You are on page 1of 6

Slab Thickness - 250mm

Stub Length - 250mm


Profis Anchor 2.5.0

www.hilti-me.com
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Sub-Project I Pos. No.:
Date:

1
11/2/2015

Specifier's comments:

1 Input data
Anchor type and diameter:

HIT-HY 200-R + Rebar 16mm

Dynamic set or any suitable annular gap filling solution


Effective embedment depth:

hef,act = 250 mm (hef,limit = - mm)

Material:

B500B

Evaluation Service Report:

ETA 12/0084

Issued I Valid:

8/8/2012 | 12/23/2016

Proof:

Design method Engineering judgement SOFA BOND - based on ETAG BOND testing

Stand-off installation:

eb = 0 mm (no stand-off); t = 25 mm

Anchor plate:

lx x ly x t = 200 mm x 600 mm x 25 mm; (Recommended plate thickness: not calculated)

Profile:

Pipe; (L x W x T) = 140 mm x 140 mm x 13 mm

Base material:

cracked concrete, C30/37, fc = 37.00 N/mm2; h = 10000 mm, Temp. short/long: 30/40 C

Installation:

hammer drilled hole, Installation condition: Dry

Reinforcement:

no reinforcement or reinforcement spacing >= 150 mm (any ) or >= 100 mm ( <= 10 mm)
with longitudinal edge reinforcement d >= 12 + close mesh (stirrups, hangers) s <=

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

Profis Anchor 2.5.0

www.hilti-me.com
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Sub-Project I Pos. No.:
Date:

11/2/2015

2 Load case/Resulting anchor forces


Load case: Design loads

Compression
1
y

Anchor reactions [kN]


Tension force: (+Tension, -Compression)
Tension force
Shear force
Shear force x
Anchor
1
3.698
5.056
0.750
2
5.894
5.056
0.750
3
11.165
5.056
0.750
4
13.362
5.056
0.750
max. concrete compressive strain:
0.12 []
max. concrete compressive stress:
3.55 [N/mm2]
resulting tension force in (x/y)=(0/-81):
34.120 [kN]
resulting compression force in (x/y)=(82/246): 9.120 [kN]

2
Shear force y
5.000
5.000
5.000
5.000

x
Tension
3
4

3 Tension load (EOTA TR 029, Section 5.2.2)


Load [kN]
13.362

Capacity [kN]
79.286

Utilization bN [%]
17

Status
OK

Combined pullout-concrete cone failure**

34.120

54.787

63

OK

Concrete Breakout Strength**

34.120

40.172

85

OK

34.120

100.191

35

OK

Steel Strength*

Splitting failure**
* anchor having the highest loading

**anchor group (anchors in tension)

3.1 Steel Strength


NRk,s [kN]
111.000

gM,s
1.400

NRd,s [kN]
79.286

NSd [kN]
13.362

3.2 Combined pullout-concrete cone failure


Ap,N [mm2]
202376

A0p,N [mm2]
136533

2
tRk,ucr,25 [N/mm ]
10.00

scr,Np [mm]
370

ccr,Np [mm]
185

yc
1.000

2
tRk,cr [N/mm ]
5.50

k
2.300

yg,Np
1.749

yg,Np
1.277

ec1,N [mm]
0

yec1,Np
1.000

ec2,N [mm]
81

yec2,Np
0.696

ys,Np
0.903

N0Rk,p [kN]
69.115

NRk,p [kN]
82.181

gM,p
1.500

NRd,p [kN]
54.787

NSd [kN]
34.120

cmin [mm]
125

yre,Np
1.000

3.3 Concrete Breakout Strength


Ac,N [mm2]
297500

A0c,N [mm2]
562500

ccr,N [mm]
375

scr,N [mm]
750

ec1,N [mm]
0

yec1,N
1.000

ec2,N [mm]
81

yec2,N
0.823

N0Rk,c [kN]
173.118

gM,c
1.500

NRd,c [kN]
40.172

NSd [kN]
34.120

Ac,N [mm2]
235000

A0c,N [mm2]
250000

ccr,sp [mm]
250

scr,sp [mm]
500

yh,sp
1.438

ec1,N [mm]
0

yec1,N
1.000

ec2,N [mm]
81

yec2,N
0.756

ys,N
0.850

N0Rk,c [kN]
173.118

gM,sp
1.500

NRd,sp [kN]
100.191

NSd [kN]
34.120

ys,N
0.800

yre,N
1.000

k1
7.200

yre,N
1.000

k1
7.200

3.4 Splitting failure

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

Profis Anchor 2.5.0

www.hilti-me.com
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Sub-Project I Pos. No.:
Date:

3
11/2/2015

4 Shear load (EOTA TR 029, Section 5.2.3)


Load [kN]
5.056

Steel Strength (without lever arm)*


Steel failure (with lever arm)*

Capacity [kN]
36.667

Utilization bV [%]
14

Status
OK

N/A

N/A

N/A

N/A

Pryout Strength**

20.224

97.664

21

OK

Concrete edge failure in direction x+**

20.224

148.089

14

OK

* anchor having the highest loading

**anchor group (relevant anchors)

4.1 Steel Strength (without lever arm)


VRk,s [kN]
55.000

VRd,s [kN]
36.667

gM,s
1.500

VSd [kN]
5.056

4.2 Pryout Strength (Concrete Breakout Strength controls)


Ac,N [mm2]
297500

A0c,N [mm2]
562500

ccr,N [mm]
375

scr,N [mm]
750

k-factor
2.000

ec1,V [mm]
0

yec1,N
1.000

ec2,V [mm]
0

yec2,N
1.000

ys,N
0.800

N0Rk,c [kN]
173.118

gM,c,p
1.500

VRd,c1 [kN]
97.664

VSd [kN]
20.224

a
0.141

b
0.066

yec,V
1.000

yre,N
1.000

4.3 Concrete edge failure in direction x+


lf [mm]
250

dnom [mm]
16.0

k1
1.700

c1 [mm]
125

Ac,V [mm2]
152813

A0c,V [mm2]
70313

ys,V
1.000

yh,V
1.000

ya,V
2.367

ec,V [mm]
0

V0Rk,c [kN]
30.843

gM,c
1.500

VRd,c [kN]
148.089

VSd [kN]
20.224

yre,V
1.400

5 Combined tension and shear loads (EOTA TR 029, Section 5.2.4)


bN
0.849
a

bV
0.207

a
1.500

Utilization bN,V [%]


88

Status
OK

bN + bV 1

6 Displacements (highest loaded anchor)


Short term loading:
NSk

9.898 [kN]

dN

0.118 [mm]

VSk

3.745 [kN]

dV

0.150 [mm]

dNV

0.191 [mm]

dN

0.173 [mm]

dV

0.225 [mm]

dNV

0.284 [mm]

Long term loading:


NSk

9.898 [kN]

VSk

3.745 [kN]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!
The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

Profis Anchor 2.5.0

www.hilti-me.com
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Sub-Project I Pos. No.:
Date:

4
11/2/2015

7 Warnings
Load re-distributions on the anchors due to elastic deformations of the anchor plate are not considered. The anchor plate is assumed to be
sufficiently stiff, in order not to be deformed when subjected to the loading!

Input data and results must be checked for agreement with the
existing conditions and for plausibility!
Checking the transfer of loads into the base material is required in accordance with EOTA TR 029, Section 7!
The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of EOTA TR029! For larger
diameters of the clearance hole see Chapter 1.1. of EOTA TR029!
The design method ETAG (filled holes) assumes that no hole clearance between the anchors and the fixture is present. This can
be

achieved by filling the gap with mortar of sufficient compressive strength (e.g. by using the Hilti Dynamic Set) or by other suitable means
The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
Bore hole cleaning must be performed according to instructions for use (blow twice with oil-free compressed air (min. 6 bar), brush twice,
blow twice with oil-free compressed air (min. 6 bar)).
Characteristic bond resistances depend on short- and long-term temperatures.
The design method SOFA assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by filling
the gap with mortar of sufficient compressive strength (e.g. by using the Hilti Dynamic Set) or by other suitable means.
The compliance with current standards (e.g. EC3) is the responsibility of the user
An SLS-check is not performed for SOFA and has to be provided by the user!

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

Profis Anchor 2.5.0

www.hilti-me.com
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Sub-Project I Pos. No.:
Date:

5
11/2/2015

8 Installation data
Anchor plate, steel: Profile: Pipe; 140 x 140 x 13 mm
Hole diameter in the fixture: df = 16 mm
Plate thickness (input): 25 mm
Recommended plate thickness: not calculated
Cleaning: Premium cleaning of the drilled hole is required

Anchor type and diameter: HIT-HY 200-R + Rebar 16mm


Installation torque: 0.000 kNm
Hole diameter in the base material: 20 mm
Hole depth in the base material: 250 mm
Minimum thickness of the base material: 290 mm

8.1 Recommended accessories


Drilling
Suitable Rotary Hammer
Properly sized drill bit

Cleaning
Compressed air with required
accessories to blow from the bottom of
the hole
Proper diameter wire brush

Setting
Dispenser including cassette and mixer
For deep installations, a piston plug is
necessary
Dynamic set
Torque wrench

100

80

100

300

100

240

80

100

100

Coordinates Anchor [mm]


Anchor
1
2
3
4

x
0
0
0
0

y
220
120
-120
-220

c-x
125
125
125
125

c+x
125
125
125
125

c-y
-

c+y
-

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

300

100

Profis Anchor 2.5.0

www.hilti-me.com
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:

Page:
Project:
Sub-Project I Pos. No.:
Date:

6
11/2/2015

9 Remarks; Your Cooperation Duties


Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted
prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the
data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be
put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly
with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or
suitability for a specific application.
You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan