SLR140

USER MANUAL

USERMANUAL
OVERCURRENTANDEARTHFAULT&REFRELAY
WITHAUTORECLOSER

SLR140

STELMEC
LIMITED
Stelmec Limited
|

Over Current and Earth Fault Relay

SLR140

USER MANUAL

PREFACE

The aim of this handbook is to provide to the user information


useful for the operation of SLR140 relay with the local MMI.
We advise you to read it carefully, in order to take note of the
available functionalities and to proceed to connection and power of
the product in accordance with the provided recommendations.
Locally settings, commissioning and real time or event readings are
accessible from keyboard and displayed on the protection display.
To be fully exploited, the available functions must be parameterized
and consulted with the settings
Software PC-Protection, provided with the product.
Before any use, we recommend you to read the safety instructions of
this Users guide.

Stelmec Limited |

Over Current and Earth Fault Relay

SLR140

USER MANUAL

Table of Contents
1. General
1.1. Safety Instructions
1.2. Relay Features
1.3. Preliminary Information
2. Introduction
2.1. Application
2.2. Main Features
3. User Interface
3.1. General
3.2. Local Panel
3.2.1. Display
3.2.2. Keypad
3.2.3. Indicators
3.2.4. RS232 Serial Communication
4. Local Panel Operation
4.1. Functional Menu Chart
4.1.1. Individual Menu Chart
4.1.2. Fault Log Settings
4.1.3. IL Settings
4.1.4. Io Settings
4.1.5. Digital Input Settings
4.1.6. Digital OP Settings
4.1.7. Force OP Settings
4.1.8. Enable Stages
4.1.9. Scalling Settings
4.1.10. System Settings
4.2. Description of Functional Menu
5. Functions
5.1. Principles of the Numerical Protection Techniques
5.2. Relay Protection Functions
5.2.1 Non-Directional over Current Protection (50/51)
5.2.2 Non-Directional Earth Fault Protection (50N/51N)
5.2.3 Circuit Breaker Failure Protection CBFP (50BF)
5.2.4. Self Supervision
5.2.5. Trip Circuit Supervision (95ABC).
5.2.6. Features
5.2.7. Auto Recloser
5.2.8. Basic Requirements
5.2.9. Restricted Earth Fault Protection(64N).

Stelmec Limited |

Over Current and Earth Fault Relay

Page no
5
6
7
8
9
9
9
10
10
10
10
10
11
12
13
13
14
14
15
16
16
17
21
22
22
23
23
24
24
25
25
26
29
30
31
31
32
32
33

SLR140

USER MANUAL

Table of Contents
6. Configuration and Parameters Settings
6.1. Measured Values
6.2. Principle of Parameter Settings
6.3. Enabling and Disabling Protection Functions
7. Communication
7.1. Mod Bus RS485 Communication
8. Output Response Curves
8.1. Low Set Characteristics Curves
8.1.1. Normal Inverse Curve
8.1.2. Very Inverse Curve
8.1.3. Extremely Inverse Curve
8.1.4. Long Time Inverse Curve
8.1.5. 1.3S Curve
8.1.6. 3S Curve
8.2. High Set Characteristics Curve
9. Application Circuit for 3O/C and 1E/F
10. Protection Stages
10.1. Over Current Protection Stages
10.2. Earth Fault Current Protection Stages
10.3. Auto - Reclose Protection
11. Technical Data
11.1. Auxiliary Supply
11.2. Current Inputs
11.3. Trip Contacts (T1&T2)
11.4. Accuracy
12. Construction
12.1. Mechanical
12.2. Dimensional Drawing
12.3. Panel Mounting
12.4. Semi-Flush Mounting
13. Commissioning
14. Ordering Information
15. Contact Information

Stelmec Limited |

Over Current and Earth Fault Relay

Page no
34
34
35
37
38
38
39
39
39
39
40
40
41
41
41
42
43
43
43
44
44
44
44
45
45
46
46
46
47
47
48
49
50

SLR140

USER MANUAL

1. General

This part of the manual describes the general function of the combined over
current and earth fault relay SLR140 includes relay operational instructions.
It also includes instructions on parameterization and configuration of the
relay and instructions on changing of settings. And includes detail protection
function descriptions, technical data sheets and case mounting.

Stelmec Limited |

Over Current and Earth Fault Relay

SLR140

USER MANUAL

1.1. Safety Instructions

For your safety, we recommend you to


information/instruction carefully before handling.

read

the

following

They have the aim of specifying the precautions essential to the good installation
and the perfect operation of the relay.
9
9
9

Connection of SLR140 relay


On load withdrawal
Removal and destructions

The terminals on the rear panel of the relay may carry dangerous voltages.
Although the auxiliary voltage is switched off. A live current transformer
secondary circuit must not be opened.
Disconnecting a live circuit may cause dangerous voltages! Any operational
measure must be carried out according to national local handling directives and
instructions.

Stelmec Limited |

Over Current and Earth Fault Relay

SLR140

USER MANUAL

1.2. Relay Features

The combined over current and earth fault relay SLR140 is a non - directional
current measuring protection relay for over current, short circuit and earth
fault
Protection.

Protection features are following


Three over current stages (I> && I>>)
One earth fault stage(Io> && Io>>)
Circuit breaker failure protection (CBFP).
Phase high set instantaneous or definite time over current stage.
Non directional definite time or inverse time (IDMT) earth fault stage.
Numerical display for setting values, measured values, recorded fault
values, indications etc.
Built-in pulse-width-modulated galvanically isolating power unit for a
wide
range of auxiliary supply.
Continuous self-supervision of relay hardware and software for enhanced
system reliability and Availability.
Auto-diagnostic fault indication to facilitate repair of a permanent internal
relay fault.
RS232 communication port for PC connections.
SCADA Port Communication for RS-485 Connections.

Stelmec Limited |

Over Current and Earth Fault Relay

SLR140

USER MANUAL

1.3. Preliminary Information

In the SLR140 Relay, technology used in digital.


Due to their design, they comprise a significant number of self controls, as well as
powering as under operation, any material or software failure is automatically
detected and announced by an alarm.
During the first use, it is does not necessary to test all the functions. It is on the
other hand recommended to look after and check the good wiring of the relay,
and the specifications of this handbook have the aim of allowing a fast setting in
order of the relay.
The user will be able then to define the setting value necessary to his installation,
and to adjust the relay using the setting software, common to the whole of the
range. The saving of the configuration and its loading will be carried out with a
laptop.
The functions of recording of events and fault recording, available through the
Setting software, will also largely contribute to the setting in the order of the
Installation.

Stelmec Limited |

Over Current and Earth Fault Relay

SLR140

USER MANUAL

2. Introduction
This part of the manual describes few applications, main features, protection
functions and contains technical data and also includes operating instructions.
2.1. Application
The versatile basic protection functions the wide variety of additional functions
and several available communication protocols render the over current and
earth fault relay (SLR140) ideal Protection relay power plants and substations
as well as for industry applications.
The modern technology in association with an extensive self supervision and a
reliable Construction ensures an extremely high availability for the SLR140
protection relay.
The relay is used for over current and earth fault protection. The relay can also
be used in other applications where a single, two or three protection relay is
needed.
2.2. Main Features

Fully digital signal handling with a powerful 8-bit micro controller high
measuring Accuracy on all setting ranges due to accurate 12-bit A/D
conversion technique.
Easy enabling and disabling of protection functions according to the needs
of
the Intended application.
Wide setting ranges for the protection functions.
Easy adaptation of the relay to various substations and alarm systems due
to a flexible signal-grouping matrix in the relay.
Recording of events and last 16 fault values into an event register, from
which data
can be read via the keypad and the display or by means of the PC based
SLR140 user interface.
Built-in fault recorder for evaluating secondary, as well as Over current
and
Neutral currents of the protective object.
Auto Reclose Function.
Stelmec Limited |

Over Current and Earth Fault Relay

SLR140

USER MANUAL

3. User Interface
3.1. General
The SLR140 relay can be controlled in two ways:
Locally with the push buttons on the relay front panel.
Locally with a PC connected to the serial port on the relay front panel.
3.2. Local Panel
Figure below show the location of the components of the local user interface
on the front panel of the relay.
LCD display
Keypad
LED Indicators
RS232 serial communication port for a PC.
3.2.1. Display
The SLR140 relay provided with clear characteristics 16x2 lines LCD display.
3.2.2. Keypad
Use the keypad and the display to navigate through the menus and to set the
required parameters/values. The keypad comprises the following keys.
Left, Right, Up, Down And Reset Keys.

Stelmec Limited |

Over Current and Earth Fault Relay

10

SLR140

USER MANUAL

Up/Down arrow keys are to select functions Increasing/Decreasing.


Left arrow key for cancellation the selected function.
Right arrow key for confirm the function.
Reset Key used for Reset functions.

3.2.3. Indicators
The relay front panel holds 9 LED indicators.

Figure 3.2 Relay front panel.

Operation Indicators
LED Indicators
AUX LED Lit
ERROR LED Lit

START LED Lit

TRIP LED Lit

L1

Stelmec Limited |

Explanation

Measure/Remarks

The Auxiliary Power Switched ON

Normal Operating State

An Internal Relay Fault has been Detected

The relay attempts to reboot. If the


error LED remains lit, call for
maintenance.

One or several signals of the output relay matrix have


been assigned to output alarm and the output has
been activated by one of the signals.

The LED is switched off, when the


signal that caused output alarm to
activate, e.g. The START signal
resets. The resetting depends on the
type of configuration. Connected or
Latched.

One or several signals of the output relay matrix have


been assigned to output Trip and the output has been
activated by one of the signals.

The LED is switched off, when the


signal that caused output Trip to
activate, e.g. The TRIP signal resets.
The resetting depends on the type of
configuration. Connected or Latched.

Trip and the output has been activated by line 1 low


set (or) high set over current.

L1 LED is glowing; When the Trip is


activating by line 1 over current.

Over Current and Earth Fault Relay

11

SLR140

USER MANUAL
L2

Trip and the output has been activated by line 2 low


set (or) high set over current.

L2 LED is glowing; When the Trip is


activating by line 2 over current.

L3

Trip and the output have been activated by line 3


low set (or) high set over current.

L3 LED is glowing; When the Trip is


activating by line 3 over current.

L0

Trip and the output have been activated by low set


(or) high set earth fault current.

L0 LED is glowing; When the Trip is


activating by earth fault current.

Battery ON/OFF indication (Optional)

Battery using time glowing.

BAT

3.2.4. RS232 Serial Communication


To connect with PC, a RS 232 serial port is available on the front panel of the
relay. The pin layout is as follows.

RS-232 Specifications
RS-232 is a complete standard. This means that the standard sets out to
ensure
Compatibility between the host and peripheral systems by specifying:
Common voltage and signal levels
Common pin-wiring configurations
A minimal amount of control information between the host and peripheral
systems.
Unlike many standards which simply specify the electrical characteristics of a
given interface, RS-232 specifies electrical, functional, and mechanical
characteristics to meet the above three criteria.

Stelmec Limited |

Over Current and Earth Fault Relay

12

SLR140

USER MANUAL
.

4. Local Panel Operation


The local panel can be used to read measured values, set parameters and
configure relay functions. However, please note that some of the parameters
can only be set by means of a PC connected to the local communication port.
4.1. Functional Menu Chart
Following figure shows the functional menu for SLR140 relay

Stelmec Limited |

Over Current and Earth Fault Relay

13

SLR140

USER MANUAL

4.1.1. Individual Menu Chart

4.1.2. Fault Log Settings

Stelmec Limited |

Over Current and Earth Fault Relay

14

SLR140

USER MANUAL

4.1.3. IL settings

Stelmec Limited |

Over Current and Earth Fault Relay

15

SLR140

USER MANUAL

4.1.4. Io Settings

Stelmec Limited |

Over Current and Earth Fault Relay

16

SLR140

USER MANUAL

4.1.5.
Setting

Stelmec Limited |

Digital Input

Over Current and Earth Fault Relay

17

SLR140

USER MANUAL

4.1.6. Digital OP Set

Stelmec Limited |

Over Current and Earth Fault Relay

18

SLR140

USER MANUAL

Stelmec Limited |

Over Current and Earth Fault Relay

19

SLR140

USER MANUAL

Stelmec Limited |

Over Current and Earth Fault Relay

20

SLR140

USER MANUAL

Stelmec Limited |

Over Current and Earth Fault Relay

21

SLR140

USER MANUAL

4.1.7. Force OP Setting

4.1.8. Enable Stages


Stelmec Limited |

Over Current and Earth Fault Relay

22

SLR140

USER MANUAL

4.1.9. Scalling Settings

4.1.10. System Settings


Stelmec Limited |

Over Current and Earth Fault Relay

23

SLR140

USER MANUAL

4. 2. Description of Functional Menu


The general menu structure is shown in above figure. The menu is based on the
users configuration and the options are according to the order code. For
example only the enabled protection stages will appear in the menu.

5. Functions
Stelmec Limited |

Over Current and Earth Fault Relay

24

SLR140

USER MANUAL

The individual protection function of the SLR140 Over current and Earth Fault
Relay can independently of each Other be enabled or disabled according to the
requirements of the application.
5.1. Principle of the Numerical Protection Technique
The SLR140 relay is designed using numerical technology. This means that
all
signal filtering, protection and control functions are made by digital
processing.
The numerical technology used in the relay is primarily based on an
adapted fast
Fourier (FFT) analysis, in which case the no of calculations (multiplications
&
additions) required to filter the measuring quantity remains reasonable.
By using synchronized sampling of the measured signal (phase or earth
fault
current) and a sample rate according to the 2n series, the FFT technique
leads to a
solution, which can be realized with just a 8 bit microcontroller without
using a separate DSP (Digital Signal Processor)

The synchronized sampling means an even number of 2n samples per


period, e.g.16 samples/period. This means that the frequency must be
measured and the no of samples per period must be controlled accordingly,
so that the no of samples per period remains constant should the frequency
change.
Figure shows the main component of the relay using numerical technology,
Stelmec Limited |

Over Current and Earth Fault Relay

25

SLR140

USER MANUAL

i.e. the
relay comprises input current transformers, digital input adapters output
relays, A/D converters and microcontroller including memory circuits.
Further the relays needs a power supply and a user interface
5.2. Relay Protection Functions
The relay having the following protection functions:

Three phase over current protection, with 50/51(3I>, 3I>>) thresholds.


Earth fault over current protection, with 50N/51N (1Io>, 1Io>>) thresholds.
50BF circuit breaker failure protection(CBFP) functions by checking of the
disappearance of the phases and earth fault currents.
Available operation functions:

Measurement of the average, instantaneous or maximum currents, phases


and earth fault current.
Control of the operation of the circuit breaker by monitoring of the
closings and
trips.
Logical selectivity functions available on the phase and earth fault
Threshold.
Internal relay NO/NC selectivity function.
The relay controlling following two reset function.
9 Hand reset.
9 Self reset.
5.2.1. Non-Directional Over Current Protection I>, I>> (50/51)
The three phase over current unit comprises adjustable over current
stages,
i.e. I>,I>>
Stage I> can be configured for definite time or inverse time operation
characteristic.
Stage I>> have definite time characteristic.
Figure 5.2.1 shows the fundamental block diagram of stage I>.

Stelmec Limited |

Over Current and Earth Fault Relay

26

SLR140

USER MANUAL

Parameters of the Over Current Stages I>, I>> (50/51)

Measured value

IL Setting

Parameter:

Value/unit:

IL

I>,I>>
I>,I>>

A
In
NI,VI,EI,LTI,3S,1.3S
DT
S
S

curve
t>
t>>
k

Max. Value of phase currents L1, L2, L3


secondary values.
Setting value in primary current units
Setting value as per unit value. setting done in x In
Operation character/inverse time(I>)
Operation character/definite time(I>)
Operation time at IDMT(I>)
Operation time at Definite time (I>>)
Time multiplier at inverse time(I>)

When the over current exceeds the low-set I> setting value, the over
current
low-set element starts and delivers a start signal to the display panel and a
group of pre assigned relay outputs. After a delay time, determined by the
inverse time current characteristics curve selected and the measured
current, this over current element operates and delivers trip signal to the
display panel and a group of relay outputs that are configured to link to the
low-set over current tripping.
When the over current exceeds the high-set I>> setting value, the over
current high-set element starts and delivers a start signal to the display
panel and a group of pre assigned relay outputs. After a preset time
determined by t>>, this over current element operates and a group of relay
outputs that are configured to link to high-set over current tripping.
The low set stage (I>, Io>) of the over current unit can be confirmed for inverse
current characteristics. Six sets of characteristics curves according to IEC
Stelmec Limited |

Over Current and Earth Fault Relay

27

SLR140

USER MANUAL

60255-3 are available for the low set stage. I.e. Normal inverse (NI), Very
inverse (VI), Extremely inverse (EI) , Long time inverse (LTI), 3S Curve and 1.3S
Curve.
5.2.2. Non-Directional Earth Fault Protection (50N/51N)
One earth fault current unit comprises adjustable earth fault current
stages,
i.e. I>,I>>
Stage Io> can be configured for definite time or inverse time operation
characteristic.
Stage Io>> have definite time characteristic.
Figure shows the fundamental block diagram of stage Io>.

Parameters of the Earth Fault Stages I>, I>> (50/51)

Measured value

Io Setting

Parameter:

Value/unit:

Io

Io>,Io>>
Io>,Io>>

A
In
NI,VI,EI,LTI,3S,1.
3S
DT
S
S

curve
to>
to>>
k

Max. Value of phase currents Lo secondary


values.
Setting value in primary current units
Setting value as per unit value. setting done in x In
Operation character/inverse time(Io>)
Operation character/definite time(Io>)
Operation time at IDMT(Io>)
Operation time at Definite time (Io>>)
Time multiplier at inverse time(Io>)

When the earth fault current exceeds the low-set Io> setting value, the
earth fault low-set element starts and delivers a start signal to the display
panel and a group of pre assigned relay outputs. After a delay time,
Stelmec Limited |

Over Current and Earth Fault Relay

28

SLR140

USER MANUAL

determined by the inverse time current characteristics curve selected and


the measured current, this earth-fault element operates and delivers trip
signal to the display panel and a group of relay outputs that are configured
to link to the low-set earth-fault tripping.
When the earth fault current exceeds the high-set Io>> setting value, the
earth fault High-set element starts and delivers a start signal to the display
panel and a group of pre assigned relay outputs. After a preset time
determined by to>>, this earth fault element operates and a group of relay
outputs that are configured to link to high-set earth fault tripping.

5.2.3. Circuit Breaker Failure Protection (50BF)


The operation of the circuit breaker failure protection is based on the
supervision of the operating time, from the pick up of the configured trip
relay
to the dropout of the same relay.
If that time is longer than the operating time of the CBFP stage, the CBFP
stage activates another output relay, which will remain activated, until the
primary trip relay resets.
The CBFP stage functions also in earth fault situations, because its function
is merely based on supervision of the function of the output relay T1.

The CBFP blocking signal prevents the CBFP stage from operating, when the
Stelmec Limited |

Over Current and Earth Fault Relay

29

SLR140

USER MANUAL

output relays or any other protection function is operated by forced


control.
This protection feature allows the relay to trip the upstream circuit breaker
when a local breaker failure condition is detected.

5.2.4. Self Supervision


The functions of the micro controller and the associated circuitry as well as
the
program execution is supervised by means of a separate watchdog circuit.
Besides supervising the relay the watchdog circuit attempts to restart the
micro controller in a fault situation. If the restarting fails, the watchdog
issues
a self-supervision alarm because of a permanent relay fault.
When the watchdog circuit detects a permanent fault it always blocks any
control of the other output relays, except for the self- supervision output
relay.
Also the internal supply voltage is supervised. Should the auxiliary supply
of
the relay disappear, an IF alarm is automatically given. The IF relay contact
is normally closed type of contact. This means that the IF relay contact is
closed, when there is an internal fault or there is no auxiliary power
supply.
If the relay is fully operational with the auxiliary power supply, the IF
contact is on the open position.

Example:IL Setting: I>0.20xIn

Stelmec Limited |

Over Current and Earth Fault Relay

30

SLR140

USER MANUAL

In
1>0.20xIn
Curve NI
t>

0.10s

secondary current [5A]


Set value of load current
Selection of delay characteristics
[NI,VI,EI,LTI,3.0S, 1.3S,DMT]
Selection of delay time

5.2.5. Trip Circuit Supervision (95ABC)


Trip circuit supervision is a critical function in a protection scheme.
Continuously monitors the status of circuit breaker trip circuits to detect:
Wiring damage
Loose terminal screws
Poorly crimped terminal wiring
CB coil open circuit CB pallet switch misaligned
Trip circuit supply failure (Blown fuse)
5.2.6. Features
Continuous monitoring of circuit-breaker trip circuits and other essential
control circuits
Preset operate time preventing unwanted alarm signals at circuit-breaker
operation
Indication of relay operation with LED indicator on the front panel and
output relay
Detects bad contact, contact welding and auxiliary voltage failures in the
supervised circuit
Stelmec Limited |

Over Current and Earth Fault Relay

31

SLR140

USER MANUAL

Block Diagram

5.2.7. Auto-Recloser
Introduction
In electric power distribution, an autorecloser is a circuit breaker equipped
with a mechanism that can automatically close the breaker after it has been
opened due to a fault
Autoreclosers are used in coordinated protection schemes for overhead line
power distribution circuits. These circuits are prone to transitory faults such as
nearby lightning strikes, wind-borne debris, animals climbing the insulators,
and the like. With a conventional circuit breaker or fuse, a transient fault
would open the breaker or blow the fuse, disabling the line until a technician
could manually close the circuit breaker or replace the blown fuse. But an
autorecloser will make several pre-programmed attempts to re-energize the
line. If the transient fault has cleared, the autorecloser's circuit breaker will
remain closed and normal operation of the power line will resume. If the fault
is some sort of a permanent fault (downed wires, tree branches lying on the
wires, etc.) the autorecloser will exhaust its pre-programmed attempts to reenergize the line and remain tripped off until manually commanded to try
again. 90% of faults on overhead power lines are transient and can be cured by
autoreclosing. [3] The result is increased availability of supply.
5.2.8. Basic Requirements
Stelmec Limited |

Over Current and Earth Fault Relay

32

SLR140

USER MANUAL

The Auto-recloser relay should reclose the breakers whenever it is


initiated by
protective relay.
The Auto-recloser relay shouldnt reclose the breakers if the initiation
occurs
during the reclaim time.
For single pole mode, the AR-Relay should only reclose the Breakers for
single
phase to earth fault.
The AR-Relay should never reclose the breakers if,
No initiation from protective relay e.g. when the breakers are
intentionally
opened by people.
Any of the Breakers is not ready, its not switched to active.

5.2.9. Restricted Earth Fault Protection (67N)


The restricted earth-fault protection is designed to detect high-resistance
earth faults within the protection zone of power transformers.
Restricted earth-fault protection as well as transformer differential
protection is based on the principle of comparison of measured variables by
comparing the residual current of the phase current transformers of the given
winding with the current of the associated grounded star point. Since residual
current may occur due to transient saturation during high through fault
currents restraining is required for restricted earth fault protection. For this
purpose two different measuring principles are available.
i.e. the biased differential scheme and the phase comparison scheme. The
biased differential scheme can be used, if the actual accuracy limit factor of
the CT is sufficient for the application. In the case of heavy CT saturation, the
phase comparison scheme is recommended to be used instead, to avoid
unwanted tripping.
The protection function block used for this application is called restricted
differential protection. Standard over current and earth fault protection relays do
not provide adequate protection for star connected primary transformer windings
particularly if the neutral is earthed through impedance.
Stelmec Limited |

Over Current and Earth Fault Relay

33

SLR140

USER MANUAL

In the SLR140 Relay For unearthed star or delta wound transformers standard earth
fault protection will work in the same way as restricted earth fault protection.

Connection scheme for restricted earth-fault protection

6. Configuration and Parameter Settings


Default Screen
3OC + 1EF RELAY
SLR14O

6.1. Measured Values


Use the DOWN key of the front panel to move to item MEASURE of the
main menu, where the values of the phase current and the earth fault
current
to be viewed in percentage by the user.
R
B

:0 A
:0 A

Y
E

:0 A
:0 A

Use the LEFT key to move to main menu.


Use the DOWN key to select the menu functions.
Use the RIGHT key to go into the selected menu.
Let us we show all main menu functions one by one.
The settings of the selected functions can be read and set separately in the sub
Stelmec Limited |

Over Current and Earth Fault Relay

34

SLR140

USER MANUAL

menus of each functions.


Available protection stages:

I>, I>>(IL Setting)


Io>, Io>>(Io Setting)
CBFP (CBFP Set)
Available other stages:

Fault Log
Digital IP Set
Digital OP Set
Force Op Stages
Enable Stages
Scaling
System Setting

6.2. Principle of Parameter Setting


This example shows how to change the IL Settings. Same as the principle is used
to change other parameters,

Use the RIGHT key to open the setting level appears on the display.
Use the UP and DOWN key to change the setting values.
The changing values are confirmed by press the RIGHT key.
Push the DOWN key to return the next submenu.
Use the UP and DOWN key to change the setting values.
The changing values are confirmed by press the RIGHT key.
Push the LEFT key twice to return to the main menu.

Fault Log
Via the submenus of the Fault Log menu the following can be read and set:
This function views the measured values of the phase current and earth
fault
Current where the faults are recorded at the moment of last 8 fault
tripping with date and time.
Function reset.
Stelmec Limited |

Over Current and Earth Fault Relay

35

SLR140

USER MANUAL

IL Settings
Via the submenus of the IL Setting menu the following can be read and set:

I> Set, I> curve, t> TMS for Low set characteristics.
As well as I>> Set and t>> TMS for high set characteristics.
Increase/decrease the settings values are done by UP/DOWN keys.

Io Settings
Via the submenus of the Io Setting menu the following can be read and set:

Io> Set, Io> curve, to> TMS for Low set characteristics.
As well as Io>> Set and to>> TMS for high set characteristics.
Increase/decrease the settings values are done by UP/DOWN keys.

Digital IP Set
Via the submenus of the Digital IP Set menu the following can be read and set:
Binary input 1, Binary input 2 configuration operation delay time.
CBFP delay time.
Digital OP Set
Via the submenus of the Digital OP Set menu, all the protection function of
output relays T1, T2, T3, T4 and T5 contacts can be open (ON) or close (OFF).
There are five relay outputs that can be programmed to respond the relay start
signal, trip signal, or both the start and trip signals. The sixth relay is act as an
internal relay failure indicator.
I> OP Config.
Low set over current output relay configuration.

I>> OP Config.
High set over current output relay configuration.

Io> OP Config.
Low set earth fault current output relay configuration.

Io>> OP Config.
Stelmec Limited |

Over Current and Earth Fault Relay

36

SLR140

USER MANUAL
High set earth fault current output relay configuration.

Latch OP Config.
Hand reset or self reset function output relay configuration.

CBFP OP Config.
Circuit Breaker Failure Protection output relay configuration.

ALM OP Config.
Alarm output relay configuration.

BI 1
Binary input 1 output relay configuration.

BI 2
Binary input 2 output relay configuration.

Force OP Stages
Via the submenus of the Force OP Stages menu, all the functional test for
output relays and output LEDs are done.
6.3. Enabling and Disabling Protection Functions
Enable Stages
Via the submenus of the Enable Stages menu, all the protection functions can
be enabled (ON) or disabled (OFF)
I>Enable
Over current low set stage (I>)

I>>Enable
Over current high set stage (I>>)

Io>Enable
Earth fault current low set stages (Io>)

Io>>Enable
Earth fault current high set stages (Io>>)

CBFP Enable
Circuit breaker failure protection (CBFP)

BI1
Binary Input 1

BI2
Binary Input 2

Scalling
Via the submenus of the Scalling menu, the primary and secondary current
ratings are read and set, where the primary current setting having maximum
1000A as well as the secondary current setting having 1A or 5A
Stelmec Limited |

Over Current and Earth Fault Relay

37

SLR140

USER MANUAL

System Setting
Via the submenus of the System setting menu the following can be read and set:
Setting of date & time.
RS485 Module configurations Port enables Protocol, Parity, and Device ID.
Reclose Function
Via the submenus of the Reclose Function menu the following can be read and
set:
No of Reclose.
Cycle Time 1, Cycle Time 2, Cycle Time 3, Cycle Time 4,
Recycle Time.
Reclose Pulse Time.
Lockout Reset Time.

7. Communication
The PC Port is used for on site parameterization of the relay, for downloading
of a program and for reading relay parameters to a PC. For connection to a PC,
one RS 232C serial port is available on the front panel of the relay.
7.1. Mod bus RS485 Communication
The interface popularly known as RS-485 is an electrical specification for
multipoint systems that use balanced lines. RS-485 is similar to RS-422, but RS422 allows just one driver with multiple receivers whereas RS-485 supports
multiple drivers and receivers.
RS-485 is actually a physical layer specification which allows multiple nodes to
be connected to a differential 2-wire bus. Unlike RS-232 which can be full
duplex (transmit and receive at the same time), RS-485 exchanges must be half
duplex. This means there must be rules about who can talk and when.
RS485 is the most versatile communication standard in the standard series

defined by the EIA, as it performs well on all four points. That is why RS485 is
currently a widely used communication interface in data acquisition and
control applications where multiple nodes communicate with each other.

Stelmec Limited |

Over Current and Earth Fault Relay

38

SLR140

USER MANUAL

8. Output Response Curves


8.1. Low Set Characteristics Curves
The inverse definite minimum time (IDMT) characteristics curve in SLR140 with
IEC 60255 having seven selectable curves which are following:
8.1.1. Normal inverse curve

8.1.2. Very inverse curve

Stelmec Limited |

Over Current and Earth Fault Relay

39

SLR140

USER MANUAL

8.1.3. Extremely inverse curve

8.1.4. Long time inverse curve

Stelmec Limited |

Over Current and Earth Fault Relay

40

SLR140

USER MANUAL

8.1.5. 1.3S curve

8.1.6. 3S curve

Stelmec Limited |

Over Current and Earth Fault Relay

41

SLR140

USER MANUAL

8.2. High Set Characteristics


The high-set is selectable between definite time and instantaneous tripping
characteristics.

9. Application Circuit for 3O/C and 1E/F

Stelmec Limited |

Over Current and Earth Fault Relay

42

SLR140

USER MANUAL

10. Protection Stages


10.1. Over Current Protection Stages
A. Over Current Stage I> (50)
Current Setting Range
Definite Time Characteristic
Operating Time
Inverse Time Characteristic
7 Characteristic Curve Sets
Time Multiplier K
Starting Time
Resetting Time
Resetting Ratio
Inaccuracy
Starting
Operating Time Definite Time
Operating Time Inverse Time

10% 300%
0.05 300.0 s (step 0.01)

EI,VI,NI,LTI,3.0 S,1.3 S,DT


0.05 2.0
<60 ms
<60 ms
0.97
2% of set value
1% or 30 ms
5% or at least 30 ms (I<50 x In)

B. Over Current Stage I>> (51)


Current Setting Range
Definite Time Characteristic
Operating Time

Stelmec Limited |

100% 4000%
0.05 2.0 s (step 0.01)

Over Current and Earth Fault Relay

43

SLR140

USER MANUAL
Starting Time
Resetting Time
Resetting Ratio
Inaccuracy
Starting
Operating Time

<30 ms
<60 ms
0.97
2% of set value
1% or 30 ms

10.2. Earth Fault Current Protection


A. Earth Fault Current Stage Io> (50N)
Current Setting Range
Definite Time Characteristic
Operating Time
Inverse Time Characteristic
4 Characteristic Curve Sets
Time Multiplier K
Starting Time
Resetting Time
Resetting Ratio
Inaccuracy

5% 100%
0.05 300.0 s (step 0.01)
EI,VI,NI,LTI,1.3Sec,3.0Sec,DMT
0.05 2.0
<60 ms
<60 ms
0.97
2% of set value or
3% of rated value
1% or 30 ms
5% or at least 30 ms (I,<5 x In)

Starting
Operating Time Definite Time
Operating Time Inverse Time

B. Earth Fault Current Stage IO>> (51N)


Current Setting Range
Definite Time Characteristic
Operating Time
Starting Time
Resetting Time
Resetting Ratio
Inaccuracy

50% 2000%
0.05 2.0 s (step 0.01)
<50 ms
<60 ms
0.97

Starting

2% of set value or
3% of rated value

Operating Time Definite Time

1% or 30 ms

10.3. Auto Reclose Protection


Reclose Delay
Close Pulse
Reclaim Time
Dead time Lockout
Recovery Delay
Reclose Shots

0.2s to 14400s (4h)


1s to 10s
0.2s to 14400s (4h)
0.2s to 14400s (4h)
0.2s to 14400s (4h)
UPTO 4 (5 Trips)

11. Technical Data


Stelmec Limited |

Over Current and Earth Fault Relay

44

SLR140

USER MANUAL

11.1. Auxiliary voltage


Supply Voltage
Supply Frequency
VA Rating
Typical Burden
Maximum Burden
Power Of Withstand

24~110V AC/DC or 85~265V AC/DC


50Hz or 60Hz
3 VA Typical
8W (For Non-Operating Relay)
<12 W (For Operating Relay)
20ms

11.2. Current Inputs


CT Inputs Phase 1A/5A

characteristics

Range Of Measurement

0.3 In to 24 In

Burden At In

<0.2 VA

Permanent Thermal Withstand

3 In

1 Sec Thermal Withstand

100 In

Dynamic Withstand (1/2 Cycle)

250 In

Earth-fault CT Input1A/5A

characteristics

Range Of Measurement

0.03 In to 2.4 In

Burden At In

<0.5 VA

Permanent Thermal Withstand

1 In

1 Sec Thermal Withstand

40 In

11.3. Trip Contacts (T1 & T2)


Number Of Contacts
Rated Voltage
Continuous Carry
Max. Making Current
Breaking Capacity, AC
Breaking Capacity, DC (L/R = 40ms)
Contact Material

2 Making Contacts
250V ac
5A
15A
2000 W/VA
50W
AgNi 90/10

11.4. Accuracy
Protection Thresholds
Time Delay
Measurements

Stelmec Limited |

5%
5 % with a Minimum of 50 ms
5%

Over Current and Earth Fault Relay

45

SLR140

USER MANUAL

12. Construction
12.1. Mechanical
Mounting
Front Panel
Approximate Weight

Panel Mounting
Standard DIN mm x mm
2.3 kg.

12.2. Dimensional Drawing

Stelmec Limited |

Over Current and Earth Fault Relay

46

SLR140

USER MANUAL

12.3. Panel Mounting

Stelmec Limited |

Over Current and Earth Fault Relay

47

SLR140

USER MANUAL

12.4. Semi-Flush Mounting

13. Commissioning
Stelmec Limited |

Over Current and Earth Fault Relay

48

SLR140

USER MANUAL

Before the commissioning of the relay, it is necessary to check that the


following:

9 The current transformers secondary rated current in conformity with the


rating mentioned on the relay label.
9 Wiring is in conformity with the connection diagram.
9 Auxiliary supply should be match with the auxiliary supply range of the
relay
label
9 Tripping circuit is OK

Stelmec Limited |

Over Current and Earth Fault Relay

49

SLR140

USER MANUAL

14. Ordering Information


When you asking for quotations or ordering, please tick the appropriate box in
line with your requirements and sent it to us.

Communicable SLR140

Models

Non-Communicable SLR140

Auxiliary voltage

24-110V AC/DC

85-265V AC/DC

Ct- Rating

1A

5A

Stelmec Limited |

( with Auto-Recloser)

Over Current and Earth Fault Relay

50

SLR140

USER MANUAL

15. Contact Information

STELMEC LIMITED
SB UNIT III,
PLOT NO 14/15,
N.H.NO.8,
SATIVALI EAST,
DIST: THANE 401202,
MAHARASHTRA, INDIA.
FAX: +91-250-3255415,
TEL: +91-250-2480671/097.

e-mail: relay@stelmec.com.
Visit Us At: www.stelmec.com.

Stelmec Limited |