UTXvRNT

Communication protocol IEC 8705103

2010-01-12

Communication protocol IEC8705103.

1. COMMUNICATION PROTOCOL IEC 8705103...................................................................................2


2. CHARACTERISTIC OF PROTOCOL IMPLEMENTATION.....................................................................2
3. LIST OF COMMANDS......................................................................................................................................3
4. SPONTANEOUS EVENTS LIST......................................................................................................................4
5. INFORMATION LIST OF THE FUNCTION GIGENERAL INTERROGATION................................6
6. LIST OF VALUES MEASURED BY THE REGULATORS.........................................................................8
7. DEFINITIONS OF A NEW ASDU FOR THE REGULATORS..................................................................10

Computers & Control

Katowice Porcelanowa 11

UTXvRNT

Communication protocol IEC 8705103

2010-01-12

1. COMMUNICATION PROTOCOL IEC 8705103.


The regulator is equipped with connectors enabling communication both in CCBUS and IEC
8705103 standard protocols.
The option TRANSFER enables selection of transfer speed both for CC-BUS and EC 8705
103 protocols. Also change of an identifier/address of the device is possible.
Selection can be done by pressing (N) key and arrow keys (up/down).
Selection is confirmed by pressing (S) key.
Ability of setting selection for communication protocol can be protected with the password.

2. CHARACTERISTIC OF PROTOCOL IMPLEMENTATION.


Physical layer.
Communication interface RS 232C, RS 485 or C&C current loop is used, there is a possibility
to select transmission speed (from 300 up to 57600 bit/s), a character is composed of 1 start
bit, 8 data bits, 1 even parity control bit and 1 stop bit.
RS 485 interface can operate in 2-wire and 4-wire systems.
RS 485 interface attends only to IEC 8705103 protocol.
Link layer.
Special character <0x5e> is not used, negative acknowledgements are in form of short frames
(frames without data).
Application layer.
Following function has been implemented (according to IEC 8705103 standard
description):
transmission of cyclic data
transmission of spontaneous data
transmission of commands
time synchronisation
Generic service is not implemented, compatibility level pertains in scope of a/m functions.
Field FUNCTION TYPE - FUN in each ASDU unit is FUN = 131.
Cyclic data.
Cyclic data are available by examining the device with link function number 11 (PRM bit=1)
in ASDU 9 form.

Computers & Control

Katowice Porcelanowa 11

UTXvRNT

Communication protocol IEC 8705103

2010-01-12

Spontaneous data.
Spontaneous data are available by setting the ACD bit by the regulator in Control field of
the protocol frame, during examining the device (cyclic data reading) with link function
number 10 (PRM bit=1).
Spontaneous data are buffered, however these data can be overwritten, resulting in
information loss. That's why it is important to examine frequently the device concerning the
spontaneous data.
Transmission of commands.
Transmission of commands is available by sending ASDU20, ASDU 41, ASDU 42 units to
the device.
Time synchronisation.
Time synchronisation is available by sending ASDU 6 unit to the device. Global or local
addressing is possible. Synchronisation frame may be confirmed in case of sending it with a
code of link function number 3 (send-confirm).

3. LIST OF COMMANDS.
Setting type set/reset:
ASDU

INF

DESCRIPTION

20

40

20

41

20
20
20
20

42
43
45
46

20

53

DCO=2 auto mode set


DCO=1 manual mode set
Unblocking of a possibility to set voltage level
LEVEL U for remote control (telemechanics)
DCO=2 (switching on)
DCO=1 (switching off)
Tap raise
Tap lower
Faults clearing
Unblocking of a possibility to set a time T1
for remote control (telemechanics)
DCO=2 (switching on)
DCO=1 (switching off)
Clearing of an IEC event log

DCO value
(double command in
ASDU 20)
DCO=2 (auto)
DCO=1 (man)
DCO=2 (switching on)
DCO=1 (switching off)
DCO=1 or DCO=2
DCO=1 or DCO=2
DCO=1 or DCO=2
DCO=2 (switching on)
DCO=1 (switching off)
DCO=1 or DCO=2

Setting the values float type (definition of ASDU 42 in chapter 6):


ASDU
42

INF
47

DESCRIPTION
Setting of a voltage level - LEVEL U

RANGE
77-130 [%]

Setting the value integer type (definition of ASDU 41 in chapter 6):


ASDU
41

INF
49

DESCRIPTION
Setting of a T1 time - T1

Computers & Control

Katowice Porcelanowa 11

RANGE
0-180 [s]

UTXvRNT

Communication protocol IEC 8705103

2010-01-12

4. SPONTANEOUS EVENTS LIST.


ASDU units for spontaneous data values of INF field.
ASDU
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

INF
23
24
25
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115

DESCRIPTION
Set of parameters number 1 active
Set of parameters number 2 active
Set of parameters number 3 active
Operation failure of the device
Analogue inputs defect
watchdog
Event data buffer overflow
Internal reset
Parameters checksum error
Loss of power supply voltage
Disturbance recorder checksum error
Supervising system communication error
Cancellation from RNT side
Cancellation from PC side
Unrecognised command
IEC buffer overflow
Processor battery failure
Writing performed to 2nd parameters set
Writing performed to 1st parameters set
Disturbance informations exist
Event informations exist

1
1
1
1

117
118
119
120

Compensation type KZ switched on for circuit 2


Compensation type KXR switched on for circuit 2
Compensation type KZ switched on for circuit 1
Compensation type KXR switched on for circuit 1

121

External pick-up of event recorder

1
1
1
1
1
1
1

122
123
124
125
126
127
128

Weekend change of pre-set voltage value


Change of pre-set voltage value, setting 1
Change of pre-set voltage value, setting 2
Change of pre-set voltage value, setting 3
First 24-hour change of pre-set voltage level
Second 24-hour change of pre-set voltage level
Third 24-hour change of pre-set voltage level

1
1
1
1
1

129
130
131
132
134

Early warning before MAX tap position


Early warning before MIN tap position
MAX position reached
MIN position reached
Fast tap change performed

136

Command UP/DN received (protocol)

Computers & Control

Katowice Porcelanowa 11

UTXvRNT

Communication protocol IEC 8705103

ASDU

INF

DESCRIPTION

1
1
1

188
189
190

Undervoltage, circuit 1 (1 U< )


Overvoltage, circuit (1 U> )
Overcurrent, circuit 1 (1 I>)

1
1

206
207

Lowering the tap


Raising the tap

1
1

208
209

Blockade of AVR manual operation mode active


External interlock

1
1
1

211
212
213

Undervoltage, circuit 2 (2 U< )


Overvoltage, circuit 2 (2 U> )
Overcurrent, circuit 2 (2 I> )

1
1

214
215

I1 and I2 currents difference, stage 1


I1 and I2 currents difference, stage 2

1
1
1
1
1
1

216
217
218
219
220
221

U1 and U2 voltages difference, stage 1


U1 and U2 voltages difference, stage 2
U1>U2
U2>U1
Not handled
THD level exceeded

1
1

222
223

RC signal
Motor protection Imoto

1
1
1
1
1
1
1
1

224
225
226
227
228
229
230
231

Motor failure, binary input


Motor run contact error
Motor run time exceeded
Regulation lower error
Regulation raise error
Control contact error
Maximal position error
Minimal position error

1
1
1
1

232
233
234
235

Par_Sel input in high state


Par_Sel input in low state
Parameter set number 1 correct
Parameter set number 2 correct

1
1
1
1
1
1
1

237
238
239
240
241
242
243

Clock error
MinMax UP blockade appeared
MinMax DN blockade appeared
Impermissible regulation level
Regulation principle not selected
blockade loss of voltage in circuit 1
blockade loss of voltage in circuit 2

Computers & Control

Katowice Porcelanowa 11

2010-01-12

UTXvRNT

Communication protocol IEC 8705103

2010-01-12

5. INFORMATION LIST OF THE FUNCTION GIGENERAL


INTERROGATION.
ASDU units for the function General Interrogation,GIvalues of INF field.
ASDU
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

INF
23
24
25
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115

DESCRIPTION
Set of parameters number 1 active
Set of parameters number 2 active
Set of parameters number 3 active
Operation failure of the device
Analogue inputs defect
watchdog
Event data buffer overflow
Internal reset
Parameters checksum error
Loss of power supply voltage
Disturbance recorder checksum error
Supervising system communication error
Cancellation from RNT side
Cancellation from PC side
Unrecognised command
IEC buffer overflow
Processor battery failure
Writing performed to 2nd parameters set
Writing performed to 1st parameters set
Disturbance informations exist
Event informations exist

1
1
1
1

117
118
119
120

Compensation type KZ switched on for circuit 2


Compensation type KXR switched on for circuit 2
Compensation type KZ switched on for circuit 1
Compensation type KXR switched on for circuit 1

121

External pick-up of event recorder

1
1
1
1
1
1
1

122
123
124
125
126
127
128

Weekend change of pre-set voltage value


Change of pre-set voltage value, setting 1
Change of pre-set voltage value, setting 2
Change of pre-set voltage value, setting 3
First 24-hour change of pre-set voltage level
Second 24-hour change of pre-set voltage level
Third 24-hour change of pre-set voltage level

1
1
1
1
1

129
130
131
132
134

Early warning before MAX tap position


Early warning before MIN tap position
MAX position reached
MIN position reached
Fast tap change performed

136

Command UP/DN received (protocol)

Computers & Control

Katowice Porcelanowa 11

UTXvRNT

Communication protocol IEC 8705103

ASDU

INF

DESCRIPTION

1
1
1

188
189
190

Undervoltage, circuit 1 (1 U< )


Overvoltage, circuit (1 U> )
Overcurrent, circuit 1 (1 I>)

1
1

206
207

Lowering the tap


Raising the tap

1
1

208
209

Blockade of AVR manual operation mode active


External interlock

1
1
1

211
212
213

Undervoltage, circuit 2 (2 U< )


Overvoltage, circuit 2 (2 U> )
Overcurrent, circuit 2 (2 I> )

1
1

214
215

I1 and I2 currents difference, stage 1


I1 and I2 currents difference, stage 2

1
1
1
1
1
1

216
217
218
219
220
221

U1 and U2 voltages difference, stage 1


U1 and U2 voltages difference, stage 2
U1>U2
U2>U1
Not handled
THD level exceeded

1
1

222
223

RC signal
Motor protection Imoto

1
1
1
1
1
1
1
1

224
225
226
227
228
229
230
231

Motor failure, binary input


Motor run contact error
Motor run time exceeded
Regulation lower error
Regulation raise error
Control contact error
Maximal position error
Minimal position error

1
1
1
1

232
233
234
235

Par_Sel input in high state


Par_Sel input in low state
Parameter set number 1 correct
Parameter set number 2 correct

1
1
1
1
1
1
1

237
238
239
240
241
242
243

Clock error
MinMax UP blockade appeared
MinMax DN blockade appeared
Impermissible regulation level
Regulation principle not selected
blockade loss of voltage in circuit 1
blockade loss of voltage in circuit 2

Computers & Control

Katowice Porcelanowa 11

2010-01-12

UTXvRNT

Communication protocol IEC 8705103

2010-01-12

6. LIST OF VALUES MEASURED BY THE REGULATORS.


ASDU
9

INF
159

DESCRIPTION
Primary voltage U1
[V]
Deviation 1
[%]
Primary current I1
[A]
Not handled
Active power 1
[MW]
Reactive power 1
[Mvar]
Apparent power 1
[MVA]
cosine U1 and I1
[+/- 180]
Tap position
Primary voltage U2
[V]
Deviation 2
[%]
Primary current I2
[A]
Not handled
Not handled
Not handled
Not handled
Not handled

Measurement ranges of UTXvRNT device:


Primary voltage 1:
connection A:
connection B:
connection C:

300
173.2
173.2

[V], on the terminals of the device


[V], on the terminals of the device
[V], on the terminals of the device

deviation 1

-100100

[%]

15
25.98
15

[A], through device terminals


[A], through device terminals
[A], through device terminals

4500
4500
2600

[W], device terminals


[W], device terminals
[W], device terminals

4500
4500
2600

[var], device terminals


[var], device terminals
[var], device terminals

connection A:
connection B:
connection C:
cosine U and I 1

4500
4500
2600
-11

[VA], device terminals


[VA], device terminals
[VA], device terminals

tap position

0100

Primary current 1:
connection A:
connection B:
connection C:
Active power 1:
connection A:
connection B:
connection C:
Reactive power 1:
connection A:
connection B:
connection C:
Apparent power 1:

Computers & Control

Katowice Porcelanowa 11

UTXvRNT

Communication protocol IEC 8705103

2010-01-12

Primary voltage 2:
connection A:
connection B:
connection C:

300
173.2
173.2

[V], on terminals of the device


[V], on terminals of the device
[V], on terminals of the device

deviation 2

-100100

[%]

15
25.98
15

[A], through device terminals


[A], through device terminals
[A], through device terminals

Primary current 2:
connection A:
connection B:
connection C:

Measurement range (maximal value gave out by the device) for each of above mentioned
quantities is equal the value given above multiplied by coefficient 1.2.
Measurement range is used to calculate values indicated by the device.
Because quantities are transmitted by protocol 103 as a numbers in form of proper fractions,
e.g. numbers in range (-1, 1), indicated value can be obtained in following way:
Indicated value=transmitted value*measurement range

Computers & Control

Katowice Porcelanowa 11

UTXvRNT

Communication protocol IEC 8705103

2010-01-12

7. DEFINITIONS OF A NEW ASDU FOR THE REGULATORS.


Direction control from master to slave station.
TYPE IDENTIFICATION 41: Command setpoint scaled integer value
0
1

0
0

1
0

0
0

1
0

0
0

0
0

1
1

TYPE IDENTIFICATION
VARIABLE STRUCTURE QUALIFIER
CAUSE OF TRANSMISSION
COMMON ADDRESS OF ASDU
FUNCTION TYPE
INFORMATION NUMBER
SVA Scaled value (int)
(2 bytes)
R II
RII -the same meaning as for ASDU 20, in control direction
TYPE IDENTIFICATION 42: Command setpoint - floating point value
0
1

0
0

1
0

0
0

1
0

0
0

1
0

0
1

TYPE IDENTIFICATION
VARIABLE STRUCTURE QUALIFIER
CAUSE OF TRANSMISSION
COMMON ADDRESS OF ASDU
FUNCTION TYPE
INFORMATION NUMBER
IEEE STD 754 - Short floating point
- float
(4 bytes)
R II
RII -the same meaning as for ASDU 20, in control direction

1
0

0
1

TYPE IDENTIFICATION 46:


0
1

0
0

1
0

Computers & Control

0
0

1
0

1
0

Katowice Porcelanowa 11

TYPE IDENTIFICATION
VARIABLE STRUCTURE QUALIFIER
CAUSE OF TRANSMISSION
COMMON ADDRESS OF ASDU
FUNCTION TYPE
INFORMATION NUMBER
1-OFF/2-ON - char
(1 byte)
U1 Percent
- char
(1 byte)
Start U1 Hour - char
(1 byte)
Start U1 Minute - char
(1 byte)
End U1 Hour
- char
(1 byte)
End U1 Minute - char
(1 byte)

10

UTXvRNT

Communication protocol IEC 8705103

2010-01-12

Direction monitoring from slave to master station.


TYPE IDENTIFICATION 43: Measurements, scaled values - integer
0
0

IV

NT

1
0
1 0 1
number n information

SB

Computers & Control

BL

OV

Katowice Porcelanowa 11

TYPE IDENTIFICATION
VARIABLE STRUCTURE QUALIFIER
CAUSE OF TRANSMISSION
COMMON ADDRESS OF ASDU
FUNCTION TYPE
INFORMATION NUMBER
Scaled value (int)
(2 bytes) := tap position
QDS - Quality Descriptor

11