Professional Documents
Culture Documents
Vibration Control, September 16, Chiba, Japan, 1996, Vol. III, pp. 291296.
of Civil Engineering and Geological Sciences, University of Notre Dame, Notre Dame, IN 46556, U.S.A.
Dept.
ABSTRACT
Because semi-active control systems combine the best
features of passive and active control, they appear to have
significant potential to advance the acceptance of structural control as a viable means for dynamic hazard mitigation. This study demonstrates experimentally the efficacy
of recently proposed acceleration feedback control strategies for semi-actively controlled structures subjected to
earthquake excitation. A new type of semi-active control
device, known as a magnetorheological damper, is implemented in a three-story model building and tested on a
uniaxial shaking table. The results reported herein indicate
that this semi-active control system is quite effective at
seismic response reduction.
1. INTRODUCTION
Semi-active control devices have received a great deal of
attention in recent years, because they offer the adaptability of active control devices without requiring the associated large power sources. As defined here, a semi-active
control device is one that cannot increase the mechanical
energy in the controlled system (i.e., including both the
structure and the device), but has properties that can be
dynamically varied. Several such devices have been proposed for civil engineering applications (see, e.g., [1, 2]
and the references contained therein).
Because of its mechanical simplicity, low operating power
requirements, environmental robustness, and demonstrated potential for developing forces sufficient for full-scale
applications [36], one particularly promising class of
semi-active control devices for seismic response reduction
is found in magnetorheological (MR) dampers [69]. MR
dampers use MR fluids to produce controllable dampers.
MR fluids typically consist of micron-sized, magneticallypolarizable particles dispersed in a carrier medium such as
mineral or silicone oil. They are the magnetic analogs of
electrorheological (ER) fluids, and like ER fluids, the essential characteristic of the MR fluids is their ability to reversibly change from a free-flowing, linear viscous fluid
to a semi-solid in milliseconds when exposed to a magnetic field (or in the case of ER fluids, an electric field).
While there are many similarities between MR and ER
fluids, there are a number of important differences [3, 4].
For example, the achievable yield stress of MR fluids is an
order of magnitude greater than its ER counterpart, and
MR fluids are not sensitive to impurities such as are commonly encountered during manufacturing and usage.
Moreover, devices employing the MR fluid can be controlled with a low power (e.g., less than 50 watts), low
voltage (e.g., ~1224V), current-driven power supply outputting only ~12 amps. This level of power can be readily supplied by batteries.
Although MR dampers offer significant promise, they are
intrinsically nonlinear (as are most semi-active control devices), making it a challenging task to develop control
strategies that can optimally exploit their unique features.
Many of the approaches proposed in the literature to control semi-active systems either use only local information
in the control algorithm, or are based on state feedback
[1012]. While local controllers can be effective, their
ability to achieve global response reduction is limited.
Moreover, the use of state feedback is generally viewed as
being impracticable for civil engineering structures. Alternatively, control strategies based on acceleration measurements can be readily implemented in full-scale structures
[1315]. For semi-actively controlled structures, Dyke, et
al. [7, 8] have proposed a clipped-optimal control strategy
based on acceleration feedback and demonstrated via simulation its efficacy for seismic response reduction.
The focus of this paper is to present experimental verification of the acceleration feedback control strategies developed by Dyke, et al. [7, 8]. Following a description of the
experimental setup, the process of system identification
Wires
Wirestoto
Electromagnet
Electromagnet
AA
AA
AAA
Bearing & Seal
AAAA
AAAA
AA
AAAA
AA
MR Fluid AAAA
AA
AAAA
AAA
AA
AA
AA
Coil
AAAA
AAA
AA
AA
A
AAAA
AAA
Diaphragm AAAA
AA
AAAAAAA
AAAA
AA
AAA
Accumulator AAAA
AAA
AAAA
AAA
AAAA
Bearing & Seal
2. EXPERIMENTAL SETUP
MR Fluid
Annular
Orifice
Coil
Diaphragm
Accumulator
A single magnetorheological (MR) damper is installed between the ground and the first floor, as shown in Fig. 1.
The MR damper employed here is a prototype device,
shown schematically in Fig. 2, obtained from the Lord
Corporation for testing and evaluation [6] (see also http://
www.rheonetic.com/mrfluid/). The damper is 21.5 cm long
in its extended position and has a 2.5 cm stroke. The
main cylinder is 3.8 cm in diameter and houses the piston,
the magnetic circuit, an accumulator and 50 ml of MR fluid. The magnetic field produced in the device is generated
by a small electromagnet in the piston head. The current
for the electromagnet is supplied by a linear current driver
which generates a current that is proportional to the ap-
Sensors are installed in the model building for use in determining the control action. Accelerometers located on
each of the three floors provide measurements the absolute accelerations xa1 xa2 xa3 , an LVDT (linear variable
differential transformer) measures the displacement x d of
the MR damper, and a force transducer is placed in series
with the MR damper to measure the control force f being
applied to the structure. Note that only these five measurements are used in the control algorithm. However, to evaluate the performance of the control strategies, LVDTs are
attached to the base and to each floor of the structure to
measure the relative displacements of the structure.
Implementation of the discrete controller was performed
using the Spectrum Signal Processing Real-Time Digital
Signal Processor (DSP) System. The specific capabilities
of this board which make it suitable for use in structural
control systems are described in Quast, et al. [17].
xa3
xa2
Current
Driver
3. SYSTEM IDENTIFICATION
One of the most important and challenging tasks in control
synthesis and analysis is development of an accurate mathematical model of the structural system under consideration, including both the structure and the associated
control devices. A block diagram of the system to be identified, including the MR damper and the test structure, is
shown in Fig. 3, where xg is the ground acceleration, v is
the command signal to the MR damper, and y is the vector of measured structural outputs. Note that the response
of the MR damper is dependent on the relative displacement x d of the structure at the point where they are con-
xa1, x d
f
xg
Control
Computer
Fig. 1. Diagram of MR Damper Implementation.
2
xd
v
MR
Damper
xg
xd
xa1
y
xa2
xa3
f
Primary
Structure
= a + b u ,
c 0 = c 0a + c 0b u
u = ( u v )
Spencer and Dyke [9] proposed a control-oriented approach to system identification for semi-actively controlled structures that will be employed in this study. Here
the problem is simplified by decoupling the identification
of the nonlinear semi-active device from that of the primary structure. If the semi-active controller is assumed to be
adequate to keep the response of the primary structure in
the linear range, then standard linear system identification
techniques can be used to develop a model for the primary
structure. Nonlinear identification means must still be employed to identify the semi-active control device. The approach consists of four steps: (i) identification of a model
for the semi-active control device, (ii) identification of a
model for the primary structure, (iii) integration and optimization of the device and structural models, and (iv) validation of the integrated model of the system. These steps
are briefly described in the subsequent paragraphs.
n1
The frequency domain approach to linear system identification presented in Dyke, et al. [1315] is used in the second step of the process, development of a model of the test
structure. As shown in Fig. 3, the two inputs to the structure are the ground excitation xg and the applied control
force f . The four measured system outputs include the
displacement x d of the structure at the attachment point
of the MR damper, and the absolute accelerations, xa1 ,
xa2 , xa3 , of the three floors of the test structure (i.e.,
y = [ x d xa1 xa2 xa3 ] ). Thus, a 4 2 transfer function matrix must be identified to describe the characteristics of the structure in Fig. 3. The eight transfer functions
are determined by independently exciting each of the inputs of the structure with a random input and measuring
the structural responses. Each of the transfer functions is
then modeled as a ratio of two polynomials in the Laplace
variable s. This task was accomplished via a least squares
fit of the ratio polynomials, evaluated on the j axis, to
the experimentally obtained transfer functions.
(1)
n
( xd y) z + A ( xd y)
1
y = ---------------- { z + c 0 xd + k 0 ( x d y ) }
c0 + c1
(2)
(3)
y
xd
Bouc-Wen
c1
k0
c0
k1
(5)
z = xd y z z
(4)
f = c 1 y + k 1 ( x d x 0 )
c 1 = c 1a + c 1b u ,
x r = Ax r + Bf + Exg ,
y = C y x r + D y f + v,
(6)
where v represents the measurement noise vector. Additional details regarding this frequency domain identification approach can be found in Dyke, et al. [1315].
fc
v = V max
v = 0
v = 0
f
4. CONTROL DESIGN
v = 0
(8)
v = 0
v = V max
(7)
xg
MR
Damper
f
Structure
xd
f
Eq. (8)
Control Law
f
fc
Kc ( s )
5. EXPERIMENTAL RESULTS
(cm)
1.3
Uncontrolled
Controlled
x3
xa3
(cm/sec2)
1.3
0
0.5
1.5
0.5
1.5
2.5
3.5
4.5
2.5
3.5
4.5
1500
1500
0
time (sec)
6. CONCLUSION
The efficacy of a new clipped-optimal control strategy
based on acceleration feedback has been experimentally
verified on a semi-actively controlled structure employing
a magnetorheological (MR) damper. This control strategy
produced excellent results, achieving significant improvements over the passive control results. Moreover, the capabilities of the MR damper have been shown to mesh
well with the requirements and constraints associated with
the seismic response reduction in civil engineering structures. Tests on recently designed full-scale MR dampers is
currently underway [5].
Table 1 provides a summary of the peak structural responses. In addition to the results for Controllers A and B,
two passive cases are reported in Table 1. Passive-off and
passive-on refer to the cases in which the voltage to the
MR damper is held at a constant value of V = 0 and
V = Vmax = 2.25 V, respectively. Here, x i is the displacement of the i th floor relative to the ground, d i is the
interstory drift (i.e., x i x i 1 ), xai is the absolute acceleration of the i th floor, and f is the measured control
force.
ACKNOWLEDGMENT
This research is supported in part by National Science
Foundation Grant Nos. CMS 9301584, CMS 9500301
and CMS 9528083. In addition, the authors from Notre
Dame would like to express their appreciation to Lord
Corporation of Cary, North Carolina for providing the
prototype magnetorheological damper.
The semi-active control systems perform significantly better than both of the passive systems. Controller A achieves
a 24.3% reduction in the peak third floor displacement and
a 29.1% reduction in the maximum interstory displacement over the best passive case. Moreover, these results
were obtained while also achieving a modest reduction in
the maximum acceleration over that of the passive response. Additional reduction in the peak third floor relative displacement over the best passive case is achieved
with Controller B (33.3%), although at an increase in the
maximum floor acceleration. Notice that for both semi-actively controlled systems, these performance gains are
achieved while requiring smaller control forces than are
required in the passive-on case.
REFERENCES
[1] Fujino, Y., Soong, T.T. and Spencer Jr., B.F.: Structural Control: Basic Concepts and Applications, Proc.
ASCE Struct. Cong., Chicago, Illinois, pp. pp. 361
370 (1996).
[2] Spencer Jr., B.F.: Recent Trends in Vibration Control
in the U.S.A., Proc., 3rd Int. Conf. on Motion and Vibr. Control, Chiba, Japan (1996).
5
(cm)
di
(cm)
xai
(cm/sec2)
f (N)
Uncontrolled
Passive-Off
Passive-On
Clipped-Optimal
Controller A
Clipped-Optimal
Controller B
0.710
1.068
1.249
0.710
0.362
0.205
879
1110
1500
0.236
0.362
0.436
0.236
0.167
0.106
666
714
804
258
0.126
0.312
0.420
0.126
0.196
0.110
920
808
897
1030
0.127
0.229
0.318
0.127
0.139
0.092
711
642
786
696
0.151
0.213
0.280
0.151
0.123
0.087
957
859
748
754
[12] Inaudi, J.A., Hayen, J.C. and Iwan, W.D.: A Semi-Active Damping Brace System, J. of Engrg. Mech.,
ASCE, submitted.
[13] Dyke, S.J., Spencer Jr., B.F., Quast, P., Sain, M.K.,
Kaspari Jr., D.C. and Soong, T.T.: Experimental Verification of Acceleration Feedback Control Strategies
for An Active Tendon System, Nat. Center for Earthquake Engrg. Res., Tech. Report NCEER-94-0024
(1994).
[14] Dyke, S.J., Spencer Jr., B.F., Quast, P., Sain, M.K.,
Kaspari Jr., D.C. and Soong, T.T.: Acceleration Feedback Control of MDOF Structures, J. of Engrg. Mech,
ASCE (in press).
[6] Spencer Jr., B.F., Dyke, S.J., Sain, M.K. and Carlson,
J.D.: Phenomenological Model of a Magnetorheological Damper, J. Engrg. Mech., ASCE, in press.
[15] Dyke, S.J., Spencer Jr., B.F., Quast, P., Kaspari Jr. and
Sain, M.K.: Implementation of an AMD Using Acceleration Feedback Control, Microcomputers in Civil
Engrg., in press.
[7] Dyke, S.J., Spencer Jr., B.F., Sain, M.K. and Carlson,
J.D.: Seismic Response Reduction Using Magnetorheological Dampers, Proc., IFAC World Cong.,
San Francisco, California (1996).
[8] Dyke, S.J., Spencer Jr., B.F., Sain, M.K. and Carlson,
J.D.: Modeling and Control of Magnetorheological
Dampers for Seismic Response Reduction. Smart
Structures and Materials, to appear.
[17] Quast, P., Sain, M.K., Spencer Jr., B.F. and Dyke,
S.J.: Microcomputer Implementations of Digital Control Strategies for Structural Response Reduction, Microcomputers in Civil Engrg., Vol. 10, pp. 1325,
(1995).
[9] Spencer Jr., B.F. and Dyke, S.J.: Semi-Active Structural Control: System Identification for Synthesis and
Analysis, Proc. of the First Europ. Conf. on Struct.
Control, Barcelona, Spain, May 2931 (1996).
[19] Dyke, S.J., Spencer Jr., B.F., Quast, P., and Sain,
M.K.: The Role of Control-Structure Interaction in
Protective System Design, J. of Engrg. Mech, ASCE,
Vol. 121, No. 2, pp. 32238 (1995).