Professional Documents
Culture Documents
GENERAL INDEX
SPECIFICATIONS
PART A
MECHANICAL
SPECIFICATION
TABLE OF CONTENTS
PART A MECHANICAL
WORKS
INDEX
SECTION: 1
1.1
GENERA
L
1.2
QUALIFICATION OF CONTRACTOR.
1.3
1.4
1.5
CONTRACT DRAWINGS.
1.6
1.7
SHOP DRAWINGS.
1.8
AS BUILT DRAWINGS.
1.9
1.10
1.11
1.12
1.13
WORKMANSHIP.
1.14
1.15
CLEANING.
1.16
ACCESSIBILITY.
1.17
1.18
1.19
TEMPORARY USAGE.
1.20
INSPECTION OF WORK.
1.21
OF MANUFACTURERS
Blaze Engineering
Consultants P O Box:
114535, Dubai.
Page 3 of
104
.0.
29degC
15KPH
0%
NC
35
NC
40
NC
40
NC50
NC
5.1
Control Switch
Each unit shall have a wall mounted electronic control switch
with
a system onof switch, room temperature control
thermostat and 3 speed control for the fan.
The units shall be provided with following
1.
2.
5.2
Antifrost
High pressure / Low pressure
safeties.
control
.4.1
INDOOR UNITS
Wall Mounted Decorative Type
Wall mounted decorative type indoor unit shall be two pipe.
Basic unit shall be single skinned construction from high
quality 1.3mm thick galvanized steel. The maximum height
for the units shall be not more than 255mm. Face velocity at
the coil not to exceed 400 FPM. Unit to be equipped with
factory installed brackets for hanging. Control box to be easy
for replacement with an option of fixing on both side of the
unit at site.
Indoor air quality: Units are to have accessible filters designed
for obtaining optimum air quality & shall be equipped with
plasma & carbon filters.
Electronic filter
Wherever applicable units should have an option of factory
installed & tested high efficiency plasma filter to remove all
the microscopic contaminants, dust, odor molecules etc. to
maintain high level of indoor air quality in areas as
specified in the schedule.
Coils
Coils will be ARI rated at least 7mm O.D. size copper tube
with aluminum fins. Aluminum fins should be coated with
special MAGIC coating to avoid formation of condensate
water droplets and thereby ensure dry coil conditions. This
will prevent corrosion and reduce resistance to airflow.
Coils shall be made of staggered heavy wall seamless copper
tubing mechanically bonded to 0.12 mm aluminum fins with 21
FPI spacing. The evaporator coil shall be minimum three rows
deep.
Controls:
The units shall be equipped with Auto Restart function, which
allows the unit to start in the same mode prior to the power
failure.
Smart controls: The units shall have the following state of
the art features.
Twin thermistor sensor to sense temperature in the room and
in the return air with a option of selecting one or both
depending on the application for uniform
and precise
temperature control..
Group control to control up to 16 units from single LCD wired
remote controller.
Central control to control up to 128 units from a central
location. Optional Tele control to operate individual units via
telephone line for units if mentioned in the schedule.
Digital thermostat: Units shall be controlled with user friendly,
wall
mounted microprocessor based LCD, wired remote
controller. The wired remote controller shall be slim having the
following
features.
24 hour ON / OFF timer in 1 hour
interval. Test run mode.
Selfdiagnosis function.
Operation indication.
Room temperature
display. Weekly
programming.
Child lock
function. 3
speed fan
control.
Linear control of E.S.P/Airflow.
The wireless remote control should be provided for all
units.
.5 EXTRACT FANS
Inline Duct Mounted
Unit casing shall be manufactured in aluminium alloy and
shall house fan assemblies, comprising double inlet forward
curved centrifugal impellers running in an individual scroll.
Impellers may be either direct driven or belt driven
.6
3.1.0
PLUMBING
1.2
building Requirement.
Hot Water system
1.5
Hot water supply to pantry & toilets shall be provided via local
electric water storage heater to be located in the ceiling void
of each toilet. No hot water has been provided for toilets in all
other sheds.
3.2.0
2.1. General
Pipe materials shall be as specified elsewhere herein. The
Contractor shall install unions or pairs of flanges in the
pipework system at the following locations
(a)
(b)
(c)
(d)
2.1.2
2.1.3
2.1.4
2.1.5
2.1.6
2.1.7
easily accessible.
2.1.8
2.1.9
2.1.10
All holes through such walls shall be closed after the erection
and testing of the pipework by means of removable split
closing plates on both sides of the wall. All closing plates
shall be manufactured from galvanized sheet steel of not less
than 16g thickness in the case of brick or concrete walls. All
closing plates shall be painted or finished in accordance with
the requirements of this specification.
2.2.
2.2.1
2.2.2
2.2.3
2.4.0
Pipes
3.3.0
3.1
SYSTEM DESIGN
This shall be double stack (soil and waste) with vent pipe
gravity drainage system designed in accordance with the
recommendations of
the Chartered Institution of Building
Services Engineers and to the requirements of the Municipality
Drainage Department.
3.1.1
System Description
3.1.2
3.1.3
3.2
PIPEWORK GENERALLY
3.1.
Installation
(a)
(b)
(c)
(d)
(e)
3.2
(a)
(b)
(c)
(d)
3.3
or
(e)
(f)
Material
(a)
(b)
(c)
3.4
3.5
Floor drains.
(a)
(b)
Roof drain
Roof drain and open to sky drains shall be heavy duty C.P.
brass connected to the rain water pipe without any trap. Size
of drain shall be as per drawings.
3.3.
3.3.1
General Requirements
(a)
in
(b)
(c)
(d)
(e)
(f)
(g)
(h)
MANHOLES
3.4.1
3.4.2
3.4.3
3.12.0
3.13.0
3.14.0
4.1.1
4.1.3
SYSTEM DESCRIPTION
4.1.3.1
4.1.3.2
4.1.3.3
(2)
(3)
Landing valves.
Hose Racks.
CO2 fire extinguishers.
Dry Powder fire extinguishers.
Automatic dry powder fire extinguishers.
Fire Pumpset.
Fire pump set shall be as per local Civil Defence
4.2.1
(4)
Breeching Inlet:
Two way breeching inlets shall be provided to the building
for the access of the Civil Defence water supply to the
building. The connections shall be on the faade section of
the building on the ground floor.
(5)
Control Requirements
The wet riser shall be pressurized to ensure the index
point fire hose rack will have a nominal pressure of 6.9
bar.
The level switches shall be provided and to be interfaced
with fire pumps and fire alarm panel.
All valves and zone flow switches shall be monitored on
the fire alarm panel with monitoring module.
(6)
Indicator Panel
The Contractor shall allow for the provision of indicator
panels to show the status of the supervised valves,
sprinkler zone valves, motorised smoke and fire dampers
and clean agent fire suppression.
(7)
1 Start relay
relays
1 Line contactor
terminals
used
1 Isolator handle
Fault on controller
OPERATION
The starting circuit shall be arranged to fail safe by utilizing a
separately fused starting relay which under normal standby
conditions
is
energised so that it remains in the "hold"
position.
If the pressure in the fire main falls to a preset value the
pressure switch in the main shall operate and release this
relay by causing it to de energise thus starting the pump.
Should the wiring to the pressure switch be disconnected or an
earth fault condition occurs on the wiring then the relay shall
release to start the pump.
System shall be suitable for power supply 400V/3
Ph/50 Hz Electric Fire Pump shall operate as follows:
Under normal conditions the pump will start
when the
controller isolator is switched to 'ON'.
Operating the stop/reset push button will stop the pump and
put the controller in standby condition. If the operating pressure
switch contacts are open the pump cannot be stopped with
the stop push button.
CONTROLLER OPERATION
When in standby condition all relays shall be energised and
illuminating "HEALTHY" lamps. In the event of failure of one
or more of the incoming supply phases the starter shall be
deenergise to prevent the pump starting and simultaneously
provide A.C. phase failure indication in the remote fire alarm
panel.
When system pressure falls relays shall cause the starting
contactors to operate and simultaneously provide pump on
demand indication in the remote alarm circuit.
Completing the operation of the starting contactors shall de
energises the closed valve bypass solenoid fitted to the pump.
Any open circuit in the pressure switch wiring shall initiate a
start sequence, also an earth fault in the pressure switch
Blaze Engineering Consultants
P O Box: 114535, Dubai.
wiring will
sequence
4.2.2
cause
1 Cam timer
1 Batteries disconnectedbuzzer
1 Failed to start
terminals
buzzer
door:
1 AC isolator
1 DC isolator
1 Tachometer
indicator lamp shall come into operation. The engine will now
continue to run until the starting pressure switch has been
reset and the fuel cutof level operated. This operation shall
cause the 'test manual start' light to illuminate and also the
'test manual start' push button to become operative.
Operating the test manual start push button will then start
the engine from the other battery, than the one which is
selected for automatic control. Once started, the engine will
again continue to run until shutdown manually, this then
restores the controller to full standby condition. Should the
controller be left in a condition with the test manual start light
illuminated, this is no way inhibits the automatic starting
should a fall in pressure be detected.
A break glass emergency start push button shall be fitted to
the front of the controller, which, when operated, completely
bypasses all automatic control and energises both starter
solenoids simultaneously.
Instrumentation
includes
battery
charger
ammeters,
tachometer, oil pressure gauge, water temperature gauge
and hours run indicator.
FIRE PUMP
SET: Jockey
pump.
Components
This unit shall be designed to operate on NFPA installations
and to AHJ requirements and shall be UL listed FM approved.
Enclosures shall be reinforced polycarbonate and fitted with
access cover secured by captive screws. Protection shall comply
with
IP65.
The following equipment shall be mounted on the enclosure
door:
Fault on controller.
IDENTIFICATION SIGNS
Drain valves, test valves, control valves, shall be fitted with
approved enameled signs indicating their use.
4.4.0
TESTING
General : All testing shall be performed under the work of this
Section. All services required for testing shall be a responsibility
of the work of this Section. The contractor shall notify the
Engineer of all tests, 48 hours prior to testing.
The
Fire
Protection
Piping
Systems
shall
be
tested
hydrostatically for not less than 2 hours at 1.5 times the
maximum system pressure.
If the systems are tested in sections, the connection to the
previously tested section shall be included.
All tests that may be required by the local Fire Authorities shall
be performed under the work of this Section in the presence of
their representative if so required.
All leaks shall be corrected and the system retested until no
leaks are found, at no extra cost.
When the various systems are completed, operation tests shall
be run,
on all equipment to demonstrate proper operating
conditions. These tests shall be run under the observation of
the Engineer.
Cost to repair any damages to the building construction
occasioned by pipe leaks or defective materials shall be
borne under the works of this Section, at no cost to the
Owner. All corrective work shall commence immediately after
damage occurs.
SECTION
5
ASHRAE
ASTM
SMACNA
CIBSE
National Association.
Chartered Institution of Building
Services Engineers.
NFPA
UL
BS
BSEN
IEC
ISO
International Electrotechnical
Commission
DEWA
DM
CD IP LPC
Plumbing, UK.
International Organization of
Dubai Electricity & WaterDepartment
*******
**
PART B
ELECTRICAL
SPECIFICATION
Specifications for
Electrical Works
TABLE OF CONTENTS
PART B ELECTRICAL WORKS
SECTION:
SECTION
GENERAL REQUIREMENTS
SECTION
FITTINGS SECTION
SECTION
3:
ELECTRICAL
ACCESSORIES
SYSTEM OFWIRING
SECTION 7
LIGHTING
SECTION 8
EMERGENCY LIGHTING
SECTION 5
SECTION
SYSTEM SECTION
PROTECTION SECTION 10
SECTION 11
LIGHTNING
EARTHING
STANDBY DIESEL
GENERATOR SECTION
12
FIRE ALARM
SYSTEM
SECTION
13
SYSTEM SECTION 14 :
CCTV MONITORING
SYSTEM SECTION 15 :
BACK GROUND
BURGLAR
CODES
AND STANDARDS
Blaze Engineering
Consultants P O Box:
114535, Dubai.
Page 25 of
120
SECTION 1
GENERAL
REQUIREMENTS
INDEX
1.0
2.0
GENERAL
3.0
4.0
5.0
CONTRACT DRAWINGS
6.0
7.0
8.0
9.0
TEMPORARY SERVICE.
1 0.0
COOPERATION
11.0
12.0
SUPERVISION.
13.0
CLEANING.
14.0
15.0
16.0
AUTHORITIES APPROVAL.
17.0
REGULATIONS
18.0
DEFINITIONS
19.0
PHASE IDENTIFICATION
20.0
VOLTAGE DROP
21.0
TELECOMMUNICATIONS INTERFERENCE
22.0
SEGREGATION OF SERVICES
23.0
BUILDER'S WORK
24.0
SUBMITTAL
S
25.0
26.0
27.0
28.0
29.0
30.0
LABELS
31.0
32.0
33.0
SYSTEM ACCEPTANCE.
34.0
35.0
GUARANTEES.
36.0
MAINTENANCE
37.0
SCHEDULE OF MANUFACTURERS
38.0
LOCA
L
DESIGN PARAMETERS
The electrical system equipment selection and installation shall
comply with the particular requirements listed hereunder.
Site Conditions
All electrical equipment and components shall be selected and
installed such as to operate satisfactorily and safely under the
following climatic conditions.
Maximum shade temperature in summer
C Direct sun temperature in summer
C Minimum ambient temperature in winter
C Relative humidity max
Rusty atmosphere
50 deg.
84 deg.
2.8 deg.
100
System of Supply
Three phase, neutral and separate protective conductor (TT).
The system of supply shall be at 400V 3Ph, 50HZ with a maximum
short circuit capacity of 50 KA for 1 second at the main bus bar
of the LV Switch Board. Single phase voltage is 230V.
The electrical system shall have following system variations at
the substation: Voltage
+/ 6%
Frequency
+/ 4%
AUTHORITIES APPROVAL.
The contractor shall be responsible for liaising with DEWA, DU,
JAFZA and the Civil Defence Authority and any other authorities
after obtaining the Consultant's approval, in order to:
(a)
(b)
(c)
(d)
Approve the
shop
Drawings,
before
ordering any
equipment,
and
commencing with the installation.
Approve any excavation prior to installation;
Acquire main supply connection;
Approve the Fire protection & Telephone systems etc.
REGULATIONS
The installation shall be carried out in accordance with the current
edition and supplements of the following Regulations and Standards:
(a)
Page 28 of
120
(b)
(c)
(d)
(f)
(g)
19.0
PHASE IDENTIFICATION
VOLTAGE DROP
The voltage drop between the incoming LV switchboard and the
extremity of any circuit shall not exceed 4% of the nominal supply
voltage.
TELECOMMUNICATIONS INTERFERENCE
The whole of the electrical installation work shall be so designed
that there is an
absolute minimum of interference with
telecommunications, and the reception of broadcasting to BS 800
or any other relevant BS.
SEGREGATION OF SERVICES
The armour of all cables, cable trays, trunking, ducts etc., shall
be prevented from coming into contact with nonelectrical
services by minimum spacing of
150mm. Where this is
impracticable they shall be bonded to the exposed metal of the
other service through a protective conductor.
10
Page 29 of
120
11
IEC
BS
Fuses 13 amp
Fuses 250 volt
Distribution Boards (ACB.MCCB)
2691
2691
604391
1362
1361
4649
1454
3871
157141A 4752
4293
3676
Degree of Protection
Protection against corrosion
529
59
1706
1363
67
4177
3535
Conduit, steel
Adaptable boxes
Conduit PVC
45681
45682
4607
Trunking steel
4678
227
227 &
245
EN 61537
6004
6500
6207
4081
Cables glands
Marking of conductors by color
446
4121
61
162
98
4533
Page 30 of
120
4363
CP1017
6651,
62305
Note : All Fire related Materials e.g. Fire Alarm, Fire Fighting, Fire Stop
Materials, Central Emergency Lighting, Fire Dampers etc., must
have Local Civil Defence Deptt. Approval.
Page 31 of
120
2.1
2.2
2.3
PVC Conduits shall be black of the extra heavy wall with 1.8mm
minimum thickness for 20mm dia conduit.
2.4
2.5
All set, fixing and wood screws used throughout the installation shall
be brass.
2.6
2.7
All circular PVC boxes where used to support lighting fittings shall
be provided with steel insert clips.
2.8
The sizes of the conduits for all wiring shall be in accordance to IEE
regulations and DEWA Standards and shall be such that a cable
can be withdrawn and another drawn in without disturbing the
remainder. However, the size of the conduit shall not be less than
20mm where used for lighting and power circuits and 25mm for
telephone / data wiring.
3.1
FLEXIBLE GI CONDUITS
3.2
3.3
4.1
CONDUIT INSTALLATION
4.2
Page 32 of
120
4.3
4.4
4.5
4.6
4.7
4.8
4.9
4.10
Conduits shall not be run closer than 0.15m to any steam or hot
water pipes and shall be run underneath such pipes rather than
over them. The conduits shall not be run closer than 0.05m to
any telephone, bell or other signalling circuit.
4.11
4.12
4.13
Not more than two right angle bends shall be installed between
boxes. Conduits shall not be laid to falls, but the Contractor shall
exercise care to ensure that no pockets are formed within the
conduit system in which water can collect. Drainage holes shall not
be provided.
4.15
In floors which are in direct contact with the earth or under which
unheated foundation voids are situated, conduits shall not be laid
to form traps in which moisture can collect. Where it is impossible
to arrange for drainage to a lower level such floors shall be avoided
altogether and the conduit shall be run in the floor above with drops
to socket outlets and other low level points.
4.16
4.17
Where steel conduits enter sheet steel wiring trunking, iron clad
gear or junction or similar boxes, the junction shall be made by
means of a flanged coupling with lead washer bearing on the
outside of the box and into which shall be screwed from the
inside of the box a hexagon smooth bore brass male bush of
heavy pattern.
4.18
4.19
4.20
4.21
All screwed joints for conduits and fittings erected in the open air,
damp situations and plant room shall be made watertight by
the application of a suitable metallic paint and conduit boxes
being fitted with rubber gasket. Separate earth continuity
conductors will be installed within the normal circuit wiring.
4.22
4.23
4.24
Draw wires shall be left in all conduit runs for other services not
included in the contract.
Page 35 of
120
6.1
B.
C.
D.
6.2
6.3
PROTECTION
Provide final protection and maintain conditions in a manner
acceptable to manufacturer to ensure that the cable tray/ladder
is without damage or deterioration to galvanized finishes with
zincrich paint recommended by the manufacturer.
7.1
7.2
General
The work in this section consists of the supply and installation
of under floor trunking/ducting system as indicated on the
drawings and as specified herein.
Contractor to provide for all components necessary
complete system whether or not specifically identified.
7.3
for
Casting
BS EN 10142: 1991
low carbon sheet
BS 6099 Part 1
Blaze Engineering Consultants
P O Box: 114535, Dubai.
and
16th Edition
protective
conductors
shall
be
provided
between
Page 37 of
120
the
LOCAL SWITCHES
9.2
9.3
Switches shall be of the quick start make, slow break type specially
designed for AC circuits to SS Standards. The operation of the
switch shall not depend wholly on the action of the spring. The
switches shall generally be of the rocker operated type.
9.4
All switch boxes shall be supplied with adjustable steel grids and
earthing terminals.
9.5
9.6
9.7
9.8
9.9
9.10
10.1
POWER OUTLETS
10.2
10.3
Switch socket outlet in the diferent areas shall be provided with pilot
lamp.
Page 38 of
120
10.4
10.5
All floor mounted socket outlets shall be fixed as part of the under
floor trunking service boxes.
10.6
10.7
11.1
11.2
11.3
12.1
GI BOXES
MOUNTING HEIGHTS
The mounting heights for the electrical equipment and accessories
shall be coordinated with the furniture layout and shall be as per
site requirements to Engineer's / ID's instruction and approval. In
general the mounting heights are as follows:
Above FFL
1.
1200 mm
above FFL From
the bottom of
switch plate
2.
450 mm
Page 39 of
120
3.
4.
MCB
5.
6.
Distribution
plant rooms.
Boards
1300 mm
2000 mm (Top)
Page 40 of
120
14.1
CABLE
14.2
All cables supplied and installed shall be selected from the following
types with stranded copper conductors and shall comply with the
appropriate British Standard referred to below as applicable.
(i)
BS. 6491
(ii)
BS.6346
(iii)
BS. 5467
(iv)
LS ZH cables
BS. 6724
(v)
(vi)
Flexible cables
BS. 4066
Part1 IEC
332
BS. 6004
a)
b)
BS. 4533
Page 41 of
120
(vii)
MICC
Cables
BS 5750
(vii) Control cables XLPE and PVC insulated 600 / 1000V BS 5467 BS
6346
14.3
14.4
14.5
14.6
The cross sectional area of every cable shall be suitable for carrying
the maximum sustained load current under normal conditions and
shall be selected in accordance with related Regulations. The cross
sectional area of the neutral conductor for 3phase circuits shall be
equal to the cross sectional area of the phase conductors. The cables
shall be selected such that the drop in voltage from the origin of the
installation to any point in the installation does not exceed 4% of the
nominal voltage when the conductors are carrying the full
load
current. but disregarding starting conditions. Voltage drop calculation
shall be submitted
for
approval
and
the
cross
sectional
area
of
the
cable
shall be increased accordingly if required to meet the above
mentioned requirement without any extra cost.
14.7
14.8
14.9
The wire armour of single core cables in the same circuit shall be
bounded together at both ends.
15.1
15.2
Page 42 of
120
15.3
All Circuit breakers, Metering and Busbar ratings shall be as per the
load schedules and drawings. The main MCCB and the feeder
breakers shall be of appropriate capacity KA 35.
15.4
Panel wiring, Terminal blocks and labels shall be as specified for the
Main Distribution Boards.
15.5
16.1
16.2
16.3
17.1
DISCONNECT SWITCHES
17.2
17.3
18.1
18.2
18.3
The
ELCB's
shall
have
a
residual
current
operated
electromechanical release and shall incorporate a filtering device
to eliminate unwanted tripping due to transient voltage. A test
button is to prove operation of the ELCB.
Page 43 of
120
The ELCB's shall have 100mA sensitivity for lighting & AC circuits
and 30mA for power circuits.
Page 44 of
120
18.4
19.1
19.2
Page 45 of 120
20.1
EXTERNAL LIGHTING
20.2
20.3
21.1
21.2
EMERGENCY LIGHTS
Where installed on the Drawings emergency light fittings of the
selfcontained, nonmaintained type shall be installed. These shall
be Ceiling or wall mounted as appropriate and as detailed in the
drawings.
Page 46 of 120
EXIT LIGHTS
Exit sign shall be installed at strategic point throughout the building
as indicated on the relevant drawings and as per approved shop
drawings.
These exit lights shall be similar to emergency lights, but
maintained type thus ensuring that the signs are permanently
illuminated.
Exit sign shall be pictorial type as per latest EN Standards and
as per Client requirements.
All exit lights shall be of the types specified and shall be installed
in a similar manner to of the emergency light fittings.
1X 18 W high lumen output recess ceiling mounted self contained
and non maintained emergency light. Sheet steel body and glass
difuser with 3 hours 3 battery back up, charge indicators, 8 hours
maximum recharging time, test button and battery Nickel
Cadmium, rechargeable maintenance free and gas tight with
3.6V/4.0 Ah.
Same as type above but surface mounted with polycarbonate body
and IP 65.
1X 1 8W high lumen output, self contained and maintained exit
light with polycarbonate body and polycarbonate difuser to IP 65
with direction arrows. Laminar shall be wall / pendant mounted
with 3 hours 3 batteries back up, charge indicator, 8 hours
Page 47 of 120
22.1
FIRE ALARM
The contractor shall supply and install a complete fire alarm
system as described herein and as shown on the plans to be
wired, connected and left in good operating condition. The
system shall include Networked Analogue Addressable main
control panel, amplifiers addressable smoke sensors, heat
sensors, alarm indicating appliances, wiring, termination, electrical
boxes, and all other necessary material for a complete operating
system. Main Fire alarm control panel shall be located individual
stores.
The complete installation shall confirm to the applicable sections
of NFPA72. NFPA71 and Electrical codes & Local authority
regulations.
The fire alarm system shall allow for loading and editing
instructions and operating sequences as necessary. The system
shall be capable of storing, and downloading while the system is in
operation, a second set of operating software resident in the
control panels as backup in case primary operating software is
corrupted. In addition, the system shall be capable of onsite
programming to accommodate system expansion and facilitate
changes in operation. All software operation shall be stored in a
nonvolatile programmable memory within the fire alarm control
unit. Loss of primary and secondary power shall not erase the
instructions stored in memory.
The system shall have the capability of recalling alarms and
trouble conditions in chronological order for the purpose of creating
an event history of 600 events.
The system shall incorporate single channel
communication and tone generating capabilities.
twoway
voice
Page 48 of 120
22.2
SEQUENCE OF OPERATION
Upon actuation of any manual station, or automatic detector or
sprinkler flow switch, or air conditioning and ventilation duct
return and exhaust air smoke detector. The system is to operate
as follows:
On the Main Panel, the annunciator (repeater) panels the green
normal LED is to extinguish and the red alarm LED is to light. An
audible single is to sound. Visually indicate on the LCD control panel
label of the addressable device or circuit of alarm initiation. The first
line is to display the user specification message indicating the floor
and zone that initiated the alarm. The second line of the LCD is to
indicating real time, number of messages waiting, type of alarm,
zone of alarm and time the alarm occurred. Red LED corresponding
to the zone in alarm in the main panel shall also be lit. The
Graphic Command Center displays the plan of the zone in alarm
with prompts for further action.
The alarm indictors on the main panel and repeater panel to
continue to flash until the alarm is acknowledged. If a subsequent
alarm is received after acknowledgment, the alarm is to sound
again. The operator is to acknowledge the alarm by pressing a
dedicated button and the buzzer is to silence provided that isn't an
additional alarms the operator is to acknowledge all pending alarms
before the buzzer is to silence. To reset the system the device is
to be cleared first then the reset button is to be pressed.
Sound evacuation alarm on floor of incidence, the floor above and
the floor below. The alarm shall consist a "slow whoop" alarm tone,
for ten second followed by the thirty second of an automatic pre
recorded voice evacuation message in Arabic and English. The
message is to ask the tenants to evacuate the building. The
message and tone shall repeat continuously (unless manually
silenced) until the alarm initiating device is restored to normal and
system reset. The silencing of an alarm condition is not to prevent
the resounding of alarm devices if a subsequent condition occur. A
time delay feature is to be provided to sound a general evacuation
Page 49 of 120
ASHRAE
ASTM
SMACNA
CIBSE
NFPA
UL
BS
BSEN
IEC
ISO
Page 50 of 120
DEWA
DU
DU Version 4 Guideline
CDA
IOP
LPC
UBC
JAFZA
EHS
********
Page 51 of 120