You are on page 1of 120

ONGC TRIPURA POWER COMPANY LIMITED

TECHNICAL SPECIFICATIONS
FOR
INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

2 X 363.3 MW
GAS BASED COMBINED CYCLE POWER PLANT,

PALATANA, UDAIPUR, TRIPURA

(This document is meant for the exclusive purpose of bidding against this specification and shall not be
transferred, reproduced or otherwise used for purposes other than that for which it is specifically issued).

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT


TECHNICAL SPECIFICATION FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS
TABLE OF CONTENT
Clause No.
A.
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
B.
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
13.0
14.0
15.0
16.0
17.0
C.
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
13.0
14.0

Description
TECHNICAL SPECIFICATIONS FOR INTERIOR WORKS CIVIL
SPECIFICATIONS FOR INTERIOR WORKS
HARDWARE
METAL WORK
MIRROR
P O P PUNNING
GLASS AND GLAZING
PAINTING, WHITE WASHING, COLOUR WASHING & DISTEMPERING
BLINDS
STANDARD WORKMANSHIP
MATERIAL ORDER STATUS / RECEIPTS AT SITE
MODE OF MEASUREMENT OF WORKS
DESCRIPTION OF WORK: HOW MEASURED MULTIPLYING FACTOR
TECHNICAL SPECIFICATION FOR INTERIOR WORKS ELECTRICAL
GENERAL TERMS
REGULATION & STANDARDS
SCOPE OF WORK
POINT WIRING
MEASUREMENTS OF POINT WIRING
CIRCUIT WIRING, SUB-MAIN WIRING AND ITS MEASUREMENT
6 & 16 AMP SWITCH SOCKET OUTLET MODULAR RANGE
LIGHTING FIXTURE AND FANS
LAMP HOLDERS, CEILING ROSES & BALLASTS
TESTING & INSTALLATION
WIRING SPECIFICATION
SWITCH-OUTLET BOXES AND JUNCTION BOXES
CONDUCTORS
EARTHING
TESTING
SAFETY REQUIREMENTS
FIRE DETECTION AND ALARM SYSTEM
TECHNICAL SPECIFICATION FOR FURNITURE
SPECIFICATIONS FOR FURNITURE / INTERIOR WORKS
WOODEN STORAGES
STORAGES IN CONFERENCE ROOM
METAL STORAGES
CHAIR WITHOUT HEADREST
CHAIR WITH HEADREST
CHAIR WITH FIXED ARM
CHAIR WITH ADJUSTABLE ARM
READING CHAIR
CHAIR FOR CAFETARIA
3 SEATER SOFA IN OFFICE ROOM
CHAIR WITH CHROME BASE
CHAIR MESH TYPE WITH FIXED BASE
CHIARS

Page No.
06
10
11
12
13
14
16
17
17
17
18
18
21
21
22
23
24
25
25
26
26
27
28
32
33
35
38
39
40
45
47
47
47
48
48
49
50
51
51
51
51
52
53

15.0
16.0
17.0
18.0
19.0
20.0
21.0
22.0
23.0
24.0
25.0
26.0
27.0
28.0
29.0
30.0
31.0
32.0
33.0
34.0
35.0
36.0
37.0
38.0
39.0
40.0
D.
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
13.0
E.
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
Annexture-I
Annexure-II

STOOL FOR PATIENT


SOFA
MANAGER TABLE LAMINATED
MANAGER TABLE PRE-LAMINATED BOARD WITH SIDE STORAGE METAL
MODESTY
MAIN TABLE
CHAIRMAN TABLE IN VENEER FINISH
CENTER TABLE AND CORNER TABLE IN MANAGERS CABIN
CENTER TABLE AND CORNER TABLE
DISCUSSION TABLE
LAB WORKING PLATFORM
LOCKERS LAB
BENCHES IN LOCKER ROOM
DISPLAY BACK
TABLE FOR PLANT SCALE
READERS TABLE
WOODEN LIBRARY RACKS
TABLES (MAIN TABLE) WITH PEDESTAL, KETBOAD TREY & CPU TROLLEY
SINGLE BED IN HOSTEL
DOUBLE BED IN HOSTEL
BED FOR PATIENT
SEMINAR HALLL AREA
RECEPTION TABLE
MODEL AND CHART TABLE
CAFETARIA TABLE
METAL RACK
LECTURE ROOM TABLE
GENERAL SPECIFICATION FOR CEILING & PARTITION
GENERAL REQUIREMENTS
STANDARD WORKMANSHIP
CEILING WORK
POST CAP METAL CEILING SYSTEM
CANOPY METAL CEILING SYSTEM
CORRIDOR METAL CEILING SYSTEM
CLIP IN METAL CEILING SYSTEM
METAL BAFFLE CEILING SYSTEM
SINGLE GLAZING FULL HEIGHT PARTITION SYSTEM
SINGLE GLAZING FULL HEIGHT PARTITION SYSTEM (WITH METAL PANEL)
TIMBER WALL CLADDING
DOUBLE GLAZING FULL HEIGHT PARTITION SYSTEM
DOUBLE LAYER WOODEN PANEL PARTITION SYSTEM
TECHNICAL SPECIFICATION FOR SYSTEM INTEGRATION WORK
DISPLAY SYSTEM
SOURCE EQUIPMENTS
AUDIO RE-INFORCEMENT SYSTEM
CONTROL SYSTEM
CABLES AND CONNECTORS
OTHER MISCELLANEOUS ITEMS
AUDIO VIDEO SYSTEM FOR 100 SEATER AUDITORIUM
DISPLAY SYSTEM FOR LECTURE HALL SOLUTION
AUDIO RE-INFORCEMENT SYSTEM FOR EXECUTIVE TRAINING ROOM
BACKGROUND MUSIC SYSTEM FOR CANTEEN

53
53
54
55

LIST OF INDIAN STANDARDS


LIST OF APPROVED MAKES OF MATERIAL INTERIOR & CIVIL WORKS

96
99

56
57
58
58
58
59
59
60
60
60
61
61
62
63
63
63
64
64
64
65
65
66
68
69
69
70
72
74
76
78
79
81
82
83
84
88
88
88
89
89
89
90
94
94
95

Annexure-III

LIST OF APPROVED MAKES


LIST OF APPROVED MAKES
LIST OF APPROVED MAKES
LIST OF APPROVED MAKES
TENDER DRAWINGS

OF
OF
OF
OF

MATERIAL
MATERIAL
MATERIAL
MATERIAL

ELECTRICAL WORKS
CEILING
FURNITURES
SYSTEM INTEGRATION WORKS

101
102
102
103
117

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

TECHNICAL SPECIFICATION FOR INTERIOR WORK - CIVIL

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 5

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

1.

SPECIFICATIONS FOR INTERIOR WORKS

1.1.

GENERAL REQUIREMENTS.

1.1.1.

The section of the specification shall be read in conjunction with the Drawings,
other Contract Documents and other sections of these specifications which shall
be deemed to be complementary to one another. The Contractor carrying our
this work shall be responsible for providing all plant, tools, materials and all
things necessary for the proper execution, completion and maintenance of these
works.

1.2.

DIMENSIONS

1.2.1.

Figured dimensions shall be taken in preference to scaled dimensions in all


cases. Before commencing any work the Contractor shall verify all requirements
on the Site.

1.3.

SAMPLES

1.3.1.

A Sample of every item of furniture / paneling / cladding / flooring /false ceiling


all other components, including their parts shall be submitted for approval before
an order is placed or manufacture commences. Approved samples shall be used
as standards of finish and workmanship.

1.4.

JOINTS AND ADHESIVES

1.4.1.

All joints shall be standard Mortise and tennon / dowel / dovetail / cross-halved /
mitred / tongue & groove / rebated. Nailed butt joints will not be permitted
except where shown in the drawings. Where mortise and tennon joints are
shown in the drawings, tennon shall fit the mortises exactly. Adhesives shall be
resin based for all carpentry work and as per approval of the Project Manager /
Architect. Lap joints with glue shall be permitted in wood skirting.

1.5.

FASTENINGS

1.5.1.

Screws, nails etc, shall be of standard iron / wire unless otherwise shown on
drawings. Screws and nails for outdoor furniture shall be of brass or other noncorrosive metal. Exposed fastenings shall match the finish of hardware. Where
screws show on a finished surface, they shall, unless otherwise detailed, be sunk
and the hole plugged with wood plug of the same wood and grain of the finished
surface. Nails on finished surfaces shall be neatly punched and the hole filled
with wood filter to match. Filling putty over screw or nail holes shall not be
permitted.

1.6.

HARDWARE

1.6.1.

Hinges, locks, latches, door tracks, nail hides etc shall be as specified or an
approved substitute equal to or better than the specified.

1.7.

METAL

1.7.1.

Where metal legs, frames and the like are used, these shall be welded, brazed,
bolted or as required, and on finished surfaces, welding, brazing, and riveting
shall be ground so that no evidence of this is apparent on the final finish of the

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 6

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

metal. All legs of case or cabinet furniture whether of wood or metal, shall be
equipped with nylon glides or castors unless otherwise shown on the drawings.
1.8.

FINISH

1.8.1.

Finishes shall be fully in accordance with the drawings and schedules. Where
timber is in natural finish, pieces shall be matched for colour and grain before
assembly. Where timber is stained the stain shall be matched throughout.
Backs of wall-hung case of cabinet furniture shall be treated with an approved
brand of wood preservative.

1.9.

CUSHION VENTS

1.9.1.

Cushion vents shall be made in the back or underside of all seat cushions in
sufficient number to allow air to escape easily and prevent torn seams.

1.10.

MOISTURE CONTENT OF CARPENTRY

1.10.1.

The moisture content of timber during manufacture, delivery to the Site,


Storage, Site Working, Assembly and Installation shall have moisture content of
12% nominal.

1.11.

SUPERIOR QUALITY TEAK/PADAUK

1.11.1.

It shall be of good quality and well-seasoned. It shall have uniform colour,


reasonably straight grains and shall be free from large, loose, dead knots,
cracks, warps, twists, bends, borer holes, shakes, sapwood or defects or any
kind. No individual hard and sound knot shall be more than 1 cm. In diameter
and aggregate area of all knots shall not exceed % of the area of the piece. It
shall be close grained and there shall not be less than six growth rings per 2.5
cm. width.

1.12.

WOOD WORK

1.12.1.

Timber used shall confirm to specifications described under materials, shall be in


accordance with the Architects drawing in every details and all joiners work shall
accurately set out, framed and finished in a proper workmanlike manner. Frames
of partitions and opening, etc., shall be of accurately planned smooth and
rebates, roundings and mouldings shall be made as shown on the drawings.
Patching or plugging of any kind shall not be allowed. Joints shall be simple,
neat and strong.

1.12.2.

Framed joints shall be coated with suitable adhesive like glue or synthetic resin
before the frames put together. All mortice and tenon joints shall fit in fully and
accurately without wedging or filling. The joints shall be pinned with hardwood
or bamboo pins of 10mm to 12mm dia, or rust resisting star shaped metal pints
of 8mm dia, after the frames are put together and pressed in position by means
of a press. The frames shall be protected during the progress of work by
providing suitable boxing. All portions of timber abutting against or embedded in
masonry or concrete shall be treated against termites by giving a coat of any
approved wood preservative. All T.W. work should be painted with a cost of
approved wood primer.

1.12.3.

No extra measurements will be given for the shape, joints of the partitions
counter, tables work etc.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 7

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

1.12.4.

All work shall be measured net as fixed. No extra measurement will be given for
shape, joints, played meeting styles of doors and windows and shall be
measured in unit of square feet.

1.12.5.

Areas over one face inclusive of exposed frame thickness (excluding width of
cover mould) shall be measure in case of T.W. Doors, windows, and ventilators,
Louvers, Portions in masonry or flooring shall not be measured.

1.12.6.

Frames and shutters shall not be painted or erected before being approved by
the Client/Architects.

1.13.

Upholstery

1.13.1.

Where the upholstery fabric is patterned no upholstery fabrication is to


commence until the Contractor has received clear instructions concerning the
direction of the pattern and the method of its joining. Upholstery will be of first
class workmanship with webbing, no-sag springs, coiled springs, padding and
filling as specified. Covering fabrics will be sewn, tufted and corded as shown on
the drawings or schedules.

1.14.

PROTECTION, DELIVERY AND STORAGE

1.14.1.

While remaining in proper wrappers the timber shall be protected from extremes
of temperatures and direct sunlight.

1.14.2.

Internal joinery and joinery timber shall be kept in its original wrappers before
working, fixing and installing on Site.

1.14.3.

All joinery to be painted shall be approximately sealed with the specified primer
to all faces before leaving its place of manufacture. All joinery to be varnished /
spirit polished shall be sealed with at least one coat of specified varnish polish at
all faces before leaving its place of manufacture. All joinery and joinery timber
shall be wrapped in proper cover before and during transport and delivery to
Site.

1.14.4.

Proper warping to external joinery and timber shall be removed on delivery to


Site or as previously specified.

1.14.5.

All timber used shall be kiln seasoned. Fire Retardant paint shall be used on all
hidden timber wherever indicated / specified anywhere in the drawings,
specifications and the various parts of this Document. All woodwork exposed or
unexposed done by the Contractor shall be coated in a colourless fire retarding
paint of brand approved by CBRI and Fire authorities. The painting work shall
be done by soft brushes, and by pencil brushes in corners etc. The rate would
include providing all material brushes etc. No extra payment would be made for
the same.

1.15.

BUILDERS HARDWARE

1.15.1.

All hardware fittings and fixtures shall be made with structural properties to
sustain safety and withstand strains and stresses to which they are normally
subjected to such as opening and closing, wind pressure etc. The fittings shall
generally conform to relevant specifications.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 8

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

1.15.2.

They shall be made true, clear straight with sharply defined profiles and unless
otherwise shown or specified with true smooth surfaces and edges, free from
defects. Screw holes shall be counter sunk to suit the head of wood screws.

1.16.

MELAMINE FINISH - GLOSSY/ NATURAL : TECHNICAL DATA

1.16.1.
1.16.2.
1.16.3.
1.16.4.
1.16.5.
1.16.6.
1.16.7.
1.16.8.

Thinner recommended : Brushing Thinner 106


Spraying Thinner 124
Mixing ratio : Base to hardener in 10:1 by volume
Drying Time : 8 Hours
Surface dry-less than 30 minutes
Hard Dry 16-20 hours
Re-coating period-overnight
Finish : 25 microns film thickness smooth and glossy

1.16.9.

Flash point: Above 14 degree C (57 degree F) Sand the surface along the grains
with Emery paper No: 180 or with a suitable grade sand paper. Brush the
surface free of loose dust. Fill the wood using wood filler. Remove excess filler
immediately after applications. Allow 2-3 hours of drying before sanding with
Emery paper no: 240-280. If desired, apply Apcolite wood stains by ragging
after filling step or mix it in Natural Wood Finish upto 20% by volume and apply
by spraying after Sealer Coat. In application by ragging allow a drying time of 510 minutes in between coats and 30-60 minutes before over coating with finish
coats. Apply a coat of Natural Wood finish Clear Sealer. After overnight drying,
smooth sand with Emery Paper No: 320 and wipe the surface free of loose dust.
Apply Apcolite Natural Wood Finish Clear Glossy as follows. Ensure that the
surface to be coated is free from loose matter. Natural Wood Finish clear Glossy
is a two component system consisting of base and hardener. These should be
mixed in a glass, plastic or enameled container. Allow the mixture to stand for
30 minutes and then apply by brushing or spraying using the recommended
thinner for consistency adjustment. The mixture of base and hardener should be
used within 8 hours. To enhance gloss and decorative value Natural Wood Finish
Clear Glossy can be buffed using suitable buffing mops but only after 48 hours
of application.

1.17.

KAILWOOD / MARANDI

1.17.1.

Wherever kailwood is specified it shall mean First Class Kailwood / Marandi


/equivalent as per approval of the Project Manager / Architect / ACE.

1.18.

PLASTIC LAMINATE VENEER

1.18.1.

Plastic decorative laminated veneer sheeting shall be ISI marked or the brand,
catalogue number and colour indicated and approved. The laminated veneer
shall be 1.5 mm thick on flat surfaces and 1 mm thick on curved surfaces unless
otherwise approved.

1.18.2.

Plastic laminate veneer shall be fire retardant to Class 1 of BS: 476 or ISI Code
where specified.

1.18.3.

Lengthwise on horizontal surfaces

1.18.4.

Vertical on vertical surfaces

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 9

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

1.18.5.

Horizontal on edges of top surfaces and shelves.

1.18.6.

No surface sanding of laminated plastics will be allowed.

1.18.7.

Unless otherwise specified, all laminated plastics shall have a standard matt or
suede finish unless where mentioned.

1.18.8.

Samples of laminated plastics showing the surface texture and pattern shall be
submitted for approval before fixing.

1.19.

Particle Board / Graded Particle Board

1.19.1.

The Particle board shall comply with ISI specifications and shall be one made
from wood particles and flat pressed with synthetic resin and/or organic binder.
Thickness shall vary as shown on drawings.

1.19.2.

Particle board shall not be used externally or internally in any essentially damp
surroundings.

1.19.3.

Manufacturer and reference for Particle Board shall be subject to approval.

1.20.

SAMPLES OF VENEER

1.20.1.

The Contractor shall submit a sample of each type of veneer for approval before
general fabrication is started.

1.20.2.

Interior Designing and Fabrication of Foam Panels : Panels shall be Interior


Designed of fabric on foam on new timber framing with insulation quilt in-fill.

1.20.3.

Framing shall be Interior Designed of approved sections as per drawing and


adequately braced to ensure rigidity. All outer exposed edges and corners shall
be pencil rounded. Joints shall be subject to approval. Screws and nails shall be
counter sunk and punched below the surface.

1.20.4.

The fabric shall be back faced with synthetic foam. The foam shall cover all
outer edges and corners of the framing and securely fixed in place to the back of
the framing with approved marking cloth.

1.20.5.

The fabric shall be evenly stretched over the foam covered framing to obtain a
tight flat and evenly finished surface. The fabric sha8ll be returned over the
framing edges and lapped 50mm over the back face of the framing and securely
fixed.

1.21.

PROTECTION OF PANELS

1.21.1.

Panels shall leave the factory in perfect condition and in protective wrappers and
be properly protected from damage.

1.21.2.

Panels shall be stacked in dry well-ventilated conditions off the ground. The
original protective wrappers shall be removed immediately prior to installation of
the panels.

1.21.3.

The Contractor shall be responsible for protecting all items of work in this
section in these areas of work forming part of his own expense any damaged
work caused through lack of adequate protection or care in installation or
handling.

1.21.4.

The Contractor shall make his own investigation to guard against local sources of
attack and damage and take all necessary precautions of protection.

2.

HARDWARE

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 10

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

2.1.

Hinges, locks, latches, door tracks etc shall be in SS brushed steel finish or as
specified and as far as possible of specified manufacture. In case of any
variation in quality, the substitute shall be equal to or better than the originally
specified and the sample should be submitted to the Architect for prior approval.

3.

METAL WORK

3.1.

The Contractor shall furnish all materials, labour, operations, equipment, tools,
plant and incidentals necessary and required for the completion of all metal work
as called for in the Drawings. The Drawings and Specification cover the major
requirements only. The supplying of additional fastenings, accessories, features
and other items not mentioned specifically herein but which are necessary to
make a complete installation shall be part of this Contract.

3.2.

All metal work shall be free from defects importing strength, durability and
appearance and shall be of the best commercial quality for purposes specified,
made with structural properties to withstand safety strains, stresses to which
they shall be normally subjected.

3.3.

SAMPLES OF METAL WORK

3.3.1.

Samples of all typical metal work shall be fabricated assembled and erected or
sub mitted to the Architect as directed by him for approval.

3.3.2.

Where metal legs/frames/sheets etc are used, these shall be welded, brazed,
bolted or riveted as required. On finished surfaces welding, brazing and riveting
shall be neatly smoothed so that no evidence of this is apparent on the final
finish of the metal which will be specified in the drawing.

3.3.3.

On all legs, wood or metal, nylon glides or castors as indicated are to be


installed.

3.3.4.

BUTT HINGES : These shall be of the heavy duty S.S. (14 gauge) of powder
coated of size required with powder coated screws. M.S. hinges shall be
manufactured by casting, unless it is specifically mentioned that the same shall
be extruded type in which case these shall be manufacturer from extruded
sections. Hinges shall be finished as specified in the respective items. The size of
butt hinges shall be taken as length of the hinge.

3.3.5.

FLOOR SPRING AND PIVOT: Hydraulically regulated floor spring and pivot shall
be conforming to IS for heavy duty performance. Suitable adjustments shall be
made such that the closing time can be raised five seconds to twenty-five
seconds. The oil filling shall work well in all seasons and shall not show any
signs of leakage of oil under working conditions. The supplier shall supply along
with the closer a wrench and spanner for carrying out adjustments. Payments
shall be made per number and includes supply of all accessories, fixing the door
pivot/ floor spring, anodizing / painting etc complete as per directions of Project
Manager.

3.4.

PAINTING-OIL/ENAMEL/PLASTIC EMULSION ETC.

3.4.1.

Ready mixed oil paint, plastic, emulsion paint, ready mixed synthetic enamel
paint, Aluminium paint, etc. shall be brought in original containers and in sealed
tins. If or any reason thinner is necessary the brand and quantity of thinner
recommended by the manufacturers or as instructed by the Architects shall be
used.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 11

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

3.4.2.

The surface shall be prepared as specified above and cost of approved primer
shall be applied. After 24 hours drying, approved if specified quality paint shall
be applied evenly and smoothly. If required a filler putty coating may be given to
give smooth finish. Each coat shall allowed to dry out thoroughly and then lightly
rubbed down with sand paper and cleaned of dust before, the next coat is
applied. Number of coats shall be as specified in the item and if however the
finish of the surface is not uniform additional coats as required shall be applied
to get good and uniform finish at no extra cost. After completion no hair marks
from the brush or clogging of paint puddles in the corners of panel angles of
mouldings shall be left on the work. The glass panes floor etc. shall be cleaned
of strains.

3.4.3.

When the final coat is applied, if directed, the surface shall be rolled with a rolled
or if directed it shall be stippled with a stippling brush.

4.

MIRROR

4.1.

GENERAL REQUIREMENTS OF MIRROR

4.1.1.

This section of the Specification shall be read in conjunction with the Drawings
and Schedules and other section of the Specification which shall be deemed to
be complimentary to one another. The Contractor carrying out this work shall
be responsible for providing all plants, tools, materials and all things necessary
for the proper execution, completion and maintenance of these works.

4.2.

SAMPLES OF MIRROR

4.2.1.

The Contractor shall submit samples of all glass and mirror types for approval.
/these shall be obtained from an approved source.

4.3.

DELIVERY AND STORAGE OF MIRRORS

4.3.1.

Delivered materials, shall match the approved samples, packaged materials shall
be delivered in the original, unopened, labeled containers of the manufacturer
clearly marked with their name and brand.

4.3.2.

Mirror shall be stored while awaiting installation in a dry, well-ventilated location


at a constant temperature maintained above dew point.

4.3.3.

Handling of mirrors shall be kept to a minimum.


against soiling, condensation, etching and the like.

4.4.

MARKING MIRROR

4.4.1.

Manufacturers or job marking on mirror and adhesive for manufacturers labels


shall not be alkaline but shall be either neutral or slightly acidic so that it is
removed after its installation.

4.5.

CUTTING MIRROR

4.5.1.

Cutting of mirrors shall be in accordance with site measurements or dimensions.


Mirror shall be fabricated from clear plate or float glass of the quality and finish
shown in the Drawings and Schedules unless otherwise required.

4.6.

THICKNESS OF MIRRORS

Mirrors shall be protected

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 12

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

4.6.1.

All fixed panel mirrors shall be as per specification given by Architect unless
otherwise stated having plus/minus 0.30mm tolerance.

4.7.

EDGES OF MIRRORS

4.7.1.

All edges of mirrors shall be polished, beveled, corner mitered to ISI


Specifications or as indicated in the drawing.

4.8.

DRILLING OF MIRRORS

4.8.1.

All drilling of holes shall be carried out at the stage of fabrication. No chipping,
starring and other visible imperfections around holes will be accepted.

4.9.

FIXING OF MIRORS

4.9.1.

Panels shall be securely fixed with screw on Z clips at minimum 600mm


centers horizontally and 1200 mm centers vertically.

4.9.2.

Mirrors shall be fixed to backings by adhesive or special fixings as shown on the


drawings or as otherwise specified using CP cap screws.

4.9.3.

Screws shall be of brass with collars and screw-on domes unless otherwise
specified.

4.10.

FINISHING OF FIXINGS

4.10.1.

All visible metal fixings shall be of approved finish to match mirror finish and
colour.

4.11.

ADHESIVES FOR MIRRORS

4.11.1.

Adhesives shall be as recommended by the silvering manufacturer and used in


accordance with the manufacturers recommendations.

4.12.

JOINTS OF MIRRORS

4.12.1.

Paper thin joints shall separate all adjoining sections of mirrors.

4.13.

PROTECTION OF MIRRORS

4.13.1.

Mirror shall be protected from paint, plaster, welding splatter, Interior Designing
scum and the like. Should any such soiling occur, the mirror shall be promptly
and completely washed off as specified below.

4.13.2.

Mirror generally shall be protected with temporary wooden barricades or other


warning devices as a deterrent against passing objects through glazed openings.

4.14.

CLEANING OF MIRRORS

4.14.1.

When directed by the Architect, the Contractor shall remove all markings and
labels from mirror and wash the mirror with mild neutral or slightly acidic
solution as recommended by the mirror manufacturer. Alkaline or abrasive
solutions should not be used.

5.

P O P PUNNING

5.1.

GENERAL

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 13

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

5.1.1.

Plaster of Paris punning (Plaster) is generally applied on already cement


plastered surface to give it a smooth and even surface.

5.2.

PREPARATION OF SURFACE

5.2.1.

Projecting burrs of mortar existing on cement plaster shall be removed. The


surface shall be scrubbed clean with wire brushes. In addition the plastered
surface shall be pock marked with pointed tool, at spacing of nor more than 4
cms c/c and depth of pock to be approx. 3 mm. This is to ensure a proper key
for the plaster. The surface shall be cleaned of all grease marks etc.

5.3.

PLASTER OF PARIS

5.3.1.

The Plaster of Paris shall be of semi-hydrate variety Calcium Sulphate. Its


fineness shall be such that when sieved through a sieve of ISI sieve designation
3.35 mm for 5 minutes after drying the residue left on it shall be not more than
1% by weight. It shall not be too quick setting. Initial setting time should not
be less than 13 minutes.

5.4.

APPLICATION OF PLASTER OF PARIS

5.4.1.

The material will be mixed with water to a workable consistency. Plaster of Paris
shall be applied directly on the wall plaster in suitable size panels and finished to
a smooth surface by steel trowels. The plaster shall be applied in such a manner
that it fully fills the gaps, and the thickness over the plastered surface is as
specified in the description of the item.

5.4.2.

The finished surface shall be smooth and true to plane, slopes or curves as
required.

6.

GLASS AND GLAZING

6.1.

EXTENT AND INTENT

6.1.1.

The Contractor shall furnish all materials, labour, tools, appliances, equipment
and INCIDENTALS REQUIRED TO COMPLETE THE INSTALLATION OF ALL GLASS
AND RELATED ITEMS.

6.1.2.

All glass shall be of the type, quality and substance specified. All glass shall be
first class in every respect and conform to ISI: 1761-1960. The glass shall be
100% free from blisters, stains, scratches and bubbles so as not to distort
visibility.

6.2.

GLASS SIZES

6.2.1.

The Contractor shall cut glass sizes by field measurements or dimensionally


approved shop drawings. The responsibility for correct glass sizes shall rest with
the Contractor. No cracked, chipped or disfigured glass shall be accepted.

6.3.

GLASS BREAKAGE

6.3.1.

The Contractor shall replace all broken, damaged and disfigured glass caused in
executing the work or by faulty installation before hand-over, at his own cost.

6.4.

MELAMINE FINISH

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 14

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

6.4.1.

Timber works shall be finished by the application of two coats of an acid


catalyzed clear lacquer (melamine) wherever it is indicated in the drawing. The
finish shall be a satin, semi-gloss finish and shall be carried out as follows:

6.4.2.

The base shall be sand papered to the desired finish and coated with a colour
tinge to give it shade. The shade shall be sealed with a coat of spirit finish.

6.4.3.

After the base, first coat of lacquer shall be applied evenly by a soft cloth or by
spray to give an even coat to the veneer surface.

6.4.4.

After the first coat has fully dried, the lacquered surface shall be rubbed down in
the direction of the veneer grain with very fine glass paper and left completely
smooth and clean before the second coat is applied.

6.4.5.

When the second coat of lacquer is fully dry, the surface shall be rubbed down in
the direction of veneer grain with very fine wire wool dipped in a petroleum
based wax to give lubrication.

6.4.6.

Twenty-four hours after completion of this process the lacquered veneer surface
shall be finished by burnishing with a soft cloth to an approved finish.

6.5.

MATERIALS FOR GLASS

6.5.1.

Glass for all glazing work shall be plain flat glass as called for in the Drawings
and schedules. Flat glass for glazing shall be 6 mm / 8 mm thick special selected
quality glass as called for, manufactured by Saint Gobain / Modifloat or other
equivalent as approved by the Architect.

6.6.

TOUGHENED GLASS

6.6.1.

The toughening of glass, where called for shall be carried out by M/s. Hindustan
Safety Glass Works or M/s. Atul Glass Works or any approved vendor to the best
standards available standards.

6.7.

GLAZING COMPOUND

6.7.1.

Glazing putty for setting glass shall be approved quality (Shalimar or approved
equivalent) suitable for use on metal windows and conforming to ISI 420-1953.
Gasket and Glazing shall be of Neoprene or EPDM of approved quality and make.

6.8.

PREPARATION OF FRAMES AND GLASS


Before installation the Contractor shall ensure that
All glazing rebates are square, plumb and true in plane, clear, dry and dust
free.
All frame adjustments are made prior to glazing.
All glass edges are clean, cut to exact sizes and grout properly allowing for
expansion tolerance as recommended by the glass manufacturer.
All sashes shall be glazed in the closed position and shall not be opened until
the compound is set.
All materials are used in strict accordance with the manufacturers
instructions.
Glass shall not be forced into place.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 15

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

All rebates / beadings etc to be pre-polished.


6.9.

GLAZING

6.9.1.

All glass is to be of approved manufacturer of approved quality and shall be free


from bubbles, smokes, waves, air holes and other defects. The kind of glass to
be used shall be as mentioned in the item or specification or in the special
provisions or as shown in detailed drawings. Thickness of glass panel shall be
uniform. All glass to be approved manufacture complying with IS: 3548 196 or
as per approved quality and sample.

6.9.2.

The compound for glazing to metal is to be special non-hardening compound


manufacture for the purpose and of 9 brand and quality approved the EIC.

6.9.3.

While cutting glass, proper allowance by made for expansion. Each square of
glazing to be in one whole sheet. On completion of work, all glass shall be
cleaned inside and outside and all cracked scratched and broken panes shall be
replaced and left in a good condition.

6.9.4.

All exposed edges of glass shall be lead polished.

6.10.

INSTALLATION & COMPLETION OF GLASS

6.10.1.

The glass shall be set on Neoprene or EDPM blocks on all sides. Glass shall be
bedded back and face and so installed as to achieve a completely water tight
and rattle free installation. The odd glass where called for shall be set with
smooth surface outside.

6.10.2.

Upon the completion of the work all glass shall be thoroughly cleaned, paint or
other marks removed. Any cracked, scratched, chipped or other defective glass
shall be removed and replaced without cost of Owner. Any loose glass shall be
set to the satisfaction of the Architect.

7.

PAINTING, WHITE WASHING, COLOUR WASHING & DISTEMPERING

7.1.

PAINT AND POLISHING

7.1.1.

All materials required for the works shall be of a specified and approved
manufacturer, delivered to the site in the manufacturers containers with the
seals etc unbroken and clearly marked with the manufacturers name or
trademark with a description of contents and colour. All material to be stored on
the Site of works.

7.1.2.

Spray painting with approved machines will be permitted only if prior written
approval has been obtained from the Architect. No spraying will be permitted in
the case of priming coats or where soiling of adjacent surface is likely to occur.
The nozzle and pressure to be so operated as to give an even coating
throughout to the satisfaction of Architect. Thinning of paint made for brushing
will not be allowed.

7.1.3.

Wood preservation shall be Soligam or any other equal / approved impregnating


wood preservative and all concealed woodwork shall be so treated.

7.1.4.

All brushes, tools, pots, kettles etc used in carrying out the work shall be clean
and free from foreign matter and are to be thoroughly cleaned out before being
used with a different type or classes of material.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 16

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

7.1.5.

All iron or steel surfaces shall be thoroughly scrapped and rubbed down with
wire brushes and shall be entirely free from rust, mill scale etc before applying
the priming coat.

7.1.6.

Surface of previous painted metal which are to be repainted shall be cleaned and
flattened down as described in surfaces of previously painted woodwork. Minor
areas of defective paint and any rust / loose scales shall be removed completely
by chipping, scraping and wire brushing back to the bare metal and touched up
with primer as described.

7.1.7.

Surfaces of new wood-work which are to be painted are to be rubbed down for
approval of the Architect prior to application of paint.

7.1.8.

Surfaces of previously painted woodwork which are to be repainted shall be


cleaned down with soap and water, detergent solution or approved solvent to
remove dirt, grease etc whilst wet the surface shall be flatted down with a
suitable abrasive and then rinsed down and allowed to dry. Minor areas of
defective paint shall be removed by scraping back to a firm edge and the
exposed surface touched up with primer as described and topped with putty.
Where woodwork has been previously painted or polished and is to be newly
polished, the same shall be prepared with scraping, burring off or rubbing down.

8.

BLINDS

8.1.

Providing and fixing roller blinds with 38mm OD roll formed and lock seamed
steel of 0.5mm thickness suitably protected against corrosion.

8.2.

Chain drive unit shall be of high engineering grade moulded plastic with steel
support pin enclosed in a plastic housing and inserted into the control tube
end.it shall be driven by a ball chain pulley attached to a specially designed
clutch mechanism, forming a continuous loop.

8.3.

Control Ball chain shall be composed of braided nylon cord (2mm dia.) with high
engineering grade plastic beads of 4.5mm diameter mounted co-axially on the
cord with a pitch of 6.2 mm (C-T-C). It is used for raising or lowering the shade.

8.4.

Bottom rail shall be aluminium tube, anodized with a diameter of 20mm and
thickness of 0.5mm. The return end cap bracket shall incorporate a snap spring
design to facilitate easy installation and removal for maintenance activities. The
bracket shall be finished with a flush mounting cover on each side providing an
aesthetic finish. The clutch should mount flush to the face of the bracket, which
minimizes the light gap between the shade and the window frame.

9.

STANDARD WORKMANSHIP

9.1.

To determine the acceptable standard of workmanship, the Contractor shall


execute a portion of the items of work as sample, for approval of the Architect,
before taking up the actual execution of the particular item of work.

9.2.

These samples, on approval of the Owner / Architect, shall be the guiding


sample for execution of the particular item of work. Work not conforming to the
approved sample shall be rejected. Rates quoted for the items shall include for
such preliminary work and shall not be paid for separately.

10.

MATERIAL ORDER STATUS / RECEIPTS AT SITE

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 17

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

10.1.

The Contractor shall inform the Project Manager as regards the quantity &
quality of the material received / available on site. The Project Manager shall
check the material stock for quantity as well as quality. He may or may not give
any prior notice to the Contractor before such a check. The Contractor shall
ensure that the Project Manager has full access to his stores at all times.

11.

MODE OF MEASUREMENT OF WORKS

11.1.

The measurement of works carried out by the Contractor shall be taken in


accordance with procedure set forth in the Priced Schedule of Quantities /
Specifications, notwithstanding any provision in the relevant standard Method of
Measurement. In case of items not covered by the Schedule of Quantities /
Specifications, measurements shall be taken in accordance with the relevant BIS
Mode of Measurement.

11.2.

Pre-measurements to the recorded for all dismantling items before starting of


the works.

11.3.

The Project Manager may from time to time advise the Contractor to measure
the work done and the Contractor shall forthwith attend or send a qualified
representative to assist the Project Manager in taking such measurements and
calculations and shall furnish all particulars or give all assistance required.

11.4.

Should the Contractor not attend or neglect or omit to send such representative
then the measurements taken by the Project Manager shall be taken to be
correct measurements of the work.

11.5.

The Contractors representative may note joint measurements along with the
Project Manager.

11.6.

All authorized extra work, omissions and all variations made without the Project
Manager knowledge, if subsequently sanctioned by him in writing shall be
included in such measurements.

11.7.

On completion of measurements of certain work up to a particular stage, these


shall be signed and dated by both the Project Manager and the Contractor as a
token of their acceptance. If the Contractor objects to any of the measurement
recorded by the Project Manager, a note to that effect shall be made in the
Measurement Book against the item objected to and such note shall be signed
and dated by both parties.

12.

DESCRIPTION OF WORK: HOW MEASURED MULTIPLYING FACTOR

12.1.

Panelled, framed, ledged, braced Measured flat shall be measured as 1/3rd and
shall not be measured as 1. Battened girthed) including Frames, edges, checks
Cleats, etc., shall be deemed to be including in the item.

12.2.

Flush, part panelled and part Glazed or gaused do -- 1 (for each side)

12.3.

THE RATES QUOTED SHALL BE INCLUDING ALL WASTAGES. THE


MEASUREMENT WILL BE TAKEN ON THE LAID AREA AND FOR THE FINISHED
PRODUCT ONLY.

SCOPE OF WORK IS DETAILED IN BILL OF QUANTITY (BOQ) & TENDER


DRAWINGS (REFER FORM 1-D OF SCHEDULE OF PRICES). IN CASE OF ANY
TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 18

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

CONFLICT WITH THE GENERAL SPECIFICATION SPECIFIED ABOVE AND THE BILL
OF QUANTITY(BOQ) AS PER FORM-1D, THE TECHNICAL SPECIFICATION
MENTIONED IN BILL OF QUANTITY ( FORM 1 D) SHALL PREVAIL.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 19

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

TECHNICAL SPECIFICATION FOR INTERIOR WORK ELECTRICAL

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 20

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

GENERAL SPECIFICATION FOR ELECTRICAL WORK- MEDIUM VOLTAGE


DISTRIBUTION SYSTEM (Internal Lighting , Power wiring,
Data
&
Voice Cabling)
1.0

GENERAL TERMS

1.1

The entire electrification work shall be carried out by licensed Electrical


Contractors in accordance with these specifications without any extra cost.

1.2

For site supervision the contractor must depute an qualified electrical engineer.
The contractor shall employ only experienced and licensed wiremen to do the
electrification work.

1.3

The work shall conform to relevant Indian Standard Specifications the I.E. Acts
and Rules and the requirements of Local Electrical Authority.

1.4

When the installation is complete, the same shall be tested with the 500 /1000
volts Megger in the presence of the Architect / Consultant and the results shall
be entered into the test certificate as per the format available with Local
Electrical Authority.

1.5

Contractor shall submit to the client 3 sets of test certificates for the installation.

1.6

The contractor shall carry out all civil works connected with the electrical job.
The contractor shall repair and make good the damages caused by him to the
civil structure, HVAC and Fire protection System or other specified work while
executing the electrification work. The foundations for the panel board and for
the poles, grouting of frames in the wall, erection of D.B./switchboards in the
wall/chasing the walls for embedding the conduits and boxes etc. are all to be
carried out by the contractor including making good the damaged civil work.

1.7

The Contractor has to submit shop drawings for the Electrical Distribution Boards
and the conduit layout to the Architect/Consultants for their approval before
starting the work. Also one set of
approved sample of the materials have to
be kept at site.

1.8

The Architect/Consultant will issue the drawings to the Contractor for carrying
out the work.

1.9

The Electrical Contractor ,his wiremen and supervisors shall be qualified and
have a valid licence while quoting as well as during the course of work.

2.0

REGULATION & STANDARDS

2.1

The system shall be governed by the requirements of IS: 732 and I.E. Rules and
NEC. IS Standards and Codes applicable for medium voltage distribution is also
listed in specification.

2.2

The definitions of terms shall be in accordance with IS: 732-1989 (Indian


Standards Cods of Practice for Electrical Wiring), except for the definitions of
point, circuit, & sub-main wiring, which are defined in clauses hereunder.

2.3

The conventional signs & symbols for technical work shall be as shown in
drawing.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 21

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

SCOPE OF WORK
The scope of work shall be generally as given in the Bill of Quantities of items
and as mentioned below :-

3.0

A. Supply, Installation, Testing and Commissioning of the following :


i.
ii.
iii.
B.

Conduiting and wiring for lighting fixtures, Ceiling fans and Exhaust
fans ,Computer & Telephone System in False Ceiling/wooden
partition walls/floor/columns/brick or concrete walls/M.S. Channel.
All types of lighting fixtures, Ceiling fans and Exhaust fans.
Providing floor channels and Junction Boxes for drawing data cabling
and power wiring for work stations.

Testing and commissioning of the entire Electrical Installation


Telephone system.

including

The contractor shall carry out and complete the work under this contract
in every respect in confirming with the current rules and regulations of the
NBC(NATIONAL BUILDING CODES), stipulations of the Indian Standard
Institution, and with the directions of and to the satisfaction of the owner. The
contractor shall furnish all labour, material, appliances, equipment,
transportation and incidentals necessary for providing, installing, testing and
commissioning of the whole electrical installation as specified herein and shown
on drawings.
This also includes any materials, appliances, equipment and incidental
work not specifically mentioned herein or noted on the drawings/documents as
being furnished or installed but which are customary to make the installation in
working order. The work shall include all incidentals and jobs connected with
Electrical installation such as earthing work and cutting chases/holes and making
good the same and grouting etc.
NOTES:
i.

All items of work under the contract shall be executed strictly in accordance with the
description of the item in the Bill of Quantities, relevant drawings and Specifications
read in conjunction with the appropriate Indian Standard Specifications, Indian
Electricity rules as amended up to date and Conditions of Contract.

ii. The rate for each item of work included in the Schedule of Quantities shall unless
expressly stated otherwise, include cost of:
a. All materials, fixing materials, accessories, operations, appliances, tools, plant,
equipment, transport, labour and incidentals required in preparation for, in the
full and entire execution and completion of the work called for in the item and as
per specifications and drawings completely.
b. Wastage on materials and labour.
c.

Loading, transporting, unloading, handling/double handling, hoisting to all levels,


setting, fitting and fixing in position, protecting, disposal of debris and all other
labour necessary in and for the full and entire execution and to fully complete the
job in accordance with contract documents, good practice and recognised
principles.

d. Liabilities, obligations and risks arising out of conditions of contract.


TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 22

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

e.

In the event of conflict between schedule of quantities and other documents


including the specifications, the most stringent shall apply and the interpretation
of the Chief Architect shall be final and binding.

iii.

The Contractor shall be paid for the actual quantity of work executed by him in
accordance with the drawings at the contract rates.

iv.

All errors in totaling the amount column and in carrying forward totals shall be
corrected.

v.

Unless otherwise stated all measurements shall be taken in accordance with Indian
Standard Electrical Installation in building Method of Measurement IS 5908 latest
revisions/ additions.

vi.

On the completion of the work the Contractor shall submit to the Owner layout
Drawings indicating the complete Electrical Installation as installed . These Drawings
shall in particular give the following information.
i.
ii.
iii.
iv.
v.
vi.
vii.
viii.

Run and size of conduit, location of inspection/outlet boxes.


Number and size of wires in each conduit.
Location of switches, outlets, DBs, Telephone, Call Bell & Music outlets etc.
Layout and particulars of mains and sub-mains and cable route etc.
Schematic diagrams for the complete Electrical System.
Complete Earthing System with size of Earthing conductors.
Layout and particulars of the Telephone and Computer system.
Substation Equipments Layout.

4.0

POINT WIRING

4.1

A point (other than socket outlet point) shall include all work necessary in
complete wiring to the following outlets from the controlling switch or MCB. The
scope of wiring for a point shall however, include the wiring work necessary in
tapping from another point in the same distribution circuit.

4.2

Ceiling rose or connector (in the case of points for ceiling/ exhaust fan points,
prewired light and call bells)

4.3

Ceiling rose (in case of pendants except stiff pendants).

4.4

Back plate (in case of stiff pendants).

4.5

Lamp holder (in case of goose neck type wall brackets, batten holders and
fittings which are not prewired).

4.6

In case of call bell points, the words controlling switch or MCB shall be read as
from the ceiling rose meant for connection to bell push.

4.7

Supplying and fixing/ drawing of cables in conduits including connections.

4.8

Supplying and fixing wood battens, bends, corners, fillers, tee-pieces etc.
required for wiring on battens.

4.9

Metal switch boxes for control switches, regulators, sockets etc. recessed or
surface type, and

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 23

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

4.9.1

Phenolic laminated sheet covers over the same for piano type switches.

4.9.2

Modular covers over the same for modular type switches and MCBs.

4.10

Supplying and fixing all accessories such as screws, clips, plugs, clamps etc. as
specified for securing, cables, battens, conduits etc. to walls, steel joists etc.

4.11

Supplying and fixing of bushed conduit or porcelain tubing for wiring to pass
through walls, floors, etc.

4.12

Supplying and fixing of joint and junction boxes.

4.13

Control switch piano type, modular type, MCB as specified in the BOQ.

4.14

Cutting holes in or through walls, taking up and re-fixing floor boards, notching
or drilling holes thorough joists and making good all disturbed work to match the
existing.

4.15

Shellac varnishing as specified to wood battens, wood blocks and other wood
fittings and fixtures.

4.16

Pointing of battens and cables or surface conduits along with painting of walls.

4.17

Testing as specified.

5.0

MEASUREMENTS OF POINT WIRING

5.1

POINT WIRING (OTHER THAN SOCKET OUTLET POINT)

5.1.1

The measurement would be as specified in the Bill of Quantity i.e RMt or as per
CPWD works manual.

5.1.2

No separate measurement shall be made for interconnections between points in


the same distribution circuits & for the circuit protective (loop earthing)
conductors between metallic switch boxes.

5.2

POINT WIRING FOR SOCKET OUTLET POINTS.

5.2.1

The light plug 5A/ 6A & power plug 15A/ 16A points wiring shall be measured as
specified in the Bill of Quantity i.e RMt, from the respective tapping point of live
cable viz switch box, another socket outlet points, or the sub distribution board
as the case may be upto the socket outlet.

5.2.2

The metal box with cover, switch/ MCB, socket outlet & other accessories shall
be measured shall be measured as specified in the Bill of Quantity.

5.2.3

The power point outlet may be 15A/ 15A or 16A/ 16A six/ three pin socket
outlet, where so specified in the tender documents.

5.3

GROUP CONTROL/ LOOP POINTS WIRING

5.3.1

In the case of points with more than one point controlled by the same switch,
the same point shall be measured in parts i.e.

5.3.2

From the switch to the first point outlet as one point and

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 24

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

5.3.3

For the subsequent points, shall be treated as separate point(s).

5.3.4

No recovery shall be made for non-provision of more than one switch/ MCB. In
such cases.

5.4

TWIN CONTROL LIGHT POINTS WIRING

5.4.1

A light point controlled by 2 Nos. of two way switches shall be measured as two
separate points from the fitting to switches on either side.

5.4.2

No recovery shall be made for non-provision of more than one ceiling rose or
connector is such cases.

6.0

CIRCUIT WIRING , SUBMAIN WIRING AND ITS MEASUREMENT

6.1

Circuit wiring shall mean the wiring from the distribution board upto the tapping
to the nearest first point of the distribution circuit viz upto the nearest switch
box.

6.2

Sub-main wiring shall mean wiring form one main/ distribution switch board to
another.

6.3

MEASUREMENT OF CIRCUIT & SUB-MAIN WIRING.

6.3.1

Circuit & Sub-Main wiring shall be measured on linear basis along the run of the
wiring or as mentioned in BOQ. The measurement shall include all lengths from
end to end of conduit or PVC casting capping as the case may be, exclusive of
interconnection inside switch board etc. The increase on account of diversion or
slackness shall not be included in the measurement.

6.3.2

The length of circuit wiring with two wires shall be measured from the
distribution board to the first nearest switch box in the circuit irrespective of
whether the neutral conductor is taken to the switch box or not.

6.3.3

When wires of different circuits are grouped in a single conduit, the same shall
be measured to the nearest switch box in the circuit irrespective of whether the
neutral conductor is taken to the switch box or not.

6.3.4

When circuit wires and wires of point wiring are run in the same conduit, circuit
wiring shall be measured on linear basis depending on the actual number of
sizes of wires run in the existing conduit.

6.3.5

Protective (loop earthing) conductors which are run along the circuit wiring and
the sub-main wiring shall be measured on linear basis and paid for separately.

7.0

6 & 16 AMP SWITCH SOCKET OUTLET - MODULAR RANGE

7.1

Switch socket outlet on lighting circuit shall be of 5 pin 6 Amp outlet and shall
have safety shutters. The switch shall be of rocker mechanism type with silver

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 25

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

safety contact. Switch and socket outlet shall be separate unit in modular range
and shall be plate type and of white finish. Switch shall be indicator type.
8.0

LIGHTING FIXTURES & FANS

8.1

Luminaire shall be supplied as per the design specified in the Schedule of


Quantities. Luminaire shall be complete in all respects with basic mounting
channel, lamp holders, starter with holder, copper/ electronic ballast, connector
block, internal wiring and decorative attachments, if any.

8.2

The light fixtures and fans shall be assembled and installed in position (both for
surface mounted and recessed version) complete and ready for service in
accordance with the detailed drawings, manufacturers instructions and to the
satisfaction of the Engineer-In-Charge.

8.3

Light fixtures in general shall be recessed type in false ceiling or surface


mounted on soffit of slab or wall with rawl plugs. Luminaries shall be installed as
specified on the drawings. Wherever luminaires are fixed on the false ceiling,
suitable supporting and fixture arrangements independent of the frame, work of
false ceiling shall be provided.

8.4

Suspended type fluorescent light fixture shall be fixed to circular junction box
with a metallic ball and socket arrangement and comprising of suspension pipes
etc., for installing the luminaries.

8.5

Fixtures shall be suspended true to alignment plumb level and capable of


resisting all lateral and vertical forces and shall be fixed as required. It is the
duty of the Contractor to make these provisions at the appropriate stage &
locations shown on the drawings.

8.6

All the materials used in the construction of luminaries shall be of such quality,
design and construction that will provide adequate protection in normal use,
against mechanical, electric failure/ faults and exposure to the risk of injury or
electric shock & shall withstand the effect of exposure to atmosphere.

8.7

Erection of fixtures shall include assembling of all components of the fixtures


such as chokes, condensers, starters, ignitor, decorative attachments, etc.

8.8

Bulkhead fittings shall be of cast iron/cast aluminum body suitably painted white
inside and grey outside complete with heat resistant glass cover, lamp holder
and wire guard suitable for 100 watts incandescent lamp.

9.0

LAMPS, LAMP HOLDERS, CEILING ROSES & BALLASTS

9.1

Fluorescent lamps shall conform to IS in all respects. Fluorescent lamps shall be


of bi-pin pattern. The colour of the light shall be white or cool day light, as
required. Unless otherwise specified. The lamps shall be of required wattage as
per approved lighting scheme.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 26

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

9.2

Accessories for light outlets such as lamp holders, ceiling roses etc. shall be in
conformity with requirements of relevant IS Specifications. Only approved make
of accessories shall be supplied.

9.3

All ballast in general shall be copper wound, electronic and shall be silent in
operation. Ballast shall have a long life and shall be highly reliable.

9.4

For fluorescent lamp fixtures low loss ballasts shall be used unless otherwise
stated.

9.5

Ballasts shall be suitable for 240V, 50 Hz AC supply

10.0

TESTING & INSTALLATION

10.1

Testing & Installation shall be as per IS: 732-1963.

10.2

The insulation resistance measured as above shall not be less than 50 divided by
the number of points on the circuits provided that the whole installation shall be
required to have an insulation resistance greater than one mega-ohm.

10.3

Control rheostate, heating and power appliance and electrical signs may, if
required, be disconnected from the circuit during the test, but in event the
insulation resistance between the case or frame work and all live parts of each
rheostat appliance and sign shall not be less than that specified in the relevant
Indian Standard.

10.4

Specification or where there are no such specifications shall not be less than half
meg-ohm.

10.5

The insulation resistance shall also be measured between all conductors


connected to one pole or phase conductor of the supply and all the conductors
connected to the middle wire or the neutral or to the other pole or phase
conductors of the supply and its value shall not be less than as specified in this
tender document.

10.6

On completion of an electrical installation (or an extension to an installation) a


certificate shall be furnished by the contractor, counter signed by the supervisor
under whose direct supervision the work has been carried out.

10.7

TESTING OF EARTH CONTINUITY PATH

10.7.1

The earth continuity conductor including metal conduits and metallic enclosures
or in all cases shall be tested for electric continuity and the electrical resistance
of the same along with the earthing lead but excluding any added resistance or
earth leakage circuit breaker measured from the connection with the earth
electrodes to any points in the earth continuity conductor in the complete
installation shall not exceed on mega-ohm.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 27

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

10.7.2

Before a completed installation or an extension to an existing installation is put


into service it shall be tested as per IS-732. The following tests shall be
specifically carried out for all lighting installations:

10.7.2.1

Insulation Resistance.

10.7.2.2

Testing of earth continuity path.

10.7.2.3

Testing of polarity of single pole switches.

10.8

LIGHTING CIRCUITS

10.8.1

All switches on and consuming devices in circuit, both polls connected together,
to obtain resistance to earth.

10.8.2

Between polls with lamps and other consuming devices remove and switches on

10.8.3

With lamps and other consuming devices in position but switches off.

10.9

RESISTANCE OF EARTH

10.9.1

The resistance of earthing system shall not exceed one ohm. Earth testing
results to be got approved by the Inspecting Authority.

11.0

WIRING SPECIFICATION :

11.1

SYSTEM OF WIRING: The system of wiring shall consist of single/multi core PVC
insulated FRLS copper conductor wires in non-metallic PVC conduits/ metallic
M.S. conduits as called for in the BOQ. All conduits shall be on the
surface,(supported from the Ceiling), in the False Ceiling and concealed in other
areas where RCC slab is provided unless otherwise called for in the drawings. All
Down conduits shall be concealed unless otherwise called for.

11.2

Prior to laying of conduits, the Contractor shall get approved the conduit layout
indicating the route of conduit, number and size of conduits, location of
junction/ inspection/pull boxes, size and location of switch boxes, point outlet
boxes and other details. These conduit layouts shall be got approved by the
Consultant and then only conduit layout should be started. Any modification or
suggestions shall be approved by the Consultant before the laying of conduits.

11.3

MATERIALS:M.S. conduits shall conform to Indian Standards IS : 1653 - 1964 Specification for Rigid Steel conduits for Electrical wiring with the latest
amendments.

11.4

M.S. CONDUITS: M.S. conduits shall be solid drawn or lap welded conduits.
Stove enameled inside and outside with minimum wall thickness of 1.6 mm for

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 28

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

conduits upto 25 mm diameter and 2.0 mm wall thickness for conduits 32 mm


diameter and above.

11.5

PVC conduits to be used for concealed work for all systems except Fire Alarm &
Computer system where M.S. conduits shall be used. PVC conduits shall conform
to Indian Standards IS : 9537(Part-3)-1983 -Specification for conduits for
Electrical Installation (Part-I) General Requirements.

11.6

PVC conduits shall be rigid, unplasticised, heavy gauge having 1.8 mm wall
thickness upto 20 mm diameter and 2.0 mm wall thickness for all sizes above 20
mm diameter. Minimum size of conduit shall be 20 mm dia. Minimum size of
conduit for Power point wiring shall be 25 mm dia. The conduits shall be
delivered to the site of construction in original bundles and each length of
conduit shall bear the label of the manufacturer. The number of insulated
copper wires that may be drawn into the conduits of various sizes are given
below and the fill shall not exceed 40% the maximum permissible number of
650/1100 volts grade single/multi core PVC insulated copper conductor wires of
different sizes, that may be drawn into rigid metallic or non-metallic conduits.

SIZE OF WIRE
SIZE OF CONDUITS (MM)
Nominal cross20
25
32
40
50 nominal dia in mm
Sectional area
of wires in sq. mm
( Maximum number of wires )
1.5
5
6
18
2.5
3
4
10
4.0
2
3
5
10
6.0
4
6
8
10.0
3
4
16.0
3
5
25.0
2
3
-

11.7

PVC CONDUIT ACCESSORIES & CONNECTIONS: The accessories used for PVC
conduits shall conform to Indian Standards IS : 3419-1988-(Specification for
fittings for non-metallic conduits).PVC conduits shall be joined by means of
screwed or plain couplers. Where there are long runs of straight conduits,
inspection boxes shall be provided at intervals as approved by the consultant.
The threads of the pipe and sockets shall be free from grease and oil. It shall be
thoroughly cleaned before making the screwed/plain joints. Proper jointing
materials as recommended by manufacturers shall be used for jointing of PVC
pipes. Use PVC couplers and connectors for PVC pipe connections and terminations in boxes. All the joints shall be fully water tight. Junction boxes and
running joints shall be provided at suitable places to allow for subsequent
extensions if any, without undue dismantling of conduit system. As far as
possible diagonal run of conduits shall be avoided. Junction between conduit and

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 29

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

adapter boxes, back outlet boxes, switch boxes and the like must be provided
with entry spouts and smooth PVC bushes. Joints between conduit and iron clad
Distribution Boards or control gear shall be effected by means of conduit
couplers into each of which will be coupled smooth PVC bush from the inside of
box or case. Conduit system shall be erect and straight as far as possible. All
jointing methods shall be subject to the approval of the consultant.

11.8

BENDS IN CONDUITS: Where necessary bends or diversions may be achieved


by means of bends and or circular inspection boxes with adequate and suitable
inlet and outlet screwed joints. In case of recessed system each junction box
shall be provided with a cover properly secured and flush with the finished wall
surface, so that the conductors inside the conduits are easily accessible. No bend
shall have a radius of less than 2.5 times the outside diameter of the conduit.
Conduits shall be cold bend by means of a Bending spring available with the
manufacturers. In case it is not available then Heat may be used to soften the
PVC conduits, by filling sand in the pipe. Use of PVC conduit in places where
ambient temperature is 60 degrees or above is prohibited. PVC Solvent shall be
used for joints between conduits, conduits & Junction box etc. PVC checknuts
and bushes shall be used for joining conduit with outlet boxes. PVC Closures
shall be provided on unused mouths of Junction boxes.

Separate conduits shall be provided for the following system.


i)
ii)
iii)
iv)
v)
vi)
vii)

Lights, Ceiling fans, Exhaust fans & 5A Light sockets.


Power sockets & A/C outlets
Telephone System
Television, Computer & Music system
Emergency System.
Public Address System
Fire Alarm System.

Separate switchboards/outlets shall be provided for the following system.


i)
ii)
iii)
iv)
v)
vi)
vii)

11.9

Lights, Ceiling fans, Exhaust fans & 5A Light sockets.


Power sockets & A/C outlets
Telephone System
Television, Computer & Music system
Emergency System.
Public Address System
Fire Alarm system .

FIXING CONDUITS: Conduits and junction boxes shall be kept in position and
proper holdfasts shall be provided. Conduits shall be so arranged as to facilitate
easy drawing of wires through them. Adequate junction boxes of approved
shape and size shall be provided. All conduits shall be installed so as to avoid
steam and hot water pipes. After the conduits, junction boxes, outlet boxes &
switch boxes are installed in position their outlets shall be properly plugged so
that water, mortar, insects or any other foreign matter does not enter into the
conduit system. Exposed conduits shall be fixed by means of spacer bar/ saddles

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 30

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

at intervals of not more than 600 mm in normal run and 500 mm from both
sides of fitting or accessories. The saddles shall be of 3 mm x 19 mm mild steel
flat, properly treated with primer and painted, securely fixed to support by
means of nuts and bolts/rawl bolts and MS screws as required.
Conduits shall be laid in a neat and organised manner as directed and approved
by the Consultant. Conduit runs shall be planned so as not to conflict with any
other service pipe lines/ducts. Where exposed conduits are suspended from the
structure they shall be clamped firmly and rigidly to hangers of design to be
approved by the Architect. Where hangers are to be anchored to reinforced
concrete appropriate inserts and necessary devices for their fixing shall be
provided at the time of fixing.
Making holes or openings in the concrete will generally not be allowed. In case it
is unavoidable prior permission of the Consultant shall be obtained. Conduits
shall be fixed in the chase by means of staples not more than 600 mm apart and
the chase filled with cement mortar 1 : 4 . Cutting of horizontal chases in walls is
prohibited.

11.10

PROTECTION OF CONDUITS : To minimize condensation or sweating inside the


conduit pipes all outlets of conduit system shall be adequately ventilated as
directed and approved by the Consultant. All screwed and socketed connections
shall be adequately made fully water tight by the use of proper jointing materials
i.e. Tropolin for PVC conduits & white lead for metal conduits.

11.11

M.S.CONDUIT ACCESSORIES & CONNECTIONS:

11.11.1

The accessories used for M.S. conduits shall conform to Indian Standards IS :
3837-1966-(Specification for fittings for Rigid steel conduits with the latest
amendments. M.S. conduits shall be joined by means of screwed or plain
couplers. Where there are long runs of straight conduits, inspection boxes shall
be provided at intervals as approved by the Consultant. The threads of the pipe
and sockets shall be free from grease and oil. It shall be thoroughly cleaned
before making the screwed/plain joints.

11.11.2

Proper jointing and Cleaning materials as recommended by manufacturers shall


be used for jointing and cleaning of M.S. pipes. Use M.S. couplers and
connectors for M.S.pipe connections and terminations in boxes. All the joints
shall be fully water tight. Junction boxes and running joints shall be provided at
suitable places to allow for subsequent extensions if any, without undue
dismantling of conduit system. As far as possible diagonal run of conduits shall
be avoided. Junction between conduit and adapter boxes, back outlet boxes,
switch boxes and the like must be provided with entry spouts and smooth M.S.
bushes and M.S. Checknuts. Joints between conduit and iron clad Distribution
Boards or control gear shall be effected by means of conduit couplers into each
of which will be coupled smooth M.S. bush from the inside of box or case.
Conduit system shall be erect and straight as far as possible. All jointing
methods shall be subject to the approval of the Consultant.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 31

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

11.11.3

M.S. CONDUIT CONNECTIONS:

11.11.3.1

Conduit connections for MS conduits shall be screwed metal to metal and be


painted with one coat of self etching zinc chromate primer and two coats of
enamel paint. The threads and sockets shall be free from grease and oil.
Connections between screwed conduit and sheet metal boxes shall be by means
of a brass hexagon smooth bore bush, fixed inside the box. Checknuts to be
provided on inside and outside of box and connected through a coupler to the
conduit or as directed by the Consultant. The joints in the conduits shall be free
of burrs to avoid damage to insulation of conductors while pulling them through
the conduits. Connections between PVC and MS conduits shall be through a
junction box. Direct connection between PVC and MS conduits is not allowed.

11.11.4

FAN BOX DETAILS

11.11.5

The Fan Box shall be 100 mm x 100 mm x 75 mm deep, M.S. box made of 2mm
thick M.S. sheet, having 12 mm dia M.S. rod, bend at centre to support the fan,
top screwed cover etc. as per the approval of the Architect/Consultants.

12.0

SWITCH-OUTLET BOXES AND JUNCTION BOXES

12.1

All Boxes shall conform to Indian Standards IS : 5133(Part-1)-1969 (Specification


for boxes for enclosure of Electrical accessories) with the latest amendments. All
outlet boxes for switches, sockets & other receptacles shall be fabricated from
1.6mm thick mild steel sheets duly painted with rust proof paint (zinc
passivated) as called for, having smooth external & internal surfaces to true
finish. Junction boxes and outlet boxes in contact with earth or installed in areas
exposed to the weather shall be of 2mm thick mild steel and painted. Where
called for, outlet boxes for receiving switches, telephone outlets T.V. outlets,
power plugs etc. shall be fabricated to proved shape and size to suit the cover
plates of approved make for different utilities. The cover plates shall be of best
quality Hylam sheets or ISI grade Urea Formaldehyde Thermosetting insulating
material which shall be both mechanically strong and fire retardant, as approved
by the Consultant. Proper supports shall be provided in the outlet boxes to fix
the cover plates of switches as required. Separate screwed earth terminal shall
be provided inside the box for earthing purpose.

12.2

All boxes shall have adequate number of knockout holes of required diameter for
conduit entry. Where called for outlet boxes for receiving switches and fan
regulators in one box, shall be fabricated to approved shape and size to accommodate fan regulators and switches to be fixed on grid plates. These boxes
shall be covered with Hylam sheets or ISI grade Urea Formaldehyde
Thermosetting insulating material which shall be both mechanically strong and
fire retardant. All junction boxes, pull boxes and outlet boxes shall be provided
with sheet cover Urea Formaldehyde Thermosetting insulating material. The box
cover shall be secured to the box with adequate number of round head brass
screws of approved make.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 32

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

12.3

Outlets exposed to the weather shall be fully weather tight, complete with
rubber gasketed covers, glass where used shall be fully heat resistant for the
duty. The outlet boxes shall be painted with two coats of bitumastic paint
before they are fixed in position. All Outlet boxes fixed in concrete/recessed in
wall shall be of a minimum depth of 55mm.

12.4

INSPECTION BOXES: Rust proof (Zinc passivated) inspection boxes of 1.6mm


thick mild steel sheet and of required size, having smooth external and internal
finish shall be provided to permit periodical inspection and to facilitate removal
and replacement of wires when required. Inspection boxes shall be mounted
flush with ceiling/walls finished surface and shall be provided with screwed
covers of Urea Formaldehyde Thermosetting insulating material sheet cover
secured to the box with brass screws. Adequate holes shall be provided for
ventilation in the inspection box covers.

12.5

TELEPHONE SYSTEM: Conduits, junction boxes, draw boxes, outlet boxes and
covers to boxes for telephone system shall be as described under relevant
clauses elsewhere in these specifications. Conduits for telephone system shall
be at least 150 mm away from the electrical conduits. The conduits for
telephone wiring shall be of specified size and shall be terminated at outlets as
indicated on the drawings. Telephone system conduits shall have 2 mm
diameter galvanized steel pull wires installed. Necessary Junction boxes to be
provided for easy drawing of the Telephone wires from each unit to the
Telephone Tag Box and from the Tag Box to the open ground.

12.6

T.V. & COMPUTER SYSTEM: Conduits junction boxes, draw boxes, outlet boxes
and covers to boxes for T.V. & Computer system shall be as described under
relevant clauses elsewhere in these specifications. Conduits for T.V. & Computer
system shall be at least 150mm away from the electrical conduits. The conduits
for T.V. & Computer wiring shall be of specified size and shall be terminated at
outlets as indicated on the drawings. T.V. & Computer system conduits shall
have 2mm diameter galvanized steel pull wires installed. Necessary Junction
boxes to be provided for easy drawing of the Television & Computer wires from
each unit to the Junction Box and from the Junction Box to the open ground.

13.0

CONDUCTORS

13.1

PVC insulated multistrand copper conductor wires of 1100 Volts grade shall be
used for three phase distribution and PVC insulated multistrand copper
conductor wires of 1100 V grade shall also be used for Single phase distribution
and shall conform to IS : 694 -1964 with the latest amendments and shall be
ISI marked.
BUNCHING OF WIRES

13.2
13.2.1

Wires carrying current shall be so bunched in the conduit that the outgoing and
return wires are drawn into the same conduit. Wires originating from two
different phases shall not be run in the same conduit.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 33

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

13.3

DRAWING OF CONDUCTORS

13.3.1

The drawing and jointing of copper conductor wires shall be executed with due
regard to the following precautions, while drawing insulated wires into the
conduits. Care shall be taken to avoid scratches and kinks which cause
breakage of conductors. There shall be no sharp bends. Insulation shall be
shaved off for a length of 15mm at the end of wire like sharpening of a pencil
and it shall not be removed by cutting it square or ringing.

13.3.2

PVC insulated copper conductor wire ends before connection shall be properly
soldered (at least 15mm length) with special Cu solder for copper conductor or
shall be properly crimped with copper lugs/sockets as the case may be. Strands
of wires shall not be out for connecting to the terminals. All strands of wires
shall be soldered at the end before connection. The connecting brass-screws
shall have flat ends. All looped joints shall be soldered and connected through
terminal block/connectors. The pressure applied to tighten terminal screws shall
be just adequate, neither too much nor too less. Conductors having nominal
cross sectional area exceeding 6 Sq mm shall always be provided with cable
sockets.

13.3.3

At all bolted terminals, brass flat washer of large area and approved steel spring
washers shall be used. Brass nuts and bolts shall be used for all connections.

13.3.4

Only certified wiremen and cable jointers shall be employed to do jointing work.
All wire shall bear the manufacturers label and the voltage grade at one meter
intervals for the full length of coil, and shall be brought to site in new and
original packages.

13.3.5

The sub-circuit wiring for points shall be carried out in looping system and no
joint shall be allowed in the length of the conductors. No wire shall be drawn
into any conduit, until all work of any nature, that may cause injury to wire is
completed. Care shall be taken in pulling the wires so that no damage occurs to
the insulation of the wire. Before the wires are drawn into the conduits the
conduits shall be thoroughly cleared of moisture, dust, and dirt or any other
obstruction by Drawing dry cloth through the conduits. The minimum size of
PVC insulated stranded copper conductor wire for all sub circuit wiring for lights,
exhaust fans, ceiling fan and 5A Light sockets points shall be 1.5 Sq mm. In
case of power circuit not more than two 15 Amp power outlets shall be grouped
in one circuit, wiring for the first power outlet shall be carried out with PVC
insulated 6.0 sq mm copper conductor wires. Wiring for the second power outlet shall be carried with PVC insulated 4.0 sq mm copper conductor wires. All
power outlets shall be connected with 4.0 sq mm PVC insulated copper
conductor wires to the earth terminal of outlet. Separate circuit shall run with
PVC insulated 4.0 sq mm copper conductor wires for water heaters, kitchen
equipment, window Air conditioners and similar outlets at locations as shown on
drawings.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 34

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

13.3.6

The minimum size of wire from final distribution board to first tapping point in
the circuit shall be 2.5 Sq mm. PVC insulated stranded copper conductor wires.
Circuit shall not have more than a total of 8 points of fans, 5A Light sockets and
Light points and its load shall not exceed 800 watts. Not more than two power
circuits shall be drawn through the same conduit. Separate earth wire shall run
for each circuit. In case two circuits of the same phase are running in the same
conduit then a common earth wire is permissible. The size of earth wire for all
the light points, ceiling fans, exhaust fans , light sockets, outlet boxes etc. shall
be 1.5 sq mm PVC insulated copper conductor wires.

13.4

JOINTS

13.4.1

All joints shall be made at main switches, distribution boards, socket outlets,
lighting outlets and switch boxes only. No joints shall be made inside conduits
and junction boxes. Conductors shall be continuous from outlet to outlet. Joints
where unavoidable, due to any specified reasons, prior permission in writing
shall be obtained from the Consultant before making such connections.

13.5

LOAD BALANCING

13.5.1

Balancing of circuits in three phase installation shall be planned before the


commencement of wiring, shall be got approved by the Consultant and shall be
strictly adhered to.

13.6

COLOUR CODE OF CONDUCTORS

13.6.1

Colour code shall be maintained for the entire wiring installation; red, yellow,
blue for three phases and off circuit black for neutral and green for earth (or
bare earth wire)

13.6.2

Telephone Multicore cables shall be of approved make and shall conform to


following specifications:
i) Type of conductor .. Electrolytic Annealed Tinned Cu conductor (ATC)
ii) Diameter of Conductor ... 0.61 mm dia uniform (minimum size)
ii) Weight of conductor .... 2.52 Kg/Km minimum.
iii) Resistance of conductor at 20 degree... 60 Ohms/Km,
iv) Radial Thickness of PVC insulation...0.3mm + 0.05mm uniform
vi) Radious Thickness of PVC sheathing ... 1.2mm uniform + 0.2mm
vii) Overall diameter of insulated conductor.. 1.2mm uniform
viii)High voltage Test. Able to withstand upto 500 volts D.C. up to 12
hours immersion in water.

14.0

EARTHING

14.1

All the non-current metal parts of electrical installation shall be earthed properly.
All metal conduits, trunking, cable sheaths, switchgear, outlet boxes, distribution
boards, light fittings, fans and all other parts made of metal or conductive

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 35

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

material shall be bonded together and connected by means of specified earthing


system.
14.2

All earthing will be in conformity with the relevant provision of Rules 33 and 61
of the Indian Electricity Rules 1956 and Indian Standard Specifications IS:30431987 with latest amendments.

14.3

EARTHING CONDUCTORS

14.3.1

All earthing conductors shall be of high conductivity electrolytic copper of 99 %


purity and shall be protected against mechanical injury or corrosion.

14.4

SIZING OF EARTHING CONDUCTORS

14.4.1

The cross sectional area of copper earthing conductor shall be same as the
active conductor for sizes of active copper conductor upto 4.0 sqmm and shall
be half the size for 16 sq mm active copper conductor and above. All fixtures,
fans, outlet boxes and junction boxes shall be earthed with 1.5 sqmm PVC
Insulated copper conductor wires. All power sockets and single phase A/C units
shall be earthed with 4.0 PVC Insulated copper conductor wires. All Three phase
Final Distribution Boards shall be earthed with 2 nos 4 mm dia bare copper
conductor wires. The sizes of the earth continuity conductors should not be less
than half of the largest current carrying conductors.

14.4.2

The Sub-Distribution Board shall be earthed to 2 nos 600mm x 600mm x 3mm


copper plate earthing stations through 25m x 3 mm copper strips.

14.5

CONNECTION OF EARTHING CONDUCTORS

14.5.1

Main earthing conductors shall be taken from the earth connections at the main
switchboards to an earth electrode with which the connection is to be made.
Submain earthing conductors shall run from the main switchboard to the subdistribution boards. Final distribution boards earthing conductors shall run from
sub-distribution boards.

14.6

PROHIBITED CONNECTIONS

14.6.1

Neutral conductor, sprinkler pipes, or pipes conveying gas, water, or


inflammable liquid, structural steel work, metallic enclosures or cables and
conductors, metallic conduits and lightning protection system conductors shall
not be used as a means of earthing an installation or even as a link in an
earthing system. The electrical resistance of metallic enclosures for cables and
conductors measured between earth connections at the main switchboard and
any other point on the completed installation shall be low enough to permit the
passage of current necessary to operate fuse or circuit breakers and shall not
exceed 1 ohm.

14.7

PROTECTION FROM CORROSION

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 36

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

14.7.1

Connections between copper and galvanised equipment shall be made on


vertical face and protected with paint and grease. Galvanised fixing clamps shall
not be used for fixing earth conductors. Only copper fixing clamps shall be used
for fixing earth conductors. When there is evidence that the soil is aggressive to
copper, buried earthing conductors shall be protected by suitable serving and
sheathing.

14.8

EARTHING STATION

14.8.1

Plate Electrode Earthing : Earthing electrode shall consist of a tinned copper


plate not less than 300mm x 300mm x 3mm thick as called for in the Schedule.
The plate electrode shall be buried as far as practicable below permanent
moisture level but in any case not less than 4.2 meters below ground level.
Wherever possible earth electrodes shall be located as near the water tap, water
drain or a down take pipe as possible. Earth electrodes shall not be installed in
proximity to a metal fence. It shall be kept clear of the buildings foundations
and in no case shall it be nearer than 2 meters from the outer face of the wall.
The earth plate shall be set vertically and surrounded with 150mm thick layer of
charcoal, dust and salt mixture. 20mm GI pipe shall run from the top edge of
the plate to the ground level. The top of the pipe shall be provided with a
funnel and a mesh for watering the earth through a pipe. The funnel over the
GI Pipe shall be housed in a masonry chamber, approximately 300mm x 300mm
x 300mm deep. The masonry chamber shall be provided with a cast iron cover
resting over a GI frame embedded in masonry. Refer Sketch for additional
details.

14.9

EARTH CONNECTION

14.9.1

All metal clad switches and other equipment carrying single phase current, shall
be connected to earth by a single connection. All metal clad switches carrying
medium voltage and high voltage shall be connected with earth by two separate
and distinct connections. The earthing conductors inside the building wherever
exposed shall be properly protected from mechanical injury by running the same
in GI Pipe of adequate size.

14.9.2

Earthing conductors outside the building shall be laid 600mm below the finished
ground level. The over lapping in copper strips at joints where required, shall be
minimum 75mm. The joints shall be riveted and brazed with copper rivets and
greased in approved manner. Sweated lugs of adequate capacity and size shall
be used for all termination of wires above 1 Sqmm size and bare copper wire
above 2.0mm dia. Lugs shall be bolted to the equipment body after the metal
body is cleaned of paint and other oily substance and properly tinned. The earth
wires entering the Final Distribution Boards shall be terminated with copper
sockets crimped to its ends and tightened to the terminal with the help of flat
end brass screws.

14.10

EARTH RESISTANCE

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 37

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

14.10.1

The earth resistivity of the soil where the earthing stations are located shall be
submitted to the Consultant before the earthing work starts and get the approval
of the Consultant/Owner. If the earth resistance is too high and multiple
electrode earthing does/not give adequate low resistance to earth, than the soil
resistivity immediately surrounding the earth electrodes shall be reduced by
adding sodium chloride, calcium chloride, sodium carbonate, copper sulphate,
salt and soft coke or charcoal in suitable proportions as directed by the
consultants.

14.11

RESISTANCE TO EARTH

14.11.1

The resistance of each earth system shall not exceed 1.0 ohm in the case of
Medium Voltage system and 0.5 ohm in the case of High Voltage system.

15.0

TESTING

15.1

On completion of the work the entire installation shall be subject to following


tests:
a) Wiring Continuity Test
b) Insulation Resistance Test
c) Earth Continuity Test
d) Earth Resistivity Test

15.2

Besides the above any other test specified by the local Authority shall also be
carried out.

15.3

All tested and calibrated instruments for testing, labour, materials and
incidentals necessary to conduct the above tests shall be provided by the
Contractor at his own cost.

15.4

TESTING OF WIRING

15.4.1

All wiring systems shall be tested for continuity of circuits, short circuits and
earthing after wiring is complete and before energising. The Test Certificates for
the complete wiring shall be submitted in the Format and the Total Electrical
Installation shall be got approved by the Electrical Inspector.

15.5

INSULATION RESISTANCE TEST

15.5.1

The insulation resistance shall be measured by applying between earth and the
whole system of conductors, or any section thereof with all fuses in place and all
switches closed (except in concentric wiring) all lamps in position of both poles
of the installation , otherwise electrically connected together, a direct current
pressure of not less than twice the working pressure(provided that it does not
exceed 660 volts for medium voltage circuits) be applied. Where the supply is
derived from A.C. three phase system, the neutral pole of which is connected to
earth, either direct or through added resistance, pressure shall be deemed to be
that which is maintained between the phase conductor and the neutral. The
insulation resistance measured as above shall not be less than 50 divided by the

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 38

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

number of points on the circuit provided that the whole installation shall not be
required to have an insulation resistance greater than one mega ohm. The
insulation resistance shall not be measured between all conductors connected to
one phase conductor of the supply and all the conductors connected to the
middle wire or to the neutral or to the other phase conductors of the supply.
Such a test shall be carried out after removing all metallic connections between
the two poles of the installation and in these circumstances the insulation
resistance between conductors of installation shall not be less than that specified
above.
15.5.2

The insulation resistance between the case of frame work of housing and power
appliances, and all live parts of each appliance shall not be less than that
specified in the relevant Indian Standard Specifications or where there is no such
specification shall not be less than half a mega ohm.

15.6

TESTING OF POLARITY OF NON-LINKED SINGLE POLE SWITCHES

15.6.1

In a two wire installation a test shall be made to verify that all non-linked single
pole switches have been fitted in the same conductor through out, and such
conductor shall be labeled or marked for connection to an outer or phase
conductor or to the non-earthed conductor of the supply. In the three or four
wire installation a test shall be made to verify that every non-linked single Pole
switch is fitted in a conductor to one of the outer or phase conductor of the
supply. The entire electrical installation shall be subject to the final acceptance
of the Consultant as well as the local authorities.

15.7

EARTH RESISTIVITY TEST

15.7.1

Earth resistivity test shall be carried out in accordance with Indian Standard code
of practice for earthing IS:3043:1987. All tests shall be carried out in the
presence of the Consultant/Owner.

15.8

TEST CERTIFICATES

15.8.1

The Electrical Installation shall be tested as per relevant Indian Standards and
Test Certificate to this effect shall be submitted to the Owner. The Contractor
has to get the Total Electrical Installation approved by the Electrical Inspector
and the permission to energise the same shall be submitted to the Owner.

16.0

SAFETY REQUIREMENTS

16.1

Safety provisions shall be generally in conformity with the relevant Indian


Standards and I.E. Rules and Regulations. In particular the following items shall
be provided.
(a) Insulation Mats
Insulation Mats conforming to IS : 5424-1969 shall be provided in front of main
switch boards and other control equipment as specified.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 39

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

(b) First Aid Charts and First Aid Box

Charts (one in English, one in Hindi, one in Regional language), displaying


methods of giving artificial respiration to a recipient of electrical shock shall be
prominently provided at appropriate place. Standard First Aid Boxes containing
materials as prescribed by St. John Ambulance brigade or Indian Red Cross
2should be provided in each sub-station.
(c) Danger Plate
Danger plates shall be provided on HV and MV equipments. MV danger notice
plate shall be 200mm x 150mm made of mild steel atleast 2mm thick vitreous
enameled white on both sides and with inscriptions in signal red colour on
front side as required.
(d) Caution Board
Necessary number of caution boards as Man on Line Dont switch on etc.
shall be available in the sub-station.
(h) Key Board
A key board of required size shall be provided at a proper place containing
castel key, and all other keys of sub-station and allied areas.

17.0

FIRE DETECTION AND ALARM SYSTEM

17.1

The contractors scope shall be removal and re-installation of smoke detectors


,sprinklers, response indicators and temperature heat detectors ( Fire sensors)
connecting, testing and commissioning to the existing conventional type fire detection
and alarm system.

17.2

In case of any damage to the existing sensors and detectors , contractor shall supply
the sensors & detectors as per the approved make.

SCOPE OF WORK IS DETAILED IN BILL OF QUANTITY (BOQ) & TENDER


DRAWINGS (REFER FORM 1-D OF SCHEDULE OF PRICES). IN CASE OF ANY
CONFLICT WITH THE GENERAL SPECIFICATION SPECIFIED ABOVE AND THE BILL
OF QUANTITY(BOQ) AS PER FORM-1D, THE TECHNICAL SPECIFICATION
MENTIONED IN BILL OF QUANTITY ( FORM 1 D) SHALL PREVAIL.ALSO REFER
ANNEXURE

AA
FOR
PRICE
BASIS
OF
ELECTRICAL
WORKS.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 40

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

ANNEXURE-AA
POINT WIRING
1.
2.
3.
4.
5.
6.
7.

8.
9.
10.
11.
12.
13.
14.
15.
16.

17.
18.
19.
20.
21.

22.

The rates for all point wiring items shall include :


Conduits, Conduit specials, bushes and other fittings concealed or exposed as called
for.
Embedding conduit and allied fittings including the outlet boxes in walls, floors etc.,
during construction and/or in chases including cutting chases and making good with
cement mortar as necessary in the case of concealed conduit work.
Providing and fixing approved fixing devices, saddles and grouting the same as
required for exposed conduits.
Fabrication and Supply of G.I .boxes for switches, ceiling fan hooks, Exhaust fans
outlet and lighting fixtures with 1.6 mm thick sheet steel.
Providing and fixing junction boxes with 3mm Hylam or 3mm/5mm thick Perspex
sheet cover duly painted from inside to match the colour of the walls. All Junction
boxes shall be MS only.
All fixing accessories such as clips, brass screws/brass washers rawl plugs etc.
All work & material necessary (including circuit wiring from DB to first tapping point
of each circuit with 2.5 sq. mm wires) in complete wiring of a switch circuit of any
length from the distribution board to the following via the switch:
a) Ceiling rose b) Connector c) Back plate d) Socket outlet
e) Lamps Holder
f) Any other terminal outlet boxes g) Ceiling fan and Exhaust fan
Switch, socket outlet as called for.
Cable/wire as required upto lamp holder.
All metal boxes and boards concealed or surface mounted including those required
for housing fan regulators.
All accessories necessary to complete wiring as specified.
FRLS PVC Insulated stranded Copper conductor earth wire for fixtures, switch outlet
boxes and third pin of 5/15 Amps. socket to common earth.
Painting all exposed M.S. conduits, outlet boxes and junction boxes.
M.S. conduit for concealed and exposed wiring.
2 mm dia G.I. pull wires in conduit work, wherever necessary.
The switch plate shall be made of I.S.I. grade Urea Formaldehyde Moulding powder.
The base of the switches shall be made from high heat resistant phenol
formaldehyde powder. The cost of switches shall include the cost of cover plates,
cadmium fixing screws etc.
The switches/sockets shall be rocker operated.
Separate Earth wire shall run along with each circuit both for power and light circuits.
Cutting of floor and making good for carrying conduits also.
Numbering of Circuits with ferrules for all circuits at both ends.
Providing 15 Amps capacity Bakelite terminal Blocks for terminating the phase,
neutral and earth wire at each fixture location.
PVC insulated copper conductor wire ends before connection shall be properly
soldered (at least 15 mm length) with special Cu solder for copper conductor or shall
be properly crimped with copper lugs/sockets as the case may be. Strands of wires
shall not be out for connecting to the terminals. All stands of wires shall be soldered
at the end before connection. The connecting brass-screws shall have flat ends. All
looped joints shall be soldered and connected through terminal block/connectors.
Provide embossing on the sockets engraving UPS and RAW
CONDUITING & WIRING FOR TELEPHONE & COMPUTER SYSTEM
The rates for conduit work shall include :

1.

All necessary specials and fittings.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 41

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.

M. S. inspection, junction and outlet boxes as required.


3/5 mm thick perspex sheet covers for inspection & junction boxes.
All fixing accessories such as clips, nails, brass screws/brass washers, etc.
2 mm dia G.I. pull wires in conduit work, wherever necessary.
Providing and fixing approved saddle, hooks and grouting the same as required in the
case of all exposed conduit work.
Embedding conduit and allied fittings including the outlet boxes in walls, floors etc.,
during construction and/or in chases including cutting chases and making good with
cement mortar as necessary in the case of concealed conduit work.
Painting all inspection, junction and outlet boxes.
PVC conduit for concealed conduit wiring .
Painting of Hylam/perspex sheet cover from inside to suit the colour of the surrounding
wall with two coats of paint.
Supply and fabrication of G.I. outlet boxes .
The outlet cover plate for Telephone outlets shall be made of I.S.I. grade Urea
Formaldehyde Moulding powder. The cost of outlets shall include the cost of cover
plates, cadmium fixing screws etc. also.
Numbering of wires on both ends of the wires for easy identification with PVC ferrules.

EARTHING
The rates for earthing items include :
1.
2.
3.
4.
5.
6.

All fixing accessories such as brass saddles, brass screws, rawl plugs etc.
Jointing by riveting in case of copper earth strips ( 2 per joint) and by welding in case
of GI strips.
Cutting chase, making holes and making good the same wherever required.
All masonry work including earth work for earthing stations, earthing tapes and wires.
Effecting adequate and proper interconnections.
Use of copper thimbles for all wire terminations in the Distribution Boards , switches
and sockets.

SUPPLY & FIXING OF LIGHTING FIXTURES AND FANS


1.
2.

The rate for fixing of lighting fixtures and fans shall include:
Receiving the fixtures from the Ownerss stores and assemble the same at site and
testing the fixture before fixing.
All components that may be required to make the installation complete in all respects
such as:
a. Suitable length of down rod, hanger and connecting wires, where called for.
b. Wires for connecting the fixtures to the point through connector blocks.
c. All wood and metal blocks to serve as base of fixtures.
d. Bonding with common earth wires.

3.
4.
5.
6.
7.
8.

Drilling holes in supports where required.


Fixing clamps, GI bolts and nuts, clips, brass screws, dash fasteners and other fixing
accessories as required, including leaving necessary provision for fixing at time of
concreting.
Approved enamel painting for hanger rods, clamps and other components and fixing
accessories as called for.
Testing and commissioning of all fixtures and fans after installation.
The lighting fixtures shall be suitable for 230 Volts, single phase 50 cycles A.C. supply
system.
Incandescent lamps shall be 100 Watts (maximum) and fluorescent lamps shall be 18
watts and 36 watts.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 42

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

9.
10.

Use G.I. suspenders and clamping to the slab with dash fasteners( 4 per fitting) ,
including turn buckle arrangements for adjustable heights for hanging. They should
be the same suspenders as used for hanging the False Ceiling grid ceiling.
The contractor to mark the size of light fittings, speaker and fire alarm components
on the false ceiling for the interior contractor to cut holes.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 43

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

TECHNICAL

SPECIFICATION

FOR

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

FURNITUTRE

Page | 44

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

1.0

SPECIFICATIONS FOR FURNITURE /INTERIOR WORKS


MODULAR CURVILINEAR WORKSTATION with dimension 1500 x 1500 x 1200
having 75mm thick tile based partition and following specifications. Complete
furniture partition should be in extruded aluminum and not in CRCA steel.

1.1

FRAME WORK

1.1.1

Extruded aluminum vertical and horizontal members, 75mm wide that can be
linked vertically & horizontally to any desired configuration. Frames shall be in 6
widths-450mm, 600mm, 750mm, 900 mm, 1050mm and 1200mm.

1.2

JOINERY

1.2.1

All connections shall be made with M6 screws.

1.2.2

TOPRUNNERS AND BOTTOM SKIRTING

1.2.3

The bottom skirting shall be 95 mm high. These plates are aluminum plates with
powder coat finish and are supplied pre fitted with each frame.

1.3

END TRIMS

1.3.1

Exposed round vertical & horizontal ends shall be covered by an aluminum


powder coated finish, which is fixed accurately at these ends.

1.4

Corner Posts

1.4.1

Module frames shall be joined by means of heavy aluminum connectors, which


accept the standard M6 screws.

1.5

Height Adjusters

1.5.1

Modular partition frames shall be supplied with heavy-duty levelers in the bottom
to adjust the unevenness of the floor. They shall be accessible without removing
the skirting. The leveling bolt allows up to 50-mm adjustment.

1.6
1.7
1.7.1

Stability

1.7.2

The 75 mm thick extruded frame shall be sufficiently rigid such that worktops
and other accessories can be cantilevered at any desired point without affecting
the overall stability.

1.8

Powder Coating

1.8.1

Powder Coating of aluminum components shall be 40-50 microns in thickness.

1.9

FASCIA TILES

Stability of Module partition does not depends on the worktop cantilevers to it.
The only requirement is a stable layout in T, L and U configurations. The
partitions configurations are free standing and do not require any indentation to
be done in the floor.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 45

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

1.9.1

Module Fascia Tiles is 9 mm thick particleboard / MDF panels fitted with nylon
clips.

1.9.2

These tiles can be unlatched with a flat tool for the removal.

1.9.3

Module fascia tiles are normally available in a wide variety of surface finishes
FABRIC, LAMINATE & MARKER BOARD.

1.10

SOFTBOARD TILES

1.10.1

Made from 9-mm thick soft board with GI frame backing to give strength and
covered with fabric.

1.11

GLASS PANELS

1.11.1

4mm Double glazed glass can be fitted to any module frame & are completely
interchangeable with regular tiles at any time.

1.12

WIRE MANAGEMENT

1.12.1

Inlet: Entry of wires shall be from corner posts or sides or frames. Wires from
ceiling are taken through a down pole, which is fitted on top of the post.
Outlet: electrical delivery ducts shall be fitted on the frames bellow or above
the worktop. The similar duct can be provided at the skirting also.

1.12.2
1.13

TRANSMISSION

1.13.1

Within a partition: Partition are hollow and allow free horizontal and vertical
movement of wires from inlet, outlet or to the next partition.

1.14

WORKTOP

1.14.1

Curvilinear Worktops are 25mm thick pre-laminated particle board with suede
finish lamination. All edges should be treated with 2mm PVC edges banded.

1.15

GABLE ENDS

1.15.1

Worktop shall be supported at one end by side panels (Gable Ends) rather than
cantilevers bracket if desired. Gable ends are 25 mm thick and attached to the
Module frames.

1.16

KEY BOARD TRAY

1.16.1

All worktops can be supplied with a pull out keyboard tray made of METAL
mounted below the surface.

1.17

FREE STANDING STORAGE

1.17.1

Module pedestals are constructed from pre-laminated board consisting of 2


utility drawer and 1 filing box drawer. The exterior is made of 18-mm pre
laminated board, while the drawers are of 12 mm board. All telescopic slides
should have soft close provision.

1.18

The product should have ISO 9001:2000, OHSAS 18001:2007 and ISO 140012004 certifications.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 46

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

2.0

WOODEN STORAGES free standing wooden storages with following features


product
SIZE 900 W X 450 D X 1200 H

2.1

CONSTRUCTION

2.1.1

Rigid knock down construction. Open-able shutters shall be made of 18 mm


thick pre laminated particle board, verticals and bottom shall be made of 18mm
thick pre laminated particle board and back also made of 18mm thick pre
laminated particle board. The top shall be of 25mm thickness.

2.2

SHUTTERS

2.2.1

Open-able shutters having 2 adjustable shelves making 3 compartments.

2.2.2

With PVC edge bending on all the exposed edges. Having all necessary fittings of
hettich/ebco make soft close hinges, locks and any miscellaneous items.

3.0

STORAGES IN CONFERENCE ROOM free standing wooden storages with


following features Product Size 900 W X 450 D X 750 H

3.1

CONSTRUCTION

3.1.1

Rigid knock down construction. Open-able shutters shall be made of 18 mm


thick pre laminated particle board, verticals and bottom shall be made of 18mm
thick pre laminated particle board and back made of 18mm thick pre laminated
particle board. The top shall be of 25mm thickness.

3.2

SHUTTERS

3.2.1

Having swing doors with glass shutters with 1 adjustable shelves making 2
compartments.

3.2.2

With PVC edge bending on all the exposed edges. Having all necessary fittings of
hettich/ebco make soft close hinges, locks and any miscellaneous items.

4.0

METAL STORAGES SIZE W-910 X D-455 X H-1980. the allowable dimensional


tolerance for overall size of the storage will be (+ / - 5mm). Similarly in the
angle bending (+ / - 3mm) in degree. free standing CRCA almirah

4.1

CONSTRUCTION

4.1.1

The Storage shelves shall be fabricated with integrated welded construction.


Body shall be made of 0.8mm CRCA sheets. Complete structure should be
Powder Coated. All the components should have finished 40 to 50 microns thick
epoxy polyester powder coating oven baked at 180 to 200 deg. C. The cold
rolled cold annealed (CRCA) sheets of 0.8mm thickness and strips and having six
folds as per design.

4.2

SHELVES

4.2.1

Each standard storage having loading shelves and the shelves can be adjustable
as per requirement with suitable systems such as clips, nuts and bolts.

4.2.2

Adjustable Shelves making 5 Compartments. Knock down Structure. The Storage


angle is precision punches slotted strips bended at sides to support the shelves

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 47

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

to ensure flexibility in adjusting the height of the shelves. Shelves are able to
carry maximum 40kgs. UDL (Uniformly Distributed Load).
4.3

FITTINGS

4.3.1

Having all necessary fittings like hettich/ebco make soft close hinges, multi point
locks and any miscellaneous items.

5.0

CHAIR WITHOUT HEADREST


HIGH BACK CHAIR WITHOUT HEADREST, VENTILATING MESH
ADJUSTABLE LUMBAR PAD & SYNCHRONIZED TILT MECHANISM.

5.1

ARMREST

5.1.1

2 way armrest adjust for 6 cm in height and swivel into 3 angular positions.

5.2

BACKREST

5.2.1

A breathable polyester mesh suspension allows improve ventilation and


transpiration to provide exceptional thermal comfort. Back frame is moulded of
resilient black poly polypropylene.

5.3

LUMBER SUPPORT PAD

5.3.1

Lumber support shall be conveniently adjusted by side knobs without getting up


from chair to customize the exact support for various panel shapes.

5.4

CHAIR MECHANISM

5.4.1

Syncro- tilt chairs employs a synchronized mechanism with tilt tension control
multi position tilt lock, and pneumatic seat height control. Advanced swivel tilt
chair provide tilt tension control multi position tilt lock, and pneumatic seat
height control.

5.5

BASE

5.5.1

This standard base is aluminum with black powder coating. Hooded dual wheel
castors in black nylon

5.6

Tilt Tension Control to obtain a balanced relining resistance.

5.7

Multi-position tilt Lock allows the back to be engaged to the preferred recline
angle.

5.8

As per manufacturer's specifications, drawings & direction of Engineer in charge.


The above chair should be as per specification and sample approved by client.

6.0

CHAIR WITH HEADREST


HIGH BACK CHAIR, HEADREST, VENTILATING MESH BACK, LUMBAR PAD &
SYNCHRONIZED TILT MECHANISM.

6.1

HEADREST

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

BACK,

Page | 48

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

6.1.1

Headrest should be adjustable for 5 cm in height. Headrest constructed by


stretching mesh fabric or leather over a springy poly polypropylene frame. Is
adjustable for 5cm in height and for 40 degree of tilt.

6.2

ARMREST

6.2.1

Two way armrest adjust for 6 cm in height and swivel into 3 angular positions.

6.3

BACKREST

6.3.1

A breathable polyester mesh suspension allows improve ventilation and


transpiration to provide exceptional thermal comfort. Back frame is moulded of
resilent black poly polypropylene.

6.4

LUMBER SUPPORT PAD

6.4.1

Lumber support shall be conveniently adjusted by side knobs without getting up


from chair to customize the exact support for various panel shapes.

6.5

CHAIR MECHANISM syncro- tilt chairs, synchronized mechanism, tilt tension


control multi position tilt lock, pneumatic seat height control, advanced swivel tilt
chair, tilt tension control multi position tilt lock & pneumatic seat height control.

6.6

BASE

6.6.1

This standard base is aluminum with black powder coated. Hooded dual wheel
castors in black nylon as per manufacturer's specifications, drawings & direction
of Engineer in charge.

7.0

CHAIR WITH FIXED ARM


LOW BACK CHAIR, PP FIXED ARM, BASE PP, TILT MECHANISM, NET BACK &
FABRIC TAPESTRY.

7.1

SEAT/BACK

7.1.1

The seat shall be made up of heat pressed plywood, upholestry with fabric and
molded poly urethane foam, together with moulded seat of 50 density. The back
is made of mesh type. Seat overall shall be 22'' wide and 18'' deep with waterfall
design. Seat height adjustable shall be 16'' to 18''. Back shall be 18'' with making
total chair height of 35.

7.2

POLYURETHANE FOAM

7.2.1

The foam shall be moulded with density 50-55 and hardness=20.

7.3

SEAT COVERS

7.3.1

The seat cover shall be injection moulded in black co polymer polypropylene.

7.4

ARMREST FIXED TYPE

7.4.1

The one piece armrest are made of black integral skin polyurethane with 50-70
hardness and reinforced with M.S. insert. The arm-rest are fitted onto the seat
with powder coated armrest brackets.

7.5

PNEUMATIC HEIGHT ADJUSTMENT

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 49

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

7.5.1

Has an adjustment stroke of 5cm.

7.6

PEDESTAL ASSEMBLY

7.6.1

The pedestal is injection moulded in black 30% glass filled nylon and fitted with
5 nos twin wheel castors.

7.7

TWIN WHEEL CASTORS

7.7.1

The twin wheel castors are injection moulded in 30% glass filled black nylon.

7.8

All are as per manufacturer's specifications, drawings & direction of Engineer in


charge.

8.0

CHAIR WITH ADJUSTABLE ARM

8.1

Providing and supplying medium Back Chair with PP adjustable arm. Base is
made of PP, having push back mechanism, net back, Fabric Tapestry.

8.2

SEAT/BACK

8.2.1

The seat shall be made up of heat pressed plywood, upholestry with fabric and
molded poly urethane foam of 50 density, together with moulded seat covers.
The back is made of mesh type. Seat overall shall be 22'' wide and 18'' deep
with waterfall design. Seat height adjustable shall be 16'' to 18''. Back shall be
18'' with making total chair height of 35.

8.3

POLYURETHANE FOAM

8.3.1

The foam is moulded with density 50-55 and hardness=20.

8.4

SEAT COVERS

8.4.1

The seat cover shall be injection moulded in black co polymer polypropylene.

8.5

ARMREST ADJUSTABLE TYPE

8.5.1

The armrest are made of black integral skin polyurethane with 50-70 hardness
and reinforced with M.S. insert. The arm-rest are fitted onto the seat with
powder coated armrest brackets. Arms height should be adjust upto 6-7 cms.

8.6

PNEUMATIC HEIGHT ADJUSTMENT

8.6.1

Has an adjustment stroke of 10cm.

8.7

PEDESTAL ASSEMBLY

8.7.1

The pedestal is injection moulded in black 30% glass filled nylon and fitted with
5 no twin wheel castors.

8.8

TWIN WHEEL CASTORS

8.8.1

The twin wheel castors are injection moulded in 30% glass filled black nylon.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 50

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

9.0

READING CHAIR
PU ARM, MS POWDER COATED BASE & FABRIC TAPESTRY.

9.1

Providing and supplying low Back Chair with PP arm. Seat fixed on MS tubular
frame.

9.2

SEAT/BACK

9.2.1

The seat and back shall be made up of heat pressed plywood, upholestry with
fabric and molded poly urethane foam, together with moulded seat covers. Seat
overall shall be 20'' wide and 18'' deep with waterfall design. Back shall be 15''
with making total chair height of 29.

9.3

POLYURETHANE FOAM

9.3.1

The foam is moulded with density 50-55 and hardness=20.

9.4

SEAT COVERS

9.4.1

The seat cover shall be injection moulded in black co polymer polypropylene.

9.5

ARMREST FIXED TYPE

9.5.1

The one piece armrest are made of black integral skin polyurethane with 50-70
hardness and reinforced with M.S. insert. The arm-rest are fitted onto the seat
with powder coated armrest brackets.

9.6

BASE

9.6.1

The Base is made of welded structure made of MS tubular frame.

9.6.2

All are as per manufacturer's specifications, drawings & direction of Engineer in


charge.

10.0

CHAIR FOR CAFETARIA

10.1

Providing and supplying cafeteria Chair with Plastic seat and back. Base shall be
made of pipe stand, as per manufacturer's specifications, drawings & direction of
Engineer in charge.

11.0

3 SEATER SOFA IN OFFICE ROOM

11.1

Sofa with Chrome Plated frame having cushion Tapestry. The base structure
shall be made of Pipe Stand in Chrome Finish. The above furniture should be as
per specification and sample approved by client.

12.0

CHAIR WITH CHROME BASE

12.1

Providing and supplying medium Back Chair with MS chrome arm. Base shall be
made of MS chrome, having centre tilt mechanism, PU upholstery.

12.2

SEAT/BACK

12.2.1

Seat overall shall be 22'' wide and 18'' deep. Seat height adjustable shall be 16''
to 18''. Back shall be 22'' with making total chair height of 39.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 51

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

12.3

ARMREST FIXED TYPE

12.3.1

The armrest shall be made of black integral skin polyurethane with 50-70
hardness and reinforced with M.S. insert. The arm-rest should be fitted onto the
seat with powder coated armrest brackets.

12.4

PNEUMATIC HEIGHT ADJUSTMENT

12.4.1

Has an adjustment stroke of 5cm.

12.5

PEDESTAL ASSEMBLY

12.5.1

The pedestal should be injection molded in chrome base and fitted with 5 no
twin wheel nylon castors.

12.6

TWIN WHEEL CASTORS

12.7

The twin wheel castors should be injection molded in 30% glass filled black
nylon.

12.8

All are as per manufacturer's specifications, drawings & direction of Engineer in


charge.

13.0

CHAIR MESH TYPE WITH FIXED BASE medium Back Chair with PP
adjustable arm. Base shall be made of MS tubular frame, having push back
mechanism, net back, Fabric Tapestry.

13.1

SEAT/BACK

13.1.1

The seat shall be made up of heat pressed plywood, upholstery with fabric and
molded poly urethane foam, together with moulded seat covers. The back
should be made of mesh type. Seat overall shall be 22'' wide and 18'' deep with
waterfall design. Seat height adjustable shall be 16'' to 18''. Back shall be 18''
with making total chair height of 35.

13.2

POLYURETHANE FOAM

13.2.1

The foam should be molded with density 50-55 and hardness=20.

13.3

SEAT COVERS

13.3.1

The seat cover shall be injection moulded in black co polymer polypropylene.

13.4

ARMREST ADJUSTABLE TYPE

13.4.1

The armrest shall be made of black integral skin polyurethane with 50-70
hardness and reinforced with M.S. insert. The arm-rest should be fitted onto the
seat with powder coated armrest brackets. Arms height should be adjust upto 67 cms.

13.5

PEDESTAL ASSEMBLY

13.5.1

The fixed type pedestal should be made of chrome finish tubular frame.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 52

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

13.5.2

All are as per manufacturer's specifications, drawings & direction of Engineer in


charge. The above furniture should be as per specification and sample approved
by client.

14.0

CHAIRS

14.1

Providing and supplying low Back Chair with chrome finish arm. Base should be
made of tubular pipe chrome plated, having plastic back

14.2

Wooden writing table of size 300 X 250 and Tapestry as per manufacturer's
specifications, drawings & direction of Engineer in charge.

15.0

STOOL FOR PATIENT DIMENSIONS: 12 X 12 X 20

15.1

Visitor Stools shall have ERW frame that makes it extremely durable. Moreover,
the legs of the stools are fitted with rubber feet. . To achieve long lasting
performance, these stools shall be pretreated and powder coated with 40-50
microns thick epoxy polyester powder coating oven baked at 180-200 degree
centralized temperature. The above furniture should be as per specification and
sample approved by client.

15.2

CRC or steel sheet duly double press bent

15.3

Pre-treated and epoxy powder coated

15.4

M.S. tubular frame fitted with PVC stump

16.0

SOFA

16.1

SOFA NORMAL IN FULLY LEATHER 3 SEATER Dimension L 2005 X D 760 X H


860

16.1.1

Base made of ply, moulded cushion 4'' high maple solids with double dowel
construction, corner blocked legs and rails.

16.1.2

Seat multi-density polyurethane foam, Catalyzed lacquer finish in all Cumberland


mapple finishes

16.1.3

Seat spring 6cm wide reinforced elastic straps fixed 4.5cm apart forming a thick
and extremely resistant base.

16.2

SOFA IN FULL LEATHERITE 1 SEATER, 2 SEATER AND 3 SEATER MODEL

16.2.1

Base ply with moulded cushion 4'' high

16.2.2

LEFT & RIGHT SIDE FRAME

16.2.2.1

Frames M.S. ERW tubes and chrome plated fitted at the extreme ends to form
leg assembly

16.2.3

MOUNTING FRAMES

16.2.3.1

Mounting frames made of M.S. ERW tubes assy. to hold the two side frame
together.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 53

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

16.2.4

ASSEMBLY

16.2.4.1

The complete frame shall be covered with replaceable leatherite. All external
surfaces have chrome finish.

16.3

SOFA FULL LEATHER IN 1 SEATER, 2 SEATER AND 3 SEATER MODEL

16.3.1

Base ply with moulded cushion 4'' high

16.3.2

LEFT & RIGHT SIDE FRAME

16.3.2.1

Frames M.S. ERW tubes and chrome plated fitted at the extreme ends to form
leg assembly.

16.3.3

MOUNTING FRAMES

16.3.3.1

Mounting frames made of M.S. ERW tubes assy. to hold the two side frame
together. Mounting frames assy. holds the two side frame together.

16.3.4

ASSEMBLY

16.3.4.1

The complete frame chrome finish covered with replaceable leather.

17.0

MANAGER TABLE LAMINATED SIZE 2000mm W X 800mm D X 750mm H

17.1

MANAGER TABLE PRE-LAMINATED BOARD WITH SIDE STORAGE

17.1.1

CREDENZA (SIDE UNIT) SIZE

17.1.1.1

1200mm x 450mm x 750mm

17.1.2

FULL HEIGHT BACK UNIT SIZE

17.1.2.1

1200mm x 450mm x 1800mm

17.1.3

PEDESTAL UNIT SIZE

17.1.3.1

400mm x 450mm x 670mm (Mobile type)

17.1.4

TABLE -TOP

17.1.4.1

25 to 40mm thick should be made of pre-laminated particle board

17.1.5

SHUTTERS

17.1.5.1

Should be made of 18mm thick pre-laminated particle board

17.1.5.2

The details of each unit are given as under

17.1.6

TABLE TOP D2000mm W X 800mm D X 750mm H

17.1.6.1

The table top consisting the top should be made out of 25-40mm thick prelaminated particle board. The edges of the top shall be covered with edge
bending tapes as per selection and approved design. The top shall be joined
with guide pin and dowels. Two number of strengthening support (vertical)
having rectangular shape and made out of 18mm thick pre-laminated particle

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 54

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

board of approved colour/design and


edges will be provided.

PVC edge banding on over all visible

17.1.7

SIDE SUPPORT WITH WOODEN LEGS

17.1.7.1

Two decorative wooden pillar legs (of any colour) with two supporting side &
one front supporting leg made out of 18mm thick pre-laminated particle board of
approved colour /design and decorative wooden beading at floor level (i.e. three
sides) . Having all necessary fittings of hettich/ebco make soft close hinges,
locks and any miscellaneous items.

17.1.8

SIDE CREDENZA UNIT DIMENSION 1200mm x 450mm x 750mm

17.1.8.1

The top of this unit should be made out of 25-40mm thick pre-laminated particle
board on the upper side. The edges of top shall be covered with edge bending
tapes as per selection and approved design and line with main table. Top rest on
two side supporting legs of size 450mm x 725 made out of 18mm thick prelaminated particle board. Flat edges duly sealed with PVC edges beading
modesty panel of size 1150 X 600 made out of 18mm particle board laminated.
Having all necessary fittings of hettich/ebco make soft close hinges, locks and
any miscellaneous items.

17.1.9

PEDESTAL UNIT DIMENSION 400MM X 450MM X 670MM

17.1.9.1

This unit shall be made out of 18mm thick pre-laminated board with having
three sliding drawer mounted on steel soft close telescopic channels having
centralized locking. Having all necessary fittings of hettich/ebco make soft close
hinges, locks and any miscellaneous items.

17.1.10

FULL HEIGHT BACK UNIT DIMENSION 1200mm x 450mm x 1800mm

17.1.10.1

The whole back unit should be made out of 18mm thick pre laminated particle
board of approved colour / design. The complete unit jointed with guide pins &
donels. Having all necessary fittings of hettich/ebco make soft close hinges,
locks and any miscellaneous items.

17.1.11
17.1.11.1

HANDLES
Handle shall be aesthetically designed handles in SS finish. All the exposed
edges are sealed with machine pressed 2mm thick PVC edge band. It shall have
rigid knock down construction.

17.1.12

The product should have ISO 9001:2000, OHSAS 18001:2007 and ISO 140012004 certifications.

18.0

MANAGER TABLE PRE-LAMINATED BOARD WITH SIDE STORAGE


METAL MODESTY

18.1

providing and supplying main table of dimension

18.2

MAIN TABLE TOP SIZE

18.2.1

1500mm W X 750mm D X 750mm H

18.3

CREDENZA (SIDE UNIT) SIZE

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 55

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

18.3.1

1200mm x 450mm x 750mm

18.4

PEDESTAL UNIT SIZE

18.4.1

400mm x 450mm x 670mm (Mobile type)

18.5

TABLE TOP

18.5.1

25 mm thick made of pre-laminated particle board

18.6

SHUTTERS

18.6.1

Shall be made of 18mm thick pre-laminated particle board

18.7

THE DETAILS OF EACH UNIT ARE GIVEN AS UNDER

18.7.1

Table Top

18.7.1.1

The table top size 1500mm W X 750mm D X 750mm H consisting the top should
be made out of 25mm thick pre-laminated particle board . The edges of the top
shall be covered with edge bending tapes as per selection and approved design.
The top shall be joined with guide pin and dowels. Top will be supported on
metal legs and should have metal modesty.

18.8

SIDE CREDENZA UNIT DIMENSION 1200mm x 450mm x 750mm

18.9

The top of this unit should be made out of 25mm thick pre-laminated particle
board on the upper side. The edges of the top shall be covered with edge
bending tapes as per selection and approved design and line with main table.
Top rest on two side supporting legs. The whole back unit would be made out of
18mm thick pre laminated particle board of approved colour / design. The
complete unit jointed with guide pins & donels.

18.10

Pedestal Unit DIMENSION 400mm X 450mm X 670mm

18.10.1.1

This unit should be made out of 18mm thick pre-laminated board with having
three sliding drawer mounted on steel telescopic channels having centralized
locking. Having all necessary fittings of hettich/ebco make soft close hinges,
locks and any miscellaneous items.

18.11

HANDLES

18.11.1

Handle shall be aesthetically designed handles in SS finish. All the exposed


edges are sealed with machine pressed 2mm thick PVC edge band. It shall have
rigid knock down construction.
The product should have ISO 9001:2000, OHSAS 18001:2007 and ISO 140012004 certifications.

18.12
19.0

MAIN TABLE

19.1

MAIN TABLE TOP SIZE

19.1.1

2100mm W X 900mm D X 750mm H

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 56

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

19.1.2

CREDENZA (SIDE UNIT) SIZE

19.1.3

1200mm x 450mm x 750mm

19.2

FULL HEIGHT BACK UNIT SIZE

19.2.1

2400mm x 450mm x 1800mm

19.3

PEDESTAL UNIT SIZE

19.3.1

400mm x 450mm x 670mm (Mobile type)

19.4

TABLE -TOP

19.4.1

25 to 40mm thick should be made of MDF board having veneer finish

19.5

SHUTTERS

19.5.1

Should be made of MDF board with veneer finish

19.6

The details of each unit are given as under

19.6.1

TABLE TOP

19.6.1.1

The table top size 2100mm W X 900mm D X 750mm H consisting the top should
be made out of 25-40mm thick MDF board having veneer finish . The edge of
the top should have reverse bull nose edge. The edges of the top shall be
properly finished as per selection and approved design. The top will be joined
with guide pin and dowels. Two number of strengthening support (vertical)
having rectangular shape and made out of 18mm thick MDF board with veneer
finish of approved colour/design shall be provided.

20.0

CHAIRMAN TABLE IN VENEER FINISH

20.1

SIDE SUPPORT WITH WOODEN LEGS

20.1.1

Two decorative wooden pillar legs (of any colour) with two supporting side &
one front supporting leg made out of 18mm thick MDF board with veneer finish
of approved colour /design and decorative wooden beading at floor level (i.e.
three sides).

20.2

SIDE CREDENZA UNIT

20.2.1
20.2.1.1

1200mm x 450mm x 750mm


The top of this unit should be made out of 25-40mm thick MDF board with
veneer finish. The edge of the top should have reverse bull nose edge matching
with the main table top. The edges of top shall be properly finished as per
approved design and line with main table. Top rest on two side supporting legs
of size 450mm x 725 made out of 18mm thick MDF board with veneer finish.
Having all necessary fittings of hettich/ebco make soft close hinges, locks and
any miscellaneous items.

20.3

PEDESTAL UNIT

20.3.1

400mm X 450mm X 670mm

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 57

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

20.3.1.1

This unit shall be made out of 18mm thick MDF board with veneer finish having
three sliding drawer mounted on steel telescopic channels having centralized
locking. Having all necessary fittings of hettich/ebco make soft close hinges,
locks and any miscellaneous items.

20.4

FULL HEIGHT BACK UNIT SIZE DIMENSION 2400MM X 450MM X 1800MM

20.4.1.1

The whole back unit would be made out of 18mm thick MDF board with veneer
finish of approved colour / design. The complete unit jointed with guide pins &
donels. Having all necessary fittings of hettich/ebco make soft close hinges,
locks and any miscellaneous items.

20.5

HANDLES

20.5.1

Handle shall be aesthetically designed handles in SS finish. All the exposed


edges are sealed with machine pressed 2mm thick PVC edge band. It shall have
rigid knock down construction.

20.6

The product should have ISO 9001:2000, OHSAS 18001:2007 and ISO 140012004 certifications. The above furniture should be as per specification and
sample approved by client.

21.0

CENTER TABLE AND CORNER TABLES IN MANAGER'S CABIN DIMENSION


1100 MM L X 750MM D X 450MM H.

21.1

Table in shape of rectangle/oval/mushroom type/square.

21.2

Made with teak wood having open grain wenge stain and white lacquered glass
on the top.

22.0

CENTRE TABLE AND CORNER TABLE DIMENSION 550 MM L X 550MM D X


450MM H.

22.1

Table in shape of rectangle/oval/mushroom type/square.

22.2

Table with top made of 10mm thick toughened glass fixed using the studs. With
base legs made of metal of 16 gauge. The above furniture should be as per
specification and sample approved by client.

23.0

DISCUSSION TABLE

23.1

DISCUSSION TABLE/ CONFERENCE TABLE VENEER FINISH DIMENSION 7200MM


W X 1800MM D X 750MM H.

23.1.1

Work surface (Oval shape) shall be made of 40MM thk MDF Board Top having
veneer finish with all the exposed edges been proper finish. The glass shall be
fixed in between for designer look.

23.1.2

The legs shall be made of 25mm MDF board with veneer finish and having
straight profile.

23.1.3

Modesty panel shall be made of 25mm MDF board with veneer finish and having
straight profile.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 58

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

23.1.4

Along with 2 Nos motorized wire manager with brush flap of dimension
W374mm*D110mm*H103mm) for provision of three power, one data, one
VGA, one audio, one microphone.

23.2

DISCUSSION TABLE /CONFERENCE TABLE LAMINATE FINISH DIMENSION


2700MM W X 900MM D X 750MM H

23.2.1

Work surface shall be made of 25MM thk pre-laminated particle Board Top with
all the exposed edges been proper finish with PVC edge bending.

23.2.2

The legs shall be made of 25mm thick pre-laminated particle board having
straight profile.

23.2.3

Modesty panel shall be made of 25mm thick pre-laminated particle board having
straight profile.

23.2.4

Along with 1 No motorized wire manager with brush flap of dimension


W374mm*D110mm*H103mm) for provision of three power, one data, one
VGA, one audio, one microphone.

23.3

DISCUSISON TABLE ROUND TOP DISCUSSION TABLE DIMENSION DIA 900MM


W X 750MM H

23.3.1

Work surface shall be made of 25MM thk pre-laminated particle Board Top with
all the exposed edges been proper finish with PVC edge bending.

23.3.2

The legs shall be made of unique die casted legs with chrome finish

23.3.3

Having all necessary fittings of hettich/ebco make hindges . All the worktops
should have metal inserts on the underside of worktops for coupling with metal
screws for complete modularity

24.0

LAB WORKING PLATFORM

24.1

Providing and supplying lab tables shall fulfill following specifications ,

24.2

Table top should made of (18 to 20mm) thick JET BLACK GRANITE TOP.
Supported by ply of 6mm.

24.3

Table frame should of E.R.W.M.S. square Tubes 25x25mm thick and finished
with epoxy powder coating.

24.4

Under bench should have storage modules made of 21 G C.R.C.A. Sheets.

24.5

The shutters are mounted to the modules by hinges which are open-able to 95
degree & self-closing on return.

24.6

Telescopic channels shall be used for the slick telescopic drawer slides which are
very sturdy & can take load upto 30kg. Modules completely finished with epoxy
powder coating. With minimum coating layer 40-50 micron.

25.0

LOCKERS LAB

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 59

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

25.1

LOCKERS DIMENSION W-380XD-458XH-1800.

25.2

The personal locker with in-built locks and without in-built locks i.e, pad lock
type having configuration depending on site conditions and the body size are
380 wide, 458 deep ,1800 high for 6 lockable doors, The allowable dimensional
tolerance for overall size of the Locker is (+ / - 5mm). Similarly in the angle
bending (+ / - 3) in degree. All the components are finished 40 to 50 microns
thick epoxy polyester powder coating oven baked at 180 to 200 deg. C. Body
shall be made of 0.8mm CRCA sheets and complete structure is Powder Coated.
The shutters of lockers shall be fixed with hinges having removable pins.

25.3

LOCKING ARRANGEMENT - Shall have 4 dial combination lock with ABS housing
having green & Red indicator. With override Emergency master key & decode
function. It should have provision of resetting combination after unlock.

25.4

Door Locker with each locker of dimension 380 W X 458mm D. Shall have
provision for Index card holder and Ventilation holes.

26.0

BENCHES IN LOCKER ROOM

26.1

Providing and supplying benches in locker room of length 1200mm, height


400mm and 300mm depth and Frames shall be constructed from strong
38x38mm RHS steel which have a tough powder coat finish. Benches are
supplied with a choice of solid Ash or Sapele hardwood timber slats which are
finished with a tough satin lacquer.

27.0

DISPLAY RACK

27.1

Providing and fixing of DISPLAY RACKS DIMENSION 6000MM W X 450MM D X


2100MM H

27.2

CONSTRUCTION

27.2.1

Rigid knock down construction.

27.3

MATERIAL

27.3.1

Structure shall be made with combination of powder coated aluminium and


CRCA of approx 50-60 micron. Front shall have the Glass shutters. All necessary
fittings of hettich/ebco make hinges.

27.4

STACKABILITY

27.4.1

The add on units can be stacked width wise to form a bank of racks having
common side panel.

27.5

ACCESSIBILITY from front sides.

27.6

NUMBER OF RACKS

27.6.1

Bottom plus 4 fixed racks on each side

28.0

TABLE FOR PLANT SCALE MODEL DIMENSION 2000MM W X 2000MM D


X 750MM

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 60

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

28.1

Table top made of 12mm thick toughened glass. Supported on designer base
made of powder coated legs.

28.2

WORKSURFACE

28.2.1

With table top made of 10-12mm thick toughened glass. The height of Table top
is 750mm.

28.3

LEGS

28.3.1

Top Supported on M.S. powder coated legs and structure size is 40 X 40.

28.4

Powder coating of approx 50-60 micron is done. Structure shall be complete


knock down.

28.5

The product should have ISO 9001:2000 and ISO 14001-2004 certifications.

29.0

READER'S TABLE DIMENSION 1800MM W X 900MM D X 750MM H.

29.1

WORKSURFACE

29.1.1

With table top shall be made of 25mm thick pre-laminated particle board. All the
exposed edges are sealed with machine pressed 2mm thick PVC edge band. The
height of Table top is 750mm.

29.2

LEGS

29.2.1

Top Supported on powder coated legs and structure .powder coating of approx
50-60 micron is done.

29.3

The product should have ISO 9001:2000, OHSAS 18001:2007 and ISO 140012004 certifications.

30.0

WOODEN LIBRARY RACKS

30.1

Providing and fixing of wooden library racks

30.2

PRODUCT SIZE DIMENSION 900MM W X 450MM D X 1800MM H

30.3

CONSTRUCTION

30.3.1

Rigid knock down construction.

30.4

MATERIAL

30.4.1

BACK PANEL shall be made of 18mm thick pre laminated particle board.
SKIRTING & SIDE PANELS shall be made of 18 mm thick pre laminated particle
board.
With PVC edge bending on all the exposed edges. Having all necessary fittings
like hettich/ebco make hinges.

30.5
30.6

STACKABILITY

30.6.1

The add on units can be stacked width wise to form a bank of racks having
common side panel.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 61

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

30.7

ACCESSIBILITY from front and back as the racks are available on both the sides.

30.8

NUMBER OF RACKS

30.8.1

Bottom plus 4 fixed racks on each side

30.9

Label holder in each main unit to apply label for indication.

31.0

TABLES DIMENSION 1200X600


keyboard trey & CPU Trolley

31.1.1

providing and supplying main table of dimension 1200 X 600 X 750

31.1.2

WORKSURFACE

31.1.2.1

With table top shall be made of 25mm thick pre-laminated particle board. All the
exposed edges are sealed with machine pressed 2mm thick PVC edge band. The
height of Table top is 750mm.

31.1.3

WIRING

31.1.3.1

The metal raceway has been provided to fix the data and power cable sockets in
table.

31.1.4

LEGS

31.1.4.1

Top Supported on 2 powder coated module legs. Legs shall be made of leg
frame, fascia & caps and tubes. Leg frame shall be made up of mild steel. Leg
fascia shall be made of CRCA and all are powder coating of approx. 50-60
micron.

31.1.5

MODESTY

31.1.5.1

Modesty panel shall be made of 18mm thick pre-laminated particle board.

31.1.6

PEDESTAL

31.1.6.1

Module pedestals shall be constructed from pre-laminated particle board


consisting of 2 utility drawer and 1 filing box drawer.

(MAIN

TABLE).

With

pedestal,

The product should have ISO 9001:2000, OHSAS 18001:2007 and ISO 14001-2004
certifications.
31.2

STUDY TABLE IN HOSTEL DIMENSION 750MM WX450MM DX750MM H.

31.2.1

WORKSURFACE

31.2.1.1

The top shall be made of 25mm thick pre-laminated particle board with all the
visible edges covered with PVC edge bending.

31.2.2

LEGS

31.2.2.1

Made of 18mm thick pre-laminated particle board. With all the exposed edges
shall be covered with 2mm thick edge bending.

31.2.3

MODESTY PANEL

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 62

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

31.2.3.1

Made of 18mm thick pre-laminated particle board. With all the exposed edges
shall be covered with 2mm thick edge bending.

31.2.3.2

Shall be provided with combination of storages and overhead storages having


closed shutters fixed with hinges. The table shall have one drawer having locking
arrangement.

32.0

SINGLE BED IN HOSTEL QUEEN SIZE BED BASICALLY DIMENSION


1981mm X 1524mm X 360mm

32.1

STRUCTURE

32.1.1

M.S. welded frame. And having pre-laminated gladding.

32.2

The bed base shall be made of 16 gauge mild steel. The structure shall be
galvanized and powder coated.

32.3

The top should be made of 12mm thick blackboard or PLPB finished with polish
to resist with moisture.

33.0

DOUBLE BED IN HOSTEL DIMENSION 1500MM X 1800MM X 360MM

33.1

Queen size bed made of wood bed without storage.

33.2

STRUCTURE

33.3

M.S. welded frame. And having pre-laminated gladding.

33.4

HEADBOARD

33.5
33.6

It shall have head board made of pre-laminated particle board.


The bed base shall be made of 16 gauge mild steel. The structure shall be
galvanized and powder coated.
The top should be made of plywood finished with polish to resist with moisture.

33.7
34.0

BED FOR PATIENT OVERALL DIMENSION: 203 (L) X 90 (W) X 60 (H)


CM

34.1

Hospital Bed that is manufactured using high grade mild steel. These beds
should have precise steel tubular frame work.

34.2

Frame work made of rectangular/ square M.S. tube

34.3

Top made of welded wire mesh

34.4

Tubular head & foot bows of unequal height

34.5

Location for Four I. V Rod

34.6

Finish: Epoxy powder coated.

35.0

SEMINAR HALL AREA

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 63

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

35.1

AUDITORIUM CHAIR FLOOR GROUTED

35.1.1

Seat shall have Self Tip Up Cushion. The Centre distance ( Arm rest to Arm
rest ) 22 as required for different sizes mentioned for different locations, Sheet
Metal Components Side Stand 70mm X 30mm heavy gage pipe. 7mm HR Plate
iron sheet deep drawn footrest.

35.1.2

Tip-up System shall have seat supporting tray of dimension 40 X 3 mm and Back
Clamps is of 14G HR sheet x 2 Nos.

35.1.3

Seat& Back Frame shall be made of 15mm thick Ply wood and Back frame is
made of Iron Frame MS Flat Patti.

35.1.4

Polyurethane Foams I Seat & Back cushioned with molded non-sagging


polyurethane molded foam of 50 density. Density is about : 50 +/- 5 Kg / M3
as Per JIS K 6401

35.1.5

Hardness of cushion is about 120 (+30 / - 20) Newton and of Back rest is 80
(+30 / - 10) Newton.

35.1.6

Constant Compression Set: (Max 13%) JIS K 6401.

35.1.7

Fabric shall exactly be as per the sample approved by and the Color / Shade.

35.1.8

Spring For Auto-Tip-Torsion

35.1.9

Arm rest Wooden arm rest with PPCP Writing Pad

35.1.10

Back Cover PPCP

35.1.11

Seat Cover PPCP

36.0

RECEPTION TABLE

36.1

RECEPTION TABLE DIMENSION 2000 X 750 X 750 (worktop height) with following
elements.

36.2

WORKSURFACE

36.2.1

Table top shall be made of 36mm thick Acrylic solid surface (corian top only of
DU-POINT). Supported on designer base either made of corian or of veneer
finish.

36.2.2

GLASS

36.2.2.1

Frosted glass of 10mm thick is fixed with studs for designer's look.

36.2.2.2

It includes fixed type 3 drawer pedestal of veneer finish.

36.2.2.3

The product should have ISO 9001:2000, OHSAS 18001:2007 and ISO 140012004 certifications.

37.0

MODEL AND CHART TABLE DIMENSION 2400 X 1200 X 750

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 64

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

37.1

Table top made of 12mm thick toughened glass. Supported on designer base
either made of chrome finish or of veneer finish.

37.2

Providing and fixing of reading table of dimension 12400 X 1200 X 750

37.3

WORKSURFACE

37.3.1

With table top made of 10-12mm thick toughened glass. The height of Table top
is 750mm.

37.4

LEGS

37.4.1

Top Supported on powder coated 40 X 40 metal legs and structure .powder


coating of approx 50-60 micron is done.

37.4.2

The product should have ISO 9001:2000, OHSAS 18001:2007 and ISO 140012004 certifications.

38.0

CAFETARIA TABLE DIMENSION 900MM X 750MM H. X 600 D.

38.1

WORKSURFACE

38.1.1

The top shall be made of 25mm thick pre-laminated particle board with all the
visible edges covered with PVC edge bending.

38.2

LEGS

38.2.1

Made of chrome finish. Having all necessary fittings like hettich/ebco make
hinges.

39.0

METAL RACK

39.1.1

Providing and supplying metal racks of dimension W-900xD-450xH-2100.

39.1.2

Free standing CRCA rack with following features

39.2

PRODUCT SIZE DIMENSION W-900xD-450xH-2100.

39.2.1

CONSTRUCTION

39.2.1.1

Body is made of 0.8mm CRCA sheets. Complete structure is Powder Coated. All
the components are finished 40 to 50 microns thick epoxy polyester powder
coating oven baked at 180 to 200 deg. C. The Rack angle is precision punches
slotted strips bended at sides to support the shelves to ensure flexibility in
adjusting the height of the shelves.

39.2.2

LOAD CAPACITY

39.2.2.1

Shelves shall be able to carry maximum 40kgs. UDL (Uniformly Distributed Load.

39.2.2.2

The Rack shelves are fabricated with integrated welded construction.

39.2.2.3

Adjustable Shelves making 5 Compartments. Knock down Structure.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 65

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

39.2.2.4

Having all necessary fittings like hettich/ebco make hindges, locks and any
miscellaneous items.

40.0

LECTURE ROOM TABLE OF DIMENSION 1200X600 X 750 (Main Table).


including pedestal, keyboard trey & CPU Trolley

40.1

WORKSURFACE

40.1.1

With table top shall be made of 25mm thick MDF board with veneer finish. All
the exposed edges are sealed with proper finish. The height of Table top is
750mm.

40.2

WIRING

40.2.1

The metal raceway has been provided to fix the data and power cable sockets in
table. Along with 1 No motorized wire manager with brush flap of
dimensionW374mm*D110mm*H103mm) for provision of three power, one
data, one VGA, one audio, one microphone.

40.3

LEGS

40.3.1

Top Supported on 2 powder coated module legs. Legs shall be made of leg
frame, facia & caps and tubes. Leg frame shall be made up of mild steel. Leg
fascia shall be made of CRCA and all are powder coating of approx. 50-60
micron.

40.4

MODESTY

40.4.1

Modesty panel made of CRCA sheet. Metal modesty shall be made of 0.8mm
thick CRCA sheet and shall have square holes of 7mmx7mm in 50mm pitch along
vertically and horizontally.

SCOPE OF WORK IS DETAILED IN BILL OF QUANTITY (BOQ) & TENDER DRAWINGS (REFER
FORM 1-D OF SCHEDULE OF PRICES). IN CASE OF ANY CONFLICT WITH THE GENERAL
SPECIFICATION SPECIFIED ABOVE AND THE BILL OF QUANTITY(BOQ) AS PER FORM-1D,
THE TECHNICAL SPECIFICATION MENTIONED IN BILL OF QUANTITY ( FORM 1 D) SHALL
PREVAIL.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 66

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

GENERAL SPECIFICATION FOR CEILING & PARTITION

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 67

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

1.0

GENERAL SPECIFICATIONS FOR CEILING & PARTITION

1.1

General Requirements.

1.1.1

The section of the specification shall be read in conjunction with the Drawings, other
Contract Documents and other sections of these specifications which shall be deemed
to be complementary to one another. The Contractor carrying our this work shall be
responsible for providing all plant, tools, materials and all things necessary for the
proper execution, completion and maintenance of these works.

1.2

Dimensions

1.2.1

Figured dimensions shall be taken in preference to scaled dimensions in all cases.


Before commencing any work the Contractor shall verify all requirements on the Site.

1.3

Samples

1.3.1

A Sample of every item of furniture / paneling / cladding / flooring / all other


components, including their parts shall be submitted for approval before an order is
placed or manufacture commences. Approved samples shall be used as standards of
finish and workmanship.

1.4

Joints and Adhesives

1.4.1

All joints shall be standard Mortise and tennon / dowel / dovetail / cross-halved /
itred / tongue & groove / rebated. False Ceiling/Partition and wall cladding work and
as per approval of the Project Manager / Architect.

1.5

Fastenings

1.5.1

Screws, nails etc, shall be of standard iron / wire unless otherwise shown on
drawings.

1.6

Hardware

1.6.1

Hinges, locks, latches, door tracks, nail hides etc shall be as specified or an approved
substitute equal to or better than the specified.

1.7

Metal

1.7.1

Where metal frames like are used, these shall be welded, brazed, bolted or as
required, and on finished surfaces, welding, brazing, and riveting shall be ground so
that no evidence of this is apparent on the final finish of the metal.

1.8

Finish

1.8.1

Finishes shall be fully in accordance with the drawings and schedules. Where timber
is in natural finish, pieces shall be matched for colour and grain before assembly.
Where timber is stained the stain shall be matched throughout. Backs of wall-hung
case of ceiling and wall cladding shall be treated with an approved brand of wood
preservative.
THE RATES QUOTED SHALL BE INCLUDING ALL WASTAGES. THE
MEASUREMENT WILL BE TAKEN ON THE LAID AREA AND FOR THE FINISHED
PRODUCT ONLY.

1.9

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 68

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

1.10

MATERIAL ORDER STATUS / RECEIPTS AT SITE :The Contractor shall inform the
Project Manager as regards the quantity & quality of the material received / available
on site. The Project Manager shall check the material stock for quantity as well as
quality. He may or may not give any prior notice to the Contractor before such a
check. The Contractor shall ensure that the Project Manager has full access to his
stores at all times.

2.0

STANDARD WORKMANSHIP

2.1

To determine the acceptable standard of workmanship, the Contractor shall execute a


portion of the items of work as sample, for approval of the Architect, before taking up
the actual execution of the particular item of work.

2.2

These samples, on approval of the Owner / Architect, shall be the guiding sample for
execution of the particular item of work. Work not conforming to the approved
sample shall be rejected. Rates quoted for the items shall include for such
preliminary work and shall not be paid for separately.

3.0

CEILING WORK

3.1

GYPSUM BOARD (SUSPENDED CEILING REGULAR)

3.1.1

Suspended ceiling, which includes GI perimeter channels of size 0.55 thick along with
perimeter of ceiling, screw fixed to brick wall/partition with the help of nylon sleeves
and screws, at 610mm centres.

3.2

JOINTING & FINISHING

3.2.1

Finally square and tapered edges of the boards are to be jointed and finished so as to
have a flush look which includes filling and finishing with jointing compound, joint
paper tape and two coats of drywall top coat suitable for Gypboard (as per
recommended practices of BPB India Gypsum).

3.2.2

Alternatively all square & tapered edge joints to be filled with Universal Board finish
plaster & joint paper tape is embedded to complete the first application. Finally 2mm
thick Board finish plaster is applied on the entire surface of Gypboard to achieve
smooth & seamless finish. The plaster application shall be carried out with BPB T & T,
as per the recommended specification of BPB IGL.

3.2.3

For lighting fittings, grills, diffusers & cut-outs etc. have to be made with the frame of
perimeter channels, supported suitably & should be considered.

3.2.4

All steel sections shall be marked with Gypsteel TM (registered trademark of BPB
IGL) & Holograms

3.3

GYPSUM GRID CEILING

3.3.1

BPB Suspended grid system with galvanized steel T section frame work of hot
dipped galvanized steel pre-coated (exposed portion only), which includes flush fitting
900mm long cross tees to be interlocked between main runners at 600mm centres to
form 900 x 600mm modules. Cut cross tees longer that 600mm to be supported

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 69

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

independently .600 x 600mm modules to be formed by fitting 600mm long flush


fitting cross tees centrally between the 900mm cross tees.
3.4

DESCRIPTION

3.4.1

Suspension system: The BPB suspension system shall be of hot dipped pre-coated
galvanized steel sections which includes the following members:

3.4.1.1
3.4.1.2
3.4.1.3
3.4.1.4

Main Runner: T Section of size 38 x 24 x 0.35mm & 3.6mtr long


Cross Runner: T Section of size 25 x 24 x 0.30mm & 1.2mtr long
Cross Runner: T Section of size 25 x 24 x 0.30mm & 0.6mtr long
Wall Angle: 24 x 24 x 0.45mm & 3.05mtr long

3.4.2

The T section shall be suspended from the soffit with the help of soffit cleat, Rawl
plug, and GI wire rod of 4mm dia with galvanized spring level clips at 900mm
centers.

3.5

BOARDING

3.5.1

8mm/9.5mm/12.5mm thick Gypboard ceiling panel of size 595mm x 595mm shall be


placed into the grid size of 600 x 600mm.

3.6

GLAZING

3.6.1

All glass is to be of approved manufacturer of approved quality and shall be free from
bubbles, smokes, waves, air holes and other defects. The kind of glass to be used
shall be as mentioned in the item or specification or in the special provisions or as
shown in detailed drawings. Thickness of glass panel shall be uniform. All glass to be
approved manufacture complying with IS: 3548 196 or as per approved quality and
sample.

3.6.2

The compound for glazing to metal is to be special non-hardening compound


manufacture for the purpose and of 9 brand and quality approved the EIC.

3.6.3

While cutting glass, proper allowance by made for expansion. Each square of glazing
to be in one whole sheet. On completion of work, all glass shall be cleaned inside and
outside and all cracked scratched and broken panes shall be replaced and left in a
good condition.

3.6.4

All exposed edges of glass shall be lead polished.

4.0

POST CAP METAL CEILING SYSTEM

4.1

METAL CEILING SYSTEM

4.1.1

Providing & fixing of Lindner LMD B 117 Post cap ceiling system LindnerGermany/Bardiss make according to EN 13964 TAIM Quality standard made up of
0.6 mm thick galvanized steel with swing down function, of size 1800X600 mm in
combination with standard 100 mm wide Post cap 11/30/100/30/11 mm, 1.00 mm
pre-galvanized steel, polyester powder coated RAL 9010 (white) , length: 3425 mm
along with end caps of post cap panels as per site requirement, square edge,
perforated to Rv 1,8-20, electro statically applied powder coating of color RAL 9010
with a Gloss rate of 20% with RAL 9010 and manufactured as per applicable EN
13964/10152/10346. Substructure Components to be manufactured with cold rolled
zinc galvanized steel in accordance with EN 13964/10152/10346 and EN ISO 12944.
at position 10/15/65 Threaded rod DIN 976-1 M6 X length with hexagonal nut M6

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 70

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

and zinc galvanized fender washer and fastening of threaded to rod suspension to
concrete slab by Hilti Anchor Fastener. Position no. 111 screwed to post cap crossing
box by means of self drilling screw, suspension by means of threaded rod and the
post cap size is 100 mm , The system should be in accordance with Material class A2s1,d0 according to EN 13501-1 "non-combustible, per the Direction of Arch-inCharge
4.2

MATERIAL

4.2.1

Metal suspended corridor ceiling panel shall be manufactured from polyester powder
coated electro galvanized steel with perforated and plain surfaces supported by post
cap profiles. The suspended ceiling shall comprise of suspension made up of
/30/100/30/11 mm, 1.00 mm pre-galvanized steel, polyester powder coated RAL
9010 (white), length: 3425 mm along with end caps of post cap panels, supported by
suspension allowing the panels to swing and slide providing maximum accessibility to
the void and all the perforated panels to be fitted with black acoustic tissue.

4.3

PANEL

4.3.1

The panel size is 1800X600-625 mm, panel with 0.6 mm thickness nominal.
Manufactured from electro galvanized steel with square edges to all four sides with
drop down and slide function, Perforation patter Rv 1,8.20( 1.8 mm dia hole and 20%
open area), polyester powder coated in RAL 9010 with minimum 60 microns
thickness shall be electro statically applied complete with factory fitted black acoustic
tissue along with the fixed panel of /30/100/30/11 mm, 1.00 mm pre-galvanized
steel, polyester powder coated RAL 9010 (white) , length: 3425 mm along with end
caps of post cap panels manufactured from electro galvanized steel , polyester
powder coated in RAL 9010 with minimum 60 microns thickness.

4.4

ACCESS

4.4.1

All the middle panels must be able to drop & slide and provide full and easy access to
the ceiling void

4.5

LEVEL

4.5.1

All the panels should be fitted to ensure accurate positioning & level of the ceiling
system as per the site/architectural requirements.

4.6

GENERAL SUSUPENSION SYSTEM

4.6.1

The panels shall be supported by the suspension system Post cap 11/30/100/30/11
mm, 1.00 mm pre-galvanized steel, polyester powder coated RAL 9010 (white) ,
length: 3425 mm along with end caps of post cap panels as per site requirement,
square edge, perforated to Rv 1,8-20, electro statically applied powder coating of
color RAL 9010 with a Gloss rate of 20% with RAL 9010 and manufactured as per
applicable EN 13964/10152/10346. Substructure Components to be manufactured
with cold rolled zinc galvanized steel in accordance with EN 13964/10152/10346 and
EN ISO 12944. at position 10/15/65 Threaded rod DIN 976-1 M6 X length with
hexagonal nut M6 and zinc galvanized fender washer and fastening of threaded to
rod suspension to concrete slab by Hilti Anchor Fastener. Position no. 111 screwed to
post cap crossing box by means of self drilling screw, suspension by means of
threaded rod and the post cap size is 100 MM.

4.7

FINISH

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 71

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

4.7.1

Finish of the ceiling tiles should be electro statically applied polyester powder coated
of minimum 60 microns with 20% gloss. Pre painted products will not be permitted.

4.8

FIRE PERFORMANCE

4.8.1

The system should be in accordance with Material class A2-s1, d0 according to EN


13501-1 "non-combustible.

4.9

PROVISIONS FOR LIGHT AND OTHER FITTINGS

4.9.1

The panels will be cut on site for the provision of light fixtures and other fittings as
per the directions of the Engineer In charge

4.10

MANUFACTURING TOLENRANCES

4.10.1 All the metal ceiling elements and the corresponding substructure should be
manufactured in accordance with ceiling standards accessed by EN 13964 & TAIM
(Federation of Industrial Metal Ceiling Manufacturers).
4.11

GREEN BUILDING

4.11.1 The metal ceiling systems should be applicable for certifications in accordance to
LEED & DGNB, Environmental product decelerations (EPD) to be submitted when
ever asked.
4.12

WARRANTY CERTIFICATE

4.12.1 Manufacturer should submit the warranty certificate for the minimum 15 years.
4.13

MEASUREMENT

4.13.1 Length & breadth of the finished ceiling shall be measured correct to a centimeter.
The area shall be calculated in square meter correct to two decimal places. No
deduction shall be made for making openings for electrical, air conditioning, fire
fighting fixtures nor shall extra payment be made either for extra materials or labor in
making such openings.
4.14

RATES

4.14.1 The rate shall include the cost of all the materials, machinery, manpower involved in
all the operations described above including cartage, loading , unloading , all taxes
like VAT, service tax, custom duty etc except the scaffolding material and the erection
labor cost
5.0

CANOPY METAL CEILING SYSTEM

5.1

METAL CEILING SYSTEM

5.1.1

Providing & fixing of canopy ceiling system made up of 0.7 mm thick galvanized steel
of custom size as per site requirement, perforated to 1.8 mm and 20% open area(
Rv1,8,20) Entire ceiling construction is to be carried out according to EN 13964, as
per manufacturer specifications.

5.2

MATERIAL

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 72

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

5.2.1

Metal suspended Canopy ceiling panel shall be manufactured from polyester powder
coated electro galvanized steel with perforated and plain surfaces., supported by
suspension allowing the panels to swing and slide providing maximum accessibility to
the void and all the perforated panels to be fitted with black acoustic tissue.

5.3

APPROVED SYSTEM

5.3.1

The panel size is custom shape panel with 0.7 mm thickness nominal. Manufactured
from electro galvanized steel with square edges to all four sides with drop down and
slide function, Perforation patter Rv 1,8.20( 1.8 mm dia hole and 20% open area),
polyester powder coated in RAL 9010 with minimum 60 microns thickness shall be
electro statically applied complete with factory fitted black acoustic tissue, polyester
powder coated RAL 9010 (white) panels manufactured from electro galvanized steel ,
polyester powder coated in RAL 9010 with minimum 60 microns thickness.

5.4

ACCESS

5.4.1

All the middle panels must be able to drop & slide and provide full and easy access to
the ceiling void

5.5

LEVEL

5.5.1

All the panels should be fitted to ensure accurate positioning & level of the ceiling
system as per the site/architectural requirements.

5.6

GENERAL SUSUPENSION SYSTEM

5.6.1

The panels shall be supported by the suspension system of hook on system made up
of galvanized steel.

5.7

FINISH

5.7.1

Finish of the ceiling tiles should be electro statically applied polyester powder coated
of minimum 60 microns with 20% gloss. Pre painted products will not be permitted.

5.8

FIRE PERFORMANCE

5.8.1

The system should be in accordance with Material class A2-s1, d0 according to EN


13501-1 "non-combustible.

5.9

PROVISIONS FOR LIGHT AND OTHER FITTINGS

5.9.1

The panels will be cut on site for the provision of light fixtures and other fittings as
per the directions of the Engineer In charge

5.10

MANUFACTURING TOLENRANCES

5.10.1 All the metal ceiling elements and the corresponding substructure should be
manufactured in accordance with ceiling standards accessed by EN 13964 & TAIM
(Federation of Industrial Metal Ceiling Manufacturers).
5.11

GREEN BUILDING

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 73

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

5.11.1 The metal ceiling systems should be applicable for certifications in accordance to
LEED & DGNB, Environmental product decelerations (EPD) to be submitted when
ever asked.
5.12

WARRANTY CERTIFICATE

5.12.1 Manufacturer should submit the warranty certificate for the minimum 15 years
5.13

MEASUREMENT

5.13.1 Length & breadth of the finished ceiling shall be measured correct to a centimeter.
The area shall be calculated in square meter correct to two decimal places. No
deduction shall be made for making openings for electrical, air conditioning, fire
fighting fixtures nor shall extra payment be made either for extra materials or labor in
making such openings.
5.14

RATES

5.14.1 The rate shall include the cost of all the materials, machinery, manpower involved in
all the operations described above including cartage, loading , unloading , all taxes
like VAT, service tax, custom duty etc except the scaffolding material and the
errection labor cost
6.0

CORRIDOR METAL CEILING SYSTEM

6.1

METAL CEILING SYSTEM

6.1.1

Providing and Fixing of Corridor Ceiling system (Drop & Slide System) The panels
shall be supported by the suspension system made from extruded drop & slide hook
on profile, wall connection, 15 mm, aluminium, polyester powder coated RAL 9010 of
length 5000 mm along with perimeter trim 43/65/2mm, made up of steel polyester
powder coated according to RAL 9010( of Lindner) of length 2500 mm in accordance
with EN 13964 /10152 and the length will be continued by using connector for
extruded drop-slide hook on profile made up of 2.0 mm thick pre galvanized steel,
supported by Hanger bracing , L angle of 2.0 mm thick GS( Electro-Galvanized
Steel) perforated angle of size 22/28 mm and length 6000 mm, Longitudinal
connector for hook on profile made up of 1.0 mm thick GMS( Electro-Galvanized
Steel)of size15X40X1 fixed to ceiling with dash fastener using 6mm thick threaded
rods made up of galvanized steel attached to hook on profile carrier at 1200mm
centre to centre as required at site all complete The functional hook-on turn-up
guarantees the drop-and-slide function of the metal ceiling panels. Riveted or
screwed parts are not permitted. By lifting, slight shifting and subsequent dropping,
the metal ceiling panel can be locked into the lowest hook-on turn-up and moved
horizontally in both directions. Each metal ceiling panel can be dropped and moved
independently without the use of any tools. The system should be in accordance with
Material class A2-s1, d0 according to EN 13501-1 "non-combustible per the Direction
of Arch-in-Charge

6.2

MATERIAL

6.2.1

Metal suspended corridor ceiling panel shall be manufactured from polyester powder
coated electro galvanized steel with perforated and plain surfaces supported in
Double and single hook on profiles. The suspended ceiling shall comprise of
suspension made up of Extruded Aluminum & galvanized steel of 1.0 mm thickness,
supported by suspension allowing the panels to drop and slide providing maximum

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 74

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

accessibility to the void and all the perforated panels to be fitted with black acoustic
tissue
6.3

APPROVED SYSTEM

6.3.1

The middle panel size is 1800X300 mm, 2100X300mm, 2400X300mm for the drop
and slide panel with 0.7 mm thickness nominal. Manufactured from electro galvanized
steel with square edges to all four sides with drop down and slide function,
Perforation patter Rv 1,8.20( 1.8 mm dia hole and 20% open area), polyester powder
coated in RAL 9010 with minimum 60 microns thickness shall be electro statically
applied complete with factory fitted black acoustic tissue along with the fixed panel of
size 450X300 mm of 0,7 mm thickness manufactured from electro galvanized steel ,
polyester powder coated in RAL 9010 with minimum 60 microns thickness.

6.4

ACCESS

6.4.1

All the middle panels must be able to drop & slide and provide full and easy access to
the ceiling void

6.5

LEVEL

6.5.1

All the panels should be fitted to ensure accurate positioning & level of the ceiling
system as per the site/architectural requirements.

6.6

GENERAL SUSUPENSION SYSTEM

6.6.1

The panels shall be supported by the suspension system made from extruded drop &
slide hook on profile, wall connection, 15 mm, aluminum, polyester powder coated
RAL 9010 of length 5000 mm along with perimeter trim 43/65/2mm, made up of
steel polyester powder coated according to RAL 9010( of Lindner) of length 2500 mm
in accordance with EN 13964 /10152 and the length will be continued by using
connector for extruded drop-slide hook on profile made up of 2.0 mm thick pre
galvanized steel, supported by Hanger bracing , L angle of 2.0 mm thick GS(
Electro-Galvanized Steel) perforated angle of size 22/28 mm and length 6000 mm,
Longitudinal connector for hook on profile made up of 1.0 mm thick GMS( ElectroGalvanized Steel)of size15X40X1 fixed to ceiling with dash fastener using 6mm thick
threaded rods made up of galvanized steel attached to hook on profile carrier at
1200mm centre to centre as required at site all complete

6.7

FINISH

6.7.1

Finish of the ceiling tiles should be electro statically applied polyester powder coated
of minimum 60 microns with 20% gloss. Pre painted products will not be permitted.

6.8

FIRE PERFORMANCE

6.8.1

The system should be in accordance with Material class A2-s1, d0 according to EN


13501-1 "non-combustible.

6.9

PROVISIONS FOR LIGHT AND OTHER FITTINGS

6.9.1

The panels will be cut on site for the provision of light fixtures and other fittings as
per the directions of the Engineer In charge

6.10

MANUFACTURING TOLENRANCES

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 75

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

6.10.1 All the metal ceiling elements and the corresponding substructure should be
manufactured in accordance with ceiling standards accessed by EN 13964 & TAIM
(Federation of Industrial Metal Ceiling Manufacturers).
6.11

GREEN BUILDING

6.11.1 The metal ceiling systems should be applicable for certifications in accordance to
LEED & DGNB, Environmental product decelerations (EPD) to be submitted when
ever asked.
6.12

WARRANTY CERTIFICATE

6.12.1 Manufacturer should submit the warranty certificate for the minimum 15 years
6.13

MEASUREMENT

6.13.1 Length & breadth of the finished ceiling shall be measured correct to a centimeter.
The area shall be calculated in square meter correct to two decimal places. No
deduction shall be made for making openings for electrical, air conditioning, fire
fighting fixtures nor shall extra payment be made either for extra materials or labor in
making such openings.
6.14

RATES

6.14.1 The rate shall include the cost of all the materials, machinery, manpower involved in
all the operations described above including cartage, loading , unloading , all taxes
like VAT, service tax, custom duty etc except the scaffolding material and the
errection labor cost.
7.0

CLIP IN METAL CEILING SYSTEM

7.1

METAL CEILING SYSTEM

7.1.1

Providing and fixing perforated metal ceiling system of size 600X 1200 mm , clip in
system with swing down, 0.6 mm pre-galvanized steel. Finish of ceiling tiles should
be of special polyester powder coated RAL 9010 color of minimum 60 microns
powder coating thickness, perforations with hole diameter 2.5 mm and open area
16%, with plain border and black tissue at back of the panel, supported by clip in
profile made of galvanized steel 0.60 mm and the suspension channel connector
made of galvanized 0.60 mm steel , length 100 mm along with hanger lower section
for suspension channel, hanger upper section for a ceiling void less than 500 mm,
including safety pin self tapping screws etc. as approved by the Engineering- Charge

7.2

MATERIAL

7.2.1

Metal suspended corridor ceiling panel shall be manufactured from polyester powder
coated electro galvanized steel with perforated and plain surfaces supported in
Double and single hook on profiles., supported by suspension allowing the panels to
drop and slide providing maximum accessibility to the void and all the perforated
panels to be fitted with black acoustic tissue

7.3

APPROVED SYSTEM

7.3.1

The panel size is 600x1200 mm with 0.6 mm thickness nominal. Manufactured from
electro galvanized steel with square edges to all four sides with drop down and slide

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 76

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

function, Perforation patter Rv 1, 8.20(1.8 mm dia hole and 20% open area),
polyester powder coated in RAL 9010 with minimum 60 microns thickness shall be
electro statically applied complete with factory fitted black acoustic tissue polyester
powder coated in RAL 9010 with minimum 60 microns thickness.
7.4

ACCESS

7.4.1

All the middle panels must be able to drop & slide and provide full and easy access to
the ceiling void

7.5

LEVEL

7.5.1

All the panels should be fitted to ensure accurate positioning & level of the ceiling
system as per the site/architectural requirements.

7.6

GENERAL SUSUPENSION SYSTEM

7.6.1

Clip in profile made of galvanized steel 0.60 mm and the suspension channel
connector made of galvanized 0.60 mm steel , length 100 mm along with hanger
lower section for suspension channel, hanger upper section for a ceiling void less
than 500 mm, including safety pin self tapping screws etc. as approved by the
Engineering- Charge

7.7

FINISH

7.7.1

Finish of the ceiling tiles should be electro statically applied polyester powder coated
of minimum 60 microns with 20% gloss. Pre painted products will not be permitted.

7.8

FIRE PERFORMANCE

7.8.1

The system should be in accordance with Material class A2-s1, d0 according to EN


13501-1 "non-combustible.

7.9

PROVISIONS FOR LIGHT AND OTHER FITTINGS

7.9.1

The panels will be cut on site for the provision of light fixtures and other fittings as
per the directions of the Engineer In charge

7.10

MANUFACTURING TOLENRANCES

7.10.1 All the metal ceiling elements and the corresponding substructure should be
manufactured in accordance with ceiling standards accessed by EN 13964 & TAIM
(Federation of Industrial Metal Ceiling Manufacturers).
7.11

GREEN BUILDING

7.11.1 The metal ceiling systems should be applicable for certifications in accordance to
LEED & DGNB, Environmental product decelerations (EPD) to be submitted when
ever asked.
7.12

WARRANTY CERTIFICATE

7.12.1 Manufacturer should submit the warranty certificate for the minimum 15 years
7.13

MEASUREMENT

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 77

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

7.13.1 Length & breadth of the finished ceiling shall be measured correct to a centimeter.
The area shall be calculated in square meter correct to two decimal places. No
deduction shall be made for making openings for electrical, air conditioning, fire
fighting fixtures nor shall extra payment be made either for extra materials or labor in
making such openings.
7.14

RATES

7.14.1 The rate shall include the cost of all the materials, machinery, manpower involved in
all the operations described above including cartage, loading , unloading , all taxes
like VAT, service tax, custom duty etc except the scaffolding material and the
errection labor cost
8.0

METAL BAFFLE CEILING SYSTEM

8.1

METAL CEILING SYSTEM

8.1.1

Providing and fixing perforated open metal baffle ceiling system Polylam of Durlum,
Linear Grid Lindner-Germany, Baffle panel 250mm X 30mmX1800mm X 0.6mm GMS.
Perforated to Rg 2,5,16 pattern with 2.5mm dia hole providing 16% open area with
soundtex or equivalent tissue bonded at the back providing NRC not less than 0.7.
The ceiling baffle units shall be installed at distance of 300 mm c/c in one direction.
The baffle units are than attached to C Channel carrier made up of 0.6 mm
galvanized steel at 1200mm c/c. The C channel carrier are than cross connected to
perforated L angle primarily Grid and suspended with M 6 threaded rod hangers
spaced 1 200mm c/c, polyester post powder coated to RAL Color Black or white with
minimum 60 micron paint thickness

8.2

MATERIAL

8.2.1

Metal suspended corridor ceiling panel shall be manufactured from polyester powder
coated electro galvanized steel with perforated and plain surfaces supported in
Double and single hook on profiles., supported by suspension allowing the panels to
drop and slide providing maximum accessibility to the void and all the perforated
panels to be fitted with black acoustic tissue

8.3

APPROVED SYSTEM

8.3.1

Providing and fixing perforated open metal baffle ceiling system Polylam of Durlum,
Linear Grid Lindner-Germany, Baffle panel 250mm X 30mmX1800mm X 0.6mm GMS.
Perforated to Rg 2,5,16 pattern with 2.5mm dia hole providing 16% open area with
soundtex or equivalent tissue bonded at the back providing NRC not less than 0.7.
The ceiling baffle units shall be installed at distance of 300 mm c/c in one direction.

8.4

ACCESS

8.4.1

All the middle panels must be able to drop & slide and provide full and easy access to
the ceiling void

8.5

LEVEL

8.5.1

All the panels should be fitted to ensure accurate positioning & level of the ceiling
system as per the site/architectural requirements.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 78

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

8.6

GENERAL SUSUPENSION SYSTEM

8.6.1

The baffle units are than attached to C Channel carrier made up of 0.6 mm
galvanized steel at 1200mm c/c. The C channel carrier are than cross connected to
perforated L angle primarily Grid and suspended with M 6 threaded rod hangers
spaced 1 200mm c/c, polyester post powder coated to RAL Color Black or white with
minimum 60 micron paint thickness

8.7

FINISH

8.7.1

Finish of the ceiling tiles should be electro statically applied polyester powder coated
of minimum 60 microns with 20% gloss. Pre painted products will not be permitted.

8.8

FIRE PERFORMANCE

8.8.1

The system should be in accordance with Material class A2-s1, d0 according to EN


13501-1 "non-combustible.

8.9

PROVISIONS FOR LIGHT AND OTHER FITTINGS

8.9.1

The panels will be cut on site for the provision of light fixtures and other fittings as
per the directions of the Engineer In charge

8.10

MANUFACTURING TOLENRANCES

8.10.1 All the metal ceiling elements and the corresponding substructure should be
manufactured in accordance with ceiling standards accessed by EN 13964 & TAIM
(Federation of Industrial Metal Ceiling Manufacturers)
8.11

GREEN BUILDING

8.11.1 The metal ceiling systems should be applicable for certifications in accordance to
LEED & DGNB, Environmental product decelerations (EPD) to be submitted when
ever asked.
8.12

WARRANTY CERTIFICATE

8.12.1 Manufacturer should submit the warranty certificate for the minimum 15 years
8.13

MEASUREMENT

8.13.1 Length & breadth of the finished ceiling shall be measured correct to a centimeter.
The area shall be calculated in square meter correct to two decimal places. No
deduction shall be made for making openings for electrical, air conditioning, fire
fighting fixtures nor shall extra payment be made either for extra materials or labor in
making such openings.
8.14

RATES

8.14.1 The rate shall include the cost of all the materials, machinery, manpower involved in
all the operations described above including cartage, loading , unloading , all taxes
like VAT, service tax, custom duty etc except the scaffolding material and the
errection labor cost
9.0

SINGLE GLAZING FULL HEIGHT PARTITION SYSTEM

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 79

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

9.1

PARTITION SYSTEM

9.1.1

Providing & fixing of Single glazing full height partition frameless up to ceiling level
(approx 2700 mm) of the applicable Standard DIN 18202, DIN 1249 DIN EN ISO
12543. Framing shall be consist of Aluminum profile 40 mm( H) X wall thickness 28
mm( Thickness) , Wall , Ceiling & Floor Connection made up of Anodized Aluminum.
Above false ceiling, vertical sections to be extended up to main ceiling and to be fixed
with suitable accessories. Sound Insulation of 35 db to be achieved using 12 mm
thick VSG toughened clear glasses of make Saint Gobain or equivalent according to
DIN EN ISO 140-03, Joint width 3 mm. Complete in all respect with all suitable
accessories as per manufacturer standards. The item is to be finished complete in all
respects. (Tendered should visit the site and check the actual floor height Partition
to be measured up to false ceiling height excluding door opening for Billing purpose)
per the Direction of Arch-in-Charge

9.2

MATERIAL

9.2.1

Framing shall be consist of Aluminum profile 40 mm( H) X wall thickness 28 mm(


Thickness) , Wall , Ceiling & Floor Connection made up of Anodized Aluminum. Above
false ceiling, vertical sections to be extended up to main ceiling and to be fixed with
suitable accessories. Sound Insulation of 35 db to be achieved using 12 mm thick
VSG toughened clear glasses of make Saint Gobain or equivalent according to DIN EN
ISO 140-03, Joint width 3 mm

9.3

APPROVED SYSTEM

9.3.1

Single glazing full height partition frameless up to ceiling level (approx 2700 mm) of
the applicable Standard DIN 18202, DIN 1249 DIN EN ISO 12543. Framing shall be
consist of Aluminum profile 40 mm( H) X wall thickness 28 mm( Thickness) , Wall ,
Ceiling & Floor Connection made up of Anodized Aluminum. Above false ceiling,
vertical sections to be extended up to main ceiling and to be fixed with suitable
accessories. Sound Insulation of 35 db to be achieved using 12 mm thick VSG
toughened clear glasses of make Saint Gobain or equivalent according to DIN EN ISO
140-03, Joint width 3 mm. Complete in all respect with all suitable accessories as per
manufacturer standards.

9.4

LEVEL

9.4.1

All the partition walls should be fitted to ensure accurate positioning & level of the
ceiling, flooring and wall system as per the site/architectural requirements.

9.5

GENERAL SUSUPENSION SYSTEM

9.5.1

Framing shall be consist of Aluminum profile 40 mm( H) X wall thickness 28 mm(


Thickness) , Wall , Ceiling & Floor Connection made up of Anodized Aluminum.

9.6

FINISH

9.6.1

Finish of the frame should be anodized aluminum.

9.7

GREEN BUILDING

9.7.1

The metal ceiling systems should be applicable for certifications in accordance to


LEED & DGNB, Environmental product decelerations (EPD) to be submitted when
ever asked.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 80

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

9.8

WARRANTY CERTIFICATE

9.8.1

Manufacturer should submit the warranty certificate for the minimum 15 years

9.9

RATES

9.9.1

The rate shall include the cost of all the materials, machinery, manpower involved in
all the operations described above including cartage, loading , unloading , all taxes
like VAT, service tax, custom duty etc except the scaffolding material and the
errection labor cost

10.0

SINGLE GLAZING FULL HEIGHT PARTITION SYSTEM( with metal panel)

10.1

PARTITION SYSTEM

10.1.1 Providing & fixing of Single glazing full height partition frameless with Solid
perforated metal panels in Artline wood finish up to ceiling level (approx 2700 mm) of
the applicable Standard DIN 18202, DIN 1249 DIN EN ISO 12543. Framing shall be
consist of Aluminum profile 40 mm( H) X wall thickness 28 mm( Thickness) , Wall ,
Ceiling & Floor Connection made up of Anodized Aluminum. Above false ceiling,
vertical sections to be extended up to main ceiling and to be fixed with suitable
accessories. Sound Insulation of 35 db to be achieved using 12 mm thick VSG
toughened glasses of make Saint Gobain or equivalent according to DIN EN ISO 14003, Joint width 3 mm. Complete in all respect with all suitable accessories as per
manufacturer standards. The item is to be finished complete in all respects.
(Tendered should visit the site and check the actual floor height Partition to be
measured up to false ceiling height excluding door opening for Billing purpose) per
the Direction of Arch-in-Charge
10.2

MATERIAL

10.2.1 Framing shall be consist of Aluminum profile 40 mm( H) X wall thickness 28 mm(
Thickness) , Wall , Ceiling & Floor Connection made up of Anodized Aluminum. Above
false ceiling, vertical sections to be extended up to main ceiling and to be fixed with
suitable accessories. Sound Insulation of 35 db to be achieved using 12 mm thick
VSG toughened clear glasses of make Saint Gobain or equivalent according to DIN EN
ISO 140-03, Joint width 3 mm
10.3

APPROVED SYSTEM

10.3.1 Single glazing full height partition frameless up to ceiling level (approx 2700 mm) of
the applicable Standard DIN 18202, DIN 1249 DIN EN ISO 12543. Framing shall be
consist of Aluminum profile 40 mm( H) X wall thickness 28 mm( Thickness) , Wall ,
Ceiling & Floor Connection made up of Anodized Aluminum. Above false ceiling,
vertical sections to be extended up to main ceiling and to be fixed with suitable
accessories. Sound Insulation of 35 db to be achieved using 12 mm thick VSG
toughened clear glasses of make Saint Gobain or equivalent according to DIN EN ISO
140-03, Joint width 3 mm. Complete in all respect with all suitable accessories as per
manufacturer standards.
10.4

LEVEL

10.4.1 All the partition walls should be fitted to ensure accurate positioning & level of the
ceiling, flooring and wall system as per the site/architectural requirements.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 81

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

10.5

GENERAL SUSUPENSION SYSTEM

10.5.1 Framing shall be consist of Aluminum profile 40 mm( H) X wall thickness 28 mm(
Thickness) , Wall , Ceiling & Floor Connection made up of Anodized Aluminum.
10.6

FINISH

10.6.1 Finish of the frame should be anodized aluminum.


10.7

GREEN BUILDING

10.7.1 The metal ceiling systems should be applicable for certifications in accordance to
LEED & DGNB, Environmental product decelerations (EPD) to be submitted when
ever asked.
10.8

WARRANTY CERTIFICATE

10.8.1 Manufacturer should submit the warranty certificate for the minimum 15 years
10.9

RATES

10.9.1 The rate shall include the cost of all the materials, machinery, manpower involved in
all the operations described above including cartage, loading , unloading , all taxes
like VAT, service tax, custom duty etc except the scaffolding material and the
errection labor cost
11.0

TIMBER WALL CLADDING

11.1

WALL CLADDING

11.1.1 Providing & fixing of Timber Wall Cladding made of frame of Galvanized Steel
maintaining minimum 40mm gap from the brick wall by using L angle, J profile,
gasket strip, Hook in bracket & self tappings screw substructure with a gap of 6001200mm c/c as per site requirement, which is to be fixed/ anchored as per
manufactures specifications and cladded with 19mm thick Timber wood as per the
Direction of Arch-in-Charge.
11.2

MATERIAL

11.2.1 Providing & fixing of Timber Wall Cladding made of frame of Galvanized Steel
maintaining minimum 40mm gap from the brick wall by using L angle, J profile,
gasket strip, Hook in bracket & self tappings screw substructure with a gap of 6001200mm c/c as per site requirement.

11.3

APPROVED SYSTEM

11.3.1 Timber Wall Cladding made of frame of Galvanized Steel maintaining minimum 40mm
gap from the brick wall by using L angle, J profile, gasket strip, Hook in bracket & self
tappings screw substructure with a gap of 600-1200mm c/c as per site requirement,
which is to be fixed/ anchored as per manufactures specifications and cladded with
19mm thick Timber wood as per the Direction of Arch-in-Charge.
11.4

LEVEL

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 82

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

11.4.1 All the partition walls should be fitted to ensure accurate positioning & level of the
ceiling, flooring and wall system as per the site/architectural requirements.
11.5

GENERAL SUSUPENSION SYSTEM

11.5.1 Frame of Galvanized Steel maintaining minimum 40mm gap from the brick wall by
using L angle, J profile, gasket strip, Hook in bracket & self tappings screw
substructure with a gap of 600-1200mm c/c as per site requirement, which is to be
fixed/ anchored
11.6

FINISH

11.6.1 Finish of the frame should be anodized aluminum.


11.7

GREEN BUILDING

11.7.1 The metal ceiling systems should be applicable for certifications in accordance to
LEED & DGNB, Environmental product decelerations (EPD) to be submitted when
ever asked.
11.8

WARRANTY CERTIFICATE

11.8.1 Manufacturer should submit the warranty certificate for the minimum 15 years
11.9

RATES

11.9.1 The rate shall include the cost of all the materials, machinery, manpower involved in
all the operations described above including cartage, loading , unloading , all taxes
like VAT, service tax, custom duty etc except the scaffolding material and the
errection labor cost
12.0

DOUBLE GLAZING FULL HEIGHT PARTITION SYSTEM

12.1

PARTITION SYSTEM

12.1.1 Providing & fixing of double glazing full height partition frameless up to ceiling level
(approx 2700 mm) of the applicable Standard DIN 18202, DIN 1249 DIN EN ISO
12543. Framing shall be consist of Aluminium profile 35mm( H) X wall thickness 100
mm( Thickness) , Wall , Ceiling & Floor Connection made up of Anodized Aluminium.
Above false ceiling, vertical sections to be extended up to main ceiling and to be fixed
with suitable accessories. Sound Insulation of 47 db to be achieved using 12 mm
thick VSG toughened clear glass of make Saint Gobain or equivalent according to DIN
EN ISO 140-03, Joint width 3 mm. Complete in all respect with all suitable
accessories as per manufacturer standards. The item is to be finished complete in all
respects. (Tendered should visit the site and check the actual floor height Partition
to be measured up to false ceiling height excluding door opening for Billing purpose)
per the Direction of Arch-in-Charge.
12.2

MATERIAL

12.2.1 Double glazing full height partition frameless up to ceiling level (approx 2700 mm) of
the applicable Standard DIN 18202, DIN 1249 DIN EN ISO 12543. Framing shall be
consist of Aluminium profile 35mm( H) X wall thickness 100 mm( Thickness) , Wall ,
Ceiling & Floor Connection made up of Anodized Aluminium. Above false ceiling,
vertical sections to be extended up to main ceiling and to be fixed with suitable
accessories. Sound Insulation of 47 db to be achieved using 12 mm thick VSG
TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 83

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

toughened clear glass of make Saint Gobain or equivalent according to DIN EN ISO
140-03, Joint width 3 mm.
12.3

APPROVED SYSTE

12.3.1 Double glazing full height partition frameless up to ceiling level (approx 2700 mm) of
the applicable Standard DIN 18202, DIN 1249 DIN EN ISO 12543. Framing shall be
consist of Aluminium profile 35mm( H) X wall thickness 100 mm( Thickness) , Wall ,
Ceiling & Floor Connection made up of Anodized Aluminium. Above false ceiling,
vertical sections to be extended up to main ceiling and to be fixed with suitable
accessories. Sound Insulation of 47 db to be achieved using 12 mm thick VSG
toughened clear glass of make Saint Gobain or equivalent according to DIN EN ISO
140-03, Joint width 3 mm. Complete in all respect with all suitable accessories as per
manufacturer standards. The item is to be finished complete in all respects
12.4

LEVEL

12.4.1 All the partition walls should be fitted to ensure accurate positioning & level of the
ceiling, flooring and wall system as per the site/architectural requirements.
12.5

GENERAL SUSUPENSION SYSTEM

12.5.1 Framing shall be consist of Aluminium profile 35mm( H) X wall thickness 100 mm(
Thickness) , Wall , Ceiling & Floor Connection made up of Anodized Aluminium.
Above false ceiling, vertical sections to be extended up to main ceiling and to be fixed
with suitable accessories.
12.6

FINISH

12.6.1 Finish of the frame should be anodized aluminum.


12.7

GREEN BUILDING

12.7.1 The metal ceiling systems should be applicable for certifications in accordance to
LEED & DGNB, Environmental product decelerations (EPD) to be submitted when
ever asked.
12.8

WARRANTY CERTIFICATE

12.8.1 Manufacturer should submit the warranty certificate for the minimum 15 years
12.9

RATES

12.9.1 The rate shall include the cost of all the materials, machinery, manpower involved in
all the operations described above including cartage, loading , unloading , all taxes
like VAT, service tax, custom duty etc except the scaffolding material and the
errection labor cost
13.0

DOUBLE LAYER WOODEN PANEL PARTITION SYSTEM

13.1

PARTITION SYSTEM

13.1.1 Providing & fixing of Double layer of Wooden panel in combination of Glass panel /full
wooden panel framing up to ceiling level( approx 2700 mm ) of the applicable
standard DIN 18202 , DIN 68100.Framing shall be consist of 35 mm X 100 mm, Wall
, Ceiling , Floor connections made up of 1.5 thick roll deformed, galvanized steel.
TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 84

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

Above false ceiling, vertical sections to be extended up to main ceiling and to be fixed
with suitable accessories. 25-50 mm thick & with 48Kg cubic meter density glass wool
to be filled in between the two 19 mm thick timber wood panels to achieve the 50 db
sound insulation according to DIN EN ISO 140-03. Complete in all respect with all
suitable accessories as per manufacturer standards. The item is to be finished
complete in all respects. The above item should be as per specification and sample
approved by client.
13.2

MATERIAL

13.2.1 Double layer of Wooden panel in combination of Glass panel /full wooden panel
framing up to ceiling level( approx 2700 mm ) of the applicable standard DIN 18202 ,
DIN 68100.Framing shall be consist of 35 mm X 100 mm, Wall , Ceiling , Floor
connections made up of 1.5 thick roll deformed, galvanized steel. Above false ceiling,
vertical sections to be extended up to main ceiling and to be fixed with suitable
accessories. 25-50 mm thick & with 48Kg cubic meter density glass wool to be filled
in between the two 19 mm thick timber wood panels to achieve the 50 db sound
insulation according to DIN EN ISO 140-03.
13.3

APPROVED SYSTEM

13.3.1 Double layer of Wooden panel in combination of Glass panel /full wooden panel
framing up to ceiling level( approx 2700 mm ) of the applicable standard DIN 18202 ,
DIN 68100.Framing shall be consist of 35 mm X 100 mm, Wall , Ceiling , Floor
connections made up of 1.5 thick roll deformed, galvanized steel. Above false ceiling,
vertical sections to be extended up to main ceiling and to be fixed with suitable
accessories. 25-50 mm thick & with 48Kg cubic meter density glasswool to be filled in
between the two 19 mm thick timber wood panels to achieve the 50 db sound
insulation according to DIN EN ISO 140-03. Complete in all respect with all suitable
accessories as per manufacturer standards
13.4

LEVEL

13.4.1 All the partition walls should be fitted to ensure accurate positioning & level of the
ceiling, flooring and wall system as per the site/architectural requirements.
13.5

GENERAL SUSUPENSION SYSTEM

13.5.1 Framing shall be consist of 35 mm X 100 mm, Wall, Ceiling, Floor connections made
up of 1.5 thick roll deformed, galvanized steel. Above false ceiling, vertical sections to
be extended up to main ceiling and to be fixed with suitable accessories. 25-50 mm
thick & with 48Kg cubic meter density glasswool to be filled in between the two 19
mm thick timber wood panels.
13.6

FINISH

13.6.1 Finish of the frame should be anodized aluminum.


13.7

GREEN BUILDING

13.7.1 The metal ceiling systems should be applicable for certifications in accordance to
LEED & DGNB, Environmental product decelerations (EPD) to be submitted when
ever asked.
13.8

WARRANTY CERTIFICATE

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 85

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

13.8.1 Manufacturer should submit the warranty certificate for the minimum 15 years
13.9

RATES

13.9.1 The rate shall include the cost of all the materials, machinery, manpower involved in
all the operations described above including cartage, loading , unloading , all taxes
like VAT, service tax, custom duty etc except the scaffolding material and the erection
labor cost.
SCOPE OF WORK IS DETAILED IN BILL OF QUANTITY (BOQ) & TENDER
DRAWINGS (REFER FORM 1-D OF SCHEDULE OF PRICES). IN CASE OF ANY
CONFLICT WITH THE GENERAL SPECIFICATION SPECIFIED ABOVE AND THE BILL
OF QUANTITY(BOQ) AS PER FORM-1D, THE TECHNICAL SPECIFICATION
MENTIONED IN BILL OF QUANTITY ( FORM 1 D) SHALL PREVAIL.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 86

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

TECHNICAL

SPECIFICATION

FOR

SYSTEM

INTEGRATION

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

WORK

Page | 87

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

TECHNICAL SPECIFICATION FOR SYSTEM INTEGRATION WORK FOR VARIOUS


BUILDINGS AT OTPC, PALATANA
1.

DISPLAY SYSTEM
i.

Full HD LED Display of 55"with Wall mount / Table mount or Full HD LED Display of 42"
with Wall mount / Table mount

ii.

DLP HD Projection system of 4500 Lumens, 350W, 3000:1, Standard Lens, Color Wheel,
Horizontal Frequency: 15,30 - 90kHz; Vertical Scan Rate: 43 - 85 Hz; Keystone Correction:
15 Vertical.

iii.

Motorized Lift for above projector

iv.

Motorized-electrically operated Matte White finished projection screen of 65 x 116" [133"


Diagonal] size, flame retardant and mildew with minimum viewing angle 60 degrees, Gain
1.0. Shall have specially designed motor mounted inside the roller with noise silencer,
three wire quick reversal type, oiled for life, with automatic thermal overload cut-out, preset but adjustable limit switches, with black masking borders standard. Bottom of fabric
shall be formed into a pocket holding metal rod. Case to be 21-gauge powder coated steel,
hexagon in shape with flat back, complete with three position control switch in box with
cover plate
Relay Interface for Up-Down movement of Motorized Projection Screen

2.

SOURCE EQUIPMENTS
i.

ii.
iii.
3.

1+ 5 party HD Point to Multipoint Video Conferencing System consisting of


--Omni Directional Microphone
--10X optical zoom Full HD Camera
--PC for Presentation sharing
--Inbuilt recording on Memory stick feature
16 port 10/100/1000 Mbps Layer2 Giga Network Switch
DVD and HDD recorder features a HD Digital Tuner, 320GB HDD, 1080p up scaling via
HDMI and MP3 Juke Box
AUDIO RE-INFORCEMENT SYSTEM

i.
ii.

Embedded Boundary Microphones on conference table


Digital Signal Processor with echo canceller for minimum 16 audio inputs

iii.

Feedback suppressor with built-in automatic mixer for the two microphone inputs should
automatically adapts up to 12 dB additional gain before feedback occurs in the acoustical
situation,

iv.

Multi-Channel Amplifier

v.
vi.

Speaker System
Volume and audio source selector panel

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 88

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

4.

CONTROL SYSTEM
i.

ii.

Dimmer / Light Control system for Presentations

iii.

Multiformat Transmitter with receiver for 2 x Laptop and 1 x VC Connectivities.

iv.

HDMI Matrix switcher of minimum 6 in and 6 out or more with Max. Data Rate 2.25Gbps
per graphic channel, HDCP Compatible, HDTV Compatible, HDMI Support HDMI (V.1.4
with 3D, Deep Color, x.v.Color), 3D Pass-Through, reclocks and equalizes the signal and
can route any input to any or all outputs simultaneously.

v.
vi.
5.

HDMI Transmitter with Receiver for Display System (55" LED Display and Projector)
HDMI Audio DeEmbedder with 1xHDMI, 1xS/PDIF, 1xTOSLINK and 1xStereo (U) outputs
for Multi-media output of laptop presentation
CABLES AND CONNECTORS

i.

ii.

Highperformance 1.5M HDMI (M) to HDMI (M) patch cord with molded HDMI connectors
at both ends and with Ethernet Support : High Data Transfer Rate Up to 10.2Gbps.
Supported Resolutions 720p/1080i/1080p Ideal for connecting HD devices to HD/full HD
plasma/LCD, PSP3, Bluray and HD DVD. Deep Color Supports 24bit, 30bit, 36bit
and 48bit (RGB or YCbCr) color depths. Multi-Channel Audio Support - Supports audio
stream for external decoding by AV receivers and automatic audio syncing capabilities.
High Quality Connectors Goldplated connectors resist corrosion.
1.5M VGA+A molded Patch cord complete with connectors

iii.

1.5M molded Audio Cable complete with connectors

iv.

Audio / Speaker cable, Twisted pair stranded 26/30 (16 AWG) copper,
connecting speakers and amplifiers

designed for

v.

Four pair individually aluminumfoil shielded twisted pair, cabled with a drain conductor
and overall braidshielded -23AWG Control Cable

vi.

Four pair individually aluminumfoil shielded twisted pair (S/FTP), cabled with a drain
conductor and overall braidshielded -23AWG Data Cable designed for twisted pair digital
transmitter receiver sets to provide optimum range and performance for 10GBaseT
applications as defined in IEEE 802.3an and for PoE+ suitable for terminated with shielded
RJ45 connectors

vii.
viii.
6.

Integrated Control System for presentation and co-ordination between various audio-video
and lighting control services through 5.2" Active Matrix Display featuring VoIP Intercom,
256 MB Flash / 128MB Standard SDRAM Memory, integrated battery, integrated kickstand
& (1) PS3.0 Power Supply and Integrated NetLinx Controller with 404 MIPS Processor,
64MB RAM, 128 MB of FLASH. 8 IR Ports, 8 I/O Ports, 8 Relays, and 7 RS-232 / 422 / 485
Ports

Shielded RJ-45 Crimp Connector for 23 AWG Cable


1.5M power molded Cable complete with connectors
OTHER MISCELLANEOUS ITEMS

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 89

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

i.
ii.

19" Equipment Rack of 24U


Online UPS of 3 KVA with 30 minutes back-up

7.

AUDIO VIDEO SYSTEM FOR 100 SEATER AUDITORIUM

7.1

DIGITAL PODIUM CONSISTING OF: i.

7.2

1/3" CCD imaging camera for digital podium with 1280 x 960 resolution, 720p format,
12X optical zoom, capable to view as small as 10mm and 260mm large objects, LED light
source, USB & LAN connectivities, capable to switch between Camera display and PC
images, complete in all respect & as per specifications.
PROFESSIONAL AUDIO SYSTEM CONSISTING OF: -

i.

wall mount main FOH speakers loudspeaker with permanent install single 15" LF, single
1.25" or more HF driver with Frequency Response (-10 dB) 45 Hz - 20 kHz and the
Sensitivity of 98 dB or more ( 1W/1m) delivering a Max SPL 131 dB or more. The
loudspeaker should have a horizontal coverage angle of 90 degree or better. It should
have Power handling continuous.600-800Watt.The loudspeaker should have integrated
bracket or min 10 suspension points for permanent installation complete in all respect & as
per specifications.

ii.

Wall mount main Delay speakers with Permanent install, flying, single 12" Full Range 2
Way loudspeaker. The loudspeaker should have frequency range (-10dB) of 55Hz-20kHz.It
should have sensitivity (1W/1m) of 99 dB delivering Max SPL of 129dB or more. The
loudspeaker should a nominal impedance of 8 ohms and it should have with power
handling pk of 1200W or more. The speaker must be a permanent install loudspeaker with
a min of 4 or more integrated suspension points complete in all respect & as per
specifications.

iii.

Subwoofer speaker with permanent installed, single 18" LF .It should have a Freq. Range
(-10 dB) of 50 Hz - 600Hz Hz. It should have a sensitivity of (1W/1m) 99 dB or more
delivering max calculated SPL of 131 dB or more. The loudspeaker should have a nominal
impedance of 8ohm and Power Handling pk. of 4000W or more complete in all respect &
as per specifications.

iv.

Stage Monitor speaker with in-built amplifier having 12" LF ,1" or more HF with frequency
range of 55Hz - 20kHz (-10dB) or better delivering a max SPL 131dB SPL .It should have
horizontal and vertical coverage angle of 90 degree and 50 degree or better. The
loudspeaker should have inbuilt amplifier of class D delivering a power of 1000W or more.
It should have integrated monitor angle on the enclosure for use floor monitor complete in
all respect & as per specifications.

v.

Wall mount loudspeaker with dual 3.5" LF or more, single 0.75"HF driver with Built-in LMT.
It should have Frequency Response (-10 dB) of 90 Hz - 20 kHz. The loudspeaker should
have a sensitivity( 1W/1m) of 85 dB or more delivering a Max SPL 106 dB or more with
Horizontal and Vertical coverage angle of 90 -120 degree and 60-90 degree respectively
.The loudspeaker should have power handling pk of 300 Watt. The loudspeaker should
have in-built LMT with power tap settings of 70V/100V:10W or more .It should have
integrated mounting bracket for permanent installation complete in all respect & as per
specifications.

vi.

Class H Dual channel power amplifier with specification as below or BETTER to suit the
power
requirement
of
proposed
speakers;
Max Midband Output Power:1150W @ 4 ohms,1750W @ 2 ohms, Max Bridged Output

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 90

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

Power:3600W @ 4 ohms, Frequency Response:20Hz - 20 KHz, THD:<0.03%,Max input


level:+21dBu,Crosstalk<80dB,input impedence:20kohm,signal to noise ratio : >110dB
,with built in protection such as Audio Limiters, Temperature, DC, HF Short Circuit, Peak
Current protections complete in all respect & as per specifications.
vii.

Dual channel power amplifier with specification as below or BETTER to suit the power
requirement
of
proposed
speakers;
Max Midband Output Power:550W @ 4 ohms,600W @ 2 ohms, Max Bridged Output
Power:1250W @ 4 ohms, Frequency Response:20Hz - 20 KHz, THD:<0.03%,Max input
level:+20dBu,Crosstalk<80dB,input impedence:20kohm,signal to noise ratio : >108dB
,with built in protection such as Audio Limiters, Temperature, DC, HF Short Circuit, Peak
Current protection complete in all respect & as per specifications.

viii.

Single channel power amplifier for Control Room Speakers with specification as below or
BETTER
to
suit
the
power
requirement
of
proposed
speakers;
Rated
Output
Power:250W@70V/100V
,Frequency
Response:70Hz
20KHz,THD:<0.5%,Max input level:+21dBu,input impedence:20kohm,,with built in
protection such as Audio Limiters, Temperature protection, Peak Current protections
complete in all respect & as per specifications.

ix.

100 W volume control for Speakers at Green room and control complete in all respect &
as per specifications.

x.

Digital Signal Processor with 2 x XLR IN, electronically balanced audio input,6 x XLR OUT,
electronically balanced audio output with 2 x XLR Thru out ,and 1x XLR AES/EBU IN digital
input, with Nominal Input Voltage:1.23V / +4 dBu, maximum input voltage:8.7V / +21
dBu, input impedance :10k Ohm, CMR:-80dB@1kHz,A/D &D/A conversion :24 bit sigma
delta,THD+N <0.01% complete in all respect & as per specifications.

xi.

10 channel Mixer with Digital Audio interface with 4 input channel & 4 output channels
with AD/DA conversion 24-bit and; USB 2.0 PC Interface, MIDI interface, OLED
display;100 Digital effects presets with at least 20 user preset available. 6 mono & 4 stereo
channels, 6 auxiliary outputs, 11 band stereo equalizer; THD (at 1kHz) <0.005%,
frequency response (-3dB):20Hz to 65kHz; crosstalk >85dB, CMRR (at 1kHz)>80dB,
Equivalent input noise:-130dBu A, maximum level Mic inputs: +21dBu complete in all
respect & as per specifications.

xii.

Handheld Wireless Mic system that has a min of 14-hour battery life from two AA alkaline
batteries. Cardiod polar pattern, Dynamic microphone ,frequency response 83Hz-18kHz,RF
sensitivity < 1.0 Uv, Image rejection>55dB,Dyanmic range >95dB and receiver having 30
channels possible, S/N ratio >100dB A, dynamic range >95db B, distortion <1
%,frequency band:618-634MHz,modulation:+/-40kHz complete in all respect & as per
specifications.

xiii.

Wireless Lapel Mic system that has a min of 14-hour battery life from two AA alkaline
batteries. Cardiod polar pattern, Dynamic microphone , frequency response 83Hz-18kHz,
RF sensitivity < 1.0 Uv, Image rejection >55dB, Dynamic range >95dB and receiver
having 30 channels possible, S/N ratio >100dB A, dynamic range >95db B, distortion <1
%,frequency band: 618-634MHz,modulation:+/-40kHz complete in all respect & as per
specifications.

xiv.

Gooseneck Mic with XLR base for podium having back electret condenser microphone
element ,Hyper Cardioid polar pattern, programmable switch, frequency response 55Hz20kHz ,sensitivity 5.5mV/Pa, clipping level >130dB SPL, output impendence 200 ohm
complete in all respect & as per specifications.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 91

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

xv.

7.3

feedback suppressor with built-in automatic mixer for the two microphone inputs should
automatically adapts up to 12 dB additional gain before feedback occurs in the acoustical
situation, complete in all respect & as per specifications.
PRESENTATION SWITCHER WITH SCALER & TOUCH CONTROL SYSTEM: -

i.

Integrated Control System for presentation and co-ordination between various audio-video
and lighting control services through 5.2" Active Matrix Display featuring VoIP Intercom,
256 MB Flash / 128MB Standard SDRAM Memory, integrated battery, integrated kickstand
&
(1)
PS3.0
Power
Supply
and
Integrated NetLinx Controller with 404 MIPS Processor, 64MB RAM, 128 MB of FLASH. 8 IR
Ports, 8 I/O Ports, 8 Relays, and 7 RS-232/422/485 Ports complete in all respect & as per
specifications.

ii.

Furniture-Mountable durable, metal enclosure for Cables, AAPs, and AC Power Outlets
with dimension of 6.96" W x 6.96" D (17.68 cm W x 17.68 cm D) that can be mounted
into a tabletop or other flat surface with a Blank anodize finish and a single Universal type
power outlet complete in all respect & as per specifications

iii.

Cable Cubby AC Universal Power Module complete in all respect & as per specifications.

iv.

Two-input automatic switcher HDCP compliant transmitter wall plate for sending HDMI or
RGBHV video, audio, and Ethernet up to 330 feet (100 m) over a single CAT 5-type cable.
The unit offered can be remotely powered. It should be able to support signal with
resolutions of 1920 x 1200 including 1080p/60 with the data rates up to 6.75 Gbps, Deep
Color up to 12-bit, 3D, HD lossless audio formats, and CEC complete in all respect & as per
specifications.

v.

Long Distance XTP Receiver for HDMI; HDCP compliant; able to support 1080p / 60 Deep
Color and 1920x1200 video signals, HDMI data rates up to 6.75 Gbps with deep color, 3D
and HD Audio; HDMI audio de-embedding with analog stereo and digital S/PDIF audio
outputs; local Analog audio also; bidirectional RS-232 and IR up to 330 feet (100 m) over
a single CAT 5-type cable; capable of remote powering complete in all respect & as per
specifications.

vi.

HDMI Matrix Switcher, should support computer-video to 1920x1200, including HDTV


1080p / 60; HDMI; data rates up to 6.75 Gbps, Deep Color up to 12-bit, 3D, and HD audio
formats, automatic cable equalization for each input to 100 feet (30 meters) at 1920 x
1200 / 8-bit color; Speed Switching for HDCP-encrypted content; Key Minder for
continuously verifying HDCP compliance; EDID Minder should automatically manage EDID
communication between connected devices; Automatic output re-clocking to Reshape and
restore timing of HDMI signals at each output, enabling transmission over long HDMI
cables; Interface Format Correction; capability to separate an embedded audio signal from
its corresponding video signal within the matrix switcher, allowing the audio and video
signals from one source to be switched to different destinations; should provide +5 VDC,
250 mA power on the HDMI outputs for external peripheral devices complete in all respect
& as per specifications.

vii.

HDMI Audio De-Embedder, Supports HDCP, HDMI audio de-embedding with analog stereo
and digital S/PDIF audio outputs; data rates up to 6.75 Gbps, Deep Color up to 12-bit, and
3D, Cable equalization at input; EDID Minder automatically manages EDID communication
between connected devices; LED indicators for HDCP confirmation, signal, Link status and
Power Complete in all respect & as per specifications.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 92

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

viii.

Long Distance XTP Transmitter for HDMI; It should be HDCP compliant and able to
support 1080p/60 Deep Color and 1920x1200 video signals, HDMI audio embedding
with analog stereo audio, local Analog audio also. Ethernet, remote power, bidirectional
RS-232 and IR up to 330 feet (100 m) over a single CAT 5-type cable; HDMI data rates up
to 6.75 Gbps with deep color, 3D and HD Audio; capable of remote powering complete in
all respect & as per specifications.

ix.

Long Distance XTP Scaling Receiver, Twisted pair HDCP compliant receiver unit that scales
HDMI, DVI, RGB, HD component video, and standard definition video to the optimal
output resolution for the display. It should accept video, audio, bidirectional RS-232 and
IR, and Ethernet up to 330 feet (100 m) over a single CAT 5-type cable with selectable
output rates from 640 x 480 to 1920 x 1200, including HDTV 1080p / 60; should support
data rates up to 6.75 Gbps, Deep Color up to 12-bit, HD lossless audio formats, and CEC
also to support various HDMI audio formats and is capable to de-embed them from HDMI
in form of Analog Stereo or S/pdif digital format with audio adjustments and muting. The
unit should be controllable via USB or Rs-232 complete in all respect & as per
specifications.

x.

9.7inch (diagonal) color touch screen or bigger LED-backlit glossy widescreen


MultiTouch display with 1024-by-768 resolution at 132 pixels per inch (ppi), support Wi-Fi
(802.11a/b/g/n) and Bluetooth 2.1 + EDR technology, should have at least 16GB of
storage memory; Built in speakers for video preview complete in all respect & as per
specifications.

xi.
7.4

Touch Panel Control Device License.


PROJECTION SYSTEM CONSISTING OF: -

i.

LCD / DLP Multimedia Projector with minimum of 6500 ANSI Lumens, Horizontal
Frequency 30-90 KHz, Vertical scan rate 50-85Hz, image size 40" - 500"; Keystone
correction of Vertical: 40 , Horizontal: 35degree and complete in all respect with
wired and wireless between PC and Projector complete in all respect & as per
specifications.

ii.

Ceiling stand for Projection System complete in all respect etc as required complete in all
respect & as per specifications.

iii.

Motorized-electrically operated Matte White finished projection screen of 57.5 x 92" [109"
Diagonal] size, flame retardant and mildew with minimum viewing angle 60 degrees, Gain
1.0. Shall have specially designed motor mounted inside the roller with noise silencer,
three wire quick reversal type, oiled for life, with automatic thermal overload cut-out, preset but adjustable limit switches, with black masking borders standard. Bottom of fabric
shall be formed into a pocket holding metal rod. Case to be 21-gauge powder coated steel,
hexagon in shape with flat back, complete with three position control switch in box with
cover plate complete in all respect & as per specifications.
Relay Interface for Up-Down movement of Motorized Projection Screen

7.5

CABLES & CONNECTORS: i.

Cat6 Cable in existing media complete in all respect & as per specifications.

ii.

Control Cable in existing media complete in all respect & as per specifications.

iii.

Speaker Cable in existing media complete in all respect & as per specifications.

iv.

Microphone Cable in existing media complete in all respect & as per specifications.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 93

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

v.

RGBHV Cable in existing media complete in all respect & as per specifications.

vi.

RG59 Video Cable in existing media complete in all respect & as per specifications.

vii.

3 core 2.5 Sq. mm copper conductor power cables in existing media complete in all
respect & as per specifications.

viii.
ix.
x.
8.0

XLR Socket / Connector with Suitable Accessories


Speaker Socket / Connector with Suitable Accessories
Phono Socket / Connector with Suitable Accessories
DISPLAY SYSTEM FOR LECTURE HALL SOLUTION

i.

ii.

Interactive Ultra-short-throw DLP Projection System for classroom usage, 3000 lumens of
brightness with 2,500:1 contrast ratio, Native resolution 1280 x 800, Throw ratio 0.19:1,
16:10 Native, 4:3, 16:9 Compatible, manually adjustable for Image Size (Diagonal) 87" to
97"
Wall mount Kit for Short throw Projection system

iii.

Interactive White-board of 103 active diagonal size suitable for above projection system
with Aspect Ratio of 16:9

iv.

Multiformat Transmitter with receiver for 1 x Laptop and 1 x White Board Connectivity.

v.
9.0

Cables and Connectors


AUDIO RE-INFORCEMENT SYSTEM FOR EXECUTIVE TRAINING ROOM

i.

Hand-held wireless microphone system

ii.

Gooseneck Mic with XLR base for podium having back electret condenser microphone
element ,Hyper Cardioid polar pattern, programmable switch, frequency response 55Hz20kHz ,sensitivity 5.5mV/Pa, clipping level >130dB SPL, output impendence 200 ohm

iii.

HDMI Audio DeEmbedder with 1xHDMI, 1xS/PDIF, 1xTOSLINK and 1xStereo (U) outputs
for Multi-media output of laptop presentation

iv.

Feedback suppressor with built-in automatic mixer for the two microphone inputs should
automatically adapts up to 12 dB additional gain before feedback occurs in the acoustical
situation,

v.

Dual channel (Stereo) Audio Amplifier & Switcher (40 Watts per Channel) 1 Stereo (B) 1
Stereo (U)

vi.
vii.

viii.

Volume controller for two channels of balanced stereo audio signals on XLR connectors
2way coaxial ClosedBack Ceiling Speakers (4) Closed Back Can with Woofer 4",
Tweeter 1", Freq 20Hz to 20kHz, Crossover Frequency 10kHz, Sensitivity 85dB.,
Frequency Response 85Hz to 20kHz., Power Rating 20W nominal, 40W Max
Cables and Connectors

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 94

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

10.0
i.
ii.

BACKGROUND MUSIC SYSTEM FOR CANTEEN


Mixer Amplifier, minimum 60 W 100/70V Speaker out.
Booster Amplifier, minimum 240 W 100/70V Speaker out.

iii.

Handheld Wireless microphone

iv.

economic flush-mounting ceiling full range loudspeaker for speech and music reproduction,
Complies to Safety acc. to EN 60065 Emergency acc. to BS 5839-8 / EN 60849,,Rated
power 6 / 3 / 1.5 / 0.75 W, Sound pressure level at 6 W / 1 W (4 kHz, 1 m)102 dB / 94 dB
(SPL),Effective frequency range (-10dB) 80 Hz to 18 kHz, Opening angle at 1 kHz / 4 kHz
(-6 dB) 160 / 65

v.

100W volume control used to adjust the level locally, Built-in 24 VDC override relay,
complies to Safety acc. to EN 60065 Self-extinguishing acc. to UL 94 V0 std, Frequency
response 50 Hz to 20 kHz (-1 dB)

vi.
vii.
viii.
ix.
x.
xi.

Housing for Volume control


CD player, able to play MP3, WMA audio files with USB input.
Equipment Rack with lockable and front perforated doors.
2 Core speaker cum control wire in existing media
3 core 1.5M molded power cable
3 core power cable in existing media

SCOPE OF WORK IS DETAILED IN BILL OF QUANTITY (BOQ) & TENDER


DRAWINGS (REFER FORM 1-D OF SCHEDULE OF PRICES). IN CASE OF ANY
CONFLICT WITH THE GENERAL SPECIFICATION SPECIFIED ABOVE AND THE BILL
OF QUANTITY(BOQ) AS PER FORM-1D, THE TECHNICAL SPECIFICATION
MENTIONED IN BILL OF QUANTITY ( FORM 1 D) SHALL PREVAIL. THE SYSTEM
INTEGRATION WORK SHALL BE EXECUTED BY THE SYSTEM INTEGRATORS
APPROVED BY OTPC.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 95

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

ANNEXTURE-I
LIST OF INDIAN STANDARDS
I.S. No. 900 Latest measurement of building and civil engineering work.
I.S. No. 287 1973.
Recommendation for maximum permissible moisture content of Tiber used for
different purposes in different climatic zones.
I. S. No. 1141 1973 code of practice for seasoning of timber.
I. S. No. 6534 1971 guiding principles for grading and inspection of timber.
I. S. No. 900 (Part XXI) 1973
Method of measurement of building and civil engineering works. Part XXI wood work
and joinery.
I. S. No. 3845 1966. Code of practice for joints used in wooden furniture.
I. S. No. 4000 1967. Wooden flush doors. Type to method of test for.
I. S. No. 4970 1973. Key for identification of commercial timbers.
I. S. No. 3364 (Part II) 1975, Method of measurement and evaluation of defects in
timber, part II converted timber.
I. S. No. 1708 1969. Method of testing small clear specimens of timber.
I. S. No. 6342 1971. Rose wood logs for production of sliced veneers.
I. S. No. 5248 1969. Teak logs for production of sliced veneers.
I. S. No. 2202 (Part I) 1973. Specification for wooden flush door shutters (solid core type
part I plywood)
I. S. No. 2338 (Part I) 1967. Code of practice for finishing of wood and wood based
materials part I operations and workmanship.
I. S. No. 7630 1975. Methods of sampling of plywood.
I. S. No. 303 1975. Specification for plywood for general purposes.
I. S. No. 3129 1965. Specification for article board for insulation purposes.
I. S. No. 3513 1966. (Part I. S. No. & part IV). High and medium density wood based
laminates part I. S. No. general purposes. Part IV sampling test.
I. S. No. 1659 1979 block boards.
I. S. No. 7316 1974. Decorative plywood using plurality or veneers for decorative faces.
I. S. No. 3478 1966. High density wood particle boards.
I. S. No. 1734 (part I to XX). Plywood method of test for
Part I... General
Part II... Plywood
Part III Battens
I. S. No. 1328 1970. Veneer decorative plywood.
I. S. No. 710 Marine ply.
I. S. No. 3087 1965. Wood particle boards (Medium density)
I. S. No. 848 1974. Specification for synthetic resin adhesives for plywood (Phenolic &
Amino plastic)
I. S. No. 2046 1969. Specification for decorative laminate.
I. S. No. 8273 1976. Fibrous gypsum plaster boards.
I. S. No. 2095 1964. Gypsum plaster boards.
I. S. No. 2542 (part I) 1978. Gypsum plaster concrete and products, methods of test for
part I plaster and concrete.
TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 96

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

I. S. No. 8272 1976. Gypsum plaster for use in the manufacture of fibrous plaster
boards.
I. S. No. 2441 1963. Fixing coiling coverings code of practice for.
I. S. No. 2835 1977. Specification for flat transparent sheet glass.
I. S. No. 2395 (Part I) 1966 2395 (Part II) 1967
Painting to concretes, masonry, plaster surfaces code of practice for part I operation and
workmanship part II schedule.
I. S. No. 3548 1966. Glazing in building code of practice for.
I. S. No. 6278 1971. White washing and colour washing, code for practice for.
I. S. No. 137 1965. Specification for ready mixed paint brushing, matt or egg shall flat
finishing, interior to Indian standards colours as required.
I. S. No. 133 1975. Specification for ready mixed paint brushing, wooden coating, interior
to Indian standard colours.
I. S. No. 129 1950. Specification for enamel interior (a) under coating (b) finishing
I. S. No. 90 1950. Specification for ready mixed paint brushing gray filler for enamel for
use over primer.
I. S. No. 129 1950. Specification for ready mixed paint brushing, finishing, interior, oil
gloss, for general purposes to Indian standard colours.
I. S. No. 533 1973. Specification for gum sprit of turpentine (oil of turpentine)
I. S. No. 101 1964. Methods of test for ready mixed paints and enamel.
I. S. No. 75 1973. Specification for linseed oil, and refined.
I. S. No. 77 1976. Specification for linseed oil, boiled for paint.
I. S. No. 124 (part I) 1976. Specification for ready mixed paint brushing, finishing, semi
glosses, for general purpose.
I. S. No. 5884 Specification for woolen carpets.
I. S. No. 104 1979. Specification for ready mixed paint brushing, finishing, zinc chrome
primer.
I. S. No. 5391 1969. Adjustable metal chairs for use of typist and operators in telephone
exchanges.
I. S. No. 8756 1978. Ball catches for use in wooden almirahs.
I. S. No. 3499 1976 (part II) chairs for office purposes metal revolving and ti in.
I. S. No. 5416 1969. General purpose wooden chairs methods of test for.
I. S. No. 6185 1971. High chairs specification and safety requirements for.
I. S. No. 4116 1976. Joints used in wooden furniture code of practice for.
I. S. No. 3845 1966. Joints used in wooden furniture code of practice for.
I. S. No. 7070 1973. Shelving racks wooden (adjustable and nonadjustable type).
I. S. No. 4414 1977. Table tops (wooden)
I. S. No. 5967 1969. Tables, wooden, methods of test for.
I. S. No. 799 1979. Drawer locks, cupboards and box locks.
I. S. No. 7981 (part I) 1975. Glossary of terms relating to builders hardware part I
locks.
I. S. No. 204 (part I II) 1978. Tower bos ferrous metals and nonferrous metals.
The various items to be used in the interior decoration work shall be of BRANDED
manufactures of market leaders above clause is only for specifying ISI standards.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 97

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

LIST OF ISO STANDARDS (FURNITURE)


ISO 9001:2008
ISO 14001-2004 Certified.
ISO 18001-2007 Certified.
LIST OF QUALITY ASSURANCE STANDARDS (CEILING)

1. DIN 18202 for general quality management system


2. LEED & DGNB for green building product.
3. DIN EN ISO 12543
4. DIN 1249
5. EN 13964 for ceiling standard as per EN
6. EN 13501-1 building material class A2-s1, d0

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 98

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

ANNEXTURE-II
LIST OF APPROVED MAKES OF MATERIALS
INTERIOR & CIVIL WORKS
S No
1

Material

Approved Brand / Make

Plastic Emulsion Paint

a) ICI Dulux
b)

Berger

c)

Nerolac

d) Asian Paints
2

Float Glass

a)

St. Gobain

b)

Modifloat

Chemical to be used for anti-termite

a)

Wood Care

Commercial Board, Ply, Teak Ply,


Commercial Ply, Flush Doors

a)

Century Sainik

b)

Merino

c)

Durian

d)

Alpro panels

Gypsum Board

a)

a)

Armstrong/ AMF/ Aerostone

Mineral Fibre Board False Ceiling /


Modular Tiles
Expansion Bolts / Dash Fasteners

a)

Hilti

Glazing Sealant

a)

GE Sealant

MDF

a)

Nuwood , Bajaj,Greenlam

10

Floor Springs / Door Closers (Normal &


Concealed types)

a)

Ozone / Ingersoll (Briton)/Geze

11

Resin Based Adhesive

a)

Fevicol/Vamicol

12

Vinyl Flooring

Armstrong , LG,Gerfloor

13

Raised Access Floor

Unifloor, Cani, Hyundai or Equivalent

14

White Board

a)

Alkon Systems / Whitemark

15

Pin-up Board

a)

Sitatex , Cellotaex

16

Fire Retardant Paint

a)

Navair

b)

Viper

a)

Spectrum

b)

Coral

a)

Asian

b)

Oikos

a)

MAC

b)

Winfab , Vista

a)

Hettich

b)

FGV

c)

Dorset

17
18
19
20

Textured Paint
Feature Paint
Vertical/ Roller Blinds
SS coated Hardware

LAGYP (Lafarge), India Gypsum

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 99

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

21

Laminate

a)

Merino

b) Greenlam
22
23

Vitrified Tiles
Wooden Flooring

c)

Century Mica

a)

Nitco or Kajaria

b)

Somany oy Asian or Equivalent

a)

Power Floor

b) Kronotek
c) Span
d)
24

25

Aluminium Alloy Extruded Section

Natural Veneers

Floor Master

a)

Hindalco

b)

Indalco

c)

Nalco

d)

Jindal

a)

Century

b) Greenply
26

Post-formed shutter storage

27

Plaster of Paris

27

Ceramic Tiles 12x12 / 16x16

c)

Durian

a)

Merino

b)

Century
Shriram, JK, Aerostone

a) Nitco
b) Asian
c) Somany

28

Locks

Dorset with separate keyhole ring / Golden / Kitch

29

Pivots, Handle Bars etc

Dorset / Golden / Kitch

30

Fabric Protection

Fabguard / Scotchguard

31

GlassWool Insulation

Twiga , Lloyod

32

Cement , White

Birla White, JK White

33

Piped / Ducted Services

Leo, Orient. Parko, Emson, Duralite,

34

Toilet Accessories, CP

Jaquar/Euronics/Gebrit/

35

Toilet Fixtures (Washbasins, WC etc)

Kohler /

36

Toilet Faucets

Jaquar /

37

Flush Doors

Kitply/ Alpro Panels /

38

Carpet Tiles

Shaw / Interface / Roya

39

PRELAMINATED PARTICLE BOARDEXTERIOR GRADE

ASSOCIATED DCOR/ ACTION TESA/ SHIRDI


INDUSTRIES

40

CRCA/STEEL

TATA STEEL/ BHUSHAN STEEL/ ESSAR STEEL

41

HARDWARE

EBCO/ HETTICH/ HAFFELE

42

FABRIC

RESPONSE/ COMRADE/ COLORAYS/ COMMRAD

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 100

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

APPROVED MAKES FOR ELECTRICAL WORKS

S No

Material

Approved Brand / Make

M V CABLES

SKYLINE/ HAVELLS/ POLYCAB

M V SWITCHGEAR

FINOLEX/ SKEYLINE/ ESC/PPPROFLEX/POLYCAB

PVC insulated copper conductor


stranded control wires of 1100 v grade
CABLE GLANDS

COPPER LUGS HEAVY DUTY

DOWELLS

RELAYS

ALSTOM/ABB/L&T

MEASURING METERS

AUTOMATIC ELECTRIC/KAPPA/ENERCON

INDICATING LAMPS

VAISHNO/CONCORD/SIEMENS/GE POWER

BREAKER CONTROL SWITCH

ALSTOM/L&T/ABB/SIEMENS

10

SELECTOR SWITCH

KAYCEE/L &T /SIEMENS

11

CAST RESIN CT'S & PT'S

AE/AVK SCGC/KAPPA/GILBERTS& MAXWELL/

12

OVERLEAD RELAYS & CONTACTORS

L & T/ SIEMENS/ABB

13

MCCB'S

L & T/GROUP SCHNEIDER/ABB/SIEMENS

14

DIGITAL METERS & KWH METERS

SECURE/L&T/ENERCON

15

PUSH BUTTONS

L & T/SIEMENS/ABB

16

MCBS

17

CABLE TRAY

MDS/L&T HAGGAR/SCHNEIDERMG/SIEMENS/HAVELL
SLOTCO/VENUS/ NEEDO/ AMAZONE

L&T GROUP/ SCHNEIDER /ABB

COMET/POWER ENGG

TERMINAL BLOCKS
RACEWAY WITH SHEET STEEL

ELMEX

20

M.S. CONDUITS AND ACCESSORIES

BEC

21

P.V.C. CONDUITS AND ACCESSORIES

BEC/ POLYPACK/ESC/KALINGA/AKG

22

SWITCHES,PLUGS,
TELEPHONE/CLIPSAL

M.K. INDIA/LEGRAND/CRABTREE/NORTH WEST

23

OUTLETS ( MODULAR TYPE

(MODULAR CLIP ON TYPE)

24

G.I. PIPE

TATA/JINDAL

25

CFL LIGHT FIXTURES

WIPRO/ PHILIPS/KESELEC/LOUISE

26

GLS LAMPS/CFL LAMPS/ TUBE LIGHT

OSRAM/ PHILIPS

27

FLUORESCENT LIGHT FIXTURES

WIPRO/ PHILIPS/KESELEC/THORN

28

EARTH LEAKAGE CIRCUIT

HAGER/ MDS/ ABB/MERLIN GERIN

29

PANELS

INDIA TECH/ ERA CONTROL /EVA ENGINERRS

30

FIRE ALARM SYSTEM

MORLEY/NOVAR/EDWARDS/APPOLO

18
19

MM ENTERPRISES/ MEM/ AMAZONE

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 101

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

31

HONEYWELL/LENEL/TYCO/SYRIS
HONEYWELL/ PELCO/SONY /SAMSUNG

32

ACCESS CONTROL SYSTEM AND


COMPONENTS &
CCTV CAMERA
DVR

33

MONITOR

SAMSUNG/ LG

SAMSUNG, NEOSYST, NOVAR, EUROPLEX, AVERS

LIST OF APPROVED MAKES (CEILING)


S.NO
1
2
3
4
5
6
7
8

ITEM
Metal False Ceiling
Gypsum False Ceiling
Illuminated Ceiling
Glass Partition System
Timber Partition System
Timber Wall Cladding
Glass Door( Single & Double Leaf)

APPROVED MAKE
Lindner, Goldbach, Virag
India Gypsum, Lafarge, USG
Lindner, Goldbach, Virag
Lindner, Goldbach, Virag
Lindner, Goldbach, Virag
Lindner, Goldbach, Virag
Lindner, Goldbach, Virag

Acoustic Soft Fiber Ceiling

Ecophon, Permaphon, Rockphon, Virag


(All materials shall be ISI mark)

LIST OF APPROVED MAKES FOR FURNITURES


S.NO
1
2
3
4
5
6

ITEM
BP
BP
BP
BP
BP
BP

APPROVED MAKE
Ergo, Harmony Systems,
Ergo, Harmony Systems,
Ergo, Harmony Systems,
Ergo, Harmony Systems,
Ergo, Harmony Systems,
Ergo, Harmony Systems,

Godrej,
Godrej,
Godrej,
Godrej,
Godrej,
Godrej,

Workstation
Storage System Compactor
Chairs & Tables
Sofa 2 seater & 3 seater
Auditorium Chairs
Discussion tables, Center & Corner
Tables, Reception Table, Cafeteria
Table
Display Rack

Haworth
Haworth
Haworth
Haworth
Haworth
Haworth

Library Racks

Godrej, BP Ergo, Harmony Systems, Haworth

Overhead storage racks

Godrej, BP Ergo, Harmony Systems, Haworth

10

Casualty Room table

Godrej, BP Ergo, Harmony Systems, Haworth

11

Podium

Godrej, BP Ergo, Harmony Systems, Haworth

Godrej, BP Ergo, Harmony Systems, Haworth

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 102

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

LIST OF APPROVED MAKES OF SYSTEM INTEGRATION WORKS

S. No.

Description of Work

CONFERFENCE ROOM SOLUTION- Control & facility


Building
DISPLAY SYSTEM

Full HD LED Display of 55"with Wall mount / Table mount

DLP HD Projection system of 4500 Lumens, 350W, 3000:1,


Standard Lens, Color Wheel, Horizontal Frequency: 15,30 - 90kHz;
Vertical Scan Rate: 43 - 85 Hz; Keystone Correction: 15
Vertical.
Motorized Lift for above projector

3
4

Motorized-electrically operated Matte White finished projection


screen of 65 x 116" [133" Diagonal] size, flame retardant and
mildew with minimum viewing angle 60 degrees, Gain 1.0. Shall
have specially designed motor mounted inside the roller with noise
silencer, three wire quick reversal type, oiled for life, with
automatic thermal overload cut-out, pre-set but adjustable limit
switches, with black masking borders standard. Bottom of fabric
shall be formed into a pocket holding metal rod. Case to be 21gauge powder coated steel, hexagon in shape with flat back,
complete with three position control switch in box with cover plate
Relay Interface for Up-Down movement of Motorized Projection
Screen

SOURCE EQUIPMENTS

1+ 5 party HD Point to Multipoint Video Conferencing System


consisting of
--Omni
Directional
Microphone
--10X
optical
zoom
Full
HD
Camera
--PC
for
Presentation
sharing
--Inbuilt recording on Memory stick feature
16 port 10/100/1000 Mbps Layer2 Giga Network Switch

6
7

DVD and HDD recorder features a HD Digital Tuner, 320GB HDD,


1080p up scaling via HDMI and MP3 Juke Box

AUDIO RE-INFORCEMENT SYSTEM

8
9

11
12

Embedded Boundary Microphones on conference table


Digital Signal Processor with echo canceller for minimum 16 audio
inputs
Feedback suppressor with built-in automatic mixer for the two
microphone inputs should automatically adapts up to 12 dB
additional gain before feedback occurs in the acoustical situation,
Multi-Channel Amplifier
Speaker System

13

Volume and audio source selector panel

10

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Approved Makes

Panasonic / Sharp
/ Hitachi
Delta
(Vivitek) / Barco /
Digital Projection
Custom

Da-lite / Draper /
Remaco

Reputed

Sony / Cisco

HP / Netgear /
Cisco
Reputed

Beyerdynamic
Bi-amp
Bosch (EV) /
Martin Audio /
Cerwin Vega
Bi-amp
Kramer / Extron /
Bosch (EV)
Biamp

Page | 103

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

CONTROL SYSTEM

14

Integrated Control System for presentation and co-ordination


between various audio-video and lighting control services through
5.2" Active Matrix Display featuring VoIP Intercom, 256 MB Flash /
128MB Standard SDRAM Memory, integrated battery, integrated
kickstand & (1) PS3.0 Power Supply and Integrated NetLinx
Controller with 404 MIPS Processor, 64MB RAM, 128 MB of FLASH.
8 IR Ports, 8 I/O Ports, 8 Relays, and 7 RS-232 / 422 / 485 Ports
Dimmer / Light Control system for Presentations

15
16
17

18
19

E
20

Multiformat Transmitter with receiver for 2 x Laptop and 1 x VC


Connectivities.
HDMI Matrix switcher of minimum 6 in and 6 out or more with
Max. Data Rate 2.25Gbps per graphic channel, HDCP Compatible,
HDTV Compatible, HDMI Support HDMI (V.1.4 with 3D, Deep
Color, x.v.Color), 3D Pass-Through, reclocks and equalizes the
signal and can route any input to any or all outputs
simultaneously.
HDMI Transmitter with Receiver for Display System (55" LED
Display and Projector)
HDMI Audio DeEmbedder with 1xHDMI, 1xS/PDIF, 1xTOSLINK
and 1xStereo (U) outputs for Multi-media output of laptop
presentation

21
22

1.5M molded Audio Cable complete with connectors

23

Audio / Speaker cable, Twisted pair stranded 26/30 (16 AWG)


copper, designed for connecting speakers and amplifiers
Four pair individually aluminumfoil shielded twisted pair, cabled
with a drain conductor and overall braidshielded -23AWG Control
Cable
Four pair individually aluminumfoil shielded twisted pair (S/FTP),
cabled with a drain conductor and overall braidshielded -23AWG
Data Cable designed for twisted pair digital transmitter receiver
sets to provide optimum range and performance for 10GBaseT
applications as defined in IEEE 802.3an and for PoE+ suitable for
terminated with shielded RJ45 connectors
Shielded RJ-45 Crimp Connector for 23 AWG Cable

25

26

Raylogic / AMX /
Crestron
Kramer / Extron

Kramer/ Extron

Kramer / Extron
Kramer / Extron

CABLES AND CONNECTORS


Highperformance 1.5M HDMI (M) to HDMI (M) patch cord with
molded HDMI connectors at both ends and with Ethernet Support
: High Data Transfer Rate Up to 10.2Gbps. Supported
Resolutions 720p/1080i/1080p Ideal for connecting HD devices to
HD/full HD plasma/LCD, PSP3, Bluray and HD DVD. Deep Color
Supports 24bit, 30bit, 36bit and 48bit (RGB or YCbCr) color
depths. Multi-Channel Audio Support - Supports audio stream for
external decoding by AV receivers and automatic audio syncing
capabilities. High Quality Connectors Goldplated connectors
resist corrosion.
1.5M VGA+A molded Patch cord complete with connectors

24

AMX / Crestron /
Extron

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Kramer / Extron /
Belden

Kramer / Extron /
Belden
Kramer / Extron /
Belden
Kramer / Extron /
Belden
Kramer / Extron /
Belden

Kramer / Extron /
Belden
Kramer / Extron /
Belden

Page | 104

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

27
F

1.5M power molded Cable complete with connectors


OTHER MISCELLANEOUS ITEMS

28

19" Equipment Rack of 24U

29

Online UPS of 3 KVA with 30 minutes back-up

II

Reputed Make

Rittal / President /
Valrack / MTS /
Intellerack
Libert / APC

Admin Building
Full HD LED Display of 42" with Wall mount / Table mount for [2 x
waiting lobby + 3 x Officer's rooms}

III
A

Admin - CONFERFENCE ROOM SOLUTION


DISPLAY SYSTEM

Full HD LED Display of 55"with Wall mount / Table mount

DLP HD Projection system of 4500 Lumens, 350W, 3000:1,


Standard Lens, Color Wheel, Horizontal Frequency: 15,30 - 90kHz;
Vertical Scan Rate: 43 - 85 Hz; Keystone Correction: 15
Vertical.
Motorized Lift for above projector

3
4

Panasonic / Sharp
/ Hitachi
Delta
(Vivitek) / Barco /
Digital Projection
Custom

Motorized-electrically operated Matte White finished projection


screen of 65" x 116" [133" Diagonal] size, flame retardant and
mildew with minimum viewing angle 60 degrees, Gain 1.0. Shall
have specially designed motor mounted inside the roller with noise
silencer, three wire quick reversal type, oiled for life, with
automatic thermal overload cut-out, pre-set but adjustable limit
switches, with black masking borders standard. Bottom of fabric
shall be formed into a pocket holding metal rod. Case to be 21gauge powder coated steel, hexagon in shape with flat back,
complete with three position control switch in box with cover plate

Da-lite / Draper /
Remaco

Relay Interface for Up-Down movement of Motorized Projection


Screen

Reputed

SOURCE EQUIPMENTS

1+ 5 party HD Point to Multipoint Video Conferencing System


consisting of:--Omni Directional Microphone--10X optical zoom Full
HD Camera--PC for Presentation sharing--Inbuilt recording on
Memory stick feature
16 port 10/100/1000 Mbps Layer2 Giga Network Switch

Panasonic / Sharp
/ Hitachi

DVD and HDD recorder features a HD Digital Tuner, 320GB HDD,


1080p up scaling via HDMI and MP3 Juke Box

AUDIO RE-INFORCEMENT SYSTEM

8
9

Embedded Boundary Microphones on conference table


Digital Signal Processor with echo canceller for minimum 16 audio
inputs

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Sony / Cisco
HP / Netgear /
Cisco
Reputed

Beyerdynamic
Bi-amp

Page | 105

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

10
11
12

Feedback suppressor with built-in automatic mixer for the two


microphone inputs should automatically adapts up to 12 dB
additional gain before feedback occurs in the acoustical situation,
Multi-Channel Amplifier
Speaker System

13

Volume and audio source selector panel

CONTROL SYSTEM

14

Integrated Control System for presentation and co-ordination


between various audio-video and lighting control services through
5.2" Active Matrix Display featuring VoIP Intercom, 256 MB Flash /
128MB Standard SDRAM Memory, integrated battery, integrated
kickstand & (1) PS3.0 Power Supply and Integrated NetLinx
Controller with 404 MIPS Processor, 64MB RAM, 128 MB of FLASH.
8 IR Ports, 8 I/O Ports, 8 Relays, and 7 RS-232 / 422 / 485 Ports
Dimmer / Light Control system for Presentations

15
16
17

18
19

E
20

Multiformat Transmitter with receiver for 2 x Laptop and 1 x VC


Connectivities.
HDMI Matrix switcher of minimum 6 in and 6 out or more with
Max. Data Rate 2.25Gbps per graphic channel, HDCP Compatible,
HDTV Compatible, HDMI Support HDMI (V.1.4 with 3D, Deep
Color, x.v.Color), 3D Pass-Through, reclocks and equalizes the
signal and can route any input to any or all outputs
simultaneously.
HDMI Transmitter with Receiver for Display System (55" LED
Display and Projector)
HDMI Audio DeEmbedder with 1xHDMI, 1xS/PDIF, 1xTOSLINK
and 1xStereo (U) outputs for Multi-media output of laptop
presentation

21
22

1.5M molded Audio Cable complete with connectors

23

Audio / Speaker cable, Twisted pair stranded 26/30 (16 AWG)


copper, designed for connecting speakers and amplifiers
Four pair individually aluminumfoil shielded twisted pair, cabled
with a drain conductor and overall braidshielded -23AWG Control
Cable
Four pair individually aluminumfoil shielded twisted pair (S/FTP),

25

AMX / Crestron /
Extron

Raylogic / AMX /
Crestron
Kramer / Extron

Kramer/ Extron

Kramer / Extron
Kramer / Extron

CABLES AND CONNECTORS


Highperformance 1.5M HDMI (M) to HDMI (M) patch cord with
molded HDMI connectors at both ends and with Ethernet Support
: High Data Transfer Rate Up to 10.2Gbps. Supported
Resolutions 720p/1080i/1080p Ideal for connecting HD devices to
HD/full HD plasma/LCD, PSP3, Bluray and HD DVD. Deep Color
Supports 24bit, 30bit, 36bit and 48bit (RGB or YCbCr) color
depths. Multi-Channel Audio Support - Supports audio stream for
external decoding by AV receivers and automatic audio syncing
capabilities. High Quality Connectors Goldplated connectors
resist corrosion.
1.5M VGA+A molded Patch cord complete with connectors

24

Bosch (EV) /
Martin Audio /
Cerwin Vega
Bi-amp
Kramer / Extron /
Bosch (EV)
Biamp

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Kramer / Extron /
Belden

Kramer / Extron /
Belden
Kramer / Extron /
Belden
Kramer / Extron /
Belden
Kramer / Extron /
Belden
Kramer / Extron /

Page | 106

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

26

cabled with a drain conductor and overall braidshielded -23AWG


Data Cable designed for twisted pair digital transmitter receiver
sets to provide optimum range and performance for 10GBaseT
applications as defined in IEEE 802.3an and for PoE+ suitable for
terminated with shielded RJ45 connectors
Shielded RJ-45 Crimp Connector for 23 AWG Cable

27

1.5M power molded Cable complete with connectors

19" Equipment Rack of 24U

29

Online UPS of 3 KVA with 30 minutes back-up

IV

Audio-Video System for 100 Seater Auditorium

DIGITAL PODIUM CONSISTING OF: -

1/3" CCD imaging camera for digital podium with 1280 x 960
resolution, 720p format, 12X optical zoom, capable to view as
small as 10mm and 260mm large objects, LED light source, USB &
LAN connectivities, capable to switch between Camera display and
PC images, complete in all respect & as per specifications.

PROFESSIONAL AUDIO SYSTEM CONSISTING OF: -

wall mount main FOH speakers loudspeaker with permanent install


single 15" LF, single 1.25" or more HF driver with Frequency
Response (-10 dB) 45 Hz - 20 kHz and the Sensitivity of 98 dB or
more ( 1W/1m) delivering a Max SPL 131 dB or more. The
loudspeaker should have a horizontal coverage angle of 90 degree
or better. It should have Power handling continuous.600800Watt.The loudspeaker should have integrated bracket or min
10 suspension points for permanent installation complete in all
respect & as per specifications.

Kramer / Extron /
Belden
Reputed Make

OTHER MISCELLANEOUS ITEMS

28

Belden

Wall mount main Delay speakers with Permanent install, flying,


single 12" Full Range 2 Way loudspeaker. The loudspeaker should
have frequency range (-10dB) of 55Hz-20kHz.It should have
sensitivity (1W/1m) of 99 dB delivering Max SPL of 129dB or
more. The loudspeaker should a nominal impedance of 8 ohms
and it should have with power handling pk of 1200W or more. The
speaker must be a permanent install loudspeaker with a min of 4
or more integrated suspension points complete in all respect & as
per specifications.
Subwoofer speaker with permanent installed, single 18" LF .It
should have a Freq. Range (-10 dB) of 50 Hz - 600Hz Hz. It should
have a sensitivity of (1W/1m) 99 dB or more delivering max
calculated SPL of 131 dB or more. The loudspeaker should have a
nominal impedance of 8ohm and Power Handling pk. of 4000W or
more complete in all respect & as per specifications.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Rittal / President /
Valrack / MTS /
Intellerack
Libert

Wolf Vision /
Bosch

Bosch (EV) /
Martin Audio /
Cerwin Vega

Bosch (EV) /
Martin Audio /
Cerwin Vega

Bosch (EV) /
Martin Audio /
Cerwin Vega

Page | 107

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

10

Stage Monitor speaker with in-built amplifier having 12" LF ,1" or


more HF with frequency range of 55Hz - 20kHz (-10dB) or better
delivering a max SPL 131dB SPL .It should have horizontal and
vertical coverage angle of 90 degree and 50 degree or better.
The loudspeaker should have inbuilt amplifier of class D delivering
a power of 1000W or more. It should have integrated monitor
angle on the enclosure for use floor monitor complete in all
respect & as per specifications.
Wall mount loudspeaker with dual 3.5" LF or more, single 0.75"HF
driver with Built-in LMT. It should have Frequency Response (-10
dB) of 90 Hz - 20 kHz. The loudspeaker should have a sensitivity(
1W/1m) of 85 dB or more delivering a Max SPL 106 dB or more
with Horizontal and Vertical coverage angle of 90 -120 degree
and 60-90 degree respectively .The loudspeaker should have
power handling pk of 300 Watt. The loudspeaker should have inbuilt LMT with power tap settings of 70V/100V:10W or more .It
should have integrated mounting bracket for permanent
installation complete in all respect & as per specifications.
Class H Dual channel power amplifier with specification as below
or BETTER to suit the power requirement of proposed speakers;
Max Midband Output Power:1150W @ 4 ohms,1750W @ 2 ohms,
Max Bridged Output Power:3600W @ 4 ohms, Frequency
Response:20Hz
20
KHz,
THD:<0.03%,Max
input
level:+21dBu,Crosstalk<80dB,input impedence:20kohm,signal to
noise ratio : >110dB ,with built in protection such as Audio
Limiters, Temperature, DC, HF Short Circuit, Peak Current
protections complete in all respect & as per specifications.
Dual channel power amplifier with specification as below or
BETTER to suit the power requirement of proposed speakers;
Max Midband Output Power:550W @ 4 ohms,600W @ 2 ohms,
Max Bridged Output Power:1250W @ 4 ohms, Frequency
Response:20Hz
20
KHz,
THD:<0.03%,Max
input
level:+20dBu,Crosstalk<80dB,input impedence:20kohm,signal to
noise ratio : >108dB ,with built in protection such as Audio
Limiters, Temperature, DC, HF Short Circuit, Peak Current
protection complete in all respect & as per specifications.
Single channel power amplifier for Control Room Speakers with
specification as below or BETTER to suit the power requirement of
proposed
speakers;
Rated Output Power:250W@70V/100V ,Frequency Response:70Hz
20KHz,THD:<0.5%,Max
input
level:+21dBu,input
impedence:20kohm,,with built in
protection such as Audio
Limiters, Temperature protection, Peak Current protections
complete in all respect & as per specifications.
100 W volume control for Speakers at Green room and control
complete in all respect & as per specifications.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Bosch (EV) /
Martin Audio /
Cerwin Vega

Bosch (EV) /
Martin Audio /
Cerwin Vega

Bosch (EV) /
Martin Audio /
Cerwin Vega

Bosch (EV) /
Martin Audio /
Cerwin Vega

Bosch (EV) /
Martin Audio /
Cerwin Vega

Bosch / Atlas /
Kramer / Extron

Page | 108

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

11

12

13

14

15

16

Digital Signal Processor with 2 x XLR IN, electronically balanced


audio input,6 x XLR OUT, electronically balanced audio output
with 2 x XLR Thru out ,and 1x XLR AES/EBU IN digital input, with
Nominal Input Voltage:1.23V / +4 dBu, maximum input
voltage:8.7V / +21 dBu, input impedance :10k Ohm, CMR:80dB@1kHz,A/D &D/A conversion :24 bit sigma delta,THD+N
<0.01% complete in all respect & as per specifications.
10 channel Mixer with Digital Audio interface with 4 input
channel & 4 output channels with AD/DA conversion 24-bit and;
USB 2.0 PC Interface, MIDI interface, OLED display;100 Digital
effects presets with at least 20 user preset available. 6 mono & 4
stereo channels, 6 auxiliary outputs, 11 band stereo equalizer;
THD (at 1kHz) <0.005%, frequency response (-3dB):20Hz to
65kHz; crosstalk >85dB, CMRR (at 1kHz)>80dB, Equivalent input
noise:-130dBu A, maximum level Mic inputs: +21dBu complete in
all respect & as per specifications.
Handheld Wireless Mic system that has a min of 14-hour battery
life from two AA alkaline batteries. Cardiod polar pattern, Dynamic
microphone ,frequency response 83Hz-18kHz,RF sensitivity < 1.0
Uv, Image rejection>55dB,Dyanmic range >95dB and receiver
having 30 channels possible, S/N ratio >100dB A, dynamic range
>95db
B,
distortion
<1
%,frequency
band:618634MHz,modulation:+/-40kHz complete in all respect & as per
specifications.
Wireless Lapel Mic system that has a min of 14-hour battery life
from two AA alkaline batteries. Cardiod polar pattern, Dynamic
microphone , frequency response 83Hz-18kHz, RF sensitivity < 1.0
Uv, Image rejection >55dB, Dynamic range >95dB and receiver
having 30 channels possible, S/N ratio >100dB A, dynamic range
>95db
B,
distortion
<1
%,frequency
band:
618634MHz,modulation:+/-40kHz complete in all respect & as per
specifications.
Gooseneck Mic with XLR base for podium having back electret
condenser microphone element ,Hyper Cardioid polar pattern,
programmable switch, frequency response 55Hz-20kHz ,sensitivity
5.5mV/Pa, clipping level >130dB SPL, output impendence 200
ohm complete in all respect & as per specifications.
feedback suppressor with built-in automatic mixer for the two
microphone inputs should automatically adapts up to 12 dB
additional gain before feedback occurs in the acoustical situation,
complete in all respect & as per specifications.

Bosch (EV) /
Martin Audio /
Cerwin Vega

MIDAS / Dynacord

Bosch (EV) /
Sennheiser

Bosch (EV) /
Sennheiser

Bosch (EV) /
Sennheiser

Bosch/ Martin
Audio / Cerwin
Vega

PRESENTATION SWITCHER WITH SCALER & TOUCH


CONTROL SYSTEM: -

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 109

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

17

18

Integrated Control System for presentation and co-ordination


between various audio-video and lighting control services through
5.2" Active Matrix Display featuring VoIP Intercom, 256 MB Flash /
128MB Standard SDRAM Memory, integrated battery, integrated
kickstand
&
(1)
PS3.0
Power
Supply
and
Integrated NetLinx Controller with 404 MIPS Processor, 64MB
RAM, 128 MB of FLASH. 8 IR Ports, 8 I/O Ports, 8 Relays, and 7
RS-232/422/485 Ports complete in all respect & as per
specifications.
Furniture-Mountable durable, metal enclosure for Cables, AAPs,
and AC Power Outlets with dimension of 6.96" W x 6.96" D (17.68
cm W x 17.68 cm D) that can be mounted into a tabletop or other
flat surface with a Blank anodize finish and a single Universal type
power outlet complete in all respect & as per specifications

19

Cable Cubby AC Universal Power Module complete in all respect &


as per specifications.

20

Two-input automatic switcher HDCP compliant transmitter wall


plate for sending HDMI or RGBHV video, audio, and Ethernet up
to 330 feet (100 m) over a single CAT 5-type cable. The unit
offered can be remotely powered. It should be able to support
signal with resolutions of 1920 x 1200 including 1080p/60 with the
data rates up to 6.75 Gbps, Deep Color up to 12-bit, 3D, HD
lossless audio formats, and CEC complete in all respect & as per
specifications.
Long Distance XTP Receiver for HDMI; HDCP compliant; able to
support 1080p / 60 Deep Color and 1920x1200 video signals,
HDMI data rates up to 6.75 Gbps with deep color, 3D and HD
Audio; HDMI audio de-embedding with analog stereo and digital
S/PDIF audio outputs; local Analog audio also; bidirectional RS232 and IR up to 330 feet (100 m) over a single CAT 5-type cable;
capable of remote powering complete in all respect & as per
specifications.
HDMI Matrix Switcher, should support computer-video to
1920x1200, including HDTV 1080p / 60; HDMI; data rates up to
6.75 Gbps, Deep Color up to 12-bit, 3D, and HD audio formats,
automatic cable equalization for each input to 100 feet (30
meters) at 1920 x 1200 / 8-bit color; Speed Switching for HDCPencrypted content; Key Minder for continuously verifying HDCP
compliance; EDID Minder should automatically manage EDID
communication between connected devices; Automatic output reclocking to Reshape and restore timing of HDMI signals at each
output, enabling transmission over long HDMI cables; Interface
Format Correction; capability to separate an embedded audio
signal from its corresponding video signal within the matrix
switcher, allowing the audio and video signals from one source to
be switched to different destinations; should provide +5 VDC, 250
mA power on the HDMI outputs for external peripheral devices
complete in all respect & as per specifications.

21

22

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

AMX / Crestron /
Extron

Extron / Kramer

Extron / Kramer

Extron / Kramer

Extron / Kramer

Extron / Kramer

Page | 110

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

23

24

25

26

HDMI Audio De-Embedder, Supports HDCP, HDMI audio deembedding with analog stereo and digital S/PDIF audio outputs;
data rates up to 6.75 Gbps, Deep Color up to 12-bit, and 3D,
Cable equalization at input; EDID Minder automatically manages
EDID communication between connected devices; LED indicators
for HDCP confirmation, signal, Link status and Power Complete in
all respect & as per specifications.
Long Distance XTP Transmitter for HDMI; It should be HDCP
compliant and able to support 1080p/60 Deep Color and
1920x1200 video signals, HDMI audio embedding with analog
stereo audio, local Analog audio also. Ethernet, remote power,
bidirectional RS-232 and IR up to 330 feet (100 m) over a single
CAT 5-type cable; HDMI data rates up to 6.75 Gbps with deep
color, 3D and HD Audio; capable of remote powering complete in
all respect & as per specifications.
Long Distance XTP Scaling Receiver, Twisted pair HDCP compliant
receiver unit that scales HDMI, DVI, RGB, HD component video,
and standard definition video to the optimal output resolution for
the display. It should accept video, audio, bidirectional RS-232
and IR, and Ethernet up to 330 feet (100 m) over a single CAT 5type cable with selectable output rates from 640 x 480 to 1920 x
1200, including HDTV 1080p / 60; should support data rates up to
6.75 Gbps, Deep Color up to 12-bit, HD lossless audio formats,
and CEC also to support various HDMI audio formats and is
capable to de-embed them from HDMI in form of Analog Stereo or
S/pdif digital format with audio adjustments and muting. The unit
should be controllable via USB or Rs-232 complete in all respect &
as per specifications.
9.7inch (diagonal) color touch screen or bigger LED-backlit glossy
widescreen MultiTouch display with 1024-by-768 resolution at
132 pixels per inch (ppi), support Wi-Fi (802.11a/b/g/n) and
Bluetooth 2.1 + EDR technology, should have at least 16GB of
storage memory; Built in speakers for video preview complete in
all respect & as per specifications.

27

Touch Panel Control Device License.

PROJECTION SYSTEM CONSISTING OF: -

28

LCD / DLP Multimedia Projector with minimum of 6500 ANSI


Lumens, Horizontal Frequency 30-90 KHz, Vertical scan rate 5085Hz, image size 40" - 500"; Keystone correction of Vertical:
40 , Horizontal: 35degree and complete in all respect with
wired and wireless between PC and Projector complete in all
respect & as per specifications.
Ceiling stand for Projection System complete in all respect etc as
required complete in all respect & as per specifications.

29

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Extron / Kramer

Extron / Kramer

Extron / Kramer

Reputed / as
recommended by
OEM
OEM
Recommended

Vivitek / Barco /
Digital Projection

Custom Design

Page | 111

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

30

Motorized-electrically operated Matte White finished projection


screen of 57.5 x 92" [109" Diagonal] size, flame retardant and
mildew with minimum viewing angle 60 degrees, Gain 1.0. Shall
have specially designed motor mounted inside the roller with noise
silencer, three wire quick reversal type, oiled for life, with
automatic thermal overload cut-out, pre-set but adjustable limit
switches, with black masking borders standard. Bottom of fabric
shall be formed into a pocket holding metal rod. Case to be 21gauge powder coated steel, hexagon in shape with flat back,
complete with three position control switch in box with cover plate
complete in all respect & as per specifications.
Relay Interface for Up-Down movement of Motorized Projection
Screen

E
31

38
39
40

Phono Socket / Connector with Suitable Accessories

33
34
35
36
37

Reputed

CABLES & CONNECTORS: Cat6 Cable in existing media complete in all respect & as per
specifications.
Control Cable in existing media complete in all respect & as per
specifications.
Speaker Cable in existing media complete in all respect & as per
specifications.
Microphone Cable in existing media complete in all respect & as
per specifications.
RGBHV Cable in existing media complete in all respect & as per
specifications.
RG59 Video Cable in existing media complete in all respect & as
per specifications.
3 core 2.5 Sq. mm copper conductor power cables in existing
media complete in all respect & as per specifications.
XLR Socket / Connector with Suitable Accessories
Speaker Socket / Connector with Suitable Accessories

32

Da-lite / Draper /
Remaco

Finolex / AMP /
Delton
Finolex / Skytone /
Delton
Finolex / Skytone /
Delton
Finolex / Skytone /
Delton
Extron / Kramer
Finolex / Skytone /
Delton
Finolex / Skytone /
Delton
Neutrik
Neutrik
Neutrik

Training Centre Building


1

Full HD LED Display of 42" with Wall mount / Table mount for [4 x
VIP suits + 1 x Common Room + 1 x Dinning area}

VI
A

CONFERFENCE ROOM SOLUTION


DISPLAY SYSTEM

Full HD LED Display of 55"with Wall mount / Table mount

DLP HD Projection system of 4500 Lumens, 350W, 3000:1,


Standard Lens, Color Wheel, Horizontal Frequency: 15,30 - 90kHz;
Vertical Scan Rate: 43 - 85 Hz; Keystone Correction: 15
Vertical.
Motorized Lift for above projector

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Panasonic / Sharp
/ Hitachi

Panasonic / Sharp
/ Hitachi
Delta
(Vivitek) / Barco /
Digital Projection
Custom

Page | 112

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

Motorized-electrically operated Matte White finished projection


screen of 65 x 116" [133" Diagonal] size, flame retardant and
mildew with minimum viewing angle 60 degrees, Gain 1.0. Shall
have specially designed motor mounted inside the roller with noise
silencer, three wire quick reversal type, oiled for life, with
automatic thermal overload cut-out, pre-set but adjustable limit
switches, with black masking borders standard. Bottom of fabric
shall be formed into a pocket holding metal rod. Case to be 21gauge powder coated steel, hexagon in shape with flat back,
complete with three position control switch in box with cover plate
Relay Interface for Up-Down movement of Motorized Projection
Screen

SOURCE EQUIPMENTS

1+ 5 party HD Point to Multipoint Video Conferencing System


consisting of:
--Omni
Directional
Microphone
--10X
optical
zoom
Full
HD
Camera
--PC
for
Presentation
sharing
--Inbuilt recording on Memory stick feature
16 port 10/100/1000 Mbps Layer2 Giga Network Switch

6
7

DVD and HDD recorder features a HD Digital Tuner, 320GB HDD,


1080p up scaling via HDMI and MP3 Juke Box

AUDIO RE-INFORCEMENT SYSTEM

8
9

11
12

Embedded Boundary Microphones on conference table


Digital Signal Processor with echo canceller for minimum 16 audio
inputs
Feedback suppressor with built-in automatic mixer for the two
microphone inputs should automatically adapts up to 12 dB
additional gain before feedback occurs in the acoustical situation,
Multi-Channel Amplifier
Speaker System

13

Volume and audio source selector panel

CONTROL SYSTEM

14

Integrated Control System for presentation and co-ordination


between various audio-video and lighting control services through
5.2" Active Matrix Display featuring VoIP Intercom, 256 MB Flash /
128MB Standard SDRAM Memory, integrated battery, integrated
kickstand & (1) PS3.0 Power Supply and Integrated NetLinx
Controller with 404 MIPS Processor, 64MB RAM, 128 MB of FLASH.
8 IR Ports, 8 I/O Ports, 8 Relays, and 7 RS-232 / 422 / 485 Ports
Dimmer / Light Control system for Presentations

10

15
16

Multiformat Transmitter with receiver for 2 x Laptop and 1 x VC


Connectivities.

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Da-lite / Draper /
Remaco

Reputed

Sony / Cisco

HP / Netgear /
Cisco
Reputed

Beyerdynamic
Bi-amp
Bosch (EV) /
Martin Audio /
Crewin Vega
Bi-amp
Kramer / Extron /
Bosch (EV)
Biamp

AMX / Crestron /
Extron

Raylogic / AMX /
Crestron
Kramer / Extron

Page | 113

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

17

18
19

E
20

HDMI Matrix switcher of minimum 6 in and 6 out or more with


Max. Data Rate 2.25Gbps per graphic channel, HDCP Compatible,
HDTV Compatible, HDMI Support HDMI (V.1.4 with 3D, Deep
Color, x.v.Color), 3D Pass-Through, reclocks and equalizes the
signal and can route any input to any or all outputs
simultaneously.
HDMI Transmitter with Receiver for Display System (55" LED
Display and Projector)
HDMI Audio DeEmbedder with 1xHDMI, 1xS/PDIF, 1xTOSLINK
and 1xStereo (U) outputs for Multi-media output of laptop
presentation

21
22

1.5M molded Audio Cable complete with connectors

23

26

Audio / Speaker cable, Twisted pair stranded 26/30 (16 AWG)


copper, designed for connecting speakers and amplifiers
Four pair individually aluminumfoil shielded twisted pair, cabled
with a drain conductor and overall braidshielded -23AWG Control
Cable
Four pair individually aluminumfoil shielded twisted pair (S/FTP),
cabled with a drain conductor and overall braidshielded -23AWG
Data Cable designed for twisted pair digital transmitter receiver
sets to provide optimum range and performance for 10GBaseT
applications as defined in IEEE 802.3an and for PoE+ suitable for
terminated with shielded RJ45 connectors
Shielded RJ-45 Crimp Connector for 23 AWG Cable

27

1.5M power molded Cable complete with connectors

25

Kramer / Extron
Kramer / Extron

CABLES AND CONNECTORS


Highperformance 1.5M HDMI (M) to HDMI (M) patch cord with
molded HDMI connectors at both ends and with Ethernet Support
: High Data Transfer Rate Up to 10.2Gbps. Supported
Resolutions 720p/1080i/1080p Ideal for connecting HD devices to
HD/full HD plasma/LCD, PSP3, Bluray and HD DVD. Deep Color
Supports 24bit, 30bit, 36bit and 48bit (RGB or YCbCr) color
depths. Multi-Channel Audio Support - Supports audio stream for
external decoding by AV receivers and automatic audio syncing
capabilities. High Quality Connectors Goldplated connectors
resist corrosion.
1.5M VGA+A molded Patch cord complete with connectors

24

Kramer/ Extron

Kramer / Extron /
Belden

Kramer / Extron /
Belden
Kramer / Extron /
Belden
Kramer / Extron /
Belden
Kramer / Extron /
Belden

Kramer / Extron /
Belden

Kramer / Extron /
Belden
Reputed Make

OTHER MISCELLANEOUS ITEMS

28

19" Equipment Rack of 24U

29

Online UPS of 3 KVA with 30 minutes back-up

VII
A

LECTURE HALL SOLUTION


DISPLAY SYSTEM

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Rittal / President /
Valrack / MTS /
Intellerack
Libert / APC

Page | 114

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

Interactive Ultra-short-throw DLP Projection System for classroom


usage, 3000 lumens of brightness with 2,500:1 contrast ratio,
Native resolution 1280 x 800, Throw ratio 0.19:1, 16:10 Native,
4:3, 16:9 Compatible, manually adjustable for Image Size
(Diagonal) 87" to 97"

Wall mount Kit for Short throw Projection system

Interactive White-board of 103 active diagonal size suitable for


above projection system with Aspect Ratio of 16:9
Multiformat Transmitter with receiver for 1 x Laptop and 1 x White
Board Connectivity.

4
5

Cables and Connectors

AUDIO RE-INFORCEMENT SYSTEM FOR EXECUTIVE


TRAINING ROOM
Hand-held wireless microphone system

6
7

8
9

10
11
12

13

VII

Gooseneck Mic with XLR base for podium having back electret
condenser microphone element ,Hyper Cardioid polar pattern,
programmable switch, frequency response 55Hz-20kHz ,sensitivity
5.5mV/Pa, clipping level >130dB SPL, output impendence 200
ohm
HDMI Audio DeEmbedder with 1xHDMI, 1xS/PDIF, 1xTOSLINK
and 1xStereo (U) outputs for Multi-media output of laptop
presentation
Feedback suppressor with built-in automatic mixer for the two
microphone inputs should automatically adapts up to 12 dB
additional gain before feedback occurs in the acoustical situation,
Dual channel (Stereo) Audio Amplifier & Switcher (40 Watts per
Channel) 1 Stereo (B) 1 Stereo (U)
Volume controller for two channels of balanced stereo audio
signals on XLR connectors
2way coaxial ClosedBack Ceiling Speakers (4) Closed Back
Can with Woofer 4", Tweeter 1", Freq 20Hz to 20kHz,
Crossover Frequency 10kHz, Sensitivity 85dB., Frequency
Response 85Hz to 20kHz., Power Rating 20W nominal, 40W Max
Cables and Connectors

Delta
(Vivitek) / Barco /
Digital Projection
Custom
Intelle-Board
Extron / Kramer

Bosch (EV) /
Sennheiser
Bosch (EV) /
Sennheiser

Kramer / Extron
Bosch (EV) /
Martin Audio /
Cerwin Vega
Kramer / Extron /
Bosch
Kramer / Extron /
Bosch
Kramer / Extron /
Bosch
Kramer / Extron /
Belden

Canteen

DISPLAY SYSTEM

Full HD LED Display of 42" with Wall mount / Table mount for

BACKGROUND MUSIC SYSTEM FOR CANTEEN

2
3
4

Mixer Amplifier, minimum 60 W 100/70V Speaker out.


Booster Amplifier, minimum 240 W 100/70V Speaker out.
Handheld Wireless microphone

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Panasonic / Sharp
/ Hitachi
Bosch
Bosch
Bosch (EV) /
Sennheiser

Page | 115

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

economic flush-mounting ceiling full range loudspeaker for speech


and music reproduction, Complies to Safety acc. to EN 60065
Emergency acc. to BS 5839-8 / EN 60849,,Rated power 6 / 3 / 1.5
/ 0.75 W, Sound pressure level at 6 W / 1 W (4 kHz, 1 m)102 dB /
94 dB (SPL),Effective frequency range (-10dB) 80 Hz to 18 kHz,
Opening angle at 1 kHz / 4 kHz (-6 dB) 160 / 65
100W volume control used to adjust the level locally, Built-in 24
VDC override relay, complies to Safety acc. to EN 60065 Selfextinguishing acc. to UL 94 V0 std, Frequency response 50 Hz to
20 kHz (-1 dB)
Housing for Volume control

CD player, able to play MP3, WMA audio files with USB input.

Equipment Rack with lockable and front perforated doors.

10

2 Core speaker cum control wire in existing media

11

3 core 1.5M molded power cable

12

3 core power cable in existing media

SYSTEM INTEGRATORS

Kramer / Extron /
Bosch

Kramer / Extron /
Bosch
Custom
Philips or
equivalent
Rittal / President /
Valrack / MTS /
Intellerack
Finolex / Skytone /
Delton
Finolex / Skytone /
Delton
Finolex / Skytone /
Delton

CEECO TECHNOLOGIES PVT. LTD., NEW DELHI


BHARAT RADIO CENTRE, LUCKNOW
PAN INTELLECOM, NEW DELHI

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 116

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

ANNEXURE-III : LIST OF TENDER DRAWINGS

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 117

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

CONTROL & FACILITY BUILDING


S.No.

DRAWING TITLE

JOB NO.

DRAWING NO.

GROUND FLOOR
(Existing Plan)
FIRST FLOOR
(Existing Plan)
SECOND FLOOR
(Existing Plan)
GROUND FLOOR
(Proposed Plan)
FIRST FLOOR
(Proposed Plan)
SECOND FLOOR
(Proposed Plan)

MUA-OTPC-A-01

AR/C&F/EX-01

MUA-OTPC-A-02

AR/C&F/EX-02

MUA-OTPC-A-03

AR/C&F/EX-03

MUA-OTPC-A-04

AR/C&F/PL-01

MUA-OTPC-A-05

AR/C&F/PL-02

MUA-OTPC-A-06

AR/C&F/PL-03

2
3
4
5
6

TRAINEE HOSTEL
S.No.

DRAWING TITLE

JOB NO.

DRAWING NO.

GROUND FLOOR
(Existing Plan)
FIRST FLOOR
(Existing Plan)
GROUND FLOOR
(Proposed Plan)
FIRST FLOOR
(Proposed Plan)

MUA-OTPC-A-19

AR/TH/EX-01

MUA-OTPC-A-20

AR/TH/EX-02

MUA-OTPC-A-21

AR/TH/PL-01

MUA-OTPC-A-22

AR/TH/PL-02

8
9
10

SWITCHYARD CONTROL ROOM BUILDING


S.No.

DRAWING TITLE

JOB NO.

DRAWING NO.

11

GROUND FLOOR
(Existing Plan)
FIRST FLOOR
(Existing Plan)
GROUND FLOOR
(Proposed Plan)
FIRST FLOOR
(Proposed Plan)

MUA-OTPC-A-31

AR/SY/EX-01

MUA-OTPC-A-32

AR/SY/EX-02

MUA-OTPC-A-33

AR/SY/PL-01

MUA-OTPC-A-34

AR/SY/PL-02

12
13
14

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 118

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

ADMIN BUILDING
S.No.

DRAWING TITLE

JOB NO.

DRAWING NO.

15

GROUND FLOOR
(Existing Plan)
FIRST FLOOR
(Existing Plan)
GROUND FLOOR
(Proposed Plan)
FIRST FLOOR
(Proposed Plan)

MUA-OTPC-A-43

AR/AD/EX-01

MUA-OTPC-A-44

AR/AD/EX-02

MUA-OTPC-A-45

AR/AD/PL-01

MUA-OTPC-A-46

AR/AD/PL-02

16
17
18

MEDICAL CENTRE BUILDING


S.No.

DRAWING TITLE

JOB NO.

DRAWING NO.

19

GROUND FLOOR
(Existing Plan)
GROUND FLOOR
(Proposed Plan)

MUA-OTPC-A-55

AR/MED/EX-01

MUA-OTPC-A-56

AR/MED/PL-01

20

TRAINING CENTER BUILDING


S.No.

DRAWING TITLE

JOB NO.

DRAWING NO.

21

GROUND FLOOR
(Existing Plan)
FIRST FLOOR
(Existing Plan)
GROUND FLOOR
(Proposed Plan)
FIRST FLOOR
(Proposed Plan)

MUA-OTPC-A-61

AR/TC/EX-01

MUA-OTPC-A-62

AR/TC/EX-02

MUA-OTPC-A-63

AR/TC/PL-01

MUA-OTPC-A-64

AR/TC/PL-02

22
23
24

CANTEEN BUILDING
S.No.

DRAWING TITLE

JOB NO.

DRAWING NO.

25

GROUND FLOOR
(Existing Plan)
GROUND FLOOR
(Proposed Plan)

MUA-OTPC-A-73

AR/CAN/EX-01

MUA-OTPC-A-74

AR/CAN/PL-01

26

FIRE STATION BUILDING


S.No.

DRAWING TITLE

JOB NO.

DRAWING NO.

27

GROUND FLOOR
(Existing Plan)
GROUND FLOOR
(Proposed Plan)

MUA-OTPC-A-79

AR/FS/EX-01

MUA-OTPC-A-80

AR/FS/PL-01

28

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 119

PLANT: 2X363.3 MW GAS BASED COMBINED CYCLE POWER PLANT

SECURITY HOSTEL
S.No.

DRAWING TITLE

JOB NO.

DRAWING NO.

29

GROUND FLOOR
(Existing Plan)
FIRST FLOOR
(Existing Plan)
SECOND FLOOR
(Existing Plan)
SECOND FLOOR
(Proposed Plan)

MUA-OTPC-A-85

AR/SH/EX-01

MUA-OTPC-A-86

AR/SH/EX-02

MUA-OTPC-A-87

AR/SH/EX-03

MUA-OTPC-A-88

AR/SH/PL-03

30
31
32

TECHNICAL SPECIFICATIONS
FOR INTERIOR DECORATION & FURNISHING OF PLANT BUILDINGS

Page | 120