Multifunction Electrical
Installation
Tester Series
Telaris ProInstall-100-EUR
The Telaris Multifunction Tester Series offers two models that verify
the safety of electrical installations in residential, commercial and
industrial applications.
The Telaris ProInstall series has been developed to carry out
the following safety measurements of electrical installations in
accordance with EN 61557:
- Insulation resistance
- RCD tests
- Low Ohm resistance
- Earth ground resistance
- Loop impedance
- Phase sequence
Tests electrical installations for safety in accordance with:
EN 61557, BS7671, IEC 60364
Lightweight and compact for portability
Easy to use, intuitive interface allowing you to work
immediately and efficiently
Insulation resistance measurements up to 1000V DC
Telaris ProInstall-200-EUR
ProInstall-100-EUR
ProInstall-200-EUR
Insulation resistance
Loop/line test
Illuminated display
Memory
6000563 A
www.Amprobe.eu
Resolution
Intrinsic accuracy
50Hz 60hz
Measurement range
Operating error
Input impedance
Overload
protection
0 - 500V
0,1V
(2% + 2D)
50 500Vac
(3% + 3D)
3,3M / 360 k
600 Vrms
Intrinsic accuracy
Measurement range
Operating error
Test current
Open circuit
voltage
(3% + 3D)
0,30 - 2000
(10% + 3D)
> 4V
Continuity Measurement
Display range
(auto-ranging)
Resolution
0 - 20
0,01
200
0,1
2000
Display range
Resolution
100 V
0 M to 20 M
20 M to 100 M
250 V
0 M to 20 M
20 M to 200 M
500 V
0 M to 20 M
20 M to 200 M
200 M to 500 M
0,01 M
0,1 M
1 M
1 mA @ 500 k
1000 V
0 M to 200 M
200 M to 1000 M
0,1 M
1 M
1 mA @ 1 M
0,01 M
0,1 M
Intrinsic
accuracy
Test current
1 mA @ 100 k
(5% + 5 dgt.)
1 mA @ 250 k
(5% + 5 dgt.),
For R > 200 M
10%
Measurement range
0,1 M to 20 M
20 M to 200 M
Operating
error
(12% + 3D)
0,25 M to 20 M
20 M to 200 M
0,5 M to 20 M
20 M to 200 M
200 M to 500 M
(12% + 3D)
(12% + 3D)
(15% + 5D)
1 M to 200 M
200 M to 1000 M
(12% + 3D)
(15% + 5D)
+20%, -0%
Impedance Measurements
Display range
(auto-ranging)
Resolution
Intrinsic accuracy
0 - 20
0,01
( 4% + 5 dgt.) no trip*
( 3% + 3 dgt.) high current
200
0,1
5%
2000
6%
Measurement range
Operating error
No trip mode
0,50 2000
(15% + 8D) *
Hi current mode
0,30 200
(10% + 5D)
PSC Test
Computation
PSC determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance.
Range
0 10 kA
Accuracy
RCD Testing
Types of RCDs tested
RCD Type
AC (Responds to AC)*
A (Responds to pulsed signal)
G (General, no delay)
S (Time delayed)
ProInstall-100-EUR
ProInstall-200-EUR
AC
AC
6000563 A
www.Amprobe.eu
Multiplier
Current accuracy
RCD type*
x1
+10% -0%
300 ms.
x1
+10% -0%
500 ms.
Multiplier
Current accuracy
x1
+10% -0%
x5
10%
RCD type
Measurement range
Europe
UK
310 ms.
2000 ms.
510 ms.
2000 ms.
x1
310 ms.
310 ms.
x1
510 ms.
510 ms.
x5
50 ms.
50 ms.
x5
160 ms.
160 ms.
Step size
50% to 110% of
RCDs rated current
10% of I PN
Resolution
Dwell time
Intrinsic accuracy
0 - 200
0,1
(3%+5 D)
2000
( 5% + 10 dgt.)
+ ( 2% + 2 D)
( 10% + 2 D)
PN
Type G
Type S
Trip current
intrinsic accuracy
300 mS / step
500 mS / step
5%
( 10% + 2 D)
Trip time
intrinsic accuracy
Measurement
range
Operating error
Output current
@128 hz
Frequency
Compliance
voltage
10 2000
(10% + 3D)
5 mA.
128 Hz
24 Volts
Indicates 1-2-3 in digital display field for correct sequence. Indicates 3-2-1 for incorrect phase.
General Specifications
Power supply
Degree of pollution
Overvoltage category
Protection degree
IP40
Protection class
II
Electrical safety
EN61010-1/VDE0411
EN61326-1
Dimensions (L x W x H)
Weight
Approximately 1450 g
For complete specifications please download the datasheet and the users manual on www.Amprobe.eu