Professional Documents
Culture Documents
- 12 Feeders.
- 1 Feeder.
- 1 Feeder.
63
4. Air Conditioning Feeder (3 phase feeder)
- 1 Feeder.
-1 Feeder.
-1 Feeder.
-12 Feeders.
-1 Feeder.
-1 Feeder.
-1 Feeder.
-1 Feeder.
-1 Feeder.
-1 Feeder.
Electronic controllers
Connected to Bus-A
Electronic controllers
Connected to Bus-B
R & Y phases 1A
12B
6A
7A
12A
1B
6B
7B
Y & B phases 2A
11B
5A
8A
11A
2B
5B
8B
R & B phases 3A
10B
4A
9A
10A
3B
4B
9B
64
2) 6 feeders for collecting electrodes-rapping motor.
3) 12 feeders for hopper heaters - (2 hopper heater per feeder).
4) 2 feeders for support insulators - (6 bus section insulator housing
per feeder).
5) 2 feeders for heaters of shaft insulators - (6 bus section shaft
insulator per feeder).
6) 1 feeder for Gas Distribution for rapping motor.
65
and h2 indicator will also glow, showing motor is in ON condition. In the
master controller mode, as long as the switching contact from the master
controller is available, k contact will be in closed condition.
Once if the
master controller contact opens, k relay will drop put and thereby K contact
will open and so supply is switched off. In the continuous mode operation, by
pressing start push button either in the local or remote, K relay will energies
and in turn close the K contact. It will be in close condition and stop push
button in the local or remote is pressed. Even in the master controller mode,
if stop push button is latched, the K relay will drop out and K contact is
open and motor is switched off. Through K contactors NC contact motor
OFF indication (h3) is available. h3 will glow if K relay drops out and the
indication shows the motor OFF condition.
As the rapping motor loads are connected to gear and tumbling
hammer arrangement, overload of the motor is possible at any time.
Overload relay contacts (98) are provided in the control circuit for switching
off K relays supply, thereby K contact will open. h1 indication will also be
available to show the motor trip condition.
66
ash level-sensing probe, 24V supply is used. 24V is made available through
110V/24V transformer. One of the NO contacts of 6 ash level indicator relays
are wired in parallel for the annunciations circuit so that if any one of the
sensing probe senses hopper over filled condition, annunciation will be
available. One reset push button is also provided for each ash level indicator,
to reset d relay. If the switching contact from the sensing probe is not in
closed condition, (i.e.,) if ash over filled condition is not available, by
pressing reset push button, d, relay can be reset.
5.11 ANNUNICATIONS
Following annunciations are provided in the ACP:
1. For rapping motor tripped annunciation one NO contact from
each rapping motor control circuit is used.
2. For hopper over filled annunciation, if any one of NO contact
of the ash level indicator closes, this annunciation will be
available.
3. One NO contact from the electronic controller is used for ESP
rectifier faculty annunciation.
4. One NO contact from the LT main switchboard is used for ESP
supply faculty annunciation.
67
415 volts phase-to-phase supply from LT Main Switchboard
comes to the Electronics Controller panel through cable. In the
electronic controller panel the antiparallel connected thyristor pair in
single phase is arranged to control the primary side A.C. supply of the
high voltage transformer rectifier unit. From the intelligent controller
gate pulses are given to the triggering circuit of the thyristors.
Intelligent controller is programmed to control current, voltage,
sparking and fault situations etc. Feedback from the high voltage D.C.
insupply is also fed to the intelligent controller and settings are done in
the controller. In the high voltage transformer rectifier unit, the
controlled primary side A.C. supply is stepped up to 70KV peak
(continuously peak) and then rectified. It is fed through a high
frequency chokes and fed to ESP emitting electrodes.
Output voltage
Input current
Output current
Phase
: single
Frequency
: 50Hz
Cooling
: ONAN
68
A double float relay is fitted in the pipe connection between the
conservator and the HVR tank. Each float is fitted with the mercury
switch. The contacts are brought to the thermometer box for alarm and
tripping. Conservator is provided with oil level indicator, Dehydrating
breather, and Relief vent. Bushings are provided on the tank side for LV
input terminals (a1, a3) Low voltage measurement terminals (av), High
voltage output terminals A1& A2 (HV + VC, HV - VC), shunt terminals
(AS1 & AS2), high voltage resistor terminals (AR).
69
(HVRC) and shunt protection diodes (S 1, S2) are mounted on a glass fiber
plate, called high voltage resistor board from which the measuring signal is
tapped.
ICE-C
intelligent
controller.
Bucholz
relay
signal,
transformer
temperature signals from thermometer box of HVR fed to the ICE-C through
upto isolator. Lamps LP-5 and LP-6 are used for alarm indications of ash level
overfilled indication and for oil level low indication respectively and that is
also wired through K5 and K6 relays. For both alarm and trip indications
hooter indication will come. Through K4 relays NO contact, hooter ON
70
circuit is wired. Once alarm accepts push button is pressed K4 relay will pick
up, so hooter will be OFF. Below the lamp indications HT interlock switch
outer accept push button at Time totalizer counter for hours of ESP in service
are mounted. In the bottom of the front panel isolating switch is provided.
2.
71
3.
Parameter
Precipitator current
Precipitator Voltage
Spark rate (sparks per min.)
Current limit Im (Max. Current)
Current limit Is (set current)
S control
T control
First ignition angle after spark
Under voltage limit
Charge ratio
Pulse current limit
Loop gain
Address
Function
Measured value
Measured value
Measured value
Setting value
Setting value
Setting value
Setting value
Setting value
Setting value
Setting value
Setting value
Setting value
Selection.
5.
6.
72
9.
73
After reaching the S level to reach I s, current slope has to be seen
which will be done by T control, which is a time set function. In order to reach
the set current limit Is, time required to reach will be set in this. During start
up for fast current rise TO function (i.e. time override function) will be used,
then the built up follows the T setting in order to reach I s. Normally it is set
at 20%.
SIGNAL
DESCRIPTION
74
N1
Input
N2
Input
N3
N4
N5
N6
N7 to
N10
N11
N12
N13
N14
N15
Input
Input
Input
Input
Input/output
Output
Output
Output
Output
Output
N16
Output
N17
Output
*-*-*-*-*-*-*-*-*-*-*-*-*-*-*-*
*-*-*-*-*-*-*-*