You are on page 1of 3

IDR-144

Data Sheet - N00397

Digital Remote Indicator

Page 1/3
April 2008

The Digital Remote Indicator, IDR 144, is micropocessed product


that can be used both as master (for link to digital transducer) and
slave (for link for link to RTU, net, etc).
(1) RS 485 Serial Interface Modbus RTU is Standard, the
second serial interface RS485 is optional.
Frontal keyboard with tactile feedback.
3 LCDs displays alphanumeric 1 line 16 characters.
Simultaneous indication of 3 voltages (U12, U23, U32) and 3
currents (I1, I2, I3), in the first reading screen.
Simultaneous indication of Active Power (Pt), Reactive Power
(Qt) and frequency (f), in the second reading screen.
Others screens: preview of others electrical variables as:
voltage line-neutral (UN1, UN2, UN3) active, reactive and
apparent power for phase (P1, P2, P3, Q1, Q2, Q3, S1, S2, S3),
and total (Pt, Qt, St), power factor for phase and total (FP1,
FP2, FF3, FPT), angular delay for phase and total (A1, A2, A3,
At), active and reactive energy, consumed and supplied
energy (Wh+, Wh-, Varh+, Varh-), current demand for phase
(DI1, DI2, DI3), active, reactive and apparent total power
demand (DPT, DQT, DST), frequency (f).
Non volatile memory to store data of RTP, RTC, IDR address
in the net, transmission rate and byte format.
Auxiliary power supply universal AC/DC
Protection: IP50 (Housing) and IP20 (terminal connection).
Reading resolution: 0,01% .
Processing resolution : 16 bits.
Software parameterization.
Phases indication : blue (1), white (2) and red (3).

Technical Data (NBR 8145)


Display
Type

Number of Display s
Illumination
Characters dimension
Variables indication
Digits coverage
Reading resolution
Processing resolution
Return time to first screen
Communication fail

Keyboard
Type
Functions

Protection

13.82kV 119.4kA
13.81kV 121.3kA
13.85kV 120.2kA

Internal memory

Type
Stored records

Non volatile
RTP, RTC, Slave number,
number of significant algorisms,
time-out, polling time,
communication RS485 (1),
transducer address in the net,
transmission rate and byte format.

Communication/ Serial Interface


Communication protocol
Serial interface
Characteristics
RS 485 (1)

RS 485 (2)
Liquid crystal display (LCD)
(1) line and (16) characters
(3) independents, alphanumeric.
Type backlight
8 x 4,34mm
numeric display until 6 digits
until 999999 with decimal point
configurable
0,01%
16 bits
configurable
indicated in the 3 displays
(*****)

Frontal with tactile feedback


Configuration of indicator
(RTP,RTC), Slave number,
number of significant algarisms,
time-out, polling time, display
timer, RS485 (1) communication,
transducer address in the net,
transmission rate, byte format and
display navigation.
Through password

Time out in the master function


Polling time
Transmission rate
Byte format
Maximum distance
Maximum number of
Slaves in the net

Electrical Characteristics

Auxiliary power supply


Power consumption
Test voltage

Climatic conditions

Operating temperature
Functioning temperature
Transport and storage
temperature
Relative humidity

Modbus RTU
RS 485
Master to link to ABB
transducers (others: upon request)
Slave to link to RTU, net, SMC,
etc
Configurable.
Configurable.
Configurable between 4800,9600,
19200bps and 34800bps (only to
RS485 (2))
Configurable by keyboard.
(8 n 2), (8 n 1), (8 e 1) e (8 o 1)
1200m
31

2060Vac/Vcc
85265Vac e 90300Vcc
38265Vac/Vcc
6 VA
1,5kV/1 min 60Hz

-20+60C
-25+70C
-40+80C
2090% UR without
condensation

IDR-144

Data Sheet - N00397

Digital Remote Indicator

Construction and mounting


Housing

Fastening
Electric connections
Frontal frame
Assembly
Protection
Dimensions
Weight

Page 2/3
April 2008

Plastic Noril Flame resistant


UL94-UO
By pairs of clamp
Terminals for pin shaped
cable shoes
Plastic gray color
Embedded in panel.
Housing: IP50
Electric connections: IP20
144x144x70mm
~0,75Kg

View behind the equipment

Electrical Connection

Obs.: All the configurations can be made by keyboard except of


the Tag, that only can be configured through IBIS-BE-cnf
software.

Additional Information
The following items contain tips and cautions to be observed by the
user for a good functional performance, as well as the maintenance
of the instrument and the safety of the installations.

Cautions
Dimensional Drawing

Dimensions in mm

Be sure that the voltage to be connected to the instrument are


compatible

Assembly Instructions
Observe the ambient temperature range. At the place of installation,
values for vibration, dust, dirt and humidity, which must remain
between the limits, established by the protection class of the
housing and the climatic group, specified in this data sheet, have to
be observed.
For mounting on DIN rail, use the snap-in device on the rear of the
instrument.
The connections can be made with pin for shaped cable shoes, for
the input signals in Voltage and Current and for the Auxiliary
Power, RS485 and digital outputs terminals type pin.

Product codification

IDR-144

Data Sheet - N00397

Digital Remote Indicator

DIGITAL REMOTE INDICATOR


Model: IDR-144
Interface: (01) RS 485
Protocol: Modbus RTU
Auxiliary Power Supply
20 60Vca/Vcc
86265Vca/90300Vcc
38265Vca/Vcc
Optional
Standard
Two (02) Interface RS485
Additional Information
Standard configuration
Client configuration

Page 3/3
April 2008

12
13
14
1
2
1
C

ABB Ltda - ATLV/IE Electrical Instrumentation


Av. Dos Autonomistas, 1496 - 06020-902 - Osasco - SP
Tel: +55(11) 3688-8330