You are on page 1of 44

GE Power Management

Relay
Selection
Guide

x
g

GET-8048A

MULTILIN
Page

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
...1
Basic
Concepts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Types of Distress . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
.3
Detection
Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Protection
Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Generators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Feeders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Buses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Incoming Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
GE Relay Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

PROTECTIVE ZONE PACKAGES


Table
of
Contents

INTRODUCTION

x
INTRODUCTION
Power distribution systems serving industrial or
commercial facilities represent a variety of costs

to the owner. Obviously, the capital cost of the


equipment is a concern, as is the cost of the energy
which that power system delivers to the loads
which convert electrical energy to a saleable
product or service. There are some less obvious
costs - the cost or reliability, measured in products
or services which cannot be sold because power
is unavailable, or an even more illusive concept,
the cost of quality, which relates to customer
satisfaction. Ultimately, as the designer of the
system struggles with devising a system
arrangement and choosing equipment, he must
face the reality that no matter how clever he is, no
matter how much redundancy he builds into the
system, and no matter how much he pays for
premium quality components, he simply cannot
build a system which will never fail.
This is where system protection, and protective
relays become important. If component failure is
inevitable, then it is necessary to provide a means
of detecting these failures. Better and faster
protection afford a number of desirable attributes,
all of which ultimately result in saving the owner
of the system money through cost avoidance.
When component distress is detected and
corrected earlier, the damage associated with the
failure is minimized, which results in lower repair
costs (or even the ability to repair versus the need
to replace). At the same time, faster and more
sensitive detection of problems means that the
cause of the problem can be corrected while it is
still a minor problem, and before it escalates into
a major catastrophe.
Protection is applied on a component basis.
Relays are associated with each major
component of the power distribution system to
detect various forms of distress associated with
those components. If one of those relays
operates (which means that an output contact
closes because the relay detects a level of
distress in excess of its calibration or setting), it
initiates tripping of circuit breakers or other
protective devices which then isolates the
defective system components. It may be
convenient to think of the circuit breaker as the
muscle that does the work of isolating the

component, while the relay is the brain which


decides that isolation is required.
Because protection is associated with
components, it has become customary to talk
about relays which .protect. the component with
which they are paired. While it is true that faster
and more sensitive protection does reduce the
amount of damage at the point of the actual fault
or distress, and in this sense, relays which detect
and de-energize defective equipment do protect
their associated components, the value of relay
protection on system continuity is even greater.
In the limit, a failed motor may have to be
replaced, but good relaying on the motor will
isolate the motor from the remainder of the power
distribution system, allowing it to continue to
function and permitting the facility to continue
in-service. Ultimately, therefore, it is system
protection and service continuity that are the
justification for good relay protection.
1
Figure 1
Zones include any circuit breakers associated with protected equipment

Zones of Protection
Other zones could be defined to
comprise buses, generators, motors,
cables, etc. Figure 2 shows one final
requirement about these zones - they
must overlap. Because protection is
applied in association with these defined
zones, it is absolutely essential that every
portion of the system must fall within a
zone in order to assure that there are no
areas which are unprotected. Figure 2
Zones must overlap

Association with a significant component (in this case,


a line).
Terminates at and includes a circuit breaker (or other
interrupter) which can respond to trip signals from
relays associated with the zone.
Represents a minimum amount of system which must
be de-energized to correct a problem anywhere in the
zone.

Primary and Backup Zones


One of the most powerful conceptual
tools available to the protection engineer is
the notion of zones" as shown in Figure 1
Rather than thinking of the power
distribution system as unbounded,
successful protection relies on visualizing
the system as a collection of discrete

zones which can be individually protected


using equipment designed to detect the
unique forms of abnormalities
associated with each component.

In spite of the best efforts of system designers and


protection specialists, and despite the fact that relays have
a historical record of being among the most reliability
components of the power system, the unexpected will
happen. This has led to the practice of assuring that failure
of a single relay can never result in loss of protection. This
so-called backup can exist in any of several forms:
Remote Backup - in which the relays of one zone have
the ability to also detect problems in adjacent zones.

BASIC CONCEPTS
Remote backup protection is the most common practice in
both industrial and commercial applications, and usually
involves time delays to assure selectivity.
Local Backup - in which each zone is equipped with a
complete set of redundant relays. Often the relays which
are designated as backup employ different measuring
principles, and in more conservative schemes, may employ
totally different signal sources, and even trip different
breakers using different battery supplies.
2

Overcurrent is the term employed in the National Electrical


Code to mean short-circuit. On a healthy system, the
flow of current is a function of the magnitude of elecrical
load. A short-circuit is a breakdown in insulation which
results in an abnormal flow of current limited only by the
impedance of the electrical distribution system. The
distress associated with a short-circuit comes about
because of the flash and arcing at the fault point, the
depression in system voltage associated with the fault, and
the thermal stress imposed on the conductors which must
carry fault current. Short-circuits are the focus of greatest
attention in protection of medium and high voltage systems.
The change in state from load current to short-circuit
current occurs rapidly. From fundamental physics, it is
known that the magnitude of current in an inductor cannot
change instantaneously. This conflict can be resolved by
considering the short-circuit current to consist of two
components, a symmetrical ac current having the higher
magnitude of the short-circuit current, and an offsetting dc
transient which has an initial magnitude equal to the initial
value of the ac current and which decays rapidly. The
initial magnitude of the dc transient is directly controlled
by the point on the voltage wave at which the short-circuit
occurs; if the short-circuit occurs at the natural zero crossing
of the driving voltage sinusoid, the transient is maximized
where as it is a minimum if the fault occurs at the crest of
the voltage sinusoid. At any subsequent point in time, the
magnitude of the dc transient is determined by the time
constant of the decay of the dc which is controlled by the
ratio of reactance to resistance in the impedance limiting

the fault. For the protection engineer, the worst case initial
current is that which includes the full dc transient.
The voltage which drives a short-circuit includes sources
such as remote generators with voltage regulators that will
maintain their value regardless of the presence of a shortcircuit
on the system, as well as nearby sources whose
voltage will decay when the short-circuit is present. The
amount of decay is determined by the nature of the source.
Nearby generators and synchronous motors which have
active excitation systems will sustain some voltage, but
since the short-circuit will cause their terminal voltage to
drop, the current they produce will gradually be reduced as
the fault is allowed to persist. At the same time, induction
motors will initially participate as short-circuit current
sources, but their voltages will decay rapidly as the trapped
flux is rapidly drained.

Overcurrent
Figure 3
Short-circuit currents include components with
both ac and dc decrement

Asymmetrical fault current with


decaying dc component
Symmetrical fault current
with ac decrement
Typical total fault current
with both ac and dc decrement
Figure 3 illustrates how the various elements of
asymmetry combine to create the most
realistic case of the decaying symmetrical
ac current combined with the decaying dc
transient. From this figure, it is possible to
describe a generalized short-circuit current
in the following terms:
High initial magnitude dc transient
component of current which decays
fairly rapidly with time.
High initial magnitude symmetrical
ac current which diminishes gradually
with time.
Symmetrical ac current lags driving
voltage by a significant angle,
approaching 90.
3

TYPES OF DISTRESS
Overload is exactly what the term implies - excessive load
demand reflected back into the power distribution system.
The undesirable aspect of overload is purely thermal (I2t)
heating in conductors and transformers, related thermal

The power distribution system can tolerate open circuits


continuously without harm. Where open circuits are a
concern is on rotating machines - motors and generators where they translate into abnormal rotor heating for which

Abnormal voltage or frequency usually is a consequence

of some form of overall system distress, and while these


symptoms may appear following failure of a power
distribution system component, this is usually indicative of
some undesirable consequence of that system failure rather

Overload
Open Circuit
Abnormal Voltage or Frequency
abuse to the power utilization equipment which interfaces
the load to the electrical system. Overload is a significant
aspect of low voltage protection, but is usually not a major
consideration at medium and high voltages.
4
these equipments have little tolerance. Hence, open circuit
protection is frequently applied on motors and generators,
and seldom on the passive portions of the distribution
system.
than a direct result of the failure itself. Undervoltage can
result in overload-like thermal heating, while overvoltage
can shorten insulation life and accelerate insulation failure
(and short-circuits). Abnormal frequency usually is
indicative of an imbalance between load and generation.

DETECTION MODES
Circuit - Current or Impedance
Based on the desire to array protection in logical zones,
the most common mode of protection is one which can not
only detect that an abnormality (such as a short circuit)
exists, but which can also determine its location. The
parameter which most simply locates faults is current short-circuits result in abnormal flow of current, and a relay
system which looks for high current will be able to selectively
detect faults. Current is the parameter which is used in the
vast majority of all protection schemes, and is used almost
exclusively from 35kV down through 120V residential
distribution.

Voltage measurements can be used to detect that


something unusual is happening on the system, but
generally voltage will not give any indication of the location

System - Voltage or Frequency


Closely related to current detection is measurement of
apparent impedance. Apparent impedance is the ratio of
voltage to current measured at a relay location and is a
direct measure of the electrical separation between the relay
location and a point on the system where the voltage is
depressed to zero by a short-circuit. Impedance
measurement is more complicated than current
measurement, and hence its use is reserved for more
critical applications at the higher voltages, typically above
69 kV.
of the problem. Hence, measurement of voltage is usually
reserved for overall system protection functions. Likewise,
frequency is an overall system issue.

PROTECTION CHARACTERISTICS
5

Time Overcurrent
The principle of time overcurrent protection is that relays
are applied appropriately at the terminals of zones, and
each relay is then given both a current pickup and a time
delay setting. The current pickup establishes the sensitivity
of the relay; a variety of rules dictate what this sensitivity
must be. Some of these rules are mandatory and must be
followed; the National Electrical Code contains a number
of requirements on the current setting of overcurrent relays.
Other rules are embodied in application standards, and
while these are not absolutely mandatory, they do represent
a consensus of the industry from which most engineers
would not want to deviate. Finally, there are several rules
of thumb, or conventional practices which, through
experience, have been recognized as good things to do.

Time overcurrent protection is the predominant form of


protective relaying in medium voltage industrial and
commercial power systems. This form of protection employs
relays with inverse time-current characteristics; that is,
operating time of these relays becomes less as the current
magnitude increases. The basic operating characteristics
trace their heritage to the natural operating characteristics
of the induction disk overcurrent relay, and as a result static
analog and digital relays are designed to emulated this basic
characteristic, but there is also a noble rationale for the
inverse-time relationship. Relays are intended to detect
and initiate tripping of high-magnitude fault currents quickly
enough to avoid thermal damage to conductors, and the
natural heating characteristic is also an inverse-time
relationship.
Traditionally, the characteristics of time overcurrent relays
has been published in the form of graphical curves showing
the dependent variable (operating time) on the vertical axis
and the independent variable (operating current) on the
horizontal axis. It is also a tradition that these curves are
plotted on a special log-log paper. These traditions trace
their origin to the manual practices involved in determining
settings for relays.
There are a number of characteristics in common use,
which are shown in Figure 4. Each of these exists to address
specific application needs. Following is a list of the most
common characteristics together with their usual
applications and also the code number which GE uses to
identify each curve shape:
Inverse medium time (51) - best suited for applications
where the variations in the magnitude of fault current are
related primarily to switching of sources on the system,
such as in paper mill systems with a number of small
hydroelectric generators which are switched on and off
depending on water conditions.
Very inverse medium time (53) - best suited for general
applications where the variations in the magnitude of fault

current are primarily determined by system impedance


and fault location. This relay characteristic is the best
choice for most industrial and commercial applications.
Inverse medium-long time (57) - best suited for
applications as backup ground fault protection on complex
low-resistance grounded medium voltage systems.
Inverse long time (66) - best suited for overload and locked
rotor protection of motors.
Extremely inverse medium time (77) - best suited for
application on utility residential distribution circuits where
selectivity with distribution fuse cutouts and reclosers is a
requirement, and where cold load pickup is a consideration.
Inverse short time (95) - best suited for backup ground
fault protection applications on solidly grounded low voltage
systems where the feeders have instantaneous ground fault
protection.
Figure 4
Inverse time characteristics of various
GE time overcurrent relay models

6
Figure 5
Selective coordination of time overcurrent relays assumes that
the backup relay will always be slower than the primary relay

The time setting is used to achieve selective backup


protection. How this happens is best illustrated with
characteristic curves as in Figure 5. For a fault on a feeder,
the current magnitude determines the operating time of all
relays. Relays which are closest to the fault have time
settings which result in faster operation than those which
are further away. Therefore, the primary relays which are
closest to the fault want to trip first while the more remote
backup relays wait, but if the primary relays (or their
associated circuit breakers) fail, then the backup relays time
out and trip. The time margin between the settings of these
relays must take into account three factors:
The operating time of the circuit breakers. Modern medium
voltage breakers are rated for 5 cycle interrupting time,and
the time allowance is traditionally 0.1 second.
Overtravel, which is the tendency for a relay to continue
to time after the fault current is interrupted by a downstream
circuit breakers. Overtravel is a natural characteristic of
the inertia of electromechanical induction disk relays, and
while exact values vary widely, the traditional allowance is
0.1 seconds. Most static analog and digital relays are
designed to have no practical overtravel. If the backup relay
has an overtravel tendency, its time delay must be long
enough to account for that overtravel.
Margin to account for imponderables such as the
uncertainties in the magnitude of fault current, inaccuracies
in instrument transformers, manufacturing and calibration
variations in relays, etc. The amount of margin allowed
depends upon how much risk the relay engineer is willing
to assume; typical values range from 0.1 to 0.3 seconds.
The total coordinating time margin is the sum of these
three factors and ranges from 0.2 to 0.5 seconds; a 0.3
second margin is often taken as a reasonable compromise

between the objectives of speed and security.


The chore of determining settings for an array of time
overcurrent relays is time consuming work which entails
making a number of engineering judgments. One must start
closest to the load and work toward the sources in the
system, determining both pickup current and time delays
settings for each relay in succession. It is not unusual to
find that this process results in excessively long relay
operating times for faults near the source, so it is then
necessary to work back through the system making other
judgments and introducing compromises. It has been
correctly said that this task is the most difficult and exacting
work within the province of the relay engineer. The traditional
approach entailed tracing relay performance curves, but
the availability of computer tools eliminate some of this
drudgery. However, even with this automation, one must
still be prepared to focus carefully on the task at hand and
be prepared to deal with exacting details.
7

Voltage
Directionality
Normal current leads voltage by 90
Figure 6
Basic system phasor relationships
Figure 7
Directional relay directionality

Many simple applications can be satisfied by relays which


measure only magnitude (of current) and time duration.
However, to achieve fast, secure, selective operation in
"network" systems which involve parallel paths between
sources and loads, or systems with multiple sources of fault
current, the relays will also be required to determine the
direction of current flow. The basic principle used in
determining directionality is that, in a power system operating
at unity power factor, phase current and phase-to-neutral
voltage are in phase, and that phase current leads the
phase-to-phase voltage between the other two conductors
by 90 Figure 6. Fault current in that conductor lags its
phase-to-neutral voltage by the angle of system impedance, .
Therefore, the phase angle of fault current in Phase A will
always lead the angle of the B-C voltage by an angle which
can never exceed 90. However, if the direction of the current
in Phase A reverses, then its' angle will lag the B-C voltage
by up to 90.
Figure 7 shows a relay characteristic which utilizes this
concept to determine directionality of fault current.
A directional relay on Phase A uses the B-C voltage as its
polarizing reference, and together they establish a
directional phasor which leads the B-C reference voltage
by an angle which is fixed in the design of the relay.
Operation can occur if the current angle falls within 90 of
the angle of the directional phasor.
In most instances, directionality is a function which is added
to other relay characteristics. That is, overcurrent relays
are made directional by incorporating a directionality

function to the design of the relay such that an overcurrent


measurement can only be made if the directionality is
satisfactory.
With induction relays, one induction unit is required for the
overcurrent measurement, while a separate unit is used to
determine the direction of the current. Digital relays are less
complex; the directional function may be a few more lines
of code.

Voltage protection tends to be applied to detect various


forms of overall system distress. The actual detection
functions can be either undervoltage (which operate in
response to an undesirable reduction in voltage) or
overvoltage (which respond to high voltage). One of the
application challenges in working with undervoltage or
overvoltage relays is that normal system voltage encompasses
a range of magnitudes around the nominal rated value.
Furthermore, there are normal system conditions which
produce momentary excursions outside this band of values.
As a result, the relays used to provide this function may be
either instantaneous or time-delayed, and in the case of
time, the delay function may be either inverse time or definite
time.
The use of inverse time delay is probably more of a tradition
traceable to the historical use of the induction disk
technology than it is something which is required by the
application. The one situation where an inverse time delay
is desirable is when a time-delayed undervoltage relay on
a bus must be selective with an inverse time overcurrent
relay on a feeder in response to system faults. Note that
while this application is possible, it is not easy to actually
do.

s
s
V
I
Directional phasor
Operating region
Non-operating
region

Figure 9
Basic operation of differential relays

The most complex relays in common application are called


distance relays because they measure the apparent
impedance between the relay and the short-circuit. The
apparent impedance is measured by computing the ratio
between voltage and current at the relay. These relays,
which are almost alway directional, are typically employed

on transmission lines where impedance is both predictable


and constant. In these applications, impedance is directly
proportional to physical distance. In fact, modern digital
distance relays have the ability to actually report this
distance as an aid to locating the point of fault. They are
also commonly used for generator protection, and in special
applications on motors.
Distance relay applications are very different from
overcurrent applications; selectivity is achieved by means
of sensitivity (distance setting) and time delay, but the timing
functions are almost always definite time rather than inverse
time. A more dramatic difference is that distance relay
application technology has its own "language", the R-X
diagram as shown in Figure 8.
The R-X diagram is a set of coordinates of impedance
where the origin is at the relay location and impedances in
the first quadrant are in the designated tripping direction of
the impedance-measuring relays. Impedances in the third
quadrant represent short-circuits in the non-tripping
direction, while second and fourth quadrant impedances
are dynamic characteristics which are beyond the depth of
this text.
Figure 8
Distance relay characteristic
shown on an R-X diagram

Distance
While overcurrent, voltage, distance and directionality are
powerful techniques, all of them involve some compromise
between the objectives of reliability, security, speed,
selectivity and economy. Differential protection is different.
It is profoundly simple, inherently secure, highly reliable,
fast, and reasonably economical. As a result, differential
protection is the most important concept in protection.
The concept is a direct extension of Kirchoff's current law the sum of all currents into a region must be zero. Current
transformers are placed at each electrical terminal of the
protected zone and wired together as indicated in Figure 9.
For external faults, where fault current passes through the
zone, current circulates in the current transformer
secondaries without passing through the relay. If the fault
is internal to the zone, then the currents introduced into the
current transformer secondaries oppose each other and
are forced to flow through the relay.
The basics of a differential application include:
CT at each power connection to the protected zone
All ct's have the same rating
Careful attention to assure proper ct connections
Differential protection is primary protection: it
cannot provide backup protection for remote zones

Differential
9

PROTECTIION PACKAGES
The following protection packages are organized according

to the types of equipment generally encountered in medium


voltage systems. Generators, Motors, Feeders,
Transformers, Buses, and Incoming Lines will be
addressed.
Packages are based on commonly used power system
configurations. Other considerations may be needed if
unique power system arrangements are used.
Qty. Device No. Description GE Model No.

GEN G E N E R A T O R
Protective Zone (GEN1)
Minimum protection for a small machine with low resistance grounding:

LOW
RES

* Locate these Ct's on neutral side


of generator if no external fault source.
BUS
51V
GEN 27 59
51GN
2 (or 3)
1
1
3

87G
RTD
49R 81L/H
32 40 46
50GS
CONTROL
PACKAGE
86G
64B
3

Device list for GEN 1


27 Undervoltage
32 Power Direction
40 Loss of Excitation
46 Current Unbalance

49R Overload (RTD)


50GS Instantaneous Overcurrent
Ground
51GN Time Overcurrent Ground
51V Time Overcurrent (V Restraint)
59 Overvoltage
64B Bus Ground Detection
81L/H Frequency
86G Lockout Auxiliary
87G Differential
10

Basic Package
3 51V Voltage-restrained Time Overcurrent Relay IFCV51AD
1 51GN Neutral Ground Overcurrent Relay DIFC or IFC53A

Options
1 27 Undervoltage Relay TOV5 or IAV54
1 32 Reverse Power Relay (detects losses over 5%) ICW51A
or Reverse Power Relay (detects losses below 5%) or GGP53C
1 40 Loss-of-excitation Relay CEH51A
1 46 Negative Sequence Relay SGC21C
1 49R Stator Overtemperature Relay (RTD input) IRT51E
1 50GS Ground Sensor Overcurrent Relay (in place of DIFC or HFC21
51GN where system ground is not generator neutral)
3 51VC Voltage-controlled Overcurrent Relay (in place of 51V) IFCS51AD
1 59 Overvoltage Relay TOV5 or
IFV71AD
1 64B Generator Ground Overvoltage Relay
(in place of 51GN where generator is ungrounded) TOV5 or
IFV51DD
1 81 L/H Under/Overfrequency Relay SFF202B
1 86G Lockout Auxiliary Relay HEA61
1 87G Self-balancing Current Differential Relay
(for connections see MTR1A figure) MDP
or Percentage Current Differential Relay or CFD22A
3*
s

Qty. Device No. Description GE Model No.


11

Protective Zone (GEN1A)


Alternate protection for a small machine with low resistance grounding:

GEN G E N E R A T O R
Device list for GEN 1A
27 Undervoltage
32 Power Direction
40 Loss of Excitation
46 Current Unbalance
49R Overload (RTD)
50GS Instantaneous Overcurrent
Ground
51GN Time Overcurrent (Ground)
51VC Time Overcurrent (V Control)
59 Overvoltage

81L/H Frequency
86G Lockout Auxiliary
87G Differential

LOW
RES
GEN
2 (or 3)
1
3*
1
3
87G
86G

* Locate these Ct's on neutral side


of generator if no external fault source.
RTD
49R
BUS
3

CONTROL
PACKAGE
50GS

40 46/49C
51GN
51
81L/H
51VC
27
59
32

Alternate Package
1 Multifunction analog relay system containing
the following modules: MID100
Multifunction Module with functions: MGC
46 Negative Sequence
49C Thermal Image
51 Definite Time Overcurrent
51GN Neutral Ground Overcurrent
51VC Voltage-controlled Overcurrent Modules MIC7/TOV4

Options
1 27 Undervoltage Module (into MID100 system) TOV5
1 32 Reverse Power Module (into MID100 system) TCW
1 81L/H Under/Overfrequency Module (into MID100 system) MFF
(For additional options, see GEN1 package)
s

Qty. Device No. Description GE Model No.


Device list for GEN 2
12 Overspeed
24 Overexcitation, Volts/Hz

27 Undervoltage
50/27 Inadvertent generator energization
32 Reverse power for anti-motoring
38 Bearing overtemperature
39 Bearing vibration (analog inputs)
40Q Loss of field
46 Negative Sequence Overcurrent(I2
2t)
47 Voltage phase reversal
49 Stator thermal (RTD and thermal
model)
50BF Breaker failure detection
50S Instantaneous overcurrent
(during startup)
50/51GN Instantaneous or definite time overcurrent
51V Voltage restrained phase overcurrent
59 Overvoltage
59GN/ 100% stator ground
27TN
60FL VT fuse failure detection
81 Over and underfrequency
87G Phase differential
86G Lockout Auxiliary

Protective Zone (GEN2)


Recommended protection for a small machine with low/high resistance grounding:

GENG E N E R A T O R
12
52

2 (or 3)

1
PROBE

50/51GN

3
1

59GN
Output
relays
RTD
RTD
GEN

BUS
1

Basic Package
1 Multifunction microprocessor-based protection SR489
including the following functions:
12 Overspeed
24 Overexcitation, Volts/Hz
27 Undervoltage
50/27 Inadvertent generator energization
32 Reverse power for anti-motoring
38 Bearing overtemperature
39 Bearing vibration (analog inputs)
40Q Loss of field
46 Negative Sequence Overcurrent (I2
2t)
47 Voltage phase reversal
49 Stator thermal (RTD and thermal model)
50BF Breaker failure detection
50S Instantaneous overcurrent (during startup)
50/51GN Instantaneous or definite time overcurrent
51V Voltage restrained phase overcurrent
59 Overvoltage
59GN/27TN 100% stator ground
60FL VT fuse failure detection
81 Over and underfrequency
87G Phase differential
Sequential tripping logic
Trip coil supervision

Options
1 86G Lockout Relay HEA61
(For additional options, see GEN1 package)
27
47
59
32
24
46
49
50S
49
38
12
27TN

50BF
Output
relays
6
86G
81O
81U
40Q
50/27
51V
60FL
87G
s

Qty. Device No. Description GE Model No.

Protective Zone (GEN3)


Minimum protection for a large machine with high resistance grounding:

GENG E N E R A T O R
** If no external fault source exists,
exchange connections of protection
from line side CT's to neutral side
CT's and vice versa.

Device list for GEN 3


21G Distance
21GX Aux to 21G
24 Overexcitation
27 Undervoltage
27TN Undervoltage (Third Harmonic)
32 Power Direction
40 Loss of Excitation
46 Current Unbalance
49R Overload (RTD)
51GN Time Overcurrent (Ground)
51V Time Overcurrent (V Restraint)
59 Overvoltage
60V Voltage Balance
64F Ground (field)
64G Ground (stator)
78 Out-of-step
81L/H Frequency
86G Lockout Auxiliary
87G Differential
13

Basic Package
1 Multifunction microprocessor-based relay system DGP--BA 0005
including the following functions:
21GX Timing auxiliary to 21G
24 Overexcitation
27 Undervoltage
27TN Third Harmonic Undervoltage
32 Reverse Power (1 step)
40 Loss-of-excitation
46 Current Unbalance (negative sequence)
51GN Ground Overcurrent (backup to 64G)
51V Voltage-restrained overcurrent
59 Overvoltage
60V VT Fuse Failure Detection
64G Stator Ground (95%)
81L/H Under/Overfrequency (2 setpoints each)
87G Percentage current differential
Accidental energization protection
Trip circuit monitoring
Personal computer communications interface,
event time tagging, fault data capture
Oscillography capture, time standard I/F
1 86G Lockout Auxiliary Relay HEA61

Options
1 21G System Backup Distance Relay (in place of 51V) SLY92/SLY82
1 49R Stator Overtemperature Relay (RTD) IRT51E
1 60V2 Voltage Balance Relay CFVB11

1 64F Field Ground Relay PJG12


1 78 Out-of-step Relay OST1000
(For additional options see GEN1 Options)
BUS
52

81L/H
27
24 32
40
59
46
51V
86G
51GN
RES 64G1
1
3**
3 21G 78
60V2

GEN
3** RTD
49R

3 (or 2)

3 (or 2)
TO
VOLT
REG

87G

64F
1 41
FIELD

60V
1
27TN
21GX
s
s

Qty. Device No. Description GE Model No.


Device list for GEN 4
21G Distance
21GX Aux to 21G
24 Overexcitation
27 Undervoltage
27TN Undervoltage (Third Harmonic)
32 Power Direction

40 Loss of Excitation
46 Current Unbalance
49R Overload (RTD)
51GN Time Overcurrent (Ground)
51V Time Overcurrent (V Restraint)
59 Overvoltage
60V Voltage Balance
64F Ground (field)
64G Ground (stator)
78 Out-of-step
81L/H Frequency
86G Lockout Auxiliary
87G Differential

GENG E N E R A T O R
Protective Zone (GEN4)
Recommended protection for a more important large machine with high resistance
grounding:
** If no external fault source exists,
exchange connections of protection
from line side CT's to neutral side
CT's and vice versa.

14

Basic Package
1 Multifunction microprocessor-based protection DGP--CA
relay including the following functions:
24 Overexcitation
27 Undervoltage Relay
27TN Third Harmonic Undervoltage
21GX Timing Auxiliary to External 21G
32 Reverse Power (2 steps)
40 Loss-of-excitation
46 Current Unbalance (negative sequence)
51GN Ground Overcurrent Relay
51V Voltage-restrained overcurrent
59 Overvoltage
60V VT Fuse Failure Detection
64G Stator Ground (100%) (Requires (3) main vts connected wye)
81L/H Under/Overfrequency (4/2 setpoints)
87G Percentage current differential
Accidental energization protection
Trip circuit monitoring
Personal computer communications interface,
event time tagging, fault data capture
Oscillography capture, printer I/F, time standard I/F
1 86G Lockout Auxiliary Relay HEA61
(For options see GEN1 and GEN3 Options)
BUS
52


81L/H
59
24 32
40
46
51V
86G
RES 64G1
1
3**
3 21G 78
60V2

GEN
3**
RTD
49R

3 (or 2)

3 (or 2)
TO
VOLT
REG

64F
1 41
FIELD

64G2
60V
87G
27
51GN
1
21GX
27TN
s
s

Qty. Device No. Description GE Model No.


15

Protective Zone (MTR1)


Minimum protection for a small induction motor (below 1500HP):

MTRM O T O R
BUS
M
3
1 50GS
49/50 49S/50
62 60V 27 47
CONTROL

PACKAGE

49R
50/51

Device list for MTR1


27 Time Undervoltage
47 Undervoltage and reverse
phase sequence
48 Incomplete sequence timer
49/50 Thermal overcurrent
49R Winding overtemperature (RTD)
49S/50 Time and instantaneous
overcurrent (locked rotor)
50GS Instantaneous overcurrent ground
50/51 Time and instantaneous
overcurrent
60V Voltage unbalance
62 Timer
48
RTD or Thermistor

Basic Package (Multiphase Overcurrent)


1 27 Undervoltage Relay IAV54E or TOV5
1 50/51/50GS Overload, Short Circuit and Ground Fault Relay MDP0 or 735

First Alternate Package (Single Phase Overcurrent)


1 27 Undervoltage Relay IAV54E or TOV5
3 50/51 Overload and Short Circuit Relay IFC66B or DIFC
1 50GS Ground Fault Relay HFC21 or DIFC

Second Alternate Package (Multiphase Overload)


1 27 Undervoltage Relay IAV54E or TOV5
1 Microprocessor-based Motor Relay including the following functions: P4A
46 Unbalance or Current-Reversal
49 Overload
49R Winding Overtemperature
50GS Ground Fault
66 Successive Starts Protection

Options
1 38 Bearing Overtemperature Relay (RTD) IRT51E
1 47 Three-phase Undervoltage and Reverse Phase Sequence ICR
Relay (in place of 27)
(Requires open-delta or wye-wye voltage transformers)
1 48 Adjustable Time Delay Relay or Timer
1 49R Winding Overtemperature Relay IRT51E
1 49S/50 Stalled Rotor Relay IFC66K
1 60V Voltage Unbalance Relay NBV11
(use with 62 and may require harmonic filter)
1 62 Timing Auxiliary Relay SAM201
s

Qty. Device No. Description GE Model No.


16

Protective Zone (MTR1A)


Recommended protection for a more important small inductions motor (below 1500 HP):

MTRM O T O R
Device list for MTR1A
27 Undervoltage
37 Undercurrent
38 Bearing Overtemperature (RTD)
46 Unbalance or current-reversal
47 Three phase undervoltage and
reverse phase sequence
48 Adjustable definite time device
or timer
49 Overload
49R Winding Overtemperature
(Thermistor or RTD)
49S Locked rotor
50 Short circuit
50GS Ground fault
60V Voltage unbalance
62 Timer
66 Successive starts
87M Differential
86,86M Lockout Auxiliary

Basic Package
1 Microprocessor-based Motor Relay including the
following functions: 239 or MMC
37 Undercurrent
38 Bearing Overtemperature (239 only)
46 Unbalance or Current-Reversal
49 Overload
49R Winding Overtemperature (Thermistor or RTD) (239 only)
49S Locked Rotor
50 Short Circuit
50GS Ground Fault
66 Successive Starts
86 Lockout Relay (239 only)
1 27 Undervoltage Relay TOV5

Options
1 86M Lockout Auxiliary Relay HEA61
1 87M Self-balance Differential Relay HFC23
(Add if required and if possible to mount three 50/5A
current transformers at the motor.)
or Percentage Differential Relay CFD22A or DTP1
(Add if required. See MTR2 figure for one-line representation)
(For additional options see MTR1)
BUS
48
62 60V
CONTROL
PACKAGE

47 27
86M 87M
3

3
49/
49S/50 37 46 66

1 50GS 49R 86 38
(3)
RTD (option) or
Thermistor
TRIP
s
s

Qty. Device No. Description GE Model No.


17

MTRM O T O R

3
87M M
86M

CONTROL
PACKAGE
3
49R

1 50GS/
51GS

3 49/49S 50/51
86
37 46
48/66
BUS

27/59 47

Protective Zone (MTR2)


Minimum protection for a large induction motor (1500 HP and above):
38
(10)
RTD TRIP

Device list for MTR2


27/59 Under and overvoltage
37 Undercurrent
38 Bearing Overtemperature (RTD)
46 Current unbalance
47 Undervoltage/reverse phase
sequence
48 Incomplete sequence
49 Overload
49R Winding overtemperature (RTD)
49S Locked rotor protection
50/51 Instantaneous & time overcurrent

50GS/ Instantaneous & time overcurrent


51GS ground sensor
66 Successive starts
86,86M Lockout Auxiliary
87M Differential

Basic Package
1 Digital Motor Relay including the following functions: 269 Plus
27 Undervoltage (Meter Option)
37 Undercurrent
38 Bearing Overtemperature (RTD)
46 Current Unbalance
47 Voltage Phase Loss/Sequence (Meter Option)
48 Incomplete Sequence
49R Winding Overtemperature
49S Locked Rotor
49/51 Overload
50GS/51GS Ground Fault
51R Jam (Running)
59 Overvoltage (Meter Option)
66 Successive Starts
86 Lockout Relay
1 87M Differential Relay CFD22A
or DTP1
1 86M Lockout Auxiliary Relay HEA61

Options
(See options for MTR1 and MTR1A)
s

Qty. Device No. Description GE Model No.


18

MTRM O T O R
Protective Zone (MTR2A)
Recommended protection for a more important large induction motor (1500 HP and
above):

CONTROL
PACKAGE
3

1 50GS/
51GS

3 49/49S 50/51
48/66
BUS

27/59 47
Motor
37
26
46
49R

10
RTD

Device list for MTR2A


27/59 Under and overvoltage
37 Undercurrent
46 Current unbalance
47 Undervoltage/reverse phase
sequence
48 Incomplete sequence
49 Overload
49R Winding overtemperature (RTD)
49S Locked rotor
50/51 Instantaneous and time overcurrent
50GS/ Instantaneous and time overcurrent
51GS ground sensor
66 Successive starts
81L/H Frequency
86M Lockout Auxiliary
87M Differential
81L/H
38
87M
86M

Basic Package
1 Digital Motor Relay including the following functions: 469
27 Undervoltage
37 Undercurrent
38 Bearing Overtemperature (RTD)
46 Current Unbalance
47 Voltage Phase Loss/Sequence
48 Incomplete Sequence
49R Winding Overtemperature
49S(26) Locked Rotor
49/51 Overload
50 Short Circuit
50GS/51GS Ground Fault
51R Jam (Running)
59 Overvoltage
66 Successive Starts
81L/H Under-and Overfrequency
87M Self-Balance Differential (for connections see MTR1A figure)
1 86M Lock-out Auxiliary Relay HEA61

Options
1 87M Differential Relay CFD22A
or DTP1
(See options for MTR1, and MTR1A)
s

Qty. Device No. Description GE Model No.


Device list for MTR3
26F Winding Overtemperature
27DC Undervoltage
37 Undercurrent
48 Incomplete sequence
50 Instantaneous overcurrent
55 Power factor
95 Reluctance Torque Sync/Re-Sync
19

MTRM O T O R
Basic Package
1 Microprocessor-based Synchronous Motor Relay including SPM
the following functions:
26F Ammortisseur Winding Overtemperature
(Include if field is accessible)
27DC Undervoltage Relay
37 Undercurrent
50 Short Circuit
55 Out of Step Protection/Power Factor
95 Reluctance Torque Synchronizing and Re-Synchronizing
96 Autoloading/Unloading Relay
BUS
CONTROL
PACKAGE

3 50 55
48
26F 37
27DC 95
Idc
Vdc

MOTOR
FIELD

Protective Zone (MTR3)


Recommended protection for a synchronous motor in addition to that provided in
preceding zones MTR1 through MTR2A:
s

Qty. Device No. Description GE Model No.


20

FDRF E E D E R
Protective Zone (FDR1)
Standard Non-directional circuit, residually connected ground relay:
Device list for FDR1
50/51 Phase overcurrent and short
circuit
51N Time delay ground fault
50N Instantaneous ground fault
BUS
52

3 50/51
LOAD
50N
51N

Basic Package

1 50/51/ Phase Overcurrent, Short Circuit and Ground Fault Relay MDP or SR735
51N or 50N

Alternate Package (Single Phase Units)


3 50/51 Phase Overcurrent & Short Circuit Relay DIFC or IFC53B
1 51N Time Delay Ground Fault Relay DIFC or IFC53A
or 50N Instantaneous Ground Fault Relay DIFC or HFC21

Second Alternate Package


1 Multifunction microprocessor-based relay system DFP100 or DFP200
including the following functions: or SR750
27 Undervoltage
46 Negative Sequence Overcurrent (DFP100 & 200 only)
47 Negative Sequence Voltage (SR750 only)
51 Phase Overcurrent
51N Residual Overcurrent
59 Overvoltage
74LM High Impedance Ground (DFP200 only)
79 Recloser
81L/H Frequency

Options
1 79 Recloser Relay SLR12

Qty. Device No. Description GE Model No.


21

FDRF E E D E R
Protective Zone (FDR2)
Standard Non-directional circuit, with ground sensor relay:
BUS
52
LOAD

3 50/51

1
51GS
50GS

Device list for FDR2


50/51 Phase overcurrent and short
circuit
50GS Instantaneous ground fault
51GS Time delay ground fault

Basic Package
1 50/51/ Phase Overcurrent, Short Circuit and Ground Fault Relay MDP / SR735
51GS or 50GS

Alternate Package (Single Phase Units)


3 50/51 Phase Overcurrent & Short Circuit Relay IFC53B / DIFCA
1 51GS Time Delay Ground Fault Relay IFC53A / DIFCA
or 50GS Instantaneous Ground Fault Relay HFC21

Second Alternate Package


1 Multifunction microprocessor-based relay system DFP100 or DFP200
including the following functions: or SR750
27 Undervoltage
46 Negative Sequence Overcurrent (DFP100 & 200 only)

47 Negative Sequence Voltage (SR750 only)


51 Phase Overcurrent
51N Residual Overcurrent
59 Overvoltage
74LM High Impedance Ground (DFP200 only)
79 Recloser
81L/H Frequency

Options
1 79 Recloser Relay SLR12

Qty. Device No. Description GE Model No.


22

FDRF E E D E R
Protective Zone (FDR3)
Standard Directional circuit:
BUS
52

3 67 67N
LINE/LOAD
TRIP
DIRECTION

Device list for FDR3


67 Directional overcurrent
and short circuit
67N Directional time delay and
instantaneous ground fault

Basic Package
1 67/67N Directional Phase and Ground Fault Relay DFP100 or
(Optional recloser 79 function is included). SR750 / SR760

Alternate Package (Single Phase Units)


3 67 Directional Overcurrent Relay IBC53 or JBC53
1 67N Directional Ground Fault Relay IBCG53 or JBCG53

Options
1 79 Recloser Relay SLR12
s

Qty. Device No. Description GE Model No.


23

FDRF E E D E R
Protective Zone (FDR4)
Long lines and critical short length lines:

BKR 52
52
87L
PILOT WIRE
86L
86L

3
3
LINE

Device list for FDR4


87L Pilot wire line
86L Lockout auxiliary
87L

Basic Package
2 87L Pilot Wire Line Differential Relay SPD11
2 86L Lockout Auxiliary Relay HEA61

Options
1 85LM Pilot Wire Monitor Relay (sending end) SPA11
1 85LM Pilot Wire Monitor Relay (receiving end) SPA12

Alternate Package
2 87L Current Differential Relay DLS3
2 86L Lockout Auxiliary Relay HEA61
s
s

Qty. Device No. Description GE Model No.


24

Protective Zone (TR1)


Protection for transformers 2500KVA and below, medium and low voltage windings:

TRTRANSFORMER
52

1
50/51
50GS
52

M.V.
L.V.

Device list for TR1


50/51 Overcurrent & short circuit
50GS Ground fault

Basic Package
1 50/51/50GS Overcurrent, Short Circuit and Ground Fault Relay MDP or SR735

Alternate Package (Single Phase Units)


3 50/51 Overcurrent and Short Circuit Relay DIFC or IFC53B
1 50GS Ground Fault Relay DIFC or HFC21

Second Alternate Package


1 Multifunction microprocessor-based relay system DFP100 or DFP200

including the following functions: or SR750


27 Undervoltage
46 Negative Sequence Overcurrent (DFP100 & 200 only)
47 Negative Sequence Voltage (SR750 only)
51 Phase Overcurrent
51N Residual Overcurrent
59 Overvoltage
74LM High Impedance Ground (DFP200 only)
81L/H Frequency

Qty. Device No. Description GE Model No.


25

TR
Protective Zone (TR2)
Protection for transformers 750kVa and above, medium voltage windings:

TRANSFORMER
52

1
50/51
50GS

63X
52
3

3
M.V.
M.V.
87T
86T
63

*INTEGRAL TO TRANSFORMER

Device list for TR2


87T Differential
86T Lockout auxiliary
50/51 Overcurrent & short circuit
50GS Ground fault
63 Integral fault pressure
63X Fault pressure auxiliary

Basic Package
1 87T Differential Relay DTP or SR745
63X Fault Pressure Auxiliary Relay
X 86T Lockout Auxiliary Relay (quantity as required) HEA61
1 50/51/50GS* Overcurrent, Short Circuit and Ground Fault Relay MDP

Alternate Package (Single Phase Units)


3 87T Differential Relay STD15C or BDD15B
X 86T Lockout Auxiliary Relay (quantity as required) HEA61
3 50/51 Overcurrent and Short Circuit Relay IFC53B
1 50GS Ground Fault Relay HFC21
1 63X Fault Pressure Auxiliary Relay HAA16B
*Note: The SR745 relay includes these functions.
s

Qty. Device No. Description GE Model No.


26

TRTRANSFORMER
Additional Transformer Ground Protection
52

52

(other devices)
87N
51G

1
1 Aux. CT

Device list for Additional


Transformer Ground Protection
51G Time overcurrent
87N Ground differential

Alternate Package (Single Phase Units)


1 51G Time Overcurrent Relay DIFC or IFC53A
1 87N Ground Differential Relay IFD51D
*Note: The SR745 digital transformer relay includes 87N.
s
s

Qty. Device No. Description GE Model No.


27

Protective Zone (BUS1)


Single source, radial configuration:

BUSB U S
52
SOURCE

3
51 51N
52 52
BUS
FEEDER (FDR)
RELAY
PACKAGE
FEEDER (FDR)
RELAY
PACKAGE

Device list for BUS1


51 Phase overcurrent
51N Ground fault

Basic Package
1 51/51N Phase Overcurrent and Ground Fault Relay MDP or SR735

Alternate Package (Single Phase Units)


3 51 Phase Overcurrent Relay DIFC or IFC53A
1 51N Ground Fault Relay DIFC or IFC53A

Second Alternate Package


1 Multifunction microprocessor-based relay system DFP100 or DFP200
including the following functions: or SR750
27 Undervoltage
46 Negative Sequence Overcurrent (DFP100 & 200 only)
47 Negative Sequence Voltage (SR750 only)
51 Phase Overcurrent
51N Residual Overcurrent
59 Overvoltage
74LM High Impedance Ground (DFP200 only)
81L/H Frequency

Options
1 64 Ground Fault Relay (ungrounded systems) TCCV

Qty. Device No. Description GE Model No.


28

BUSB U S
Protective Zone (BUS2)
Multiple sources with bus tie breaker:
Device list for BUS2
51 Phase overcurrent
51N Ground fault
52 52 FEEDER (FDR)
RELAY
PACKAGE
FEEDER (FDR)
RELAY
PACKAGE
52
SOURCE
52
SOURCE


52
3
51
BUS
51N
51
51N

3
33

Basic Package
1 51/51N Phase Overcurrent and Ground Fault Relay MDP or SR735

Alternate Package (Single Phase Units)


3 51 Phase Overcurrent Relay DIFC or IFC53A
1 51N Ground Fault Relay DIFC or IFC53A

Second Alternate Package


1 Multifunction microprocessor-based relay system DFP100 or DFP200
including the following functions: or SR750
27 Undervoltage
46 Negative Sequence Overcurrent (DFP100 & 200 only)
47 Negative Sequence Voltage (SR750 only)
51 Phase Overcurrent
51N Residual Overcurrent
59 Overvoltage
74LM High Impedance Ground (DFP200 only)
81L/H Frequency

Options
1 64 Ground Fault Relay (ungrounded systems) TCCV

Qty. Device No. Description GE Model No.


29

BUSB U S
Protective Zone (BUS3)
Single or multiple sources, with or without bus tie breakers:
52 52
52

3
BUS
3
87B

Device list for BUS3


87B Differential

Basic Package
3 87B Differential Relay PVD21 or SBD11

Qty. Device No. Description GE Model No.


30

BUSB U S
Protective Zone (BUS4)
Multiple sources, bus tie breakers, multi-ratio CT's:
52 52

33
87B
52
BUS
52 52

33

33

Device list for BUS4


87B Differential

Basic Package
1 87B Differential Relay BUS1000

Qty. Device No. Description GE Model No.


31

Protective Zone (IL1)


Single source incoming line (no internal generation):

IL INCOMING LINE
52

3
51N
51

PLANT
MAIN BUS
TO UTILITY SOURCE
TO 87B

27 59 81L/H

Device list for IL1


27 Undervoltage
51 Phase overcurrent
51N Residual overcurrent
59 Overvoltage
81L/H Frequency

Basic Package
1 51/51N Phase Overcurrent and Ground Fault Relay MDP

First Alternate Package


1 51/51N Phase and Ground Overcurrent Relay with High DFM3
74LM Impedance Ground Fault Detection (Power Quality Option)

Second Alternate Package


1 Multifunction microprocessor-based relay system DFP100 or DFP200 or
including the following functions: SR750
27 Undervoltage
46 Negative Sequence Overcurrent (DFP100 & 200 only)
47 Negative Sequence Voltage (SR750 only)
51 Phase Overcurrent
51N Residual Overcurrent
59 Overvoltage
74LM High Impedance Ground (DFP200 only)
81L/H Frequency

Options (Single Phase Units)


4 51, 51N Phase/Ground Overcurrent Relays DIFC or IFC53A
1 27 Undervoltage Relay TOV or NGV
1 59 Overvoltage Relay TOV or NGV
1 81L/H Over and underfrequency Relay SFF202B or MFF1
(add if upstream auto-reclosing is a concern)
1 87B Differential Relay
(See Bus Protective Zone for Details)
s
s

Qty. Device No. Description GE Model No.


32

IL INCOMING LINE
Protective Zone (IL2)
Single source incoming line via utility transformer (no internal generation):
52

PLANT
MAIN BUS
TO 87B

60V 62
51
51G1 51G2

3 2 (or 3)

TO UTILITY SOURCE
TRANSFORMER
TO TRANSFORMER
NEUTRAL CT

Device list for IL2


51 Phase overcurrent

51G-1 Ground overcurrent


51G-2 Ground overcurrent
60V Voltage unbalance
62 Timer
TO 87T

Basic Package
1 51/51G Phase Overcurrent and Ground Fault (Bus) Relay MDP

First Alternate Package


1 51/51G/ Phase and Ground Overcurrent Relay with High DFM3
74LM Impedance Ground Fault Detection (Power Quality Option)

Second Alternate Package


1 Multifunction microprocessor-based relay system DFP100 or DFP200 or
including the following functions: SR750
27 Undervoltage
46 Negative Sequence Overcurrent (DFP 100 & 200 only)
47 Negative Sequence Voltage (SR750 only)
51 Phase Overcurrent
51N Residual Overcurrent
59 Overvoltage
74LM High Impedance Ground (DFP200 only)
81L/H Frequency

Options (Single Phase Units)


4 51, 51N Phase/Ground Overcurrent Relays DIFC or IFC53A
1 60V Voltage Unbalance Relay NBV11
(add if high side fusing could result in single phase of motors)
1 62 Timing Auxiliary Relay SAM201 or IAV51M
1 51G2 Ground Fault (transformer secondary) Relay DIFC or IFC53A
(add for two step trouble-shooting for transformer/bus grounds)
1 87B and Differential Relay
87T (See Bus and Transformer Protective Zones for Details)
(For additional options see IL1)
ss
s
s
s

Qty. Device No. Description GE Model No.


33

IL INCOMING LINE
Protective Zone (IL3)
Single source incoming line with internal generation:
52

PLANT
MAIN BUS
TO 87B

TO UTILITY SOURCE
51
51N 67N


87L 2 (or 3)
3
85
LM/TT

67

AUX PT
PILOT
WIRES
TO UTILITY
86L

Device list for IL3


51 Phase overcurrent
51N Residual overcurrent
67 Directional phase overcurrent
67N Directional ground overcurrent
85LM/TT Communication monitor
86L Lockout auxiliary
87L Differential

Basic Package
1 87L Pilot Wire Line Differential Relay SPD11*
1 86L Lockout Auxiliary Relay HEA61
1 67/67N Directional Phase and Ground Overcurrent Relay MOR3
1 51/51N Phase Overcurrent and Ground Fault Relay MDP

Alternates
1 87L/85LM/ Line Differential & Channel Monitor & Transfer DLS3*
85TT Trip Auxiliary Relay
3 67 Directional Phase Overcurrent Relay (Single Phase Units) IBC53 or JBC53
1 67N Directional Ground Overcurrent Relay (Single Phase Units) IBCG53 or JBCG53
4 51, 51N Phase/Ground Overcurrent Relays (Single Phase Units) DIFC or IFC53A

Options
1 85LM Pilot Wire Monitor [different device at send SPA11A or 12A*
and receive ends] Relay
1 85LM/TT Pilot Wire Monitor and Transfer Trip Auxiliary Relay SPA11B or 12B*
[different device at send and receive ends]
1 87B Differential Relay
(See Bus Protective Zones for Details)
(For additional alternates and options see IL1 and IL2)
Notes: *Must be selected in accordance with companion relay at opposite
end of the line. Pilot wire protective auxiliaries may be required.
s
s
s
s

Qty. Device No. Description GE Model No.


34

IL INCOMING LINE
Protective Zone (IL4)
Dual source incoming line (dual line with internal generation & via utility transformer):
Device list for IL4

27L Undervoltage
32 Power direction
47 Phase undervoltage and
reverse phase sequence
50L Instantaneous overcurrent
51B Phase time overcurrent
51BN Residual time overcurrent
51G Ground overcurrent
59B Overvoltage
59L Overvoltage
62 Timer
67 Directional phase overcurrent
67N Directional ground overcurrent
81L/H Frequency

3
3

TO 87B1
TO UTILITY SOURCE
(XFMR T1)
52
2 (or 3)

3
67 32 62
67N
51G

47 59B 81L/H
3
TO 87T1
TO MAIN
BKR 2

87B1
51BN
50L
27L
TO CTs ON
XFMR 'T1'
HIGH SIDE
59L
TO L-N VT ON XFMR 'T1'
HIGH SIDE
MAIN 1
TRIP
DIRECTION
FOR 67, 67N, 32
PLANT
MAIN BUS
52
TIE

33
51B

Basic Package
1 67/67N Directional Phase and Ground Overcurrent Relay MOR3
1 51B/51BN Phase Overcurrent (Partial Differential) and MDP

Ground Fault Relay


1 51G Ground Overcurrent (for transformer lowside) Relay DIFC

Options
1 27L Line Undervoltage (transformer highside) Relay TOV5 or NGV
1 59L Line Overvoltage (transformer highside) Relay TOV5 or NGV
(Add 27L & 59L as a means of detecting Delta-Wye
transformer highside ground fault after utility separation.)
1 32 Power Directional Relay (detects transf. magnetizing current) CCP13E
1 62 Auxiliary Timing Relay SAM201
(add 32 & 62 in lieu of 27L and 59L as alternate means of
detecting system ground faults)
1 47 Phase Undervoltage and Reverse Phase Sequence Relay ICR53A
(add if required for motor bus monitoring or intertie)
1 59B Bus Overvoltage Relay (add if required for intertie) TOV5 or NGV
1 81L/H Over and Underfrequency Relay SFF202B
(add for intertie or load shedding requirements) or MFF1
1 50L Instantaneous Overcurrent Relay PJC11AV or
(add if highside disconnect is not rated for fault interruption) CHC11A
1 87B and 87T Differential Relay
(See Bus and Transformer Protective Zones for Details)
(For additional alternates and options see IL1 and IL2)
s
s
s
s
s
s
s
s
s
s

35
239 Small HP MV motor management relay 49/50/51(+)
269 PLUS Medium HP MV motor management relay 87(+)
469 Large HP MV motor management relay with metering 87(+)
489 Small/medium size generator relay 87(+)
735/737 3 phase + ground feeder relay 50/51
745 Transformer management relay 87(+)
750/760 Multifunction feeder relay 50/51(+)
ALPS High speed distance relay 21(+)
BDD Transformer differential, harmonic restraint 87
BUS1000 Bus protection relay 87
CAP Power directional 32
CCP Power directional 32
CEB Phase offset MHO distance 21, 68
CEH Loss of excitation 40
CEX57 Angle impedance 78
CEY Phase MHO distance 21
CEY-IAC Phase distance overcurrent 21/50/51
CEYG Ground MHO distance 21N
CFD Machine differential 87
CFV Instantaneous overvoltage 59
CFVB Voltage balance 60
CHC Instantaneous overcurrent 50
CJCG Ground directional overcurrent 67
CLPG Carrier ground 67
DAR Reclosing 79
DBF Breaker failure relay 50BF
DBT Breaker coil/tripping circuit supervision relay 74
DDS Digital distribution system 50/51(+)
DFF Frequency relay 81
DFM Feeder monitor + hi impedance ground 51/51G/74
DFP100 Multifunction feeder relay with reclose 50/51(+)
DFP200 Multifunction feeder + hi impedance ground 50/51/74(+)
DGP Generator protection 87(+)
DIAC Time overcurrent relay 51, 50/51
DIFC Time overcurrent relay 51, 50/51
DLP Distance relay 21(+)
DLS Current differential line protection 87(+)

DSFC Time overcurrent relay 51, 50/51


DTP Transformer protection relay 87
GCX Phase reactance distance 21
GCY Phase MHO distance 21
GGP Sensitive power directional 32
GSY Generator out-of-step 78
GXS Auto sync/sync check 25
HAA Annunciator auxiliary 30, 74
HEA Auxiliary lockout 86
HFA Multicontact auxiliary 86, 94
HFC Instantaneous overcurrent 50
HGA Contact auxiliary 27, 74, 94
HGA18 Reclosing 79
HMA Contact auxiliary 27, 74, 94
HSA Auxiliary lockout 86
IAC Time overcurrent 51, 50/51
IAV Time over/under voltage 27, 59, 64
IBC Phase directional overcurrent 67
IBCG Ground directional overcurrent 67N
ICR Undervoltage and phase sequence 47
ICW Time over/underpower 32, 37
IFC Time overcurrent 51, 50/51
IFCS Time overcurrent with voltage control 51
IFCV Time overcurrent with voltage restraint 51V

RELAY INDEX
IFD Transformer differential 87
IFV Time overvoltage 59, 64
IJC Current balance 46
IJD Machine differential 87
IJF Over/under frequency 81
IJS Synchronism check 25
IRT Temperature 38, 49
JBC Phase directional overcurrent 67
JBCG Ground directional overcurrent 67N
JBCV Directional overcurrent, voltage restraint 67
LPS Distance relay 21(+)
MCP Capacitor bank protection 50/51(+)
MDP 3 phase + ground feeder relay 50/51
MFF Over/under frequency 81
MGC Small generator protection 46, 49, 51
MIC Overcurrent 50/51
MLJ Synchrocheck 25
MLP Three pole tripping distance relay 21
MMC Small motor protection 49/50(+)
MOR Directional overcurrent with reclosing 50/51/79
MRC Thermal image 49, 50/51
MRS Transmission line reclosing 79
NAA Pilot/distance auxiliary 78, 85
NBT Breaker trip supervisor 74
NBV Voltage balance 47, 60
NGA Contact auxiliary 94
NGV Instantaneous under/over voltage 27, 59
NLR Multi-shot reclosing 79
NSR Single-shot reclosing 79
OST Out-of-step protection 78
PJC Instantaneous overcurrent 37, 50, 76
PJG Machine field ground 64
PJV Over/under voltage 27, 59
PLS Polyphase transmission line protection system 21(+)
PVD Bus differential 67
SAM Time delay 2
SBA Breaker auxiliary 94
SBC Breaker backup 50BF
SBD Bus differential 87
SCA Directional comparison, blocking auxiliary 85
SFF Over/underfrequency 81
SGC Negative sequence overcurrent 46
SLJ Synchronism check 25
SLR Multi-shot reclosing 79
SLV Over/under voltage 27, 59
SLY Phase distance 21, 68
SLYG Ground distance 21N, 68
SPA Pilot wire monitor 85
SPD AC pilot wire 87
SPM Synchronous motor controller 50/55/27(+)
STD Transformer differential 87
STV Overexcitation (V/Hz) 24
TCC Directional overcurrent 67
TCCV Ground fault 64

TCW Directional power 32


TLS Phase/zone transmission line protection system 21(+)
TOC Overcurrent 50/51
TOV Over/under voltage 27, 59
TRS Transmission line reclosing 79
TTS Transformer differential 87
TYS Phase/zone transmission line protection system 21(+)

MODEL DESCRIPTION DEVICE NO. MODEL DESCRIPTION DEVICE NO.

ANSI DEVICE NUMBERS/DESCRIPTION


2 Time-delay
21 Distance
25 Synchronism-check
27 Undervoltage
30 Annunciator
32 Directional power
37 Undercurrent or underpower
38 Bearing
40 Field
46 Reverse-phase
47 Phase-sequence voltage
49 Thermal
50 Instantaneous overcurrent
51 AC time overcurrent
59 Overvoltage
60 Voltage balance
63 Pressure
64 Apparatus ground
67 AC directional overcurrent
68 Blocking
69 Permissive
74 Alarm
76 DC overcurrent
78 Out-of-step
79 AC reclosing
81 Frequency
85 Carrier or pilot-wire
86 Lock out
87 Differential
94 Tripping

U.S. Standards
ANSI ANSI/IEEE Title
1. 100-1992 Standard Dictionary of Electrical and Electronic Terms
2. 375-1975 Graphic Symbols for Electrical and Electronic Diagrams
(R1989)
3. Y14.15-1996 Electrical and Electronics Diagrams
(R1988)
4. C37.2-1991 Electrical Power System Device Function
5. C37.90-1989 Relays and Relay Systems Associated with Electric
Power Apparatus
6. C37.95-1989 Guide for Protective Relaying of Utility-Consumer
Interconnections
7. 242-1986 Recommended Practice for Protection and Coordination
(R1991) of Industrial and Commercial Power Systems
European Standards
8. IEC-255 Protective Relay Standards
Codes
9. 1993 National Electrical Code NFPA Publication 1993
Books
10. Industrial Power Systems Handbook D.L. Beeman, Editor, McGraw-Hill Book Co., 1955
Standards may be purchased from:
American National Standards Institute, Inc.
11 West 42nd Street
New York, NY 10036
Institute of Electrical and Electronics Engineers, Inc.
Service Center
445 Hoes Lane
Piscataway, NJ 08855

National Fire Protection Association


1 Batterymarch Park
Quincy, MA 02269
Note: IEC Standards may be purchased from the American National Standards Institute.
36

REFERENCES

GE Power Management
GET-8048A
TCC/MPI - 01.98 - 1000

Relay Selection Guide

MULTILIN

UTILITY INDUSTRIAL EUROPE


GE Power Management GE Multilin GEPCE
205 Great Valley Parkway 215 Anderson Avenue Avenida Pinoa 10
Malvern, PA Markham, Ontario 48016 Zamudio Vizcaya
USA 19355 Canada L6E 1B3 Spain
Tel: (610) 251-7000 Tel: (905) 294-6222 Tel: +34-4-485-8800

http://www.ge.com/edc/pm

You might also like