Relion 615 series

Motor protection and control


REM615

Compact and versatile solution for


industrial power distribution systems
REM615 is a dedicated motor protection and control IED,
perfectly aligned for protection, control, measurement
and supervision of asynchronous motors in the
manufacturing and process industry.
Application
REM615 has been designed to be the main protection for
asynchronous motors and their drives in manufacturing
and process industry. Typically, the motor IED is used with
circuit-breaker or contactor-controlled HV motors, and with
contactor-controlled, medium-sized and large LV motors
in a variety of drives. The drives include both continuously
and intermittently operated asynchronous motor drives with
varying load, such as pumps and conveyors, crushers and
choppers, mixers and agitators, fans and aerators.
REM615 is now available in a fourth standard configuration,
D, which includes three combi-sensor inputs for phase
currents (Rogowski coil) and voltages (voltage divider). The
other standard configurations use conventional current and
voltage instrument transformers.
To further improve the arc fault protection and minimize
the effects of an arc fault, 615 series IEDs can now also be
ordered with an optional I/O module equipped with highspeed outputs. Compared to conventional binary outputs, the
high-speed outputs decrease the operate time by four to six
milliseconds.
The standard configurations can be tailored to meet the
application requirements using the IEC61850-compliant
protection and control IED manager PCM600.
Human-machine interface (HMI)
As a member of the Relion product family, REM615 shares
the same Human Machine Interface (HMI) look and feel as the
other Relion IEDs. The location of a push button with a certain
function is always the same and the menu structure identical.
Consequently, once you become familiar with one Relion IED,
you can use them all.
The 615 series IEDs are equipped with a large graphical
display which can show customizable single-line diagrams
(SLD) with position indication for the circuit breaker,
disconnectors and the earthing switch. Also measured
values provided by the chosen standard configuration can
be displayed. The SLDs can be accessed not only locally,
but also via the web browser-based HMI. The SLDs can be
adjusted to meet user requirements using PCM600.

2 Motor protection and control | REM615

Standardized communication
REM615 fully supports the IEC61850 standard for
communication in substations, including fast GOOSE and
IEC61850-9-2LE. REM615 also supports both the parallel
redundancy protocol (PRP) and high-availability seamless
redundancy (HSR) protocols. In addition, the IED supports
the DNP3, IEC 60870-5-103 and Modbus protocols. By
using protocol adapter SPA-ZC 302, also Profibus DVP1 is
now supported. REM615 is able to use two communication
protocols simultaneously.
For redundant Ethernet communication, REM615 offers either
two optical or two galvanic Ethernet network interfaces. A
third port with a galvanic Ethernet network interface provides
connectivity of any other Ethernet devices to an IEC 61850
station bus inside a switchgear bay. The redundant Ethernet
solution can be built on the Ethernet-based IEC 61850,
Modbus and DNP3 protocols.
The implementation of the IEC 61850 standard in REM615
covers both vertical and horizontal communication, including
GOOSE messaging with both binary and analog signals,
together with parameter setting according to IEC 618508-1. Also process bus with sampled values of analog phase
voltages is supported. For time-critical applications, REM615
supports synchronization over Ethernet using SNTP or over
a separate bus using IRIG-B. For process-bus applications,
which require high-accuracy time synchronization,
IEEE1588 is used, with a time stamp resolution of only four
microseconds at the most. IEEE 1588 is supported in all
variants with a redundant Ethernet communication module.
615 series
REM615 is a member of ABBs Relion product family and its
615 protection and control series. The 615 series IEDs are
characterized by their compactness and withdrawable-unit
design. Re-engineered from the ground up, the 615 series has
been designed to unleash the full potential of the IEC61850
standard for communication and interoperability of substation
automation devices. In addition to REM615, the 615 series
includes the following IEDs:
REF615 Feeder protection and control
RED615 Line differential protection and control
RET615 Transformer protection and control
REU615 Voltage protection and control
REV615 Capacitor bank protection and control

UL1UL2UL3

REM615

MOTOR PROTECTION AND CONTROL IED

PROTECTION

LOCAL HMI

ALSO AVAILABLE
Configuration
System
HMI
Time
Authorization

Master Trip
Lockout relay
94/86

ESC

- Disturbance and fault recorders


- Event log and recorded data
- High-Speed Output module (optional)
- IED self-supervision
- Local/Remote push button on LHMI
- User management
- Web HMI

Clear

R
L

U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A

3I

3I<
37

I2>M
46M

I2>>
46R

Is2t n<
49, 66, 48, 51LR

3Ith>M
49M

ARC
50L/50NL

3I>>>
50P/51P

3I>/Io>BF
51BF/51NBF

Ist>
51LR

STANDARD
CONFIGURATION

ESC

Clear

AND

R
L

OR

COMMUNICATION

CONDITION MONITORING
AND SUPERVISION

3I

Protocols:
IEC 61850-8-1/-9-2LE1
1
Modbus
1
IEC 60870-5-103
1
DNP3
1

0
0
1
0
0
1 0

Io

3I>
51P-1

FUSEF
60

OPTS
OPTM

Io

CBCM
CBCM
2

1
1
0
1
1
1

0
1
0
1
0
1

0
0
1
0
0
0

Interfaces:
Ethernet: TX (RJ45), FX (LC)
Serial:
Serial glass fiber (ST),
RS-485, RS-232/485
D-sub 9, IRIG-B

MCS 3I
MCS 3I

TCS
TCM

0
0
1
1
0
0

1
1
1
1
1
1

1
0
0
0
1
0

Redundant protocols:
HSR
PRP
RSTP

Io

Io>>
51N-2

Io
MEASUREMENT

CONTROL AND INDICATION 1)


Object

Io>
67N-1

Uo

3U<
27

DC

ES

1)

U2>
47O-

U1<
47U+

UL1UL2UL3

f>/f<,
df/dt
81

Ind

3)

- I, U, Io, P, Q, E, pf, f
- Limit value supervision
- Load profile record
- RTD/mA measurement (optional)
- Symmetrical components

3)

CB

2)

UL1UL2UL3

Ctrl

2)

Analog interface types

Check availability of binary inputs/outputs


from technical documentation
Control and indication function for
primary object
Status indication function for
primary object

1)

Current transformer

Voltage transformer

1)

Conventional transformer inputs

ESTART
ESTART

REMARKS
18

MAP
MAP

6xRTD
2xmA

Optional
function

Calculated
value

3 No. of
instances
Io/Uo

OR Alternative
function to be
defined when
ordering

Protection function overview of the B configuration of REM615.

REM615 | Motor protection and control 3

Standard configurations

Standard configurations
Description
Motor protection, optional RTD/mA inputs, CB control and with the optional I/O module control of
two network objects
Motor protection with current, voltage and frequency based protection and measurement functions,
optional RTD/mA inputs, CB control and with the optional I/O module control of one network object
Motor protection with current, voltage and frequency based protection and measurement functions and CB control
Motor protection with current, voltage and frequency based protection and measurements functions,
CB condition monitoring, CB control and sensor inputs for phase currents and phase voltages

Supported functions, codes and symbols


Functionality
Protection
Three-phase non-directional overcurrent protection, low stage
Three-phase non-directional overcurrent protection, instantaneous stage
Non-directional earth-fault protection, low stage
Non-directional earth-fault protection, high stage
Directional earth-fault protection, low stage
Three-phase undervoltage protection
Positive-sequence undervoltage protection
Negative-sequence overvoltage protection
Frequency protection
Negative-sequence overcurrent protection for motors
Loss of load supervision
Motor load jam protection
Motor start-up supervision
Phase reversal protection
Thermal overload protection for motors
Circuit breaker failure protection
Master trip
Arc protection
Multi-purpose protection1)
Control
Circuit-breaker control
Disconnector control
Earthing switch control
Disconnector position indication
Earthing switch indication
Emergergency startup

4 Motor protection and control | REM615

Standard
configuration
A
B
C
D

1, 2,.. = number of included instances / I/Os


( ) = optional

IEC 61850

IEC 60617

IEC-ANSI

PHLPTOC

3I>

51P-1

PHIPTOC

3I>>>

50P/51P

EFLPTOC

Io>

51N-1

2)

EFHPTOC

Io>>

51N-2

2)

DEFLPDEF

Io>

67N-1

PHPTUV

3U<

27

PSPTUV

U1<

47U +

NSPTOV

U2>

47O -

FRPFRQ

f>/f<, df/dt

81

MNSPTOC

I2>M

46M

LOFLPTUC

3I<

37

JAMPTOC

Ist>

51LR

STTPMSU

Is2t n<

49, 66, 48, 51LR

PREVPTOC

I2>>

46R

MPTTR

3Ith>M

49M

CCBRBRF

3I>/Io>BF

51BF/51NBF

TRPPTRC

Master Trip

94/86

ARCSARC

ARC

50L/50NL

(3)

(3)

(3)

(3)

MAPGAPC

MAP

MAP

18

18

18

18

CBXCBR

I O CB
I O DCC
I O ESC

I O CB
I O DCC
I O ESC

I O DC
I O ES

ESSXSWI

I O DC
I O ES

ESMGAPC

ESTART

ESTART

DCXSWI
ESXSWI
DCSXSWI

1
1

3)

2) 5)

1
1

3)

2) 4)

1
1

3)

3) 6)

2(5)7)

2(5)7)

2(5)7)

2(5)7)

REM615 | Motor protection and control 5

Supported functions, codes and symbols


Functionality
Condition Monitoring
Circuit-breaker condition monitoring
Trip circuit supervision
Current circuit supervision
Fuse failure supervision
Runtime counter for machines and devices
Measurement
Disturbance recorder
Load profile record
Three-phase current measurement
Sequence current measurement
Residual current measurement
Three-phase voltage measurement
Residual voltage measurement
Sequence voltage measurement
Three-phase power and energy measurement, including power factor
RTD/mA measurement
Frequency measurement
IEC 61580-9-2 LE (Voltage sharing)

6 Motor protection and control | REM615

1, 2,... = number of included instances / I/Os


( ) = optional

IEC 61850

IEC 60617

IEC-ANSI

SSCBR

CBCM

CBCM

TCSSCBR

TCS

TCM

CCRDIF

MCS 3I

MCS 3I

SEQRFUF

FUSEF

60

MDSOPT

OPTS

OPTM

RDRE

DR

DFR

LPDMSTA

LOADPROF

LOADPROF

CMMXU

3I

3I

CSMSQI

I1, I2, I0

I1, I2, I0

RESCMMXU

Io

In

VMMXU

3U

3V

RESVMMXU

Uo

Vn

VSMSQI

U1, U2, U0

V1, V2, V0

PEMMXU

P, E

P, E

XRGGIO130

X130 (RTD)

X130 (RTD)

(1)

(1)

(1)

FMMXU

SMVSENDER

SMVSENDER

SMVSENDER

(1)

(1)

(1)




4)

5)

5)

6)

Multi-purpose protection is used for, for example, RTD/mA based protection, or Analogue Goose
Io selectable by parameter, Io measured as default
Io selectable by parameter, Io calculated as default
Uo selectable by parameter, Uo measured as default
Uo calculated and negative sequence voltage selectable by parameter, Uo calculated as default
Uo calculated is always used
Master Trip included and connected to corresponding HSO in the configuration only when BIO0007 module is used.
If additionally the ARC option is selected, then ARCSARC is connected in the configuration to the corresponding Master Trip input.
7)
Only available with COM0031-0034
1)
2)
3)

REM615 | Motor protection and control 7

ABB Oy, Medium Voltage Products


Distribution Automation
P.O. Box 699
FI-65101 VAASA, Finland
Phone: +358 10 22 11
Fax:
+358 10 22 41094
ABB Limited, Distribution Automation
Maneja, Vadodara 390013, India
Phone: +91265 260 4386
Fax:
+91265 263 8922
www.abb.com/substationautomation

1MRS 756902 F, 5.0

For more information, please refer to


REM615 Product Guide, or contact us:

Copyright 2014 ABB. All rights reserved.