MEDIUM VOLTAGE SWITCHGEAR

HE
Distribution surge arresters

In order to provide high quality energy,


utilities must continuously improve their
network’s reliability, which is why over-voltage
protection is of key importance.

With appropriate surge protection, you can


increase service and personnel safety while
reducing system outage costs.

THE RIGHT SURGE ARRESTER


AT THE RIGHT PLACE!

Our HE surge arresters are designed for use in areas with strong lightning
exposure and high pollution levels to ensure over-voltage protection on
overhead medium-voltage networks from 5 to 42 kV.

Based on the latest technology, each surge arrester is manufactured with metal
oxide blocks, a material with non-linear resistance characteristics, enabling to
vary instantaneously from an isolating state to a conductive state in the event of
an over-voltage.

The blocks are mechanically bounded in a reinforced synthetic resin


fiber-glass, encapsulated in a silicone rubber housing to provide the required
insulation withstand.

The HE surge arrester range meets IEC 60099-4 and ANSI/IEEE C62.11
standard requirements.

Customer benefits
• Continuity of service
• Equipment and
personnel safety
• Improved power quality
• Maintenance-free design

T&D
MVB#3-HE[GB] 13/02/04 12:02 Page 2

BASIC VERSION: TYPE “NO”

This surge arrester is equipped with bolts,


>> Nominal discharge current 10 kA (8/20 impulse)
spring washers and clamps for connection
to transmission lines and the ground. >> High current impulse withstand 100 kA (4/10 impulse)
>> Rated voltage From 5 kV to 42 kV
The following options provide end-of-life
signalling: >> Creepage distance >31mm/kV (level IV as per IEC 60815)
• Disconnector option type “sd”:
>> Energy absorption capability 4.8 kJ per kV of Uc (4/10 impulse)
Automatic disconnecting device (ground
lead) together with an insulating bracket. >> Long duration current 300 A (2 ms impulse)
Sensitivity: 20A / 1s. This option must be
>> Short circuit current withstand 20 kA / 0.2 s – 600 A / 1s
selected when the operator needs to prioritize
service continuity.
• Indicator option type “if”:
Fault current detection module (electronic ACCESSORIES
circuit) which displays a red flag allowing for
easy fault detection. Sensitivity: 10A / 0.5s. • Bracket (NEMA type) for horizontal
This option is recommended when the ope- or vertical mounting on cross arm
rator wants the continuity of protection to • Three phase bracket
be prioritized. • Ground lead

>> Distribution heavy Units HE 05 HE 06 HE 09 HE 10 HE 12 HE 15 HE 18 HE 21 HE 24 HE 27 HE 30 HE 33 HE 36 HE 39 HE 42


duty surge arresters
>> Rated voltage Ur kV rms. 5 6 9 10 12 15 18 21 24 27 30 33 36 39 42
>> Continuous operating voltage Uc kV rms. 4.25 5.1 7.65 8.4 10.2 12.7 15.3 17.5 20 22.5 25 27.5 30 31.2 33.6

All trade names or trademarks mentioned herein whether registered or not, are the property of their owners. - 389191982 RCS PARIS - Creation: L’Etroit Unlimited - Printed in France.
>> Maximum residual voltage
- at 5kA 8/20 impulse kV peak 14.3 15.4 26.4 27.5 30.8 40.7 46.2 56.1 61.2 72.2 76.2 87.2 91.7 98.8 101.6
- at 10kA 8/20 impulse 15.2 16.4 28.1 29.3 32.8 43.3 49.1 59.7 65.1 76.8 81.1 92.8 97.5 105.1 108.1
- at 20kA 8/20 impulse 16.8 18.1 31.1 32.4 36.2 47.8 54.3 66.0 71.9 84.9 89.6 102.5 107.7 116.1 119.5
>> Switching residual voltage kV peak 12.1 13.0 22.3 23.3 26.1 34.4 39.0 47.5 51.8 61.1 64.5 73.8 77.5 83.6 85.9
at 500A - 30/80 impulse)

• MVB-L3-HE ENG-76 - © - AREVA - 2004. AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks of AREVA.
>> Steep current impulse residual kV peak 16.4 17.7 30.3 31.6 35.4 46.8 53.0 64.5 70.3 82.9 87.6 100.2 105.3 113.5 116.7
voltage (10 kA - 1/2.5 impulse)
>> Insulation withstand kV peak 95 95 95 95 95 110 110 125 125 170 170 170 170 170 170
>> Creepage distance mm 480 480 480 480 480 650 650 800 800 1200 1200 1200 1200 1200 1200
>> Clearance distance to ground mm 69 73 109 112 123 155 173 205 222 257 270 306 320 344 353
>> Dimensions B mm 245 285 325 405
D mm 105 175
E mm 14 24
>> Weight - option sd Kg 1.2 1.2 1.4 1.4 1.5 1.8 1.9 2.5 2.6 3.0 3.1 3.3 3.4 3.6 3.6
For other ratings or technical details, please contact us.

• SOUTH EAST ASIA


Ø12
Tel.: +65 67 49 07 77 - Fax: +65 68 41 95 55
• PACIFIC
Tel.: +65 67 49 07 77 - Fax: +65 68 46 17 95 Option sd
• CHINA
Tel.: +86 10 64 10 62 88 - Fax: +86 10 64 10 62 64
• INDIA
Tel.: +91 44 2431 7100 - Fax: +91 44 2434 1297
• NORTH AMERICA
Tel.: +1 (484) 766-8100 - Fax: +1 (484) 766-8650
• CENTRAL AMERICA
Tel.: +52 55 11 01 10 00 - Fax: +52 55 26 24 04 93
B

• SOUTH AMERICA Ø110

Tel.: +55 11 3491 7469 - Fax: +55 11 3491 7476


• FRANCE
Ø14
Tel.: +33 (0)1 40 89 66 00 - Fax: +33 (0)1 40 89 67 19
• BRITISH ISLES
Tel.: +44 (0) 1785 27 41 08 - Fax: +44 (0) 1785 27 45 74
• NORTHERN EUROPE
Tel.: +49 69 66 32 11 51 - Fax: +49 69 66 32 21 54
E

• CENTRAL EUROPE & WESTERN ASIA


Tel.: +48 22 850 96 96 - Fax: +48 22 654 55 88
• NEAR & MIDDLE EAST M12
D
Tel.: +971-6-556 0559 - Fax: +971-6-556 5133
• MEDITERRANEAN, NORTH & WEST AFRICA
Tel.: +33 (0)1 41 49 88 38 - Fax: +33 (0)1 41 49 24 23
Our policy is one of continuous development. Accordingly
• SOUTHERN & EASTERN AFRICA the design of our products may change at any time. Whilst
Tel.: +27 11 82 05 111 - Fax: +27 11 82 05 220 every effort is made to produce up to date literature, this
brochure should only be regarded as a guide and is
intended for information purposes only. Its contents do not
constitute an offer for sale or advise on the application of
T&D Worldwide Contact Centre any product referred to in it. We cannot be held responsible
for any reliance on any decisions taken on its contents
contact.centre@areva-td.com without specific advice.
www.areva-td.com

You might also like