Professional Documents
Culture Documents
I.
INTRODUCTION
PROPOSED
METHOD
The authors of this paper thank the National Council for Scientific and Technological Development (CNPq) for allowing this work.
RESULTS
Current (kA)
0
-1
180
200
I633a
I633b
I633c
20
40
60
80
100
120
140
160
Time (ms)
Currents in the Branch 671-675 without AP
180
200
I675a
I675b
I675c
1
0
-1
20
40
60
80
100
120
Time (ms)
140
160
180
200
1.5
1
0.5
0
-0.5
-1
20
40
60
80
100
120
Time (ms)
140
160
200
I633a
I633b
I633c
1
Current (kA)
180
1.5
0.5
0
-0.5
-1
20
40
2
Current (kA)
60
80
100
120
140
160
Time (ms)
Currents in the Branch 632-634 without AP
40
0
-1
Current (kA)
20
In this scenario, consider the occurrence of a double-lineto-ground (ACG) fault on the node 675. As shown, the system
without adaptive protection (Fig. 3 and Fig.5):
2
Current (kA)
Current (kA)
TABLE I.
60
80
100
120
140
Time (ms)
Currents in the Branch 671-675
160
200
I675a
I675b
I675c
1
0
-1
180
20
40
60
80
100
120
Time (ms)
140
160
180
200
Breaker State
20
40
60
80
100
120
140
160
180
200
Current (kA)
Breaker 650
0.5
0
Breaker 633
0.5
0
20
40
60
80
100
120
140
160
180
0
-2
20
40
60
80
100
120
Time (ms)
140
160
180
200
Current (kA)
20
40
60
80
100
120
State Breaker 650
140
20
40
60
80
100
120
State Breaker 633
140
160
180
200
20
40
60
80
100
120
State Breaker 675
140
160
180
200
40
60
80
100
120
Time (ms)
140
160
180
60
80
100
120
Time (ms)
140
160
180
200
2
0
-2
-4
20
40
60
200
40
80
100
120
Time (ms)
140
160
180
200
I675a
I675b
I675c
2
0
-2
-4
20
40
60
80
100
Time (ms)
120
140
160
180
200
1
Breaker State
20
20
Breaker 650
0.8
0.6
0.4
0.2
0
20
40
60
80
100
120
140
160
180
200
Breaker 675
Breaker State
Breaker 675
0.5
200
200
Breaker 633
-4
Current (kA)
Breaker State
180
180
-2
Breaker 650
1
0
160
160
I675a
I675b
I675c
60
80
100
120
140
Time (ms)
Currents in the Branch 671-675 without AP
Current (kA)
SG
40
2
1.5
20
Breaker 675
0.5
0
200
-4
0
0.5
20
40
60
80
100
120
Time (ms)
140
160
180
200
SG
Breaker State
Breaker State
2
0
20
40
60
80
100
120
140
160
180
Similar results were obtained for the system with AP. Due
to the fact of the system is heavily loaded and considering that
the inclusion of synchronous machines substantially
aggravates this situation, the occurrence of single-phase faults
does not modify significantly the current values.
200
Breaker 650
1
0
20
40
60
80
100
120
140
160
180
200
Breaker 675
0.5
0
20
40
60
80
100
120
Time (ms)
140
160
180
200
Figure 10. Case 2 with adaptive protection: setting group of relays and
breakers state.
1.5
0
-0.5
0
20
40
1.5
60
80
100
120
140
Time (ms)
Currents in the Branch 632-634 without AP
160
180
Current (kA)
200
0.5
20
40
60
80
100
Time (ms)
120
140
160
180
20
40
1.5
60
80
100
120
140
Time (ms)
Currents in the Branch 671-675 without AP
160
180
200
I675a
I675b
I675c
1
0.5
0
-0.5
0
20
40
60
80
100
Time (ms)
120
140
160
180
200
200
1.5
-0.5
-1
-1
-1
0.5
-0.5
I633a
I633b
I633c
Current (kA)
Current (kA)
Current (kA)
1
0.5
-1
1.5
1
0.5
0
-0.5
-1
20
40
60
80
100
Time (ms)
120
140
160
180
200
1.5
I675a
I675b
I675c
Current (kA)
1
0.5
0
-0.5
-1
20
40
60
80
100
Time (ms)
120
140
160
180
200
Breaker 650
V.
Breaker State
20
40
60
80
100
120
140
160
180
200
APPENDIX
Breaker 633
0.5
0
TABLE II.
0
20
40
60
80
100
120
140
160
180
200
Pb1 = 2.1 MW
Xd = 2.0
Xq = 0.2
Xq0 = 0.035
Breaker 675
1
0
20
40
60
80
100
120
Time (ms)
140
160
180
200
Figure 13. Case 3 without adaptive protection: setting group of relays and
circuit breakers state.
SG
1.5
1
20
40
60
80
100
120
State Breaker 650
140
Breaker State
20
40
60
80
100
120
State Breaker 633
140
160
20
40
60
80
100
120
State Breaker 675
140
160
180
200
180
200
Breaker 675
0.5
0
200
Breaker 633
1
0
180
Breaker 650
1
0
160
20
40
60
80
100
120
Time (ms)
140
160
180
200
Figure 14. Case 3 with adaptive protection: setting group of relays and
circuit breakers state.
IV.
CONCLUSION
Distributed Generators
Pb2=1.1MW
Vb=4160V
Xd = 0.263
Xd = 0.173
Xl = 0.18
Td=1.105
R = 2.85e-3
H = 2.6
Xq = 1.6
Td= 0.035
REFERENCES
[1]
[2]