Professional Documents
Culture Documents
4380078PD
Issue 8. NW 2000
6875009BLK-62
6875010BLK-62
6875010BLK-62A
MbDULAR -48 MC, 100 AMP
SWITCHMODE RECTIFIER SYSTEM(S)
WITH DISTRIBUTION, LVD,
LO/HI VOLT ALARMS, BATIXRY DISCONNECT
11-08-M) RFS
r~
4380078PD.da
ISSUE
kwe s. NO 2cal
I
I
I
I
I
I
I
I
I
DESCRIPTION
PART NUMBER
4380084PD
4390933P
6421015P
TABLE OF CONTENTS
DescriDtion
TOC
List of Figures, Referenced Information
Foreword
Warnings and Cautions
section I
1.1
1.2
1.3
1.3.1
I .3.2
1.3.3
1.3.4
1.3.5
1.3.6
1.3.7
1.3.8
1.3.8.1
1.3.8.2
1.3.8.3
1.3.9
1.3.9.1
1.3.9.2
1.3.9.3
1.3.9.4
1.3.9.5
1.3.9.6
1.3.9.7
1.3.9.8
1.3.9.9
1.3.9.10
1.3.10
1.3.11
1.3.12
1.3.13
1.4
1.4.1
1.4.2
I .4.3
1.5
1.6
1.7
General Information
General
System Description
Standard Features
Front Access
Simple Configuration
Hot Insertion
Input Protection
output Protection
LVD and LVPU
Low Voltage and High Voltage Setpoints
Rectifier Module Indicators
AC ON Indicator
Rectifier Fail
Equalize ON
Distribution and Alarm Panel Indicators
Distribution Fuse Alarm
AC Fail
RFA MIN
RFAMAJ
Test
LVD
Hv
LV
Power On
BATT DISC.
Alaml.s
Battery Disconnect
VOLT/AMPS
High Temperature Shutdown
Primary System Components
Distribution and Alarm Panel
Rectifier Shelf
Rectifier Module
Monitored Faults
Configuration Arrangement
8
8
8
8
8
8
8
8
8
9
9
9
9
9
10
10
10
10
10
10
10
10
10
10
10
11
11
11
11
II
11
11
11
12
12
12
12
section II
2.1
2.2
2.2. I
2.3
2.3.1
2.3.2
2.3.3
Power Information
General
Input Power Requirements
Input Electrical Connections
Output Ratings
Float Regulation
Equalize Setting
Output Current
14
14
14
14
14
14
14
14
SectiodT%ra
Front Matter
3
5
6
7
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
Section/Pars
section III
&
1.5
15
1.5
16
3.4
3.4.1
3.4.2
3.5
DWXiDtiOIl
System Installation
G.%W.d
Specifications
Recommended Terminal, Wire, and
Fuse Sizes
system Installation
Pre-Installation Checks
Installation
Operational Checkout
Section Iv
4.1
4.2
4.2.1
4.3
22
22
22
22
22
Section v
5.1
5.2
5.2.1
5.3
23
23
23
23
23
Section VI
6.1
6.2
6.2.1
6.2.1.1
25
25
25
25
25
6.2.1.2
6.2.1.3
6.2.1.4
6.2.2
6.2.3
6.2.4
6.3
Section VII
7.1
7.2
Theory of Operation
GeWX3l
System Theory of Operation
30
30
30
Section VIII
System ConfigurationSmarts
List
GOXd
Contigurations
31
3.1
3.2
3.3
8.1
8.2
18
18
19
20
27
27
27
28
28
29
29
31
31
LIST OF FIGURES
Name
Figure Number
I-1
System
system Connections
3-1
REFERENCED
INFORMATION
EQUIPMENT
Eauioment Nomenclature
Digital Multimeter
Part Number
Fluke 87
Manufacturer
John Fluke
Mfg. Co. Inc.,
Everett, WA
ID Number
SM50F48PMPD
CONSUMABLES
Nomenclature
N/A
Part Number
Manufacturer
Manufacturer
PECO II
Galion, OH
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
FOREWORD
This manual is intended to help the user of the 100 Amp Modular Rectifier Systems (system) install, test,
troubleshoot, and remove the system. For information on the modules that comprise the system, refer to the manuals
on those components. If you should have any questions or problems with the installation or maintenance of the
system you should contact one of the following sources:
Service
If you should need any assistance on any of the equipment produced by PECO II, Inc. we have complete
Engineering and Field Service Groups available in our Galion, OH facility. For any engineering or field service
support, please contact:
(419) 468-7700 (direct line to the Field Service Group)
(419) 468-7600 (Operator, ask to speak to the Field Service Group)
For pans replacement or ordering information please contact the Field Service Group at one of the above listed
numbers. If you have all pertinent information, you may simply forward a purchase order to one of the following:
PECO II, Inc.
P.O. Box 910
Galion. OH 44833-0910
iix to (419) 468-1587
Give the PECO II part number and engineering level of the equipment.
If the pan is electrical, please include the circuit reference numbers and the PECO U part numbers.
If the part is mechanical in nature, please give a description as to where the equipment is used.
1.
ELECTRICAL SHOCK HAZARD. W NOT AlTEMPTTO REMOVE. MAINTAIN. OR INSTALLTHIS EQUIPMENT WilH
POWER APPLLED. PERSONNEL THAT ATTEMFT TO WORK ON THIS EQUrPMENT WH THE POWER APPLIED MAY
SUBJECT THEMSELVES OR OTHERS TO ELFCTRlcAL SHOCK THAT MAY CAUSE SERIOUS INJURY OR DEATH.
2. t
THE AlTEMPTED USE OFTHIS EQUIPMENT BY UNAUTHORaED OR UNTRAINED PERSONNU IS STRICTLY FORBIDDEN.
PERSONNEL THAT AlTEMPT TO WORK ON THIS EQUIPMENT WVOUT THE PROPER TRAINING MAY SUB,ECT
THEMSELVES OR OTHERS TO ELECTRICAL SHOCK THAT MAY CAUSE SERIOUS INJURY OR DEATH,
3. .
4.
Do NOT AlTEMPT TO WORK ON THIS EQUIPMENT IF ,T IS OR HAS BEEN EXPOSED TO A HIGH MOlSTURB COND,TION.
iT IS RECOMMENDED THE EQUIPMENT BE R!ZTURNED TO PECO II TO BE PROPERLY TESTED. WORKING ON THls
EQUIFMENT DURING A HIGH MOlSTURE CONDTON SUBJECTS THE USER TO ELECTRICAL SHOCK THAT MAY CAUSE
SERIOUS EVJURY OR DEATH.
USE OF AN AITACHMENT OTHER THAN ONE THAT HAS BEEN APPROVED BY PECO Is FORBIDDEN. THE Al-,?ZMPTED
USE OF UNAUTHORIZEDATTACHMENTS
W,LL OLD ANY AND ALL WARR-. ,MPL,ED OR OTHER, AND WILL,
Do NOT OPERATE THIS EQUIPMENT IF rr HAS BEEN DROPPED 0~ OTHERME HAS PosstBLY BEEN DAMAGED.
TRYING TO OPERATE THIS EQUIPMENT IF m HAS BEEN DAMAGED SUBJECTS YOURSELF OR OTHERS TO ELEC,RICAL
SHOCK THAT MAY CAUSE SEPJOUS INJURY OR DEATH.
BEFORE YOU PROCEED. ENSURE THE AC INPUT SOURCE Is NOT LhB AND THE INPUT C,RCU,T BREAKER(S,VVSE(S)
HAS BEEN UPPED OR REMOVU). IFTHESE PROCEDUP.ES HAVE NOT BEBN mLLOWZD AND THE EPUT,OUTPUT
POWER Is LlvE SERIOUS PERSONNELINJURY OR DEATH MAY OCCUR.
A RACWSHELF MAY CONTm SEVERAL OPERATING SYSTEMS. IF THERE IS ANOTHER SYSTEM IN THE GENERAL
AREA YOU WANT TO INSTALL THIS SYSTEM. BE CAUTIOUS OF ANY EXPOSED CONNECTORS OR WIRE.5 AND. WITH
PERMISSION. REMOVE POWER TO THE OTHER SYSTEMS. FAILURE TO TAKE THE NECESSARY S-PRECAUTIONS
SUBJECTS THE INSTALLER OR MAINTENANCE PERSONNEL TO SEVERE ELECTRICAL SHOCK THAT MAY CAUSE
SERIOUS INlURY OR DEATH.
8.
ENSURE AU AC INPUT Ls DISCONNECTED (BOTH LEGS).
9. I
I
THIS EQUIPMENT MAY CONNECT TO LEAD-ACID BATTERIES. BATIERY POSTS. TERMINALS. AND RELATED
ACCESSORIES CONTAIN LFAD AND LEAD COMPOUNDS. CHEMICALS KNOWN TO THE STATE OF CALIFORNLA TO
CAUSE CANCER AND BIRTH DEFECTS OR OTHER R!ZPRODUCIIE HARM. WASH HANDS AFl??R HANDLING.
CAUTIONS
1.
2.
IF CONNECITNG BATTERIES. REMOVE THE BAITERY BOX FUSE OR TRIP THE CIRCU,T BREAKER AND REMEMBER
THAT THE POLARITY Is CR7CAL TO AVOID DAMAGE TO THE SYSTEM. CHECK BATlERIES AND CONN!ZCONS FOR
PROPER PoLxwu AND mwR BEmRE CONNECTING THE BATTERIES TO THE SYSTEM.
3.
TO REMOVE THE CIRCUIT BREAKERS OR FUSES. BOTH THE DC AND AC INPUT TO THE SYSTEM W,LL NEED TO BE
DISCONNECTED. THEREBY DISABLING THE SYSTEM OUTPUT TO THE LOAD(S). TAKE THE NECESSARY
PRECAUTIONS AND IMORM THE PLANT ENGINEER THAT THE SYSTEM OUTPUT POWER TO THE LOADS WILL BE
DISABLED.
4.
5.
FUSE HOLDERS AND FUSES ARE TO BE LOADED TO 80 PERCENT OF THEIR AMPERE RATING.
PERFORM,NG
ANY MAINTENANCE.
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
GENERAL
The paragraphs that follow contain information that is intended to help the user with the understanding of the 1Cil
Amp Modular Rectitier Systems (system) operation. The system is configured with two Rectifier Modules to
produce either 100 Amps or 50 Amps redundant. It includes a Distribution and Alarm Panel with Battery
Disconnect. Included are paragraphs that explain the system description, standard features, modules. configuration
arrangement, and shelf dimensions.
1.2 SYSTEM DE%XIPTION
The 100 Amp Modular Rectifier Systems (system) is a modular design rectifier system capable of providing either
100 amps or 50 amps redundant utilizing a single DC bus output via the four distribution circuit breakers on the
front of the system. The system operates from 184-264 VAC, 45-60 Hz individual AC input from the AC Power
Service Cabinet to the individual Rectifier Modules via a connection on the rear of each Rectifier Shelf.
Each modular rectifier can be hot inserted. meaning the rectifiers can be removed or installed without shutting down
the entire system provided proper start-up procedures are used. In addition, the system can be operated with or
without batteries and comes supplied with single DC Distribution, an output voltage adjustment (float and equalize)
on the Rectifier Modules, Low Voltage Disconnect (L.VD) and Pick Up (LVFU). HV and LV adjust, Battery
Disconnect, and alarm capability via the DC Distribution and Alann Panel.
13 STANDARD FEATURES
The system comes with many standard features. These features are detailed in the following paragraphs.
1.3.1 FRONT ACCESS
The system has been designed to allow the user total front access to all controls and indicators.
1.32 SIMPLE CONFIGURATION
The system is configured for up to 100 amps or 50 amps redundant.
1.3.3 HOT INSERTION
Rectifiers can be removed/installed without shutting down the entire system provided proper start-up procedures
are followed.
1.3.4 INPUT PROTECTION
Primary input protection is provided by the customer. All input lines need to have protection.
13.5 OUTPUT PROTECTION
Over voltage protection is provided in each rectifier. Should the DC output go above the preset limit the faulty
rectifier is automatically shut down.
1.3.6 LOW VOLTAGE DISCONNECT (LVD) AND LOW VOLTAGE PICK-UP (LVPU)
The system comes equipped with Low Voltage Disconnect (LVD) and Low Voltage Pick-up (LVPU) circuitry. If
the load power is being supplied by the batteries but the battery output is no longer sufficient to power the load(s)
and reaches the LVD setpoint. the system will shut down the output to the load(s) to protect the batteries. This
LVD shutdown is factory set to -42 VDC, however there is an adjustment potentiometer on the front of the
Distribution and Alarm Panel to adjust this setpoint.
The Low Voltage Pick-up (LVPIJ) feature senses when the batteries have recovered and are. capable of providing
the load power. This LVPU is factory set to -49 VDC, however there is an adjustment potentiometer on the front
of the Distribution and Alarm Panel to adjust this setpoint.
In addition, there are test points and aTEST switch that allows these setpoints to be adjusted without taking the
plant off-line as the potentiometers for LVD and LVPU are set. It is recommended that whenever LVD and
LVPU are adjusted, the TEST switch located directly above the LVD and LVPU potentiometers is moved to the
TEST position (Amber TEST lamp illuminated). It is just as important to remember to move this switch away
from the test position back the system on-line position after the potentiometers are adjusted. Refer to the
adjustment procedures in Section VI.
13.7 LOW VOLTAGE AND HIGH VOLTAGE SETPOINTS
The system comes equipped with Low Voltage and High Voltage circuitry. If the system output were to go
above(factory
set at 57.0 VDC) or below (factory set at 49.0 VDC) the setpoints, the system would shutdown and
the loads would be transferred to the batteries (if available).
In addition, there are test points and a TEST switch that allows these setpoints to be adjusted without taking the
plant off-line as the potentiometers for I-IV and LV are set. It is recommended that whenever HV and LV are
adjusted, the TEST switch, located above the HV and LV indicators and potentiometers, is moved to the TEST
position. After the HV and LV potentiometers are adjusted, moving the TEST switch ot of TEST will enable the
HV and LV circuits at the adjusted value. Refer to the adjustment procedures in Section VI.
1.3.8 RECTIFIER MODULE INDICATORS
The types of indicators located on the Rectifier Module are as described in the following paragraphs:
1.3.8.1 AC ON INDICATOR
A green AC ON LED, located on the front of each Rectifier Module, will illuminate when AC input voltage is
present.
1.3.8.2 RECTIFIER FAIL
A red Rectifier Fail Alarm (RFA) indicator, located on the front of each Rectifier Module, will illuminate if any
condition occurs which disables the output of any Rectifier Module in the shelf. Conditions which result in a
RFA are as follows:
A. Complete loss of the AC input voltage.
B. Rectifier output voltage exceeds the high voltage shutdown point.
C. Any failure condition that disables the rectifier output.
I
I
I
I
I
I
I
I
,I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
~1
I
I
I
I
I
I
POWER ON
A green Power On (PWR ON) indicator will illuminate whenever there is DC power available.
PRIMARY
There is a normally closed loop located on the rear of the system on the alarm terminal block that is provided to
connect an external temperature sensor. The sensor connects between tbe NC and common terminals. If the
external sensor senses a high temperature condition, the loop opens and the system will shut down. Typical
applications would be ambient air temperature sensing in a hut environment or remote plant control. These
contacts are jumpered at the factory between the NC and common terminals and the jumpers should be left in
place if they are. not be used.
1.4
I
I
I
I
I
I
I
I
I
1~
1~
I
I
I
I
I
I
I
I
S YS TEM COMPONENTS
The system is comprised of.two primary components consisting of the DC Distribution and Alarm Panel and the
Rectifier Shelf and Modules. A brief descriptiori of each follows. For a more detailed description and theory of
operation of the components, refer to Section VII, Theory of Operation.
1.4.1 DISTRIBUTION AND ALARM PANEL
The Distribution and Alarm Panel provides the DC distribution via circuit breakers wired to individual bus bars
and plant alarm interfaces via a connection on the backplane. DC output connections are dual DC crimp type lugs
and the plant alarm interface is provided via .a pressure type terminal block. Table I-l includes the alarms. The
panel also includes the system adjustment pots and test points to be used during system adjustment or test.
Additionally, the panel also includes the battery disconnect switch and ABS fuses.
1.4.2 RECTIFIER SHELF
The Rectifier Shelf is designed to house up to two 50 amp Rectifiers each. The system has been designed to
provide a total of 100 amps output or 50 amps redundant. dependant on power requirements.
I1
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
Abbrev.
LVD
Cause
Output Voltage
<42 VDC
Generated BY
Distribution/
Alarm Panel
StandardlOmional
Standard
Output Breaker/
Fuse Open
BKR
OPEN
Any Output
BreakWElec.
Trip Only
Distribution/
Alarm Panel
Standard
AC Fail
AC FAIL
AC Failure
Rectifier Module
Standard
Low Voltage
LV
Output Voltage
~49 VDC
Distribution/
Alarm Panel
Standard
High Voltage
I-IV
Output Voltage
257 VDC
Distribution/
Alarm Panel
Standard
RF Major
RF MAJOR
Rectifier
FailWZS
Rectifier Module
Standard
12
13
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
This section is provided to detail the specific input and output power required or provided by the system. Included
are input requirements, output ratings and various other signals that are required and/or provided by the system.
2.2 INPUT POWER REQUIREMENTS
The input voltage required is single phase 184-264 VAC, 45-60 Hz, individual feed to the Rectifier Modules.
2.2.1 INPUT ELECTRICAL CONNECTIONS
The rectifiers are configured for individual AC~input to the rectifiers via the terminals on the back of the system.
2.3 OUTPUTRATINGS
The output rating of the system is dependant on the configuration. The system has a maximum power output of
either 100 Amps or SO Amps redundant.
2.3.1 FLOAT REGULATION
Float Regulation voltage is factory set at 54.00 VDC for all conditions of AC input and loads from 0 to 100 Amps.
2.3.2 EQUALIZE SETlTNG
Output current is dependant on the number of Rectifier Modules equipped. Each rectifier is capable of providing
up to 50 Amps, maximum system output is either 100 Amps or 50 Amps redundant.
14
CtX.l
Efficiency
Recommended
AC Breaker
40 Amps (264 Feeder VAC), per system (2 Rect. Modules); 20 Amps Individual; 2-P&
Circuit Breaker
Float Voltage
Equalize Voltage
Hv
LV
LVD
Current
50 Amps per Rectifier Module. The Modules are placed in parallel for a maximum
output current of 100 Amps (DC Nominal)
Regulation
<O.l%line
<O.l%load
At 0 - 100% load
15
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
N&e
<
<
<
<
Filtering
32 dBm-c when connected to batteries with an AH rating of four (4) times the load
current
Size
System Shelf: 19.0 in. wide x 8.00 high x 17.75 in. deep (System Max. Dimensions
Given)
MOUtltig
Weight
Temperature
Altitude
Cooling
Humidity
85% Non-condensing
Shock
This equipment, in its shipping container, withstands shock developed during shipping
without physical damage or degradation of the electrical performance.
Vibration
Heat Dissipation: Nominal input with output adjusted for 54.00 VDC.
Modules
Shelf Amps
BTU/HR
100
3280
Ventilation
System Ventilation openings should not be blocked and the ambient temperature of the
air entering the system should not exceed 50C (122F).
16
Terminal Type
PreSSWe
20 GA
T~llIlillZd
Capacity
16-6 GA
Terminal Type
#IO Lug
10 GA Minimum
Terminal Type
4 GA-500 MCM
Recommended Wire
Size
l/O GA Minimum
Table 3.4. System 48 VLK Output Terminals (Ground and -48 VDC)
Terminal Capacity
Terminal Type
8-2 GA
Recommended Wire
SiZ.2
8 GA Minimum @ 50
AllIPS
*Output breaker size is dependant on load(s). Maximum of 50 amps per breaker position. In addition, output
breakers should he max. loaded to 80% of the CB rating.
Table 3-5. Rectifier Commercial AC Input Terminals
17
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
II
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
stzE%continued
Note: Wire sizes are based on the voltage drop considerations and the National Electric Code Table 310-16 for
copper wire.
&t&5: A terminal block is provided for Battery Load. GRD Return Leads require dual hole lug terminations
connecting to the +BAT BUS BAR.
-6: Installation of the system should be in an area that is accessible to qualified personnel only.
Note: The bay the system is to be installed into must be secured to the building structure before the equipment can
be operated.
Note:. I?stallation of the system should be in an area that is accessible only to qualified personnel.
3.4 SYSTEM INSTALLATION
(See figure 3-l and the installation prints cont&ned
The paragraphs that follow contain the necessary procedures to install the system. The system can be rack or wall
mounted and can be utilized with or without a battery box.
3.4.1
PRE-INSTALLATION
CHECKS
(3) Inspect the equipment. Note any shipping damage, if present, aad immediately notify the carrier and
PECO II at the numbers listed at the front of this manual. It is recommended that if there is shipping
damage photographs be taken of the damage.
(4)
Take an inventory.
B. The system list number that was ordered will be internally wired at the factory. The only wiring that will be
connected by the installer is the -48 VDC output to the loads (maximum four breaker locations, or bulk), AC
individual input to the Rectifier Modules, alarm wiring to customer famished external alarms (if required). and the
battery box connection to the positive and negative bus bars.
C. Ensure the system matches the order that was placed.
D. Determine the installation location and input power location to be used by the system.
E. The system has been configured for 184-264 VAC. 45-60 Hz it%48 VDC out.
I8
3.42 INSTALLATION
A. Install the system as follows:
(1) Install the mounting brackets as required for flush or relay rack mounting.
(2) Ensure there is proper clearance in the rack to install the system.
(3) Put the system into position and secure with the screws located at each mounting bracket (four screws
equally spaced each side recommended). Remove the cover that coven the bonom two screws. Install the
cover after the system is secured to the rack.
(4) Trip the AC plant input circuit breaker(s) or remove the input fuse(s), and, if equipped, the -48 VDC
battery Box interface circuit breaker or remove the input fuse.
(5) Trip the system OUTPUT breakers.
B. Gain access to the back of the system and remove the screws that secure the Rectifier Shelf rear access cover.
C. Connect the -48 VDC load(s) to the bus bar (from the Circuit Breakers CBl tbm CB4, as required) on the rear
of the Distribution and Alarm Panel with dual hole II4 on 0.62 in. style lugs. Up to four loads can be connected,
however the maximum breaker size per position is 50 amps. Secure the output wires to the DC lugs with the
bolts. Recommended wire and terminal sizes are listed in the tables at the front of this section.
D. Use dual hole l/4 on 0.62 in. lugs and connect the DC Load Ground(s) to the +BAT Bus Bar with the two
bolts. The +BAT Bus is clearly identified.
Note: In the following step, NEC requires that all AC wires are not exposed. It is required that all AC wires be
run thru conduit. Dependant on local codes, all power wires may need protection. Before you connect the
system, it is advisable to check with the Plant Engineer or local authorities to review local codes regarding types
of conduit and protection. If acceptable. flexible conduit is recommended. In addition, NEC also requires that all
AC and DC wires must be segregated from one another and the alarm wires must exit from the DC side.
E. Place the commercial AC individual input power through the outer case access port. Place the commercial
power to the LINE l(Ll), LINE 2 (L.2). and Ground (GR) terminals of the Input Tetination Terminal Block,
connect as required. Secure the wires to the terminal block with the screws. Recommended wire, circuit
breaker/fuse, and terminal sizes are listed in the tables at the front of this section.
F. Place the Chassis Ground wire to the CH GROUND location on the right, rear of the chassis, aft looking
forward at the terminal provided. Secure the wire to the post with the nut and washers. Recommended wire and
terminal sizes are listed in the tables at the front of this section.
I9
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
SYSTEM
INSTALLATION-continued
C. Connect the Plant Alarm Interface. Recommended wire size is listed in the tables at the front of this section.
Run the alarm interface wires, as directed by the Plant Engineer, through the outer case access port. Connect the
alamw from the interface on the rear of the Distribution and Alarm Module to the plant interfaces as follows:
: The Alarm Terminal block (TB I) is clearly marked as to the Form C contacts for NC, NO, and C.
(1) Connect the Low Voltage Disconnect alarm to the alarm interface terminal block marked LV DISC on
the rear of the system.
(2) Connect the Breaker Open alarm to the alarm interface terminal block marked BKR OPEN on the rear
of the system.
(3) Connect the AC Fail alarm to the alarm interface terminal block marked AC FAIL on the rear of the
system.
(4) Connect the Low Voltage Alarm to the alarm interface terminal block marked LV ALARM on the rear
of the system.
(5) Connect the High Voltage Alarm to the alarm interface terminal block marked HV ALARM on the r&r
of the system.
(6) Connect the Rectifier Fail Major alarm to the alarm interface terminal block marked RF MAJOR on the
rear of the system.
(7) Connect the external high temperature shutdown from an external senssor to the HI TBMP contacts on
the alarm interface terminal block. There is one available position that is jumpered at the factory to
maintain a closed circuit (system shuts down with an open). If no sensor is to be connected, leave the
jumper installed.
H. If a Battery Box is to be connected to the system, proceed as follows:
(1) Connect the Battery interface to the System 48 VDC Battery Bus Bars. For the purpose of this
installation, it is recommended that the GRD is connected prior to connecting the -48 VDC. After the
ground is connected, connect the -48 VDC to the system with the lug located behind the bus bar. This will
give the rear cover enough clearance to be installed. Use dual hole 318 on I.0 in. style lugs. Secure the
leads to the - BAT and + BAT Bus Bars with the hardware provided. Refer to the tables at the front of this
section for recommended lug and wire size.
I. Ensure all leads are terminated with the correct polarity, there are no loose connections or shorted leads, and
there is unrestricted airflow through the unit.
J. Install the system rear cover and secure. it to the system with the hardware provided.
K. Perform the Operational Checkout Procedure (paragraph 3.5).
3.5 OPERATIONAL CHECKOUT
Perform tbe operational checkout of the system per Section VI. Operational Checkout and Troubleshooting.
20
BaTIN,
_-__-_
__-___--A----
I
I
I
I
I
I
21
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
22
The system is modular in design and the Rectifier Modules are easily installed. This section gives the procedures
necessary for the installation of the system components that are repairable by field service technicians. The removal
of these components is covered in Section N, Module and Parts Removal.
Only the Rectitier Modules and the output circuit breakers can be removed and installed from/to the system. For
any other system errors, contact PECO II Field Service at the numbers listed in the front matter of this manual fox
repair.
5.2 INSTALLING A MODULE
MODULE INSTALLATION
I-
B. Ensure the AC circuit breaker in the AC Power Service Cabinet and the DC circuit breaker for the rectifier
were set to OFF.
C. Install the module into position and apply even pressure across the face of the unit until the connector is fully
engaged to the backplane. The module should slide into position with little resistance.
D. Tighten the module holding screws (three screws total).
E. Perform the operational checkout located in Section VI.
5.3 OUTPUT CIRCUIT BREAKER INSTALLATION
Install the Output Circuit Breakers on the Distribution and Alarm Panel as follows:
A. If not already accomplished, trip the system AC feed circuit breaker or remove the input fuse(s) at the AC Power
Service Cabinet.
B. If not already accomplished and if equipped with a battery box, set the DC Battery Disconnect switch on the
front panel to remove the charging circuits. The indicator lamp should come on
C. Ensure the system has the power removed.
23
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
1~
1~
I
I
D. Install the circuit breaker into position and push to secure it to the circuit breaker bus bar.
I
E. Install the front access cover and secure with the screws.
F. The installation is complete. Perform the Operational Checkout in Section VI.
I
I
I
I
I
I
I
I
I
I
I
I
I
I
24
OPERATIONAL
CHECKOUT
The following procedure must be followed after installation OT performing any maintenance to the system.
6.2.1 Complete Operational Checkout
6.2.1.1 Initial Turn-On and System Output Voltage Adjushnent
A. Put the ALARM TEST switch, located on the front of the Distribution and Alano Panel, oat of the test
position 0XST LED not illuminated).
B. Ensure the AC power from the AC Service cabinet is not engaged and if not already accomplished, trip the
DC circuit breaker directly below each Rectifier Module.
c. Remove the Rectifier Modules from all but the fmt position
D. If not already accomplished, insert a Rectifier Module into the lint position on the mounting shelf.
E. Ensure the rectifier module is f&y in place.
F. Turn the AC Power Service Cabinet circuit breaker for the Rectifier Module in the first position to ON.
2.5
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
,I
I
;I
I
I
~1
I
I
I
I
I
&&: The following steps are used to adjust the plant float and equalize, set point voltage to a setting different
than the factory settings.
H. Float and Equalize adjustments. Adjust the plant Float and Equalize settings by using the steps that follow.
If tbe Float or Equalize factory settings are acceptable, go to paragraph G.
Note: There is a slight difference between the bus voltage and the actual output of the Rectifier. Do not use tbe
voltage reading from the Rectifiers digital meter. Set a Fluke digital multimeter on the front panel set to read
~60 VDC. Use Ihe voltage reading from the Testpoints GRD and -BAT on the front of the Distribution and
Alarm Panel.
1. Wbile.watching Fluke digital multimeter,,adjust the plant float voltage using the float adjust pot located
on the front panel of the Rectifier Module. Adjust the voltage to the value determined by the Site Engineer
(LocaI Engineer).
&&: When the plant float and equalize voltage is set to a value higher than the factory setting, it is likely
that the HV abum indicator on the front panel of the Distribution and Alarm Panel will illuminate and the
Rectifier output will not be available. If an HV condition does come on, you will need to adjust the HV
circuit of the Rectifter Module per paragraph 6.2.2. before proceeding and reset the AC circuit breaker(s)
located within the Power Service Cabinet to reset the Rectifier Shelf.
2. Identify the new float voltage setting on the front of the plant.
3. Adjust equalize voltage (high charge) to the value as determined by the Plant Operator as follows:
a. Repeat step 2.a and 2. b. above, except set the Float/Equalize switch. located on the front of the
Rectifier Module, to the Equalize position.
4. After changing the equalize voltage on the Rectifier Module, return the Float/F.qualize switch to the
Float position.
I. Remove AC power at the Power Service Cabinet and trip the DC circuit breaker located just below the
Rectifier.
J. Remove the Rectifier Module in position number one and install another Rectifier Module in position
number two (Rectifier Module not previously adjusted).
K. Repeat steps E., F., G.. and H. for the remaining Rectifier Module, excluding do not perform paragraph F.
step 2.a. thm 2.d. if the Rectifier Module Float and Equalize voltage do not require adjustment.
L . Ensure both the AC and DC circuit breakers are in the OFF position and then install all Rectifier Modules
into the shelf.
M. Ensure all rectifiers are firmly in place.
N. Repeat step K. for the Rectifier Modules in position number two.
0. Turn the AC circuit breaker(s), located in dte AC Power Service Cabinet, to the ON position until all the
Rectifiers within the system come on line.
26
P. Apply the load(s) to the system by setting the load circuit breakers on the DC Distribution and Alarm Panel.
&&e: There is a slight difference between the bus voltage and the actual output of the Rectifier. Do not use the
voltage reading from the Rectifiers digital meter. Set a Fluke digital multimeter on the front panel set to read
~60 VDC. Use the voltage reading from the Testpoints GRD and -BAT on the front of the Distribution and
Alarm Panel.
Q. With the digital multimeter set to read <60.VDC, measure the system output voltage on the Testpoints GRD
and -BAT on the front of the Distribution and Alarm Panel. Output voltage should read whatever the value the
system has been adjusted to (factory setting is 54.00 VDC).
R. If the Float Adjust pot was adjusted, ensure the AC ON indicator located on the front panel of each Rectifier
Module is illuminated and the Rectifier Fail Alarm (RFA) is not illuminated. Also ensure no fail indicators are
illuminated on the Distribution and Alarm Panel.
S. The system is operational. Continue with the operational checks of the system.
6.2.1.2 AC FAIL TEST
Note: Assumes fully charged batteries and that the loads are connected.
A. Remove the AC input fuse or trip the circuit breaker at the AC service cabinet to the system.
B. All Rectitier Module AC ON L.EDs (green) will go off.
C. The RFA LED (red) on the Rectifier Modules and Dishibution and Alarm Panel will come on and the
Form C contact on tbe alarm terminal block located on the rear of tbe system will change state.
D. There should not be a disruption of the loads.
E. Restore the AC power to the system by inserting the fuse OT setting the circuit breaker at the AC service
cabinet. The system should return to normal operation.
6.2.1.3 DL5TRlBUTION FUSE ALARM TFST
The System is equipped with electrical trip circuit breakers only. Tripping the circuit breaker on the front panel
will not cause tbe Form C contacts to change position or cause the front panel indicator to illuminate. The Form
C contact change (electrical trip) and DFA indicator has been tested at the factory for proper operation.
6.2.1.4 FUSE ALARM TEST
A. Remove the fuse on the front of the Distribution and Alarm Panel. The power lamp will go out and the
DFA on the front panel will illuminate. In addition, tbe RF Major alarm will change state.
B. Insert the fuse. The system should return to normal operation.
27
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
28
E. While watching the voltage meter, adjust the TEST ADJ potentiometer to the desired LV PICKUP setting.
F. Adjust the LV PICKUP potentiometer until the LVD lamp goes out and immediately stop. The LV PICKUP
setting is adjusted to the value set by the TEST ADJ potentiometer in step E.
G. On the front of the Distribution and Alarm Panel, put the ALARM TEST switch back in normal system
operation. The TEST LED should go out. The pickup and dropout setpoint adjustments are complete and the
system should return to normal operation.
6.2.4 COMPLETION OF TESTS
If the Initial Turn-on and operational checks are complete and the system is operating properly, the tests are
complete. Perform normal clean up, collect all tools. and close all access doors, ect. If there was a problem with
the test and acceptance procedures, it is advisable to call PECO II Field Service at the numbers listed at the front
of this manual.
6.3 TROIJEILESHOOTING
Troubleshooting of the system is limited to performing the start-up and operational checks. If further assistance is
required, contact the PECO II Field Service at the numbers listed in the front matter of this manual.
Whenever a malfunction occurs, tint look for the obvious fault. Try to find out whether is caused by the system or
by its environment (e.g. temperature, humidity or load). In addition, there may be other situations such as:
A. Input Voltage is missing/ not at the correct level.
B. Input and Output connections are not securely fastened.
c. Coectors are not secure.
D. Blown fuses.
E. Tripped circuit breakers.
Always check these external factors before concluding that your inverter system is faulty. If, for instance, the unit
stops due to overheating it may have been overloaded, the ambient temperature may be too high, the ventilation slots
could be blocked or a cooling fan may be out of order.
29
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
~
~
11
I
:I
I
,I
I.
I
I
I
I
I
I
I
I
I
I
I
I
I
30
VIII
SYSTEM
CONFIGURATIONS/PARTS
LIST
8.1 GENERAL
This section gives the complete parts listing of the system for the components that are repairable at the field level.
Available systems are identified by a conftguration
model code (CC) alpha assignment. Each component as
identified on the parts list has the configuration model code character assigned. In many cases the parts are used on
all systems produced by PECO II. If the component is used on all systems, the configuration model code will have a
dash.
Indenture Code (IC) on the parts list refers to the level of indenture of a part as compared to the assembly. For
example, an assembly may have several subassemblies. Under the subassemblies there may be parts associated with
that subassembly. In this example tlwassembly would not have an indenture level since that is the main component.
The subassembly would be indenture level I. The pat% that make that subassembly would be indenture level 2.
As Required (A/R) in the Quantity (QTY) column implies that the part may be used more than once and is
dependant on the operator. In addition, if a dash precedes an Item Number (i.e., -10) that item is used by the
assembly but is not referenced in the illustration.
8.2 CONFIGURATIONS
The system is Configuration A
TABLE 8-1. System Parts Listing
Item No.
-I
Nomenclature
System
cc
A
-10
SM50F48PM
Rectifier Module,
48V, 50A
on
(2.2)
-20
3050076P-50
Output Circuit
Breaker, 50 Amps
31
AIR
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
Al-l-ACHMENTS
32
I
I
4380084PD
Issue 1, Nov 1996
Page 1 of 15
I f2
i%
Iz
:
POWER DATA
for
RECTIFIER MODULE
SM50F48PM (-48V)
(As Used with 6875009BLK-62)
I
I
I
I
I,
I
1.0
SPECIFICATIONS
438
0084PD
2.0 INSTALLATION
<ng
D.D.
Galion, Ohio
Lppr
D.D.
Printed in U.S.A.
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
4380084PD
Issue 1, Nov 1996
Page 02
TABLE OF CONTENTS
DESCRIPTION
1.0 SPECIFICATIONS
1.1 GENERAL
1.2
INPUT RATINGS
OUTPUT
RATINGS
1.3
1.4 MECHANICAL SPECIFICATIONS
~1.5 STANDARD FEATURES
1.6
FACTORY SETTINGS
1.7 ENVIRONMENTALSPECIFICATIONS
1.8 RECTIFIER SHELF
2.0
2.1
2.2
2.3
2.4
2.5
2.6
INSTALLATION
GENERAL
AC INPUT CONNECTIONS
OUTPUT CONNECTIONS
INITIAL TURN ON
ADDING/REPLACING A RECTIFIER.
REMOVING A RECTIFIER
4380084PD
Issue 1, Nov 1996
Page 03
1.0
SPEB
1.1
GENERAL
Rectifier Module (SMSOF48PM) is a -48 VDC @ 50 Amp self
contained unit. The Rectifier is a fully regulated, DC
isolated output switchmode Rectifier designed to charge
batteries. while supplying power to telecommunication.
equipment.
The Rectifier can also operate as a Battery Eliminator not
requiring-external
batteries.
The Rectifier is of modular
.design for easy upgrading or replacement in a shelf
configuration.
-
9
237.74mn
SM50F48PM
FFIONT VIEW)
I
I
I
I
I
I
I
I
I
I
I,
1~
1~
I
I
I
I
I
I
4380084PD
Issue 1, Nov 1996
Page 04
I
1.2
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
INPUT
RATING8
A. VOLTAGE:
176-265 Volts AC
57-63 Hz (Single Phase).
B. CURRENT.AT
NOMINAL OUTPUT:
D. EFFICIENCY:
88% TO 90% 50-100% Load
54.5 VDC @ 50 ADC.
F. INTERNAL PROTECTION:
Fuse (20A) in series with AC Input Line.
field replaceable.
Volts
I.T.
SM50F48PM
230
500
TABLE A
4380084PD
Issue 1, Nov 1996
Page 05
1.3 OUTPUT RATINGS
A. VOLTAGE:
Float Adjust:
Minimum 50 to 55 VDC.
PROTECTION:
1. output: Electronic Current Limit limits the,output
current to 51.0 Amps or 102% of rated output.
(Factory setting)
2. Short Circuit: Electronic Current Limited
(Internal fuse if the electronic
current limit fails).
C. REGULATION:
1. Static:
millivolts
peak-to-peak
I
I
I
I
I
I
I
I
I
I
I
y
I
I
I
I
I
I
I
I
I
I
I
I
1
I
I
I
,I
~1
I
I
I
I
I
I
I
I
4380084PD
Issue 1, Nov 1996
Page 06
1.4
MECHANICAL SPECIFICATIONS
A. HEIGHT:
9.36 Inches
237.74 mm.
B. WIDTH:
5.10 Inches
129.54 mm.
C. LENGTH:
13.00 Inches
330.20 mm.
D.
18.00 Lbs
WEIGHT:
1.5 STANDARD
8.16 kg.
FBATUREB
CURRENT WALE-IN
Upon 10turn-on'* of the Rectifier, the output current will
gradually increase to it's required output load in
approximately eight (8) seconds.
E. ME TER (DIGITAL)
Selectable Voltmeter/Ammeter,
a c c u r a c y i s f18.
F. OVER TEMPERATURE
Rectifier will shutdown due to an internal over temperature
condition.
This could be the result of a fan failure or
other abnormal condition.
G. AIARM INDICATION
Any condition resulting in Rectifier failure, including AC
'%.u-n-off11 or a "fan failure" will provide a signal to the
Office Alarm terminals and will light the RFA LED (Red),
located on the front panel.
4380084PD
Issue 1, NOV 1996
Page 07
1.6
FACTORY
SETTING8
1.7
54.48 VDC
(2.27V per cell for 24 cells).
55.40 VDC
(2.3OV per cell for 24 cells).
C. CURRENT.LIMIT:
58.00 VDC.
ENVIRONMENTAL
SPECIFICATIONS
C. COOLING:
Forced Air - Keep ventilating passage ways to the unit
unobstructed to insure adequate cooling during
operation.
Otherwise over temperature
protection alarm may be activated.
1.8
RECTIFIER
SHELF
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
1
I
4300084PD
Issue 1, Nov 1996
Page 08
2.0
INSTALLATION
2.1 GENERAL
The Rectifier's Input and Output connections are plugable
connectors for the purpose of paralleling and "HOT" Insertion into a working
system.
2.2
AC
:INPUT'CONNECTIONS
GRD).
Ll MODULE "A"
m
MODULE "8"
m
SM50F48PM
(REARVEW)
4380084PD
Issue 1, Nov 1996
Page 9
2.3 OUTPUT CONNECTIONS
Alarms and Control leads enter the unit along with the power
contacts at the lower rear panel of the unit.
The Power and Alarm & Control
pins and their function are described as follows:
A...OUTPUT'POWER'CONNECTIONS.
(+I
Positive.Power
(ltB@l Module):
Output connection.
l234567-
Module):
Vacant
Vacant
Vacant
Vacant
Vacant
Vacant
Vacant
ll- CLSO
CONTROLLED LOAD SHARE lead. When connected
between other like Rectifiers Modules will Load Share within 22% of rated
load.
12- RFA-NO
RECTIFIER FAILURE ALARM (RFA).
These leads
13- RFA-COM are from a set of relay contacts called
14- RFA-NC
"Form C" contacts.
The RFA relay alarm
contacts are shown in their alarm state
(De-energized).
Relays release on alarm
conditions, alarm circuits are energized in
their "Normal" no alarm condition.
I
I
I
I
I
I
I
I
I
I
1~
I
I
I
I
I
I
I
I
4380084PD
Issue 1, Nov 1996
Page 10
2.3 OUTPUT CONNECTIONS (Cont)
I-
15- VI
CURRENT MONITOR lead is provided for Remote Monitoring of
the Rectifier's output current.
A 1.0 volt/lO.O Amp current signal
referenced:to.~the NegativetSense lead is provided for use with
a
remote;.Monitor,inq~System;:
16- Vacant
I
I
I
I
I
I
I
I
I
I
I
19- RHV
REMOTE HIGH VOLTAGE lead will accept an external
If the Rectifiers output
high voltage signal (Battery) from a system.
current is more than lo&, this signal will shut down the Rectifier Module.
iO- RM-EQ REMOTE EQUALIZE lead will accept an external
equalize signal (Ground) from a system controller or other external system to
raise the plant battery voltage for the purpose of battery maintenance.
4380084PD
Issue 1, Nov 1996
Page 11
2.4
INITIAL TURN ON
_.
-..:B.~;'Makesure:that:the:Output
Circuit Breaker, located on shelf
below the .Rectifier, for.the-new Rectifier is "OFF".
C.- Insert.the new Rectifiersinto
.
,:
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
II
I
4380084PD
Issue 1, NOV 1996
Page 12
2.5 ADDING / REPLACING A RECTIFIER
When adding / replacing Rectifiers to a "working" system,
proceed as follows:
A. Decide where the new Rectifier Module will be added.
-.B::..,Remove:the.:blank filler'panel where the new Rectifier
will be.inserted..~
I_...
:.
,.
:.i
.,
.,
:.
I
I. The Rectifier will turn "ON".
The GO LED (Green) will
.~ light..!-Then.-digital:meter
will indicate.the output voltage with the SELECT
I switch.-in.the ?V! (Volts) 'position.
The..FloatVoltage ~is::adjustable.using
the FL (Float- Adj)
I pot,J..located
on.the, front panel of.the Rectifier.
NOTE: Before making adjustment of the FL (Float Adj) pot,
A clockwise (CW)
operate
switch to the **FLOAT@' position.
I directionFLOAT/EQUAL
will increase the Float Voltage and a counterclockwise (CCW)
direction will decrease the Float Voltage setting.
I
K. The Equalize Voltage is adjusted after the Float Voltage is
set.
The Equalize Voltage is adjustable using the EQ (Equalize Adj) pot,
located on the front panel.
Before making adjustment on the
EQ (Equalize
I Adjust)
pot, operate FLOAT/EQUAL switch to the "EQUAL1* position. A clockwise
(CW) direction will increase the Equalize Voltage and a
counterclockwise (CCW) direction will decrease the Equalize Voltage setting.
I
L. Return FLOAT/EQUAL switch to the "FLOAT@' position.
the CAP CHARGE switch for five (5) seconds,
I then M.turnPress*'ON"andtheholdOutput
Circuit Breaker/switch.
The Rectifier is now in
"service".
I
I
4380084PD
Issue 1, Nov 1996
Page 13
2.6 REMOVING A RECTIFIER
When removing Rectifiers from a "working" system, proceed as follows:
A. Decide what Rectifier needs to be l'removed'*.
B.~ Turnthe STANDBY/ON switch, located.onthe front of the
:
: . Rectif~ier,::to? the'-"STARDBY1'. position..
for
CL Turn. ?OFF'*the.AC~~Circuit~
Breaker, located. on the Shelf,
the,~,Rectitier~ being "removed!':. "
D.;..:I~Turn:.:.?OFF,!5~:.the.~
Output:.Circuit,.:Breaker,~
below
the.:Rectifier::
located on shelf.
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
4380084PD
Issue 1, Nov 1996
Page 14
II
I
.._~I
...er..J.
3.1 GENERAL
The Rectifier features,
Rectifier, are as follows:
:I;:
II
NOTE:. The.~Current:TestPointOsignal
signal.
B. TEST-LED (Amber) will light when the Rectifier has an
~p,e~ (-) Negative Sense lead.
I
I
I
~
~1
"stand-by"
condition.
.F.. EQUALIZE- ADJUST' pot is. used .to adjust the equalize
r.voltage output.of:.the Rectifier. I'
~ I-
I
I
I
I
I
"A"
4380084PD
Issue 1, Nov 1996
Page 15
3.2 FLOAT/EQUALIZE VOLTAGE ADJUST
Operate the "STANDBY/ON" switch, located on the Rectifier, to the
l'STANDBY1* position. Operate the Rectifier Shelf Breaker/Switch to the **OFF11
position... .Now operate the "STANDBY/ON" switch to the "ON" position.
A. .The Float Voltage-is.adjustable:using.the FLOAT ADJ (FL).
-.:~.pot,.-;located~~on...the~frontl-panel..of~r..the:..Rectifi;er..
-:
.:~z%:I? . ..~.~::-=:NOTE-:~:Before~~.making--adj,ustment:of.'-the FLOAT ADJUST;'(
1~~pat~~~~opeltatep,F~AT~EQUAL~:switch
'.to. the: ."FLOAT" position:::.A clockwise' (CW)
-._
-~direction.~w~~~;increase~~theoat;Voltage,and.a counterclockwise'(CCW)
~~~ectio~~~wi,~l.rdecrease~the~~-;Floa.t-..Voltage.~.setting..
, . . .
B. The-Equalize--Voltage:is-.adjusted afterthe Float Voltage is
set.. The-.Equalize.Voltage is~adjustable..using:the.-EQUALIZE.ADJ.Spot,-.located
onnthe front panel, of the ,-Rectifier.
Before making adjustment on the
Equalize Adjust (EQ)'pot; operateFLOAT/EQUALswitch to the "EQUAL" position.
A clockwise (CW) direction will increase the Equalize Voltage and a
counterclockwise (CCW) direction will decrease the Equalize Voltage setting.
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
6
I
MANUtACTURINb
7
NOttS:
I
9
1 T-439093SP
CA
,
-8
5 . T O P S I D E IRING.
6
BOTTOSIDE
YlR,NG
HAVE B E E N
D
ENGINEERING
NOTES:
c
E
~!$i%:%%a T-439D933P
W.l&
A
SHEET (\I
9
I
8
9
A
D
c
E
F
G
H
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I,
I
-4
al
cl
"
MANUAL
for
PEC 1015
PEC 1015A
RECTIFIER SYSTEM
-48 VDC @ 50-200 AMP
I
I
I
I
I
DESCRIPTION
Manual
PEC 1015. PEC lOl5A
Power Data Sheets
PEC 1015, PEC lOl5A (Shelf)
Power Data Sheets
Rectifier (-48V)
Schematic
Rectifier Shelf
PART NUMBER
6421015P
4381015PD
SM50F48PMPD
4390332P
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
SERVICE - If for any reason further assistance is needed on any power equipment, complete engineering and field
service groups are available in Galion. Ohio, to assist you in any way possible.
CALL: 4 19/468-7700 Field Service
419/468-7600 and ask for Field Service.
PARTS ORDERING - Replacement pans for power equipment may be obtained by forwarding B Purchase Order
to:
PECO II, Inc
P. 0. Box 910
Galion; Ohio 44833
kx to: (419) 462-8180
Include the following information:
A. PECO II part number and engineering level of equipment
B. If part is electrical, give circuit reference numbers and PECO II part numbers.
C. If pan is mechanical in nature, give description as to where it is used.
RETURN & REPAIR - Equifiment may be returned to the Factory for repair. In order to do this, the procedure
must be as follows:
A. Call: 419/468-7700 Field Service
Or
419/468-7600 and ask for Field Service.
B. Request a @MA) Returned
POWER DATA
for
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
PEC 1015
PEC 1015A
RECTIFIER
SYSTEM
SECTIONS
1.0
SPECIFICATIONS
1.1
1.2
1.3
1.4
1.5
1.6
General
Output Ratings
Input Ratings SMSOF48P
Input Ratings SM50F48PM
Standard Features
Environmental Ratings
2.0
DIMENSIONS
3.0
INSTALLERS
CONNECTIONS
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
4381015PD
Issue 9, Aug 1997
Page 02
1.0 SPECIFICATIONS
1.1
GENERAL
The PEC 1015 (Individual AC Input) & PEC 1015A (Bulk AC Input)
Rectifier System (48 VDC) is designed to "power" a load while
"charging" a battery. However, this system will operate as a
BATTERY-LESS SYSTEM and does not require batteries to
function.
The Modular Rectifier outputs are paralleled on a
common output bus. Alarms are available per Module or Shelf.
The PEC 1015 & PEC 1015A Rectifier System is housed in the
following rectifier shelf combinations:
A. PEC 1015:
B. PEC 1015A: 23" shelf x 12.25" high x18.0" deep & has four
(4) AC & four (4) DC Circuit Breakers.
NOTE: 23" RECTIFIER SHELF can accommodate up to four (4)
PEC
1015
PEC
1015A
23
PART
NUMBERS
INCH
SHELF
6571015P48-0
6571015P48D-0
6571015R48-0
6571015P-0
6571015R-0
6571015P48-OPS
X
X
X
X
X
X
6571015PA-0
TERMINATION
(See
There
Note)
INTERFACE
BOARD
YES
NO
x
X
X
X
X
-I-+
D. PEC 101SA: 19" shelf x 12.25 inches high x 18.0 inches deep
& has three (3) AC & three (3) DC Circuit
Breakers.
NOTE: 19" RECTIFIER SHELF can accommodate up to three (3)
4381015PD
Issue 9, Aug 1997
Page 03
1.1 GENERAL (Cant)
E. SWITCHMODE RECTIFIERS (SM50F48P or SM50F48PM):
(1) Rectifier:
(2) Rectifiers:
Three (3) Rectifiers:
Four (4) Rectifiers:
One
TWO
NOTE:
1 . 2 OUTPUT
48V @ 50
48V @ 100
48V @ 150
48V @ 200
Amp
Amp
Amp
Amp
RATING
ADJUSTMENT
FLOAT
VOLATGE
CONVENTIONAL
FLOODED CELL SETTINGS
54.48VDC
I
52.08VDC
I
NUMBER OF RECTIFIERS
(oer shelf assembly)
TABLE l-2
CURRENT
200
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
~1
I
I
I
I
I
I
I
4381015PD
Issue 6, May 1996
Page 04
1.3 INPUT RATINGS (SM5OF48P RECTIFIER)
A. VOLTAGE: Nominal 230 VAC RMS, single phase, 47 to 63 Hz,
with input voltage ranges of i/-15%.
B. TYPICAL DATA: When rectifier system is equipped with one
(1) Rectifier module, fully charged batteries, and nominal
input, the following data applies:
1. Rectifier output voltage initially adjusted to 54.48
VDC at 50% load is as follows:
PERCENT
LOAD
INPUT
CURRENT
INPUT
VA
INPUT
WATTS
PERCENT
EFFICIENCY
10
1.8
469
413
66.0
50
6.81
1582
1566
87.0
100
13.93
3167
3135
86.9
230 VAC
196 VAC
16.36 AAC
INPUT
CURRENT
INPUT
VA
INPUT
WATTS
PERCENT
EFFICIENCY
10
7.2
1876
1651
66.0
50
27.23
6325
6262
87.0
100
55.73
12665
12539
86.9
230 VAC
196 VAC
65.44 AAC
4381015PD
Issue 5, May 1996
Page 05
1.4
INPUT
RATINGS (SM50F48PM
RECTIFIER)
PERCENT
LOAD
10
I
I
INPUT
CURRENT
1.67
INPUT
VA
INPUT
WATTS
384
357
PERCENT
EFFICIENCY
I
76.3
50
6.63
1525
1511
90.1
100
13.16
3026
3003
90.7
230
VAC
176
VAC
17.35 AAC.
6.7
1536
1428
73.3
50
26.52
6100
6044
90.1
100
52.64
12104
12012
90.7
230 VAC
176 VAC
69.4 AAC.
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
4381015PD
Issue 5, May 1996
Page 06
1
STANDARDFEATURES
4381015PD
Issue 6, May 1996
Page 07
1.6 ENVIRONMENTAL RATINGS
A. OPERATING AMBIENT TEMPERATURE RANGE:
0C to + 50C (+32"F to + 122F)
B. STORAGE TEMPERATURE RANGE:
-40C to +85"C (-40'F to + 185F)
C. ALTITUDE:
Sea Level to 4800 ft: 0C to +SO"C (+32"F to +122"F)
4800 ft: to
7000 ft: 0C to +45"C (+32"F to +113"F)
,700O ft: to 10,000 ft: 0C to +4O"C (+32"F to +104"F)
D. HUMIDITY: This system is capable of operating in an
ambient relative humidity range of 0 to 95%, noncondensing.
E. SHOCK: This equipment, in its shipping container,
withstands shock developed when one edge of the container
is dropped 6 inches while the opposite edge is resting on
the ground, or is dropped 2 inches on any surface without
physical damage or degradation of the electrical
performance.
F. VIBRATION: This equipment, in its shipping container,
withstands vibration encountered is shipping without
physical damage or degradation of the electrical
performance.
G. HEAT DISSIPATION:
54.47 VDC.
NO. OF
MODULES
1
2
3
50
100
150
200
BTU/HR
SM50F48P
1400.0
2800.0
4200.0
5fifio.o
SMSOF48PM
953.0
1906.0
2859.0
3812.0
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
4381015PD
Issue 5, May 1996
Page 08
2.0 DIMENSIONS (Rectifier Shelf)
PEC 1015
(TYPICAL)
_-____ - -_--- -__-------__----__-_---_-__--_-
I
I
I
__-__
4381015PD
Issue 9, Aug 1997
Page 09
3.0
INSTALLERS
3.1
PEC
CONNECTIONS
Connect
Connect
Connect
Connect
Ll,
Ll,
Ll,
Ll,
L2,
L2,
L2,
L2,
&
&
&
&
GR
GR
GR
GR
to
to
to
to
TBl
TB2
TB3
TB4.
I
I
I
I
I
I
I
I
I
I
I
I,
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
4381015PD
Issue 9, Aug 1997
Page 10
3.2 PEC 1015A RECTIFIER SHELF SYSTEM
The PEC 1015A Rectifier Shelf System should be installed as
follows:
A. PEC 1015A RECTIFIER SYSTEM (Bulk AC Input)
1. AC Input (230 VAC):
a. Connect Ll, L2, & GR to TBl.
2. Battery Bus (Single Output):
a. Connect (+) Battery Lead to GND Bus Bar.
b. Connect (-1 Battery Lead to -48V Bat Bus Bar.
3. Alarms Out (RFA):
a. Connect TB5,
4381015PD
Issue 9, Aug 1997
Page 11
3.3 INSTALLERS CONNECTIONS
(GND)
BUS
&NO)
BUS
fI
IIon
AC INPUT
(TB4)
VI E W )
AC INPUT
(W
AC INPUT
@32)
(TBl)
AC INPUT
VIEW)
OUT
085)
L ALARMS OUT
(TB5)
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
4381015PD
Issue 9, Aug 1997
Page 12
3.3
I
I
~1
I
I
I
I
I
I
I
I
I
I
I
I
ALARMS
OUT
(TBS)
INSTALLERS
CONNECTIONS
(Cant)
4381015PD
Issue 9, Aug 1997
Page 13
4.0 INSTALLERS NOTES
4.1 INSTALLERS INFORMATION NOTES
PEC 1015
AC INPUT (TBl, 2,
TERMINALS
CAPACITY
TYPE
10 Ga
Screw
Term
Maximum
INPUT
VOLTAGE
RECOMMENDED
WIRE
SIZE
BRANCH CIRCUIT
PROTECTION
(2 POLE CIR BKR)
230
12 Ga
20 Amps
PEC 1015
TERMINALS
CAPACITY
TYPE
2 Ga
Maximum
Screw
Term
ALARM
INPUT
VOLTAGE
RECOMMENDED
WIRE
SIZE
BRANCH CIRCUIT
PROTECTION
(2 POLE CIR BKR)
230
4 Ga
80 Amps
TERMINALS
TERMINALS
CAPACITY
TYPE
12 Ga
Maximum
Pressure
Terminal
3, & 4) [Individual]
(See Note 4.1.5)
RECOMMENDED
WIRE
SIZE
22 Ga
CAPACITY
TYPE
RECOMMENDED
WIRE
SIZE
6 Ga
Maximum
Crimp Lug
0.25" x 0.625"
As
Req'd
TERMINALS
I
I
I
I
I
I
I
I
I
1~
1~
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
4381015~~
Issue I. Aug 1996
Page 14
4.1 INSTALLERS INFORMATION NOTES (Cant)
E. Wire sizes based on National Electric Code Table 310-16 for
copper wire with rated conductor temperature of 75"~
operating in 30C ambient. For operation in ambient
higher than 30C apply derating factors listed in Table
310-16 of the National Electric Code.
F. Equipment grounding conductor size based on recommendations
of National Electric code Table 250-95 for copper wire. If
aluminum or copper clad aluminum grounding conductor is
used, refer to Table 250-95 for increased conductor size.
G. Connect this wire to C.0 GRD, per local Telephone Company
grounding schematic.
4381015PD
Issue 7, Aug 1996
Page 15
4.2 ADDING A RECTIFIER (SM50F48P) 6 PLANT ADJUSTMENT (Cent)
NOTE: If the Plant Float or Equalize voltage needs to be
Rectifiers,
Rectif ier.
I
I
I
I
I
I
I
I
I
I
I
,I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
4381015PD
Issue 7, Aug 1996
Page 16
4.4 ADDING / REPLACING A RECTIFIER (SMSOF48PM) & ADJUSTMENT
4381015PD
Issue 7, Aug 1996
Page 11
4.4 ADDING / REPLACINGARECTIFIER
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
SM50F48PMPD
(
RECTIFIER MODULE
SM50F48PM
(-48V)
Produced By:
08
880 2851 P
07
880 1271 P
02-07-00 VLD
See E. C. History
DESCRIPTION
ISS
ISSUE
File Name: .%450F48PMPD.W80
ISSUB 8. M a r 2000
Eng
D.D
Awr
D.D
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
TABLE OF CONTENTS
Section/Pars
Description
Paqe
Front Matter
TOC
i- ii
List of Figures
iii
Referenced Information
iv
Foreword
Section I
General Information
l-01
1.1
1.2
Specifications
I-01
1.3
Standard Features
l-01
1.3.1
Voltage Control
l-02
1.3.2
Remote Sensing
l-02
1.3.3
Load Sharing
l-02
1.3.4
Current Walk-In
l-02
I-02
1.3.5
1.3.6
Over Temperature
l-02
1.3.7
Alarm Indication
l-02
1.4
l-02
1.4.1
Test Points
I-02
1.4.2
Test LED
l-02
1.4.3
Standby/ON Switch
l-02
1.4.4
GO LED
l-02
1.4.5
Float Adjust
l-02
1.4.6
Equalize Adjust
I-02
1.4.7
Current Limit
l-02
1.46
High Voltage
l-02
1.4.9
Float/Equalize
l-02
1.4.10
Fail LED
l-02
1.4.11
Select Switch
l-02
SectionlPara
Description
1.5
Agency Approvals
l-02
1.6
Environment Specifications
l-02
Section II
2.1
General
2-01
2.2
installation
Z-01
2.3
Initial Turn On
2-02
2.4
Tools Required
2-02
Section Ill
3.1
General
3-01
3.2
Maintenance
3-01
3.3
Adjustments
3-01
3.4
Factory Settings
3-01
3.5
Tools Required
3-01
Section IV
Troubleshooting
4.1
General
4-01
4.2
Troubleshooting
4-01
4.3
Tools Required
4-01
ii
I
I
I
I
I
I
I
I
I
I
I
I
I
SM50F48PMPD
Issue 8, Mar 2000
LIST OF FIGURES
Name
I
I
I
~1
~1
I
I
I
I
I
I
I
I
Fisure Number
Rectifier
Module
Rectifier
Module(Front
Rectifier Module(Rear
l-l
View)
1-2
View)
2-1
REFERENCED
INFORMATION
I
EQUIPMENT
Eauipment
Nomenclature
Part Number
Manufacturer
Fluke 87
John Fluke
Mfg. Co. Inc.,
Everett, WA
ID Number
Manufacturer
Part Number
Manufacturer
Part Number
Manufacturer
SPARES
Consumables
Nomenclature
N/A
Recommended Spares
Nomenclature
N/A
iv
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
II
I
I
I
I
I
I
I
I
I
I
SM50F48PMPD
Issue 8, Mar 2000
FOREWORD
1. Give the PECO II part number and engineering level
of the equipment.
2. If the part is electrical, please include the circuit
reference numbers and the PECO II part numbers.
3. If the part is mechanical in nature, please give a
description as to where the equipment is used.
Information/Ordering
Note:
WARNINGS:
1. ELECTRlCAL SHOCK HAZARD. DO NOT.ATIEMPT TO REMOVE, MAlNTAlN. OR INSTALL MIS EQUIPMENT WITH POWER APPLIED.
PERSONNEL THAT ATTEMPT TO WORK ON THIS EQUIPMENT WlTHOUT THE PROPER TRAINING MAY SUBJECT THEMSELVES
OR OTHERS TO ELECTRICAL SHOCK THAT MAY CAUSE SERIOUS INJURY OR DEATH.
smcny
3. DO NOT A,TEMPT TO WORK ON THIS EGUIPMENT IF IT IS OR HAS SEEN EXPOSED TO A HIGH MOISTURE CONDITION. IT IS
RECOMMENDED THE EGUIPMENT BE RETURNED TO PECO II TO BE PROPERLY TESTED. WORKING ON THIS EQUIPMENT
DURING A HIGH MOISTURE CONDITION SUBJECTS THE USER TO ELECTRICAL SHOCK THAT MAY CAUSE SERIOUS INJURY OR
DEATH.
4. USE OF AN AITACHMENTOTHER
THAN ONE THAT HAS SEEN APPROVED BY PECO II IS FORBIDDEN. THE AlTEMPTED USE OF
UNAUTHORlZED AITACHMENTS WILL VOID ANY AN D ALL WARRANTIES, IMPLlED OR OTHER, AND WILL INCREASE RISK OF
FIRE, OR MAY POSSIBLY CAUSE ELECTRICAL SHOCK, INJURY. OR DEAT TO PERSONNEL.
5. DO NOT OPERATE THIS EQUIPMENT IF IT HAS BEEN DROPPED OR OTHERWISE HAS POSSIBLY SEEN DAMAGED. TRYING TO
OPERATE THlS EGUIPMENT IF IT HAS BEEN DAMAGED SUBJECTS YOURSELF OR OTHERS TO ELECTRICAL SHOCK THAT MAY
CAUSE SERIOUS INJURY OR DEATH.
6. ONLY RECTlFlER MODULES CAN SE INSTALLED INTO A WORKING SYSTEM. FOR ALL OTHER MODULES, REMOVE SYSTEM POWER
BEFORE ATTEMPTlNG ANY MAINTENANCE. FAILURE TO REMOVE POWER COULD CAUSE SYSTEM DAMAGE AND INCREASES
THE POSSIBILITY OF ELECTRICAL SHOCK THAT COULD CAUSE SERIOUS PERSONNEL INJURY OR POSSIBLE DEATH.
,,A RACK,SHELF MAY CONTAlN SEVERAL OPERATING SYSTEMS. IF THERE IS ANOTHER SYSTEM IN THE GENERAL AREA YOU WANT
TO ,NSTALL THlS SYSTEM, SE CAUTlOUS OF ANY EXPOSED CONNECTORS OR WIRES AND, WITH PERMISSION, REMOVE
POWER TO THE OTHER SYSTEMS. FAJLURE TO TAKE THE NECESSARY SAFETY PRECAUTIONS SUBJECTS THE INSTALLER OR
MAINTENANCE PERSONNEL TO SEVERE ELECTRICAL SHOCK THAT MAY CAUSE SERIOUS INJURY OR DEATH.
8. DO NOT PLUG THE OTHER END OF THE POWER CORDS INTO THE AC SERVICE. POWER WILL SE APPLIED DURING THE
OPERATlONAL CHECKOUT PROCEDURE.
CAUTIONS:
I
I
I
I
I
I
I
I
I
I
I
1. THE SYSTEM IS DELICATE AS COMPARED TO THE MGER POWER EGUIPMENT. DO NOT APPLY TOO MUCH FORCE TO THE
MOUNT,NG SCREWS, RETAINERS. ETC. OR DAMAGE TO THE EOUIPMENT MAY OCCUR.
2. THE MODULE SHOULD SLIDE EASILY INTO THE CAGE. DO NOT FORCE THE MODULE INTO THE CAGE. DAMAGE TO THE MODULE OR
SYSTEM BACKPLANE COULD OCCUR.
II
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
SMSOF48PMPD
Issue 8, Mar 2000
Section I
General Information
1.1 GENERAL.
The paragraphs that follow contain information that is
intended to help the user with the understanding of the
Rectifier Module. This Rectifier is a -48 VDC 50 Amp
self contained unit. The Rectifier is a fully regulated, DC
isolated output Switchmode Rectifier designed to
charge batteries while supplying power to
telecommunication equipment. The Rectifier can also
operate as a Battery Eliminator not requiring external
batteries. The Rectifier is of modular design for easy
upgrading or replacement in a PECO II shelf
configuration.
Over Voltage
Protection
Mechanical
Specifications
1.2 SPECIFICATIONS.
The following infonation is intended to give the user a
quick reference to information that is necessary to install
and operate the system. Included are input
requirements, output signal characteristics, size, weight,
and generated system noise.
Input Requirements
Voltage/
Current
TIF
Efficiency
88 to 90% at 50-100%
@50ADC.
Power Factor
AC Input
Protection
Load 54.5VDC
output
Voltage
Voltage
Regulation
No. ot
Modules
Shelf Output
Current
BTUMR
50 Amp
1122
1.4.10 Fail LED. The Fail LED(Red) will light when the
Rectifier fails to operate.
4800ftto7000ft: 0Cto+45C(+32Fto+113F)
7000ftto10.000ft: OCto+40C(+32Fto+104F)
Humidity: 95% Non-condensing (Maximum).
C. COOLING:
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
Figure l-l.
Rectifier Module
l-03
I
I
I
I
I
I
I
I
I
I
I
I
I
Figure 1-2.
Rectifier Module(Front View)
l-04
I
I
I
SMSOF48PMPD
Issue 8. Mar 2000
I
I
I
Section II
Rectifier Module Installation
2.1 GENERAL.
11-CLSO
CONTROLLED LOAD SHARE
lead. When connected between other like Rectifiers
Modules will Load Share within c/-2% of rated load.
12- RFA-NO
13- RFA-COM
14- RFA-NC RECTIFIER FAILURE ALARM
(RFA). These leads are from a set of relay contacts
called Fon C contacts. The RFA relay alarm contacts
are shown in their alarm state (De-energized). Relays
release on alarm conditions, slam-t circuits are
energized in their Normal no alarm condition.
15-VI
CURRENT MONITOR lead is
provided for Remote Monitoring of the Rectifiers output
current. A 1 .O volt/lO.O Amp current signal referenced
to the Negative Sense lead is provided for use with a
remote Monitoring System.
16- Vacant
17- BTC
BATTERY TEMPERATURE
COMPENSATOR lead is provided to vary the output
voltage of the Rectifier to compensate for battery
temperature in the range of 10C to 65C.
18- Vacant
REMOTE HIGH VOLTAGE lead
19- RHV
will accept an external high voltage signal (Battery) from
a system controller. If the Rectifiers output current is
more than 10%. this signal will shut down the Rectifier
Module.
2CI- RM-EQ
REMOTE EQUALIZE lead will
accept an external equalize signal (Ground) from a
system controller or other external system to raise the
plant battery voltage for the purpose of battery
maintenance.
I
I
I
(B Module):
Pin Number
(+)
Positive Power Output connection.
Negative Power Output connection.
(4
I-
I
I
I
I
I
I
I
I
2-01
I
G. The Rectifier will come on line. The GO LED
(Green) will light. The digital meter will indicate the
output voltage or current, depending on the position of
the V/A switch (Volts/Amps), located to the right of the
meter. Upon turn-on of the Rectifier, the output current
will gradually increase to its required load,
approximately eight (8) seconds to full output.
2-02
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
MODULE Ii
lNPUT
L2 /
T% -
AODULE 0
OUTPUT
C-1 -
I
I
I
I
I
I
(+) -
Figure 2-I.
Rectifier Module (Rear View)
2-03
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
Section III
Maintenance and Adjustments
(2) The Equalize Voltage is adjusted after the Float
Voltage is set. The Equalize Voltage is adjustable using
the EQUALIZE ADJ pot, located on the front panel of
the Rectifier. Before making adjustment on the
Equalize Adjust (EQ) pot, operate FLOAT/EQUAL
switch to the EQUAL position. A clockwise (CW)
direction will increase the Equalize Voltage and a
counterclockwise (CCW) direction will decrease the
Equalize Voltage setting.
3.1 GENERAL.
This section gives the procedures to perform
maintenance and adjustments on the Rectifier Module.
3.2 MAINTENANCE.
This section gives the procedures to perform
maintenance on the Rectifier Module.
3.3 ADJUSTMENTS.
Plant setting
PM, -l,-2
PM-3
Float Voltage
54.48 VDC
54.48 VDC
Equalize Voltage
56.40 VDC
55.20 VDC
Current Limit
5 1 .OO Amps
51.00 VDC
58.00 VDC
58.00 VDC
3-01
I
I
I
I
I
I
I
I
II I
I
I
I
I
I
I
I
I
I
I
Section IV
Troubleshooting
4.1 GENERAL.
Digital Voltmeter
Slotted Screwdriver (Fine Blade) or Tweaker
4.2
TROUBLESHOOTING.
4-01