Room Air Conditioner


SERVICE MANUAL
CAUTION
- BEFORE SERVICING THE UNIT, READ THE SAFETY
PRECAUTIONS IN THIS MANUAL.
- ONLY FOR AUTHORIZED SERVICE.

MODEL: WR-8030
WM-1031
WM-1231
HBLG8003R
R1200M
R1200E

WM-8031
WR-1230
WR-1030
HBLG1003R
L1204R

CONTENTS
1. PREFACE

3. INSTALLATION

1.1 SAFETY PRECAUTIONS................................2


1.2 INSULATION RESISTANCE TEST .................2
1.3 SPECIFICATIONS...........................................3
1.4 FEATURES......................................................4
1.5 CONTROL LOCATIONS .................................4

3.1 SELECT THE BEST LOCATION...................13


3.2 CHECK OF INSTALLATION..........................13
3.3 HOW TO DRAIN............................................13
3.4 HOW TO INSTALL ........................................14
3.4.1 WHEN USING GASKET.......................14
3.4.2 WHEN USING INSTALLATION KITS...14

2. DISASSEMBLY INSTRUCTIONS

4. TROUBLESHOOTING GUIDE

2.1 MECHANICAL PARTS ....................................6


2.1.1 FRONT GRILLE .....................................6
2.1.2 CABINET ................................................6
2.1.3 CONTROL BOX .....................................6
2.2 AIR HANDLING PARTS ..................................7
2.2.1 AIR GUIDE AND TURBO FAN ...............7
2.2.2 FAN ........................................................7
2.2.3 SHROUD ................................................8
2.3 ELECTRICAL PARTS......................................8
2.3.1 OVERLOAD PROTECTOR ....................8
2.3.2 COMPRESSOR......................................8
2.3.3 CAPACITOR...........................................9
2.3.4 POWER CORD ......................................9
2.3.5 MOTOR ................................................10
2.4 REFRIGERATION CYCLE ............................10
2.4.1 CONDENSER.......................................10
2.4.2 EVAPORATOR.....................................10
2.4.3 CAPILLARY TUBE ...............................11

4.1 OUTSIDE DIMENSIONS ...............................17


4.2 PIPING SYSTEM...........................................18
4.3 TROUBLESHOOTING GUIDE ......................19

5. SCHEMATIC DIAGRAM
5.1 CIRCUIT DIAGRAM ......................................27
5.2 ELECTRONIC CONTROL DEVICE...............28
5.3 COMPONENTS LOCATION(FOR MAIN P.C.B ASM) ..29
5.4 COMPONENTS LOCATION(FOR DISPLAY P.C.B ASM)...29

6. EXPLODED VIEW ..................................30


7. REPLACEMENT PARTS LIST ........31

1. PREFACE
This SERVICE MANUAL provides various service information, including the mechanical and electrical
parts etc. This room air conditioner was manufactured and assembled under a strict quality control system.
The refrigerant is charged at the factory. Be sure to read the safety precautions prior to servicing the unit.

1.1 SAFETY PRECAUTIONS

1.2 INSULATION RESISTANCE TEST

1. When servicing the unit, set the ROTARY SWITCH


or POWER SWITCH to OFF and unplug the power
cord.
2. Observe the original lead dress.
If a short circuit is found, replace all parts which
have been overheated or damaged by the short
circuit.
3. After servicing the unit, make an insulation resistance test to protect the customer from being
exposed to shock hazards.

1. Unplug the power cord and connect a jumper


between 2 pins (black and white).
2. The grounding conductor (green) is to be open.
3. Measure the resistance value with an ohm meter
between the jumpered lead and each exposed
metallic part on the equipment at all the positions
(except OFF) of the ROTARY SWITCH.
4. The value should be over 1M.

1.3 SPECIFICATIONS
1.3.1 FOR WR-8030, WM-8031, WM-1031, WR-1230, WM-1231, HBLG8003R, HBLG1003R,
WR-1030, R1200M, L1204R, R1200E
MODELS
ITEMS

WM-8031
WM-1031
HBLG8003R HBLG1003R

WR-8030

POWER SUPPLY

WM-1231
L1204R
R1200E

WR-1230
R-1200M

WR1030

1, 115, 60Hz

COOLING CAPACITY

(Btu/h)

8,000

10,000

12,000

10,000

INPUT

(W)

800

1,020

1,220

1,020

RUNNING CURRENT

(A)

7.3

9.2

11.0

9.2

(BTU/W.h)

10

E.E.R
OPERATING

INDOOR (C)

CONDITION

OUTDOOR (C)

REFRIGERANT (R-22) CHARGE


EVAPORATOR
CONDENSER

9.8
26.7(DB)* 19.4(WB)**
35(DB)*

23.9(WB)**

300g(10.6oz)

520g(18.3oz)

470g(16.6oz)

520g(18.3oz)

2 ROW 11STACKS

3 ROW 11STACKS

2 ROW 12STACKS

3 ROW 11STACKS

2 ROW 17STACKS

2 ROW 16STACKS

2 ROW 16STACKS

FAN, INDOOR

TURBO FAN
PROPELLER TYPE FAN WITH SLINGER RING

FAN, OUTDOOR
2/3

FAN SPEEDS, FAN/COOLING

3/3

2/3

3/3

2/3

6 POLES

FAN MOTOR
OPERATION CONTROL

ROTARY SWITCH

REMOTE CONTROLLER

ROTARY SWITCH REMOTE CONTROLLER ROTARY SWITCH

ROOM TEMP. CONTROL

THERMOSTAT

THERMISTOR

THERMOSTAT THERMISTOR THERMOSTAT

VERTICAL LOUVER (RIGHT & LEFT)

AIR DIRECTION CONTROL

HORIZONTAL LOUVER (UP & DOWN)


SLIDE IN-OUT CHASSIS

CONSTRUCTION
PROTECTOR

COMPRESSOR

OVERLOAD PROTECTOR

FAN MOTOR

INTERNAL THERMAL PROTECTOR


(3 WIRE WITH GROUDING)

POWER CORD

ATTACHMENT PLUG (CORD-CONNECTED TYPE)


DRAIN PIPE OR SPLASHED BY FAN SLINGER

DRAIN SYSTEM
NET WEIGHT

(lbs/kg)

62/28

OUTSIDE DIMENSION

(inch)

203/32 x 13 29/32 x 193/8

(W x H x D)

(mm)

510 x 354 x 490

* DB:Dry Bulb
** WB:Wet Bulb

1.4 FEATURES

Built-in adjustable Thermistor


Washable one-touch filter
Compact size
Reliable and efficient rotary compressor is equipped.

Designed for COOLING ONLY.


Powerful and whispering cooling.
Slide-in and slide-out chassis for the simple
installation and service.
Low air-intake, top cooled-air discharge.

1.5 CONTROL LOCATIONS


THERMOSTAT
Thermostat will automatically control the temperature of
the room. Select a higher number (the right side of arc)
for a cooler temperature in the room. The temperature is
selected by positioning the knob to the desired position.
The 5 or 6 position is a normal setting for average
conditions.

OFF
MED
FAN

HIGH
COOL

LOW
FAN

MED
COOL
LOW COOL

OPERATION

THERMOSTAT

OFF

: Turns the air conditioner to off.

MED FAN

: Permits the medium fan speed operation


without cooling.

LOW FAN

: Permits the low fan speed operation


without cooling.

OPERATION

HIGH COOL : Permits cooling with the high fan speed


operation.
MED COOL : Permits cooling with the medium fan
speed operation.
LOW COOL : Permits cooling with the low fan speed
operation.

DISPLAY

REMOTE CONTROL

Power

1
AIR
PURIFIER

Cool

F1 LOW
F2 MED
F3 HIGH

Energy
Saver

Air
Purifier

Temp
Power

Fan Speed
Temp

MODE

Timer

TIMER

TEMP
FAN
SPEED

POWER

Sleep

Mode

Timer

Auto
Swing

Timer

Fan Speed

5
3

4
2

Fan
Dry

Mode

Precaution: The Remote Control unit will not function properly if strong light strikes the sensor window of the air
conditioner or if there are obstacles between the Remote Control unit and the air conditioner.
POWER BUTTON
To turn the air conditioner ON, push the button. To turn the air conditioner OFF, push the button again.
This button takes priority over any other buttons.
ROOM TEMPERATURE SETTING BUTTON
This button can automatically control temperature of the room. The temperature can be set within a range of 16C to 30C
by 1C
Select the lower number for lower temperature of the room.
OPERATION MODE SELECTION BUTTON
Every time you push this button, it will shift among COOL, ENERGY SAVER, FAN and DRY.
- Energy Saver: If Energy Save mode is selected, the fan stops when the compressor stops cooling.
Approximately every 3 minutes the fan will turn on and check the room air to determine if cooling is needed.
FAN SPEED SELECTOR
Every time you push this button, it is set as follows.
(Hi Low Med Hi Low ...)
ON/OFF TIMER BUTTON
You can set the time when the unit will turn on or turn off automatically by pressing the timer button. If the unit is operating,
this button controls the time it will be turned off. If the unit is off state, this button controls the time it will start. Every time
you push this button, the remaining time will be set as follows.
- Stopping operation
(1Hour 2Hours 3Hours 4Hours 5Hours 6Hours 7Hours 8Hours 9Hours 10Hours 11Hours
12Hours 0Hour 1Hour 2Hours ... )
- Starting operation
(1Hour 2Hours 3Hours 4Hours 5Hours 6Hours 7Hours 8Hours 9Hours 10Hours 11Hours
12Hours off 1Hour 2Hours ... )
6 REMOCON SIGNAL RECEIVER
7 AIR PURIFIER

Press the Air Purifier button.


Operation will start when the button is pressed and stop when the button is pressed again.
Set the fan speed with the remote control. You can select the fan speed in three steps high, low or medium.
Each time the button is pressed, the fan speed mode is shifted.
If you press the only Air Purifier button, only air purifying operates.
Then, fan speed is low. You can select the fan speed in three steps high, low or medium.
Each time the button is pressed, the fan speed mode is shifed.
8 SLEEP MODE

Press the sleep mode button to set the time you want the unit to turn off automatically.
Every time you push this button, the remaining time will be set as follows.
(1Hour 2Hours 3Hours 4Hours 5Hours 6Hours 7Hours 0Hour 1Hour 2Hours ... )
The temperature setting will be raised by 2F in 30 minutes and by 4F in 1 hour to prevent overcooling during sleep.

2. DISASSEMBLY INSTRUCTIONS
Before the following disassembly, POWER SWITCH set to OFF and disconnect the power cord.

2.1 MECHANICAL PARTS


2.1.1 FRONT GRILLE
1. Open the lnlet grille downward and remove the air
filter.
2. Remove the screw which fastens the front
grille.(See Figure 1)
3. Pull the front grille from the right side.
4. Remove the front grille.(There are 4 hooks.)
5. Re-install the components by referring to the
removal procedure, above.

ER
POW
P
TEM
DE
MO
FAN
ED
E SPE
TIM

2.1.2 CABINET
1. After disassembling the FRONT GRILLE, remove
the 2 screws which fasten the cabinet at both
sides.
2. Remove the 2 screws which fasten the cabinet at
back.
3. Pull the base pan forward. (See Figure 2)
4. Remove the cabinet.
5. Re-install the components by referring to the
removal procedure, above.

Figure 1

2.1.3 CONTROL BOX

COO
L

FAN
DRY

FAN

INDO

HEA
T

OR

DEF
ROS
T

DES
ENE
SAVRGY
ER
PURAIR
YFIE
AUT R
RES
O
TAR

IRED

1. Remove the front grille. (Refer to section 2.1.1)


2. Remove the cabinet. (Refer to section 2.1.2)
3. Remove the 2 screws which fasten the power
cord.
4. Disconnect the grounding screw from the
evaporator channel.
5. Remove the 1 screw which fasten the control box
cover.
6. Remove the housing which connects PCB and
motor wire in the control box.
7. Disconnect the housing which connects Plazma
Air Purifier.(Optional)
8. Remove the screw at left cover of filter case and
open the cover to remove inner screw. (Optional)
9. Remove the nut which fastens the terminal cover.
10. Remove the terminal cover.
11. Remove all the leads from the overload protector.
12. Discharge the capacitor by placing a 20,000
ohmresistor across the capacitor terminals.
13. Raise the control box upward completely.
(See Figure 3)
14. Re-install the components by referring to the
removal procedure, above.
(Refer to the circuit diagram found on page 27 in
this manual and on the control box.)

TIM

FAN
SPE
ED

MO

DE
TEM
P
POW
ER

Figure 2

COO
L

FAN
DRY

FAN

INDO

HEA
T

DEF
ROS

OR

T
DES
IRED

TIM
E

ENE
SAVRGY
ER
PURAIR
YFIE
AUT R
RES
O
TAR
T

FAN
SPE
ED

MO
DE
TEM
P
POW
ER

Figure 3

2.2 AIR HANDLING PARTS


2.2.1 AIR GUIDE AND TURBO FAN
1. Remove the front grille. (Refer to section 2.1.1)
2. Remove the cabinet. (Refer to section 2.1.2)
3. Remove the control box. (Refer to section 2.1.3)
4. Remove the 4 screws which fasten the brace.
5. Remove the brace.
6. Remove the 2 screws which fasten the air guide
upper.
7. Remove the air guide upper.(See figure 4)
8. Remove the 2 screws which fasten the evaporator.
9. Move the evaporator forward and pulling it upward
slightly. (See Figure 5)
10. Pull out the hook of orifice by pushing the tabs
and remove it. (See Figure 6)
11. Remove the clamp with a hand plier which
secures the turbo fan.
12. Remove the turbo fan.
13. Remove the 2 screws which fasten the air guide
from the base pan.
14. Move the air guide backward, and pull out from
the base pan.(Move the air giude lower carefully.)
15. Re-install the components by referring to the
removal procedure, above.

Figure 4

Figure 5

2.2.2 FAN
1. Remove the cabinet. (Refer to section 2.1.2)
2. Remove the brace (Refer to section 2.2.1)
3. Remove the 5 screws which fasten the condenser.
4. Move the condenser to the left carefully.
5. Remove the clamp which secures the fan.
6. Remove the fan. (See Figure 7)
7. Re-install by referring to the removal procedure.

Figure 6

Figure 7
7

2.2.3 SHROUD
1. Remove the fan. (Refer to section 2.2.2)
2. Remove the shroud. (See Figure 8)
3. Re-install the components by referring to the
removal procedure, above.

Figure 8

2.3 ELECTRICAL PARTS


2.3.1 OVERLOAD PROTECTOR
1. Remove the cabinet. (Refer to section 2.1.2)
2. Remove the nut which fastens the terminal cover.
3. Remove the terminal cover. (See Figure 9)
4. Remove all the leads from the overload protector.
5. Remove the overload protector.
6. Re-install the components by referring to the
removal procedure, above.

Figure 9

2.3.2 COMPRESSOR
1. Remove the cabinet. (Refer to section 2.1.2)
2. Discharge the refrigerant system using a FreonTM
Recovery System.
If there is no valve to attach the recovery system,
install one (such as a WATCO A-1) before venting
the FreonTM. Leave the valve in place after
servicing the system.
3. Remove the overload protector. (Refer to section
2.3.1)
4. After purging the unit completely, unbraze the
suction and discharge tubes at the compressor
connections.
5. Remove the 3 nuts and the 3 washers which
fasten the compressor.
6. Remove the compressor. (See Figure 10)
7. Re-install the components by referring to the
removal procedure, above.

Figure 10

2.3.3 CAPACITOR
1. Remove the control box. (Refer to section 2.1.3)
2. Open the top cover from the control box.
(See Figure 11)
3. Pull out the capacitor from the control box.
4. Disconnect all the leads of capacitor terminals.
5. Re-install the components by referring to the
removal procedure, above.

CO
OL

FA
N

IN
DO
OR

DR
Y

FA
N

HE
AT

DES
IR
ED

DEF
RO
ST
EN
ER
SA G
VE Y
R
PU AIR
RY
FI
AU ER
RES TO
TA
RT

Figure 11

2.3.4 POWER CORD


1. Remove the control box. (Refer to section 2.1.3)
2. Open the top cover from the control box.
(Refer to section 2.3.3)
3. Disconnect the front panel from the control box.
(See Figure 12)
4. Disconnect two leads from the capacitor and relay.
5. Pull out the power cord.
6. Re-install the component by referring to the above
removal procedure, above.
(Use only one ground-marked hole for ground
connection.)
7. If the supply cord of this appliance is damaged, it
must be replaced by the special cord.
(The special cord means the cord which has the
same specification marked on the supply cord
attached at the unit.)

CO

OL
FAN
DRY

IND
OOR

FA

HEA
T

DEF
ROS
T

DES
IRE
D

TIM
E

ENE
SAVRGY
ER
PURAIR
YFIE
AUT R
RES
O
TAR
T

FAN
SPE
ED

MO
DE
TEM
P
PO
WE
R

Figure 12

2.3.5 MOTOR
1. Remove the cabinet. (Refer to section 2.1.2)
2. Remove the turbo fan. (Refer to section 2.2.1)
3. Remove the fan. (Refer to section 2.2.2)
4. Remove the 4 screws which fasten the motor from
the air guide. (See Figure 13)
5. Remove the motor.
6. Re-install the components by referring to the
removal procedure, above.(See Figure 13)

2.4 REFRIGERATING CYCLE


2.4.1 CONDENSER
CAUTION

Figure 13

Discharge the refrigerant system using a


FreonTM Recovery System.
If there is no valve to attach the recovery
system, install one (such as a WATCO A-1)
before venting the FreonTM. Leave the valve in
place after servicing the system.
1. Remove the cabinet. (Refer to section 2.1.2)
2. Remove the 5 screws which fasten the
brace.(Refer to section 2.2.1)
3. Remove the 5 screws which fasten the condenser
and shroud.
4. After discharging the refrigerant completely,
unbraze the interconnecting tube at the condenser
connections.
5. Remove the condenser.
6. Re-install the components by referring to notes.
(See Figure 14)

2.4.2 EVAPORATOR

Figure 14

1. Remove the control box.(Refer to section 2.1.3)


2. Remove the air guide upper. (Refer to section
2.2.1)
3. Remove the 2 screws which fasten the evaporator.
4. Move the evaporator sideways carefully.
(Refer to section 2.2.1)
5. After discharging the refrigerant completely,
unbraze the interconnecting tube at the evaporator
connections.
6. Remove the evaporator.
7. Re-install the components by referring to notes.
(See Figure 15)

Figure 15

10

2.4.3 CAPILLARY TUBE


3. Remove the capillary tube.
4. Re-install the components by referring to notes.

1. Remove the cabinet. (Refer to section 2.1.2)


2. After discharging the refrigerant completely,
unbraze the interconnecting tube at the capillary
tube.(See caution above)

NOTES
Replacement of the refrigeration cycle.
1. When replacing the refrigeration cycle, be sure to
Discharge the refrigerant system using a FreonTM
recovery System.
If there is no valve to attach the recovery system,
install one (such as a WATCO A-1) before venting
the FreonTM. Leave the valve in place after
servicing the system.
2. After discharging the unit completely, remove the
desired component, and unbraze the pinch-off
tubes.
3. Solder service valves into the pinch-off tube ports,
leaving the valves open.
4. Solder the pinch-off tubes with Service valves.
5. Evacuate as follows.
1) Connect the vacuum pump, as illustrated figure
16A.
2) Start the vacuum pump, slowly open manifold
valves A and B with two full turns
counterclockwise and leave the valves open.
The vacuum pump is now pulling through valves
A and B up to valve C by means of the manifold
and entire system.
CAUTION
If high vacuum equipment is used, just crack
valves A and B for a few minutes, then open
slowly with the two full turns counterclockwise.
This will keep oil from foaming and being
drawn into the vacuum pump.
3) Operate the vacuum pump for 20 to 30 minutes,
until 600 microns of vacuum is obtained. Close
valves A and B, and observe vacuum gauge for
a few minutes. A rise in pressure would
indicate a possible leak or moisture remaining in
the system. With valves A and B closed, stop
the vacuum pump.
4) Remove the hose from the vacuum pump and
place it on the charging cylinder. See figure
16B.
Open valve C.
Discharge the line at the manifold connection.
5) The system is now ready for final charging.

6. Recharge as follows :
1) Refrigeration cycle systems are charged from
the High-side. If the total charge cannot be put
in the High-side, the balance will be put in the
suction line through the access valve which you
installed as the system was opened.
2) Connect the charging cylinder as shown in figure
16B.
With valve C open, discharge the hose at the
manifold connection.
3) Open valve A and allow the proper charge to
enter the system. Valve B is still closed.
4) If more charge is required, the high-side will not
take it. Close valve A.
5) With the unit running, open valve B and add the
balance of the charge.
a. Do not add the liquid refrigerant to the Lowside.
b. Watch the Low-side gauge; allow pressure to
rise to 30 lbs.
c. Turn off valve B and allow pressure to drop.
d. Repeat steps b. and c. until the balance of the
charge is in the system.
6) When satisfied the unit is operating correctly,
use the pinch-off tool with the unit still running
and clamp on to the pinch-off tube. Using a tube
cutter, cut the pinch-off tube about 2 inches from
the pinch-off tool. Use sil-fos solder and solder
pinch-off tube closed. Turn off the unit, allow it to
set for a while, and then test the leakage of the
pinch-off connection.

11

Equipment needed: Vacuum pump, Charging cylinder, Manifold gauge, Brazing equipment. Pin-off tool capable
of making a vapor-proof seal, Leak detector, Tubing cutter, Hand Tools to remove components, Service valve.

COMPOUND GAUGE

CONDENSER
(HIGH PRESSURE SIDE)

MANIFOLD
GAUGE

B
CAPILLARY TUBE

SEE INSETS
BELOW
EVAPORATOR
(LOW PRESSURE SIDE)

COMPRESSOR

LOW

HI

A
B

EXTERNAL
VACUUM PUMP
CHARGING
CYLINDER

Figure 16B-Charging

Figure 16A-Pulling Vacuum

12

3. INSTALLATION
3.1 SELECT THE BEST LOCATION

FENCE

AWNING
COOLED AIR

HEAT
RADIATION

30"~60"

1.To prevent vibration and noise, make sure the unit


is installed securely and firmly.
2.Install the unit where the sunlight does not shine
directly on the unit.
3.The outside of the cabinet must extend outward for
at least 12" and there should be no obstacles, such
as a fence or wall, within 20" from the back of the
cabinet because it will prevent heat radiation of the
condenser.
Restriction of outside air will greatly reduce the
cooling efficiency of the air conditioner.

ABOUT 1/2"
Over 20"

CAUTION
Figure 17

All side louvers of the cabinet must remain


exposed to the outside of the structure.
4.Install the unit a little slanted so the back is slightly
lower than the front (about 1/2 "). This will help force
con-densed water to the outside.
5.Install the unit from the bottom about 30"~60"
above the floor level.

3.2 CHECK OF INSTALLATION


The setting conditions must be checked prior to
initial starting.
The undermentioned items are especially important
checking points when the installation is finished.
1. Grounding wire (Green or Green and Yellow) is
provided in the power cord. The green wire must
be grounded.
2. Connect to a single-outlet 15A circuit.
(or 20A circuit for Electric Heater Model)
3. To avoid vibration or noise, make sure the air
conditioner is installed securely.
4 Avoid placing furniture or draperies in front of the
air inlet and outlet.

BASE PAN

Figure 18

BOTTOM
1

HOLE RUBBER

3.3. HOW TO DRAIN


(When using drain pipe)
The air conditioner must be installed horizontally or
tilted slightly to the outside for proper water
drainage.
On exceptionally hot and humid days the air
conditioner may overflow condensed water.
If the air conditioner is used in hot and a high
humidity zone, exchange the
HOLE RUBBER
for the
DRAIN PIPE.(See figure 18, figure 19.)

13

BASE PAN
BOTTOM

Figure 19
2

HOLE RUBBER

3.4 HOW TO INSTALL


3.4.1 WHEN USING GASKET
A
2

1
2

COOL FAN DRY HEAT DEFROST

FAN
INDOOR

DESIRED

COOL FAN DRY HEAT DEFROST

FAN

ENERGY
SAVER
AIR
PURYFIER
AUTO
RESTART

INDOOR

DESIRED

ENERGY
SAVER
AIR
PURYFIER
AUTO
RESTART

RIGHT SIDE
B

B
C
J H

HORIZONTAL
LINE

1. WINDOW (WIDTH-A, HEIGHT-B)


2. GASKET
3. WALL

4. DETAILS 5.1 x 30 ROUND HEAD WOOD


SCREWS

535mm
(211/2")

366mm
(147/16")

250mm
(10")

30mm
(11/16")

0~25mm
(0~1")

OVER 420mm
(OVER 1617/32")

32
(11/4")

5~10mm 0~5mm
(3/16"~3/8") (0~3/16")

3.4.2 WHEN USING INSTALLATION KITS


A. WINDOW REQUIREMENTS

25" to 36"

This unit is designed for installation in


standard double hung windows with actual opening
widths from 25" to 36".
The top and bottom window sash must open
sufficiently to allow a clear vertical opening of 16"
from the bottom of the upper sash to the window
stool.

15" min

Stool

Offset
/ " to 11/4"

1 2

Sill
Interior wall

Exterior

203/32" min
(Without frame curtain)
B. INSTALLATION KITS CONTENTS
2

13

12

NO.
1
2
3
4
5
6
7
8
9
10
11
12
13

11

10

14

NAME OF PARTS
FRAME CURTAIN
SILL SUPPORT
BOLT
NUT
SCREW(TYPE A)
SCREW(TYPE B)
SCREW(TYPE C)
FOAM-STRIP
FOAM-PE
UPPER GUIDE
FOAM-PE
FRAME GUIDE
WINDOW LOCKING BRACKET

Q'TY
2
2
2
2
16
3
5
1
1
1
1
2
1

SUGGESTED TOOL REQUIREMENTS


SCREWDRIVER(+, -), RULER, KNIFE, HAMMER, PENCIL, LEVEL
PREPARATION OF CHASSIS
1. Remove the screws which fasten the cabinet at
both sides and at the back.
2. Slide the unit out from the cabinet by gripping the
base pan handle and pulling forward while
bracing the cabinet.
3. Cut the window sash seal to the proper length. Peel
off the backing and attach the Foam-Pe
to the
underside of the window sash.
4. Remove the backing from the top upper guide
Foam PE
and attach it to the bottom of the Upper
Guide .
5. Attach the upper guide onto the top of the cabinet
with 3 type A screws.
6. Insert the Frame Guides
into the bottom of the
cabinet.
7. Insert the Frame Curtain
into the upper guide
and Frame Guides .
8. Fasten the curtains to the unit with 4 Type A screws
at the both sides.

Shipping
Screws

COOL
FAN
DRY
HEAT

FAN

INDOO

DEFR
OST

R
DESIR
ED

ENER
SAVEGY
R
AIR
PURY
FIER
AUTO
REST
ART

TIME
FAN
SPEE
D MOD
E
TEMP

POW
ER

COOL
FAN
DRY
HEAT

FAN

INDOO

DEFR
OST

R
DESIR
ED

ENER
SAVEGY
R
AIR
PURY
FIER
AUTO
REST
ART

TIME
FAN
SPEE
D MOD
E
TEMP

POW
ER

EPS Material
COO
L

FAN
DRY
HEAT

FAN

INDOO

DEFR
OST

R
DESIR
ED

ENER
SAVEGY
R
AIR
PURY
FIER
AUTO
REST
ART

TIME
FAN
SPEE
D MOD
E
TEMP

POW
ER

13
10

CABINET INSTALLATION

(Type A)

1. Open the window. Mark a line on center of the


window stool (or desired air conditioner location).
Carefully place the cabinet on the window stool and
align the center mark on the front angle with the
center line marked in the window stool.

11

11
5

2. Pull the bottom window sash down behind the


upper guide until it meets.

NOTE:
Do not pull the window sash down so tightly that the
movement of Frame Curtain
is restricted.

(Type A)

Upper Guide
Window stool
Front Angle
Figure 20
Window Sash

Upper guide

Foam-pe 13
Cabinet
Frame Curtain

Foam-pe 10

15

Figure 21

3. Loosely assemble the sill support using the parts


in Figure 22.

INDOOR

OUTDOOR
Sill Support 2
Nut 4

Bolt 3

4. Select the position that will place the sill


support near the outer most point on sill
(See Figure 22)

Figure 22

12 Frame Guide

5 Screw(Type A)
About 1/2"

NOTE: Be careful when you install the cabinet


are broken easily).
(Frame Guides

5. Attach the sill support to the cabinet track hole in


relation to the selected position using
2 Type A screws in each support (See Figure 23).

Cabinet
OUTDOOR

INDOOR

Figure 23

Screw(Type B) 6

Screw(Type A) 5
About 1/2"

6. The cabinet should be installed with a very slight


tilt (about 1/2") downward toward the outside
(See Figure 24).
Adjust the bolt and the nut of Sill Support
for
balancing the cabinet.

Sill support 2
7. Attach the cabinet to the window stool by
driving the screws
(Type B: Length sixteen
millimeters and below.) through the front angle into
window stool (5/8").

8. Pull each Frame Curtain


properly to each
window sash track, and repeat step 2.

Sash track

Front Angle
Sill support 2

to the window sash


9. Attach each Frame Curtain
by using screws
(Type C).
(See Figure 25)

Screw(Type B) 6
Figure 24

Type C

Figure 25

16

10. Slide the unit into the cabinet.(See Fig. 26)


CAUTION: For security purpose, reinstall screws (Type
A) at the cabinet's sides.

Power cord

COOL
FAN

DRY

HEAT
DEFROST

FAN
INDOOR
DESIRED

ENERGY
SAVER
AIR
PURYFIER
AUTO
RESTART

TIME

FAN
SPEED

MODE
TEMP
POWER

Screw(Type A)
Screw(Type A)

Figure 26

11. Cut the Foam-Strip


to the proper length and insert
between the upper and lower window sash.
(See Fig. 27)

Foam-Strip 8

Figure 27

12. Attach the window Locking Bracket


screw. (See Fig. 28)

with a type C

13

Figure 28

13. Attach the front grille to the cabinet by inserting the


tabs on the grille into the tabs on the front of the
cabinet. Push the grille in until it snaps into
place.(See Fig. 29)
R
POWE

TEMP

MODE
FAND
SPEE
TIME

14. Lift the inlet grille and secure it with a type A screw
through the front grille.(See Fig. 30)

Figure 29

Figure 30

COOL FAN DRY HEAT DEFROST

FAN
INDOOR

DESIRED

ENERGY
SAVER
AIR
PURYFIER
AUTO
RESTART

Figure 31

4. TROUBLESHOOTING GUIDE
4.1 OUTSIDE DIMENSIONS

unit: mm(inch)

490(19 3/8" )
29(1 5 /32")

126.5(431/32")

510 20 3 32
COOL FAN DRY HEAT DEFROST

FAN
INDOOR

DESIRED

ENERGY
SAVER
AIR
PURYFIER
AUTO
RESTART

29

354(13 /32")

18(23/32")

17

4.2 PIPING SYSTEM

CONDENSER COIL
FAN

CAPILLARY TUBE

MOTOR
COMPRESSOR

TURBO FAN

EVAPORATOR COIL

Figure 32 is a brief description of the important components and their function in what is called the refrigeration
system. This will help you to understand the refrigeration cycle and the flow of the refrigerant in the cooling cycle.

ROOM AIR CONITIONER


CYCLE OF REFRIGERATION

EVAPORATOR COILS

CONDENSER COILS

COMPLETE LIQUID
BOIL OFF POINT
COOLED
AIR

SUCTION LINE
COOL LOW PRESSURE VAPOR

VAPOR INLET
HOT
DISCHARGED
AIR

ROOM AIR HEAT LOAD

MOTOR

OUTSIDE COOLING
AIR FOR REFRIGERANT
PASS THROUGH

COMPRESSOR
OIL

LIQUID
PRESSURE
DROP

LIQUID OUTLET
(LIQUID REFRIGERANT)

HIGH PRESSURE VAPOR


LIQUID REFRIGERANT

CAPILLARY TUBE

Figure 32
18

LOW PRESSURE VAPOR

4.3 TROUBLESHOOTING GUIDE


In general, possible trouble is classified in two kinds.
The one is called Starting Failure which is caused from an electrical defect, and the other is ineffective Air
Conditioning caused by a defect in the refrigeration circuit and improper application.
Unit runs but poor cooling.
Ineffective Cooling

Check cold air circulation


for smooth flow.

Dirty indoor coil


(Heat exchanger)

Check outdoor coil


(heat exchanger) & the fan
operation.

Check heat load


increase.

Clean condenser.
Check gas leakage.

Not on separate circuit.


Malfunction of fan

Clogged of air filter.

Repair gas leak.

Replacement of unit if the


unit is beyond repair.

Obstruction at air outlet

Check inside gas


pressure.

Adjusting of refrigerant
charged.

Correct above trouble


Malfunction of compressor.

Check clogging in refrigeration circuit.

Repair clogging in refrigeration circuit.

Replacement of
compressor.

Satisfactory operation with


temperature difference of
inlet & outlet air ;
44~50F(7~10C)

19

Fails to Start

Check of power source.

Check circuit breaker


and fuse.

Check of control switch


setting.

Gas leakage of feeler bulb


of thermostat

Check of control switch.

Compressor only fails to


start.

Fan only fails to start.

Improper wiring.
Drop of power voltage.
Improper thermostat setting.
Defect of fan motor
capacitor.

Defect of compressor
capacitor.
Loose terminal connection.
Capacitor check.

Irregular motor resistance


( ).
Irregular motor insulation
( ).

Improper wiring.
Replacement
Replacement of fan motor.

Irregular motor resistance (

Irregular motor insulation (

Regular but fails to start.

Replacement of compressor
(locking of rotor, metal).
Replacement of compressor
(Motor damaged)
20

ELECTRICAL PARTS TROUBLESHOOTING GUIDE: WM-8031, WM-1031

Possible Trouble 1

The unit does not operate.

Is the Trans input power


AC 115V?

NO

Check
Check the
the Fuse.
Fuse.
Check
the
Check thewiring
wiringdiagram.
diagram.

YES

Is the Trans output power


about AC 14V?

NO

Is shorted the Trans. output?

YES

Is output Voltage of IC01D


DC 12V?

YES

NO

Check the Main


PCB pattern.

Exchange the Trans.


Exchange D02D~D05D.
Exchange IC01D.

NO

YES

Is output Voltage of IC02D


DC 5V?

NO

Exchange IC02D.

YES

Is the reset circuit all right?


(The No.14 of
Micom is 5V.)

NO

Exchange IC01A, C02A.

YES
Is the
connection between
AC and DC
all right?

NO

Connect connector
exactly.

NO

Check the PCB


pattern.

YES

Is the voltage No.18 of Micom


DC 5V?
YES
Exchange AC PCB Ass'y.

21

Possible Trouble 2

The compressor does not operate.

Is setting
Temp. set lower than Room
Temp.-0.5C?

NO

Select the setting Temp. to lower Number.

YES

Is the voltage No.10


of IC01M 0V?

NO

Is the voltage N0.9 of


IC01M DC 12V?
YES

YES
Check the RY-COMP.
Check the wiring
Diagram.

Exchange IC01M.

NO

Is the Unit for 3 minutes


delay?

NO

YES
Wait 3 Minutes.

Exchange MAIN
PCB Ass'y.

Possible Trouble 3

Is the wire connection of


RY-COMP all right?

The compressor always operate.

Connect LEAD Wire to


RY-COMP again.

NO

YES
Check the RY-COMP.

22

Possible Trouble 4

FAN does not operate.

Is the voltage NO.1 or 2 or 4


of IC01M DC 12V?

NO

Exchange IC01M.

YES

Is the voltage NO.16 or 15 or 13


of IC01M 0V?

NO

Exchange IC01M.

YES
Check the RY-Hi or
RY-Med or RY-Lo.
Check the wiring diagram.

Possible Trouble 5

Remote controller does not operate.

Is the voltage of Battery


about over 2.3V?

NO

Exchange the battery.

YES
Is the voltage No.10
of CN-AC/DC on DC PCB
Ass'y DC 5V?

NO

Check
Checkthe
thePCB
PCBpattern.
pattern.

YES

Is the connection of
CN-AC/DC all right?

Connect connector to
CN-AC/DC exactly.

NO

YES
Exchange Receiver Ass'y.

23

Possible Trouble 6

It displays abnormally on DC PCB Assy.

Is the IC01G all right?

NO

Exchange IC01G.

YES
NO
Is the connection of
CN-AC/DC all right?

NO

Connect connector
to CN-AC/DC exactly.

NO

Exchange IC03G
(Q01G~Q04G for
Delux Model).

YES
Does the IC03G
(Q01G~Q04G for Delux Model)
operate normally on DC
PCB Ass'y?
YES
Exchange the DC
PCB Ass'y.

24

COMPLAINT
Fan motor will not run.

CAUSE

REMEDY

No power

Check voltage at outlet. Correct if none.

Power supply cord

Check voltage to rotary switch. If none, check power


supply cord. Replace cord if circuit is open.

Rotary switch

Check switch continuity. Refer to wiring diagram for


terminal identification. Replace switch if defective.

Wire disconnected or
connection loose

Connect wire. Refer to wiring diagram for terminal


identification. Repair or replace loose terminal.

Capacitor (Discharge
capacitor before testing.)

Test capacitor.
Replace if not within 10% of manufacturer's rating.
Replace if shorted, open, or damaged.

Will not rotate

Fan blade hitting shroud or blower wheel hitting


scroll. Realign assembly.
Units using slinger ring for condenser fan must have
1
/4 to 5/16 inch clearance to the base. If it hits the
base, shim up the bottom of the fan motor with
mounting screw(s).
Check fan motor bearings; if motor shaft will not
rotate, replace the motor.

Fan motor runs


intermittently

Revolves on overload.

Check voltage. If not within limits, call an electrician.


Test capacitor.
Check bearings. Does the fan blade rotate freely?
If not, replace fan motor.
Pay attention to any change from high speed to
low speed. If the speed does not change, replace the
motor.

Fan motor noise.

Compressor will not run,


but fan motor runs.

Fan

If cracked, out of balance, or partially missing,


replace it.

Blower

If cracked, out of balance, or partially missing,


replace it.

Loose clamper

Tighten it.

Worn bearings

If knocking sounds continue when running or loose,


replace the motor. If the motor hums or noise
appears to be internal while running, replace motor.

Voltage

Check voltage.
If not within limits, call an electrician.

Wiring

Check the wire connections, if loose, repair or


replace the terminal. If wires are off, refer to wiring
diagram for identification, and replace. Check wire
locations. If not per wiring diagram, correct.

Rotary

Check for continuity, refer to the wiring diagram for


terminal identification. Replace the switch if circuit is
open.

25

COMPLAINT
Compressor will not run,
but fan motor runs.

Compressor cycles on
overload.

Compressor cycles on
overload.

Compressor cycles on
overload.

Insufficient cooling or
heating

Excessive noise

CAUSE

REMEDY

Thermostat

Check the position of knob If not at the coldest


setting, advance the knob to this setting and restart
unit.
Check continuity of the thermostat. Replace
thermostat if circuit is open.

Capacitor (Discharge
capacitor before servicing.)

Check the capacitor.


Replace if not within 10% of manufacturers rating.
Replace if shorted, open, or damaged.

Compressor

Check the compressor for open circuit or ground. If


open or grounded, replace the compressor.

Overload

Check the compressor overload, if externally


mounted. Replace if open. (If the compressor
temperature is high, remove the overload, cool it,
and retest.)

Voltage

Check the voltage.


If not within limits, call an electrician.

Overload

Check overload, if externally mounted.


Replace if open. (If the compressor temperature is
high, remove the overload, cool, and retest.)

Fan motor

If not running, determine the cause. Replace if


required.

Condenser air flow


restriction

Remove the cabinet. inspect the interior surface of


the condenser; if restricted, clean carefully with a
vacuum cleaner (do not damage fins) or brush.
Clean the interior base before reassembling.

Condenser fins (damaged)

If condenser fins are closed over a large area on the


coil surface, head pressures will increase, causing
the compressor to overload. Straighten the fins or
replace the coil.

Capacitor

Test capacitor.

Wiring

Check the terminals. If loose, repair or replace.

Refrigerating system

Check the system for a restriction.

Air filter

If restricted, clean of replace.

Exhaust damper door

Close if open.

Unit undersized

Determine if the unit is properly sized for the area to


be cooled.

Blower or fan

Check the set screw or clamp. If loose or missing,


correct. If the blower or fan is hitting air guide,
rearrange the air handling parts.

Copper tubing

Remove the cabinet carefully and rearrange tubing


not to contact cabinet, compressor, shroud, and
barrier.

26

5. SCHEMATIC DIAGRAM
5.1 CIRCUIT DIAGRAM

MODEL: WM-8031, WM-1031, WM-1231,


HBLG8003R, HBLG1003R,
L1204R, R1200E
1

POWER INPUT
BK(BR)
WH(BL)
(Plain)
(Ribbed)

CN-AC/DC

5
RY-HI

CAPACITOR

RY-MED

MOTOR

CN-AC/DC

CN-MOTOR

BK
BL
RD
YL
OR

RY-LOW

GN/YL
(GN)

MODEL: WR-8030, WR-1230, WR-1030,


R1200M

10

CN-TH1

YL

BK

CN-PWR

GN/YL
(GN)

RY-COMP

4
S
OLP

WIRING DIAGRAM

BL

CAPACITOR

3854AR3563N

OR(BR)
C

COMP.

H.V.
ASSEMBLY
BK

S
BR(YL)

BK

BK

RD

RD

BL

BL

OLP
THERMOSTAT

H
BK
RD

RD

P.T.C

8
AIR FILTER
ASSEMBLY

WIRING DIAGRAM

3854AR3563A

S: Service Parts
N: Non Service Parts
LOCATION
NO.

MOTOR

OR(BR)

SWITCH

AC PCB
ASSEMBLY

BL

BK

BL

YL

BL

COMP.

BK

4 M

YL

CN-12V

CN-HVB

DC12V

FUSE
250V/T2A
(115V/T2A)

BK(BR)
(Plain)

6 H

6
ZNR01J

WH(BL)
(Ribbed)

RD

THERMISTOR

RD

RD

POWER
TRANS

OR(BR)

8 L

GN(GN/YL)

ROTARY SWITCH

DC PCB
ASSEMBLY

DESCRIPTION

Q'TY
PER SET

REMARKS

MOTOR ASSY

CAPACITOR

COMPRESSOR

OVERLOAD PROTECTOR

DC PCB ASSEMBLY

AC PCB ASSEMBLY

THERMISTOR

PLASMA FILTER ASSY

THERMOSTAT

10

ROTARY SWITCH

27

28

MAIN POWER

FAN

COMP

HERM

CAPACITOR

FAN
MOTOR

S/V4WAY

HVB

SW1

SW2

PIPE-TH

YW396-03AV

CN-PWR

YW396-09AV

250V/T2A

FUSE

G4A-1A-E-LG

RY-COMP

CN-MOTOR

YW396-03AV(YL)

J5

C01T

5V

0.1
50V

SMW200-03(WH)

CN-12V

SMW200-03(YL)

CN-CONT

SMW200-03(BL)

CN-HVB

SMW250-02

CN-TH2

CN-4WAY

SMW200-03
(RD)

CN-TELE

D01T

R01J

SVC271D-14A
SVC271D-14A

ZNR01J

120 1/2W

0.1/275V

C01J

RY-LOW

RY-MED

RY-HI

RY-4WAY

1000
35V

D04D
+
C01D
0.1
50V

10

11
12

1000
16V

C03D

7812

IC01D

C02D

51580-12
52045-1245
STRAIGHT

CN-AC/DC

12V

5V

CN-TH2

RY-HI

RY-MED

RY-LOW

RY-4WAY

D05D

Tx

Rx

RY-COMP

CN-4WAY

D02D~D05D
1N4004

D03D

D02D

J07

J7

A104M

Q02T

5V

0.001
25V

C03T

R01T
1K

Q03T
C104M

POWER TRANS

Heat Pump

RY-4WAY
X

12V

C104M

Q01T

A104M

Q04T

Cool Only

Model

1N4148

5V

7805

IC02D

0.01
25V

C04D

12V

ROOM-TH
2

1
2

0.01
25V

C05D

Vout

220
10V

C05D

PKM13EPY
-4002

BZ01E

RECEIVER

GND

Vcc

51581-12(YEONHO)
52044-1245(MOLEX)
ANGLE

5V

ULN2004A

IC01M

16

15

14

13

11
12

10

+
0.01
50V

C06D

R02E
20

1K

5V

R01E
1K

680pF
50V

C01L

20K

HI

MED

ION

HVB

LOW

4WAY

SYNC

COMP

LED out3

Buzzer

Receiver

12.1K
1%

6.2K
1%

R01P

R02H

R04H

5V

R01L

OR2H

R22H
12.1K
1%

12.1K
1%

5V

R21H

5V

OR1H

12V

CN-AC/DC

12

11

12V

220
10V

C02L

5V

10

SMAW200-02

CN-TH1

2
1

33

32

31

30

29

28

27

26

25

24

23

RT8.00MG

OSC01B

34

22

Option2
5V

LED out2

35

21

36

20

17

16

MICOM

18

5V

1M

R01B

37

38

R12F
10K

39

40

TMP87CH47U

19

Room TH
KEY1

VAref
KEY0

Option1
LED out1

VSS
SLIDE SW

Pipe TH
LED out0

Osc out
VDD

41

15

Osc in
5V

SEG-g

42

14

/Reset
SEG-f

43

44

12

0.01
50V

C01A

13

TEST
SEG-e

0.001

SEG-d

C02T

10

11

SEG-c

SEG-b

SEG-a

Digit0 (Scan0)

Digit1 (Scan1)

Digit2 (Scan2)

Digit3 (Scan3)

Digit4 (Scan4)

SCL

SDA

Rx

R05P
10K

1uF
10V

+ C02A

20K

R01A

3.6V

10

11

12

13

14

15

16

12V

C02F
0.001

R07G 680

R06G 680

R05G 680

R04G 680

R03G 680

R02G 680

R01G 680

R03F
10K

R01F
10K

R06P
10K

C01F
0.001

ULN2004A

IC01G

S7136

IC01A

5V

SCL

WP
6

Vcc 8

GND SDA 5

A2

A1

A0

CAT93C46

1K

R04P

5V

Q02G
Q01G

COOL

SW04G

E/SAVER

FAN

TIMER

DRY/HEAT

D05G

10

Digit0

SW06G

TEMP UP

D06G

88 SEGMENT

Digit1
a

SW05G

MODE

SW03G

TIMER

ON/OFF
SW02G
D02G

TEMP DOWN

D03G

A101S

FAN

A101S

SW01G

DEFROST

D04G

D01G

A101S

Q03G

20K

20K

R04P
R03P

R02P

EEPROM

EEPROM R04P

Non Auto Restart

Model
Auto Restart

5V

5.2 ELECTRONIC CONTROL DEVICE

MODEL : WM-8031, WM-1031, WM-1231,HBLG8003R, HBLG1003R, L1204R, R1200E

5.3 COMPONENTS LOCATION(FOR AC P.C.B ASM)


MODEL : WM-8031, WM-1031, WM-1231, HBLG8003R, HBLG1003R, L1204R, R1200E

J2
IC01D

C02D

J7
RY-HI

CN-PWR

CN-4WAY

ZNR01J

C01J

R01J

C04D
C05D
RY-LOW

D05D

D04D

D03D

QIC02DT

CN-TH2

RY-MED

HEAT SINK

CN-AC/DC

Q04T

PCB:6870A90068A

Q03T

C03T

J1

CN-TELE

J3

CN-12V

CN-HVB

D02D

CN-MOTOR

J6

J5

D01T
C02T

J4 Q02T

CN-CON

R01T Q01T

E03J

C01D

ASSEMBLY:6871A20167

E01J

J8

RY-4WAY
RY-COMP

E02J

POWER
TRANS

E04J

E05J

FUSE
250V/T2A

5.4 COMPONENTS LOCATION(FOR DC P.C.B ASM)


MODEL : WM-8031, WM-1031, WM-1231, HBLG8003R, HBLG1003R, L1204R, R1200E

29

6. EXPLODED VIEW
731373

554030

149980
148000
130910

W48602

346811

559011

359012
W48602

352390-2
354210
249950

263230
152312

268712

268714

352390-1

135500
W0CZZ

238310

349001

349480
130410

264110

237200

567502

554160
135312

147582

249950
550140

147581

269310

552111

266003

352115
135500
W0CZZ

152302
352113
264110
135313

149410

30

35211A

352113

7. REPLACEMENT PARTS LIST

R: Service Parts
N: Non Service Parts
PART NO.

LOCATION
NO.

DESCRIPTION

130410
130910
135312
135303
135313
135500
237200
147581
147582-1
147582-2
148000
149410
149980
152302
269310
238310
249950
263230
264110
266003
267110
268712
268714
346811
349001
349480
352113
352115
352390-2
352390-1
354210
559012
550140
552111
554030
554031
554160
559010
567502
731373
35211A
W0CZZ
W48602

BASE ASSEMBLY,SINGLE
CABINET ASSEMBLY,SINGLE
GRILLE ASSEMBLY,FRONT(SINGLE)
GRILLE,INLET
GRILLE ASSEMBLY,INLET
COVER,CONTROL(INDOOR)
PANEL,CONTROL
LOUVER,HORIZONTAL
LOUVER,VERTICAL
LOUVER,VERTICAL
BRACE
KNOBS ASSEMBLY
SHROUD
FILTER(MECH),A/C
THERMOSTAT
ESCUTCHEON
CONTROL BOX ASSEMBLY,SINGLE
THERMISTOR
POWER CORD ASSEMBLY
SWITCH, ROTARY
REMOTE CONTROLLER
PWB(PCB) ASSEMBLY,DISPLAY
PWB(PCB) ASSEMBLY,MAIN
MOTOR ASSEMBLY,SINGLE
DAMPER,VENTILATION
ORIFICE
TUBE ASSEMBLY,DISCHARGE SINGLE
TUBE ASSEMBLY,EVAPORATOR IN
AIR GUIDE ASSEMBLY
AIR GUIDE ASSEMBLY
EVAPORATOR ASSEMBLY,FIRST
FAN,TURBO
ISOLATOR,COMP
TUBE ASSEMBLY, CAPILLARY)
CONDENSER ASSEMBLY,FIRST
CONDENSER ASSEMBLY,BENT
COMPRESSOR
FAN ASSEMBLY,AXIAL
O.L.P
INSTALL PARTS ASSEMBLY,SINGLE
TUBE ASSEMBLY,SUCTION SINGLE
CAPACITOR
CLAMP,SPRING

WR-8030

WM-0831

WM-1031

WR-1230
R1200M

WM-1231
L1204R

REMARK

3041A20021V
3091AR2317K
3531A20097A
3530A20038A
3550A30194A
3720A10113A
4758A20019A
4758A20040A
4758A20040B
4800A30002A
4941A30020A
4998A10023A
5231A20006A
2H01109M
4995A20279A
6411A20011T
2H00598E
4681A20069M
4900A20003A
4948A10014A
5211A20708B
5211A20559K
5239A20012A
5239A20005A
5421A10026B
5900A20020A
4830AR4335A
5211A30275N
5403A20092B
5416A20014B
5900AR1167B
6750A30001N
3127A10015B
5211A20228R
6120AR2359V
3H02932B

3041A20021V
3091AR2317K
3531A20097A
3530A20038A
3550A30114A
3720A10111A
4758A20019A
4758A20040A
4758A20040B
4800A30002A
4998A10023A
5231A20006A
3831A10021J
4995A20278A
6323A20004D
6411A20011F
6711A20034G
6871A20324B
6871A20167C
4681A20069G
4900A20003A
4948A10014A
5211A20708B
5211A20559K
5239A20012A
5239A20005A
5421A10026B
5900A20020A
4830AR4335A
5211A30275N
5403A20092B
5416A20014B
5900AR1167B
6750A30001N
3127A10015B
5211A20228R
6120AR2359V
3H02932B

3041A20021N
3091AR2317K
3531A20097A
3530A20038A
3550A30114A
3720A10111A
4758A20019A
4758A20040A
4758A20040B
4800A30002A
4998A10012A
5231A20006A
3831A10021J
4995A20278B
6323A20004D
6411A20011R
6711A20034G
6871A20324B
6871A20167C
4681A20069H
4900A20003A
4948A10014A
5211A10074J
5211A20470F
5239A20012A
5239A20005A
5421A10026C
5900A20020A
4830AR4335A
5211A30275M
5403A20043M
2520UKLC2CA
5900AR1167B
6750U-L031A
3127A10015B
5211A20228S
0CZZA20001N
3H02932B

3041A20020L
3091A10032M
3531A20098A
3530A20037A
3550A30194A
3720A10113A
4758A20018A
4758A20041A
4758A20041B
4800A30002B
4941A30020A
4998A10016A
5231A20007A
2H01109M
4995A20279C
6411A20011U
2H00598E
4681A20069P
4900A20002A
4948A10015A
5211A10074K
5211A20559N
5238A20008A
5239A20004A
5421A20130A
5900A20019C
4830AR4335A
5211A30275P
5403AR2921H
2520UKFC2AA
5900A10009B
6750U-L029A
3127A10015G
5211A20441F
0CZZA20001N
3H02932B

3041A20020L
3091A10032M
3531A20098A
3530A20037A
3550A30114A
3720A10111A
4758A20018A
4758A20041A
4758A20041B
4800A30002B
4998A10016A
5231A20007A
3831A10021J
4995A20278C
6323A20004D
6411A20011H
6711A20034G
6871A20324B
6871A20167C
4681A20069J
4900A20002A
4948A10015A
5211A10074K
5211A20559N
5238A20008A
5239A20004A
5421A20130A
5900A20019C
4830AR4335A
5211A30275P
5403AR2921H
2520UKFC2AA
5900A10009B
6750U-L029A
3127A10015G
5211A20441F
0CZZA20001N
3H02932B

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)

31

R: Service Parts
N: Non Service Parts
LOCATION
NO.

130410
130910
135312
135303
135500
147581
147582-1
147582-2
148000
149410
149980
152302
237200
238310
269310
249950
263230
264110
266003
267110
268714
268714
346811
349001
349480
352113
352115
35211A
352390-1
352390-2
354210
559012
550140
552111
554030
554031
554160
559010
567502
731373
W0CZZ
W48602

PART NO.
DESCRIPTION
BASE ASSEMBLY,SINGLE
CABINET ASSEMBLY,SINGLE
GRILLE ASSEMBLY,FRONT(SINGLE)
GRILLE,INLET
COVER
LOUVER,HORIZONTAL
LOUVER,VERTICAL
LOUVER,VERTICAL
BRACE
KNOB ASSEMBLY
SHROUD
FILTER ASSEMBLY,AIR CLEANER
PANEL, CONTROL
ESCUTCHEON
THERMOSTAT
CONTROL BOX ASSEMBLY,SINGLE
THERMISTOR ASSEMBLY
POWER CORD ASSEMBLY
SWITCH, ROTARY
REMOTE CONTROLLER ASSEMBLY
PWB(PCB) ASSEMBLY,MAIN(AC)
PWB(PCB) ASSEMBLY,MAIN(DC)
MOTOR ASSEMBLY,SINGLE
DAMPER,VENTILATION
ORIFICE
TUBE ASSEMBLY,DISCHARGE SINGLE
TUBE ASSEMBLY,EVAPORATOR IN
TUBE ASSEMBLY,SUCTION SINGLE
AIR GUIDE ASSEMBLY
AIR GUIDE ASSEMBLY
EVAPORATOR ASSEMBLY,FIRST
FAN,TURBO
ISOLATOR,COMP
TUBE ASSEMBLY , CAPILLARY
CONDENSER ASSEMBLY,FIRST
CONDENSER ASSEMBLY,BENT
COMPRESSOR
FAN ASSEMBLY,AXIAL
O.L.P
INSTALL PARTS ASSEMBLY, SINGLE
CAPACITOR,DRAWING
CLAMP,SPRING

HBLG8003R
3041A20021V
3091AR2317K
3531A20160A
3530A20075A
3550A30114A
4758A20019A
4758A20040B
4758A20040A
4800A30002A
4998A10023A
5231A20006A
3720A10111A
3831A10021E
4995A20194V
6323A20004D
6411A20011F
6711A90019C
6871A20167C
6871A20324A
4681A20069G
4900A20003A
4948A10014A
5211A20708B
5211A20559K
5211A20228R
5239A20005A
5239A20012A
5421A10026B
5900A20020A
4830AR4335A
5211A30275N
5403A20092B
5416A20014B
5900AR1167B
6750A30001N
3127A10015B
6120AR2359V
3H02932B

HBLG1003R

WR-1030

R1200E

3041A20021N 3041A20021N 3041A20020L


3091AR2317K 3091AR2317K 3091A10032M
3531A20160A 3531A20097A 3531A20161B
3530A20075A 3530A20038A 3530A20076A
3550A30114A 3550A30194A 3550A30114A
4758A20019A 4758A20019A 4758A20018A
4758A20040B 4758A20040A 4758A20041A
4758A20040A 4758A20040B 4758A20041B
4800A30002A 4800A30002A 4800A30002B
4941A30020A
4998A10012A 4998A10012A 4998A10016A
5231A20006A 5231A20006A 5231A20007A
3720A10111A 3720A10113A 3720A10111A
3831A10021E
3831A10021J
2H01109M
4995A20194W 4995A20279B 4995A20278C
6323A20004D
6323A20004D
6411A20011R 6411A20011V 6411A20011H
2H00598E
6711A90019C
6711A20034C
6871A20167C
6871A20324B
6871A20324A
6871A20167C
4681A20069H 4681A20069N 4681A20069J
4900A20003A 4900A20003A 4900A20002A
4948A10014A 4948A10014A 4948A10015A
5211A10074J 5211A10074J 5211A10074K
5211A20470F 5211A20470F 5211A20559N
5211A20228S 5211A20228S 5211A20441F
5239A20005A 5239A20005A 5238A20008A
5239A20012A 5239A20012A 5239A20004A
5421A10026C 5421A10026C
5900A20020A 5900A20020A 5900A20019C
4830AR4335A 4830AR4335A 4830AR4335A
5211A30275M 5211A30275M 5424AR3448G
5403AR2921H
5403A20043M 5403A20043M
2520UCDK004 2520UCDK004 2520UKFC2AA
5900AR1167B 5900AR1167B
6750U-L031A 6750U-L031A 6750U-L029A
3127A10015B 3127A10015B 3127A10015G
0CZZA20001N 0CZZA20001N 0CZZA20001N
3H02932B
3H02932B
3H02932B

NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)

32

REMARK
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R