24.9
11.03
42.0
24.8
11.50
39.9
24.4
12.23
37.9
23.9
12.82
35.7
23.3
13.41
33.6
22.8
13.99
4. Formulas:
Cldb = Cedb 2
SHCkW x 1000
1.23 x L/s
TCkW x 1000
1.20 x L/s
15
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
1950/0.06
62
71.9
56.3
5.47
69.0
59.7
5.77
64.9
57.9
6.32
60.4
55.7
6.59
55.9
53.2
6.99
51.1
50.4
7.37
67
80.1
46.6
5.73
77.1
50.5
6.04
72.7
48.8
6.61
68.1
47.2
6.86
63.4
45.4
7.26
58.4
43.5
7.63
72
88.3
55.1
6.02
85.4
40.6
6.34
80.8
39.1
6.54
76.2
37.5
7.19
71.1
35.9
7.58
65.8
34.1
7.95
62
74.9
62.3
5.60
71.7
66.6
5.90
67.4
64.6
6.45
63.0
62.2
6.71
59.0
59.0
7.13
55.1
55.0
7.54
3000/0.095
72
91.3
60.4
6.14
88.5
44.1
6.49
83.8
42.7
6.69
78.8
41.3
7.34
73.5
39.6
7.72
57.9
37.9
8.10
62
77.4
69.1
5.74
74.3
73.8
6.05
70.7
70.5
6.60
66.7
66.7
6.90
62.5
62.7
7.34
58.7
58.6
7.75
67
85.2
55.3
6.00
82.0
62.0
6.31
77.1
60.2
6.86
72.0
58.6
7.11
66.8
56.8
7.49
61.3
54.8
7.87
72
92.9
23.7
6.24
90.0
47.0
6.57
85.5
45.9
3.46
80.1
44.1
7.40
75.0
43.0
7.83
69.0
41.3
8.20
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
1950/0.06
62
88.6
72.7
6.09
81.6
69.5
6.65
76.2
66.9
7.15
71.2
64.4
7.62
66.2
62.0
8.08
65.2
61.3
8.36
67
96.5
61.7
6.29
89.9
59.2
6.90
85.3
57.3
7.42
80.3
55.3
7.91
75.3
53.2
8.40
72.5
51.9
8.70
72
104.4
50.5
6.51
97.8
48.1
7.12
93.5
46.5
7.70
88.3
44.5
8.22
83.2
42.6
8.74
79.9
41.3
9.09
3250/0.10
67
105.7
77.0
6.57
98.3
75.0
7.17
93.1
73.4
7.71
87.6
71.2
8.22
81.9
69.1
8.71
78.5
67.0
9.04
72
112.6
59.1
6.76
105.7
57.0
7.39
100.9
55.7
7.98
95.1
53.9
8.51
89.4
52.0
9.03
85.3
50.3
9.38
16
4. Formulas:
Fldb = Fedb 2
SHCBtuh
1.09 x cfm
TCBtuh
4.50 x cfm
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
2500/0.09
62
95.1
77.4
7.39
88.9
79.9
7.91
81.8
76.4
8.64
74.2
72.1
9.06
67.4
67.3
9.71
63.2
63.2
10.37
67
108.3
64.2
7.69
102.3
69.3
8.24
94.7
66.2
8.94
86.4
62.8
9.42
77.2
59.1
10.04
69.2
56.0
10.68
72
116.7
77.2
7.83
112.0
55.1
8.42
107.2
53.8
8.85
101.8
51.8
9.74
94.2
49.5
10.42
84.4
46.0
11.09
62
104.5
87.6
7.55
98.5
93.5
8.08
91.2
89.5
8.77
83.4
83.4
9.26
75.6
75.6
9.97
68.5
68.5
10.69
4000/0.13
72
124.4
84.7
8.10
119.2
63.7
8.69
113.7
61.4
9.03
107.6
60.8
9.96
100.6
59.0
10.66
92.3
56.9
11.37
62
107.0
95.0
7.56
102.7
102.2
8.15
98.0
98.0
8.91
91.3
91.3
9.48
82.8
82.7
10.19
74.2
74.2
10.93
67
115.8
75.9
7.84
110.8
85.1
8.41
105.0
83.9
9.17
98.7
82.6
9.66
88.4
78.7
10.31
76.0
73.0
10.97
72
124.2
32.4
8.10
119.0
64.4
8.67
114.2
63.2
4.60
108.0
61.7
9.98
101.0
60.1
10.68
93.0
58.4
11.41
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
3150/0.13
62
125.1
107.5
9.48
115.4
103.1
10.15
105.5
98.9
10.83
94.1
92.7
11.54
86.9
86.8
12.26
79.9
79.9
13.00
67
137.3
90.6
9.60
129.6
87.7
10.33
122.0
84.8
11.06
112.2
81.2
11.83
100.4
76.4
12.55
88.5
71.7
13.29
5250/0.22
67
145.9
111.0
9.69
139.0
110.1
10.49
132.0
109.2
11.28
123.2
107.4
12.07
109.9
102.2
12.85
96.7
96.2
13.64
72
156.4
83.8
9.84
150.3
83.0
10.67
144.1
82.2
11.48
136.4
80.4
12.33
126.6
78.3
13.15
116.8
76.0
13.97
4. Formulas:
Fldb = Fedb 2
SHCBtuh
1.09 x cfm
TCBtuh
4.50 x cfm
17
6.
7.
3. Factory-shipped drive range is 10.33 to 14.67 r/s. Other r/ss may require
a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors
8.
9.
Pressure (Pa)
300
350
R/s
kW
R/s
kW
13.0 1.23 13.6 1.45
13.3 1.36 13.9 1.59
13.6 1.49 14.4 1.73
13.9 1.62 14.8 1.87
14.2 1.77 15.0 2.04
14.5 1.93 15.3 2.21
14.8 2.14 15.6 2.41
15.2 2.36 15.9 2.63
400
R/s
kW
13.7 1.70
14.1 1.85
14.9 2.00
15.5 2.15
15.8 2.32
16.1 2.50
16.4 2.70
450
R/s
kW
13.9 1.95
14.3 2.11
15.1 2.27
16.0 2.43
16.5 2.60
16.9 2.78
500
R/s
kW
14.2 2.19
14.6 2.35
15.0 2.53
16.4 2.71
17.1 2.88
up to the kW ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See EvaporatorFan Motor Performance table on page 24 for additional information.
Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
To convert kW to bkW:
BkW = kW x Motor Efficiency
Motor Efficiency: .81
Maximum Continuous kW: 2.12
Interpolation is permissible. Do not extrapolate.
Static pressure losses (i.e., economizer, electric heater) must be added
to external static pressure before entering Fan Performance table.
50
R/s
7.4
7.6
7.6
8.0
8.4
8.8
9.1
9.5
9.9
10.3
100
kW
0.35
0.39
0.56
0.66
0.74
0.85
0.96
1.09
1.24
1.41
R/s
8.7
8.8
8.9
9.3
9.6
10.0
10.3
10.7
11.0
11.4
kW
0.46
0.49
0.67
0.78
0.87
0.96
1.06
1.18
1.31
1.47
150
R/s
9.9
10.0
10.2
10.5
10.7
11.1
11.3
11.7
12.0
12.3
kW
0.58
0.69
0.83
0.91
0.99
1.10
1.22
1.34
1.48
1.64
External Static
250
kW
R/s
kW
0.72 11.9 0.80
0.77 12.0 0.88
0.91 12.1 1.05
1.03 12.4 1.16
1.14 12.7 1.28
1.25 12.9 1.40
1.37 13.2 1.53
1.51 13.5 1.68
1.66 13.8 1.84
1.81 14.1 2.02
200
R/s
11.0
11.1
11.1
11.4
11.8
12.1
12.3
12.6
12.9
13.2
LEGEND
BkW Fan Input kW x Motor Efficiency
kW
Kilowatt Input to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.
7.
3. Factory-shipped drive range is 11.50 to 15.00 r/s. Other r/ss may require
a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors
18
6.
8.
9.
Pressure (Pa)
300
350
R/s
kW
R/s
kW
12.9 0.86 13.7 0.96
13.0 0.87 13.8 1.02
13.1 1.21 13.9 1.22
13.3 1.30 14.1 1.41
13.5 1.42 14.3 1.57
13.8 1.55 14.5 1.70
14.0 1.69 14.8 1.86
14.3 1.86 15.0 2.03
14.6 2.04 15.3 2.21
14.9 2.21 15.6 2.43
400
R/s
kW
13.8 1.02
13.9 1.08
14.0 0.79
14.6 1.25
15.1 1.67
15.3 1.88
15.5 2.02
15.8 2.21
16.0 2.42
16.3 2.64
450
R/s
kW
14.4 1.08
14.6 1.20
15.0 1.43
15.4 1.64
15.7 1.83
16.0 2.00
16.3 2.23
16.4 2.40
16.7 2.61
17.0 2.86
500
R/s
kW
14.7 1.23
15.0 1.45
15.6 1.64
16.0 1.75
16.4 1.88
16.7 2.09
17.0 2.36
17.2 2.62
17.3 2.82
17.6 3.08
up to the kW ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See EvaporatorFan Motor Performance table on page 24 for additional information.
Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
To convert kW to bkW:
BkW = kW x Motor Efficiency
Motor Efficiency: .83
Maximum Continuous kW: 2.60
Interpolation is permissible. Do not extrapolate.
Static pressure losses (i.e., economizer, electric heater) must be added
to external static pressure before entering Fan Performance table.
50
R/s
9.0
9.2
9.4
9.7
9.9
10.1
10.4
10.6
10.8
11.1
11.3
11.6
11.9
12.0
12.4
12.6
12.9
13.2
100
kW
0.58
0.62
0.67
0.73
0.79
0.94
1.01
1.07
1.13
1.21
1.29
1.36
1.45
1.54
1.64
1.75
1.85
1.95
R/s
10.2
10.4
10.6
10.8
11.0
11.2
11.4
11.6
11.8
12.0
12.1
12.3
12.5
12.7
12.9
13.1
13.3
13.5
kW
0.73
0.79
0.84
0.89
0.96
1.11
1.17
1.22
1.29
1.35
1.43
1.51
1.58
1.67
1.76
1.85
1.95
2.06
150
R/s
11.3
11.5
11.7
11.9
12.1
12.2
12.4
12.5
12.7
12.9
13.1
13.2
13.4
13.6
13.8
14.0
14.2
14.4
kW
0.88
0.94
1.01
1.08
1.14
1.26
1.33
1.40
1.46
1.55
1.63
1.71
1.81
1.89
1.99
2.08
2.19
2.29
External Static
250
kW
R/s
kW
1.00 13.2 1.21
1.06 13.2 1.24
1.14 13.3 1.28
1.21 13.5 1.35
1.29 13.6 1.44
1.42 13.9 1.56
1.51 14.0 1.64
1.59 14.2 1.72
1.68 14.4 1.81
1.76 14.5 1.91
1.84 14.7 2.01
1.92 14.9 2.12
2.00 15.1 2.23
2.09 15.3 2.34
2.19 15.5 2.45
2.30 15.6 2.56
2.42 15.8 2.65
2.54 16.0 2.77
200
R/s
12.1
12.3
12.5
12.7
12.9
13.0
13.3
13.5
13.7
13.8
14.0
14.1
14.3
14.5
14.6
14.8
15.0
15.2
LEGEND
BkW Fan Input kW x Motor Efficiency
kW
Kilowatt Input to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.
6.
7.
3. Factory-shipped drive range is 11.83 to 14.83 r/s. Other r/ss may require
a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors
8.
9.
Pressure (Pa)
300
350
R/s
kW
R/s
kW
14.2 1.24 15.1 1.28
14.3 1.29 15.1 1.41
14.4 1.38 15.2 1.54
14.5 1.48 15.3 1.67
14.6 1.64 15.4 1.82
14.7 1.75 15.5 1.94
14.8 1.81 15.6 2.02
15.0 1.89 15.7 2.10
15.1 1.98 15.8 2.19
15.3 2.07 16.0 2.27
15.4 2.17 16.2 2.36
15.6 2.28 16.3 2.47
15.8 2.39 16.5 2.58
15.9 2.51 16.6 2.69
16.1 2.64 16.8 2.82
16.3 2.77 16.9 2.94
16.5 2.91 17.1 3.08
16.7 3.04 17.3 3.23
400
R/s
kW
16.0 1.44
16.0 1.59
16.1 1.73
16.1 1.86
16.2 1.94
16.2 2.12
16.3 2.21
16.5 2.32
16.6 2.40
16.7 2.51
16.8 2.60
17.0 2.70
17.1 2.80
17.3 2.90
17.4 3.02
17.6 3.14
17.7 3.29
17.9 3.44
450
R/s
kW
16.5 1.68
16.6 1.81
16.6 1.94
16.7 2.02
16.8 2.13
16.9 2.29
17.0 2.40
17.2 2.51
17.3 2.60
17.4 2.71
17.5 2.82
17.6 2.93
17.8 3.04
17.9 3.16
18.1 3.28
18.2 3.40
18.4 3.51
18.5 3.65
500
R/s
kW
17.3 1.80
17.3 1.93
17.4 2.06
17.4 2.15
17.5 2.29
17.4 2.44
17.6 2.56
17.8 2.68
18.0 2.80
18.1 2.92
18.2 3.04
18.3 3.15
18.4 3.29
18.6 3.41
18.7 3.55
18.8 3.67
19.0 3.80
19.1 3.92
up to the kW ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See EvaporatorFan Motor Performance table on page 24 for additional information.
Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
To convert kW to bkW:
BkW = kW x Motor Efficiency
Motor Efficiency: .85
Maximum Continuous kW: 3.78
Interpolation is permissible. Do not extrapolate.
Static pressure losses (i.e., economizer, electric heater) must be added
to external static pressure before entering Fan Performance table.
6.
7.
3. Factory-shipped drive range is 10.33 to 14.67 r/s. Other r/ss may require
a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors
8.
9.
Pressure (Pa)
300
350
R/s
kW
R/s
kW
13.4 1.19 14.2 1.43
13.7 1.37 14.5 1.61
14.0 1.55 14.8 1.79
14.3 1.73 15.1 1.97
14.7 1.93 15.5 2.18
15.1 2.13 15.9 2.41
15.5 2.36 16.3 2.64
16.0 2.62 16.7 2.88
400
R/s
kW
15.3 1.86
15.5 1.98
15.7 2.10
15.9 2.22
16.2 2.34
16.6 2.66
17.0 2.91
450
R/s
kW
15.8 2.10
16.1 2.24
16.4 2.38
16.7 2.52
16.9 2.69
17.3 2.92
500
R/s
kW
16.8 2.55
17.0 2.65
17.2 2.75
17.4 2.85
17.6 2.97
up to the kW ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See EvaporatorFan Motor Performance table on page 24 for additional information.
Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
To convert kW to bkW:
BkW = kW x Motor Efficiency
Motor Efficiency: .81
Maximum Continuous kW: 2.12
Interpolation is permissible. Do not extrapolate.
Static pressure losses (i.e., economizer, electric heater) must be added
to external static pressure before entering Fan Performance table.
19
50
R/s
7.9
8.2
8.4
8.8
9.2
9.7
10.2
10.6
11.1
11.6
100
kW
0.39
0.42
0.56
0.66
0.74
0.85
0.96
1.09
1.24
1.41
R/s
9.3
9.5
9.6
10.0
10.4
10.8
11.2
11.7
12.1
12.5
kW
0.51
0.55
0.78
0.86
0.95
1.07
1.19
1.34
1.49
1.67
150
R/s
10.4
10.6
10.8
11.1
11.5
11.8
12.2
12.6
13.0
13.4
kW
0.63
0.69
0.88
0.98
1.09
1.22
1.35
1.51
1.67
1.86
External Static
250
kW
R/s
kW
0.75 12.8 0.86
0.80 12.9 1.92
0.96 12.6 1.09
1.10 12.9 1.22
1.23 13.2 1.35
1.37 13.6 1.49
1.51 13.9 1.66
1.67 14.3 1.85
1.86 14.7 2.04
2.05 15.0 2.25
200
R/s
11.4
11.5
11.7
12.0
12.4
12.8
13.1
13.5
13.9
14.3
LEGEND
BkW Fan Input kW x Motor Efficiency
kW
Kilowatt Input to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.
6.
7.
3. Factory-shipped drive range is 11.50 to 15.00 r/s. Other r/ss may require
a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors
8.
9.
Pressure (Pa)
300
350
R/s
kW
R/s
kW
13.0 0.90 13.9 1.02
13.1 1.02 14.2 1.14
13.3 1.18 14.3 1.34
13.7 1.33 14.5 1.47
14.0 1.49 14.8 1.57
14.4 1.65 15.1 1.79
14.7 1.81 15.4 1.98
15.0 2.01 15.7 2.18
15.4 2.23 16.1 2.40
15.8 2.46 16.5 2.67
400
R/s
kW
14.6 1.13
14.8 1.38
15.1 1.58
15.4 1.67
15.6 1.77
15.8 1.94
16.1 2.13
16.4 2.36
16.8 2.59
17.1 2.86
450
R/s
kW
15.4 1.38
15.6 1.65
15.9 1.81
16.2 1.90
16.4 1.97
16.5 2.09
16.7 2.29
17.1 2.54
17.4 2.80
17.7 3.08
500
R/s
kW
16.3 1.60
16.5 1.83
16.7 2.03
16.8 2.12
17.1 2.21
17.3 2.31
17.4 2.46
17.7 2.71
18.0 2.99
up to the kW ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See EvaporatorFan Motor Performance table on page 24 for additional information.
Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
To convert kW to bkW:
BkW = kW x Motor Efficiency
Motor Efficiency: .83
Maximum Continuous kW: 2.60
Interpolation is permissible. Do not extrapolate.
Static pressure losses (i.e., economizer, electric heater) must be added
to external static pressure before entering Fan Performance table.
50
R/s
9.2
9.5
9.7
9.9
10.2
10.4
10.7
10.9
11.1
11.4
11.6
11.9
12.1
12.4
12.6
12.8
13.1
13.3
13.6
13.8
100
kW
0.55
0.61
0.66
0.72
0.78
0.85
0.91
1.07
1.12
1.19
1.26
1.34
1.42
1.51
1.60
1.70
1.79
1.91
2.01
2.13
R/s
10.3
10.6
10.8
11.0
11.2
11.5
11.7
11.9
12.1
12.4
12.6
12.8
13.0
13.2
13.5
13.7
13.9
14.2
14.4
14.6
kW
0.72
0.78
0.84
0.89
0.95
1.01
1.08
1.22
1.29
1.36
1.45
1.53
1.62
1.71
1.81
1.92
2.02
2.14
2.26
2.38
150
R/s
11.3
11.5
11.7
11.9
12.1
12.4
12.6
12.8
13.0
13.2
13.4
13.7
13.9
14.1
14.3
14.5
14.7
15.0
15.2
15.4
kW
0.81
0.87
0.91
1.01
1.10
1.20
1.29
1.37
1.45
1.54
1.62
1.71
1.80
1.89
2.00
2.12
2.22
2.34
2.47
2.60
External Static
250
kW
R/s
kW
0.98 13.1 1.08
1.04 13.3 1.18
1.09 13.5 1.27
1.15 13.7 1.34
1.22 13.8 1.41
1.29 14.0 1.48
1.38 14.2 1.55
1.52 14.4 1.67
1.60 14.6 1.75
1.69 14.7 1.84
1.78 14.9 1.93
1.88 15.1 2.03
1.99 15.3 2.15
2.09 15.5 2.26
2.21 15.7 2.39
2.33 15.9 2.51
2.45 16.1 2.64
2.57 16.4 2.77
2.69 16.6 2.92
2.82 16.8 3.07
200
R/s
12.3
12.4
12.6
12.8
13.0
13.2
13.4
13.6
13.8
14.0
14.2
14.4
14.6
14.8
15.0
15.3
15.5
15.7
15.9
16.1
LEGEND
BkW Fan Input kW x Motor Efficiency
kW
Kilowatt Input to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.
7.
3. Factory-shipped drive range is 11.83 to 14.83 r/s. Other r/ss may require
a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors
20
6.
8.
9.
Pressure (Pa)
300
350
R/s
kW
R/s
kW
14.0 1.22 14.9 1.27
14.2 1.28 15.0 1.35
14.3 1.32 15.1 1.44
14.5 1.46 15.2 1.38
14.6 1.58 15.4 1.71
14.8 1.67 15.5 1.76
15.0 1.76 15.7 1.92
15.1 1.86 15.8 2.02
15.3 1.95 16.0 2.12
15.5 2.03 16.2 2.22
15.6 2.12 16.3 2.33
15.8 2.22 16.5 2.44
16.0 2.32 16.7 2.54
16.2 2.42 16.9 2.64
16.4 2.54 17.0 2.76
16.6 2.68 17.2 2.88
16.8 2.82 17.4 3.01
17.0 2.97 17.6 3.14
17.2 3.12 17.8 3.30
17.4 3.26 18.0 3.47
400
R/s
kW
15.8 1.41
15.9 1.48
16.0 1.55
16.1 1.71
16.2 1.79
16.3 1.89
16.4 2.01
16.5 2.20
16.7 2.29
16.8 2.40
17.0 2.52
17.2 2.64
17.3 2.76
17.5 2.88
17.7 3.01
17.8 3.14
18.0 3.25
18.2 3.39
18.4 3.52
18.6 3.67
450
R/s
kW
16.7 1.47
16.8 1.53
16.9 1.66
17.0 1.79
17.0 1.92
17.1 2.06
17.1 2.18
17.2 2.36
17.3 2.47
17.5 2.59
17.7 2.71
17.8 2.83
18.0 2.96
18.1 3.09
18.3 3.23
18.5 3.36
18.6 3.51
18.8 3.65
19.0 3.80
19.2 3.93
500
R/s
kW
17.4 1.63
17.4 1.78
17.5 1.88
17.5 2.02
17.6 2.15
17.6 2.28
17.7 2.36
17.7 2.51
17.9 2.64
18.1 2.77
18.3 2.90
18.4 3.03
18.6 3.16
17.7 3.30
18.9 3.44
19.1 3.59
19.2 3.75
19.4 3.90
19.5 4.06
19.7 4.22
up to the kW ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See EvaporatorFan Motor Performance table on page 24 for additional information.
Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
To convert kW to bkW:
BkW = kW x Motor Efficiency
Motor Efficiency: .85
Maximum Continuous kW: 3.78
Interpolation is permissible. Do not extrapolate.
Static pressure losses (i.e., economizer, electric heater) must be added
to external static pressure before entering Fan Performance table.
LEGEND
Bhp
Brake Horsepower
Watts Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.
6.
7.
3. Factory-shipped drive range is 620 to 880 rpm. Other rpms may require a
field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors
8.
9.
1.8
2.0
Rpm Watts Rpm Watts
736 1945
666 2060
759 1988
697 2123
805 2075
760 2250
851 2162
823 2377
863 2206
855 2445
897 2249
887 2504
931 2326
935 2595
955 2394
972 2678
964 2436
986 2718
973 2479
999 2759
987 2554 1019 2839
997 2637 1034 2917
1006 2727
1014 2807
1021 2902
up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See EvaporatorFan Motor Performance table on page 24 for additional information.
Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
To convert Watts to Bhp:
Watts x Motor Efficiency
Bhp =
746
Motor Efficiency: .81
Maximum Continuous Watts: 2120
Interpolation is permissible. Do not extrapolate.
Static pressure losses (i.e., economizer, electric heater) must be added
to external static pressure before entering Fan Performance table.
LEGEND
Bhp
Brake Horsepower
Watts Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.
6.
7.
3. Factory-shipped drive range is 690 to 900 rpm. Other rpms may require a
field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors
8.
9.
1.8
Rpm Watts
830
998
843 1079
855 1186
868 1303
880 1429
925 1604
935 1709
944 1836
952 1920
963 2005
970 2134
976 2230
981 2309
986 2389
993 2478
1000 2587
1008 2698
1015 2819
2.0
Rpm Watts
883 1240
898 1357
910 1474
924 1546
942 1681
964 1761
975 1811
984 1903
993 2014
1001 2091
1007 2221
1017 2362
1024 2496
1029 2605
1034 2707
1039 2800
1046 2904
1053 3029
up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See EvaporatorFan Motor Performance table on page 24 for additional information.
Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
To convert Watts to Bhp:
Watts x Motor Efficiency
Bhp =
746
Motor Efficiency: .83
Maximum Continuous Watts: 2120
Interpolation is permissible. Do not extrapolate.
Static pressure losses (i.e., economizer, electric heater) must be added
to external static pressure before entering Fan Performance table.
21
LEGEND
Bhp
Brake Horsepower
Watts Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.
3. Factory-shipped drive range is 710 to 890 rpm. Other rpms may require a
field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors
6.
7.
8.
9.
1.6
Rpm Watts
911 1606
920 1676
929 1755
940 1826
952 1887
965 2010
973 2123
980 2210
987 2307
994 2405
1001 2503
1009 2602
1018 2701
1028 2801
1037 2901
1046 3019
1056 3147
1064 3285
1073 3433
1083 3590
1093 3748
1.8
Rpm Watts
940 1685
951 1747
965 1843
980 1940
989 2054
1000 2150
1013 2290
1022 2396
1030 2503
1037 2602
1045 2710
1051 2828
1058 2937
1066 3047
1074 3166
1084 3276
1093 3396
1103 3516
1112 3655
1121 3804
1129 3962
2.0
Rpm Watts
971 1826
985 1922
999 2027
1010 2133
1021 2229
1035 2308
1046 2432
1058 2557
1068 2683
1077 2801
1085 2919
1092 3037
1100 3157
1106 3285
1113 3414
1121 3544
1129 3674
1137 3795
1147 3925
1157 4055
1166 4204
7.
3. Factory-shipped drive range is 620 to 880 rpm. Other rpms may require a
field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors
22
6.
8.
9.
1.6
Rpm Watts
922 1902
924 1928
929 1980
934 2032
937 2058
939 2084
944 2119
949 2188
953 2232
957 2275
967 2377
978 2479
989 2595
1000 2702
1011 2832
1022 2933
1.8
Rpm Watts
759 2219
790 2246
853 2283
916 2326
947 2343
979 2369
987 2428
1002 2495
1003 2521
1004 2554
1010 2637
1019 2735
1030 2847
1040 2956
2.0
Rpm Watts
1004 2640
1007 2652
1013 2677
1019 2702
1022 2710
1025 2727
1039 2791
1041 2831
1045 2854
1050 2878
1056 2925
1061 3002
up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See EvaporatorFan Motor Performance table on page 24 for additional information.
Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
To convert Watts to Bhp:
Watts x Motor Efficiency
Bhp =
746
Motor Efficiency: .81
Maximum Continuous Watts: 2120
Interpolation is permissible. Do not extrapolate.
Static pressure losses (i.e., economizer, electric heater) must be added
to external static pressure before entering Fan Performance table.
Bhp
Brake Horsepower
Watts Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.
6.
7.
3. Factory-shipped drive range is 690 to 900 rpm. Other rpms may require a
field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors
8.
9.
1.6
Rpm Watts
811 1034
825 1097
848 1240
887 1357
918 1519
926 1613
933 1656
934 1718
940 1853
947 1946
956 2039
966 2134
976 2238
985 2344
994 2451
1003 2560
1011 2679
1021 2810
1.8
Rpm Watts
889 1321
907 1429
929 1528
954 1690
963 1834
974 1920
983 1963
988 1980
989 2031
991 2099
997 2195
1004 2291
1013 2397
1023 2514
1032 2633
1042 2763
1051 2895
1060 3029
2.0
Rpm Watts
946 1645
959 1771
975 1878
987 1959
999 2040
1012 2134
1017 2177
1025 2230
1032 2282
1038 2318
1043 2380
1045 2478
1051 2569
1059 2688
1068 2819
1078 2952
1087 3097
1090 3276
up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See EvaporatorFan Motor Performance table on page 24 for additional information.
Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
To convert Watts to Bhp:
Watts x Motor Efficiency
Bhp =
746
Motor Efficiency: .83
Maximum Continuous Watts: 2120
Interpolation is permissible. Do not extrapolate.
Static pressure losses (i.e., economizer, electric heater) must be added
to external static pressure before entering Fan Performance table.
Bhp
Brake Horsepower
Watts Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.
6.
7.
3. Factory-shipped drive range is 710 to 890 rpm. Other rpms may require a
field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors
8.
9.
1.6
Rpm Watts
950 1474
960 1571
963 1668
968 1764
975 1826
983 1887
991 2202
1001 2299
1010 2405
1020 2521
1029 2638
1039 2764
1049 2882
1059 3010
1070 3138
1081 3258
1092 3387
1103 3525
1114 3674
1126 3822
1137 4009
1.8
Rpm Watts
989 1597
1001 1703
1010 1799
1018 1940
1021 2062
1026 2212
1030 2361
1040 2476
1049 2593
1059 2710
1068 2837
1077 2955
1087 3092
1097 3230
1107 3368
1117 3516
1127 3655
1138 3804
1149 3934
1160 4083
1171 4242
2.0
Rpm Watts
1000 1755
1006 1834
1018 1940
1022 2045
1039 2203
1051 2370
1064 2512
1075 2638
1085 2773
1095 2901
1105 3028
1114 3166
1124 3304
1133 3442
1143 3590
1152 3748
1162 3897
1172 4055
1182 4223
1193 4382
1204 4531
up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See EvaporatorFan Motor Performance table on page 24 for additional information.
Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
To convert Watts to Bhp:
Watts x Motor Efficiency
Bhp =
746
Motor Efficiency: .85
Maximum Continuous Watts: 3775
Interpolation is permissible. Do not extrapolate.
Static pressure losses (i.e., economizer, electric heater) must be added
to external static pressure before entering Fan Performance table.
23
UNIT RATED
VOLTAGE
008
009
012
014
400
400
400
400
MAXIMUM
ACCEPTABLE
CONTINUOUS
BkW*
1.79
1.79
2.16
3.13
LEGEND
Bhp Brake Horsepower
BkW kW x Motor Efficiency
MAXIMUM
ACCEPTABLE
CONTINUOUS
BHP*
2.40
2.40
2.90
4.20
MAXIMUM
ACCEPTABLE
OPERATING
WATTS
2120
2120
2120
3775
MAXIMUM
AMP DRAW
2.7
2.7
2.7
5.7
*Extensive motor and electrical testing on these units ensures that the
full range of the motors can be utilized with confidence. Using your fan
motors up to the ratings shown in this table will not result in nuisance
tripping or premature motor failure. Unit warranty will not be affected.
0
14.67
15.00
14.83
14.25
14.58
14.58
12
1
13.83
14.25
14.25
112
13.33
13.92
13.72
312
11.67
12.58
12.75
4
11.25
12.25
12.50
412
10.83
11.92
12.17
5
10.33
11.50
11.83
4
675
735
750
4 1 2
650
715
730
5
620
690
710
0
880
900
890
855
875
875
12
1
830
855
855
1 1 2
800
835
835
24
312
700
755
765
L/s
All
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300
1 HEATER
MODULE
6
8
10
12
14
16
18
19
21
23
25
27
29
2 HEATER
MODULES
10
12
15
17
20
22
25
27
29
32
34
37
39
ECONOMIZER
5
6
7
8
9
10
11
12
13
14
15
16
17
CFM
All
2200
2500
3000
3500
4000
4500
5000
5500
6000
1 HEATER
MODULE
.02
.03
.05
.07
.08
.10
.12
.14
.16
2 HEATER
MODULES
.03
.05
.07
.09
.12
.14
.16
.19
.21
ECONOMIZER
.02
.02
.03
.04
.05
.06
.07
.08
.09
UNIT ELECTRICAL
CHARACTERISTICS
008
400-3-50
009
400-3-50
012,
014
400-3-50
ACCESSORY
kW
9.7
11.5
19.3
22.9
29.0*
9.7
11.5
19.3
22.9
29.0*
9.7
11.5**
19.3
22.9
29.0*
34.7*
PART NO.
CRHEATER-----123A00
120A00
121A00
122A00
121A00, 123A00
123A00
120A00
121A00
122A00
121A00, 123A00
123A00
120A00
121A00
122A00
123A00, 121A00
120A00, 122A00
MULTIPLICATION FACTORS
HEATER kW
RATING
(Nominal Voltage)
400
VOLTAGE
DISTRIBUTION
V-3-50
380
415
420
MULTIPLICATION
FACTOR
FOR CAPACITY
0.902
1.076
1.101
MULTIPLICATION
FACTOR
FOR FULL LOAD AMPS
0.949
1.037
1.050
25
Electrical data
UNIT
50TJ
NOMINAL
VOLTAGE
(50 Hz)
VOLTAGE
RANGE
Min
Max
COMPR
(ea)
RLA
LRA
OFM
(ea)
IFM
ELECTRIC HEAT*
POWER SUPPLY
FLA
FLA
Nominal
kW
9.7
11.5
19.3
22.9
29.0
9.7
11.5
19.3
22.9
29.0
9.7
19.3
22.9
29.0
34.7
11.5
19.3
22.9
29.0
34.7
FLA
MCA
MOCP**
13.9
16.5
27.8
33.1
41.8
13.9
16.5
27.8
33.1
41.8
16.5
27.8
33.1
41.8
50.1
16.5
27.8
33.1
41.8
50.1
17.8
20.7
23.9
38.1
44.6
55.5
20.5
20.7
23.9
38.1
44.6
55.5
24.0
24.9
39.1
45.6
56.5
66.9
29.4
29.4
40.8
47.3
52.8
68.6
20
25
25
40
45
60
25
25
25
40
45
60
30
30
40
45
60
70
35
35
45
50
60
70
008
400
(3 phase)
380
420
6.2
37.7
0.6
2.6
009
400
(3 phase)
380
420
7.4
46.0
0.6
2.6
012
400
(3 phase)
380
420
8.6
55.0
0.6
3.4
014
400
(3 phase)
380
420
10.4
72.0
0.6
4.8
LEGEND
CE
The Mark of the European Community
FLA
Full Load Amps
IFM
Indoor (Evaporator) Fan Motor
LRA
Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
OFM
Outdoor (Condenser) Fan Motor
RLA
Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 400 v. If power
distribution voltage to unit varies from rated heater voltage, heater kW
will vary accordingly.
Heaters are field installed only.
**Fuse or circuit breaker.
Fusing in single point box provides the required branch circuit
protection.
NOTES:
1. Unit total kW values are determined under test conditions stated in
European Standard EN60335-2-40.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent
of voltage imbalance.
% Voltage imbalance
max voltage deviation from average voltage
= 100 x
average voltage
26
UNIT
TOTAL
kW
9.5
11.1
12.9
20.8
24.4
30.4
10.3
11.1
12.9
20.8
24.4
30.4
11.2
13.4
21.3
24.9
30.9
36.6
15.9
15.9
21.8
25.2
31.2
36.9
MINIMUM
UNIT
DISCONNECT
FLA
19
19
22
35
41
57
21
21
22
35
41
51
25
25
36
42
52
62
31
31
38
44
54
63
LRA
99
115
133
133
133
133
134
134
190
Average Voltage =
CONDENSER-FAN
DISCHARGE AIR
EURO-STYLE
CONTROL BOX
FIELD-SUPPLIED
DISCONNECT
PER LOCAL
CODES*
OUTDOORAIR INLET
POWER WIRING
SLAB MOUNT
OPTIONAL FACTORY-INSTALLED
DISCONNECT SWITCH
CONTROL WIRING
COMPRESSOR
27
LEGEND
AHA
C
CAP
CB
CC
COMP
D
EC
ECON
EPS
ER
FPT
FSS
HPS
HR
IFC
IFM
LPS
LS
LSM
NC
NO
OAT
OFM
PE
PL
R
SAT
SEN
SW1
SW2
NOTES:
1. If any of the original wire furnished must be replaced, it must be
replaced with type 90 C wire or its equivalent.
2. Three-phase motors are protected under primary single-phasing
conditions.
3. Thermostat:
HH07AT170,172,174 and P272-2783
Subbase:
HH93AZ176,178 and P272-1882,1883.
4. Set heat anticipator at 1 amp.
5. Use copper conductors only.
28
SW3
SW4
TB
TC
TH
TRAN
29
Controls
Operating sequence
Cooling, units without economizer When thermostat calls for cooling, terminals G and Y1 are energized. The
indoor (evaporator) fan contactor (IFC), and compressor
contactor no. 1 (C1) are energized and evaporator-fan motor, compressor no. 1, and condenser fans start. The
condenser-fan motor runs continuously while unit is cooling. If the thermostat calls for a second stage of cooling by
energizing Y2, compressor contactor no. 2 (C2) is energized and compressor no. 2 starts.
Heating, units without economizer (If Accessory Heater
is Installed) Upon a call for heating through terminal
W1, IFC and heater contactor no. 1 (HC1) are energized.
On units equipped for 2 stages of heat, when additional
heat is needed, HC2 is energized through W2.
Cooling, units with economizer When the outdoorair temperature is above the outdoor-air thermostat (OAT)
setting and the room thermostat calls for cooling, compressor contactor no. 1 is energized to start compressor no. 1
and the condenser-fan motor. The evaporator-fan motor is
energized and the economizer damper moves to the minimum position. Upon a further call for cooling, compressor
contactor no. 2 will be energized, starting compressor
no. 2. After the thermostat is satisfied, the damper moves
to the fully closed position.
When the outdoor-air temperature is below the OAT setting and the thermostat calls for cooling, the economizer
dampers move to the minimum position. If the supply-air
temperature is above 13.9 C (57 F), the damper continues
to open until it reaches the fully open position or until the
supply-air temperature drops below 13.9 C (57 F).
30
Application data
Outdoor installation Units approved for outdoor installation only.
Ductwork Secure vertical discharge ductwork to roof
curb. For horizontal discharge applications, either attach
ductwork to unit, or use field-supplied flanges attached to
the horizontal discharge openings and attach all ductwork
to flanges.
Horizontal discharge To convert from vertical discharge to horizontal discharge:
1. Remove economizer or two-position damper to gain access to return duct opening.
2. Move the horizontal-discharge duct opening covers to
the vertical discharge openings.
3. Rotate economizer or two-position damper 90 degrees.
4. Remove screws along right side of barometric relief
damper and relocate them across top of damper so
damper opens freely at bottom.
5. Install block-off plate over the opening on the access
panel.
Thru-the-bottom service connections Power connections made through the bottom of the unit must utilize
an accessory Carrier roof curb and accessory thru-the-bottom
power connection accessory kit.
Thermostat Use of 2-stage heating and cooling thermostat is recommended for all units. A 2-stage cooling
thermostat is required on units with accessory economizer
to provide integrated cooling.
Heating-to-cooling changeover All units are automatic changeover from heating to cooling when automatic
changeover thermostat and subbase are used.
Airflow Units are draw-thru on cooling and blow-thru
on heating.
Maximum airflow To minimize the possibility of condensate blow-off from evaporator, airflow through units
should not exceed 236 L/s per kW (500 cfm/ton).
Minimum airflow For cooling, minimum airflow is
142 L/s per kW (300 cfm/ton). For units with electric heating, required minimum L/s (cfm) is 1062 (2250) for 50TJ008;
1203 (2550) for 50TJ009; and 1416 (3000) for 50TJ012
and 014.
Minimum ambient cooling operating temperature
The minimum temperature for size 008-014 standard units
is 4 C (25 F).
Internal unit design Due to Carriers internal unit
design (draw-thru over the motor), air path, and specially
designed motors, the full kW horsepower (maximum continuous bkW and bhp) listed in the Physical Data tables and
the notes following each Fan Performance table can be utilized with confidence.
Using Carrier motors with the values listed in the Physical and Fan Performance Data tables will not result in nuisance tripping or premature motor failure. The unit warranty will not be affected.
31
Guide specifications
Packaged Rooftop Cooling Unit with
Electric Heat Option Constant Volume
Application
HVAC Guide Specifications
Size Range: 21.5 to 35.9 kW (6.1 to 10.2 Tons)
Nominal Cooling
Carrier Model Number: 50TJ
Part 1 General
1.01 SYSTEM DESCRIPTION
A. Outdoor rooftop- or slab-mounted, electrically controlled cooling unit with optional heat utilizing a
hermetic compressor for cooling duty and electric
resistance coils for heating duty. Unit shall discharge
supply air vertically or horizontally as shown on contract drawings.
1.02 QUALITY ASSURANCE
A. Unit shall be designed in accordance with European
Standard EN60335-2-40, and shall be tested in accordance with Eurovent standards.
B. Unit shall be rated in accordance with ARI Standards
210/240 or 360 and 270 (U.S.A. Standards).
C. Unit shall be designed to conform to ASHRAE 15,
latest revision. Unit shall be designed in accordance
with UL 1995 (U.S.A. Standards) and shall be certified under Canadian Standards as a total package for
safety requirements.
D. Unit shall be manufactured in a facility registered to
ISO-9002/BS5750, Part 2.
E. Roof curb shall be designed to conform to NRCA
Standards (U.S.A. Standards).
F. Insulation and adhesive shall meet NFPA 90A requirements (U.S.A. Standard) for flame spread and smoke
generation.
G. Unit casing shall be capable of withstanding Federal
Test Method (U.S.A. Standard) Standard No. 141
(Method 6061) 500-hour salt spray test.
1.03 DELIVERY, STORAGE, AND HANDLING
A. Unit(s) shall be stored and handled per manufacturers recommendations.
Part 2 Products
2.01 EQUIPMENT (STANDARD)
A. General:
Factory-assembled, single-piece cooling unit with optional electric heat. Contained within the unit enclosure shall be all factory wiring, piping, controls, refrigerant charge (R-22), and special features required
prior to field start-up.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized steel,
bonderized and coated with a baked enamel finish
on all externally exposed surfaces.
2. Evaporator fan cabinet interior shall be insulated
with a minimum 13-mm (12-in.) thick flexible fiberglass insulation coated on the air side. Aluminum foil-faced fiberglass insulation shall be used
in the furnace compartment.
32
C.
D.
E.
F.
G. Filter Section:
1. Standard filter section shall consist of factoryinstalled, low-velocity, throwaway, 51-mm (2-in.)
thick fiberglass filters of commercially available
sizes.
2. Filter face velocity shall not exceed 1.64 m/s
(320 fpm) at nominal airflows.
3. Filter section shall use only one size filter.
4. Filters shall be accessible through an access panel
with no-tool removal.
H. Controls and Safeties:
1. Unit Controls:
Unit shall be complete with self-contained lowvoltage control circuit.
2. Standard Safeties:
a. Unit shall incorporate compressor overtemperature and overcurrent safety devices to shut
off compressor.
b. Heating section shall be provided with the following minimum protections:
1) High-temperature limit switches.
2) Overcurrent protection.
I. Operating Characteristics:
1. Unit shall be capable of starting and running at
46.1 C (115 F) ambient outdoor temperature,
meeting maximum load criteria of ARI Standard
210/240 or 360 (U.S.A. Standards) at 10%
voltage.
2. Compressor with standard controls shall be capable of operation down to 25 F ambient outdoor
temperature.
J. Electrical Requirements:
All unit power wiring shall enter unit cabinet at a single
factory-predrilled location.
K. Motors:
1. Compressor motors shall be cooled by refrigerant
passing through motor windings and shall have line
break thermal and current overload protection.
2. Indoor blower (evaporator fan) motor shall have
permanently lubricated bearings and inherent
automatic-reset thermal overload protection.
3. Totally-enclosed condenser-fan motor shall have
permanently lubricated bearings and inherent
automatic-reset thermal overload protection.
L. Special Features:
Certain features are not applicable when the features
designated by * are specified. For assistance in amending the specifications, contact your local Carrier Sales
Office.
1. Roof Curbs: (Horizontal and Vertical)
a. Formed galvanized steel with wood nailer strip
and shall be capable of supporting entire unit
weight.
b. Allows for installing and securing ductwork
to curb prior to mounting unit on the curb.
2. Integrated Economizer:
a. Integrated integral-modulating type capable
of simultaneous economizer and compressor
operation.
b. Includes all hardware and controls to provide
cooling with outdoor air.
c. Equipped with low-leakage dampers not to
exceed 3% leakage, at 249 Pa (1 in. wg) pressure differential.
d. Capable of introducing up to 100% outdoor
air in both minimum and fully-open
positions.
e. Equipped with a gravity relief sliding plate
damper. Damper shall close upon unit shutoff.
f. Designed to close damper during loss-ofpower situations with emergency power
supply.
g. Dry bulb outdoor-air thermostat protection
shall be provided as standard.
h. Economizer has a guillotine-style damper.
3. Manual Outdoor-Air Damper:
Manual damper package shall consist of damper,
birdscreen, and rainhood which can be preset to
admit up to 50% outdoor air for year-round
ventilation.
4. 100% Two-Position Damper:
a. Two-position damper package shall include
single blade damper and motor. Admits up
to 100% outdoor air.
b. Damper shall close upon evaporator fan shutoff.
c. Designed to close damper during loss of power
situations.
d. Equipped with barometric relief damper.
5. 25% Two-Position Damper:
a. Two-position damper package shall include
single blade damper and motor. Admits up
to 25% outdoor air.
b. Damper shall close upon evaporator fan
shutoff.
c. Designed to close damper during loss of power
situations.
d. Equipped with barometric relief damper.
6. Solid-State Enthalpy Control:
Capable of sensing outdoor-air enthalpy content
(temperature and humidity) and controlling economizer cut-in point to have minimum heat content
air passing over the evaporator coil for most efficient system operation.
7. Differential Enthalpy Sensor:
a. For use with economizer only.
b. Capable of comparing enthalpy content (temperature and humidity) of outdoor and indoor air and controlling economizer cut-in
point at the most economical level.
33
34
11-95
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 1b 6b
Page 36
Printed in U.S.A.
Form 50TJ-C4PD