Impedance Relay Timing Test Report

27-Nov-14

UNIT-3 \ 7UM62
Location Path

UNIT-3

Test and Test Definition Information

Test Plan Name

FIELD FAILURE -40G

Test Name

40G TIME TEST WITH UV-CHAR2

Test Type

Z-Time

Test Definition Name

40G TIME TEST WITH UV

Tested Date

27-11-2014

Tested By

NTPC KORBA GRP ST-1

Evaluation

Fail

Test Definition Description


Relay Under Test General Parameters

Relay Name

7UM62

Serial Number
Manufacturer

SIEMENS

Nominal Ratings:

fn

Model

50.000 Hz
110.00 V (Ph-Ph)
5.000 A

Vn
In
VTR

22000 : 110

Station Name

KORBA

7UM62X

Max Test Current

2000.000% In
1000.00% Vn

Max Test Voltage

A-B-C

Phase Names and Rotation


CTR

20000 : 5

Protected Object Parameters

Protected Object Name

UNIT-5 GENERATOR MAIN-1

Protected Object Parameters


Relay Functions

Function Name

FF WITH UV

Function Type

Display values in

Secondary

Inherent Op Time

Impedance
0 ms

General Tolerances

Absolute Minimum

0.010 Ohm

Absolute Minimum Time

20.0 ms

Zone Elements
Zone Name

1_Xd_2

Char Type

General

Fault
Type

3-Ph

Characteristic
Angle

t nom
[ms]

(90.00)

Doble

10000

Residual Compensation

Z tol

t tol

-%

+%

-%

10.00

10.00

+%

10.00 10.00

Page 1 of 4

Impedance Relay Timing Test Report

27-Nov-14

UNIT-3 \ 7UM62
F6000 Instrument HW and SW Information

F6TesT Software Version

3.12.0 Build 0020

F6000 Model Number

F6150

F6000 CPU ID

67191110

F6000 Firmware Version

5.4.2

F6000 Options

F6810 : High power convertible voltage/current sources


F6909 : Front Panel Interface
F6910 : Simulator control and automation interface
F6800 : Metering & Transducer Interface
F6875 : Variable battery simulator
F6844 : Logic I/O 4 board
F6860 : IEC61850 GOOSE and GSSE messaging support
F6870 : IEC 61850 sampled values channels
F6835 : CPU3
F6005 : Enhanced ratings current amplifiers
F6803 : Wireless network connection

Doble

Page 2 of 4

Impedance Relay Timing Test Report

27-Nov-14

UNIT-3 \ 7UM62
Test Configuration

Pre-fault Voltage

110.00

Pre-fault Current

0.000

Test Method

Angle

0 Deg

Constant Current

Desired Test Current

10

Max Acceptable Voltage

65 % of rating

dc transient, fault inception angle


Minimum Offset
Time constant L/R
Values are in

0.00 ms

CT direction

Towards Line

Secondary
Trigger Selection

Test Timing

Pre-fault Duration
Max. Fault Duration
Max Fault Duration For Faster Zones

0.7000 s

Fault Type

12.0000 s

AN

x Tmax

CB Trip Time

0.0000 s

Time between shots

0.1000 s

Trigger

BN
CN
AB
BC
CA
ABC

Doble

LN1 0->1

Page 3 of 4

Impedance Relay Timing Test Report

27-Nov-14

UNIT-3 \ 7UM62
Fault Type

ABC

Angle

[]

[]

%Zone

Zone

t exp

t act

[s]

[s]

Eval

t min

t max

Err

[s]

[s]

[%]

V
Test

I
Test

[V]

[A]

15.930

210.00

89.90

1_Xd_2

10.0000

10.0305

Pass

9.0000

NoOp

0.31

41.28

2.591

19.470

210.00

110.10

1_Xd_2

NoOp

10.0461

Fail

NoOp

NoOp

41.28

2.120

27.592

240.00

89.90

1_Xd_2

10.0000

10.0461

Pass

9.0000

NoOp

0.46

41.28

1.496

33.723

240.00

110.10

1_Xd_2

NoOp

NoOp

Pass

NoOp

NoOp

41.28

1.224

31.860

270.00

89.90

1_Xd_2

10.0000

10.0359

Pass

9.0000

NoOp

0.36

41.28

1.296

38.940

270.00

110.10

1_Xd_2

NoOp

NoOp

Pass

NoOp

NoOp

41.28

1.060

27.592

300.00

89.90

1_Xd_2

10.0000

10.0415

Pass

9.0000

NoOp

0.42

41.28

1.496

33.723

300.00

110.10

1_Xd_2

NoOp

NoOp

Pass

NoOp

NoOp

41.28

1.224

15.930

330.00

89.90

1_Xd_2

10.0000

10.0435

Pass

9.0000

NoOp

0.43

41.28

2.591

19.470

330.00

110.10

1_Xd_2

NoOp

10.0415

Fail

NoOp

NoOp

41.28

2.120

Fault Type

ABC

Doble

Page 4 of 4