You are on page 1of 13

Product guide

September 2013

Who we are

Over 300 customers in 90


countries already trust our
technology

Products

HVPD are experts in the growing industry


of partial discharge (PD) testing and
monitoring of in-service high voltage
cables and plant. We offer a complete
range of equipment that gives an early
warning of faults and deterioration in
medium and high voltage (MV and HV)
insulation, allowing plant owners to take
early corrective action.
We provide bespoke solutions to our
growing customer base in the oil and gas,
renewables, shipping, transmission and
distribution, and power generation
industries.

Partial discharge is caused by discontinuities and aws in medium and high


voltage electrical insulation. PD activity will
eventually lead to complete insulation
failure which in turn can cause unplanned
outages and downtime. PD occurs due to
many factors including poor installation,
ageing, manufacturing defects, environmental impact and third-party damage.
If costly unplanned outages are to be
avoided, it is vital to carry out regular PD
testing as part of a condition-based
management (CBM) regime. This enables
operators to take baseline PD readings in
order to evaluate insulation quality, to
locate PD activity sites and to target repairs.

A complete range of
products

www.hvpd.co.uk

Products range from the simple-to-use,


PDS Air handheld surveying tool for rapid
screening of large numbers of MV assets, to
the HVPD Multi Permanent Monitor for
remote-access, continuous monitoring of
critical, MV/HV networks and/or plant
exhibiting signicant levels of PD activity.
Our products are complemented by a full
range of PD sensors for different applications, hardware accessories, industry-leading software, and customer support
services.

Screening

PDS Air

Handheld surveying tool

Page 10

Diagnostic

HVPD Longshot

Portable diagnostic unit

Page 12

Software

PDGold, PDReader and PDMap

Data collection and analysis

Page 13

Monitoring

HVPD Mini Monitor

4-channel

Page 14

HVPD Multi Portable Monitor

16-channel

Page 16

HVPD Multi Permanent Monitor

16-channel: master unit plus up


to 5x 16-ch. expansion nodes

Page 18

HVPD Sensors

Temporary and permanent

Page 20

Sensors range

HFCT, HVCC, TEV, AA

Page 21

Sensors selection by application

For all types of plant and cables

Page 22

Permanent installation kits

HFCT, HVCC, Ex/ATEX

Page 23

Sensors

HVPDs unique, condition-based asset


management approach comprises a
complete range of partial discharge test,
monitoring and sensor solutions for
identifying, locating and monitoring partial
discharge activity in both local-area and
wide-area MV and HV networks.

info@hvpd.co.uk

Industries

Innovative technologies
and over two decades
of experience

Oil and Gas

Renewables

Transmission and Distribution

Shipping

Our technology addresses the specic


issues in the offshore renewables industry
where 80% of insurance claims to date
have been cable-related.
Offshore Wind Turbine Condition
Monitoring

HVPD have a wealth of experience of PD


testing and monitoring of rotating HV
machines used both onshore and
offshore in the oil and gas industry.
Alongside the testing and monitoring of
rotating HV machines, past projects
include on-line PD testing and monitoring
of cables and cable accessories, switchgear, power transformers and bushings.
The HVPD Multi Permanent Monitor
was developed specically for the oil and
gas industry. It allows long-term, safe and
continuous condition monitoring of
medium voltage (3.3 to 36 kV) Ex/ATEX
HV motor feeder circuits in hazardous
gas zones using On-line Partial Discharge
(OLPD) sensors installed at the central
switchboard.
Using HVPDs unique, patent-pending
technology and software algorithms, the
monitors are able to carry out remote
OLPD monitoring of the complete network,
including the switchgear, cable and the
motor stator winding.
Each 16-channel HVPD Multi
Permanent Monitor module can monitor
up to 4x HV motor feeders to provide an
early warning of incipient insulation faults.
4

With over 15 years of experience in offshore


and onshore cable PD test services, HVPD
are committed to developing cost-benecial
solutions for our renewable energy
customers.
Our services include commisioning and
on-line PD testing and monitoring of MV
and HV cables, and Time Domain Reectometry (TDR) testing to provide TDR
signatures of cables for the detection and
location of cable faults. Our test engineers
are certied with BOSIET (Basic Offshore
Safety Induction and Emergency Training)
and Working at Height and Rescue
qualications.

HVPDs Wind Turbine Holistic Electrical


and Condition Monitoring Solution
(WTHCM), currently under development
in September 2013, will cover all of the
condition monitoring aspects for offshore
wind turbine drive trains, power converters and high voltage plant. It includes
specic modules for assessing both the
electrical and mechanical condition of the
offshore wind turbine generators and
combines PD, motor current signature
analysis, power converter and power
quality monitoring along with vibration
monitoring technology.
The nal system will be able to detect
up to 90% of the failure modes for
offshore wind turbines and their electrical
and mechanical components.

Power Generation

Offshore Wind Farm Subsea Cable


Monitoring
HVPDs Offshore High Voltage Network
Monitoring System (OHVMS) is designed to
address the emerging industry demand for
on-line condition monitoring (CM) of critical
subsea MV and HV AC cable networks.
OHVMS is a highly innovative system that
builds on HVPDs existing PD monitoring
technology and features additional diagnostic indicators including sheath current,
over-current and power quality monitoring
information.
www.hvpd.co.uk

Our equipment is used around the world


to test all types of MV, HV and EHV plant
operating at up to 750 kV including
switchgear, power cables, transformers,
CTs/VTs, and rotating machines in both
public utility and large private networks.
Our Wide Area Network PD Database
has been developed in conjuction with a
number of UK utilities including EDF
Energy/UKPN, Scottish Power and
Scottish and Southern Energy. It has
been designed to meet the requirements of the developing Smart Grid,
providing real-time, insulation condition
monitoring systems for wide-area,
electricity transmission and distribution
networks.

HVPD have been providing non-invasive, on-line PD testing on both cruise


ships, and oil and gas drilling vessels
since 2005, helping to ensure reliability
of the complete vessels MV electrical
networks, including generators and
drive/pump motors, cables, switchgear
and transformers.
Developed specically for the
shipping industry, our Local Area
Network PD Monitoring (LANPD)
Database meets the requirements of
smaller contained MV networks, such as
oil drilling vessels, FPSOs and large
cruise ships. Ethernet/LAN-connected
HVPD Multi Permanent Monitor units
are installed to provide real-time,
insulation PD condition monitoring
across the complete MV network.

We have supplied condition-based


assessment of MV and HV networks in the
power generation industry for over a decade,
providing our customers with diagnostic and
testing services, consultancy services,
training and PD monitoring systems.
info@hvpd.co.uk

Applications

On-line field applications

Cables

Switchgear

Motors and Generators

Transformers

PD can occur in any MV or HV cable


operated at 3.3 kV or above. Our testing
can locate potential failure sites to within
0.5% of a cables overall length using the
technique of On-line Cable Mapping.

The formation of surface tracking and PD


related erosion can lead to in-service failures
through ashover. HVPDs technology can
be used to test Air-Insulated Switchgear
(AIS), Solid-Insulated Switchgear (SIS)
and Gas-Insulated Switchgear (GIS).

On-line PD testing is now widely accepted


in the rotating HV machine industry as the
best way to assess the stator winding
condition of in-service HV motors and
generators. Using the HVPD Longshot
PD diagnostic system with its dedicated
PDGold software it is possible to carry
out both on-line (in-service) and off-line
(factory) PD testing of rotating machine
high voltage insulation.

HVPD offer a number of on-line PD test and


monitoring solutions for in-service testing of
oil, solid, and gas insulated transformers.
HVPDs on-line PD screening of medium
voltage (3.3 to 45 kV) and high voltage (66
kV+) transformers gives pre-qualication of
any dangerous discharges emanating from
within the main MV/HV windings and/or the
accessories attached to the transformers.

Case study

Case study

Early-life on-line PD testing of the motors


for a power generation company

On-line PD testing of a generator


transformer

HVPD performed on-line testing on 3x


6.6 kV water pump motors from two
different manufacturers. Baseline
spot-tests produced an assessment of the
present insulation condition of the stator
windings and provided a basis for future
PD trending.
HVPD Longshot results indicated that
one of the manfacturers motors had stator
winding insulation in the Unreliable
condition category.
Our client led a warranty claim with
the manufacturer, based on inadequate
design of the stator winding. Two separate
third party off-line PD tests backed up our
ndings and the motors were rewound
and repaired under warranty.

Following a failure in the 275 kV generator


conecting link in a transformer, the cable
and sealing end were replaced. On-line
measurements on the transformer and
repaired HV connecting link were carried
out at the commissioning stage.
HFCT sensors were attached around
the earth connections of the HV cable and
TEV probes were used to perform the
time-of-ight measurements to locate the
PD events. PD was identied and traced to
support insulators on the blue phase
connecting link between the HV cable
sealing end and the transformer output
bushing. These were then repaired and
the transformer, retested for PD, passed
as suitable for service.

Case study
On-line PD cable testing and mapping
for a light rail operator
A 33 kV XLPE cable system had been in
service for twelve months before faults
began to occur at cable joints. The HVPD
Longshot with PDMap detected
high-magnitude cable PD activity on
multiple circuits.
Out of more than one hundred 33 kV
circuits tested, signicant PD was
detected within six, putting them in the
Red condition category: Major concern,
locate PD and then repair or replace.
The sources of PD were mapped and
located to specic joints which were then
replaced and retested to verify that the
repairs were successful.

Case study
Switchgear PD monitoring for a
distribution utility customer
The HVPD Mini Monitor identied
rising PD levels in an 11 kV switchboard.
Transient Earth Voltage (TEV) sensors,
attached to the metal-clad switchgear,
identied surface discharge from two
panels. Intermittent PD activity between
5 a.m. and 9 a.m. was caused by the
formation of condensation on insulation
surfaces as the dew point was reached
(this would have been missed if PD
spot-tests had been carried out during
normal working hours). The client was
able to correct this issue cost-effectively
by installing temperature-controlled
space heating into their switchboard.

www.hvpd.co.uk

info@hvpd.co.uk

Benchmarking

Services

Expertise, training
and support for total
peace of mind

Site surveys
Many of our projects begin with carrying
out a test survey and engineering evaluation of our clients MV/HV networks with
asset management recommendations in
the site survey report.

Dedicated customer training


and support

Risk assessment

Continuous monitoring
Our 24/7 PD monitoring gives plant operators total peace of mind, with continually
updated measurement and analysis to
provide alerts and early warnings of
developing faults.
Asset performance information can be
accessed worldwide via the HVPD central
database with the Critical Condition
Benchmarking (CCB).

Practical PD training courses


We run a range of comprehensive,
practical and theoretical PD courses from
Beginner (Level I) through Intermediate
(Level II) to PD Test Engineer (Level III).
Visit www.hvpd.co.uk/training-courses
for upcoming course dates.

Off-line laboratory testing


Our 100 kV HV test facility is equipped
with electromagnetic shielding, providing
high resolution (down to 1 pC), off-line
PD test capability to IEC 60270 and
other industry standards, along with tan
delta (loss-angle) testing capability.

Equipment installation and


commissioning
Our highly-experienced team can install
temporary or permanent PD sensors and
monitoring systems at the customers
facilities including hardware and software
network infrastructure integration.

Data analysis
Our highly-trained team of UK and
overseas engineers are available to our
customers for post-purchase support,
providing vital data analysis and advice
via email and telephone.

The table below shows a typical HV


networks Top 20 33 kV circuits, OLPD
tested by HVPD, ranked by their
criticality. The colour-coded condition
assessment is based on HVPD guideline, peak and cumulative PD levels.

A quantiable method of assessing the


likelihood of costly outages by comparing
customers PD test results against all others
held in HVPDs OLPD Database.
This unique and extensive database,
backed by over 20 years of PD data and
test experience, enables us to clearly
identify the bad actors of PD activity in a
clients MV or HV network. Test data is
compiled into an OLPD League Table
which clearly identifies the plant/cables in
need of immediate preventative interventions or longer term diagnostic monitoring.

We tailor our on-site training courses to


suit the customers engineers, giving them
the resources and skills to most effectively
test their network with HVPD equipment,
and perform data collection and analysis.

Diagnostic services
Live plant PD testing, diagnostics, and
extended monitoring without any costly
interruption to service.
Off-line testing: HVPDs factory
acceptance PD testing, VLF testing, and
on-site commissioning tests can detect
any problems with plant before they are
put into service.

Critical Condition Benchmarking


(CCB) System

www.hvpd.co.uk

Criticality
number

Circuit

Comments

Peak Cable
PD Level
(pC)

Local
PD Level
(dB)

Cumulative
Cable PD Level
(nC/cycle)

OLPD
Criticality
(%)

DUB to MPS1 C2

B Phase

25888

<10

247

97.4

ABS to AH C2

B/Y Phase

9729

<10

120

90.3

BUR to HCC C2

B/Y Phase

3781

<10

12.3

78.7

BUR to HCC C1

B/Y Phase

3245

<10

7.9

78.1

ABS to AH C1

B/Y Phase

2920

<10

14.4

77.4

NHD to QYD C2

R Phase

2849

<10

15.0

76.2

ALQ to AHS C2

B Phase

1733

<10

4.6

70.6

MPS3 to BNS C2

R/B Phase

1337

<10

6.4

65.5

NHD to QYD C1

R Phase

887

<10

8.8

47.8

10

HCC to CRK C1

Y/B Phase

759

<10

2.5

39.2

11

AHS to SLD

Y/R Phase

705

<10

3.1

38.5

12

STD to ABH

Y Phase

238

<10

1.0

24.1

13

ALR to BNS C1

B Phase

184

<10

0.9

18.6

14

ALR to BRJ

no PD detected

<10

15

ALG to PMD

no PD detected

<10

16

ALG to KBW

no PD detected

<10

17

AQD to AQ2

no PD detected

<10

18

JDD to CRK

no PD detected

<10

19

ODM to JDF C1

no PD detected

<10

20

ODM to JDF C2

no PD detected

<10

info@hvpd.co.uk

Maintenance
action

Major concern,
locate PD and then
repair or replace

Some concern,
repeat test and
regular monitoring
recommended

Re-test in
12 months

PDS Air

Handheld surveying tool

10

Specially designed to screen MV plant of


voltage rating 3.3 to 36 kV, the unit is
suitable for testing power cables, joints and
terminations, motors and generators,
switchgear, power transformers, and
instrument transformers (current/voltage).
PDS Air provides rapid test times as
low as three to ve seconds per item and
is also capable of PD surveying of outdoor
switch yards using the outdoor parabolic
receiver.

The PDS Air has built-in TEV and


Airborne Acoustic (AA) sensors for testing
metal-clad MV switchgear and includes an
additional split-core HFCT sensor for MV
cable testing.
The unit is supplied with an HFCT100/50
sensor, 100 kHz high-pass lter, headphones, accessories and carry case.
Optional extras include: indoor acoustic
probe, outdoor parabolic receiver, laser
enhancement eyewear and Peltor PPE
headphones.

www.hvpd.co.uk

info@hvpd.co.uk

11

HVPD Longshot

Portable diagnostic unit

Designed for diagnostic PD testing of all


types of medium (3.3 to 45 kV) and high
voltage (66 kV+) cables and plant. Suitable
for testing power cables, joints and
terminations, motors and generators,
switchgear, power transformers and
bushings, and instrument transformers
(current/voltage), the unit can be used to
test MV, HV and EHV plant up to 750 kV.
Synchronous and wideband (200 MHz)
data acquisition accurately and rapidly
measures PD magnitude and wave
shapes. This light and portable unit has a
typical spot-test time of ve to ten
minutes per plant item. Short-term PD
monitoring of up to 48 hours is also
possible.

Software

HVPD Longshot is designed to be


used for both on-line (in-service) and
off-line (factory/laboratory) testing and is
the most versatile PD test unit presently
in the market.
The unit comes with pre-loaded
PDGold and PDReader v7 data
analysis and reporting software. Optional
PDMap expansion software, with the
Portable Transponder System,
enables On-line Cable Mapping (PD site
location) on cables of up to 10 km in
length.
Available with a range of sensors and
accessories for multi-application testing,
the unit can be used to test all types of
MV/HV/EHV plant and cables.

Industry-leading data acquisition,


automatic analysis and PD location
PDGold and PDReader
Dedicated software for HVPD Longshot
providing PD signal acquisition for on-site
spot-testing and up to 48-hour monitoring
of key assets. Data preview and automatic
report generation, can be made either
immediately on-site or off-site with any
Windows-based PC.
PD events are extracted from power
cycles and classied by type for post-test
analysis and report generation. PD levels
are displayed in pC, mV and dB, depending
on the source and type of PD and the PD
sensor used, with the background noise
being automatically removed.

PDGold v7

PDMap
Optional expansion software for the HVPD
Longshot providing PD site location on
cables of up to 10 km in length.
Used with HVPDs Mini Pulse Generator
and Portable Transponder accessories at
cable terminations, PD sites are accurately
located along the length of power cables by
measuring pulse travel times.

PDReader v7

12

www.hvpd.co.uk

info@hvpd.co.uk

13

HVPD Mini Monitor


Deployment of HVPD Mini Monitor on a MV Network

4-channel on-line monitor


for temporary or
permanent installation

14

A unique, portable 4-channel on-line PD


monitor designed for both short-term and
long-term PD monitoring of MV plant and
cables (3.3 to 45 kV). Low-cost, easy to
install, 24/7 PD monitoring technology for
cables, metal-clad switchgear and other
plant. A precedence functionality enables
determining the direction and location of
PD activity within MV networks.
Using remote access connections, data
can be uploaded and benchmarked
against HVPDs Wide Area PD Monitoring
Database to assess criticality.

The HVPD Mini Monitor logs peak,


count (number of pulses), and cumulative
PD to provide a measure of the PD
severity in each measurement period.
Supplied with two HFCT sensors to
measure PD activity in cables and two
TEV sensors for local PD activity in
terminations and switchgear, AC/DC
power supply and protective earth cable.

www.hvpd.co.uk

info@hvpd.co.uk

15

HVPD Multi Portable Monitor

16-channel on-line
monitor for temporary
installation

16

A 16-channel on-line PD monitor designed


for both short and medium-term continuous on-line PD monitoring of MV (3.3 to 45
kV) cables, switchgear and other plant,
without the need for outage.
The HVPD Multi Portable Monitor
detects and logs load varying and intermittent PD activity to provide a measure of
the cumulative PD activity in a monitoring
period. The internal hard disk stores up to
12 months of PD data.

The system incorporates the unique PD


EventRecogniser software which
provides automatic analysis and differentiation of PD pulses from electrical noise
and interference.
The HVPD Multi Portable Monitor
system and its sensors and accessories
can be configured according to specific
requirements as stated by the customer or
as defined during a site survey.

www.hvpd.co.uk

info@hvpd.co.uk

17

HVPD Multi Permanent Monitor

16-channel on-line monitor


for permanent installation

18

Designed for long-term continuous on-line


PD monitoring of rotating machines, MV
cables, switchgear, ring-main units and
transformers.
HVPD Multi Permanent Monitor
detects and logs load varying and intermittent PD activity to provide a cumulative
measurement in a monitoring period. Incorporating the unique PD EventRecogniser
software the unit provides automatic
analysis and differentitation of PD pulses
from electrical noise and interference.
Using remote access connection, data
can be uploaded and compared against
HVPDs Wide Area PD Monitoring Database
to assess criticality.

Remote monitoring

HVPD Multi Permanent Monitor


features 16 sensor channels for HVCC/
HFCT/ TEV sensors and optional
Linearplex module adding up to 32
AA sensors for detection of coronal and
surface discharges.
The unit can be congured to the
customers specific site requirements.
Up to 5x additional, 16-channel
measurement nodes can be added to
the master unit to provide up to 96
HVCC/HFCT/TEV channels and up to
192 AA sensors.

www.hvpd.co.uk

Technology specifically for


the oil and gas industry

Remote on-line PD monitoring


of HV Ex/ATEX motors
This unique, patent-pending technology
has been designed specifically for the
on-line PD monitoring of Ex/ATEX HV
motors located in hazardous gas zones.
Using HVPDs innovative technology,
incorporating HVPD Multi Permanent
Monitors and new software algorithms, it is
now possible to carry out remote OLPD
monitoring of the complete MV networks
including switchgear, cable and the motor
stator winding using OLPD sensors
installed at the central switchboard.

info@hvpd.co.uk

Each 16-channel HVPD Multi Permanent Monitor module measures the PD


signals from up to 4 HV motor feeders to
provide an early warning of incipient
insulation faults.
Data analysis is carried out by the
units EventRecogniser, knowledge-based software using PD pulse
wave shape data analysis techniques to
identify the sources of PD activity.

19

Sensors

Temporary and permanent


installation

Our sensor range

HVPDs comprehensive range of specialised sensors include HFCT (High


Frequency Current Transformer) sensors
for cables, HVCC (High Voltage Coupling
Capacitor) couplers for rotating machines,
and TEV (Transient Earth Voltage) or AA
(Airborne Acoustic) for the detection of
local PD in switchgear.
The use of permanent sensors enables
a reduction in the time and cost of
performing periodic on-line PD diagnostic
spot-testing as no outage is required after
installation.

HFCT
High Frequency Current Transformer
Portable or permanent sensors for the
measurement of cable PD and/or remote
monitoring of rotating HV machines. These
can be attached around the earth strap
connection and/or around the insulated core
of the cable (depending on the type of cable
termination). Environmentally screened,
high current, and Ex/ATEX (explosive
environment) versions are also available.

HVCC
High Voltage Coupling Capacitor
This PD sensor coupler is used for the
measurement of PD within rotating HV
machines and is designed for permanent
installation inside the machine cable/terminal box. Ex/ATEX (explosive environment) versions of this sensor are also
available.

TEV
Transient Earth Voltage
For the detection of local PD. Can be
installed on both the inside and the
outside of the metal-clad switchgear
housing. They can also be used to detect
PD in transformer and machine/terminal
cable boxes.

AA
Airborne Acoustic
Suitable for the detection of airborne
PD signals with line of sight to the PD
source. Installed inside the switchgear
to provide maximum sensitivity.
20

www.hvpd.co.uk

info@hvpd.co.uk

21

Recommended sensors
by application

Permanent sensor
installation kits

Power cables
Switchgear

HFCT
Air-insulated

HFCT

AA

Permanent HFCT sensor kits are


designed for sensor installation inside
the cable boxes of the asset under test.
The kit includes three HFCT sensors,
one TEV sensor, sensor terminal box
and accessories.

TEV
HFCT
Solid-insulated

TEV
HFCT

Rotating machines

Transformers

Permanent sensor kits provide a


convenient and cost-efcient solution for
periodic on-line testing in situations
where MV/HV plant outages are rare.

Gas-insulated

TEV
HFCT

Cable-Fed <1000A

High Current HFCT

Bus-Fed / Cable-Fed >1000A

HVCC
TEV
HFCT
Bushing Tap

HVCC

HFCT sensors are available in various sizes and portable and permanent versions. Contact us for further information.
HFCT and HVCC sensors are available as Ex/ATEX versions, certified for installation in hazardous explosive gas environments.

Permanent HVCC sensor kits are


designed for installation within the
cable termination boxes of the rotating
HV machines.
Includes three HVCC sensors, HV
jumper cables, BNC signal cables,
earth cables, sensor terminal box
and accessories.

Ex/ATEX versions
HFCT and HVCC sensor kits are also
available as Ex/ATEX versions,
certified for installation in
hazardous, explosive gas environments. BNC signal cables, earth
cables, Ex/ATEX-rated sensor terminal
box and other accessories are included
as standard.

22

www.hvpd.co.uk

info@hvpd.co.uk

23

HVPD Head Office

Partners and distributors

128 Metroplex Business Park


Broadway, MediaCityUK,
Salford, M50 2UW
United Kingdom

Australia
Live HV
Telephone: +61 1600 460 579
www.livehv.com.au

Philippines
NC Power Corp
Telephone: +63 2366 9469
www.ncpowersales.com

Telephone:
Facsimile:
Email:
Website:

Belgium
Seba Service
Telephone: +32 2272 0590
www.seba-service.be

Russia
Skomplekt
Telephone: +79 167 868 605
www.skomplekt.com

China
HVPD China Office
Telephone: +86 1860 4269 606
www.hvpd.co.uk/china

Saudi Arabia
YBA Kanoo
Telephone: +966 506 204 283
www.kanoo.com

Hong Kong
C&K Instrument (HK) Limited
Telephone: +852 2690 3081
www.cnkgroup.com

Slovakia
SEBA Slovakia Spol. s.r.o
Telephone: +42 1 255 423 958
www.sebakmt.sk

India
Diagnostic Technologies
Telephone: +91 250 239 0786
www.diatechindia.com

South Africa
Martec Cable Services
Telephone: +27 829 039 544
www.martec.co.za

Indonesia
P. T. Dinamika Elektra Mandiri
Telephone: +62 21530 3888
www.de-mandiri.com

South Korea
PSD Tech. Inc
Telephone: +82 1087 644 890
www.psdtech.com

+44 (0) 161 877 6142


+44 (0) 161 877 6139
info@hvpd.co.uk
www.hvpd.co.uk

Malaysia
IPEC Malaysia 1
Telephone: +603 8023 1912
www.my-ipec.com.my

Sweden
Swedish Neutral AB
Telephone: +46 858 171 344
www.swedishneutral.se

New Zealand
Lord Power Equipment
Telephone: +64 1800 485 990
www.lordpowerequipment.com.au

Thailand
Plan Market Gold Co. Ltd
Telephone: +66 2314 1341
www.planmarketgold.com

Norway
Karsten Moholt AS
Telephone: +47 5594 3400
www.karsten-moholt.no

UAE
YBA Kanoo
Telephone: +971 4 2253201
www.kanoo.com

Oman
Rakun Al Yaqueen International LLC
Telephone: +96 824 600 420
www.rayoman.com

USA
PDMS
Telephone: +1 832 291 7560
www.pdmsltd.com

You might also like