You are on page 1of 8

F6TesT

Test Result Details

28-Nov-14

UNIT-3 SIPROTEC.mdb \ UNIT-3

Location Path

UNIT-3

Relay Under Test General Parameters

Relay Name

7UM62

Serial Number
Manufacturer

SIEMENS

Nominal Ratings:

fn

Model

50.000 Hz
110.00 V (Ph-Ph)
5.000 A

Vn
In
VTR

15750 : 110

Station Name

KORBA

7UM62X

Max Test Current

2000.000% In
1000.00% Vn

Max Test Voltage

A-B-C

Phase Names and Rotation


CTR

10000 : 5

Protected Object Parameters

Protected Object Name

UNIT-5 GENERATOR MAIN-1

Protected Object Parameters


Test and Test Definition Information

Test Plan Name

UNDER FREQ

Test Name

PICKUP

Test Type

Ramp

Test Definition Name

81UF ST1 PICKUP

Tested Date

28-11-2014

Tested By

NTPC KORBA GRP ST-1

Evaluation

Op

Test Definition Description


F6000 Instrument HW and SW Information

F6TesT Software Version

3.12.0 Build 0020

F6000 Model Number

F6150

F6000 CPU ID

67191110

F6000 Firmware Version

5.4.2

F6000 Options

F6810 : High power convertible voltage/current sources


F6909 : Front Panel Interface
F6910 : Simulator control and automation interface
F6800 : Metering & Transducer Interface
F6875 : Variable battery simulator
F6844 : Logic I/O 4 board
F6860 : IEC61850 GOOSE and GSSE messaging support
F6870 : IEC 61850 sampled values channels
F6835 : CPU3
F6005 : Enhanced ratings current amplifiers
F6803 : Wireless network connection

Doble

Page 1 of 8

Test Result Details

28-Nov-14

UNIT-3 SIPROTEC.mdb \ UNIT-3

Test Configuration

Test Module

Frequency-Auto-Auto-Single - Ramp

Values are

Secondary

Source Configuration
Source

Pre-fault
Amplitude

Action
Ph Ang [deg]

Amplitude

Ph Ang [deg]

Frequency(Hz)

VA

63.51 V

0.00

63.51 V

0.00

Action

VB

63.51 V

-120.00

63.51 V

-120.00

Action

VC

63.51 V

120.00

63.51 V

120.00

Action

IA

0.000 A

0.00

0.000 A

0.00

50.000

IB

0.000 A

0.00

0.000 A

0.00

50.000

IC

0.000 A

0.00

0.000 A

0.00

50.000

Ramp Details

Trigger

LN1 0->1

Delay

0.0000 s

Pre-fault Duration

0.0000 s

Offset Frequency

49.0000 Hz

Offset Frequency Duration

Duration

0.0000 s

1.0000 s
-0.1000 Hz/s

Delta Frequency
Delta Time

0.5000

Frequency Limit

48.0000 Hz

Ramp Result
Test Objective

Expected
[Hz]

Ramp1

Actual

-tol [Hz]

+tol [Hz]

Error[Hz]

Eval

[Hz]

48.400

Doble

Op

Page 2 of 8

Test Result Details

28-Nov-14

UNIT-3 SIPROTEC.mdb \ UNIT-3

Test and Test Definition Information

Test Plan Name

UNDER FREQ

Test Name

PICKUP

Test Type

Ramp

Test Definition Name

81UF ST2 PICKUP

Tested Date

28-11-2014

Tested By

NTPC KORBA GRP ST-1

Evaluation

Pass

Test Definition Description


F6000 Instrument HW and SW Information

F6TesT Software Version

3.12.0 Build 0020

F6000 Model Number

F6150

F6000 CPU ID

67191110

F6000 Firmware Version

5.4.2

F6000 Options

F6810 : High power convertible voltage/current sources


F6909 : Front Panel Interface
F6910 : Simulator control and automation interface
F6800 : Metering & Transducer Interface
F6875 : Variable battery simulator
F6844 : Logic I/O 4 board
F6860 : IEC61850 GOOSE and GSSE messaging support
F6870 : IEC 61850 sampled values channels
F6835 : CPU3
F6005 : Enhanced ratings current amplifiers
F6803 : Wireless network connection

Doble

Page 3 of 8

Test Result Details

28-Nov-14

UNIT-3 SIPROTEC.mdb \ UNIT-3

Test Configuration

Test Module

Frequency-Auto-Auto-Single - Ramp

Values are

Secondary

Source Configuration
Source

Pre-fault

Action

Amplitude

Ph Ang [deg]

Amplitude

Ph Ang [deg]

Frequency(Hz)

VA

63.51 V

0.00

66.00 V

0.00

Action

VB

63.51 V

-120.00

66.00 V

-120.00

Action

VC

63.51 V

120.00

66.00 V

120.00

Action

IA

0.000 A

0.00

0.000 A

0.00

50.000

IB

0.000 A

0.00

0.000 A

0.00

50.000

IC

0.000 A

0.00

0.000 A

0.00

50.000

Ramp Details

Trigger

LN1 0->1

Delay

0.0000 s

Pre-fault Duration

0.0000 s

Offset Frequency

48.0000 Hz

Offset Frequency Duration

Duration

0.0000 s

1.0000 s
-0.1000 Hz/s

Delta Frequency
Delta Time

0.5000

Frequency Limit

47.0000 Hz

Ramp Result
Test Objective

Expected
[Hz]

Ramp1

Actual

-tol [Hz]

+tol [Hz]

Error[Hz]

Eval

[Hz]

47.400

47.400

Doble

0.000

Pass

Page 4 of 8

Test Result Details

28-Nov-14

UNIT-3 SIPROTEC.mdb \ UNIT-3

Test and Test Definition Information

Test Plan Name

UNDER FREQ

Test Name

ST TIME

Test Type

Ssimul

Test Definition Name

81UF ST1 TIME

Tested Date

28-11-2014

Tested By

NTPC KORBA GRP ST-1

Evaluation

Pass

Test Definition Description


F6000 Instrument HW and SW Information

F6TesT Software Version

3.12.0 Build 0020

F6000 Model Number

F6150

F6000 CPU ID

67191110

F6000 Firmware Version

5.4.2

F6000 Options

F6810 : High power convertible voltage/current sources


F6909 : Front Panel Interface
F6910 : Simulator control and automation interface
F6800 : Metering & Transducer Interface
F6875 : Variable battery simulator
F6844 : Logic I/O 4 board
F6860 : IEC61850 GOOSE and GSSE messaging support
F6870 : IEC 61850 sampled values channels
F6835 : CPU3
F6005 : Enhanced ratings current amplifiers
F6803 : Wireless network connection

Doble

Page 5 of 8

Test Result Details

28-Nov-14

UNIT-3 SIPROTEC.mdb \ UNIT-3

Test Configuration

State No

UF ST1

Name

Source Name

Amplitude

Ph Ang [deg]

Frequency (Hz)

VA

63.51 V

0.00

48.5000

VB

63.51 V

-120.00

48.5000

VC

63.51 V

120.00

48.5000

7.0000 s

State Duration
Trigger

0->1

Trigger Condition

LN1

Measurement
Timer Name

Timer

Start State

1-UF ST1

Stop Signal

LN1, 0->1

t Exp
[s]

5.0000

t Act
[s]

5.4160

+ tol
[%]

10.000

- tol
[%]

10.000

t Err

Eval

[%]

8.320

Pass

Oscillograph

Doble

Page 6 of 8

Test Result Details

28-Nov-14

UNIT-3 SIPROTEC.mdb \ UNIT-3

Test and Test Definition Information

Test Plan Name

UNDER FREQ

Test Name

ST TIME

Test Type

Ssimul

Test Definition Name

81UF ST2 TIME

Tested Date

28-11-2014

Tested By

NTPC KORBA GRP ST-1

Evaluation

Pass

Test Definition Description


F6000 Instrument HW and SW Information

F6TesT Software Version

3.12.0 Build 0020

F6000 Model Number

F6150

F6000 CPU ID

67191110

F6000 Firmware Version

5.4.2

F6000 Options

F6810 : High power convertible voltage/current sources


F6909 : Front Panel Interface
F6910 : Simulator control and automation interface
F6800 : Metering & Transducer Interface
F6875 : Variable battery simulator
F6844 : Logic I/O 4 board
F6860 : IEC61850 GOOSE and GSSE messaging support
F6870 : IEC 61850 sampled values channels
F6835 : CPU3
F6005 : Enhanced ratings current amplifiers
F6803 : Wireless network connection

Test Configuration

State No
Source Name

Amplitude

Ph Ang [deg]

Frequency (Hz)

VA

63.51 V

0.00

47.4000

VB

63.51 V

-120.00

47.4000

VC

63.51 V

120.00

47.4000

4.0000 s

State Duration
Trigger

UF ST2

Name

LN1

Trigger Condition

Doble

0->1

Page 7 of 8

Test Result Details

28-Nov-14

UNIT-3 SIPROTEC.mdb \ UNIT-3

Measurement
Timer Name

Timer

Start State

1-UF ST2

Stop Signal

LN1, 0->1

t Exp
[s]

2.0000

t Act
[s]

2.3479

+ tol
[%]

20.000

- tol
[%]

t Err

20.000

17.395

Eval

[%]

Pass

Oscillograph

Doble

Page 8 of 8