ProSafe-RS
Vnet/IP
IM 32S56H10-21E
IM 32S56H10-21E
3rd Edition
Introduction
Vnet/IP is a network that conforms to the IEEE802.3 and TCP/IP communication standards.
The ProSafe-RS can configure a safety control system using Vnet/IP as its control bus.
This manual describes the network and engineering of Vnet/IP.
This manual provides information for systems consisting of ProSafe-RS alone or systems where
ProSafe-RS is integrated with CENTUM VP/CS 3000.
SEE
ALSO
If you integrate ProSafe-RS with FAST/TOOLS (Yokogawa SCADA system), read the following instead of this
manual.
4, Vnet/IP in FAST/TOOLS-Integrated Configuration in Integration with FAST/TOOLS (IM 32S56H20-21E)
IM 32S56H10-21E
ii
Engineering
Guide
IM 32S01S10-21E
IM 32S01C10-21E
Software
Safety Control Station
Reference
IM 32S03B10-21E
Integration with
CENTUM VP/CS 3000
Open Interfaces
IM 32S01E10-21E
IM 32S05B10-21E
Engineering
Reference
Utilities and
Maintenance
Reference
IM 32S04B20-21E
Messages
IM 32S02B10-21E
Integration with
FAST/TOOLS
IM 32S04B10-21E
ProSafe-RS
System Test
Reference
IM 32S04B30-21E
IM 32S56H20-21E
Hardware
Vnet/IP
Safety Control
Stations
(Hardware)
IM 32S06C10-21E
Communication
Devices
ProSafe-RS
Vnet/IP
IM 32S06H10-21E
IM 32S56H10-21E
Installation
Installation
Manual
Software Help
IM 32S01C50-21E
Read Me First
IM 32S56H10-21E
iii
Safety Precautions
n Safety, Protection, and Modification of the Product
In order to protect system controlled by this product, the product itself and ensure safe
operation, observe the safety precautions described in this users manual. We assume no
liability for safety if users fail to observe these instructions when operating the product.
You must use this product according to the instructions described in user manuals. If not,
protective functions of this product may not work as expected.
If any protection or safety circuit is required for system controlled by the product or for the
product itself, prepare it separately.
Be sure to use the parts approved by Yokogawa Electric Corporation (hereafter simply
referred to as YOKOGAWA) when replacing parts or consumables.
Modification of the product is strictly prohibited.
The following symbols are used on the product and in this user manual to indicate that
safety precautions are required:
Indicates that user must take caution. The symbol on the equipment refers the user to the
relevant manual to avoid potentially hazardous situations that may result in injury or death.
The symbol appears next to the cautionary information in user manuals required to avoid
harm to personnel and to the equipment.
Indicates a protective grounding terminal. Before using the product, ground the terminal.
Indicates a functional grounding terminal. Before using the product, ground the terminal.
Indicates an AC supply.
Indicates a DC supply.
IM 32S56H10-21E
iv
n Notes on Handling User Manuals
Please hand over user manuals to your end users so that they can have them on hand for
convenient reference.
Please read the user manuals thoroughly before using the product.
The purpose of these user manuals is not to warrant that the product is well suited to any
particular purpose but rather to describe the functional details of the product.
YOKOGAWA reserves the right to make improvements in the user manuals and product at
any time, without notice or obligation.
If you have any questions, or you find mistakes or omissions in the user manuals, please
contact our sales representative or your local distributor.
n Notes on Software
YOKOGAWA makes no warranties, either expressed or implied, with respect to the
softwares merchantability or suitability for any particular purpose, except as specified in the
terms of warranty.
This software may be used on one machine only. If you need to use the software on another
machine, you must purchase another copy of the software.
It is strictly prohibited to reproduce the product except for the purpose of backup.
Store the CD-ROM (the original medium) in a safe place.
It is strictly prohibited to perform any reverse-engineering operation, such as reverse
compilation or reverse assembling on the product.
No part of the product may be transferred, converted or sublet for use by any third party,
without prior written consent from YOKOGAWA.
IM 32S56H10-21E
Documentation Conventions
n Typographical Conventions
The following typographical conventions are used throughout the user manuals:
FIC100.SV=50.0
Mark:
Indicates a space between character strings that must be entered.
Example: Calling the tuning view with the tag name of S0001 on HIS (Human Interface Station of
the integrated CENTUM).
S0001TUN
IM 32S56H10-21E
vi
n Symbol Marks
Throughout this user manual, you will find that several types of symbols are used to identify
different sections of text. This section describes these icons.
CAUTION:
Indicates instructions that must be observed in order to prevent physical injury and death of
operator.
WARNING :
Indicates instructions that must be observed in order to prevent software or hardware from
being damaged or system from becoming faulty.
IMPORTANT :
TIP:
SEE :
ALSO
Clicking a reference displayed in green can call up its source, while clicking a reference
displayed in black cannot.
n Drawing Conventions
Some drawings in the user manual may be partially emphasized, simplified, or omitted, for the
convenience of description.
Note that screen images in user manuals may be slightly different from the actual ones (for
example, display positions and case differences), and some show only example images.
SEE
ALSO
For information about the functions and usage of CENTUM VP components, see CENTUM VP Users
Manuals (IM) and related Technical Information (TI) and General Specifications (GS).
For information about the functions and usage of CENTUM CS 3000 components, see CENTUM CS 3000
Users Manuals (IM) and related Technical Information (TI) and General Specifications (GS).
IM 32S56H10-21E
vii
n About Explanation of System Behavior
In this manual, system behavior is explained assuming the use of the latest software and
hardware that Yokogawa provides at the publication of the manual. Wherever a topic needs
explanation of earlier revisions of software or hardware, a link to the required explanation is
provided so that you can read them according to your system.
SCSP1-S :
SCSP2-S :
To explain the functions of these different types of SCS, the following generic terms or
abbreviations may be used in this manual.
SCS
SCSV
SCSP
SCSV1
SCSP1
SCSP2
IM 32S56H10-21E
viii
n Trademark Acknowledgments
CENTUM, ProSafe, Vnet/IP and STARDOM are registered trademarks of YOKOGAWA.
Microsoft, Windows, Windows Vista, Visual Basic, Visual C++ and Visual Studio are either
registered trademarks or trademarks of Microsoft Corporation in the United States and/or
other countries.
Adobe, Acrobat and Acrobat Reader are either registered trademarks or trademarks of
Adobe Systems Incorporated in the United States and/or other countries.
Ethernet is a registered trademark of XEROX Corporation.
Modicon and Modbus are registered trademarks of Schneider Electric SA.
PLC is a registered trademark of Rockwell Automation, Inc.
HART is a registered trademark of the HART Communication Foundation.
All other company and product names mentioned in this users manual are trademarks or
registered trademarks of their respective companies.
We do not use TM or mark to indicate those trademarks or registered trademarks used in
this users manual.
IM 32S56H10-21E
TocA-1
ProSafe-RS
Vnet/IP
IM 32S56H10-21E 3rd Edition
CONTENTS
PART-A
Vnet/IP Network
A1.
A2.
A3.
A4.
A2.1
A2.2
A3.2
A3.3
A3.4
A3.5
IM 32S56H10-21E
TocB-1
ProSafe-RS
Vnet/IP
IM 32S56H10-21E 3rd Edition
CONTENTS
PART-B
Engineering
B1.
Overview of Engineering........................................................................B1-1
B2.
Network Engineering..............................................................................B2-1
B2.1
B2.2
B2.3
B3.
B4.
Engineering on CENTUM........................................................................B4-1
B4.1
B4.2
B4.3
IM 32S56H10-21E
A1-1
IM 32S56H10-21E
A2-1
SENG
Exaopc
Vnet/IP
domain 3
Bus 1 side
Bus 1 side
L3SW
L3SW
SCSP
L2SW
L2SW
L2SW
L2SW
L2SW
L2SW
Vnet/IP
domain 1
Vnet/IP
domain 2
L3SW
Bus 2 side
Bus 2 side
L3SW
Router
FCS
V net router
V net domain 4
Bus 2 side
General-purpose
Ethernet device
Vnet/IP network
Intranet
SENG:
SCSP, SCSV:
V net router:
HIS:
FCS:
Exaopc:
L2SW:
L3SW:
SCSV
Safety engineering PC
Safety control station
Router that connects a V net domain with a Vnet/IP domain
CENTUM operation and monitoring station
CENTUM control station
OPC server
Layer 2 switch
Layer 3 switch
A020001E.ai
TIP
In this manual, the safety control station connected in a Vnet/IP network is referred to as SCSP, and the safety
control station connected in V net is referred to as SCSV.
IM 32S56H10-21E
A2-2
l Vnet/IP Station
A Vnet/IP station in a domain is connected to a Layer 2 switch in each bus. The Vnet/IP stations
are the following below. Stations of a CENTUM system on a Vnet/IP network are also the network
components for system configuration.
SENG
SENG is a Safety Engineering PC. It is a Vnet/IP station connected to the Vnet/IP network
through a VI702/VI701 card. The VI702/VI701 card contains two ports of connectors to
connect Vnet/IP communication cables to support duplexed Vnet/IP buses.
SCSP (SSC60S, SSC60D, SSC50S, SSC50D)
SCSP is a Safety Control Station connected on the Vnet/IP network. The transmission
speed of SCSP is 100Mbps.
V net Router (AVR10D)
A V net router is a device dedicated for connecting a Vnet/IP domain with a V net domain. It
performs the frame conversion and filtering between Vnet/IP and V net. The V net router is a
device of CENTUM system.
HIS
HIS is an Operation and monitoring station of CENTUM, in which, the CENTUM engineering
builders should be installed. If the V net routers are used in the system, the engineering
builders are required for engineering and maintenance for the V net routers. The HIS
hardware configuration is similar to SENG. Same as the V net router, the HIS is also a
station of CENTUM system.
SEE
ALSO
For more information about Vnet/IP stations of CENTUM system, see the following:
System Components of Vnet/IP Network in A1, Overview of Vnet/IP Network of the CS 3000 Vnet/IP
(IM 33Q06H90-31E).
System Components of Vnet/IP Network in A1, Overview of Vnet/IP Network of the CENTUM VP
Vnet/IP (IM 33L01A10-40E).
l Vnet/IP Domain
A Vnet/IP domain consists of two independent subnets of bus 1 and bus 2. Each domain can
have a maximum of 64 Vnet/IP stations and 124 general-purpose Ethernet devices (PCs,
routers, etc.).
If a safety system is integrated with a CENTUM system, the integrated system can have a
maximum of 16 Vnet/IP and V net domains.
l Layer 2 Switch
The Vnet/IP stations and general-purpose Ethernet devices in a domain are connected to the
Vnet/IP buses through the Layer 2 switches. At least two Layer 2 switches are required for bus1
and bus 2 respectively.
l Layer 3 Switch
Layer 3 switches are used to connect among Vnet/IP domains on each bus.
l Router
Routers with security capabilities are used for connecting bus 2 with external network such as
Intranet so as to ensure the security of the Vnet/IP network.
IM 32S56H10-21E
A2-3
IMPORTANT
Use a hub to adjust traffic of communication flow from general-purpose Ethernet devices
to a Vnet/IP network so as to prevent it from exceeding 300 Mbps (for example, up to three
100 Mbps ports).
On the Vnet/IP network, SCSP stations that are connected to general-purpose Ethernet
devices should use Layer 2 switches. The Layer 2 switches should be the intelligent
switches that can prevent the open communication multicasts from flowing into the SCSP
stations.
SEE
ALSO
For more information about selecting the Layer 2 switches for network configuration, see the Vnet/IP Network
Configuration Guide (TI 33P01B10-31E).
IM 32S56H10-21E
A2-4
This section explains a system configured solely with ProSafe-RS. In this type of system,
Vnet/IP network is used as the control network.
IMPORTANT
Under the following circumstances, the ProSafe-RS should be integrated with CENTUM system:
When ProSafe-RS stations on a V net domain are communicating with other ProSafe-RS
stations on a Vnet/IP domain through V net routers.
When ProSafe-RS stations on multiple Vnet/IP domains are communicating with each other
through Layer 3 switches.
IM 32S56H10-21E
A2-5
When integrated with CENTUM, a system configured by placing the SCSP stations and
an SENG on a Vnet/IP network; and placing the SCSV stations and an SENG on a V net
network
IMPORTANT
The inter-SCS safety communication between SCSP stations cannot be established if the two
stations located in two Vnet/IP domains are separated by a V net domain.
SEE
ALSO
IM 32S56H10-21E
A3-1
Bus 1
L2SW
L2SW
L2SW
L2SW
Bus 2
Vnet/IP domain
BCV
V net
domain
SCSP
L2SW
Vnet/IP
domain
Vnet/IP
domain
L2SW
L3SW
BCV:
L2SW:
L3SW:
Bus converter
Layer 2 switch
Layer 3 switch
A030001E.ai
IM 32S56H10-21E
A3-2
Devices in a Vnet/IP domain are connected in the star network using Layer 2 switches
of 1 Gbps as the key devices. Since the redundantly configured Vnet/IP buses are also
functioning as independent subnets of each bus, it is necessary to install a Layer 2 switch
for each bus.
IMPORTANT
Multiple stations are connected to Layer 2 switches. It is strongly recommended to protect Layer
2 switches with an uninterruptible power supply (UPS) so that Layer 2 switches will not stop due
to power failure.
If the Layer 2 switches stop due to power failure, there will be the following effects:
Communication error will occur.
For dual-redundant SCSP or FCS stations, when both buses fail, the controlling CPU will
also fails and the control will be switched to the standby CPU. Then the dual-redundant
stations will run in non-redundant mode.
If a Layer 2 switch is restarted by momentary power failure, it takes several seconds for the
communication with stations to recover.
Max. 7 levels
IMPORTANT
The connection between any two communicating stations should avoid multiple routes.
Otherwise, the communication may not be properly performed.
SCSP
SCSP
L2SW
L2SW
L2SW
A030101E.ai
IM 32S56H10-21E
TIP
A3-3
It is also possible to use a connection faster than 1 Gbps for the connection between Layer 2 switches.
For dual-redundantly configured stations such as SCSP stations or V net routers, though two CPU modules
are separately connected with UTP cables to Layer 2 switches, both CPU modules are counted as one
communication station or one communication device.
SENG
UTP cable
Max. 100 m
Bus 1 side
L2SW
L2SW
Bus 2 side
Optical fiber
cable
Max. 5 km
L2SW
L2SW
SCSP
L2SW:
Layer 2 switch
A030102E.ai
IM 32S56H10-21E
A3-4
A Layer 3 switch is required for the connection between Vnet/IP domains. Install a Layer 3
switch in each bus of dual-redundantly configured Vnet/IP buses and connect it to other
domains. By using a leased line as the transmission path, the domains can be connected
through the wide area networks.
IMPORTANT
The connection between any two communicating domains should avoid multiple routes.
Otherwise, the communication may not be properly performed.
Domain 1
L3SW
Domain 2
L3SW
Domain 3
L3SW
A030201E.ai
Domain 4
Bridge
Domain 1
L3SW
Bi-Directional
L3SW
Domain 2
Domain 5
L3SW
L3SW
Hierarchical
Domain 3
L3SW
Domain 6
L3SW:
Layer 3 switch
A030202E.ai
IM 32S56H10-21E
A3-5
l Bi-Directional Connection
This connection type does not differentiate the upper and lower relationships between Vnet/IP
domains. This type of connection can be established by setting the domain to receive HIS
messages, FCS messages and FCS TCP communication frames from other domains. Moreover,
when a domain is set to receive FCS messages, it can also receive SCS messages (such as
system alarm messages). If a domain is set to receive FCS TCP frames, it can also receive SCS
TCP communication frames. By the default settings on the Domain Properties dialog box, the
domain is set to receive all the transmissions.
l Hierarchical Connection
This connection type differentiates the upper and lower relationships between Vnet/IP domains.
This type of connection can be established by setting a lower domain not to receive HIS
messages, FCS messages and FCS TCP communication frames from upper domains; but all
the stations in the upper domains can receive HIS messages, FCS messages, and FCS TCP
communication frames from the lower domain. Moreover, when the domain is set to receive FCS
messages, it can also receive SCS messages (such as system alarm messages). If the domain
is set to receive FCS TCP frames, it can also receive the SCS TCP communication frames.
l Bridge Connection
This connection type guarantees the independence of a domain. It can be established by
setting the domain not to receive HIS messages, FCS messages and FCS TCP communication
frames from another domain and by setting the time group to 0 so as not to perform time
synchronization.
IMPORTANT
If the SENG and the SCSP stations are located in 2 different Vnet/IP domains, both domains
should be set to allow the reception of FCS TCP communication for engineering and
maintenance purpose.
When two SCSP stations in two domains are performing inter-SCS safety communication,
both domains should be set to allow the reception of FCS TCP communication.
When two SCS stations in two domains are performing inter-SCS safety communication
and one domain is a V net domain, both domains should be set to allow the reception of
FCS TCP communication. Moreover, the V net router, the bus converter (BCV) and the
communication gateway (CGW) should also be set to allow the reception of FCS TCP
communication.
SEE
ALSO
TIP
To access the tag names of function blocks or variables from the CENTUM stations across the domains is
possible regardless the type of connections.
When setting domain properties, it is also possible to set the domain to receive HIS messages only, FCS
messages only or FCS TCP communication only.
IM 32S56H10-21E
A3-6
A Vnet/IP domain can be connected with a V net domain via a V net router. When
integrated with CENTUM system, this type of connection can be applied.
SENG
Ethernet
HIS
Connect to bus 2
SENG
HIS
Vnet/IP
network
V net
V net router
SCSV
SCSP
FCS
FCS
A030301E.ai
IMPORTANT
Allocate only one path from a Vnet/IP network to a specific control bus domain via a V net router.
If a V net router is defined so that two or more paths exist as paths to a specific control domain,
the following problems will occur:
The path from the Vnet/IP side to the corresponding V net domain changes randomly.
Communication frames to nonexistent domains converge depending on the definition of the
routing of the V net router.
If two Vnet/IP domains are separated by a V net domain, communication cannot be performed
between the two Vnet/IP domains.
IM 32S56H10-21E
A3-7
L2SW
1 Level
L2SW
L2SW
L2SW
[GW 0 Level]
L2SW
Max. 7 Levels.
Max. 5km using
optic fiber cable
between L2SWs.
(The Max.
distance of the
two stations in
the same domain
is 40 km.)
Vnet/IP
domain
Vnet/IP
domain
L3SW
AVR
V net
Vnet/IP
domain
L3SW
[GW 0 Level]
BCV/
BCV/
CGW
L3SW
SCSP
SCSV
L2SW:
L3SW:
AVR:
BCV:
CGW:
V net
BCV/
CGW
L3SW Max.
Vnet/IP
15 Levels.
[GW 1 Level]
V net
domain
(The transmission
delay between
any two stations
is less than 250 ms.)
[GW 2 Level]
Between Vnet/IP domains.
[GW 0 Level]
BCV/CGW
Max. 2
Levels.
(Not counting
the Vnet/IP
and AVR
levels.)
Layer 2 switch
Layer 3 switch
V net router
Bus converter
Communication gateway unit
A030302E.ai
IM 32S56H10-21E
A3-8
V net
BCV/
CGW
V net
BCV/
CGW
[GW 0 Level]
AVR
V net
[GW 1 Level]
V net
BCV/
CGW
Vnet/IP domain
AVR
AVR
Vnet/IP domain
[GW 0 Level]
V net
V net
AVR
BCV/
CGW
AVR
[GW 2 Level]
V net
[GW 1 Level]
Vnet/IP domain
BCV/
CGW
AVR
V net
[GW 2 Level]
[GW 2 Level]
SCSP
SCSV
AVR :
BCV :
CGW:
[GW 0 Level]
[GW 1 Level]
V net
[GW 2 Level]
V net
[GW 1 Level]
BCV/CGW Max.
2 Levels.
(Not counting
the Vnet/IP and
AVR levels.
BCV/
CGW
V net
[GW 2 Level]
V net router
Bus converter
Communication gateway unit
A030303E.ai
SEE
ALSO
For more information about the number of levels of bus converters that connect other control buses, see the
following:
L1.1, Outline of Bus Converter for V net in Communication Devices of CS 3000 Reference (IM 33S01B3001E)
L1.1, Outline of Bus Converter for V net in Communication Devices of CENTUM VP Reference (IM
33M01A30-40E)
IM 32S56H10-21E
A3-9
IMPORTANT
Same as the general transmission delay between any two Vnet/IP domains, the
transmission delay here should also be less than 250 ms.
If inter-SCS safety communications are performed between domains connected over a
wide area, it is recommended that the public communication lines should be faster than
100Mbps.
HIS/SENG
SCSP
SCSV
Vnet/IP
domain A
V net
CGW
Router
CGW
Router
Vnet/IP
domain A
Router
Router
Router
Router
Router
Router
Router
Router
Vnet/IP
domain B
V net
SCSV
SCSP
HIS
Ethernet
Vnet/IP
domain B
V net
router
SCSP
SENG
V net
SCSV
SENG
A030401E.ai
IM 32S56H10-21E
A3-10
How to check the Vnet/IP bus status will be explained in this chapter.
Bus status of
other domains
Bus status in
own domain
Communication
status between
stations in
own domain
Communication
status of devices
connected
between domains
Communication
status between
stations in
other domains
A030501E.ai
IM 32S56H10-21E
A3-11
Including SENG, HIS and the non-redundant stations (such as SCS with single CPU module).
Based on this diagnostic information the communication statuses of all stations in a domain can
be displayed on the HIS Network Status Display dialog box.
SEE
ALSO
C2, Network Status Display Dialog Box in the CS 3000 Vnet/IP (IM 33Q06H90-31E)
C2, Network Status Display Dialog Box in the CENTUM VP Vnet/IP (IM 33L01A10-40E)
TIP
If both buses failed to communicate with a specific station, it will be indicated as the station failure, and the bus
status will not be indicated as abnormal.
IM 32S56H10-21E
A3-12
IM 32S56H10-21E
A4-1
Time group 1
SNTP server
HIS
SENG
Vnet/IP
domain 1
HIS
L3SW
L3SW
Vnet/IP
domain 2
SNTP server
Time accuracy in a
domain 1 ms
L3SW
L3SW
HIS
SENG
Vnet/IP
domain 3
L3SW
L3SW
SCSP
SCSP
SEE
ALSO
IM 32S56H10-21E
A4-2
In a domain
1 ms, When one bus is abnormal, the accuracy may become worse than 1 ms
due to heavy open communication traffic.
Among domains
5 ms, When one bus is abnormal, the accuracy may become worse than 5 ms
due to heavy open communication traffic.
The relative time accuracy deteriorates in proportion to transmission delay time
variations among domains.
The system software of a Vnet/IP station references the network time, and adjusts its own system
time according to the network time. Because of the differences in the time adjustment methods,
the deviations between the system time and the network time are as shown below:
Table
Time Adjustment
Max. 0.5 s
None
n Time Group
The time group denotes a range in which time synchronization is performed. The entire Vnet/IP
network can be defined on one time group. On the other hand, by separating domains in the
same Vnet/IP network into time groups, the range in which time synchronization is performed can
be limited.
Specify a time group using a number from 0 to 7. The default time group number is 1. To perform
time synchronization only in a domain, set the time group number to 0.
If an SNTP sever does not exist in a time group, one of Vnet/IP stations in a time group will act
as the time master station, and other stations in the same time group will synchronize with the
network time of the time master station.
SEE
ALSO
For more information about setting the domain properties, see the following:
For more information about time group and the inter-SCS safety communication, see the following:
Precaution for Engineering in 2.8, Inter-SCS Safety Communication in the Engineering Guide (IM
32S01C10-21E)
IM 32S56H10-21E
A4-3
n SNTP Server
To synchronize the network time of a Vnet/IP station with a standard time, connect an SNTP
server in each time group. Only one SNTP server can be connected to each bus within the same
time group. Generally, connect an SNTP server to bus 1 of Vnet/IP.
For the dual-redundant SNTP servers, one more SNTP server needs to be added and connected
to bus 2 of Vnet/IP. After connecting the SNTP server, the time master station in the Vnet/IP
network will synchronize the time according to the SNTP server on one bus. If the SNTP server
fails, the time synchronization will be performed with another SNTP server on the other bus.
IMPORTANT
After connecting an SNTP server in the time group if the SNTP server is not available for
synchronization, a notification will be broadcasted. Under this circumstance, all stations in the
time group will synchronize their time with the time master station of the time group. When
the SNTP server becomes ready for time synchronization, all stations in the time group will
synchronize their time with the SNTP server instead of the time master station.
192.168.<domain number>.254
Note that the configuration of SNTP server need not be performed from SENG or HIS. When
SNTP server is connected to the Vnet/IP network, the Vnet/IP stations will perform time
synchronization with the SNTP server automatically.
IM 32S56H10-21E
A4-4
SEE
ALSO
For more information about SOE in SCSP station, see the following:
A7, SOER in the Safety Control Station Reference (IM 32S03B10-21E)
For more information about SYS_NETST, see the following:
C10.4, SYS_NETST (Control Bus Status Indicator) in the Safety Control Station Reference (IM
32S03B10-21E)
For more information about SCS Constants builder, see the following:
3.1.3, SCS Constants Builder in the Engineering Reference (IM 32S04B10-21E)
IM 32S56H10-21E
A4-5
SEE
ALSO
For more information about setting V net router properties, see the following:
B2.5, Setting the V net Router in the CS 3000 Vnet/IP (IM 33Q06H90-31E)
B2.5, Setting the V net Router in the CENTUM VP Vnet/IP (IM 33L01A10-40E)
SEE
ALSO
For more information about setting V net router properties, see the following:
B2.5, Setting the V net Router in the CS 3000 Vnet/IP (IM 33Q06H90-31E)
B2.5, Setting the V net Router in the CENTUM VP Vnet/IP (IM 33L01A10-40E)
IM 32S56H10-21E
B1-1
SEE
ALSO
For more information about installation for creating Vnet/IP domains, see the following:
3.4, Installation and Setup of Vnet/IP in the Installation (IM 32S01C50-21E)
For more information about integration with CENTUM and installation for creating Vnet/IP domains, see the
following:
11, Installation and Setup of Vnet/IP in the CS 3000 Installation (IM 33Q01C10-01E)
SEE
ALSO
IM 32S56H10-21E
B2-1
IMPORTANT
For the SCSP stations on the Vnet/IP network that connected with general-purpose Ethernet
devices, SCSP stations should be connected on the Layer 2 switches and the Layer 2 switches
should be the intelligent switches that can prevent the open communication multicasts flow into
the SCSP stations.
SEE
ALSO
For more information about network configuration and Layer 2 switch, see the Vnet/IP Network Configuration
Guide (TI 33P01B10-31E).
IM 32S56H10-21E
B2-2
In this chapter, how to set the hardware addresses for Vnet/IP stations and the setting
items will be explained.
SEE
ALSO
For more information about the hardware setting, see the following chapters in the Safety Control Stations
(Hardware) (IM 32S06C10-21E)
4.2, Processor Module
6.7, Setting the Vnet/IP Interface Card Station Address
For more information about setting V net router, see the following:
Domain Number
The Vnet/IP domain number needs to be set within the range of 1 to 31 (When integrated with
CENTUM: 1 to 16). The domain numbers of the connected Vnet/IP network and V net network
should not be identical.
The domain number can be set by the DIP switch on the hardware.
Station Number
The Vnet/IP station number needs to be set within the range of 1 to 64. The station numbers in
the same domain should not be identical.
The station number can be set by the DIP switch on the hardware.
IM 32S56H10-21E
B2-3
The following two types of IP addresses should be set by the user for the stations
connected on the Vnet/IP network.
Open Communication IP Address
This is the IP address used for various standard protocols of Ethernet.
Control Bus TCP/IP Protocol IP Address
This is the IP address used exclusively for TCP/IP applications over control bus.
IMPORTANT
The IP address used by Vnet/IP device must not be identical with the IP address of other
communication device.
SEE
ALSO
For more information about setting SENG open communication IP address, see the following sections in the
Installation (IM 32S01C50-21E):
3.4.5 Setting Vnet/IP Network Connection (Windows Vista/Windows Server 2008)
3.4.6 Setting Vnet/IP Network Connection (Windows XP/Windows Server 2003)
IM 32S56H10-21E
TIP
B2-4
IP network address
Bus 1
Bus 2
Host Addresses
The host address for the control communication of Vnet/IP is determined by the station number, and 2 to
129 are used. Other host addresses are used for the following purposes:
1:
Reserved
130 to 253:
for open communications (On bus 2 only)
254:
for SNTP server
Example of Control Communication IP Addresses
An example of control communication IP addresses of SENG is described below.
These IP addresses will be automatically set in the SENG.
[Example]
For the SENG with domain number 1 and station number 64:
Network address of bus 1 = 192.168.<domain number>.0 = 192.168.1.0
Network address of bus 2 = 192.168.<128 + domain number>.0 = 192.168.129.0
The host address is determined by the following formula:
Host address = Station number x 2
Therefore, the host address is as follows:
Host address = 64 x 2 = 128
The IP addresses of the SENG for control communication are as follows:
IP address of bus 1 = 192.168.1.128
IP address of bus 2 = 192.168.129.128
IM 32S56H10-21E
B2-5
SEE
ALSO
For more information about setting SCS control bus TCP/IP protocol IP addresses, see the following:
n Setting an IP Address in 3.1.1, SCS Project Creation Procedure of the Engineering Reference (IM
32S04B10-21E)
For more information about setting SENG control bus TCP/IP protocol IP addresses, see the following
sections in the Installation (IM 32S01C50-21E):
3.4.5 Setting Vnet/IP Network Connection (Windows Vista/Windows Server 2008)
3.4.6 Setting Vnet/IP Network Connection (Windows XP/Windows Server 2003)
IMPORTANT
Do not change the setting of Control Bus TCP/IP Protocol in the Network tab of Vnet/IP Station
Properties when working on CENTUM engineering builders.
IM 32S56H10-21E
B2-6
This section describes the procedures and precautions that must be followed when you
add a station or a domain to an existing Vnet/IP network.
WARNING
Before you add a station, make sure that there are no duplicate station addresses.
Turn off the power of the additional station before you connect the cables.
l Case 1: When using existing Layer 2 switches (ports are available on existing
Layer 2 switches)
TIP
1.
In the Network Status Display dialog box on an HIS, check that both buses are normal.(*1)
2.
3.
Connect the BUS1 port of the additional station to the Layer 2 switch for BUS1 with a cable.
If the port on the Layer 2 switch is disabled, enable the port.
4.
In the Network Status Display dialog box, check that both buses are normal.(*1)
5.
Connect the BUS2 port of the additional station to the Layer 2 switch for BUS2 with a cable.
If the port on the Layer 2 switch is disabled, enable the port.
6.
In the Network Status Display dialog box, check that both buses are normal.(*1)
7.
8.
In the Network Status Display dialog box, check that both buses are normal.(*1)
*1:
In the case of a system consisting of only ProSafe-RS stations, use an SCS status display window (either SCS Status Overview
or SCS State Management) of SCS Maintenance Support Tool on an SENG to check the bus status. When you call up the SCS
status display window, select the project of a running SCS and then call up the window.
Alternatively, you can add a station to Layer 3 switches directly instead of Layer 2 switches.
IM 32S56H10-21E
B2-7
l Case 2: When you need to add Layer 2 switches (no ports are available on
existing Layer 2 switches)
Firstly, carry out steps 1 to 11 as shown below to add Layer 2 switches for BUS1 and BUS2.
Next, carry out the procedure for Case 1 above to add a station.
1.
In the Network Status Display dialog box on an HIS, check that both buses are normal.(*1)
2.
Disconnect the cable between any one of the existing stations and a Layer 2 switch for
BUS1.
3.
Connect the additional Layer 2 switch for BUS1 to the existing Layer 2 switch for BUS1 with
a cable.
4.
Turn on the power of the Layer 2 switch that you have added.
5.
Connect the existing station that you have disconnected at step 2 to the newly added Layer
2 switch for BUS1 with a cable.
6.
In the Network Status Display dialog box, check that both buses are normal.(*1)
7.
Disconnect the cable between any one of the existing stations and a Layer 2 switch for
BUS2.
8.
Connect the additional Layer 2 switch for BUS2 and the existing Layer 2 switch for BUS2
with a cable.
9.
Turn on the power of the Layer 2 switch that you have added.
10. Connect the existing station that you have disconnected at step 7 to the newly added Layer
2 switch for BUS2 with a cable.
11. In the Network Status Display dialog box, check that both buses are normal.(*1)
This completes the addition of Layer 2 switches.
Now, carry out the procedure for Case 1 to add a station.
*1:
In the case of a system consisting of only ProSafe-RS stations, use an SCS status display window (either SCS Status Overview
or SCS State Management) of SCS Maintenance Support Tool on an SENG to check the bus status. When you call up the SCS
status display window, select the project of a running SCS and then call up the window.
IM 32S56H10-21E
B2-8
WARNING
Make sure that there are no duplicate station addresses (domain number + station number) in
the system.
The procedures for two cases are provided below.
l Case 1: When using existing Layer 3 switches (ports are available on existing
Layer 3 switches)
Firstly, carry out steps 1 to 5 shown below to configure Layer 3 switches for BUS1 and BUS2.
Next, add stations by following the procedures in n Procedures and Precautions for Adding a
Vnet/IP Station.
1.
In the Network Status Display dialog box on an HIS, check that both buses are normal.(*1)
2.
Make the necessary settings on the existing Layer 3 switch for BUS1.
If the port on the Layer 3 switch is disabled, enable the port.
3.
In the Network Status Display dialog box, check that both buses are normal.(*1)
4.
Make the necessary settings on the existing Layer 3 switch for BUS2.
If the port on the Layer 3 switch is disabled, enable the port.
5.
In the Network Status Display dialog box, check that both buses are normal.(*1)
In the case of a system consisting of only ProSafe-RS stations, use an SCS status display window (either SCS Status Overview
or SCS State Management) of SCS Maintenance Support Tool on an SENG to check the bus status. When you call up the SCS
status display window, select the project of a running SCS and then call up the window.
IM 32S56H10-21E
B2-9
l Case 2: When you need to add Layer 3 switches (no ports are available on
existing Layer 3 switches)
Firstly, carry out steps 1 to 7 as shown below to add Layer 3 switches for BUS1 and BUS2. Next,
add stations by following the procedures in n Procedures and Precautions for Adding a Vnet/IP
Station.
1.
In the Network Status Display dialog box on an HIS, check that both buses are normal.(*1)
2.
Make the necessary settings on the Layer 3 switch for BUS1 that you are going to add.
3. Connect the additional Layer 3 switch for BUS1 to an existing Layer 2 or Layer 3 switch for
BUS1 with a cable.
4.
In the Network Status Display dialog box, check that both buses are normal.(*1)
5.
Make the necessary settings on the Layer 3 switch for BUS2 that you are going to add.
6.
Connect the additional Layer 3 switch for BUS2 and an existing Layer 2 or Layer 3 switch for
BUS2 with a cable.
7.
In the Network Status Display dialog box, check that both buses are normal.(*1)
In the case of a system consisting of only ProSafe-RS stations, use an SCS status display window (either SCS Status Overview
or SCS State Management) of SCS Maintenance Support Tool on an SENG to check the bus status. When you call up the SCS
status display window, select the project of a running SCS and then call up the window.
IM 32S56H10-21E
B3-1
IMPORTANT
When passing data between SENG and HIS, or when SENG is sharing database with other
SENG, if the network addresses of the devices are different, the names of other devices or PCs
should be put into the hosts file for name resolution.
SEE
ALSO
For more information about creating SCS project, see the following:
3.1, Creation of New SCS Projects in the Engineering Reference (IM 32S04B10-21E)
IM 32S56H10-21E
B4-1
IM 32S56H10-21E
B4-2
IMPORTANT
The domain number defined in the newly created SCSP station should be the domain number of
the Vnet/IP domain instead of the V net domain. If the V net domain is defined, the station needs
to be deleted and then created again with the correct Vnet/IP domain number.
SEE
ALSO
For more information about creating SCS project on CENTUM, see the following:
2.2, Engineering of the CENTUM Side in the Integration with CENTUM VP/CS 3000 (IM 32S01E10-21E)
Station Type
SSC60D-S
SSC60D-F
Duplexed Safety Control Unit (for Vnet/IP, Wide Range Temperature Type)
SSC60S-S
SSC60S-F
Table
Station Type
SEE
ALSO
Description
Description
SSC50D-S
SSC50D-F
Duplexed Safety Control Unit (for Vnet/IP, Wide Range Temperature Type)
SSC50S-S
SSC50S-F
For more information about defining SCS stations on CENTUM, see the following:
2.2.1, SCS Creation in the Integration with CENTUM VP/CS 3000 (IM 32S01E10-21E)
IM 32S56H10-21E
B4-3
When integrated with CENTUM, domain properties should be set and downloaded
using CENTUM engineering builders. The domain properties are downloaded right after
changing and downloaded with the project common files.
If a system consists of ProSafe-RS only, there will no need to set the domain properties,
the default settings should be used.
SEE
ALSO
For more information about setting domain properties, see the following:
Setting (Default)
Description
Time Group
0 to 7 (1)
Connect Bus 1
nnn.nnn.nnn.nnn
(None)
Connect Bus 2
nnn.nnn.nnn.nnn
(None)
SNTP Server
IP Address
checked.
Domain (*1)
Checked/Unchecked:
Receive/Not receive
(Receive)
Comment
Reception
HIS Message
from Domains
Checked/Unchecked:
FCS Message Receive/Not receive
(Receive)
Checked/Unchecked:
Receive/Not receive
(Receive)
FCS TCP
*1:
*2:
Display only
Select All and Clear All are buttons, cannot be used for setting.
IM 32S56H10-21E
B4-4
When integrated with CENTUM, the communications between Vnet/IP domain and V
net domain are performed through a V net router. Setting the V net router needs to be
performed on CENTUM engineering builders.
SEE
ALSO
For more information about system engineering through V net router, see in 2.1, System Configuration of
the Engineering Guide (IM 32S01C10-21E)
Precautions when Engineering CENTUM Systems for Using V net Routers: SCSP
Precautions when Engineering CENTUM Systems for Using Vnet/IP Domains: SCSP
For more information about setting V net router, see the following:
B2.5, Setting the V net Router in the CS 3000 Vnet/IP (IM 33Q06H90-31E)
B2.5, Setting the V net Router in the CENTUM VP Vnet/IP (IM 33L01A10-40E)
IM 32S56H10-21E
Rev-1
Revision Information
Title
: ProSafe-RS Vnet/IP
Manual No. : IM 32S56H10-21E
Dec. 2009/3rd Edition/R2.03 or later*
Overall
A3
B2.3
*: Denotes the release number of the software corresponding to the contents of this users manual. The
revised contents are valid until the next edition is issued.