User’s Manual for

MD Controller.

Indotech Industrial Solutions Pvt.Ltd


1/2 Ankur Plaza Mumbai Banglore Highway Bridge
Warje Pune 411058
Indotech Industrial Solutions Pvt. Ltd.

CONTENTS

1) Introducing MD Controller……………………………………………2

2) How does it work? ………………………………………………….3

3) Product Features………………………………………………………4

4) Installation………………………………………………………………5

5) Device Functionality………………………………………………….6

6) Technical Details………..……………………………………………12

5.1) Specifications………………………………………………..12
5.2) Indications and Switches………………………………..13

7) Appendices

Appendix A- Maximum Demand Terminology………….14


Appendix B- Wiring Diagrams ………………………………15
Appendix C- Technical Support……………………………..16

MD Controller User Manual V 1.0 2

Rising Indotech Shines Technology


Indotech Industrial Solutions Pvt. Ltd.

1. Introducing MD Controller.

Non-domestic electrical power users often have to pay a maximum


demand charge in addition to the usual charge for the number of units
consumed. This charge is usually based on the highest amount of
power used during some period (say 30 minutes) during the metering
month.
The maximum demand charge often represents a large portion of the
total bill and may be based on only one isolated 30-minute episode of
high power use. Monitoring power use and turning off or reducing non-
essential loads during such periods of high power use can realize
considerable savings. The ETMD-04 is a realistically priced stand-alone
controller suitable for small to medium consumers wishing to reduce
their maximum demand in an economical and simple manner. The unit
can also be used for reducing cable and transformer loadings.

Apart from this ETMD-04 gives you a runtime Power usage and
continuous monitoring of Voltage, Current, and Power in kVA. On a
LCD display panel it shows the continuously varing readings.

At the controlling end ETMD-04 comes with the facility to control


certain activities of the plant. This can be achieved by giving the
threshold values of MD to the ETMD-04 via a keyboard. So in the
process of monitoring if it detects current MD grater than or closed to
user set MD then it can trip the switches or MCBs as per requirement.

MD Controller User Manual V 1.0 3

Rising Indotech Shines Technology


Indotech Industrial Solutions Pvt. Ltd.

2. How does it work?

MD controller works on principle of instantaneous readings of voltage


and current and calculating power in kVA. At the same time system’s
Real Time Clock will keep track of time and calculates present MD.
Then according to the logic the current MD and the MD configured by
user is compared and the predefined load tripping action is taken.

After a predefined time it again calculates the MD. Now if the


calculated MD is less than the current MD then it reconnects the load
in proper sequence and if it is greater than the current MD then it trips
the next load. This action continues forever and thus the total load
gets controlled and the desired MD is restricted from reaching its
maximum limit.

In this manner a record of the average power use over the last 15
minutes is obtained in a so-called "sliding window". The ETMD-04 is
also available on request with a 15 or 30 min sliding window. The
controller compares this running average with a set target load value
and operates a set of relays if the target appears in danger of being
exceeded. The relay contacts are used to switch off non-critical
electrical loads and hence hold the overall load to a prescribed limit.
The unit also records the highest value of running average load to date
and operates an alarm relay when a new high is recorded. A visual
display is provided of the running average which can also display the
target value or the recorded maximum on request.

MD Controller User Manual V 1.0 4

Rising Indotech Shines Technology


Indotech Industrial Solutions Pvt. Ltd.

3. Product Features

Sr. Description
No.
1 Advanced micro controller technology.
Display of rms voltage, current, average &
2
instantaneous demand, at a time.
Selectable display of maximum demand with date and
3
time.

4 Adjustable integration time 30/15 min.

5 Adjustable on and off delay.

6 Password protection for setting.

7 Step less MD setting up to 500 KVA.

8 Programmable CT ratio.

9 4 Potential free contacts for tripping different loads.

10 *Interfacing to PC through RS232 is possible.

* Optional Feature

MD Controller User Manual V 1.0 5

Rising Indotech Shines Technology


Indotech Industrial Solutions Pvt. Ltd.

4. Installation

Electrical Connections

WARNING The MD Controller is to be used by qualified


personnel only. Do not install the ETMD-04 on
a power line unless you are qualified to do
so. High voltages that can cause burns and lethal
shocks are present when working on live power
line.
To assure operator safety, when making
connections to power lines, always start by
connecting the instrument power, which contains
the safety earth ground.

In order to install ETMD-04 at the client’s end, one should follow the
procedure provided in user manual: -
 Check the client’s mains supply; get a clear idea about the power flow of

the existing plant.

 Do the power connections as prescribed in the approved drawings.

(You can refer to the wiring diagram given in appendix A.)

 Check the CT directions.

 Adjust the CT ratio as pr the requirement.


 Make connections of the loads as per requirement.

 Check the calibration for voltage as well as current.

MD Controller User Manual V 1.0 6

Rising Indotech Shines Technology


Indotech Industrial Solutions Pvt. Ltd.

5. Device Functionality

It describes the user not only how to operate the system but
also gives a clear idea about the all the indications.
Lets start with the key functionality; on the front panel of the
PMR we have total five keys. Their functions are as below:

Auto/Manual Key : This key gives the provision to user


for shifting from auto to manual and vice-versa.
In manual mode the pages are displayed manually by
using UP-DOWN arrow keys.
In auto mode the pages will automatically scrolled at
predefined refresh rate.

Theses keys are used to scroll the display UP and DOWN.


The same keys are used as Yes and No keys for the
setting confirmation option.

The fourth key is a SET key. It is used for entering into


the configuration mode.

MD Controller User Manual V 1.0 7

Rising Indotech Shines Technology


Indotech Industrial Solutions Pvt. Ltd.

Apart from these keys the front panel also consists of some LED
message information. There are total of five LEDs, out of which one is
POWER indication LED and four are load indications LEDs.

The output relays are connected to the load control circuits in


whichever safe and reliable manner the user deems desirable.
Relay 1 is the lowest priority relay and is the first to operate in the
event of load shedding being required therefore use it to control loads
that are generally unimportant. Relay 2 is the next highest priority and
should control loads of slightly higher priority. Relay 3 operates when
the target has been exceeded and should be connected to loads of
high priority.

For better understanding of the device please refer the “Page


Sequence” diagrams in following pages.

MD Controller User Manual V 1.0 8

Rising Indotech Shines Technology


Indotech Industrial Solutions Pvt. Ltd.

Auto Mode

MD Controller User Manual V 1.0 9

Rising Indotech Shines Technology


Indotech Industrial Solutions Pvt. Ltd.

Manual Mode
E
R_Phase_Details

D
R_Phase_Details
234.5V 0025 A

Entering into
Configuration Mode

Y_Phase_Details

SET
Y_Phase_Details
238.5V 0055 A
A/M

B_Phase_Details
Selecting
Auto Mode
B_Phase_Details
240.5V 0040 A

Total_KVA
B

Total_Power
0164KVA

MD Controller User Manual V 1.0 10

Rising Indotech Shines Technology


Indotech Industrial Solutions Pvt. Ltd.

A
B

Set and Current


MD Details
D
Set MD Curr.MD
500KVA 150KVA

Entering into
Configuration Mode

Maximum_MDDetails
SET

Max. MD
A/M 192KVA

Selecting
Auto Mode
Instantaneous MD
Details

Instantaneous_MD
220KVA

MD Controller User Manual V 1.0 11

Rising Indotech Shines Technology


Indotech Industrial Solutions Pvt. Ltd.

Configuration Mode

Entering
Configuration Mode

Select MD Delay
UP DOWN

Set MD 125 KVA Set Delay 10


minutes.

A/M SET SET A/M

*Press to SET accept and A/M to reject.

MD Controller User Manual V 1.0 12

Rising Indotech Shines Technology


Indotech Industrial Solutions Pvt. Ltd.

6. Technical Details

 Specifications

Sr.
Particulars Specifications
No.

1 Power Supply 12 Volt DC @ 1A.

2 Measured Voltage Range 0-500 Volt AC (P-N)

3 Measured Current Range 0-1000 Amps, AC RMS/Phase

4 Phases Measured 1Ph / 3Ph-4 Wire

5 Display 16 Char, 2 Line Display

6 Operating Temperature -15° to 60°C

7 Physical Dimensions (LxBxH) mm


(110x192x96) mm

8 Weight 1 KG.

9 IP Protection IP 43

10 Mounting Panel Mountable

MD Controller User Manual V 1.0 13

Rising Indotech Shines Technology


Indotech Industrial Solutions Pvt. Ltd.

 Indications and Switches

 Indications

Indications

LEDs ON OFF

L1 Load 1 ON Load 1 OFF

L2 Load 2 ON Load 2 OFF

L3 Load 3 ON Load 3 OFF

L4 Load 4 ON Load 4 OFF

 Switches + Keys

Particulars Purpose

ON/OFF switch Power ON / OFF


Auto/Manual Parameter
A/M Key Scanning Mode Selection.
(NO for Confirmation)
Up Key UP Scrolling

Down Key DOWN Scrolling


To Enter into Configuration
SET
mode. (NO for Confirmation)

MD Controller User Manual V 1.0 14

Rising Indotech Shines Technology


Indotech Industrial Solutions Pvt. Ltd.

Appendix A: Maximum Demand Terminology.

 Set MD :

It is the user configurable demand at which the user wishes to limit


his Maximum demand. (This is an instantaneous value and the
loads will be cut-off after the load exceeds the set value)

 Current MD::

It is the Maximum Demand of the user integrated over the period of


15 min or ½ hour as prescribed by the respective supplying
authority.

 Maximum MD :

It is the highest value of the Current MD during the specified


period, it can be cleared by the user. At the rear side of the device
a RESET key is provided to reset these readings after it is checked.

 Instantaneous MD :

It is the highest value of Instantaneous Demand placed by the


user’s load on the supply system during the specified period, it can
be cleared by the user.

MD Controller User Manual V 1.0 15

Rising Indotech Shines Technology


Indotech Industrial Solutions Pvt. Ltd.

Appendix B : Connection Diagram.

MD Controller User Manual V 1.0 16

Rising Indotech Shines Technology


Indotech Industrial Solutions Pvt. Ltd.

Appendix C: Technical Support.

Contact :

Indotech Industrial Solutions Pvt.Ltd


1/2 Ankur Plaza, Mumbai Banglore Highway Bridge,
Warje Pune 411058

Tele: 91-20-25232221
Fax: 91-20-25231588
Email: project@indotechindustries.com
Web: www.indotechindustries.com

MD Controller User Manual V 1.0 17