1. General .............................................................................................................................................1
2. Main function...................................................................................................................................3
3. Control principle ..............................................................................................................................8
4. Technique index .............................................................................................................................10
5. Frame and panel definition ............................................................................................................13
5.1 Trunk configuration ..............................................................................................................13
5.2 Main inserted pieces..............................................................................................................13
5.3 Panel definition and illumination..........................................................................................14
5.4 Keystroke definition..............................................................................................................15
5.5 Display lamp illumination.....................................................................................................15
6Man-machine operation ...............................................................................................................17
6.1 Main page layout illumination ..............................................................................................17
6.2 LCD main menu tree frame illumination..............................................................................17
6.3 Main Menu instruction..........................................................................................................18
6.4 Run Monitor instruction........................................................................................................19
6.5 Set Point instruction ..............................................................................................................19
6.6 Parameter Set Instruction ......................................................................................................21
6.7 Event Record Instruction ......................................................................................................24
6.8 Manual Print introduction .....................................................................................................25
6.9 Other Function introduction..................................................................................................26
7. Instruction of backboard terminals connection and installation ....................................................30
7.1 Power board terminals instruction ........................................................................................32
7.2 TA board terminals instruction..............................................................................................32
7.3 TV board terminals instruction .............................................................................................32
7.4 CPU board terminals instruction...........................................................................................33
7.5 EDI heavy current input board terminals instruction............................................................35
7.6 Output board terminals instruction .......................................................................................35
8. Debug and dispose of abnormity ...................................................................................................38
9. Commissioning instructions and notices........................................................................................40
10. Storage and maintain....................................................................................................................40
11. Whole set supplied .......................................................................................................................40
Appendix 1: Set point table................................................................................................................41
Appendix 2: Parameter list.................................................................................................................46
Appendix 3: Back up scheme instruction ..........................................................................................49
(V1.42)
2011.03.
The company reserves the right to change products, the specification is subject to change without
notificationthe device shall prevail. For details, please call the company or the local agents.
2
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
2. Main function
The main function of SID-409 as follows:
Reserve supply auto put in function
Normal manual switch function
Protection function
Reserve supply auto put in fault lock function
Event record function
Transferring record wave function
Communication, print, GPS adjusting time function
caused by putting in backup supply to ensure the success of backup switch, so SID-3YL Inrush
Suppressor is needed when the transformer backup switch is cold backup.
2.1.2 Backup switch control logic
The reserve supply switch process concludes: charging, operation and affirm reset.
The charging:
When incomer and bus voltage and every breaker state are at normal condition, the charging
begins. The Auto switch lamp on the panel begins to wink, and after ten seconds the lamp
constant bright, it indicates that the Reserve auto-transfer enter operation and monitor state.
The operation process:
Under monitoring state, if the reserve supply has voltage and no blocking signal, then the
following conditions happen:
1)
Bus voltage lower than no-voltage set-point, and the last time exceed the no-voltage starting
time.
2)
The work power switch turn to open and remain mis-trip starting time.
If any conditions is satisfied, and the working line has no current (to avoid mis-trip when the bus
TV line-break, use line current as the lock criterion of bus no-voltage), it will trip off the work
power switch. The device will close the reserve supply switch and input the reserve supply when
the bus no-voltage test condition is satisfied and the delay set-point is maturated. After transfer, no
matter success or fail, the device enters the state of affirm reset.
The affirm reset process:
Under the affirm reset state, the device stores the record wave dates. It may not enter charging
state to ready for next transfer until delay 10s and remote or local reset operation is received. If the
operation succeeded, the device reset automatically after 10s.
4) The manual switch function can be select, and the switch mode can be set according to
different needs.
Through setting the manual switch set-point, the device can realize flexible configuration of
manual switch function in a variety of occasions, the set options as follows:
[Exit] --- Exit manual switch function.
[Series] --- Check bus, backup supply with voltage, trip work (backup) switch first, and then
close backup (work) switch.
[Auto Parallel] --- Detect bus voltage and backup supply voltage, if the parallel synchronizing
condition is satisfied, close backup switch first, then trip work switch.
[Semi-auto Parallel] --- Detect bus voltage and backup supply voltage, if the parallel
synchronizing condition is satisfied, close backup switch. Work switch is operated manually.
[Parallel & Series] --- Detect the parallel synchronization conditions as the [Auto Parallel] logic,
if the synchronization conditions can not satisfied in the detect delay then choose [Series Switch].
2.2.2 Manual switch control logic
Under normal running condition, the device can realize the transfer function between work
supply and reserve supply through external manual switch (pulse) signal or remote switch order.
Normal manual switch has test synchronization function.
When the breaker state is satisfied for manual switch condition, the manual switch lamp
normal bright, and the Reserve auto-transfer device enter the manual switch operation and monitor
state. Under this state, if local or remote manual switch signal is gathered, working breaker will
transfer with backup breaker automatically. If the operation fails, the device enter waiting affirm
reset state. It may not enter charging state to ready for next transfer until delay 10s and remote or
local reset operation is received. If the operation succeeded, the device reset automatically after 10s.
When the bus linkage over-current protection segment 2 function is put in, and the bus linkage
current larger than segment 2 set-point, bus breaker will tripped after time set-point delayed.
2.3.3Bus linkage haste protection
When bus breaker changes from open to closed, the device opens haste protection for 5 seconds.
During the period if haste protection function is put in, bus linkage current is larger than current set
point, the bus breaker tripped after set time delayed.
2.3.4 No-voltage alarm protection
When no-voltage alarm protection of every incomer and bus is put in and the voltage is lower
than each no-voltage alarm voltage set-point, the general alarm signal is port-out after no-voltage
alarm set time delayed.
2.3.5 Incomer TV disconnection alarm
Each incomer TV secondary disconnection protection soft switch put in and incomer voltage
lower than 70%Un and incomer breaker is at closed, after ten seconds delayed, alarm signal send by
protection and device TV disconnection alarm signal is sent out.
2.3.6 Bus TV disconnection alarm
Bus TV disconnection protection soft switch put in, single phase or three-phase voltages lower
than 70%Un, after ten seconds delayed, alarm signal sent by protection and device TV disconnection
alarm signal is sent out.
total twice. The device storage is up to 12 groups of record data. The contents include bus voltage,
bus current, incomer voltage, incomer current and all digital input information e.g.. The wave
recording event index can be looked over in wave recording event, the waveform, record data can
be transmitted to background computer for analyzing.
7
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
3. Control principle
In the backup switching process, before closing the breaker, to avoid the high residual voltage
causing large surge current when closing, it will damage the device or make the backup switch and
normal switch fail, so in occasion that the reliability requirement is very strict but speed
requirements isnt that high, we can use bus un-voltage detection to ensure the success of backup
switch or normal series switch. Un-voltage switch means after tripping the work supply switch,
check bus voltage, until the three line voltages of bus are all lower than voltage set-point of bus
un-volt. switch, and after the time set-point of un-volt. switch, closing the backup supply switch is
allowable, the software flow of backup switch control logic is shown in figure 1.
Normal manual switch is mainly used in work supply and backup supply switching for each other
when normal operating, such as overhaul, test etc. Therefore, in occasion of high requirement of
continuity and reliability about supply and allow short time loop closing, we can select Parallel
Auto / Semi-auto mode, while if loop closing is not allowed, we must select series mode. Normal
manual switch logic is shown in figure 2.
Control logic software procedure:
START
A
Fill the auto-switch
charge condition?
Trip succeed?
Y
Charge 10s timer
come?
N
Reset the charge timer
auto-switch lamp dark,
return to charge status
N
Work switch open and
delay time come?
Report overtime
incident
N
Bus un-voltage and
delay time come?
Y
Trip work supply switch
Switch succeed
Device locked
General alarm
Waiting for reset
Switch failed
Device locked
General alarm
Waiting for reset
8
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
9
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
4. Technique index
4.1 Rated data
Power supply
TV signal
TA signal
Frequency
50 Hz
Thermal stability
AC voltage circuit: long run
1.2 Un
Un----rated voltage
2 In
In-----rated current
1 second
40 In
<0.5 VA/phase
AC current signal
<1 VA/phase
(In=5A)
-20~+ 55
in house whose temperature is -30~+80, the relative humidity not
larger than 80%, surrounding air does not contain acidic, alkaline or other caustic, volatile gas,
and the house is rain and snow prevented; under high-point, if no excitation, no irreversible
change, the device can working normally when temperature restore.
Relative humidity: the month average of maximal relative humidity of the most humid month
is 90%, and the month average of minimal temperature is 25 and no dew appears. The
highest temperature is +40, the maximal average humidity does not exceed 50%.
Atmospheric pressure: relative height above sea level is less than 2 km.
Vibration endurance
The device can endure vibration endure test whose inclemency grade is as stated in 4.2.2
of GB/T11287-2000.
Impact endurance
The device can endure impact endure test whose inclemency grade is as stated in 4.2.2
of GB/T14537-1993.
Collision
The device can endure collision test whose inclemency grade is as stated in 4.3 of
GB/T14537-1993.
12
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
It outputs +5V, 12V and +24V. +5V voltage is for digital circuit, 12V is for A/D sampling,
and 24V is for driving relay and light coupling circuit of internal DI signal.
AC inserted piece
TV inserted board can connect to 7 channels of voltage.
TA inserted board can connect to 6 channels of current.
CPU inserted piece
CPU inserted piece is composing of main control CPU, SDRAM, Flash Memory and A/D
sample chip. The main control CPU is high speed RISC MPU, its master frequency reaches
200MHz, support DSP operation dictate integration. It adopts 14 channels high precision
high speed synchronous sampling technique to ensure response speed of device. All
industrial and military IC make the device own high stability and high reliability.
Signal inserted piece
Signal board can divided into two types: digital input and digital output.
There are one input pieces, and can totally connect to 15 strong electric input points. The
drive voltage is 220V DC, brought in from extern.
There are two digital output pieces, owning 23 independent output nodes.
Man-machine conversation inserted piece
It mainly refers to the fore panel which provides 9 keystrokes, 16 signal lamp, a LCD screen
of 192*64 size for convenient of man-machine conversation, and at the same time a USB 2.0
Host interface for special use of factory test.
Panel of the device is composing of display lamps, LCD screen and keyboard viewed from left to
14
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
right.
Exit
Reset
press transitorily revert control, alarm, lamp signal. Long-term (longer than 1.6s) press
revert device.
Note that, display in reverse of parameter, symbol, number or letter express the present location
of cursor.
Illumination
Name
1DL
Blocking
signal
2DL
when alarming
BLOCKING
Illumination
lamp,
3DL
putout
COMMUNICATION
Communication indicating
lamglitter when message
4DL
normal
15
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
ACTION
COUPLER
Load
shedding
signal
BACKUP
SWITCH
shedding
COUPLER
Coupler
closed
signal
CLOSED
MANAUL
SWITCH
RUNNING
closed
COUPLER
Coupler
tripped
signal
TRIPPED
second normally
tripped
16
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
6Man-machine operation
Man-machine page layout is made up of display lightkeystrokeLCD. The hardware has been
explained before, please refer to frame and panel definition in section 5. And here will be a
presentation about the content and manipulation of every LCD page layout.
In the figure:
On the top left corner is scheme name: SID-409.
On the right of top corner is the number of the scheme running currently: scheme 02 (See
appendix 3 for detail)
On the middle: The name of the device: Reserve Supply Auto-transfer Device.
Area Number of the set-point running currently: 02.
Running time: 2008-06-06 14:06:06.
On the bottom line is the status of device, if any abnormal present, the corresponding record will
display at here. Record displays when abnormal disappear; if transfer acted, here display
corresponding action event for prompt. Check event details in event record.
Run Moniotr
Parameter Set
Language
MAIN
MENU
Scheme
Telesignalling Event
Self-checking Event
Event Record
Operate Event
Protection Event
Record Waveform Event
Print Event
Manual Print
Device Debug
Time Adjust
Driving
Communication
Record Waveform
Telecontrol
Event Clear
Other Function
Password Set
Product Information
Manufacturer Founction
Revert Way
Measure Debug
Telemetering Cycle
Resume Default Value
Reset Count
Linkage Logic
Output Board Choose
Software Updata
and bus of 7 AC voltage channels and 6 current channels. After enter the run monitor main menu
through pressing Enter, the user can choose primary value and secondary value to examine.
Enter to put in. The device provides ten set point areas numbered from 0~9. Before enter Set
Point Monitor, you need to choose set point area, Current Set Point Area is currently running set
point area number, Select Set Point Area is the set point area which need to be monitoredpress
+/- to change Select Set Point Area number. You can examine set point of ten areas. If the set point
area selected is the same of the current one, then you can check the set point of current area.
Note that: Set Point Monitor is only used for check set point, but not for modifying. If you want
to modify the set point, enter Set Point and input the right password.
password is 0000 and you can set new password as you like) to enter Set Point page. There are
three setting contents in the page, which is shown in figure 10:
Set Point
Set Point Switch
Set Point Modify
Set Point Copy
Device Status: Normal
number, press ENTER to complete the switch. For example, Current Set Point Area is 2, Set
Point Select Area is 0, as shown in figure 11, after press enter button, the Current Set Point
Area is modified to 0, as shown in fig. 12.
This is for modifying set point with different type in different area. After enter Set Point
Modify, you should firstly choose the area number which needs to be modified. Current Set Point
Area shows the area number that device currently uses, Set Point select area shows the area
number that you want to modify. Press +/- to change the select area numberpress Enter to enter
the corresponding page. There is four type set point for the device: Reverse Supply transfer Set
Point, Manual Switch Set Point, Protection Set Point and Expand Set point, and the menu is shown
in figure 13. You can consult Appendix 1 Set point table and setting introduction to modify set point.
Please pay attention to the range of value. If the scope is exceededthe modified value will not be
memorized. Press Enter to save the set after modifying, and return to previous menu.
20
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
change the number of set point area. Press up, Down to move cursor, choose the content which
you want to amend. Press Enter to copy date from Source Set Point Are to Aim Set Point
Area. For example, if you want to copy date from set point area 1 to set point area 2firstly
set
Source Set Point Area to 1as shown in figure 14and then press Down to move cursor to Aim
Set Point Area, set Aim Set Point Area to 2as shown in figure 15. After pressing Enter, the
set point will be copied from Set Point Area 1 to Set Point Area 2.
Telesignalling Parameter:
This is used for setting 17 channels the anti-trill time and digital input propertynormal
open/normal close of Telesignalling sampling. Press Up, Down to turn over pages and
21
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
choose digital input with different number to set. Press LeftRight to select the anti-trill time
and digital input property of this route, press +/- to set the time value and convert the digital input
property between normal open and normal close. As shown in figure 17. In the figure, the number
01 on top left corner represents the current digital input sequence number, the number 16 on
top right corner represents that there are 17 routes of signal totally. After finish the settingpress
Enter to save, and return to previous menu.
AC Parameters:
These parameters are for setting current transformer and potential transformer ratio, secondary
rated value of TV/TA. Press Up and Down to turn over page and choose AC variable with
different sequence number to set. Press Left and Right to choose rated value and ratio
property of this route of AC variable secondary TV/TA, press +/- to set the rated value and ratio.
The primary rated value of instrument transformer is calculated automatically and is shown in
figure 18. In the figure, the number 1 on top left corner represents current AC variable
sequence number, the number 9 on top right corner represents that there are 9 routes of AC
variable totally. After finish the settingpress Enter to save, and return to the previous menu.
Figure 18 AC Parameters
Communication Parameter:
This function is for setting series interface, Ethernet interface and CAN Bus communication
parameters. After entering Communication Parameter page, press Up, Down to choose the set
communication type. Choose Network Parameter to enter Network Parameter Set page, you can set
IP, subnet Mask and Gateway of network, as shown in figure 19. Choose CAN Bus to enter the
CAN Bus and set the parameters. You can set CAN Bus Communication Address, Baud Ratio, as
22
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
Net 2 Set
IP Addr 192.000.000.002
Mask
255.255.000.000
Gateway 192.000.000.001
IP Addr 192.001.000.002
Mask
255.255.000.000
Gateway 192.001.000.001
Note:
In RS485 series port 1-3 parameter Setting, Communication Rule SID-TEST is used to test series
port communication link hardware.
RS485 series port 1 is used to communicate with background supervisory control.
Communication rule which contains IEC60870-5-103, Modbus is supplied to users for choosing.
Communication AddressBaud RatioCheck Way can be set according to the setting area.
RS485 series port 2 is used to communicate with printer. Baud Ratio is fixed to 9600 bpsCheck
Way is No Check. Note that when the device is connected with printer directlyyou must choose
EPSON ESC/P rule. And when the device connects with printer through print server SID-401PS,
you must choose SID-401PS rule. Supervision communication can choose IEC60870-5-103
Modbus.
RS485 series port 3 is used to communicate with GPS. Communication rule contains
IRIG-BRS485IRIG-BTTLWEIKOT.
Language Setting:
This is for setting page layout with Chinese or English language. Press up, down to choose
23
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
Scheme Set:
This is for setting scheme that consists with locale primary electric main connection, as shown in
figure 22. The characteristic of every scheme and primary main bus connection is introduced in
presentation of logic scheme in Appendix 3. Press +/- to set the serial number of scheme. After
finish the setting, press Enter to save, and return to previous menu. Return to main menu, you can
see the scheme number running currently on the top right corner.
Telesignalling Event:
It is for displaying telesignalling event happened. The telesignalling event can be divided into
real telesignlling event (real status change event of 16 real digital input signal channels) and virtual
telesignalling event (action event is recorded in the process of auto-transfer and manual switch).
Press up, down to turn over page. The event is listed by time, and the number of latest event is
1.
Protection Event:
It is used for displaying protection or switch event which had happened. Press up, down to
turn over page. The event is listed by time, and the number of latest event is 1.
Record Waveform Event:
24
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
This is used for displaying recorded event and waveform. Events are listed by time. The last
event gets 1.
Operation Event:
It is for displaying local operation (remote debug, modify set point, parameter etc) and remote
control that have happened. Press up, down to turn over page. The event is listed by time, and
the number of latest event is 1.
Self Check Event:
It is used to display happened device self check events, mainly are self diagnose information of
important element on master CPU. Press up, down to turn over page. The event is listed by time,
and the number of latest event is 1.
Used to printing different types of events. Enter into manual print page, select print event, then it
will go into the print event page as shown in Figure 24. Press up, down, left, right to move the
cursor, press + / - key to modify the cursor line. The event type, paper type, starting time, ending
time can be set respectively, and print out the event record which occurred between starting time
and ending time. Note the starting time must be less than or equal to the end time, then it can be
print correctly. After setting, press the Enter key to start printing the corresponding events.
Print Set-point:
Used to printing set-points in different areas. Enter into the manual print page, select the print
25
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
set-point, then it will go into print set-point page as shown in Figure 25. Press up, down key to
move the cursor to select the set-point area, paper type or print type. Press + / - key to modify the
cursor line. After setting, it will come out the dialog box "confirm the implementation", press the
Enter key to execute the print options in the print set-point area, press exit key will not
implemented.
6.9.1
Device Debug
Device Debug contains five items, which include: Drive Debug, Communication Debug, Record
Waveform Debug, Telecontrol Debug, and Breaker Time Test.
Drive Debug
This is used for output relay testing. Entering Drive Debug needs right password. When in
Drive Debug, the logic control function and the protection will quit. The drive debug page layout
is shown in figure 27, the number on the top right corner (12 is backup, 14 is control circuit board,
22 is output expansion board), the driving number changed as the output board altered, if it displays
1 on the top left corner, it means that its the first output circuit driving currently. Press Up/Down
to move cursor to choose output test circuit. If test item is Output, press Enter to control the
corresponding relay output, and then Output will become Return. Press Enter again will
control corresponding relay return. Note that, the cursor can be moved only when the relay is at
Return status.
26
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
Communication Debug:
This is used for testing communication channel. It can transmit virtual input signal, virtual
measurement signal to background supervisory control softwarecheck the parameters of the
communication link and the background. Communication debug contains two options:
Telesignalling Debug, Telemetering Debug.
Enter Communication Debug to choose Telesignalling Debug, press enter to put in
Telesignalling Debug page, as shown in figure 28There are 120 channels of Telesignalling signal
(event virtual Telesignalling and input real Telesignalling) to dummy transmitted. Press +/- to
switch test option clear/setup. When it is clear, press Enter and then it will transmit 0.
When it is setup, press Enter and then it will transmit 1.
Enter Communication Debug, choose Telemetering Debug and enter Telemetering Debug
page which is shown in figure 29there are 13 channels of telemetering signal which can be dummy
transmitted. Press +/- to manual set telemetering value, press Enter to transmit telemetering
data to background.
Enter to trigger a record wave event, as shown in figure 6.26And solidify record wave data needs
about 3 seconds.
27
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
Telecontrol Debug
This function is used for simulating telecontrol switch on the spotand testing respond action to
telecontrol the device operation. The Telecontrol Debug page layout is shown in figure 31, 7on
the top right corner indicates that therere 7 circuits telecontrol objectives, 1on the top left corner
indicates that its the first circuit runningcurrently. Press +/- to switch test option off/ on.
After press Enter, dialog box Sure? appears, then press Enter again to perform corresponding
telecontrol operation, or press Exit to cancel corresponding telecontrol operation.
6.9.2
Time Adjust
This function is used for adjusting current run time, Time Adjust page is shown in figure 32.
Press Left, Right to move the cursor, press +/- to change the time value, press Enter to
confirm the time adjusted.
6.9.3
Event Clear
This is used for clearing every kinds of event record and reset count. The Event Clear page is
shown in figure 33. Press Up Down to choose the option which to be cleared, press Enter to
execute it.
6.9.4
Password Set
Password Set page is shown in figure 34. This function is for setting new password. The
password is 0000 when the device leave factory, user can set new password by himself. Please pay
attention that when set new password, it need to input new password twice and they must be same.
Once the setting is successful, you must remember the new one in order to operate next time.
6.9.5
Product Information
Product Information mainly contains current version, CRC verify code, contact phone and our
companys address, as shown in figure 35. If technique support is needed, you can contact with us
through contact manner.
6.9.6
Manufactory Function
Factory Function contains eight functions: Revert Way, Measure Debug, Telemetering Cycle,
Resume Default Value, Reset Count, linkage Logic and Output Board Choose. They are mainly
provided for personnel of our company to use. The user neednt know.
29
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
POWER
JK7
EDO
JK5
EDI
CPU
JK4
JK3
10
10
10
10
11
11
11
12
12
12
13
13
13
14
14
14
15
15
15
16
16
16
17
18
19
20
TV
TA
JK2
JK1
10
10
11
11
12
12
30
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
32
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
Instruction
CAN Communication
Interface
RS485 Communication
Interface 1
RS485 Communication
Interface 2
Signal Reset
24V
Weak
Backup
Current
Input
GPS Second Pulse
GPS485 Interface
Net Communicate Interface
Definition
Signification
TX+
Send signal+
33
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
TX-
Send signal-
RX+
Receive signal +
N/C
Vacancy
N/C
Vacancy
RX-
Receive signal -
N/C
Vacancy
N/C
Vacancy
The connection between multi-device and one printer server as follow: (Two device adopt
RS485multi-device adopt Ethernet).
Note: When device communicate with GPS, before connect corresponding terminals please turn
GPS communication signal to RS 485 communicate mode.
34
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
Note:
1 KM select DC 220V or 110V.
2 Device input signal uses electrical independent contact mode, so please connect public point with
negative pole of exterior input signal.
If the second output board is TRIP-Jk6, output board is control circuit, the terminals sketch map
46:
If the second output board is OUT-JK6, output board is expansion output board the terminals
sketch map 47:
Code
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Name
Public Point
Expansion Output 1
Expansion Output 2
Public Point
Expansion Output 3
Expansion Output 4
Public Point
Expansion Output 5
Expansion Output 6
NC
Public Point
Expansion Alarm 1
Public Point
Expansion Alarm 2
Public Point
Expansion Alarm 3
Public Point
Expansion Alarm 4
NC
NC
Instruction
Expansion
Output 12
Expansion
Output 34
Expansion
Output 56
Not Connect
Expansion
Alarm 1
Expansion
Alarm 2
Expansion
Alarm 3
Expansion
Alarm 4
Not Connect
Note:
The six outputs of the breaker in EDO_JK5 have different definition in different scheme. Please
refer to terminals instructions in appendix 3 for detail.
37
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
If all checking above are correct, the device is out of question. To be cautiously, you can renew
device set-point; observe the device action to confirm validity of set point.
Device fault alarm
If the device hardware went wrongLCD shows the fault information and send alarm, then lock
the output circuit of protection. The device will send alarm signal when lost power.
GPS time calibrating
The device receive information as year, month, date, hour, minute and second by communicate
with main automation transformer substation. Moreover, the device collocate a GPS time
calibrating communication interface and a second pulse input interface, which can connect to GPS
directly or connect to second pulse output in substation, time calibrating precision is less than 1 ms.
Net communication
The device can communicate with microcomputer monitor or protection manager, the
communicate interface can be RS-485 or Ethernet
Dispose of abnormity
38
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
Table 3
Abnormal phenomenon
Solution
Line 1 TV disconnection
Line 2 TV disconnection
Line 3 TV disconnection
Bus 1 TV disconnection
Bus 2 TV disconnection
A/D fault
Output fault
Setp-oint fault
Transfer channel
39
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
40
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
setting
System
Default
set-point
Instruction
To choose Unidirectional Switch (only transfer from work
Switch Direction
01
[Unidirectional
Switch
Bi-directional Switch]
02
03
Pulse Of Trip
[020 -- 999]ms
Bi-directional
Switch
200ms
1 [Ua Ub Uc Uab
Ua
Ubc Uca]
05
2 [Ua Ub Uc Uab
user customize
For setting the type of incomer voltage, which can be
0.0
Ua
Ubc Uca]
07
0.0
3 [Ua Ub Uc Uab
Ua
Ubc Uca]
09
10
[0 +30 -30]
TA of Input Line 1
[None Having]
0.0
None
41
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
applied by user customize
To set TA connection between line 2 and device, for
11
TA of Input Line 2
None
[None Having]
12
TA of Input Line 3
None
[None Having]
90.0%Un
Line
[85.0 --100.0] %Un
14
15
16
customize
Low- Volt.
Set of Line
90.0%Un
80.0%Un
70.0%Un
0.20S
Volt.
[0.02 10.00]S
18
19
Mis-trip
Start
Delay
[0.05 5.00]S
The delay ids used for ensure loss power when accident
0.05S
Bus
20.0%Un
The delay ids used for ensure loss power when accident
1.00S
of Switch
30.00S
Auto Parallel
02
42
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
03
04
05
06
07
08
09
10
11
0.50Hz
Clamp of Decoupling
[Off, On]
Delay of Decoupling
[0.05 5.00]S
Bus
Breaker
Closing
10.0
On
0.20S
100ms
Protection set-point
01
Bus
Over
02
Breaker
Breaker
Current
Off
Over
Current
6.00A
[1.00 99.99]A
Bus
03
Breaker
Over
0.2S
10.00]S
04
Bus
Breaker
Current
Over
[On, Off]
Current 2
Bus
05
Breaker
Off
Over
Current
5.00A
[1.00 99.99]A
Bus
06
Breaker
Over
0.50S
10.00]S
07
Bus
Breaker
Over
Off
43
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
Current haste
Bus
08
user customize
[On, Off]
Breaker
Over
5.00A
[1.00 99.99]A
Bus
09
Breaker
Current
Haste
Over
Time
0.20S
[0.10 3.00]S
10
11
12
13
14
15
16
17
18
19
20
21
Bus 1 TV Line-break
Alarm [ On ,Off]
Bus 2 TV Line-break
Alarm
[ On ,Off]
Line 1 TV Line-break
Alarm
[ On ,Off]
Line 2 TV Line-break
Alarm
[ On ,Off]
Line 3 TV Line-break
Alarm
[ On ,Off]
10.00S
10.00S
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
02
100ms
03
TA of Input Line 4
[None Having]
None
44
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
To set TA connection between line 5 and device, for
04
TA of Input Line 5
[None Having]
None
05
TA of Input Line 6
[None Having]
None
[All
switches,
incomer
Off
switches, Off]
07
08
09
10
11
12
13
Zero
set-point 1
Zero
set-point 2
Zero
set-point 3
Zero
set-point 4
Zero
set-point 5
Zero
set-point 6
Zero
set-point 7
dimension
[0000 - 9999]
dimension
[0000 - 9999]
dimension
[0000 - 9999]
dimension
[0000 - 9999]
dimension
[0000 - 9999]
dimension
[0000 - 9999]
dimension
[0000 - 9999]
0000
Backup
0000
Backup
0000
Backup
0000
Backup
0000
Backup
0000
Backup
0000
Backup
Remark:
System set-point
This is used for setting system value which is used in common.
45
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
Code
Name
Range
Default value
Telesignalling parameter
Anti-trill time
01 - 16
[ 1-999 ]ms
10ms
[Open/Close]
Open
time
Input attribute
01 - 16
AC parameter
01
Bus 1 voltage
[1- 9999]
100
TV
02
Bus 2 voltage
[1- 9999]
100
Ratio
03
Line 1 voltage
[1- 9999]
100
04
Line 2 voltage
[1- 9999]
100
05
Line 3 voltage
[1- 9999]
100
06
[1- 9999]
100
TA
07
Line 1 current
[1- 9999]
100
Ratio
08
Line 2 current
[1- 9999]
100
09
Line 3 current
[1- 9999]
100
10
[1- 999] V
100 V
11
[1- 999] V
100 V
12
[1- 999] V
100 V
Secondary
13
[1- 999] V
100 V
rated value
14
[1- 999] V
100 V
15
Bus
secondary
[1- 999] V
5A
16
[1- 999] V
5A
17
[1- 999] V
5A
18
[1- 999] V
5A
breaker
rated current
Communication parameter
Network
communication
01
IP
[002 -- 255]
192.0.0.49
Mask
[-]
255.255.0.0
Gateway
[-]
192.0.0.1
Communication address
[0 - 127]
46
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
Communication protocol
01
[IEC60870-5-103Modbus
SID-TEST
SID-TEST]
Communication velocity
9600 bps
Check way
No check
RS 485
parity]
series
Communication address
[0 - 127]
communication
Communication protocol
IEC60870-5-103Modbus
02
SID-TEST]
Communication velocity
[300bps -- 19200bps ]
9600 bps
Check way
No check
parity]
Communication address
[0 - 127]
Communication protocol
[SID-TEST
IRIG-BRS485
03
1
SID-TEST
IRIG-BTTLWEIKOT]
Communication velocity
9600 bps
Check way
No check
parity]
CAN Bus
communication
01
Communication address
[0 - 999]
001
Communication velocity
[20kbps50kbps125kbps]
125kbps
Language
Language
01
Chinese
[Chinese/English]
Chinese
Scheme
Scheme
01
Scheme
[1 -- 20]
Remark
Telesignalling parameter
This is used for setting input signal attribute and anti-disturb time, the default value: open,
10 ms
Ac parameter
This is used for setting AC current and voltage transformer ratios. The secondary rated
47
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
48
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
Control logic
Normal operating:
1 DL closedbus I energized by supply 1 through 1 DL.
2 DL closedbus II energized by supply 2 through 2 DL.
Bus breaker tripped, bus I, bus II backing for each other.
Device energized, if the voltage of bus I and bus II are both higher than voltage set-point
respectively, the device begin to charge 10 s, then system enter fault monitor state.
Backup switch logic:
When bus I voltage low or 1DL mis-trip, bus II voltage is higher than under-voltage set-point,
then trip 1DL, after the un-volt. test and delay condition of bus I are satisfied, close bus breaker.
When bus II voltage low or 2DL mis-trip, bus I voltage is higher than under-voltage set-point,
then trip 2DL, after the un-volt. test and delay condition of bus II are satisfied, close bus breaker.
(Only valid if bi-direction transfer is selected).
Manual transfer logic:
When bus breaker closed, 1DL or 2DL tripped, and the reserve supply has voltage; or 1DL and
49
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
2DL closed, bus breaker tripped, and the external input signal mode 1 or mode 2 closed, the manual
switch function of the device is available. The transfer logics in different transfer mode as follow:
[Series Switch]:
Both bus breaker and 2DL are closed, 1DL tripped, and incomer 1 voltage is higher than
under-voltage set-point, if manual switch signal presence, trip bus breaker and close 1DL when the
un-volt. test condition of bus I is satisfied.
Both bus breaker and 1DL are closed, 2DL tripped, and incomer 2 voltage is higher than
under-voltage set-point, if manual switch signal presence, trip bus breaker and close 2DL when the
un-volt. test condition of bus II is satisfied.
Both 1DL and 2DL are closed, bus breaker tripped, the external input signal mode 1 closed, mode
2 tripped, and incomer 1 voltage is higher than under-voltage set-point, if manual switch signal
presence, trip 2DL , close bus breaker when the un-volt. test condition of bus II is satisfied.
Both 1DL and 2DL closed, bus breaker tripped, the external input signal mode 2 closed, mode 1
tripped, and incomer 2 voltage is higher than under-voltage set-point, if manual switch signal
presence, trip 1DL and close bus breaker when the un-volt. test condition of bus I is satisfied.
[Auto Parallel]:
Both bus breaker and 2DL are closed, 1DL tripped, and incomer 1 voltage is higher than
under-voltage set-point, if manual switch signal presence, close 1DL when the parallel
synchronization condition is satisfied, trip bus breaker after closed successfully, if tripped
successfully, then the transfer process is over, otherwise decoupling and trip 1DL; (Note: The
decoupling function can be applied by user customize)
Both bus breaker and 1DL are closed, 2DL tripped, and incomer 2 voltage is higher than
under-voltage set-point, if manual switch signal presence, close 2DL when the parallel
synchronization condition is satisfied, trip bus breaker after closed successfully, if tripped
successfully then the transfer process is over, otherwise decoupling and trip 2DL; (Note: The
decoupling function can be applied by user customize)
Both 1DL and 2DL are closed, bus breaker tripped, and mode 1 closed, if manual switch signal
presence, close bus breaker when the parallel synchronization condition is satisfied, trip 2DL after
closed successfully, if tripped successfully then the transfer process is over, otherwise decoupling
and trip bus breaker; (Note: The decoupling function can be applied by user customize)
Both 1DL and 2DL are closed, bus breaker tripped, and mode 2 closed, if manual switch signal
presence, close bus breaker when the parallel synchronization condition is satisfied, trip 1DL after
closed successfully, if tripped successfully then the transfer process is over, otherwise decoupling
50
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
and trip bus breaker; (Note: The decoupling function can be applied by user customize)
[Semiauto Parallel]:
The parallel closing process is the same as [Auto Parallel], if closing successfully then the
transfer process is over.
[Parallel & Series]:
Detect the parallel synchronization conditions as the [Auto Parallel] logic, if the synchronization
conditions can not satisfied in the detect delay then choose [Series Switch].
After manual switch, the device will return to normal operating mode.
Terminal instruction:
Control logic
Normal operating:
Bus energized by supply 1 through 1 DL, bus breaker. Power supply 2 is used for backing
through 2DL.
Device energized, if backup supply voltage and bus voltage are higher than voltage set-point
respectively, the device begin to charge 10 s, then system enter fault monitor state.
System switches logic:
Bus breaker and 1DL are closed, 2DL tripped, if bus low-voltage or 1DL mis-tripped, voltage of
power supply 2 is higher than under-voltage set-point, then trip 1DL, after the un-volt. test and
delay condition of bus are satisfied, close 2DL.
Bus breaker and 2DL are closed, 1DL tripped, if bus low-voltage or 2DL mis-tripped, voltage of
power supply 1 is higher than under-voltage set-point, then trip 2DL, after the un-volt. test and
delay condition of bus are satisfied, close 1DL. (Only valid if bi-direction transfer is selected).
Manual transfer logic:
When bus breaker closed, 1DL or 2DL tripped, and the reserve supply has voltage, the manual
switch function of the device is available. The transfer logics in different transfer mode as follow:
[Series Switch]:
Both bus breaker and 2DL closed, 1DL tripped, and incomer 1 voltage is higher than
under-voltage set-point, if manual switch signal presence, trip 2DL, after the un-volt. test and delay
condition of bus are satisfied, close 1DL.
Both bus breaker and 1DL closed, 2DL tripped, and incomer 2 voltage is higher than
under-voltage set-point, if manual switch signal presence, trip 1DL, after the un-volt. test and delay
condition of bus are satisfied, close 2DL.
52
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
[Auto Parallel]:
Both bus breaker and 2DL closed, 1DL tripped, and incomer 1 voltage is higher than
under-voltage set-point, if manual switch signal presence, close 1DL when the parallel
synchronization condition is satisfied, trip 2DL after closed successfully, if tripped successfully then
the transfer process is over, otherwise decoupling and trip 1DL; (Note: The decoupling function can
be applied by user customize)
Both bus breaker and 1DL closed, 2DL tripped, and incomer 2 voltage is higher than
under-voltage set-point, if manual switch signal presence, close 2DL when the parallel
synchronization condition is satisfied, trip 1DL after closed successfully, if tripped successfully then
the transfer process is over, otherwise decoupling and trip 2DL; (Note: The decoupling function can
be applied by user customize)
[Semiauto Parallel]:
The parallel closing process is the same as [Auto Parallel], if closing successfully then the
transfer process is over.
[Parallel & Series]:
Detect the parallel synchronization conditions as the [Auto Parallel] logic, if the synchronization
conditions can not satisfied in the detect delay then choose [Series Switch].
After manual switch, the device will return to normal operating mode.
Terminal instruction:
53
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
AC Current Value (JK1)
Code
Name
1
ML-Ia
2
ML-Ia'
3
ML-Ib
4
ML-Ib'
5
ML-Ic
6
ML-Ic'
7
1L-I1
8
1LI1'
9
2L-I2
10
2L-I2'
11
NC
12
NC
Output(Jk5)
Code
Name
1
Public Point
2
1DL Tripping
3
1DL Closing
4
Public Point
5
2DL Tripping
6
2DL Closing
7
Public Point
8
NC
Bus Breaker Tripping
9
10
Public Point
11
NC
Bus Breaker Closing
12
Signal Public Point
13
Backup Switch Act
14
External Fault Alarm
15
16
Device Alarm
17
NC
18
NC
19
Device Blocking
20
Instruction
Link Line Phase A
Current
Link Line Phase B
Current
Link Line Phase C
Current
Incomer 1 Current
Incomer 2 Current
Not Connected
Instruction
1DL Breaker
Transfer Output
2DL Breaker
Transfer Output
Bus Breaker
Tripping Output
Bus Breaker
Closing Output
Central Signal
Alarm Output
Instruction
Bus Phase A Voltage
Bus Phase B Voltage
Bus Phase C Voltage
Not Connected
Not Connected
Not Connected
Incomer 1 Voltage
Incomer 2 Voltage
Not Connected
Input(JK3)
Code
Name
1
1DL Breaker Aux. Contact
2
2DL Breaker Aux. Contact
3
Bus Breaker Aux. Contact
4
NC
5
General Blocking
6
-KM
7
NC
8
NC
9
NC
10
NC
11
NC
12
NC
13
NC
14
NC
15
Signal Reset
16
Manual Switch Input
Not Connected
Central Signal
Alarm Output
Control logic
Normal operating:
Bus energized by supply 1 through 1 DL. Power supply 2 is used for backing through 2DL.
Or bus energized by supply 2 through 2DL. Power supply 1 is used for backing through 1DL.
(Only valid if bi-direction transfer is selected).
Device energized, if backup supply and bus voltage are higher than voltage set-point
respectively, the device begin to charge 10 s, then system enter fault monitor state.
Backup switch logic:
1DL closed, 2DL tripped, if bus low-voltage or 1DL mis-tripped, voltage of power supply 2 is
higher than under-voltage set-point, then trip 1DL, after the un-volt. test and delay condition of bus
are satisfied, close 2DL.
2DL closed, 1DL tripped, if bus low-voltage or 2DL mis-tripped, voltage of power supply 1 is
higher than under-voltage set-point, then trip 2DL, after the un-volt. test and delay condition of bus
are satisfied, close 1DL. (Only valid if bi-direction transfer is selected).
Manual transfer logic:
When 1DL or 2DL tripped, and the voltage of reserve supply is higher than under-voltage
set-point, the manual switch function of the device is available. The transfer logics in different
transfer mode as follow:
[Series Switch]:
2DL closed, 1DL tripped, and incomer 1 voltage is higher than under-voltage set-point, if manual
switch signal presence, trip 2DL, after the un-volt. test and delay condition of bus are satisfied,
close 1DL.
1DL closed, 2DL tripped, and incomer 2 voltage is higher than under-voltage set-point, if manual
switch signal presence, trip 1DL, after the un-volt. test and delay condition of bus are satisfied,
close 2DL.
[Auto Parallel]:
2DL closed, 1DL tripped, and incomer 1 voltage is higher than under-voltage set-point, if manual
switch signal presence, close 1DL when the parallel synchronization condition is satisfied, trip 2DL
after closed successfully, if tripped successfully then the transfer process is over, otherwise
decoupling and trip 1DL; (Note: The decoupling function can be applied by user customize)
1DL closed, 2DL tripped, and incomer 2 voltage is higher than under-voltage set-point, if manual
switch signal presence, close 2DL when the parallel synchronization condition is satisfied, trip 1DL
after closed successfully, if tripped successfully then the transfer process is over, otherwise
55
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
decoupling and trip 2DL; (Note: The decoupling function can be applied by user customize)
[Semiauto Parallel]:
The parallel closing process is the same as [Auto Parallel], if closing successfully then the
transfer process is over.
[Parallel & Series]:
Detect the parallel synchronization conditions as the [Auto Parallel] logic, if the synchronization
conditions can not satisfied in the detect delay then choose [Series Switch].
After manual switch, the device will return to normal operating mode.
Terminal instruction:
AC Current Value (JK1)
Code
Name
1
NC
2
NC
3
NC
4
NC
5
NC
6
NC
7
1L-I1
8
1L-I1'
9
2L-I2
10
2L-I2'
11
NC
12
NC
Output(Jk5)
Code
Name
1
Public Point
2
1DL Tripping
3
1DL Closing
4
Public Point
5
2DL Tripping
6
2DL Closing
7
Public Point
8
NC
9
NC
10
Public Point
11
NC
12
NC
13 Signal Public Point
14 Backup Switch Act
External Fault Alarm
15
16
Device Alarm
17
NC
18
NC
19 Device Blocking +
20
Device Blocking -
Instruction
Not Connected
Not Connected
Not Connected
Incomer 1 Current
Incomer 2 Current
Not Connected
Instruction
1DL Breaker
Transfer Output
2DL Breaker
Transfer Output
Not connected
Not connected
Central Signal
Alarm Output
Instruction
Bus Phase A Voltage
Bus Phase B Voltage
Bus Phase C Voltage
Not Connected
Not Connected
Not Connected
Incomer 1 Voltage
Incomer 2 Voltage
Not Connected
Input(JK3)
Code
Name
1
1DL Breaker Aux. Contact
2
2DL Breaker Aux. Contact
3
NC
4
NC
5
General Blocking
6
-KM
7
NC
8
NC
9
NC
10
NC
11
NC
12
NC
13
NC
14
NC
15
Signal Reset
16
Manual Switch Input
Not connected
Central Signal
Alarm Output
Control logic
Normal operating:
Bus energized by supply 1 through 1DL. Power supply 2 is used for backing through 2DL.
Or bus energized by supply 2 through 2DL. Power supply 1 is used for backing through 1DL.
(Only valid if bi-direction transfer is selected).
Device energized, if bus voltage is higher than voltage set-point, the device begin to charge 10
s, then system enter fault monitor state.
Backup switch logic:
1DL closed, 2DL tripped, if bus I low-voltage or 1DL mis-tripped, then trip 1DL, after the
un-volt. test and delay condition of bus are satisfied, close 2DL.
2DL closed, 1DL tripped, if bus I low-voltage or 2DL mis-tripped, then trip 2DL, after the
un-volt. test and delay condition of bus are satisfied, close 1DL. (Only valid if bi-direction transfer
is selected).
Manual transfer logic:
When 1DL or 2DL tripped, the manual switch function of the device is available. For there has
no voltage transformer in this scheme, so only series switch is available, and parallel & series is
also valid. The series switch logic as follow:
[Series Switch]:
2DL closed, 1DL tripped, if manual switch signal presence, trip 2DL, after the un-volt. test and
delay condition of bus are satisfied, close 1DL.
1DL closed, 2DL tripped, if manual switch signal presence, trip 1DL, after the un-volt. test and
delay condition of bus are satisfied, close 2DL.
After manual switch, the device will return to normal operating mode.
57
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
Terminal instruction:
AC Current Value (JK1)
Code
Name
1
NC
2
NC
3
NC
4
NC
5
NC
6
NC
7
1L-I1
8
1L-I1'
9
2L-I2
10
2L-I2'
11
NC
12
NC
Output(Jk5)
Code
Name
1
Public Point
2
1DL Tripping
3
1DL Closing
4
Public Point
5
2DL Tripping
6
2DL Closing
7
Public Point
8
NC
9
NC
10
Public Point
11
NC
12
NC
13 Signal Public Point
14 Backup Switch Act
External Fault Alarm
15
16
Device Alarm
17
NC
18
NC
19
Device Blocking
20
Instruction
Not Connected
Not Connected
Not Connected
Incomer 1 Current
Incomer 2 Current
Not Connected
Instruction
1DL Breaker
Transfer Output
2DL Breaker
Transfer Output
Not connected
Not connected
Central Signal
Alarm Output
Instruction
Bus Phase A Voltage
Bus Phase B Voltage
Bus Phase C Voltage
Not Connected
Not Connected
Not Connected
Not Connected
Not Connected
Not Connected
Input(JK3)
Code
Name
1
1DL Breaker Aux. Contact
2
2DL Breaker Aux. Contact
3
NC
4
NC
5
General Blocking
6
-KM
7
NC
8
NC
9
NC
10
NC
11
NC
12
NC
13
NC
14
NC
15
Signal Reset
16
Manual Switch Input
Not connected
Central Signal
Alarm Output
58
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
Control logic
Hot backup: The transformer of backup supply is in no-load status when normal operating, the
high-voltage side breaker connected with the backup supply when in closed status.
Normal operating:
Bus energized by supply 1 through 1DL and 3DL. Power supply 2 is used for backing through
2DL.
Or bus energized by supply 2 through 2DL and 4DL. Power supply 1 is used for backing
through 1DL. (Only valid if bi-direction transfer is selected).
Device energized, if backup supply voltage and bus voltage are higher than voltage set-point
respectively, the device begin to charge 10 s, then system enter fault monitor state.
Backup switch logic:
1DL, 3DL and 4DL are closed, 2DL tripped, if bus low-voltage or 1DL mis-tripped, voltage of
power supply 2 is higher than under-voltage set-point, then trip 1DL, after the un-volt. test and
delay condition of bus are satisfied, close 2DL.
2DL, 3DL and 4DL are closed, 1DL tripped, if bus low-voltage or 2DL mis-tripped, voltage of
power supply 1 is higher than under-voltage set-point, then trip 2DL, after the un-volt. test and
delay condition of bus are satisfied, close 1DL. (Only valid if bi-direction transfer is selected).
Manual transfer logic:
When 1DL, 3DL and 4DL are closed, 2DL tripped, or 2DL, 3DL and 4DL are closed, 1DL
tripped, voltage of backup supply is higher than under-voltage set-point, the manual switch function
of the device is available. The transfer logics in different transfer mode as follow:
[Series Switch]:
2DL, 3DL and 4DL are closed, 1DL tripped, and incomer 1 voltage is higher than under-voltage
set-point, if manual switch signal presence, trip 2DL, after the un-volt. test and delay condition of
59
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
bus are satisfied, close 1DL when the bus un-volt. test conditions satisfied.
1DL, 3DL and 4DL are closed, 2DL tripped, and incomer 2 voltage is higher than under-voltage
set-point, if manual switch signal presence, trip 1DL, after the un-volt. test and delay condition of
bus are satisfied, close 2DL.
[Auto Parallel]:
2DL, 3DL and 4DL are closed, 1DL tripped, and incomer 1 voltage is higher than under-voltage
set-point, if manual switch signal presence, close 1DL when the parallel synchronization condition
is satisfied, trip 2DL after closed successfully, if tripped successfully then the transfer process is
over, otherwise decoupling and trip 1DL; (Note: The decoupling function can be applied by user
customize)
1DL, 3DL and 4DL are closed, 2DL tripped, and incomer 2 voltage is higher than under-voltage
set-point, if manual switch signal presence, close 2DL when the parallel synchronization condition
is satisfied, trip 1DL after closed successfully, if tripped successfully then the transfer process is
over, otherwise decoupling and trip 2DL; (Note: The decoupling function can be applied by user
customize)
[Semiauto Parallel]:
The parallel closing process is the same as [Auto Parallel], if closing successfully then the
transfer process is over.
[Parallel & Series]:
Detect the parallel synchronization conditions as the [Auto Parallel] logic, if the synchronization
conditions can not satisfied in the detect delay then choose [Series Switch].
After manual switch, the device will return to normal operating mode.
Terminal instruction:
60
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
AC Current Value (JK1)
Code
Name
1
NC
2
NC
3
NC
4
NC
5
NC
6
NC
7
1L-I1
8
1L-I1'
9
2L-I2
10
2L-I2'
11
NC
12
NC
Output(Jk5)
Code
Name
1
Public Point
2
1DL Tripping
3
1DL Closing
4
Public Point
5
2DL Tripping
6
2DL Closing
7
Public Point
8
NC
9
NC
10
Public Point
11
NC
12
NC
13 Signal Public Point
14 Backup Switch Act
External Fault Alarm
15
16
Device Alarm
17
NC
18
NC
19
Device Blocking
20
Instruction
Not Connected
Not Connected
Not Connected
Incomer 1 Current
Incomer 2 Current
Not Connected
Instruction
1DL Breaker
Transfer Output
2DL Breaker
Transfer Output
Not connected
Not connected
Central Signal
Alarm Output
Instruction
Bus Phase A Voltage
Bus Phase B Voltage
Bus Phase C Voltage
Not Connected
Not Connected
Not Connected
Incomer 1 Voltage
Incomer 2 Voltage
Not Connected
Input(JK3)
Code
Name
1
1DL Breaker Aux. Contact
2
2DL Breaker Aux. Contact
3
3DL Breaker Aux. Contact
4
4DL Breaker Aux. Contact
5
General Blocking
6
-KM
7
NC
8
NC
9
NC
10
NC
11
NC
12
NC
13
NC
14
NC
15
Signal Reset
16
Manual Switch Input
Not connected
Central Signal
Alarm Output
Control logic
Cold backup: The transformer of backup supply is in no-power status when normal operating,
the double side breakers are disconnected.
Normal operating:
Bus energized by supply 1 through 1DL and 3DL. Power supply 2 is used for backing through
2DL and 4DL.
Or bus energized by supply 2 through 2DL and 4DL. Power supply 1 is used for backing
through 1DL and 3DL. (Only valid if bi-direction transfer is selected).
Device energized, if backup supply voltage and bus voltage are higher than voltage set-point
respectively, the device begin to charge 10 s, then system enter fault monitor state.
Backup switch logic:
1DL and 3DL closed, 2DL and 4DL tripped, if bus low-voltage or 1DL (3DL) mis-tripped,
voltage of power supply 2 is higher than under-voltage set-point, then trip 1DL and 3DL, after the
un-volt. test and delay condition of bus are satisfied, close 4DL, if 4DL closed successfully, then
close 2DL, the transient exciting current generated by close the transformer with no-load through
4DL may cause 4DL close fail.
2DL and 4DL closed, 1DL and 3DL tripped, if bus low-voltage or 2DL (4DL) mis-tripped,
voltage of power supply 1 is higher than under-voltage set-point, then trip 2DL, 4DL, after the
un-volt. test and delay condition of bus are satisfied, close 3DL, if 3DL closed successfully, then
close 1DL. (Only valid if bi-direction transfer is selected). As mentioned above, close the
transformer with no-load through 3DL may cause 3DL close fail.
Manual transfer logic:
When 1DL and 3DL closed, 2DL and 4DL tripped, or 2DL and 4DL are closed, 1DL and 3DL
tripped, voltage of backup supply is higher than under-voltage set-point, the manual switch function
of the device is available. The transfer logics in different transfer mode as follow:
[Series Switch]:
2DL and 4DL closed, 1DL and 3DL tripped, and incomer 1 voltage is higher than under-voltage
set-point, if manual switch signal presence, trip 2DL and 4DL, after the un-volt. test and delay
condition of bus are satisfied, close 3DL, if 3DL closed successfully, then close 1DL.
1DL and 3DL closed, 2DL and 4DL tripped, and incomer 2 voltage is higher than under-voltage
set-point, if manual switch signal presence, trip 1DL and 3DL, after the un-volt. test and delay
condition of bus are satisfied, close 4DL, if 4DL closed successfully, then close 2DL.
[Auto Parallel]:
62
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
2DL and 4DL closed, 1DL and 3DL tripped, and incomer 1 voltage is higher than under-voltage
set-point, if manual switch signal presence, close 3DL, then close 1DL when the parallel
synchronization condition is satisfied, trip 2DL and 4DL after closed successfully, if tripped
successfully then the transfer process is over, otherwise decoupling and trip 1DL and 3DL; (Note:
The decoupling function can be applied by user customize)
1DL and 3DL closed, 2DL and 4DL tripped, and incomer 2 voltage is higher than under-voltage
set-point, if manual switch signal presence, close 4DL, then close 2DL when the parallel
synchronization condition is satisfied, trip 1DL and 3DL after closed successfully, if tripped
successfully then the transfer process is over, otherwise decoupling and trip 2DL and 4DL; (Note:
The decoupling function can be applied by user customize)
[Semi-auto Parallel]:
The parallel closing process is the same as [Auto Parallel], if closing successfully then the
transfer process is over.
[Parallel & Series]:
Detect the parallel synchronization conditions as the [Auto Parallel] logic, if the synchronization
conditions can not satisfied in the detect delay then choose [Series Switch].
After manual switch, the device will return to normal operating mode.
For the transient exciting current generated by close the transformer with no-load may cause
transformer protection mis-trip, and re-trip the breaker in the supply side, this will lead the transfer
control fail. To solve this problem, we designed SID-3YL Inrush Suppresser. This device can
suppress the transient exciting current generated by close the transformer with no-load, and achieve
success at the first time. The suppresser can install on the operating box of 3DL and 4DL, and send
the control signal of 3DL or 4DL to the Inrush Suppresser, then the Suppresser will connect the
tripping, closing circuit to realize close successfully one time.
Terminal instruction:
63
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
AC Current Value (JK1)
Code
Name
1
NC
2
NC
3
NC
4
NC
5
NC
6
NC
7
1L-I1
8
1L-I1'
9
2L-I2
10
2L-I2'
11
NC
12
NC
Output(Jk5)
Code
Name
1
Public Point
2
1DL Tripping
3
1DL Closing
4
Public Point
5
2DL Tripping
6
2DL Closing
7
Public Point
8
3DL Tripping
9
3DL Closing
10
Public Point
11
4DL Tripping
12
4DL Closing
13 Signal Public Point
14 Backup Switch Act
External Fault Alarm
15
16
Device Alarm
17
NC
18
NC
19
Device Blocking
20
Instruction
Not Connected
Not Connected
Not Connected
Incomer 1 Current
Incomer 2 Current
Not Connected
Instruction
1DL Breaker
Transfer Output
2DL Breaker
Transfer Output
3DL Breaker
Transfer Output
4DL Breaker
Transfer Output
Central Signal
Alarm Output
Instruction
Bus Phase A Voltage
Bus Phase B Voltage
Bus Phase C Voltage
Not Connected
Not Connected
Not Connected
Incomer 1 Voltage
Incomer 2 Voltage
Not Connected
Input(JK3)
Code
Name
1
1DL Breaker Aux. Contact
2
2DL Breaker Aux. Contact
3
3DL Breaker Aux. Contact
4
4DL Breaker Aux. Contact
5
General Blocking
6
-KM
7
NC
8
NC
9
NC
10
NC
11
NC
12
NC
13
NC
14
NC
15
Signal Reset
16
Manual Switch Input
Not connected
Central Signal
Alarm Output
Scheme 7: Double backup transfer control (Exclusive backup, secondary backup supply has
no PT)
Wiring diagram as figure 60:
Normal operating:
Bus energized by supply 1 through 1DL, supply 2 and 3 is used for backup (supply 2 is primary
backup, 3 is secondary backup, 2 take precedence over 3), 1DL closed, 2DL and 3DL tripped;
Or bus energized by supply 2 through 2 DL, supply 1 and 3 is used for backup (supply 1 is
primary backup, 3 is secondary back up, 1 take precedence over 3, only valid if bi-direction transfer
be selected), 2DL closed, 1DL and 3DL tripped; bus I energized by supply 2 through 2 DL, supply 3
is used for backup (Only valid if single direction transfer be selected), 2DL closed, 3DL tripped.
Device energized, if backup supply voltage and bus voltage are higher than voltage set-point
respectively, the device begin to charge 10 s, then system enter fault monitor state.
Backup switch logic:
1DL closed, 2DL and 3DL tripped, if bus low-voltage or 1DL mis-tripped, voltage of power
supply 2 is higher than under-voltage set-point, then trip 1DL, after the un-volt. test and delay
condition of bus are satisfied, close 2DL, if 2DL closed fail, then close 3DL; if supply 2 is
low-voltage, then trip 1DL, after the un-volt. test and delay condition of bus are satisfied, close
3DL.
2DL closed, 1DL and 3DL tripped, if bus low-voltage or 2DL mis-tripped, voltage of power
supply 1 is higher than under-voltage set-point, then trip 2DL, after the un-volt. test and delay
condition of bus are satisfied, close 1DL (Only valid if bi-direction transfer is selected), if 1DL
closed fail, then close 3DL. If select single direction transfer or supply 2 is low-voltage, then trip
2DL, after the un-volt. test and delay condition of bus are satisfied, close 3DL.
Manual transfer logic:
When one of 1DL, 2DL and 3DL is closed, and the others are tripped, the manual switch function
of the device is available. The transfer logics in different transfer mode as follow:
[Series Switch]:
1DL closed, 2DL and 3DL tripped, and incomer 2 voltage is higher than under-voltage set-point,
if manual switch signal presence, trip 1DL, after the un-volt. test and delay condition of bus are
satisfied, close 2DL; if 2DL closed fail or incomer 2 is un-voltage, then close 1DL if manual switch
signal presence, after the un-volt. test and delay condition of bus are satisfied, close 3DL.
2DL closed, 1DL and 3DL tripped, and incomer 1 voltage is higher than under-voltage set-point,
if manual switch signal presence, trip 2DL, after the un-volt. test and delay condition of bus are
satisfied, close 1DL, if 1DL closed fail or incomer 2 is un-voltage, then close 2DL if manual switch
signal presence, after the un-volt. test and delay condition of bus are satisfied, close 3DL .
3DL closed, 1DL and 2DL tripped, and manual switch signal presence, if incomer 1 and 2 voltage
65
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
are both or only incomer 1 voltage is higher than under-voltage set-point, , trip 3DL, after the
un-volt. test and delay condition of bus are satisfied, close 1DL, if 1DL closed fail or incomer 1 is
un-voltage and incomer 2 voltage is higher than under-voltage set-point, then trip 3DL and close
2DL
[Auto Parallel]:
1DL closed, 2DL and 3DL tripped, and incomer 2 voltage is higher than under-voltage set-point,
if manual switch signal presence, close 2DL when the parallel synchronization condition is satisfied,
trip 1DL after closed successfully, if tripped successfully then the transfer process is over, otherwise
decoupling and trip 2DL. (Note: The decoupling function can be applied by user customize)
2DL closed, 1DL and 3DL tripped, and incomer 1 voltage is higher than under-voltage set-point,
if manual switch signal presence, close 1DL when the parallel synchronization condition is satisfied,
trip 2DL after closed successfully, if tripped successfully then the transfer process is over, otherwise
decoupling and trip 1DL. (Note: The decoupling function can be applied by user customize)
3DL closed, 1DL and 2DL tripped, and incomer 1 voltage is higher than under-voltage set-point,
if manual switch signal presence, close 1DL when the parallel synchronization condition is satisfied,
trip 3DL after closed successfully, if tripped successfully then the transfer process is over, otherwise
decoupling and trip 1DL. (Note: The decoupling function can be applied by user customize); if 1DL
closed fail or incomer 1 is un-voltage and incomer 2 voltage is higher than under-voltage set-point,
close 2DL when the parallel synchronization condition is satisfied, trip 3DL after closed
successfully, if tripped successfully then the transfer process is over, otherwise decoupling and trip
2DL. (Note: The decoupling function can be applied by user customize)
[Semi-auto Parallel]:
The parallel closing process is the same as [Auto Parallel], if closing successfully then the
transfer process is over.
[Parallel & Series]:
Detect the parallel synchronization conditions as the [Auto Parallel] logic, if the synchronization
conditions can not satisfied in the detect delay then choose [Series Switch].
After manual switch, the device will return to normal operating mode.
Note: When supply 3 used as work supply to energize the bus, the device only open the manual
switch function, and backup supply 1 take precedence over backup supply 2.
Terminal instruction:
66
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
AC Current Value (JK1)
Code
Name
1
NC
2
NC
3
NC
4
NC
5
NC
6
NC
7
1L-I1
8
1L-I1'
9
2L-I2
10
2L-I2'
11
3L-I3
12
3L-I3'
Output(Jk5)
Code
Name
1
Public Point
2
1DL Tripping
3
1DL Closing
4
Public Point
5
2DL Tripping
6
2DL Closing
7
Public Point
8
NC
9
3DL Tripping
10
Public Point
11
NC
12
3DL Closing
13 Signal Public Point
14 Backup Switch Act
External Fault Alarm
15
16
Device Alarm
17
NC
18
NC
19
Device Blocking
20
Instruction
Not Connected
Not Connected
Not Connected
Incomer 1 Current
Incomer 2 Current
Incomer 3 Current
Instruction
1DL Breaker
Transfer Output
2DL Breaker
Transfer Output
3DL Breaker
Tripping Output
3DL Breaker
Closing Output
Central Signal
Alarm Output
Not connected
Central Signal
Alarm Output
Control logic
67
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
The specialty of the scheme is that backup supply will convert to exclusive backup after
switching successfully. Exclusive backup still keep exclusive backup mode to run after switching
successfully, the device will return to plural reserve mode after manual switch successfully only.
Normal operating:
Plural reserve:
1DL closedbus I energized by supply 1 through 1DL.
2DL closedbus II energized by supply 2 through 2DL.
Bus breaker tripped, bus I, bus II backing for each other.
Device energized, if the voltage of bus I and bus II are both higher than voltage set-point
respectively, the device begin to charge 10 s, then system enter fault monitor state.
Exclusive backup:
1DL and bus breaker closed2DL tripped, bus I and bus II energized by supply 1 through 1DL
and bus switch, supply 2 is used for backup through 2DL;
2DL and bus breaker closed1DL tripped, bus I and bus II energized by supply 2 through 2DL
and bus switch, supply 1 is used for backup through 1DL (Only valid if bi-direction transfer is
selected).
Device energized, if backup supply voltage and bus voltage are higher than voltage set-point
respectively, the device begin to charge 10 s, then system enter fault monitor state.
Backup switch logic:
Plural reserve:
When bus I voltage low or 1DL mis-trip, bus II voltage is higher than under-voltage set-point,
then trip 1DL, after the un-volt. test and delay condition of bus I are satisfied, close bus breaker.
When bus II voltage low or 2DL mis-trip, bus I voltage is higher than under-voltage set-point,
then trip 2DL, after the un-volt. test and delay condition of bus II are satisfied, close bus breaker.
(Only valid if bi-direction transfer is selected)
Exclusive backup:
1DL and bus breaker closedWhen bus I and bus II voltage low or 1DL mis-trip or bus breaker
mis-trip(Only valid if switch mis-trip monitor set-point select all the switches), supply 2 voltage is
higher than under-voltage set-point, then trip 1DL or bus breaker, after the un-volt. test and delay
condition of bus I and bus II are satisfied, close 2DL.
2DL and bus breaker closedWhen bus I and bus II voltage low or 2DL mis-trip or bus breaker
mis-trip(Only valid if switch mis-trip monitor set-point select all the switches), supply 1 voltage is
higher than under-voltage set-point, then trip 2DL or bus breaker, after the un-volt. test and delay
68
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
condition of bus I and bus II are satisfied, close 1DL. (Only valid if bi-direction transfer is selected)
Manual transfer logic:
When bus breaker closed, 1DL or 2DL tripped, backup supply voltage is higher than
under-voltage set-point, the manual switch function of the device is available. The transfer logics in
different transfer mode as follow:
[Series Switch]:
2DL and bus breaker closed, 1DL tripped, and incomer 1 voltage is higher than under-voltage
set-point, if manual switch signal presence, trip bus breaker, after the un-volt. test and delay
condition of bus I are satisfied, close 1DL;
1DL and bus breaker closed, 2DL tripped, and incomer 2 voltage is higher than under-voltage
set-point, if manual switch signal presence, trip bus breaker, after the un-volt. test and delay
condition of bus II are satisfied, close 2DL;
1DL and 2DL closed, bus breaker tripped, external input signal mode 1 closed, mode 2 tripped
and bus I voltage is higher than under-voltage set-point, if manual switch signal presence, trip 2DL,
after closing delay of reserve supply switch, and close bus breaker when the bus II un-volt. test
conditions satisfied;
1DL and 2DL closed, bus breaker tripped, external input signal mode 2 closed, mode 1 tripped
and bus II voltage is higher than under-voltage set-point, if manual switch signal presence, trip 1DL,
after closing delay of reserve supply switch, and close bus breaker when the bus I un-volt. test
conditions satisfied;
[Auto Parallel]:
2DL and bus breaker closed, 1DL tripped, and incomer 1 voltage is higher than under-voltage
set-point, if manual switch signal presence, close 1DL when the parallel synchronization condition
is satisfied, trip bus breaker after closed successfully, if tripped successfully then the transfer
process is over, otherwise decoupling and trip 1DL. (Note: The decoupling function can be applied
by user customize)
1DL and bus breaker closed, 2DL tripped, and incomer 2 voltage is higher than under-voltage
set-point, if manual switch signal presence, close 2DL when the parallel synchronization condition
is satisfied, trip bus breaker after closed successfully, if tripped successfully then the transfer
process is over, otherwise decoupling and trip 2DL. (Note: The decoupling function can be applied
by user customize)
1DL and 2DL closed, bus breaker tripped, and mode 1 voltage closed, if manual switch signal
presence, close bus breaker when the parallel synchronization condition is satisfied, trip 2DL after
69
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
closed successfully, if tripped successfully then the transfer process is over, otherwise decoupling
and trip bus breaker. (Note: The decoupling function can be applied by user customize);
1DL and 2DL closed, bus breaker tripped, and mode 2 voltage closed, if manual switch signal
presence, close bus breaker when the parallel synchronization condition is satisfied, trip 1DL after
closed successfully, if tripped successfully then the transfer process is over, otherwise decoupling
and trip bus breaker. (Note: The decoupling function can be applied by user customize);
[Semi-auto Parallel]:
The parallel closing process is the same as [Auto Parallel], if closing successfully then the transfer
process is over.
[Parallel & Series]:
Detect the parallel synchronization conditions as the [Auto Parallel] logic, if the synchronization
conditions can not satisfied in the detect delay then choose [Series Switch].
After manual switch, the device will return to normal operating mode.
Terminal instruction:
70
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
Scheme 9: Double backup transfer control (Exclusive backup, secondary backup supply has
PT)
Wiring diagram as figure 64:
Control logic
Characteristics:
If the status of the external input value mode 1 and mode 2 are different, the work supply is
incomer 1, backup supply is determined by mode selection status. When mode 1 closed, mode 2
tripped, incomer 2 is the backup supply; When mode 2 closed, mode 1 tripped, incomer 3 is the
backup supply.
If the status of the external input value mode 1 and mode 2 are same, the close sequence of
backup supply is determined by quality of the voltage, the priority level of the voltage from high to
low isincomer 1incomer 2incomer 3the principle of backup switch is as follows:
: Incomer 2 and 3 are backup supplies, if only the voltage of incomer 2 is qualified, close 2DL;
if only the voltage of incomer 3 is qualified, close 3DL; if both the voltage of incomer 2 and 3 are
qualified, close 2DL; if close 2DL failed, then close 3DL;
: Incomer 1 and 3 are backup supplies, if only the voltage of incomer 1 is qualified, close 1DL;
if only the voltage of incomer 3 is qualified, close 3DL; if both the voltage of incomer 1 and 3 are
qualified, close 1DL; if close 1DL failed, then close 3DL;
: Incomer 3 is backup supply, if the voltage of incomer 3 is qualified, close 3DL;
: Incomer 1 and 2 are backup supplies, if only the voltage of incomer 1 is qualified, close 1DL;
if only the voltage of incomer 2 is qualified, close 2DL; if both the voltage of incomer 1 and 2 are
qualified, close 1DL.
Normal operating:
When mode 1 and mode 2 are both closed or tripped:
1DL closed, 2DL and 3DL tripped, bus energized by supply 1 through 1DL, supply 2 and 3 is
used for backup (supply 2 is primary backup, 3 is secondary backup, 2 take precedence over 3);
2DL closed, 1DL and 3DL tripped, bus energized by supply 2 through 2DL, supply 1 and 3 is
used for backup (supply 1 is primary backup, 3 is secondary back up, 1 take precedence over 3,
(Only valid if bi-direction transfer be selected); bus energized by supply 2 through 2DL, supply 3 is
used for backup (Only valid if single direction transfer be selected).
When mode 1 closed, mode 2 tripped:
1DL closed, 2DL and 3DL tripped, bus energized by supply 1 through 1DL, supply 2 is used for
backup;
2DL closed, 1DL and 3DL tripped, bus energized by supply 2 through 2DL, supply 1 is used for
backup (Only valid if bi-direction transfer be selected).
When mode 2 closed, mode 1 tripped:
72
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
1DL closed, 2DL and 3DL tripped, bus energized by supply 1 through 1DL, supply 3 is used for
backup;
3DL closed, 1DL and 2DL tripped, bus energized by supply 3 through 3DL, supply 1 is used for
backup (Only valid if bi-direction transfer be selected).
Device energized, if the voltage of bus and any backup supplies are qualified, the device begin to
charge 10 s, then system enter fault monitor state.
Backup switch logic:
When mode 1 and mode 2 are both closed or tripped:
1DL closed, 2DL and 3DL tripped, if bus low-voltage or 1DL mis-tripped, then trip 1DL, after
the un-volt. test and delay condition of bus are satisfied, close backup supply according to backup
close principle .
2DL closed, 1DL and 3DL tripped, if bus low-voltage or 2DL mis-tripped, then trip 2DL. If
bi-direction transfer is effective, after the un-volt. test and delay condition of bus are satisfied, close
backup supply according to backup close principle . If single direction transfer is effective, close
backup supply according to backup close principle .
When mode 1 closed, mode 2 tripped:
1DL closed, 2DL and 3DL tripped, if bus low-voltage or 1DL mis-tripped, then trip 1DL, after
the un-volt. test and delay condition of bus are satisfied, close 2DL.
2DL closed, 1DL and 3DL tripped, if bus low-voltage or 2DL mis-tripped, then trip 2DL, after
the un-volt. test and delay condition of bus are satisfied, close 1DL. (Only valid if bi-direction
transfer be selected)
When mode 2 closed, mode 1 tripped:
1DL closed, 2DL and 3DL tripped, if bus low-voltage or 1DL mis-tripped, then trip 1DL, after
the un-volt. test and delay condition of bus are satisfied, close 3DL.
3DL closed, 1DL and 2DL tripped, if bus low-voltage or 3DL mis-tripped, then trip 3DL, after
the un-volt. test and delay condition of bus are satisfied, close 1DL. (Only valid if bi-direction
transfer be selected)
Manual transfer logic:
When mode 1 and mode 2 are both closed or tripped:
[Series Switch]:
1DL closed, 2DL and 3DL tripped, if manual switch signal presence, trip 1DL, after the un-volt.
test and delay condition of bus are satisfied, close backup supply according to backup close
principle .
73
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
2DL closed, 1DL and 3DL tripped, if manual switch signal presence, trip 2DL, after the un-volt.
test and delay condition of bus are satisfied, close backup supply according to backup close
principle .
3DL closed, 1DL and 2DL tripped, if manual switch signal presence, trip 3DL, after the un-volt.
test and delay condition of bus are satisfied, close backup supply according to backup close
principle .
[Auto Parallel]:
1DL closed, 2DL and 3DL tripped, and incomer 2 voltage is higher than under-voltage set-point,
if manual switch signal presence, close 2DL when the parallel synchronization condition is satisfied,
trip 1DL after closed successfully, if tripped successfully then the transfer process is over, otherwise
decoupling and trip 2DL. (Note: The decoupling function can be applied by user customize); if
close 2DL fail, or incomer 2 un-voltage and incomer 3 voltage is higher than under-voltage
set-point, close 3DL when the parallel synchronization condition is satisfied, trip 1DL after closed
successfully, if tripped successfully then the transfer process is over, otherwise decoupling and trip
3DL. (Note: The decoupling function can be applied by user customize).
2DL closed, 1DL and 3DL tripped, and incomer 1 voltage is higher than under-voltage set-point,
if manual switch signal presence, close 1DL when the parallel synchronization condition is satisfied,
trip 2DL after closed successfully, if tripped successfully then the transfer process is over, otherwise
decoupling and trip 1DL. (Note: The decoupling function can be applied by user customize); if
close 1DL fail, or incomer 1 un-voltage and incomer 3 voltage is higher than under-voltage
set-point, close 3DL when the parallel synchronization condition is satisfied, trip 2DL after closed
successfully, if tripped successfully then the transfer process is over, otherwise decoupling and trip
3DL. (Note: The decoupling function can be applied by user customize).
3DL closed, 1DL and 2DL tripped, and incomer 1 voltage is higher than under-voltage set-point,
if manual switch signal presence, close 1DL when the parallel synchronization condition is satisfied,
trip 3DL after closed successfully, if tripped successfully then the transfer process is over, otherwise
decoupling and trip 1DL. (Note: The decoupling function can be applied by user customize); if 1DL
closed fail or incomer 1 is un-voltage and incomer 2 voltage is higher than under-voltage set-point,
close 2DL when the parallel synchronization condition is satisfied, trip 3DL after closed
successfully, if tripped successfully then the transfer process is over, otherwise decoupling and trip
2DL. (Note: The decoupling function can be applied by user customize)
[Semiauto Parallel]:
The parallel closing process is the same as [Auto Parallel], if closing successfully then the
74
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
Terminal instruction:
76
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com
AC Current Value (JK1)
Code
Name
1
NC
2
NC
3
NC
4
NC
5
NC
6
NC
7
1L-I1
8
1L-I1'
9
2L-I2
10
2L-I2'
11
3L-I3
12
3L-I3'
Output(Jk5)
Code
Name
1
Public Point
2
1DL Tripping
3
1DL Closing
4
Public Point
5
2DL Tripping
6
2DL Closing
7
Public Point
8
NC
9
3DL Tripping
10
Public Point
11
NC
12
3DL Closing
13 Signal Public Point
14 Backup Switch Act
External Fault Alarm
15
16
Device Alarm
17
NC
18
NC
19
Device Blocking
20
Instruction
Not Connected
Not Connected
Not Connected
Incomer 1 Current
Incomer 2 Current
Incomer 3 Current
Instruction
1DL Breaker
Transfer Output
2DL Breaker
Transfer Output
3DL Breaker
Tripping Output
3DL Breaker
Closing Output
Central Signal
Alarm Output
Not connected
Central Signal
Alarm Output
77
Tel (0755)83416189 ,83663989
Fax (0755)83663603
website http://www.szidd.com