Professional Documents
Culture Documents
Expansion module
PAC PROFIBUS DP
Manual
02/2009
A5E01168846B-05
Introduction
Safety instructions
Description
Installation
Parameter
assignment/Addressing
Configuring
Troubleshooting/FAQs
Technical data
10
Dimension sheets
11
Appendix
ESD directives
List of abbreviations
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken.
CAUTION
without a safety alert symbol, indicates that property damage can result if proper precautions are not taken.
NOTICE
indicates that an unintended result or situation can occur if the corresponding information is not taken into
account.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The device/system may only be set up and used in conjunction with this documentation. Commissioning and
operation of a device/system may only be performed by qualified personnel. Within the context of the safety notes
in this documentation qualified persons are defined as persons who are authorized to commission, ground and
label devices, systems and circuits in accordance with established safety practices and standards.
Trademarks
All names identified by are registered trademarks of the Siemens AG. The remaining trademarks in this
publication may be trademarks whose use by third parties for their own purposes could violate the rights of the
owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
Siemens AG
Industry Sector
Postfach 48 48
90026 NRNBERG
GERMANY
A5E01168846B-05
02/2009
Table of contents
1
Introduction................................................................................................................................................ 9
1.1
1.2
1.3
1.4
1.5
Further documentation.................................................................................................................10
Description............................................................................................................................................... 13
3.1
3.2
Features .......................................................................................................................................14
3.3
Structure.......................................................................................................................................15
3.4
3.4.1
3.4.2
Installation ............................................................................................................................................... 17
4.1
4.2
Unpacking ....................................................................................................................................18
4.3
4.4
Measured variables......................................................................................................................23
5.2
5.2.1
5.2.2
5.2.3
5.2.4
5.2.5
5.2.6
5.2.7
5.3
5.3.1
5.3.2
5.3.3
5.3.4
5.3.5
5.3.6
5.3.7
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Table of contents
5.3.8
5.3.9
5.3.10
5.3.11
5.3.12
5.3.13
5.3.14
5.3.15
5.3.16
5.3.17
5.3.18
5.3.19
5.3.20
5.3.21
5.3.22
5.3.23
5.4
5.5
Reading and writing data record with other PROFIBUS DP masters ......................................... 53
5.6
Protocol sequence for read data record and write data record................................................... 53
5.7
5.8
5.8.1
5.8.2
5.8.3
Data formats................................................................................................................................ 58
Energy counters .......................................................................................................................... 58
Limits ........................................................................................................................................... 58
Digital inputs status and digital outputs status ............................................................................ 59
Configuring .............................................................................................................................................. 61
6.1
6.2
6.3
6.4
6.5
Information and settings on the SENTRON PAC Power Monitoring Device .............................. 70
Cleaning ...................................................................................................................................... 73
7.2
Repair.......................................................................................................................................... 73
7.3
Disposal....................................................................................................................................... 74
7.4
8.2
8.2.1
8.2.2
8.2.3
8.2.4
8.3
Diagnostics LED.......................................................................................................................... 83
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Table of contents
Troubleshooting/FAQs............................................................................................................................. 85
9.1
10
11
Standards.....................................................................................................................................87
10.2
Technical data..............................................................................................................................87
10.3
10.4
Labeling........................................................................................................................................91
Appendix.................................................................................................................................................. 95
List of abbreviations................................................................................................................................. 99
C.1
Abbreviations ...............................................................................................................................99
Table 5- 2
Table 5- 3
Table 5- 4
Table 5- 5
Table 5- 6
Table 5- 7
Data records of the SENTRON PAC devices addressed via slot number 1 ...............................32
Table 5- 8
DPV1 data records for the PAC PROFIBUS DP expansion module ...........................................32
Table 5- 9
Table 5- 10
Table 5- 11
Structure of data record DS68 - read access and write access ..................................................35
Table 5- 12
Table 5- 13
Table 5- 14
Table 5- 15
Table 5- 16
Table 5- 17
Table 5- 18
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Table of contents
Table 5- 19
Table 5- 20
Table 5- 21
Table 5- 22
Table 5- 23
Table 5- 24
Table 5- 25
Table 5- 26
Table 5- 27
Table 5- 28
Structure of data record DS255, IM0 data read access only ...................................................... 50
Table 5- 29
Structure of data record DS255, IM1 data - read access and write access ............................... 51
Table 5- 30
Structure of data record DS255, IM2 data - read access and write access ............................... 51
Table 5- 31
Structure of data record DS255, IM3 data - read access and write access ............................... 51
Table 5- 32
Structure of data record DS255, IM4 data - read access and write access ............................... 52
Table 5- 33
Table 5- 34
Table 5- 35
Table 5- 36
Table 5- 37
Scheme: Input statuses and output statuses of the SENTRON PAC Power Monitoring
Device ......................................................................................................................................... 60
Table 6- 1
Factory settings........................................................................................................................... 61
Table 6- 2
Table 6- 3
Table 6- 4
Table 6- 5
Table 6- 6
Table 8- 1
Table 8- 2
Structure of the diagnostic interrupts of the SENTRON PAC Power Monitoring Device slave diagnostics......................................................................................................................... 76
Table 8- 3
Structure of the diagnostic interrupts of the SENTRON PAC Power Monitoring Device device diagnostics....................................................................................................................... 76
Table 8- 4
Structure of the diagnostic interrupts of the SENTRON PAC Power Monitoring Device interrupt messages...................................................................................................................... 77
Table 8- 5
Table 8- 6
Table 8- 7
Table 8- 8
Table 8- 9
Device diagnostics data Yes/No: Structure of the device diagnostics in byte 10 ....................... 80
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Table of contents
Table 8- 10
Communication faults: Structure of the device diagnostics in byte 11 and the interrupt
message in byte 18......................................................................................................................80
Table 8- 11
Violation of the limits: Structure of the device diagnostics in byte 12 and the interrupt
message in byte 19......................................................................................................................80
Table 8- 12
Invalid values and invalid settings: Structure of the device diagnostics in byte 13 and the
interrupt message in byte 20........................................................................................................81
Table 8- 13
Table 8- 14
Table 10- 1
Table 10- 2
Table 10- 3
Table 10- 4
Table 10- 5
Table 10- 6
Table A- 1
Table C- 1
Meaning of abbreviations.............................................................................................................99
Figures
Figure 3-1
Schematic view of the side and front of the PAC PROFIBUS DP expansion module.................15
Figure 4-1
Figure 5-1
Parameterizing the PAC PROFIBUS DP expansion module - example 1: Add basic type 1
to slot 1.........................................................................................................................................25
Figure 5-2
Figure 5-3
Figure 5-4
Figure 5-5
Figure 5-6
Figure 5-7
Figure 5-8
Figure 5-9
Figure 5-10
Figure 6-1
Configuring the integration of PROFIBUS using STEP 7 and the GSD file ................................62
Figure 6-2
Figure 10-1
Figure 10-2
Figure 11-1
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Table of contents
Figure 11-2
Bottom view and top view with sub D socket connector and the dimensions of the pin
contact between the PAC PROFIBUS DP expansion module and the SENTRON PAC ........... 93
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Introduction
1.1
1.2
Orientation aids
General information
The manual includes the following orientation aids:
Table of contents
List of figures and tables
List of abbreviations
Glossary
Index
1.3
Description
The package includes:
The PAC PROFIBUS DP expansion module
The operating instructions for the PAC PROFIBUS DP expansion module
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Introduction
1.4 Latest information and correction sheet
1.4
Up-to-the-minute information
You can obtain further assistance by calling the following numbers:
Technical Assistance:
Phone:
Fax:
Correction sheet
A correction sheet is included at the end of the manual. Please use it to record your
suggestions for improvements, additions and corrections, and return the sheet to us. This will
help us to improve the next edition of the manual.
1.5
Further documentation
Overview
You can find more information, e.g. parameters, values, and setting options for the
SENTRON PAC Power Monitoring Device in the following manuals:
Manual for the SENTRON PAC Power Monitoring Device
Operating instructions for the SENTRON PAC Power Monitoring Device
You can find more information on SIMATIC in the following manuals:
SIMATIC NET "PROFIBUS Network Manual"
SIMATIC "Configuring Hardware and Connections with STEP 7"
"SIMATIC PCS 7 Block Library PAC3200"
"SENTRON PAC3200 block library for SIMATIC WinCC"
Support (http://support.automation.siemens.com)
You can find more information on PROFIBUS in the:
PROFIBUS RS485-IS User and Installation Guide
(http://www.profibus.com/pall/meta/downloads/article/00332/)
You can find more information on the PAC PROFIBUS DP expansion module in the
operating instructions for the PAC PROFIBUS DP expansion module.
10
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Safety instructions
2.1
Safety notes
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
11
Safety instructions
2.1 Safety notes
12
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Description
3.1
Area of application
The PAC PROFIBUS DP expansion module is designed for use with a SENTRON PAC
Power Monitoring Device. The guidelines for the SENTRON PAC Power Monitoring Device
also apply to the PAC PROFIBUS DP expansion module.
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
13
Description
3.2 Features
3.2
Features
You can use the PAC PROFIBUS DP expansion module to access the SENTRON PAC
Power Monitoring Devices during operation.
Overview
Features include:
Communication based on the PROFIBUS DP master-slave principle:
The PAC PROFIBUS DP expansion module provides the PROFIBUS DP master with
measured values of the SENTRON PAC Power Monitoring Device. It receives
information, e.g. commands, from the PROFIBUS DP master, and forwards this
information to the SENTRON PAC Power Monitoring Device.
Function: PROFIBUS DP slave
Communication with the class 1 master and the class 2 masters
Cyclic data transfer
Acyclic data transfer
Specific GSD file for every Power Monitoring Device type. This allows correct integration
into the controller.
Automatic detection of the baud rate
Clock synchronization depending on the device type
Setting the PROFIBUS address:
At the device
With parameterization software
Per PROFIBUS
Generation of diagnostic interrupts and process interrupts
Diagnostics also via the local display
Status display via LED
To ensure galvanic isolation between the SENTRON PAC Power Monitoring Device and
the PROFIBUS.
14
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Description
3.3 Structure
3.3
Structure
(1)
Sub D socket
(2)
(3)
Ventilation slots
(4)
LED
Figure 3-1
Schematic view of the side and front of the PAC PROFIBUS DP expansion module
3.4
PROFIBUS functions
3.4.1
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
15
Description
3.4 PROFIBUS functions
3.4.2
Unsupported functions
Unsupported functions
The following PROFIBUS functions are not supported:
SYNC / UNSYNC
FREEZE / UNFREEZE
16
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Installation
4.1
Procedure
1. Mount the SENTRON PAC Power Monitoring Device and the PAC PROFIBUS DP
expansion module.
2. Connect the SENTRON PAC Power Monitoring Device.
3. Connect the PAC PROFIBUS DP expansion module to the PROFIBUS network.
4. Check all connections and settings.
5. Apply supply voltage to the SENTRON PAC Power Monitoring Device. The
SENTRON PAC Power Monitoring Device and expansion module are then ready for
operation.
6. Parameterize the SENTRON PAC Power Monitoring Device as described in the manual
for the SENTRON PACxxxx Power Monitoring Device.
7. Set the planned PROFIBUS address on the SENTRON PAC Power Monitoring Device.
8. Configure the PAC PROFIBUS DP expansion module. The STEP 7 HW Config, for
example, can be used as the configuring tool.
Assign the SENTRON PAC Power Monitoring Device to the PROFIBUS network.
Link the device-specific GSD file for the PAC PROFIBUS DP expansion module.
Select the basic types or the desired measured variables for the SENTRON PAC
Power Monitoring Device.
Transfer the parameter assignment to the PROFIBUS DP master.
See also
Unpacking (Page 18)
Installation and connection (Page 18)
Measures to be performed prior to start-up (Page 21)
Cyclic data traffic (Page 24)
Default settings (Page 61)
Configuration scenarios (Page 61)
Changing the address (Page 62)
Configuring by means of the GSD file (Page 63)
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
17
Installation
4.2 Unpacking
4.2
Unpacking
Observe the ESD guidelines. Open the packaging with care. Do not use excessive force.
Checks
After receiving the module, and before installing it, you should make the following checks:
Check the packaging for damage.
Make sure that the package contents are complete.
Check the module for external damage.
Please contact your Siemens sales partner in the following cases:
The packaging is damaged
The contents of the package are not complete
The module is damaged
Storage
Store the PAC PROFIBUS DP expansion module in a dry place.
NOTICE
Formation of condensation
Store the device in the service room for at least two hours before applying voltage to the
device for the first time. This will equalize the temperature and prevent the formation of
condensation.
See also
Electrostatic sensitive devices (ESD) (Page 97)
4.3
Tools
To install the PAC PROFIBUS DP expansion module you will need the following tool:
A PZ1 cross-tip screwdriver, 2.9 mm, 0.5 Nm cal. ISO 6789
Assembly
Install the PAC PROFIBUS DP expansion module before operating the SENTRON PAC.
Observe the ESD guidelines.
18
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Installation
4.3 Installation and connection
CAUTION
Impairment and endangering of operation
Damaged components can impair and endanger operation. Never use damaged
components.
CAUTION
Faulty sub D connector and faulty connector to the SENTRON PAC Power Monitoring
Device
Dirty or bent pins can affect the function of the connectors. The connectors can be
destroyed. Do not allow the pins to become dirty.
Make sure that:
There are no metal parts between the pins.
There are no metal parts adhering to the pins.
The pins do not bend.
Do not touch the pins.
NOTICE
Do not cover the ventilation slots
If the ventilation slots are covered, the PAC PROFIBUS DP expansion module can
overheat. Make sure that the ventilation slots are not covered.
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
19
Installation
4.3 Installation and connection
Figure 4-1
20
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Installation
4.4 Measures to be performed prior to start-up
The following general points must be observed when connecting:
Equipotential bonding of the PAC PROFIBUS DP expansion module
Bus terminating resistors
Note
Bus terminating resistor
There is no bus terminating resistor in the PAC PROFIBUS DP expansion module. The
bus terminator is provided by the PROFIBUS adaptor plug, which includes a bus
terminating resistor. You can find more information in the operating instructions for the
PROFIBUS adaptor plug.
Please note:
The PROFIBUS installation guidelines in "PROFIBUS RS485-IS User and Installation
Guideline"
The "SIMATIC NET PROFIBUS Network Manual"
See also
Further documentation (Page 10)
Safety notes (Page 11)
Electrostatic sensitive devices (ESD) (Page 97)
Unpacking (Page 18)
Measures to be performed prior to start-up (Page 21)
4.4
Checks
Once you have correctly installed the PAC PROFIBUS DP expansion module, you should
carry out the following checks:
1. Check that the PAC PROFIBUS DP expansion module is connected to the
SENTRON PAC Power Monitoring Device correctly.
2. Check that the connector of the PROFIBUS cable is plugged into the sub D socket of the
PAC PROFIBUS DP expansion module correctly and screwed down tightly.
3. Check that the ventilation slots are not covered.
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
21
Installation
4.4 Measures to be performed prior to start-up
22
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Parameter assignment/Addressing
5.1
Measured variables
The measured variables and status information of the SENTRON PAC are available to the
higher-level power management system or automation system via PROFIBUS.
See also
Introduction (Page 9)
Energy counters (Page 58)
Further documentation (Page 10)
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
23
Parameter assignment/Addressing
5.2 Cyclic data traffic
5.2
5.2.1
Introduction
Description
In cyclic data traffic, each message frame transfers an optional number of user data. Cyclic
data exchange is especially suitable for transferring information that is required continuously
and quickly. The time interval between two message frames depends on:
The number of nodes
The data volume
The baud rate
All available data types that PROFIBUS can transfer are defined in the GSD file for the
SENTRON PAC Power Monitoring Device. There are three basic types with predefined
measured variables for time-saving commissioning and efficient data transfer. The user can
also define individual measured variables to be transferred.
Note
Note the quantity structure
The maximum quantity structure of the SENTRON PACxxxx for PROFIBUS is 244 bytes of
input data and 2 bytes of output data.
See also
Standards (Page 87)
Further documentation (Page 10)
24
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Parameter assignment/Addressing
5.2 Cyclic data traffic
5.2.2
Basic type 1
Structure
The structure of basic type 1 is fixed. The length of basic type 1 is 20 bytes of input data and
2 control bytes (output data). The following information is transferred in basic type 1.
Table 5- 1
Byte
Data value
Format
Unit
0 ... 3
Status information
Unsigned long
4 ... 7
Current a
Float
8 ... 11
Current b
Float
12 ... 15
Current c
Float
16 ... 19
Float
Figure 5-1
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
25
Parameter assignment/Addressing
5.2 Cyclic data traffic
See also
Status information in the cyclic channel (Page 28)
Control bytes (Page 30)
Basic type 2 (Page 26)
Basic type 1 and basic type 2 DS51 (Page 34)
5.2.3
Basic type 2
Structure
Basic type 2 is an extension of basic type 1. This means that you can easily add basic type 1
and basic type 2 during the project design phase. You can also use basic type 2 as a
separate unit. The structure of basic type 2 is fixed. Basic type 2 is 24 bytes.
Table 5- 2
Byte
Data value
Format
Unit
0 ... 3
Voltage a-b
Float
4 ... 7
Voltage b-c
Float
8 ... 11
Voltage c-a
Float
12 ... 19
Double Float
Wh
20 ... 23
Float
See also
Basic type 1 (Page 25)
Basic type 1 and basic type 2 DS51 (Page 34)
5.2.4
Basic type 3
Structure
The structure of basic type 3 is fixed. Basic type 3 contains the control bytes.
Table 5- 3
26
Device
Length in byte
SENTRON PAC3200
112
SENTRON PAC4200
116
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Parameter assignment/Addressing
5.2 Cyclic data traffic
Table 5- 4
Byte
Format
Unit
0 ... 3
Status information
Unsigned long
4 ... 7
Voltage a-n
Float
8 ... 11
Spannung b-n
Float
12 ... 15
Voltage c-n
Float
16 ... 19
Voltage a-b
Float
20 ... 23
Voltage b-c
Float
24 ... 27
Voltage c-a
Float
28 ... 31
Current a
Float
32 ... 35
Current b
Float
36 ... 39
Current c
Float
40 ... 43
Power factor a
Float
44 ... 47
Power factor b
Float
48 ... 51
Power factor c
Float
52 ... 55
THD voltage
a1)
Float
56 ... 59
Float
60 ... 63
THD voltage
c1)
Float
64 ... 67
Float
68 ... 71
THD current
b1)
Float
72 ... 75
THD current
c1)
Float
76 ... 79
Line frequency
Float
Hz
80 ... 83
Float
84 ... 87
Float
VA
88 ... 91
Float
92 ... 95
Float
Var
96 ... 99
Float
Float
Float
Unsigned long
Float
Neutral conductor
current2)
See also
Status information in the cyclic channel (Page 28)
Control bytes (Page 30)
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
27
Parameter assignment/Addressing
5.2 Cyclic data traffic
5.2.5
Procedure
In cyclic mode, you can specify other individual measured variables to be transferred.
Figure 5-2
5.2.6
Status information
In cyclic data traffic, the status information is sent on every data exchange at the beginning
of a basic type 1 and basic type 3 data structure. You can add the status information during
the configuration phase. The status information is treated as diagnostics data for the device.
28
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Parameter assignment/Addressing
5.2 Cyclic data traffic
Table 5- 5
Byte
Bit
Description
Byte n
System status
Byte n + 1
Device status
Byte n + 2
Device diagnostics
Byte n + 3
Component diagnostics
Reserved
Reserved
Reserved
Reserved
Reserved
10
Reserved
11
Reserved
12
Reserved
13
Reserved
14
Reserved
15
Reserved
16
17
18
19
Reserved
20
Reserved
21
Reserved
22
Reserved
23
Reserved
24
Reserved
25
Reserved
26
Reserved
27
Reserved
28
Reserved
29
Reserved
20
Reserved
31
Reserved
The diagnostics information remains active until acknowledged. The status information
remains active as long as the cause exists. Status information is not acknowledged.
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
29
Parameter assignment/Addressing
5.2 Cyclic data traffic
5.2.7
Control bytes
Description
The control bytes are delivered with basic type 1 and basic type 3 as standard. Alternatively,
you can add the control bytes during the configuration phase.
These commands can be used to clear the memory contents or to change the tariff, for
example. When you set a bit, the function belonging to the bit is activated. You must reset
the control bit afterwards. The class 1 master sends these commands to the PROFIBUS DP
slave.
Structure
Table 5- 6
Byte
Byte n
Byte n + 1
Activation
Description
Rising edge
transition1)
Rising edge
transition1)
Rising edge
transition1)
Reserved
Reserved
Reserved
Rising edge
transition1)
8
9
Rising edge
transition1)
10
Level sensitive
ON = 1
OFF = 0
11
Level sensitive
ON = 1
OFF = 0
12
Reserved
13
Reserved
14
Reserved
15
Reserved
1) Only a change from 0 to 1 activates this function, e.g., changing bit 8 from 0 to 1 brings about a changeover to the
highest tariff. The value 1 or a reset from 1 to 0 has no effect.
2) SENTRON PAC4200 and higher
NOTICE
Only one set of control bytes
There can only be one set of control bytes per device. If you add basic type 1 or basic
type 3 during the parameterization stage, then you must not add control bytes separately.
30
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Parameter assignment/Addressing
5.3 Acyclic data traffic
See also
Basic type 1 (Page 25)
5.3
5.3.1
Introduction
Requirements
For acyclic data traffic, you require a DPV1-enabled class 1 master or a DPV1-enabled class
2 master.
Description
In addition to cyclic data traffic, acyclic data can be transferred, e.g. parameters, diagnostics
information, commands, further data. Acyclic data transfer takes place in parallel with cyclic
data traffic.
You can use acyclic data traffic with the following methods:
The SENTRON PACxxxx block libraries for SIMATIC display the measured values in
faceplates and make these available in the SIMATIC S7 for further processing.
SIMATIC S7 CPUs contain system function blocks (SFB52, SFB53, SFB54). With these,
the CPUs can read and write the data records individually, and read the alarm messages.
Every other PROFIBUS DP master can implement the data records.
Note
Acyclic connections to masters
The expansion module supports up to five acyclic connections simultaneously:
up to four with class 2 masters and one with a class 1 master.
5.3.2
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
31
Parameter assignment/Addressing
5.3 Acyclic data traffic
Data records of the SENTRON PAC devices addressed via slot number 1
Description
SENTRON
PAC3200
only
SENTRON
PACxxxx
Access
DS1
System diagnostics
DS51
DS68
RW
DS69
DS72
DS73
DS74
DS76
DS92
DS93
Commands
DS94
DS95
RW
DS131
RW
DS132
RW
DS202
Current
DS203
Voltage
RW
DS204
Power
DS205
Energy counters
RW
DS206
DS255
IM0: R
IM1 to IM4:
RW
32
Description
Access
DS255
RW
Abbreviation
Meaning
Read
Write
RW
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Parameter assignment/Addressing
5.3 Acyclic data traffic
See also
Addressing parameter (Page 52)
5.3.3
DS1
Data record DS1 contains the data for system diagnostics.
Table 5- 9
Byte
Bit position
Length in bits
Format
Description
32
Unsigned char
Header
32
Unsigned long
Reserved
16
Unsigned short
Reserved
10
Unsigned char
11
Unsigned char
12
Unsigned char
13
Unsigned char
14
Bit
Reserved
Bit
Reserved
Bit
Reserved
Bit
Reserved
Bit
Reserved
Bit
Reserved
15
Bit
Reserved
Bit
Bit
Bit
Bit
Reserved
Bit
Bit
Reserved
Bit
Bit
Bit
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
33
Parameter assignment/Addressing
5.3 Acyclic data traffic
Byte
Bit position
16
0
1
17
Length in bits
Format
Description
Bit
Bit
Bit
Bit
Limit violations
Bit
Reserved
Bit
Reserved
Bit
Reserved
Bit
Reserved
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Total bytes: 18
1) On SENTRON PAC3200 only
5.3.4
DS51
Data record DS51 contains basic type 1 and basic type 2.
Table 5- 10
Byte
Number of
bits
Format
Description
32
Struct
Header
32
Unsigned long
Reserved
16
Unsigned short
Reserved
10
160
Struct
Basic type 1
30
192
Struct
Basic type 2
Total bytes: 54
See also
Basic type 1 (Page 25)
Basic type 2 (Page 26)
Reading data records DS51 and DS205 (Page 56)
34
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Parameter assignment/Addressing
5.3 Acyclic data traffic
5.3.5
DS68
Data record DS68 contains the output signals.
Table 5- 11
Byte
Number of
bits
Format
Description
32
Struct
Header
32
Unsigned long
Reserved
16
Unsigned short
Reserved
10
32
Unsigned long
14
32
Unsigned long
Reserved
18
32
Unsigned long
Reserved
22
32
Unsigned long
Reserved
Total bytes: 26
See also
Digital inputs status and digital outputs status (Page 59)
5.3.6
DS69
Data record DS69 contains the output signals.
Table 5- 12
Byte
Number of
bits
Format
Description
32
Struct
Header
32
Unsigned long
Reserved
16
Unsigned short
Reserved
10
32
Unsigned long
14
32
Unsigned long
Reserved
18
32
Unsigned long
Reserved
22
32
Unsigned long
Reserved
Total bytes: 26
See also
Digital inputs status and digital outputs status (Page 59)
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
35
Parameter assignment/Addressing
5.3 Acyclic data traffic
5.3.7
DS72
Data record DS72 contains the maximum and minimum current values.
Table 5- 13
Byte
Number of
bits
Format
Description
32
Struct
Header
32
Unsigned long
Reserved
16
Unsigned short
Reserved
10
32
Float
Maximum current a
14
32
Float
Maximum current b
18
32
Float
Maximum current c
22
32
Float
26
32
Float
Minimum current a
30
32
Float
Minimum current b
34
32
Float
Minimum current c
38
32
Float
Total bytes: 42
5.3.8
DS73
Data record DS73 contains the maximum and minimum voltage values.
Table 5- 14
36
Byte
Number of bits
Format
Description
32
Struct
Header
32
Unsigned long
Reserved
16
Unsigned short
Reserved
10
32
Float
14
32
Float
18
32
Float
22
32
Float
26
32
Float
30
32
Float
34
32
Float
38
32
Float
42
32
Float
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Parameter assignment/Addressing
5.3 Acyclic data traffic
Byte
Number of bits
Format
Description
46
32
Float
50
32
Float
54
32
Float
58
32
Float
62
32
Float
66
32
Float
70
32
Float
Total bytes: 74
5.3.9
DS74
Data record DS74 contains the maximum and minimum power values.
Table 5- 15
Byte
Format
Description
32
Struct
Header
32
Unsigned long
Reserved
16
Unsigned short
Reserved
10
32
Float
14
32
Float
18
32
Float
22
32
Float
26
32
Float
30
32
Float
34
32
Float
38
32
Float
42
32
Float
46
32
Float
50
32
Float
54
32
Float
58
32
Float
62
32
Float
66
32
Float
70
32
Float
74
32
Float
78
32
Float
82
32
Float
86
32
Float
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
37
Parameter assignment/Addressing
5.3 Acyclic data traffic
Byte
Number of
bits
Format
Description
90
32
Float
94
32
Float
98
32
Float
102
32
Float
106
32
Float
110
32
Float
114
32
Float
118
32
Float
122
32
Float
126
32
Float
130
32
Float
134
32
Float
5.3.10
DS76
Data record DS76 contains the maximum and minimum line frequency values and the THD
values.
Table 5- 16
Byte
Number of
bits
Format
Description
32
Struct
Header
32
Unsigned long
Reserved
16
Unsigend short
Reserved
10
32
Float
14
32
Float
18
32
Float
22
32
Float
26
32
Float
30
32
Float
34
32
Float
38
32
Float
Total bytes: 42
38
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Parameter assignment/Addressing
5.3 Acyclic data traffic
5.3.11
DS92
Data record DS92 contains status information and diagnostic information.
Table 5- 17
Byte
Number of
bits
Format
Description
32
Struct
Header
32
Unsigned long
Reserved
16
Unsigned short
Reserved
10
32
Unsigned long
14
32
Unsigned long
18
32
Unsigned long
22
32
Unsigned long
26
32
Unsigned long
Total bytes: 30
5.3.12
Commands DS93
DS93
Data record DS93 contains command information.
Table 5- 18
Byte
Bit
position
Number of
bits
Format
Description
32
Struct
Header
32
Unsigned long
Reserved
16
Unsigned short
Reserved
10
Unsigned char
Command counter
11)
Bit
11)
Bit
11)
Bit
11)
Bit
11)
Bit
Bit
Reserved
Bit
Reserved
Bit
Reserved
11
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
39
Parameter assignment/Addressing
5.3 Acyclic data traffic
Byte
Bit
position
Number of
bits
Format
Description
12
11)
Bit
11)
Bit
12)
Bit
12)
Bit
Bit
Reserved
Bit
Reserved
Bit
Reserved
Bit
Reserved
11)
Bit
11)
Bit
Bit
Bit
Reserved
Bit
Reserved
Bit
Reserved
Bit
Reserved
13
14
Bit
Reserved
Unsigned char
Reserved
Total bytes: 15
1) "1" means: The action is executed.
"0" means: The action is not executed.
2) "1" means: Signal = 1
"0" means: Signal = 0
3) If parameterized and available
4) Not on SENTRON PAC3200
5.3.13
Current measured values, voltage measured values, and power measured values
DS94
DS94
Data record DS94 contains the current measured values, the voltage measured values, and
the power measured values.
Table 5- 19
Byte
40
Format
Description
32
Struct
Header
32
Unsigned long
Reserved
16
Unsigned short
Reserved
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Parameter assignment/Addressing
5.3 Acyclic data traffic
Byte
Number
of bits
Format
Description
10
32
Float
Voltage a-n
14
32
Float
Voltage b-n
18
32
Float
Voltage c-n
22
32
Float
Voltage a-b
26
32
Float
Voltage b-c
30
32
Float
Voltage c-a
34
32
Float
Current a
38
32
Float
Current b
42
32
Float
Current c
46
32
Float
Apparent power a
50
32
Float
Apparent power b
54
32
Float
Apparent power c
58
32
Float
Active power a
62
32
Float
Active power b
66
32
Float
Active power c
70
32
Float
Reactive power a
74
32
Float
Reactive power b
78
32
Float
Reactive power c
82
32
Float
Power factor a
86
32
Float
Power factor b
90
32
Float
Power factor c
94
32
Float
THD-R voltage a
98
32
Float
THD-R voltage b
102
32
Float
THD-R voltage c
106
32
Float
THD-R current a
110
32
Float
THD-R current b
114
32
Float
THD-R current c
118
32
Float
Line frequency
122
32
Float
126
32
Float
130
32
Float
134
32
Float
138
32
Float
142
32
Float
146
32
Float
150
32
Float
154
32
Float
158
32
Float
Active tariff
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
41
Parameter assignment/Addressing
5.3 Acyclic data traffic
5.3.14
DS95
Data record DS95 contains the value of the working hours counter and the value of the
configurable universal counter.
Table 5- 20
Byte
Number
of bits
Format
Description
32
Struct
Header
32
Unsigned long
Reserved
16
Unsigned short
Reserved
10
32
Unsigned long
14
32
Unsigned long
Universal counter1)
Total bytes: 18
1) 0xFFFFFFFF means: No action.
Every other value is accepted.
5.3.15
DS131
Data record DS131 contains setting parameters for the SENTRON PAC Power Monitoring
Device.
Table 5- 21
Byte
42
Format
Description
32
Struct
Header
32
Unsigned long
Reserved
16
Unsigned short
Reserved
10
32
Unsigned long
Connection type:
0 = 3P4W
1 = 3P3W
2 = 3P4WB
3 = 3P3WB
4 = 1P2W
14
32
Unsigned long
18
32
Unsigned long
Primary voltage
22
32
Unsigned long
Secondary voltage
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Parameter assignment/Addressing
5.3 Acyclic data traffic
Byte
Number of
bits
Format
Description
26
32
Unsigned long
30
32
Unsigned long
Primary current
34
32
Unsigned long
Secondary current
38
32
Unsigned long
42
32
Unsigned long
Line frequency
46
32
Float
50
32
Unsigned long
Demand period
54
32
Unsigned long
Synchronization
58
32
Unsigned long
62
32
Unsigned long
Reserved
66
32
Unsigned long
70
32
Unsigned long
74
32
Unsigned long
78
32
Unsigned long
82
32
Unsigned long
86
32
Unsigned long
Reserved
90
32
Unsigned long
94
32
Unsigned long
98
32
Unsigned long
102
32
Unsigned long
Dialog language
106
32
Unsigned long
110
32
Unsigned long
114
32
Unsigned long
118
32
Unsigned long
Display contrast
122
32
Unsigned long
126
32
Unsigned long
130
32
Unsigned long
See also
Further documentation (Page 10)
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
43
Parameter assignment/Addressing
5.3 Acyclic data traffic
5.3.16
DS132
Data record DS132 contains parameters for setting the limit values.
Table 5- 22
44
Byte
Number of
bits
Format
Standard
Description
Unsigned
char
Unsigned
char
0x00
Unsigned
char
Unsigned
char
0x00
32
Unsigned
long
0x00
Reserved
16
Unsigned
short
0x00
Reserved
10
Unsigned
char
0x01
11
Unsigned
char
0x00
Reserved
12
32
Unsigned
long
16
32
Float
Hysteresis
20
32
Unsigned
long
Delay
24
32
Unsigned
long
28
32
Unsigned
long
Source
32
32
Float
Value
36
32
Unsigned
long
MODE / <
Header coordination
Header reserved
Header slot number
Limit 0
ON/OFF
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Parameter assignment/Addressing
5.3 Acyclic data traffic
Byte
Number of
bits
Format
Standard
Description
40
32
Unsigned
long
44
32
Float
Hysteresis
48
32
Unsigned
long
Delay
52
32
Unsigned
long
56
32
Unsigned
long
Source
60
32
Float
Value
64
32
Unsigned
long
MODE / <
68
32
Unsigned
long
Limit 1
Limit 2
ON/OFF
ON/OFF
72
32
Float
Hysteresis
76
32
Unsigned
long
Delay
80
32
Unsigned
long
84
32
Unsigned
long
Source
88
32
Float
Value
92
32
Unsigned
long
MODE / <
96
32
Unsigned
long
Limit 3
ON/OFF
100
32
Float
Hysteresis
104
32
Unsigned
long
Delay
108
32
Unsigned
long
112
32
Unsigned
long
Source
116
32
Float
Value
120
32
Unsigned
long
MODE / <
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
45
Parameter assignment/Addressing
5.3 Acyclic data traffic
Byte
Number of
bits
Format
Standard
Description
124
32
Unsigned
long
128
32
Float
Hysteresis
132
32
Unsigned
long
Delay
136
32
Unsigned
long
140
32
Unsigned
long
Source
144
32
Float
Value
148
32
Unsigned
long
MODE / <
152
32
Unsigned
long
Limit 4
ON/OFF
ON/OFF
Limit 5
156
32
Float
Hysteresis
160
32
Unsigned
long
Delay
164
32
Unsigned
long
168
32
Unsigned
long
Source
172
32
Float
Value
176
32
Unsigned
long
MODE / <
Total bytes:
180
See also
Further documentation (Page 10)
5.3.17
Current DS202
DS202
Data record DS202 contains the current values.
Table 5- 23
46
Byte
Number of
bits
Format
Description
32
Struct
Header
32
Unsigned long
Reserved
16
Unsigned short
Reserved
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Parameter assignment/Addressing
5.3 Acyclic data traffic
Byte
Number of
bits
Format
Description
10
32
Float
Current a
14
32
Float
Current b
18
32
Float
Current c
22
32
Float
THD-R current a
26
32
Float
THD-R current b
30
32
Float
THD-R current c
34
32
Float
Total bytes: 38
5.3.18
Voltage DS203
DS203
Data record DS203 contains the voltage values.
Table 5- 24
Byte
Number of bits
Format
Description
32
Struct
Header
32
Unsigned long
Reserved
16
Unsigned short
Reserved
10
32
Float
Voltage a-n
14
32
Float
Voltage b-n
18
32
Float
Voltage c-n
22
32
Float
Voltage a-b
26
32
Float
Voltage b-c
30
32
Float
Voltage c-a
34
32
Float
THD-R voltage a
38
32
Float
THD-R voltage b
42
32
Float
THD-R voltage c
46
32
Float
50
32
Float
Total bytes: 54
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
47
Parameter assignment/Addressing
5.3 Acyclic data traffic
5.3.19
Power DS204
DS204
Data record DS204 contains the power values.
Table 5- 25
Byte
Number of bits
Format
Description
32
Struct
Header
32
Unsigned long
Reserved
16
Unsigned short
Reserved
10
32
Float
Apparent power a
14
32
Float
Apparent power b
18
32
Float
Apparent power c
22
32
Float
Active power a
26
32
Float
Active power b
30
32
Float
Active power c
34
32
Float
Reactive power a
38
32
Float
Reactive power b
42
32
Float
Reactive power c
46
32
Float
Power factor a
50
32
Float
Power factor b
54
32
Float
Power factor c
58
32
Float
62
32
Float
66
32
Float
70
32
Float
Total bytes: 74
5.3.20
DS205
Via data record DS205, the master can read out and set all energy counters in Double Float
format.
Table 5- 26
Byte
48
Format
Description
32
Struct
Header
32
Unsigned long
Reserved
16
Unsigned short
Reserved
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Parameter assignment/Addressing
5.3 Acyclic data traffic
Byte
Number of
bits
Format
Description
10
64
Double Float
18
64
Double Float
26
64
Double Float
34
64
Double Float
42
64
Double Float
50
64
Double Float
58
64
Double Float
66
64
Double Float
74
64
Double Float
82
64
Double Float
Total bytes: 90
1) 0xFFFFFFFFFFFFFFFF means: No action. Every other value is accepted.
See also
Reading data records DS51 and DS205 (Page 56)
5.3.21
DS206
Data record DS206 contains the average power values over a demand period.
Table 5- 27
Byte
Number of
bits
Format
Description
32
Struct
Header
32
Unsigned long
Reserved
16
Unsigned short
Reserved
10
32
Float
14
32
Float
18
32
Float
22
32
Float
26
32
Float
30
32
Float
34
32
Float
38
32
Float
42
32
Unsigned long
46
32
Unsigned long
Total bytes: 50
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
49
Parameter assignment/Addressing
5.3 Acyclic data traffic
5.3.22
You address slot number 0 with the diagnostics address you have defined in the properties
of the DP slave in the HW Config, for example.
Table 5- 28
Byte
Number of bits
Format
Standard
Description
Unsigned char
0x08
Unsigned char
0x00
Reserved
16
Unsigned short
65000
80
10 bytes
0x00
I&M header
16
Unsigned short
42
160
Char 20
36
128
Char 16
52
16
Unsigned short
54
32
1*char
3*unsigned short
58
16
Unsigned short
0x0000
60
16
Unsigned short
F600
IM0 profile ID
62
16
Unsigned short
0x00
64
16
Unsigned short
0x0101
66
16
Unsigned short
001E
Total bytes: 68
1) Standard: 42. "42" stands for Siemens AG.
50
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Parameter assignment/Addressing
5.3 Acyclic data traffic
Table 5- 29
Structure of data record DS255, IM1 data - read access and write access
Byte
Number of bits
Format
Standard
Description
Unsigned char
0x08
Unsigned char
0x00
Reserved
16
Unsigned short
65001
80
10 bytes
0x00
I&M header
14
256
Char 32
20h
46
176
Char 22
20h
Total bytes: 68
Table 5- 30
Structure of data record DS255, IM2 data - read access and write access
Byte
Number of bits
Format
Standard
Description
Unsigned char
0x08
Unsigned char
0x00
Reserved
16
Unsigned short
65002
80
10 bytes
0x00
I&M header
14
128
Char 16
"YYY-MM-DD"
30
304
Char 38
00h
Reserved
Total bytes: 68
Table 5- 31
Structure of data record DS255, IM3 data - read access and write access
Byte
Number of bits
Format
Standard
Description
Unsigned char
0x08
Unsigned char
0x00
Reserved
16
Unsigned short
65003
80
10 bytes
0x00
I&M header
432
Char 54
20h
IM3 comment
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
51
Parameter assignment/Addressing
5.3 Acyclic data traffic
Table 5- 32
Structure of data record DS255, IM4 data - read access and write access
Byte
Number of bits
Format
Standard
Description
Unsigned char
0x08
Unsigned char
0x00
Reserved
16
Unsigned short
65004
80
10 bytes
0x00
I&M header
432
Char 54
00h
IM4 signature
5.3.23
Addressing parameter
When addressing data, PROFIBUS assumes that the slaves have a modular physical design
or that they are structured internally into function units or "modules".
,QGH[
,QGH[
,QGH[
,QGH[
,QGH[
6ORWb
([SDQVLRQ
PRGXOH
6ORWWR\
6ORW[
IXWKHU
H[SDQVLRQ
PRGXOH
30'
Maximum number of slots for the relevant SENTRON PAC Power Monitoring Device
Figure 5-3
See also
Reading data records DS51 and DS205 (Page 56)
52
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Parameter assignment/Addressing
5.4 Reading and writing data record with SIMATIC S7
5.4
SIMATIC S7
The SIMATIC S7 offers the following system function blocks:
SFB 52 "RDREC" (read record): Read a data record
SFB 53 "WRREC" (write record): Write data record
SFB 54 "RALRM" (read alarm): Read alarm
The description, functional principle, and use of the system function blocks is contained in
the manuals for the SIMATIC and the STEP 7 Online Help.
5.5
PROFIBUS DP master
Other PROFIBUS DP masters offer the following functions from the PROFIBUS Guideline
"Communication and Proxy Function Blocks according to IEC 61131-3":
Function block "RDREC" (read record): Read a data record
Function block "WRREC" (write record): Write data record
Function block "RALRM" (read alarm): Read alarms
5.6
Protocol sequence for read data record and write data record
Fundamentals
The class 1 master has send authorization and corresponds cyclically over the MS0 channel
consecutively with slave 1, slave 2 etc. by means of request and response. Following this, it
passes the send authorization to the class 2 master. The class 2 master can establish an
acyclic connection with any slave in the remaining time of the programmed cycle, and
exchange data with this slave over the MS2 channel. At the end of the current cycle time, it
returns the send authorization to the class 1 master. The class 1 master can exchange
acyclic data with slaves in a similar way over the MS1 channel.
Different data records have been defined for the SENTRON PAC Power Monitoring Device.
Each data record has a maximum length of 200 bytes. This supports the routing property of
the acyclic data.
The DPV1 protocol is used for acyclic data exchange between a PROFIBUS DP class 1
master or a class 2 master and the slave. The DPV1 protocol is downward compatible. This
allows you to connect PROFIBUS DP-V0 and PROFIBUS DP-V1 devices on one segment.
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
53
Parameter assignment/Addressing
5.6 Protocol sequence for read data record and write data record
With a class 2 master, you can establish communication with slaves
that have not been configured and parameterized by this master
that still have a connection to a class 1 master.
Figure 5-4
6ORW
6ORW
6ORW
/HQJWK
'DWD
,QGH[
/HQJWK
'DWD
)XQFWLRQ
QXPEHU
Figure 5-7
,QGH[
)XQFWLRQ
QXPEHU
Figure 5-6
/HQJWK
)XQFWLRQ
QXPEHU
Figure 5-5
,QGH[
6ORW
,QGH[
/HQJWK
Figure 5-8
6ORW
,QWHUUXSWW\SH
6SHFLILHU
)XQFWLRQQXPEHU
Function number
(UURU'HFRGH
(UURU&RGHb
(UURU&RGHb
If an error occurs:
Boolean OR operation of the function number from DPV1 with 0x80
= B#16#DE with read data record
= B#16#DF with write data record
Error Decode
Error detection
Error Code 2
Figure 5-9
54
Error Code 1
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Parameter assignment/Addressing
5.6 Protocol sequence for read data record and write data record
Note
The structures of the error message frame and the error codes comply with the PROFIBUS
standard.
You can find further information in IEC 61158 and the "PROFIBUS Profile Guidelines Part 1:
Identification & Maintenance Functions".
Function numbers
Table 5- 33
Function number
Meaning
0x48
Idle
0x51
Data Transport
0x56
0x57
Initiate
0x58
Abort
0x5C
0x5E
Read
0x5F
Write
Causes
Table 5- 34
Error Code 1
Error
Meaning
0xA0
Reading error
0xA1
Write error
0xA9
0xB0
Invalid index
0xB1
0xB2
Invalid slot
Occurs when invalid slot specified for Read and Write DSx
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
55
Parameter assignment/Addressing
5.7 Reading data records DS51 and DS205
Error Code 1
Error
Meaning
0xB5
Status conflict
0xC2
See also
Addressing parameter (Page 52)
Reading data records DS51 and DS205 (Page 56)
5.7
56
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Parameter assignment/Addressing
5.7 Reading data records DS51 and DS205
Procedure
352),%86PDVWHU
5HTXLUHPHQW
,QGH[GDWD
5HTXLUHPHQW
'DWD
%XV
3$&352),%86'3
H[SDQVLRQPRGXOH
:ULWH'6UHTXHVW
ZLWKLQGH[LQJZLWKE\WHVRIGDWD
5HTXLUHPHQW
:ULWHUHSRQVH
,QGH[HG
GDWD
6(175213$&
5HDG'6UHTXHVW
5HDG'6UHVSRQVH
ZLWKHUURUFRGH[&
5HDG'6UHTXHVW
5HDG'6UHVSRQVH
ZLWKHUURUFRGH[&
5HDG'6UHTXHVW
5HVSRQVH
'DWD
Figure 5-10
5HVSRQVH
,QGH[HG
GDWD
5HDG'6UHVSRQVH
ZLWKLQGH[HGGDWD
The DP master indexes the data with the Write DSxx request. Indexing is carried out with a
4-byte-long header whose content is irrelevant. After indexing the Read DS request, only this
DP master is permitted to fetch the data. If another master attempts to fetch this data, its
Read DS request will be rejected with error code 0xB5.
All subsequent Read DS requests of this DP master, and the indexing attempts of all other
DP masters, will also be rejected with the error code 0xC2 until the DP master fetches the
requested data.
Each indexed Read DS request has a maximum life of approximately 10 s. Following this,
the PAC PROFIBUS DP expansion module is ready for indexing again.
The PAC PROFIBUS DP expansion module checks the formal correctness of the Write
request for:
Message frame length: e.g. 4 bytes at indexing
Index
If an error occurs, the request is rejected and an error code is sent
See also
Protocol sequence for read data record and write data record (Page 53)
Addressing parameter (Page 52)
Diagnostic interrupt (Page 76)
Device-specific diagnostic messages (Page 81)
Basic type 1 and basic type 2 DS51 (Page 34)
Energy counter DS205 (Page 48)
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
57
Parameter assignment/Addressing
5.8 Data formats
5.8
Data formats
5.8.1
Energy counters
Name
Format
Value range
Float
Overflow 1.0e+12
Float
Overflow 1.0e+12
Float
Overflow 1.0e+12
Float
Overflow 1.0e+12
Float
Overflow 1.0e+12
Float
Overflow 1.0e+12
Float
Overflow 1.0e+12
Float
Overflow 1.0e+12
Float
Overflow 1.0e+12
Float
Overflow 1.0e+12
In the GSD file, the measured variables in Double Float format are indicated by (D), and the
measured variables in Float format by (F).
Note
Resetting the energy counters
If you carry out calculations with these measured variables in Float format, e.g. to calculate
the daily or monthly consumption, inaccuracies arise in the case of values with more than 7
representable digits. You can ensure the accuracy of the measured values by resetting the
energy counters before the counter value exceeds 7 digits.
See also
Measured variables (Page 23)
5.8.2
Limits
The SENTRON PAC3200 offers limit values. These limit values are available via the
PROFIBUS in the "Limit Violations" measured variable.
58
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Parameter assignment/Addressing
5.8 Data formats
Name
Byte
Bit
Format
Value range
Access
Bit
0, 1
Limit value 0
Bit
0, 1
Limit value 1
Bit
0, 1
Limit value 2
Bit
0, 1
Limit value 3
Bit
0, 1
Limit value 4
Bit
0, 1
Limit value 5
Bit
0, 1
Note
Limit violations can trigger diagnostic interrupts.
See also
Structure of the device-specific diagnostics (Page 79)
Device-specific diagnostic messages (Page 81)
5.8.3
Input statuses and output statuses of the SENTRON PAC Power Monitoring Device
The following are available via the PROFIBUS:
The input status of the internal input of the SENTRON PACxxxx Power Monitoring Device
in the measured variable "Digital inputs status"
The output status of the internal output of the SENTRON PACxxxx Power Monitoring
Device in the measured variable "Digital outputs status"
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
59
Parameter assignment/Addressing
5.8 Data formats
Table 5- 37
Scheme: Input statuses and output statuses of the SENTRON PAC Power Monitoring Device
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Byte 0
MSB
Byte 1
Byte 2
Byte 3
DI / DO 0.11) 2)
1) = Read access
2) "0" = OFF; "1" = ON1)
Abbreviation
Meaning
LSB
MSB
See also
Status of the output signals DS68 (Page 35)
Status of the DS69 input signals (Page 35)
60
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Configuring
6.1
Default settings
Factory settings
Parameter
6.2
Value
Address
126
Automatic recognition
Automatic recognition
Language
Configuration scenarios
In the SIMATIC environment you can configure the SENTRON PAC Power Monitoring
Device and the PAC PROFIBUS DP expansion module in the following way.
Integration of the SENTRON PAC Power Monitoring Device via PROFIBUS using
STEP 7 and the device-specific GSD file
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
61
Configuring
6.3 Changing the address
Configuring the integration of PROFIBUS using STEP 7 and the GSD file
*6'3$&[[[[
6,0$7,&67(3
352),%86
6(175213$&
Figure 6-1
Configuring the integration of PROFIBUS using STEP 7 and the GSD file
Note
Configuration with other tools
You can also use configuration tools from other manufacturers for the configuration.
6.3
62
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Configuring
6.4 Configuring by means of the GSD file
Change the address of each device before you begin transferring data. You can change the
address:
Via the menu of the SENTRON PAC Power Monitoring Device
With SENTRON powerconfig via the Ethernet interface
With the PROFIBUS configuring software, e.g., STEP 7
Via the PROFIBUS interface by means of a class 2 master
CAUTION
Address change on device immediately valid
When you change the address of the PROFIBUS DP slave on the SENTRON PAC, the
PAC PROFIBUS DP expansion module is automatically restarted as soon as you quit
the menu. The new address is then active. Reconfigure the PROFIBUS DP master with
the new address. Communication is interrupted until this change takes effect.
6.4
Places
Meaning
1 ... 2
3 ... 4
Version of the GSD file, e.g. "01" for the first version
5 ... 8
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
63
Configuring
6.4 Configuring by means of the GSD file
Language
GSE
English (ANSI)
GSG
German
GSF
French
GSI
Italian
GSP
Portuguese
GSS
Spanish
GSD
Assignment of the GSD file to the device and firmware version of the expansion module
Table 6- 4
Meaning
SIEM8163.GSx
SI018163.GSx
SI018173.GSx
Note
Latest version of the GSD file
You can find the latest version of the GSD file in each case on the Internet Online service
and support (http://www.siemens.com/automation/service&support).
64
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Configuring
6.4 Configuring by means of the GSD file
Sequence
1
Screen
Start HW Config in
the SIMATIC
Manager.
Confirm in the
"Options" > "Install
GSD File" menu.
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
65
Configuring
6.4 Configuring by means of the GSD file
Sequence
3
Screen
66
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Configuring
6.4 Configuring by means of the GSD file
Sequence
4
Screen
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
67
Configuring
6.4 Configuring by means of the GSD file
Sequence
5
Screen
Select the
SENTRON PAC
Power Monitoring
Device in the
hardware tree:
"PROFIBUS DP" >
"Additional
Devices" >
"SENTRON" >
"PACxxxx"
68
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Configuring
6.4 Configuring by means of the GSD file
Sequence
7
Screen
Drag the
SENTRON
PACXXXX Power
Monitoring Device
from the hardware
tree to the
PROFIBUS DP
master system 1.
Set the address of
the PAC
PROFIBUS DP
expansion module.
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
69
Configuring
6.5 Information and settings on the SENTRON PAC Power Monitoring Device
NOTICE
Do not use the universal module
Because of the predefined data types and the available measured values, the use of the
STEP 7 universal module in the configuration is not supported.
See also
Default settings (Page 61)
Latest information and correction sheet (Page 10)
6.5
Figure 6-2
You will find the following information listed in the upper half of the screen form:
The order number
The serial number of the PAC PROFIBUS DP expansion module
The firmware version of the PAC PROFIBUS DP expansion module
In the "DIAG" field, you can see the communication status of the PAC PROFIBUS DP
expansion module:
70
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Configuring
6.5 Information and settings on the SENTRON PAC Power Monitoring Device
Table 6- 6
Status
Meaning
BAUD_SRCH
WAIT_PRM
PRM_FAULT
WAIT_CFG
CFG_FAULT
DATA_EXCH
CON_MC2
"PROFIBUS ADDRESS":
Each expansion module requires a unique address. The address 126 is the default for
startup purposes. Change this address!
Valid address area:
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
1 ... 126
71
Configuring
6.5 Information and settings on the SENTRON PAC Power Monitoring Device
72
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Cleaning
Description
The PAC PROFIBUS DP expansion module is maintenance-free.
NOTICE
Damage due to detergents
Detergents can damage the device. Do not use detergents.
NOTICE
Faulty connector
Be careful not to bend the pins of the connector. Bent pins can destroy the connector.
1. Use only a dry, lint-free, antistatic cloth to clean the housing.
2. Clean the pins carefully using a brush.
7.2
Repair
Procedure
NOTICE
Loss of certification and warranty
If you open the module, the module certification will be lost and the Siemens warranty will
be invalidated. Only the manufacturer is permitted to carry out repairs on the module.
Return faulty or damaged modules to Siemens for repair or replacement.
If the module is faulty or damaged, proceed as follows:
1. Discharge yourself.
2. Remove the module.
3. Pack the module in a suitable manner to prevent it from being damaged during transport.
4. Return the module to Siemens. You can obtain the address from:
Your Siemens sales partner
Technical Assistance
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
73
See also
Latest information and correction sheet (Page 10)
Electrostatic sensitive devices (ESD) (Page 97)
7.3
Disposal
7.4
Firmware updates
SENTRON powerconfig
Note
Performing a firmware update
Before updating the firmware, consult Technical Assistance to confirm that it is necessary.
Update the firmware only if absolutely necessary.
You update the firmware with the configuration software SENTRON powerconfig . Additional
information on updating the firmware can be found in the online help for
SENTRON powerconfig.
See also
Power failure during firmware update (Page 85)
74
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Process interrupts
Byte 0
Sign-Len
Byte 1
Interrupt
type1)
Byte 2
Byte 3
Byte 4 to byte x
Slot2)
Specifier3)
Event messages4)
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
75
8.2
Diagnostics concept
8.2.1
Diagnostic interrupt
Diagnostic information
The following PROFIBUS DP diagnostic information is available:
1. Slave diagnostics in accordance with standard
2. Enhanced diagnostics
Device diagnostics with diagnostic interrupts
The PAC PROFIBUS DP expansion module reports device diagnostics to the master
in the form of interrupts. The master must acknowledge the interrupts.
Device faults or parameter errors are interrupt sources for diagnostic interrupts.
In the SIMATIC environment, SFB 54 reads the diagnostic interrupt messages.
Structure of the diagnostic interrupts of the SENTRON PAC Power Monitoring Device - slave diagnostics
To standard
Byte 0
Byte 1
Byte 2
Byte 3
Device status 1 to 3
Byte 4
Byte 5
Low byte
63
Manufacturer's
ID2)
1) This is the address of the master that has parameterized the slave and that has read and write access to the slave. If
the value here is FFH, the slave has not been parameterized.
2) The manufacturer's ID identifies the slave model, e.g., "8163H" for the SENTRON PAC3200.
Table 8- 3
Structure of the diagnostic interrupts of the SENTRON PAC Power Monitoring Device - device diagnostics
To standard
Byte 6
Sign-Len
Length of device
diagnostics in
bytes
Manufacturer-specific
Byte 7
Byte 8
Byte 9
Slot2)
Specifier3)
Status
type1)
Byte 10
Byte 11
Byte 12
Device
diagnostics data
Yes/No
Communicatio Violation of
n faults
the limits
Byte 13
Invalid values
and invalid
settings
76
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Structure of the diagnostic interrupts of the SENTRON PAC Power Monitoring Device - interrupt messages
To standard
Manufacturer-specific
Byte 14
Byte 15
Byte 16
Byte 17
Byte 18
Byte 19
Byte 20
Sign-Len
Interrupt
type1)
Slot2)
Specifier3)
Communication faults
Violation of the
limits
Length of the
tag in bytes
Table 8- 5
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
No further differentiation
No additional
acknowledgement required
Additional
acknowledgement required.
0 ... 63
See also
Structure of the device-specific diagnostics (Page 79)
Reading data records DS51 and DS205 (Page 56)
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
77
8.2.2
Status 1
Table 8- 6
78
Bit
Status
Meaning
Cause/remedy
Check:
Is the correct PROFIBUS address set
on the slave?
Are the bus connectors connected?
Has voltage been applied to the
SENTRON PAC Power Monitoring
Device?
The slave type does not match Match the actual configuration to the
the software configuration.
planned configuration.
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Status 2
Table 8- 7
Bit
Status
Meaning
Cause/remedy
Parameters have to be
reassigned to the slave.
Check:
The parameter assignment
The configuration
Whether the device-specific GSD file
and the Power Monitoring Device go
together.
There is a diagnostic
message.
Response monitoring is
enabled for this slave.
Status 3
Table 8- 8
8.2.3
Bit
Status
Meaning
0 ... 6
There are more device diagnostic messages than can be displayed in the
diagnostic message frame.
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
79
Structure
Table 8- 9
Bit
Status
Meaning
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Table 8- 10
Communication faults: Structure of the device diagnostics in byte 11 and the interrupt
message in byte 18
Bit
Status
Message
Reserved
Reserved
Table 8- 11
80
Violation of the limits: Structure of the device diagnostics in byte 12 and the interrupt
message in byte 19
Bit
Status
Message
Limit violations
Reserved
Reserved
Reserved
Reserved
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Invalid values and invalid settings: Structure of the device diagnostics in byte 13 and the
interrupt message in byte 20
Bit
Status
Message
See also
Device-specific diagnostic messages (Page 81)
Diagnostic interrupt (Page 76)
Limits (Page 58)
8.2.4
Message
Meaning
Data invalid
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Remedy
81
Meaning
Remedy
Check:
The voltage converter ratio
The setting of the rated voltage
If these settings are correct and the
error persists, there is a safety
problem. Switch the device off.
Check whether:
The number of parameterized
pulses is too low.
The parameterized pulse is too
long.
If necessary, adjust the relevant
settings.
Limit violations
Check:
The settings on the SENTRON PAC
The values
Check:
The settings on the SENTRON PAC
The values
Check:
The settings on the SENTRON PAC
The values
Check:
The settings on the SENTRON PAC
The values
Check:
The offset
The number of registers
82
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Meaning
Remedy
Check:
The offset
The number of registers
The parameter value
Check:
The values.
See also
Structure of the device-specific diagnostics (Page 79)
Limits (Page 58)
8.3
Diagnostics LED
Description
The diagnostics LED indicates the communication status.
Table 8- 14
Color
Status
Description
Measures
Green
Off
Green
Static ON
Green
Flashing
Red
Static ON
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
83
Status
Description
Measures
Red
Flashing
Orange
Static ON
Flashing
Flashing
1) A parallel connection to a class 2 master has no effect on the green status of the LED.
2) This is only the case if there is no connection to the class 1 master.
84
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Troubleshooting/FAQs
9.1
See also
Firmware updates (Page 74)
Latest information and correction sheet (Page 10)
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
85
Troubleshooting/FAQs
9.1 Power failure during firmware update
86
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
10
Technical data
10.1
Standards
Description
Table 10- 1
Standard
Title
IEC 61158-2:2004
"Digital data communications for measurement and control - Fieldbus for use in industrial
control systems - Part 2: Physical layer specification and service definition"
IEC 61158-3:2003
"Digital data communications for measurement and control - Fieldbus for use in industrial
control systems - Part 3: Data link service definition"
IEC 61158-4:2004
"Digital data communications for measurement and control - Fieldbus for use in industrial
control systems - Part 4: Data link protocol specification"
IEC 61158-5:2004
"Digital data communications for measurement and control - Fieldbus for use in industrial
control systems - Part 5: Application layer service definition"
IEC 61158-6:2004
"Digital data communications for measurement and control - Fieldbus for use in industrial
control systems - Part 6: Application layer protocol specification"
IEC 61784-1:2004
PROFIBUS Standard
Note
Other standards
In addition to the above-mentioned standards, those listed in the "SENTRON PACxxxx"
manual also apply.
10.2
Technical data
Mechanical data
Table 10- 2
63 mm x 43 mm x 22 mm
69 mm x 43 mm x 22 mm
Mounting position
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
87
Technical data
10.2 Technical data
Values
Housing design
Tolerances
Weight
45 g
14-pin connector
Length of cable
Power supply
Cooling
Flammability class
V-0
Electrical data
Table 10- 3
TIA/EIA-485-A1)
ANSI
Protective circuit for
PROFIBUS interface, galvanically isolated from
the device
5V5%
10 mA, maximum
In expansion module
Insulating voltage
Max. 500 V
1) Formerly RS 485
88
Values
IP20
2 in accordance with
IEC 61010-1:2001
Recycling symbol
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Technical data
10.3 Communication interface
Note
Other technical data
The other mechanical and electrical data and ambient and environmental conditions are
identical to those for the SENTRON PAC Power Monitoring Device. You can find more
information in the operating instructions and manual for the SENTRON PAC Power
Monitoring Device.
See also
Standards (Page 87)
10.3
Communication interface
Technical data
Table 10- 5
Connector
1 to 126 1)
1) Each device on the bus must have a unique address. Address 126 is only used for commissioning
purposes. It must not be used for data communication.
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
89
Technical data
10.3 Communication interface
Figure 10-1
Table 10- 6
Pin
Designation
Meaning
Range
NC
Not assigned
NC
Not assigned
RxD/TxD-P
Receive/transmit data-P
ANSI TIA/EIA-485-A1)
Control-P (RTS)
Control signal
TTL
DGND
GND
VP
5 VEXT / 10 mA
NC
Not assigned
RxD/TxD-N
Receive/transmit data-N
NC
Not assigned
ANSI TIA/EIA-485-A1)
1) Previously RS 485
2) Only for the bus terminating resistors
90
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Technical data
10.4 Labeling
10.4
Labeling
Description
The graphic below shows the positioning of the label on the housing of the
PAC PROFIBUS DP expansion module.
(1)
Nameplate
Figure 10-2
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
91
Technical data
10.4 Labeling
92
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
11
Dimension sheets
11.1
Dimension sheets
Figure 11-2
Bottom view and top view with sub D socket connector and the dimensions of the pin
contact between the PAC PROFIBUS DP expansion module and the SENTRON PAC
Figure 11-1
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
93
Dimension sheets
11.1 Dimension sheets
94
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Appendix
Correction sheet
Have you noticed any errors while reading this manual? If so, please use this form to tell us
about them. We welcome comments and suggestions for improvement.
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
95
Appendix
Fax response
From (please complete):
To
Name
SIEMENS AG
I IA CD MM 3
Company/Department
Address
_________________________________________________________________________________
Fax: +49 (0)9621-80-3337
Manual title:
Table A- 1
96
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
ESD directives
B.1
ESD guidelines
CAUTION
Electrostatic sensitive devices
Electronic modules contain components that can be destroyed by electrostatic discharge.
These modules can be easily destroyed or damaged by improper handling.
You must discharge your body electrostatically immediately before touching an
electronic component. To do this, touch a conductive, grounded object, e.g., a bare
metal part of a switch cabinet or the water pipe.
Always hold the component by the plastic enclosure.
Electronic modules should not be brought into contact with electrically insulating
materials such as plastic film, plastic parts, insulating table supports or clothing made of
synthetic fibers.
Always place electrostatic sensitive devices on conductive bases.
Always store and transport electronic modules or components in ESD-safe conductive
packaging, e.g. metallized plastic or metal containers. Leave the component in its
packaging until installation.
CAUTION
Storage and transport
If you have to store or transport the component in non-conductive packaging, you must first
pack the component in ESD-safe, conductive material, e.g., conductive foam rubber, ESD
bag.
The diagrams below illustrate the required ESD protective measures for electrostatic
sensitive devices.
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
97
ESD directives
B.1 Electrostatic sensitive devices (ESD)
E
H
H
I
F
I
F
(1)
ESD seat
(2)
(3)
I
F
Protective measures
98
Conductive floor
ESD table
ESD footwear
ESD smock
ESD bracelet
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
List of abbreviations
C.1
Abbreviations
Overview
Table C- 1
Meaning of abbreviations
Abbreviation
Meaning
ANSI
CAN
CE
Communauts Europennes
CEI
CISPR
CRC
CSA
DIN
DP
Distributed I/Os
DR
Data record
ESD
EIA
EMC
Electromagnetic compatibility
EN
European Standard
EU
European Union
FCC
GSD
HT
High Tariff
HW Config
I&M
ID
Identification number
IEC
IEEE
IP
International Protection
ISM
ISO
LED
LSB
LT
Low Tariff
MSB
MS0
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
99
List of abbreviations
C.1 Abbreviations
100
Abbreviation
Meaning
MS1
MS2
NAFTA
NEMA
PAC
PMD
PI
RALRM
Read alarm
RDREC
Read record
RET_VAL
RMS
RS
SFB
SFC
System function
TIA
THD
THD-R
Relative THD
UL
VDE
RLO
WRREC
Write record
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Glossary
Baud rate
The baud rate is the rate of data transmission. It indicates the number of bits transferred in
one second. All nodes on a PROFIBUS subnet must support the selected baud rate.
Bus
Shared transmission path over which all devices on the communication bus are connected. It
has two defined ends. In the case of PROFIBUS, the bus is a twisted pair or optical fiber
cable.
Bus system
All nodes physically connected to a bus cable form a bus system.
Class 1 DP master
The class 1 DP master handles user data traffic with the DP slaves assigned to it.
Class 2 DP master
The DP master provides services such as reading the input data, output data, diagnostics,
and control bytes.
Cycle time
The cycle time of a PROFIBUS segment is made up of the number of nodes. It is set, for
example, in STEP 7 in the HW Config.
Cyclic execution
The DP master accesses the DP slaves regularly. In doing so, the DP master reads the input
data of the slaves and forwards output data to the slaves.
Diagnostics
The detection, localization, visualization and further evaluation of errors, disturbances and
messages.
Diagnostics offers monitoring functions that automatically run while the system is in
operation. This reduces startup times and standstill times. Plant availability increases.
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
101
Glossary
Equipotential bonding
Electrical connection (equipotential bonding conductor) which brings the bodies of electronic
equipment and foreign conductive bodies to an equal or approximately equal potential. This
prevents disruptive or dangerous voltages between these bodies.
Master
When a master is in possession of the token, it can send data to other nodes and request
data from other nodes.
Nodes
Device which can send, receive or amplify data on the bus, e.g., PROFIBUS DP master,
PROFIBUS DP slave.
PROFIBUS
PROCESS FIELDBUS, a European process and fieldbus standard defined in the PROFIBUS
standard EN 50170, Volume 2 PROFIBUS. This standard specifies the operational, electrical
and mechanical properties of a bit-serial field bus system.
PROFIBUS is a bus system that connects PROFIBUS-compatible automation systems and
field devices together at the cell level and field level.
PROFIBUS address
Every device on the communication bus receives a unique PROFIBUS address. The device
on the communication bus is identified on PROFIBUS with this address.
The factory address setting for the PAC PROFIBUS DP expansion module is address 126.
Addresses 1 to 126 are permissible.
Slave
A slave can only exchange data after being requested to by the master.
102
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Index
"
"DIAG" field, 70
"RALRM" function block, 53
"RDREC" function block, 53
"WRREC" function block, 53
A
Active energy export, 58
Active energy import, 58
Active energy import tariff 1, 26
Acyclic data traffic, 31, 52
Acyclic data transfer, 14
Address, 61, 62
Change, 63
Address area
Supported, 89
Valid, 71
Ambient conditions, 88
ANSI TIA/EIA 485 A protective circuit, 88
Apparent energy, 58
Apply supply voltage, 17
Area of application, 13
Assembly, 17, 18
Average power values over a demand period, 32, 49
B
Basic type, 24
Basic type 1, 24, 25, 26, 30, 32, 34
Basic type 2, 24, 26, 32, 34
Length of message, 26
Basic type 3, 24, 26, 30
Baud rate, 14, 24, 61, 71, 89
Block libraries for SIMATIC, 23, 31
Bottom view, 93
Bus connector, 78
Bus fault, 83
Bus installation, 78
Bus traffic, 14
C
CALL mechanism, 56
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
D
Data exchange
Cyclic, 83
Data invalid, 81
Data traffic
103
Index
Acyclic, 31
Cyclic, 24, 28
Data volume, 24
Default settings, 61
Degree of protection, 88
Detergents
Damage, 73
Device diagnostic interrupts, 81
Device diagnostics, 29, 30, 76, 78, 79
Structure, 80
Device diagnostics data, 80
Device status, 29
Diagnostic information, 29, 39, 76
Diagnostic interrupts, 59, 76
Diagnostic message frame, 79
Diagnostic messages, 81
Diagnostics address, 50
Diagnostics LED, 83
Digital data communications for measurement and
control, 87
Digital inputs status, 35, 59
Digital outputs status, 35, 59
Dimensions of housing, 87
Discharge, 20, 73, 97
Disposal, 74
Double Float format, 58
DPV1 data record, 31
DPV1-enabled master, 31
E
Edge transition, 30
Electrical data, 88
Electrical isolation, 88
Electrostatic sensitive devices, 97
Endangering of operation, 19
Energy counter, 48
Energy counters, 32, 58
Reset, 30
Energy values, 23
Enhanced diagnostics, 76
Environmental conditions, 88
Error Code 1, 55
Error message frame, 54
ESD bracelet, 98
ESD footwear, 98
ESD guidelines, 97
ESD Guidelines, 18
ESD protective measures, 97
ESD seat, 98
ESD smock, 98
ESD standing position, 98
104
ESD table, 98
F
Factory settings, 61
Fail-safe power supply, 85
Fault display, 83
Features, 14
Firmware incompatible, 81
Firmware update, 84, 85
Duration, 85
Firmware updates, 74
Firmware version of the expansion module, 70
Flammability class, 88
Float format, 58
Front view, 93
Functions with limited support, 15
G
Galvanic isolation, 88
GSD file, 14, 17, 78, 79
Language, 64
GSDF file, 24, 63
Guide pin, 20
H
Hardware fault, 84
High tariff, 30
Housing design, 88
Humidity, 11
HW Config, 65
I
I&M data, 50
I&M data records, 32, 50
I&M device identification, 32
IM0 data, 50
IM1 data, 51
IM2 data, 51
IM3 data, 51
IM4 data, 52
Index, 52
Index 255, 50
Initialization phase, 78
Input data, 25, 26, 27
Input signals, 35
Installation location, 17
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
Index
Insulating voltage
maximum, 88
Intended use, 13
Interrupt message, 77, 81
Interrupt type, 77
Invalid settings, 81, 82
Invalid values, 81
L
Labeling, 91
Language, 61
LED, 15, 83
Length of cable, 88
Level sensitive, 30
Limit value settings, 32
Limit values, 59
Limit violations, 82
Line frequency, 32
Line frequency values, 38
Loss of warranty, 73
Low tariff, 30
M
Manufacturer's ID, 76
Master, 76, 78
Class 1, 54, 71, 83
Class 2, 31, 71, 83
Master-slave principle, 14
Maximum pulse rate exceeded, 82
Maximum values
Reset, 30
Maximum/minimum values, 23
Measured variables, 23, 24
free choice, 28
Mechanical data, 87
Message frame, 24
Message frame formats, 54
Minimum values
Reset, 30
Modular system design, 52
Moisture, 11
Mounting position, 87
N
Nameplate, 91
Number of nodes, 24
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05
O
Order number, 70
Orientation aids, 9
Output data, 25
Output not remote operated, 82
Output signals, 35
P
Packaging, 18
Parameter assignment, 84
Parameter assignment error, 84
Parameterize, 17
Parameters for setting the limit values, 44
Perform checks, 18
Permissible degree of pollution, 88
Pin, 19, 73
PIN assignment, 90
Power failure, 85
Power measured values, 32, 40
Power supply, 88
Fail-safe, 85
Power values, 32, 37, 48
Process interrupts
Structure, 75
PROFIBUS adaptor plug, 21
PROFIBUS address, 17, 71, 78, 83
PROFIBUS address of the master, 76
PROFIBUS connection, 90
PROFIBUS DP master, 63
PROFIBUS DP Master, 14, 17
PROFIBUS DP slave, 14, 63
PROFIBUS functions, 16
PROFIBUS ID number, 63
PROFIBUS network, 17
Pulse rate, 29
Q
Quantity structure, 24
R
Reactive energy export, 58
Reactive energy import, 58
Recycling, 74
Recycling symbol, 88
Repair, 73
Required basic knowledge, 9
Response monitoring, 14, 79
105
Index
S
S7-V1 system diagnostics, 33
Safe isolation from supply, 20
SENTRON PAC events, 75
Serial number, 70
Setting parameters, 42
SFB 52 "RDREC", 53
SFB 53 "WRREC", 53
SFB 54 "RALRM", 53
Side view, 93
SIMATIC environment, 61
SIMATIC Manager, 65
Slave, 76, 78, 84
Slave diagnostics in accordance with standard, 76
Slot, 76
Slot number, 52
Slot number 0, 50
Slot number 1, 50
Specifier, 76, 77
station address
Incorrect, 71
Status 1, 78
Status 2, 79
Status 3, 79
Status and diagnostics, 32
Status display, 83
Status information, 23, 25, 28, 29, 39
Status of the input signals, 32
Status of the output signals, 32
Status type, 76
STEP 7, 81
Storage, 97
Structure, 15
Structure of the device diagnostics, 80
Structure of the process interrupts, 75
Sub D connector, 19, 20
Sub D socket, 15, 20, 21, 87, 89, 93
Support
Technical, 73
Switch outputs, 30
Switching tariff, 30
System function blocks, 53
System function blocks (SFB53/54), 31
System status, 29
Technical support, 73
Temperature compensation, 18
THD values, 32, 38
Tightening torque, 20
Tolerances, 88
Tools, 18
Top view, 93
Total active power, 25
Total power factor, 26
Transport, 97
U
Universal counter, 32, 42
Unpacking, 18
Update firmware, 81
V
Valid address area, 71
Ventilation slots, 15, 19, 21, 88
Violation of the limits, 80
Voltage measured values, 32, 40
Voltage out of range, 82
Voltage ph-ph, 26
Voltage terminals, 20
Voltage values, 32, 36, 47
W
Weight, 88
Wetness, 11
Working hours counter, 32, 42
Y
Y link, 15
T
Technical data, 89
106
PAC PROFIBUS DP
Manual, 02/2009, A5E01168846B-05