You are on page 1of 62

Power Quality and Harmonic

Mitigation

AccuSine

Add photo in this area

Make the most of your


energy
Make the most of
SM
your energy

Agenda
Overview
Harmonic Basics
IEEE 519
Conventional Harmonic Mitigation Methods
AccuSine PCS
Applications & Installation Notes
Specification Recommendations
Summary

Schneider Electric

- Power Quality Correction Group May 2009

Schneider Power Quality Correction Group

Power Factor Correction and


Harmonic Filtering:
Capacitor Systems
LV & MV up to 15 kV
Fixed, Standard and
Detuned Auto Banks
AccuSine PCS

Voltage Regulation:
Hybrid VAR Compensator
Electronic Sag Fighter

Schneider Electric

- Power Quality Correction Group May 2009

Harmonic Basics
Resultant
Waveform

What are harmonics?


Proliferated by power semiconductor devices
Converts power (AC to DC)
A harmonic is a component of a periodic wave
having a frequency that is an integer multiple of
the fundamental power line frequency
Characteristic harmonics are the
predominate harmonics seen by the power
distribution system
Predicted by the following equation:
Hc = np +/- 1
hC = characteristic harmonics to be expected
n = an integer from 1,2,3,4,5, etc.
p = number of pulses or rectifiers in circuit

Schneider Electric

- Power Quality Correction Group May 2009

3rdHarmonic

7thHarmonic

5thHarmonic

Harmonic
1
2
3
4
5
6
7
:
19

Fundamental

Frequency
60Hz
120Hz
180Hz
240Hz
300Hz
360Hz
420Hz
:
1140Hz

Sequence
+
0
0
0
0
+
:
+

Multi-pulse Converters

Hc = np +/- 1
Hc = characteristic
harmonic order present
n = an integer
p = number of pulses

Schneider Electric

- Power Quality Correction Group May 2009

Hn
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
43
45
47
49

Harmonics present by rectifier design


Type of rectifier
1 phase 2 phase 3 phase 3 phase 3 phase
4-pulse
4-pulse 6-pulse 12-pulse 18-pulse
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
5

Harmonic Basics
Nonlinear loads draw it
Example: 6-Pulse VFD

Inverter

Converter
DC bus

A
B
C

Schneider Electric

- Power Quality Correction Group May 2009

Harmonic Basics
Why a concern?
Current distortion
Added heating, reduced capacity in :
Transformers
Conductors and cables
Heating effect proportional to harmonic order
squared
Nuisance tripping of electronic circuit
breakers (thermal overload)
Blown fuses
Detrimental to generators
Heating of windings
Detrimental to UPS
UPS cant supply the current

Schneider Electric

- Power Quality Correction Group May 2009

Ih

Loads

Vh = Ih x Zh

Harmonic Basics
Voltage distortion
Interference with other electronic loads
Faulting to destruction
Creates harmonic currents in linear loads
Generator regulators cant function
Shut downs

Ih

Not compatible with standard PF caps


Potential resonance condition
Excessive voltage
Overheating of PF correction capacitors
Tripping of PF protection equipment
Shutdown / damage to electronic equipment
Loads

Vh = Ih x Zh

Schneider Electric

- Power Quality Correction Group May 2009

Total Power Factor


TPF = (DPF) x (Distortion factor)
KW
DPF =
KVAf

= Cos

Distortion Factor =

= Cos

1 + THD(I)2

TPF = Total or true power factor


DPF = Displacement power factor
Distortion Factor = Harmonic power factor

Schneider Electric

- Power Quality Correction Group May 2009

Total Power Factor Example


Variable frequency drive (PWM type)
DPF = .95
THD(I) = 90%
(no DC choke & no input line reactor)
Distortion Factor =

= .7433

1 + .92
TPF = .95 x .7433 = .7061

Schneider Electric

- Power Quality Correction Group May 2009

10

How are harmonics handled today?


Mixed bag of objectives
Basis of compliance is mixed
THDi, THDv, TDD?
IEEE 519-1992?
Where is PCC?
What level of harmonics is to be attained?
How to obtain compliance?
Sometimes defined
Sometimes open ended
Validation
Poorly defined
By each equipment vendor
No Total Responsibility for harmonics
Has the User been protected where it matters inside the facility

Schneider Electric

- Power Quality Correction Group May 2009

11

Typical Present Situation


Specifications direct manufacturers of nonlinear loads to comply within
equipment specifications
Manufacturers of nonlinear loads have other concerns
Sell standard equipment at competitive prices
Leads to minimized harmonic solutions
Leads to misleading information about harmonic performance
Leads to operational difficulties
e.g. Cant operate on backup generators/UPS
Force the IEEE 519 discussion to the utility PCC

Many types of solutions are not compatible


Each manufacturer does his own thing without regard to other solutions
Approaches are for my equipment only
My simulation is for my equipment only I cant include the others

Total solution not achieved


User has system that exceeds specification objectives
Consulting engineers cant get overall compliance

Schneider Electric

- Power Quality Correction Group May 2009

12

ANSI Standard IEEE 519-1992


Issues addressed:
THD(V) delivered by utility to user (Chapter 11)
THD(V) must be < 5% [< 69 KV systems]
Defines the amount of TDD a user can cause (Chapter 10)
Based upon size of user in relation to power source
Table 10.3 for systems < 69 kV
Defines limits for voltage notches caused by SCR rectifiers Table
10.2
Defines PCC (point of common coupling)

Schneider Electric

- Power Quality Correction Group May 2009

13

IEEE 519-1992
Defines current distortion as TDD
Total Demand Distortion
Largest amplitude of harmonic current occurs at maximum
load of nonlinear device if electrical system can handle
this it can handle all lower amplitudes
Always referenced to full load current
Effective meaning of current distortion

Defines voltage distortion as THD


Total harmonic voltage distortion

Does not use THD(I)


Total harmonic current distortion
Instrument measurement (instantaneous values)
Uses measured load current to calculate THD(I)

Schneider Electric

- Power Quality Correction Group May 2009

14

IEEE 519-1992
TDD and THD(I) are not the same except at 100% load
As load decreases, TDD decreases while THD(I) increases.
Example:

Total I,
rms
Full load

Schneider Electric

936.68
836.70
767.68
592.63
424.53
246.58
111.80

- Power Quality Correction Group May 2009

Measured
Fund I, Harm I,
rms
rms
936.00
836.00
767.00
592.00
424.00
246.00
111.00

35.57
34.28
32.21
27.23
21.20
16.97
13.32

THD(I)
3.8%
4.1%
4.2%
4.6%
5.0%
6.9%
12.0%

TDD
3.8%
3.7%
3.4%
2.9%
2.3%
1.8%
1.4%
15

IEEE 519-1992 Table 10.3


Current Distortion Limits for General Distribution
Systems (<69 kV)
I sc / Iload
<20
20<50
50<100
100<1000
>1000

<11
4.0%
7.0%
10.0%
12.0%
15.0%

11<=h<17 17<=h<23 23<=h<35


2.0%
1.5%
0.6%
3.5%
2.5%
1.0%
4.5%
4.0%
1.5%
5.5%
5.0%
0.2%
7.0%
6.0%
2.5%

h>=35
0.3%
0.5%
0.7%
1.0%
1.4%

TDD
5.0%
8.0%
12.0%
15.0%
20.0%

Isc = short circuit current capacity of source


Iload = demand load current (fundamental)
TDD = Total Demand Distortion
(TDD = Total harmonic current distortion measured against
fundamental current at demand load.)

Schneider Electric

- Power Quality Correction Group May 2009

16

Harmonic Standards
Most harmonic problems are not at the PCC with utility.
Typically harmonic problem occur:
Within a facility
With generator & UPS operation
Where nonlinear loads are concentrated

Need to protect the user from self by moving the harmonic


mitigation requirements to where harmonic loads are located

Schneider Electric

- Power Quality Correction Group May 2009

17

Agenda
I. Harmonic Basics
II. Conventional Harmonic Mitigation Methods
III. AccuSine PCS
IV. Applications
V. Specification Recommendations
VI. Summary

Schneider Electric

- Power Quality Correction Group May 2009

18

Harmonic Mitigation Methods


Typically applied per device
Line reactors/DC bus chokes/isolation transformers
5th harmonic filters (trap filters)
Broadband filters
Multi-pulse transformers/converters
Active front end (AFE) converter

System solution
Active harmonic filter

Schneider Electric

- Power Quality Correction Group May 2009

19

Harmonic mitigation methods - (Applied per VFD)


Solution

Advantage

Disadvantage

Typical %
TDD

Typical Price
Multiplier*

Dependent
upon SCR***

Cost of transformer and


installation change out

Increase short
circuit capacity

Reduces THD(V)

Increases TDD
Not likely to occur**

C-Less Technology

Lower TDD
Simplified design
Less cost

Compliance is limited
Application limited
Size limited

30 - 50% TDD

0.90 - 0.95

Impedance (3% LR
or 3% DC choke)

Low cost adder


Simple

Compliance difficult

30 - 40% TDD

1.05 - 1.15

5th Harmonic filter

Reduces 5th & total


TDD

Does not meet harmonic


levels at higher orders^

18 - 22% TDD

1.20 - 1.45

Broadband filter

Reduces TDD (thru


13th)

Large heat losses


Application limited

8 - 15% TDD

1.25 - 1.50

12-pulse rectifiers

Reduces TDD
Reliable

Large footprint/heavy
Good for >100 HP

8 - 15 % TDD

1.65 - 1.85

18-pulse rectifiers

Reduces TDD
Reliable

Large footprint/heavy
Good for >100 HP

5 - 8% TDD

1.65 - 1.85

Active front end


converter

Very good TDD


Regeneration
possible

Large footprint/heavy
Very high cost per unit
High heat losses

< 5% TDD

2.0 - 2.5

* Price compared to a standard 6-pulse VFD.


** Utilities and users are not likely to change their distribution systems.
*** Increasing short circuit capacity (lower impedance source or larger KVA capacity) raises TDD but lowers THD(V).
^ Can be said for all methods listed.

Harmonic mitigation methods


Solution

Advantage

Disadvantage

Typical %
TDD

Typical Price
Multiplier*

Dependent
upon SCR***

Cost of transformer and


installation change out

Increase short
circuit capacity

Reduces THD(V)

Increases TDD
Not likely to occur**

C-Less Technology

Lower TDD
Simplified design
Less cost

Compliance is limited
Application limited
Size limited

30 - 50% TDD

0.90 - 0.95

Impedance (3% LR
or 3% DC choke)

Low cost adder


Simple

Compliance difficult

30 - 40% TDD

1.05 - 1.15

5th Harmonic filter

Reduces 5th & total


TDD

Does not meet harmonic


levels at higher orders^

18 - 22% TDD

1.20 - 1.45

Broadband filter

Reduces TDD (thru


13th)

Large heat losses


Application limited

8 - 15% TDD

AccuSine

12-pulse rectifiers

Reduces TDD
Reliable

Large footprint/heavy
Good for >100 HP

8 - 15 % TDD

1.65 - 1.85

18-pulse rectifiers

Reduces TDD
Reliable

Large footprint/heavy
Good for >100 HP

5 - 8% TDD

1.65 - 1.85

Active front end


converter

Very good TDD


Regeneration
possible

Large footprint/heavy
Very high cost per unit
High heat losses

AccuSine
< 5% TDD

2.0 - 2.5

* Price compared to a standard 6-pulse VFD.


** Utilities and users are not likely to change their distribution systems.
*** Increasing short circuit capacity (lower impedance source or larger KVA capacity) raises TDD but lowers THD(V).
^ Can be said for all methods listed.
Schneider Electric

- Power Quality Correction Group May 2009

21

Inductors/Transformers/DC Bus Chokes


Description:
Converter-applied inductors or isolation transformers.
Pros:

Inexpensive & reliable


Transient protection for loads
1st Z yields big TDD reduction (90% to 35% w/3% Z)
Complimentary to active harmonic control

Cons:
Limited reduction of TDD at equipment terminals after 1st Z
Reduction dependent on source Z

Schneider Electric

- Power Quality Correction Group May 2009

22

5th Harmonic Filter (Trap


Filter)
Inductor (Lp) and Capacitor (C) provide low
impedance source for a single frequency
(5th)
Zs

Must add more tuned filters to filter more


frequencies

Inductor Ls required to detune filter from


electrical system and other filters

Vs

Ls
Lp
C

Load

If Ls not present, filter is sink for all 5th


harmonics in system
If Ls not present, resonance with other
tuned filters possible
Injects leading reactive current (KVAR) at
all times may not need

Schneider Electric

- Power Quality Correction Group May 2009

23

Broadband Filters
L

~
Source

Load

Lp
C

Mitigates up to 13th order or higher


Each inductor (L) > 8% impedance
V drops ~ 16% at load
Trapezoidal voltage to load
Can only be used on diode converters
Prevents fast current changes (only good for centrifugal loads)
When generators are present, re-tuning may be required
Capacitor (C) designed to boost V at load to proper level (injects leading VARs)
Physically large
High heat losses (>5%)
Series device

Schneider Electric

- Power Quality Correction Group May 2009

24

Multi-Pulse Drives
Description: Drives/UPS with two (12 pulse) or three (18 pulse) input bridges
fed by a transformer with two or three phase shifted output windings.
Pros:
Reduces TDD to 10% (12 pulse) & 5% (18 pulse) at loads
Reliable

Cons:

High installation cost with external transformer


Large footprint (even w/autotransformer)
Series solution with reduction in efficiency
One required for each product
Cannot retrofit

Schneider Electric

- Power Quality Correction Group May 2009

25

Harmonic mitigation methods


VFD mitigation topologies
6-Pulse converter

12-Pulse converter

18-Pulse converter
Multipulse
Transformer

DC Link
Reactor

DC+
Line
Reactor

2
9

DC Bus

Rectifier Assembly

Load

Wye

AC Line

DC-

Delta
Transformer
Tertiary

Delta

C-less or 3% reactance min (if


included); small footprint,
simplified cabling

Large footprint, more steel


& copper (losses)

Externally mounted 3 winding


transformer; more wire and
cabling; complicated

100

100

100

6 pulse

12 pulse

18 pulse
0.0s

Current waveform distorted


TDD 30% to 40% with 3% reactor
(depending on network impedance)

Schneider Electric

- Power Quality Correction Group May 2009

Current slightly distorted


TDD 8% to 15% (depending on
network impedance)

0.02s

Current wave form good


TDD 5% to 7% (depending on
network impedance)

26

Active Front End (AFE) Converters


Used in UPS and VFD
Replaces diode converter with IGBT converter
The hype
Permits current smoothing on AC lines (< 5% TDD)
Permits 4-quadrant operation of VFD
Maintains unity TOTAL PF
Meets all harmonics specs around the world

Input Filter
Required to
limit THDv to
<5%
A
C
S
o
u
r
c
e

VFD
IGBT

Filter
Schneider Electric

Converter

- Power Quality Correction Group May 2009

DC Bus

IGBT

Inverter

AC
Motor

27

AFE Converters
Significant harmonics above 50th order
American Bureau
of Shipping (ABS)
requires
examination to
100th order when
AFE applied

Higher frequencies
yield higher heating
of current path &
potential resonance
with capacitors

Schneider Electric

- Power Quality Correction Group May 2009

28

AFE Converters
Cons

200
KVA
rated
AFE
VFD

PWM
VFD

DC
Drive

PF
caps

100
KVA
rated

Schneider Electric

- Power Quality Correction Group May 2009

Larger and more expensive than 6 pulse drives


Approximately twice the size & price
Mains voltage must be free of imbalance and voltage
harmonics
Generates more harmonics
Without mains filter THD(V) can reach 40%
Requires short circuit ratio > 40 at PCC
Switched mode power supplies prohibited
Capacitors prohibited on mains
IGBT & SCR rectifiers prohibited on same mains
No other nonlinear loads permitted

29

Agenda
I. Harmonic Basics
II. Conventional Harmonic Mitigation Methods
III. AccuSine PCS
IV. Applications
V. Specification Recommendations
VI. Summary

Schneider Electric

- Power Quality Correction Group May 2009

30

The System Solution


The System Solution:
Single point of responsibility for the total harmonics
One specification for harmonic definitions
One validation responsibility and guarantee

Standard nonlinear products


3% input line reactors on most non-linear devices, 3% DC bus choke okay for
PWM VFD
Limits rms current at load for diode rectifiers
Avoids interaction with snubber circuit for SCR rectifier

Best cost and performance

Compatible with all nonlinear products


Compliance with harmonic specifications
Controls harmonic levels with facility

Schneider Electric

- Power Quality Correction Group May 2009

31

Schneider Electrics Solution


AccuSine Power Correction System (PCS)
Active harmonic filter
Provides 5% TDD per load or system
Cancels everything from 2nd to 50th harmonic order
Used on any/all nonlinear load
Active reactive current correction
Does not use PF capacitors
Used to correct Displacement PF
In conjunction with or independent of harmonic control (dual mode)
High-speed reactive power

Schneider Electric

- Power Quality Correction Group May 2009

32

Active Harmonic Filter System Solution


Applied to one or many nonlinear loads
VFD, UPS, UV, DC drives, DC power supplies

Provides DPF correction


More cost effective for multiple loads
For two or more drives, AccuSine and 6 pulse drive combination
has lower initial and operating costs than 18 pulse drives
For installations with redundant drives, size AccuSine for the
operating drives only

Saves space
Lower heat losses
Not critical to operation
Parallel connected

Schneider Electric

- Power Quality Correction Group May 2009

33

Comparison of 18-P VFD to


AccuSine PCS + standard VFD
Footprint required
AccuSine PCS+ Std VFD less than 18-P VFD
(w/autotransformer) for all conditions

Heat losses
AccuSine PCS+ Std VFD less than 18-P VFD
Exception at single units of 50-75 HP, advantage 18-P VFD

Less costly to operate AccuSine PCS+ Std VFD


Less site cooling required with AccuSine PCS + Std VFD

Price (first cost)


When more than one VFD, AccuSine PCS + Std VFD always
beats 18-P VFD
If only one VFD involved, 300-500 HP sizes favor 18-P VFD

Schneider Electric

- Power Quality Correction Group May 2009

34

AccuSine Active Harmonic Filter

Is

CT
Ia

Source

AHF

Il

AHF

Load

Parallel connected
Is + Ia = Il
Ia includes 2nd to 25/50th
harmonic current
Is <5% TDD
Schneider Electric

- Power Quality Correction Group May 2009

35

AccuSine PCS
Power Diagram
IGBT Module

Pre-charge
Contactor

S1

S3

S5

DC Bus
Capacitors

Fuse

AC
Lines

Fuse

Line
Inductor

Fuse

Inductor

Filter
Board

S2

Schneider Electric

- Power Quality Correction Group May 2009

S4

S6

36

System Solution
AccuSine PCS Sizing Example
A 125 HP variable torque 6-pulse VFD with 3% LR
Required AHF filtering capability = 47.5 amperes

Two 125 HP VT 6-pulse VFD w/3% LR


Required AHF size = 84.4 amps

Three 125 HP VT 6-pulse VFD w/3% LR


Required AHF size = 113.5 amps

Six 125 HP VT VFD w/3% LR


Required AHF size = 157.6 amps
(not 6 x 47.5 = 285 amps)

Schneider Electric

- Power Quality Correction Group May 2009

37

AccuSine Performance
At VFD Terminals
AccuSine injection

Source current

Schneider Electric

- Power Quality Correction Group May 2009

Order
Fund
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
43
45
47
49
TDD

AS off
AS on
% I fund % I fund
100.000%100.000%
0.038% 0.478%
31.660% 0.674%
11.480% 0.679%
0.435% 0.297%
7.068% 0.710%
4.267% 0.521%
0.367% 0.052%
3.438% 0.464%
2.904% 0.639%
0.284% 0.263%
2.042% 0.409%
2.177% 0.489%
0.293% 0.170%
1.238% 0.397%
1.740% 0.243%
0.261% 0.325%
0.800% 0.279%
1.420% 0.815%
0.282% 0.240%
0.588% 0.120%
1.281% 0.337%
0.259% 0.347%
0.427% 0.769%
1.348% 0.590%
35.28% 2.67%
38

700 HP Drive AccuSine ON OFF

Schneider Electric

- Power Quality Correction Group May 2009

39

700 HP Drive AccuSine ON OFF

Schneider Electric

- Power Quality Correction Group May 2009

40

700 HP Drive AccuSine ON OFF

Schneider Electric

- Power Quality Correction Group May 2009

41

700 HP Drive AccuSine ON OFF

Schneider Electric

- Power Quality Correction Group May 2009

42

700 HP Drive AccuSine ON OFF

Schneider Electric

- Power Quality Correction Group May 2009

43

Applications
Most common VFD sites
Centrifugal pumps and fans
Pumping Stations
Potable
Wastewater
Wastewater Plants
Water Purification (potable)

Disinfectant Systems
UV systems (ultraviolet)

Electronic ballasts 3
Ozone generators (SCR power supplies)

Industrial in-rush support

Schneider Electric

- Power Quality Correction Group May 2009

44

AccuSine PCS Specifications

Universal Application
208 480 VAC
No user action required to set
Highly customized transformers for higher voltages (to 15 kV)
50 or 60 Hz

Fuse protected (200,000 AIC)


UL 508 & CSA approved
CE EMC - 400V
Logic ride through 1 to 10 minutes

Schneider Electric

- Power Quality Correction Group May 2009

45

Specification Discussion
Write a specification in Section 16 for an active harmonic filter
Specify any points of concern for insertion of AHF
Size of AHF
Located per electrical bus
Specify total responsibility for all harmonics in facility
Specify TDD levels desired at each location
5% TDD guarantees 5% THDv (caused by the loads) with any source
Specify compliance tests for each location

Write standard nonlinear load specification


Reduces harmonic incompatibilities and product interactions
Need 3% impedance on each nonlinear load

Universal solution
Good for all nonlinear loads
Apply AccuSine per electrical bus (best economics)

Can attain 5% TDD per load or bus inside the plant


Avoids harmonic problems both TDD and THD(V)

Write TDD specs not THD(I) at 5%


Schneider Electric

- Power Quality Correction Group May 2009

46

AccuSine Tools
Internet Tools
Active Filter Guide Spec (www.reactivar.com)
Stand alone spec section (Section 16)
Includes harmonic and PF correction requirements
Selection Program (www.squaredleantools.com)
Easy selection based upon loads not source (same
selection for utility or generator)
Simple tool to use
We guarantee results if used properly during
design/layout stage
Brochure
Application Notes
Water/wastewater and other applications
Installation Bulletin
Best/total information for consultant
MCC Selector

Schneider Electric

- Power Quality Correction Group May 2009

47

Product Package
Standard (UL only)
Enclosed NEMA 1
50 amp 48H x 21W x 19D, 250 lbs
100 amp 65H x 21W x 19D, 350 lbs
Wall mounted
300 amp 75H x 32W x 20D, 775 lbs
Free standing

Chassis & NEMA12 Also Available

Schneider Electric

- Power Quality Correction Group May 2009

48

Product Package
International enclosures
NEMA 12, IP30, IP54
50 amp 75(1905mm) x 31.5(800mm)
x 23.62(600mm)
Weight 661Ib(300Kg)
100 amp 75(1905mm) x
31.5(800mm) x 23.62(600mm)
Weight 771Ib(350 Kg)
300 amp 91(2300mm) x
39.37(1000mm) x 31.5(800mm)
Weight 1212Ib(550 Kg)
Free standing with door interlocked
disconnect
CE Certified, C-Tick, ABS, UL, CUL

Schneider Electric

- Power Quality Correction Group May 2009

49

Product Re-packaging
Maximum ambient into air inlet 400C
Must meet air flow at inlet of AccuSine
50 amp 300 CFM
100 amp 500 CFM
300 amp - 1250 CFM

Heat released
50 amp 1800 watts
100 amp 3000 watts
300 amp 9000 watts

DIM considerations required


On chassis
Remote with cable

Schneider Electric

- Power Quality Correction Group May 2009

50

Product Re-packaging
MCC Packaging
50 & 100 amp models only
Requires one vertical 20 x 20 section
Includes circuit breaker

Schneider Electric

- Power Quality Correction Group May 2009

51

AccuSine PCS Current Transformers


AC lines
Class 1
400 Hz
Four sizes
500:5/1000:5/3000:5/5000:5
Stock split core round units

Added to AccuSine (when parallel connected & source sense)


Use solid core at equal ratio as AC lines CT

Schneider Electric

- Power Quality Correction Group May 2009

52

AccuSine PCS Performance


Load(s)
DEFINITIONS

Source

XFMR

Is = source current

Is

Il

Ias = AccuSine current


Ias

Il = total load current


(vector representations)

AccuSine Logic
Is + Ias = Il
AccuSine injects the harmonics the loads want
Schneider Electric

- Power Quality Correction Group May 2009

53

AccuSine PCS Performance


Obtain 5% TDD (current distortion)
Overall 10:1 attenuation
Cos = .998
Obtain near unity lagging DPF (Cos )
Optional: Inject to obtain a user set point
Either or both functions
VAR compensation
100 second detect-to-inject
Dynamic response
cycle to full control for step load changes

Schneider Electric

- Power Quality Correction Group May 2009

54

AccuSine PCS Overall Performance


Harmonic compensation
2nd through 50th order
Includes inter-harmonics
Independent of source impedance
Selection and operation same whether on AC line or backup generator or UPS
output

Reactive current injection


Secondary function to harmonic mode
Defaults to unity lagging set point
Injects leading or lagging reactive current

Schneider Electric

- Power Quality Correction Group May 2009

55

AccuSine PCS Cos Performance


In dual mode (Cos + Cos )
Reactive current injection is secondary to harmonic mitigation

Activation of Cos in the field via DIM


Default to unity lagging Cos
Can enter a set point (i.e. 0.90 lagging)
Can inject leading (capacitive) or lagging (inductive) reactive current

Schneider Electric

- Power Quality Correction Group May 2009

56

Dual Mode Operation


Ias =

Ih2 + Ir2

Ias = rms output current of AccuSine


Ih = rms harmonic current
Ir = rms reactive current
Ias
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0

Schneider Electric

- Power Quality Correction Group May 2009

Examples
Ih
10.0
20.0
30.0
40.0
50.0
60.0
70.0
80.0
90.0
95.0

Ir
99.5
98.0
95.4
91.7
86.6
80.0
71.4
60.0
43.6
31.2

57

AccuSine PCS
Installation Considerations
(When in harmonic mode does not apply for reactive mode-only)

Schneider Electric

- Power Quality Correction Group May 2009

58

AccuSine PCS Installation Considerations


For Optimal Performance:
Impedance 3% input line reactors (minimum) on every nonlinear load
Transformer, 3% DC bus choke for PWM VFD or long power cables (not
encapsulated type) can substitute for line reactors
Standardizes selection of AccuSine
Diode rectifiers: Need to limit rms current at load (limits rise of Ihrms at load)
Thyristor rectifiers: Need to protect snubbers (capacitors) on thyristor
No capacitors downstream of CT

Schneider Electric

- Power Quality Correction Group May 2009

59

AccuSine PCS Installation Considerations


Main Left

Main Right

Main-tie-main
Tie

CBml

CTml

CTtl

CBal

AccuSine L

CBmr

CTtr

CTmr
CBar

AccuSine R

This configuration provides individual AccuSine


operation per side regardless of breaker positions.

Schneider Electric

- Power Quality Correction Group May 2009

60

Summary
Universal solution
Good for all nonlinear loads (3-phase)
Apply AccuSine per electrical bus (best economics)

System Solution
Can attain 5% TDD per load or bus inside the plant
Guarantees 5% THDv
Requires 3% impedance at loads

Selection based upon loads


Easy to use on-line tool
www.squaredleantools.com

Schneider Electric

- Power Quality Correction Group May 2009

61

Thank You

Questions?

Schneider Electric

- Power Quality Correction Group May 2009

62

You might also like