Professional Documents
Culture Documents
Basics of Protection
ES is used to drain
trapped charges to
ground before
doing any
maintenance work on
a line
The assembly of
relay, CB, CT, PT,
isolator, fuse,
busbar etc. is also
termed switchgear.
Isolator provides additional safety during any maintenance work. This is a no-load
device i.e. designed to be switched on or off under no load condition.
Following sequence is used for the operation of switches and CB
During Opening a line:
1.Trip CB
2.Open isolator
3. Close earthing switch
A high-speed relay is one that operates in less than 50 msec (three cycles on a 60
Hz basis) (IEEE 100).
The term instantaneous is defined to indicate that no (time) delay is purposely
introduced in the action of the device (IEEE 100). In practice, the terms
instantaneous and high-speed are used interchangeably to describe protective
relays that operate in 50 msec or less.
Modern high-speed circuit breakers for high voltage systems operate in the
range of 1750 msec (one to three cycles at 60 Hz); others operate at less than 83
msec (five cycles at 60 Hz).
Thus, the total clearing time (relays plus breaker) typically ranges from
approximately 35130 msec (two to eight cycles at 60 Hz).
In the lower-voltage systems, in which time-coordination is required between
protective relays, relay-operating times generally will be slower; typically on the
order of 0.21.5 sec for the primary zone.
Simplicity less
service continuity and fault current more
Fault types
Faults can be broadly classified into two main areas, which have been designated
active and passive.
Active faults:
The active fault is when actual current flows from one phase conductor to another
(phase-to-phase), or alternatively from one phase conductor to earth (phase-to-earth).
This type of fault can also be further classified into two areas, namely the solid fault and
the incipient fault.
The solid fault occurs as a result of an
immediate complete breakdown of
insulation as would happen if, say,
Passive faults:
Passive faults are not real faults in the true sense of the word, but are rather
conditions that are stressing the system beyond its design capacity, so that ultimately
active faults will occur.
Typical examples are:
Overloading leading to over heating of insulation (deteriorating quality,
reduced life and ultimate failure).
Overvoltage: Stressing the insulation beyond its withstand capacities.
Under frequency: Causing plant to behave incorrectly.
Power swings: Generators going out-of-step or out-of-synchronism with each
other.
It is therefore very necessary to monitor these conditions to protect the system
against these conditions.
Circuit breakers
Where fuses are unsuitable
or inadequate, protective
relays and circuit breakers are
used
in
combination
respectively to detect and
isolate faults.
The first characteristic is referred to as the tripping time and is expressed in cycles.
Modern high-speed circuit breakers have tripping times between three and eight
cycles.
The tripping or total clearing or break time is made up as follows:
Opening time: The time between instant of application of tripping power to
the instant of separation of the main contacts.
Arcing time: The time between the instant of separation of the main circuit
breaker contacts to the instant of arc extinction of short-circuit current.
Total break or clearing time: The sum of the above.
The selection of the breaking capacity depends on the actual fault conditions
expected in the system and the possible future increase in the fault level of the main
source of supply.
Arc
The arc has three parts:
1. Cathode end (ve): There is approximately 3050 V drop due to emission of
electrons.
2. Arc column: Ionized gas, which has a diameter proportional to current.
Temperature can be in the range of 600025 000 C.
3. Anode end (+ve): Volt drop 1020 V.
TRV (Transient Recovery Voltage)
When short-circuit occurs, fault current flows corresponding to the network
parameters. The breaker trips and the current is interrupted at the next natural current
zero. The network reacts by transient oscillations, which gives rise to the transient
recovery voltage (TRV) across the circuit breaker main contacts.
Overcoming TRV
All breaking principles involve the separation of contacts, which initially are bridged by
a hot, highly conductive arcing column.
After interruption at current zero, the arcing zone has to be cooled to such an extent
that the TRV is overcome and it cannot cause a voltage breakdown across the open
gap.
Figure 7.9
Diagrammatic representation
Because it is virtually impossible for electricity to flow in a vacuum, the early designs
displayed the ability of current chopping i.e. switching off the current at a point on the
cycle other than current zero. This sudden instantaneous collapse of the current
generated extremely high-voltage spikes and surges into the system, causing failure of
equipment.
Another phenomenon was pre-strike at switch on. Due to their superior rate of dielectric
recovery, a characteristic of all vacuum switches was the production of a train of pulses
during the closing operation. Although of modest magnitude, the high rate of rise of
voltage in pre-strike transients can, under certain conditions produce high-insulation
stresses in motor line end coils.
Subsequent developments attempted to alleviate these shortcomings by the use of
softer contact materials, in order to maintain metal vapor in the arc plasma so that it did
not go out during switching. Unfortunately, this led to many instances of contacts welding
on closing.
Merits of VCB:
Demerits of VCB
(3.18)