Technical Data TD01412057E

Effective August 2010

Pow-R-Command 5000
Building Automation Controller
General overview
The Pow-R-Command 5000 Building Automation
Controller (PRC5000) is a state-of-the-art controller
for every aspect of your building and process
operations. The PRC5000 is a Web-enabled device
that communicates TCP/IP and has a Linux-based
operating system for secure operations. The controller has canned and custom Web pages that can
be viewed with a standard Internet browser. In
this Web page interface, the building can be monitored and manually controlled.

Network philosophy
The PRC5000 has an Ethernet connection used
for programming and Web page connection. The
PRC5000 has two local unitary networks. Each
supports up to 120 devices. Unitary Ethernet
Interface modules (UEI) can be used to connect
13 additional networks to the PRC5000 with up
to 120 devices controlled on each.

Technical Data TD01412057E


Effective August 2010

Figure 1. Expanded Riser Diagram


2

eaton corporation www.eaton.com

Pow-R-Command 5000
Building Automation Controller

Pow-R-Command 5000
Building Automation Controller

Technical Data TD01412057E


Effective August 2010

Supported hardware

Device specifications

The PRC5000 can be used as the master device on the various


Pow-R-Command device RS-485 networks, including the PRC100,
PRC1000, PRC2000, and PRC4000 lighting control system
controllers. The PRC5000 controller also utilizes control cards
called Universal Unitary Controllers (UUCs) connected on its RS-485
network. These UUCs are used to control many different machines
and devices. The controller cards are mounted locally in each
apparatus, which accepts dry-contact and analog level inputs to
monitor status of the machine/device, and supplies dry-contact and
analog level outputs to control different aspects of the machine/
device. These controller cards can be programmed to use the inputs
and control the outputs in numerous ways. HVAC control, conveyor
system, or point-of-use control for pneumatic or electrical systems
can be controlled by monitoring the inputs. These inputs are used in
logical calculations to control outputs, which can also be controlled
by time-of-day scheduling programmed into the control card.

The PRC5000 is a 24 Vac device with: one RJ45 Ethernet port,


two separate RS485 networks, one serial connection, and two USB
connections for future functionality (Figure 7). The controller also
has a 15 Vdc supply for peripheral devices.
On the left side of the controller below the 24V connector is the
power LED, indicating the presence of power on the controller bus
(Figure 5). Just below the power indicator is the Status LED that
indicates the status of the controller. Normal status is blinking
once per second; Fault status is represented by a solid on or off
state of the LED.

Figure 5. 24V Connection

Figure 6. LAN1 and LAN2


Connections

Figure 2. UUC4 Controller Card Has Four Digital Outputs,


Three Analog Outputs, and Eight Analog Inputs

Figure 3. Duct Temperature Sensor


Figure 7. PRC5000 Connectors
On the right side of the controller, there is a row of LEDs in the
lower corner. The top LED is the LAN1 activity indicator, and the
second LED is the LAN2 activity indicator.

Figure 4. Area Temperature Sensor


eaton corporation www.eaton.com

Pow-R-Command 5000
Building Automation Controller

Technical Data TD01412057E


Effective August 2010

External cabinet
The PRC5000 is offered with an 18.00H x 12.00W x 4.00Dinch
(457.2H x 304.8W x 101.6Dmm) wall-mountable external cabinet
with a 120 Vac supply, fuse protected at 3A. Also included in the
cabinet are a 24V controller supply transformer and a convenience
outlet. The cabinet is offered with an optional modem for dial-in
support and programming.

Figure 8. PRC5000 in External Cabinet with Modem


Table 1. Specifications
Description

Specification

Controller dimensions H x W x D in inches (mm)

10.50 x 5.12 x 4.00


(266.7 x 130.0 x 101.6)

Controller voltage

24 Vac or Vdc

Power usage

10 VA

Communication

Two each RS-485, Ethernet

Supplied voltage

15V at 120 mA

External cabinet supply voltage

120 Vac

External cabinet current

3A

Ambient operating temperature

110F (43C)

Certifications

ULT and FCC approved

Table 2. Product Selection


Description

Part No.

Catalog No.

Building Automation Controller

42C2894G01

PRC5000

Enclosure with transformer and


convenience outlet

42C2894G02

PRCENC

PRC5000 in external enclosure

42C3587G01

PRC5000E

PRC5000 in external enclosure with modem

42C3587G02

PRC5000EM

Eaton Corporation
Electrical Sector
1111 Superior Ave.
Cleveland, OH 44114
United States
877-ETN-CARE (877-386-2273)
Eaton.com
2010 Eaton Corporation
All Rights Reserved
Printed in USA
Publication No. TD01412057E / Z10128
August 2010

PowerChain Management is a registered


trademark of Eaton Corporation.
All other trademarks are property of their
respective owners.

You might also like