ADDAD-5 Series

10 (100) A, 20(160)A, Class 1


1.5(6)A Class 0.5S
3 Phase 4 Wires, 3 Phase 3 Wires Direct
Connection
And
CT, CT-VT Through Connection
Multi Tariff Digital Energy Meter

V4, September 2012

Advanced Electronics Company, Ltd.


P. O. Box 90916
Riyadh 11623
Kingdom of Saudi Arabia

1/17

Revision History
Revision
1
2
3

Date
July 2011
August 2011
September 2011
February 2012

September 2012

Highlights
Preliminary Electrical Parameters
Update specification
Update specification
Update Meter picture
Connection diagram updated for CT/VT,
Note update in pg.3: phase-Y as reference instead of phase-B

Notice
The information contained in this document is subject to change without notice. AEC makes no
warranty of any kind with regard to this material, including, but not limited to, the implied
warranties of merchantability and fitness for a particular purpose. AEC shall not be liable for
errors contained herein or incidental consequential damages in connection with the furnishing,
performance, or use of this material.
This document contains proprietary information which is protected by copyright. All rights are
reserved. No part of this document may be photocopied or otherwise reproduced without consent
of AEC.
Copyright (c) 2012 by AEC
Published in a limited copyright sense, and all rights, including trade secrets, are reserved.

V4, September 2012

2/17

1. Introduction
The ADDAD-5 Smart Meters are designed to meet the needs of residential, commercial and
industrial energy consumers. AECLs IEC-Standard Multi Tariff Digital Energy Meters set a new
standard for revenue-grade energy meters. It provides a highly accurate energy and demand
metering system with a comprehensive information display on an extended temperature large
LCD. It is capable of remote access via a various types of communication ports in metersin
addition it can be easily connected to SCADA system.
The ADDAD -5 poly phase smart meter series comprises of 10(100) A, 20(160) A, 1.5(6) A, 3Phase-4-Wires, 3-Phase-3-Wires, Direct (Whole current) connection, Transformer operated CT
and CT-VT through connection meters.
The emerging AMR technologies in the metering industry call for smart meters that have
enormous communication capabilities. The ADDAD-5 Smart Meters composite of all advanced
metering functionalities and its robust communication capabilities can easily be an integral part of
the Automatic Meter Reading System (AMR) or Smart grid. AEC also provides state of the art
AMR software to manage its smart meters remotely.

Notes:
All default values are configured based on customer request.
For 3P3W meters phase-Y is considered as reference instead of neutral

V4, September 2012

3/17

1.1 Meter Front Display

Note: The above display is just a sample and the text on meter name plate shall vary according
to meter type.

V4, September 2012

4/17

2. Product Description
2.1 Meter Features
kWh, kvarh and kVAh digital metering in import and export directions
Separate registers for import and export
Meets international standard IEC62052-11, IEC62053-21, IEC62053-22 and IEC62053

23.
Class 1 and Class 0.5S accuracy for kWh. Class 2 for kvarh per IEC62053-23
-20 to +70C operational temperature
Wide range three phase power supply built in up to 318V L-N or 550V L-L.
Extended Temperature Large LCD display, with programmable number of digits for
displaying the reading.
Pulse LED for accuracy testing (Imp/kWh and Imp/kvarh)
SO and EOI electrical output pulse per IEC62053-31.
Internal Real Time Clock with battery backup. Per IEC62054-21 (2004-05).
Storing reading in EEPROM that does not require any battery backup with minimum data
retention of 20 years
Measure and display the following:
kWh, kvarh, kVAh in all tariffs, import and export directions.
PF for total system power factor and per phase,
Voltage per phase,
Current per phase,
Total three-phase active power.
Total three-phase reactive power,
Total three-phase apparent power,
Line frequency,
Demand kW, kvar and kVA total import and export directions
Maximum Demand kW, kvar and kVA import and export directions (Basic &TOU)

Configurable to select block method or sliding window method for demand calculation
8 Multiple Tariffs registers for kWh, kvarh and kVAh (Time of Use) import and export
directions
o Up to 8 TOU
o Up to 620 Special days.
20 days regular (repeated every year e.g. national day)
600 irregular days for 30 years (each year 20 days)
o Up to 10 seasons
o Up to 10 weeks
o Up to 31 days
o Each day up to 10 Scripts

Simple Meter installation at site, with date and time stamp recording:
o Catch reverse run caused by cable swapping.
o Catch phase and neutral swapping.
o Catch unconnected phases.
o Catch Phase sequence revisal

Tamper detection with date and time stamp recording:


o Detect top cover open
o Detect terminal cover open
o Detect external CT short for CT operated Meters (requires CT on neutral line).

V4, September 2012

5/17

Detect Outage.

Event detection with date and time stamp:


Over Current/Under Voltage limit violation
Detect low total system power factor
Auto demand reset.
Manual demand reset.
Meter Configuration.
Battery failure
Clock Initialization
Memory Error
Meter Initialization
Time change (Before/After)
Demand Reset
Manual Demand Reset
Auto-Reset
Meter Configuration Change
Communication Port log
Output Relay Control

Support Demand integration periods of 5, 15, 30 and 60 minutes.


Store the maximum demand for the below registers:
1.
2.
3.
4.
5.
6.
7.
8.

Max Demand kW Import


Max Demand kW Export
Max Demand kvar Import
Max Demand kvar Export
Max Demand kvar Q1
Max Demand kvar Q4
Max Demand kVA Import
Max Demand kVA Export

Load Profile storage for 4320 points (enough for 90 days at 30 minutes interval)
Load Profile storage for (9 channels) + (Temperature, Status, Date/Time stamp)
The 9 channels are selected from the below channel options:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.

V4, September 2012

Demand kW Import
Demand kW Export
Demand kvar Import
Demand kvar Export
Demand kvar Q1
Demand kvar Q4
Demand kVA Import
Demand kVA Export
Average PF
Voltage Phase 1
Voltage Phase 2
Voltage Phase 3
Current Phase 1
Current Phase 2
Current Phase 3
Power Factor Phase 1
Power Factor Phase 2
Power Factor Phase 3
Frequency

6/17

Support 12 programmable EOB (End Of Billing).


Daily Energy profile provide reading for the last previous 4 days
Utility Sealed battery door and reset switch.
Communication Features
Optical Communication port complies with IEC62056-21 Mode E, 9600bps.
RS485, 9600bps.

V4, September 2012

7/17

2.2 Electrical Specifications


Meter Type
Accuracy Class
kWh
kVARh
kVAh
Standard
Connection
Operating Frequency
Input Voltage Range for
measurements (L-to-N)
Range, VAC

Nominal, VAC

10(100)

20(160)

1.5(6)

1
2
1
IEC62053-21,
IEC62053-23
3 Ph 4 Wire

1
2
1
IEC62053-21,
IEC62053-23
3 Ph 4 Wire

60Hz

60Hz

0.5s
2
1
IEC62053-22,
IEC62053-23
3 Ph 4 Wire,
3 Ph 3 Wire
60Hz

100 to 318

100 to 318

100 to 318 3P4W


86 to 120 3P3W

3x127/220,
3x133/230,
3x220/380,
3x 230/400,
3x 277/480

3x127/220,
3x133/230,
3x220/380,
3x 230/400,
3x 277/480

3P4W:
3x127/220,
3x133/230,
3x220/380,
3x 230/400,
3x 277/480
3P3W:
3x100,
3x110,
3x120

Maximum Power Supply


Operating Voltages
L-N VAC
L-L VAC
Current and Voltage Connection

Reference Current, (In) (Amps)


Maximum Current, (Imax) (Amps)
Short Circuit Current, (Amps)
30xImax for Direct for 10ms
20xImax for CT for 500ms
Minimum Current, (Amps)
(0.05 In) A for (DIRECT)
(0.01 In) A for (CT, CT-VT)
Starting Current, (Amps)
(0.004 In) A (DIRECT)
(0.001 In) A (CT, CT-VT)
Power consumption in voltage
circuit per phase
At 3x133/230
At 3x230/400
At 3x277/480

V4, September 2012

318
550
Direct
(Whole current)

318
550
Direct
(Whole current)

318
550
CT, CT-VT

10
100
3000

20
160
4800

1.5
6
120

0.5

0.015

0.04

0.08

0.0015

0.5 W, 0.65 VA
0.6 W, 1.0 VA
0.65 W, 1.2 VA

0.5 W, 0.65 VA
0.6 W, 1.0 VA
0.65 W, 1.2 VA

0.5 W, 0.65 VA
0.6 W, 1.0 VA
0.65 W, 1.2 VA

8/17

Power consumption in Current


circuit per phase
At 10 A
At 100 A
At 1.5 A
At 6 A
Output Pulse Ratio
imp / kWh
imp / kVARh
Output Pulse LED
Color
Peak emission
wavelength
Spectral Line Half-width

0.05 VA
5 VA

0.05 VA
5 VA
0.06 VA
0.4VA

1000
1000

1000
1000

10000
10000

Red
635nm
40nm

Red
635nm
40nm

Red
635nm
40nm

SO & EOI Output Pulse


Switching Power
No. of Measuring Element:
3Phase 4Wire
Energy
Voltage
Current
3Phase 3Wire
Energy
Voltage
Current

30V / 30mA

3
3
3

3
3
3

3
3
3 + Neutral

Conductor bore diameter

9.2mm

2
2
2
9.2mm

5mm

2.3 Electromagnetic Compatibility Specifications


Test severity level 4.
Electrostatic discharge
Per IEC61000-4-2

Contact Discharge: Test Voltage 8kV.


Air Discharge: Test voltage 15kV.
Test severity level 3.
Frequency band 80MHz to 2000MHz.

Electromagnetic HF field
Per IEC61000-4-3

Test field strength 10V/m. with current


Test field strength 30V/m. without current
Test severity level 4.

Fast transient burst


Per IEC61000-4-4 (5/50nS
waveform)

Test voltage at current and voltage circuit: 4kV.

Conducted EMC

Per CISPR 22 class B

V4, September 2012

Test duration 60 seconds.

9/17

Frequency band 150kHz to 30MHz.


Radiated EMC
Surge immunity Test
Per IEC61000-4-5 (1.2/50us)

Per CISPR 22 class B


Frequency band 30MHz to 1000MHz.
Test severity level 4.
Test Voltage 4kV.
Test Voltage
Common mode, 2.5kV

Damped Oscillatory wave


immunity
Per IEC61000-4-12

Differential mode, 1kV


Test frequency
100kHz, repetition rate, 40Hz
1MHz, repetition rate, 400Hz

Immunity to conducted
disturbances
Per IEC61000-4-6
Power Frequency withstand
voltage

Frequency band 150kHz to 80MHz.

2kV

2.4 Electrical Compatibility Specifications


Static meters for active energy
(classes 1 and 2)

Per IEC62053-21

Static meters for active energy


(classes 0,2 S and 0,5 S)

Per IEC62053-22

Static meters for reactive


energy (classes 2 and 3)

Per IEC62053-23

2.5 Communication Interface


OPTICAL Port
Optical Link

Infrared, 860nm - 950nm

Optical Port

Per IEC62056-21

Max. Baud rate

9600 bps

RS485

9600 bps

2.6 Backed up Battery for the RTC


Back up type
Life

Lithium Battery
Meter operates in normal conditions: 10 years.
With AC power off: 1 year.

V4, September 2012

10/17

2.7 Back up for readings and Data


Back up type

EEPROM

Life

With AC power off: 20 years.

2.8 Output Relay Specifications

Rated Voltage

The contact is change over, form C,


NO/NC
250VAC/ 30VDC

Continuous rated current

2A

Max. Operating Voltage

250VAC/ 30VDC

Contact

2.9 Mechanical Specifications


Terminal insulation

Per IEC 62052-11

Impulse Voltage Withstand

6KV (1.2/50uS impulse) 62053-11

Terminal heat resist

Per IEC62052-11, IEC60095-2-11

Dust & water

Per IEC62052-11, IEC529; IP54


Per IEC 62052-11, IEC 60068-2-5,
procedure A, 55C, 3 days
10-150Hz @ 1g, 75 min.

Solar Radiation
Vibration

Per IEC 62052-11, IEC60068-2-6


Shock

Half sine @ 30g impulse for 18ms

LCD Viewing area Dimensions (mm)

Per IEC 62052-11, IEC68-2-27


(Direct) Whole current meter is 2.4 kg,
(CT, CT-VT) Transformer Operated Meter
is 1.6 kg.
Direct: W= 189, H= 270, D= 107.3
CT and CT/VT: W= 189, H= 270, D= 87.3
73 x 31.5

LCD main digit size Dimensions (mm)

9.0x4.5

Case Material

Polycarbonate.
IEC 62052-11, IEC 60068-2-75.
Apply kinetic energy of 0.2J

Weight
Overall Dimensions (mm)

Spring hammer

2.10 Climatic Specifications

V4, September 2012

11/17

Dry heat

Per IEC 62052-11, IEC 60068-2-2

Cold

Per IEC 62052-11, IEC 60068-2-1


Per IEC 62052-11, IEC 60068-2-30 for
outdoor meter

Damp heat cyclic

2.11 Environmental Specifications


Operating Temperature

-20 to +70 degree C

Storage Temperature

-30 to +85 degree C

Humidity

95 % non-condensing

2.12 LCD Appearance

V4, September 2012

12/17

2.13 Dimension and appearance


Direct Meters:

CT and CT/VT Meters:

V4, September 2012

13/17

3.2 Connection Diagram:


DIRECT (WHOLE CURRENT) 3-PHASE 4-WIRES (3P4W) TYPE METERS

21

22

RJ45-left
15

10

11

V4, September 2012

Power Flow

16

17

COM NO NC
Output Relay

Source

RJ45-Right

Load

14/17

CT, CT-VT 3-PHASE 4-WIRES (3P4W) TYPE METERS

V4, September 2012

15/17

CT-VT 3-PHASE 3-WIRES (3P3W) TYPE METERS

V4, September 2012

16/17

6. Ordering Information
The meter can be ordered using below format.
1

Model #
ADDAD5
Meter Type
Direct

CT-VT

CT

Meter Connection
3P3W

3P4W

Meter Accuracy
Class 2

Class 1

Class 0.5

Class 0.2

Voltage Range
(3x 133/230 and 3x 230/400 VAC)

(3x 110 120 VAC)

(3x 57.7/100 ~ 69.3/120)

(3x 57.7/100 ~ 3x 230/400 VAC)

3x 277/480 VAC

(3x 127/220 ~ 3x 277/480 VAC)

Current Range
10(100) A

20(160) A

1.5(6) A

1(6) A

5(6) A

1(1.2)A

Additional Communication Port


RS485 Port

V4, September 2012