You are on page 1of 49

ETICS Anchors

Simply faster,
safer and
more efficient!

As of: June 2011

Anchor table

EJOT fastening systems for ETICS


a solution for everything.
For the anchor table simply fold.

Substrates

Use category A:
Normal weight concrete

Use category B:
Solid masonry

Use category C:
Hollow or perforated masonry

Use category D:
Lightweight aggregate concrete

Use category E:
Autoclaved aerated concrete

Anchor table

ejotherm anchors with European Technical Approval (ETA)


Fasteners for insulation boards

Rail systems

ejotherm
STR U

ejotherm
STR H

EJOT
H1 eco

ejotherm
NTK U

ejotherm
NT U

ejotherm
SDK U

ejotherm
NK U

page 18

page 19

page 22

page 23

page 24

page 27

page 28

Normal weight concrete C12/15 acc. to EN 206-1

Normal weight concrete C16/20 - C 50/60


acc. to EN 206-1

Weather shell of concrete C16/20 - C50/60

Clay bricks (Mz) acc. to DIN 105

Solid lime sandstone (KS) acc. to DIN EN 106

Solid masonry of lightweight concrete (V)


acc. to DIN 18152

Vertically perforated clay bricks (Hlz)


acc. to DIN 105

Sand-lime perforated bricks (KSL)


acc. to DIN EN 106

Lightweight concrete hollow blocks (HbL)


acc. to DIN 18151

Lightweight aggregate concrete (LAC)

Vertical coring reference bricks (Hlz) acc. to


NORM B 6124

Autoclaved aerated concrete P2-P7

Wooden substrates and metal sheets


(without ETA)

Fastening solutions for special applications with German DIBt approval


Clinker systems

Speciality solutions

EJOT
SDF-S plus
8UB

EJOT
SDP-S plus
8UB

EJOT
SDM-T plus
8/60 U

EJOT
VSD

EJOT
WSS/Keri

Normal weight concrete

Clay bricks

Solid lime sandstone

Vertically perforated clay bricks

Solid masonry or solid blocks of lightweight


concrete

Sand-lime perforated bricks

Lightweight concrete hollow blocks

Weather panels of three layer facade


envelope (concrete)

Lightweight aggregate concrete

Autoclaved aerated concrete acc. to DIN

Autoclaved aerated concrete acc. to TGL

Application ruled in the approval

Proof of qualification through tests on the building

- no approval

Content
5

Your strong partner

ETICS experience

13

References

14

The ejotherm generation

15

The EJOT STR-principle

17

ejotherm washer anchors

18

ejotherm STR U Cap anchor for concrete and masonry

19

ejotherm STR H Cap anchor for wood and metal sheets

20

ejotherm STR accessories

22

EJOT H1 eco - Universal hammer-in anchor

23

ejotherm NTK U Telescope anchor

24

ejotherm NT U Universal hammer-in anchor

25

EJOT additional washer

2 6

ejotherm anchors for rail fastenings

27

ejotherm SDK U Screw-in anchor for rails

28

ejotherm NK U Hammer-in anchor for rails

29

Accessories for rail fastenings

3 0

EJOT anchor for clinker systems

31

EJOT SDFS plus 8UB Clinker system anchor for concrete and masonry

32

EJOT SDPS plus 8 Clinker system anchor for gas concrete

33

Solutions for special applications

33

EJOT SDMT plus 8/60U Specialist for problematic substrates

34

EJOT VSD Renovation anchor for prewall shells

35

EJOT WSS and Keri Renovation rods for weather shells

36

EJOT special drill for optimum loads in perforated bricks

36

EJOT spiral anchor for fastening of light attachments on ETICS facades

37

Fasteners for ceiling insulation

38

EJOT DDS and DDT Ceiling insulation screw with additional washer

39

EJOT DDA Ceiling insulation anchor

4 0

EJOT anchor basics

Imprint
Publisher:
EJOT Baubefestigungen GmbH
57334 Bad Laasphe
Germany
Layout and execution:
conception Werbung & Marketing GmbH, 57072 Siegen
EJOT Baubefestigungen GmbH
Photos:
Title and Underground garage, Niels Otto
Bricklayer, Birgid Allig/zefa/Corbis
Freiherr-vom-Stein-Gymnasium, Mnster, Christian Richters Fotografie
Schlossarkaden Braunschweig, ECE
Products, Theissen Fotodesign
Print:
Schlabach GmbH & Co. KG, D57339 Erndtebrck
Legal notes:
Our latest sales terms and delivery conditions apply.
EJOT products are constantly enhanced. They are subject to technical changes,
assortment and price changes. During planning and use of our products please
comply with accepted engineering rules, planning laws as well as relevant safety
regulations. The national technical approvals granted to our products can be
downloaded on the internet at www.ejot.com.
by EJOT Baubefestigungen GmbH
EJOT is a registered trademark of EJOT GmbH & Co. KG.
ejotherm is a registered trademark of EJOT Baubefestigungen GmbH.
TORX is a registered trademark of Camcar, Div. of Textron, Rockford, IL.

Your strong partner

5
2
1

EJOT Building Fasteners:


Over 30 years of
specialist knowledge
around the building
envelope

3
a

External Thermal Insulation Composite Systems


(WDVS)
Special anchors for fixing insulation on external wall
systems
Rear ventilated facades (VHF)
Fasteners and anchors for fixing brackets to substrate,
frame to brackets, insulation to substrate and facade
fascias on rear ventilated systems

Flat roofing (FLD)


Fasteners, stress plates and installation tools for the
efficient attachment of insulation and waterproof
membrane to deck

Industrial Window and Facades Technique (IFF)


Application specific fasteners for UPVC window and
door manufacturing and aluminium/glass curtain wall
systems

Fastening Systems for Solar Installations


For fastening uprights for solar and photovoltaic
installations

c
a

Industrial lightweight construction (ILB)


High-quality fastener products for fixing profiled
sheets and sandwich panels on industrial steel frame
construction

Your strong partner

EJOT Your strong partner


for fastening solutions in the
building industry

l Expertise and experience

With over 30 years of experience and development know-how


Made in Germany, we understand the requirements of a fastener and its application on building envelopes very precisely.
Our knowledge is the base and source of our products and
subsequent solutions which offer our customers real benefits.

l Quality and easy installation

The quality of our products surpass planning laws and legal


requirements. Our highest aim is to ensure quick and easy
assembly.
l Customer-friendly service

We make a point of building trusting and friendly relationships


with our customers. Our personal advisers offer 24-hour
customer service. If required our employees deliver technical
back-up on the building site. In addition we provide our knowhow through training seminars.

l There for you worldwide

Our Europe-wide sales and service network with over 25 sub sidiaries as well as a worldwide project support team is pleased
to help our customers at any time.

ETICS competency

Your service Our quality:


EJOT philosophy sets
standards

Are you absolutely sure what is behind the old rendering?


ETICS are often used in renovation. The major part of the
structural fabric is of bad quality or combined masonry was
used. The bearing capacity of the old render is reduced
through environmental stress.
The ejotherm anchor generation provides safety. Especially
the ejotherm STR U can be used in any substrate. As the
first 8 mm ETICS anchor, it obtained a European Technical
Approval for all building material categories. Despite shortest
anchorage depths, it reaches the highest characteristic loads.
With EJOT quality your service promise will not hang by
a thread

ETICS competency

I cannot afford a construction site to stagnate due to


installation problems, and even worse customer
complaints. Today, everything has to be fast and
smooth but without reduction of quality and
security. EJOT anchors are great to work with.
Especially the STR principle is simply ingenious.
100% setting control and homogeneous insulation
surfaces thus I can still relax after many years.

ETICS competency

Your system Our know-how:


over 30 years of ETICS anchors
by EJOT

Through our close contact to practitioners and developers,


we are able to develop ideal fastening solutions for today and
tomorrows facade insulation systems. Make use of this head
start for your system and experience how decades of knowhow create easy and quick installation.
Based on this practical experience, in special cases our
experts work out individual solutions for you even right on
the building site.
Some examples of our service:
l personal consultants
l competent consulting via phone or e-mail
l fast and reliable delivery service
l anchor pull-out tests on site
l trainings in fastening technology
l support with bidding processes
Your benefits:
l custom-designed solutions you can rely on
l our decades of know-how
l planning security

10

ETICS competency

As consultant of a system owner, I know


the daily difficulties and annoyances that
make life hard for users and cost them
valuable time. With EJOT anchors, the
right choice is easy, and I can rely on that
they work even when the conditions at
the object are not ideal.

!
EJOT anchors for ETICS are important components
of high-grade facade systems. Like all other system
components they are exclusively sold to system owners.

11

ETICS competency

Your advantage
Our programme:
anchor choice
made easy

Which anchor do I need for which substrate? What do I do when faced with
mixed masonry? Our ejotherm family with European Technical Approval (ETA)
simplifies your choice. Powerful anchors provide for secure fastening in all
substrates and with all kinds of insulation materials.
Your benefits:
l clear product range for all substrates
l solutions for all insulation materials
l easy anchor choice
l reduced stock volume
Moreover you have a special programme with cost-efficient special solutions
at your hand. Typical applications are:
l rebuilding the stability of damaged ETICS
l solutions for renovating the renovation
l re-establishing the stability of weather shells and prewall shells

Use category A

Use category B

Use category C

Use category D

Use category E

Lightweight
aggregate concrete

Autoclaved aerated
concrete

ejotherm STR U
competitive product A
competitive product B
competitive product C
Normal weight concrete

Solid masonry

Hollow or perforated
masonry

12

ETICS competency

To me as a planer, energy savings and the design of a new ETICS


facade are most important. Moreover I am responsible that the
facade is secure and immaculate even after years this is what the
client expects. That is why we advertise ejotherm STR U. If necessary, EJOT experts already consult me during the bidding process
even right on the building site.

13

References

Freiherr-vom-Stein-Gymnasium, Munster

EJOT The Quality Connection:


international customers
rely on EJOT

During more than three decades, over 500,000,000 sqm


of ETICS facades have been fastened with EJOT anchors
without even a single incident! This equals an area of more
than 70,000 football pitches. Roughly 150 billion litres of
heating oil or 440 million tons of CO2 have been saved a
valuable contribution to the environment, which is growing
daily.
More and more international customers and principals rely on
sophisticated fastening solutions and the competent advice
by EJOT.
EJOT - The Quality Connection also internationally!

Ginger & Fred, Prague

Estate Blumlgerfeld, Celle

Schloss-Arkaden Braunschweig

Music Academy, Stuttgart


14

The ejotherm generation

Up to 45 mm
shorter
anchor lengths

Short and good


quick and economic:
performance up, costs down

The new ejotherm generation makes it possible. Specially


developed expansion zones enable highest characteristic
loads with minimum anchorage depths. The result: quick
installation and economic total cost.
Your benefits:
l up to 45 mm shorter anchor lengths*)
l valuable safety reserves in doubtful substrates
l economic anchor usage
l universal expansion zones for maximum use range
l universal drill diameter for all substrates (8 mm)
*)

in comparison with earlier EJOT anchors

nominal anchorage depth hnom

characteristic load
ejotherm STR U
ejotherm NT U

competitive product A
competitive product B
cost
installation time, anchor length, drill abrasion

performance
safety, number of anchors/m2,
sensitivity with varying substrate qualities

Substrate: Vertically perforated clay bricks (Hlz)


Source: specifications of the individual European Technical Approval (ETA)

15

The EJOT STR principle

Your guarantee
Our STR principle

For long-lasting beautiful facades


With its STR principle, EJOT has developed a unique fastening system. Without any additional work, the anchor washers
are installed countersunk and covered with an insulation cap.
This creates a homogenous surface and an even rendering,
which helps to avoid anchor marks.
For all substrates
The ejotherm STR U is the first 8 mm ETICS anchor with
European approval for all building materials, including gas
concrete (use categories A - E). For fastenings on wooden
materials we provide ejotherm STR H. Both anchors are
installed with the same ejotherm STR tool.

Easy installation:
1 Quick drilling thanks to reduced drill depth
2 Put anchor with pre-mounted screw into the hole until
the plate bears on the surface
3 Screw with the STR tool: countersinking happens
automatically (no milling, no dust)
4 Insert the STR insulation cap ready!

For all insulation materials


Both ejotherm STR U and ejotherm STR H can be either
installed countersunk according to the STR principle or plain
with the surface with the STR plug. This way an adaptation to
all commonly used types of insulation is possible.
Quality and safety in XXXL
The EJOT STR princple is available for insulation of up to
400 mm the perfect fastening system for zero- and lowenergy houses.

16

ejotherm washer anchors

ejotherm washer anchors


anchor choice made easy

When fastening ETICS, insulation boards are usually attached


to the facade with adhesive and then fastened with anchors.
The bearing load of the system is carried onto the facade
via shearing forces. High-quality washer anchors, installed
through the insulation, guarantee additional contact pressure
through their stiff washers. This contact pressure supports the
permanent frictional bonding between adhesive and substructure. Due to a strong hold in the wall and the contact pressure
of the washer the clamping of the insulation board is ensured
(screw clamp effect).
ejotherm washer anchors with European Technical Approval
offer certified safety even under high wind loads. Through their
washers and the expansion element, they redirect the tensile
load into the bearing substructure.
The washer anchors of the ejotherm generation make things
easy for you:
Easy anchor choice for safe anchoring in any building material.
Together with a minimum anchor depth and maximum performance. Performance up, total cost down! For long-lasting,
energy-saving facades.

17

ejotherm STR U
Cap anchor for concrete and
masonry

ble in
Availa new
three hs!
lengt

l approved for all categories of building

materials
l the EJOT STR principle with STR cap for homogeneous

surfaces and even rendering - quick and easy without


milling dust
l also installable flush with the surface with STR plug
l shortest anchorage depths, highest loads for maximum

safety and economic anchor usage


l permanent contact pressure
l optimised thermal bridges
l premounted screw for quick installation
l 100% setting control: the countersunk installation of the

washer signalises safe anchorage

Technical data

Installation

Anchor diameter

8 mm

Washer diameter

60 mm

_
Drill hole depth, countersunk installation h1 >

50 mm (90 mm)

_
Drill hole depth, plain with the surface h2 >
_
Anchorage depth hef >

25 mm (65 mm)

35 mm (75 mm)

Use categories acc. to ETA

A, B, C, D, E

European Technical Approval

ETA-04/0023

Values in parentheses: anchoring in gas concrete (use category E)

Characteristic loads
Normal weight concrete C 12/15 acc. to EN 206-1

1.5 kN

Normal weight concrete C 16/20 - C 50/60 acc. EN 206-1

1.5 kN

Weather shell of concrete C16/20 - C 50/60

1.5 kN

Clay bricks (Mz) acc. to DIN 105

1.5 kN

Solid lime sandstone (KS) acc. to DIN EN 106

1.5 kN

Solid masonry of lightweight concrete (V) acc. DIN 18152

0.6 kN

Vertically perforated clay bricks (Hlz) acc. to DIN 105

1.2 kN

Vertical coring reference bricks (Hlz) acc. NORM B 6124

0.75 kN

Sand-lime perforated bricks (KSL) acc. to DIN EN 106

1.5 kN

Lightweight concrete hollow blocks (HbL) acc. DIN 18151

0.6 kN

Lightweight aggregate concrete (LAC)

0.9 kN

Autoclaved aerated concrete P2 - P7

0.75 kN

Please note: For calculation of design loads the national safety factors have to
be included (e.g. Germany: 3). Please observe the approval.

Countersunk installation acc. STR


principle with STR cap

Installation flush with the surface


with STR plug

Product range

Use category

Use category

Product name

Use category

Use category

A D

and

A D

and

Insulation (mm)

Insulation (mm)

length (mm)

Insulation (mm)

Insulation (mm)

length (mm)

New build. Renovation New build. Renovation New build. Renovation New build. Renovation
)

1)

280

260

240

200

ejotherm STR U 315

603)

ejotherm STR U 135

300

280

260

240

ejotherm STR U 335

120 100

80 603)

ejotherm STR U 155

320

300

280

260

ejotherm STR U 355

140 120

100 80

ejotherm STR U 175

340

320

300

280

ejotherm STR U 375

160 140

120 100 ejotherm STR U 195

360

340

320

300

ejotherm STR U 395

180 160

140 120 ejotherm STR U 215

380 360

340 320

ejotherm STR U 415

200 180

160 140 ejotherm STR U 235

400 380

360 340

ejotherm STR U 435

420 400 380 360

ejotherm STR U 455

220

ejotherm STR U 115

100 80

80 603)

Product name

200

180

160

240

220

200

180 ejotherm STR U 275

260

240

220

200 ejotherm STR U 295

) 10 mm adhesive

ejotherm STR U 255

) 10 mm adhesive and 20 mm old render

3)

Product code: 8709 ... 400 (e.g. ejotherm STR U 115: 8709 115 400)

to be installed plain with the surface only

Pease note: Always use in combination with STR cap and STR plug respectively

Packaging: 100 pieces/unit

18

ejotherm STR H
Cap anchor for wood and metal sheets
l for wooden substrates as well as metal sheets of up to

0.75 mm
l the EJOT STR principle with STR cap for homogenous

surfaces and even rendering


- quick and easy without milling dust
l also installable flush with the surface with STR plug
l permanent contact pressure
l 100% setting control: the countersunk installation of the

plate signalises safe anchorage

Installation

Technical data
Screw diameter

6 mm

Washer diameter

60 mm

Screw-in depth

30 - 40 mm

Recommended use loads


_ 17,0 mm)
Wood fibreboards (thickness >
_ 13,0 mm)
Chipboards (thickness >

0.25 kN
0.25 kN

_ 12,5 mm)
Gypsum fibreboards (thickness >
_ 16,0 mm)
OSB plates (thickness >

0.25 kN

_ 27 mm)
Solid wood plates (thickness >

0.25 kN

0.15 kN

The recommended use loads are calculated with a safety factor of 3.


They may differ according to the object.

Special solution: EJOT self-drilling screw


JT3-ST-2-6,0 incl. washer plate element 60
Special solution for the corrosion resistant fastening of
External Thermal Composite Systems made of phenolic resin
and mineral wool insulation board.
Fastener can optionally be mounted flush with the surface or
embedded according to the EJOT STR principle.

Countersunk installation acc.


STR principle with STR cap

Installation flush with the


surface with STR plug

For further questions please contact the responsible


EJOT contact person.

Product range
Countersunk

Installation plain


installation

with the surface

and

Insulation (mm)

Insulation (mm)

length (mm)

40

ejotherm STR H 080

Product name

8711 080 400

60 ejotherm STR H 100

80

80 ejotherm STR H 120

8711 120 400

100

100 ejotherm STR H 140

8711 140 400

8711 100 400

8711 160 400

120

120 ejotherm STR H 160

140

140 ejotherm STR H 180

8711 180 400

160

160 ejotherm STR H 200

8711 200 400


8711 220 400

180

180 ejotherm STR H 220

200

200 ejotherm STR H 240

8711 240 400

220

220 ejotherm STR H 260

8711 260 400

240

240 ejotherm STR H 280

8711 280 400

260

260 ejotherm STR H 300

8711 300 400

Note: Always use in combination with STR cap and STR plug respectively.

Product code

Packaging: 100 pieces/unit

19

ejotherm STR accessories

ejotherm STR cap EPS


l specially developed system cap of polystyrene (EPS)
l to be used with ejotherm STR U and ejotherm STR H
l colours: white or grey

ejotherm STR cap MW


l specially developed system cap of mineral wool
l to be used with ejotherm STR U and ejotherm STR H

ejotherm STR plug


l special plug of polystyrene (EPS)
l to be used with ejotherm STR U when installed flush with

the surface
l ejotherm STR plug is included in the delivery of

ejotherm STR H

Product range
Product name

Product code

(pieces/box)

Packaging

ejotherm STR cap EPS white

8593 000 093

100

ejotherm STR cap EPS grey

8593 111 070

100

ejotherm STR cap MW

8593 000 098

100

ejotherm STR plug

8709 033 000

500

20

ejotherm STR accessories


ejotherm STR tool
l specially developed tool for countersunk installation of

ejotherm STR U and ejotherm STR H


l sturdy construction for long durability
l wear parts are exchanged quickly
l set comprises: STR-tool, additional cutting metals,

angle screw driver, bits for all applications

ejotherm STR tool spare kit


l to replace wear parts of the STR tool
l set comprises: 3 cutting metals,

3 bits for countersunk installation

ejotherm STR renovation cutter


l for subsequently securing ETICS facades:

cost-efficient re-establishment of the structural stability


through subsequent anchoring
l avoids the de-installation of the old system in many cases
l utilisation of the EJOT STR technology:
1. mill the existent plaster layer,

2. install the ejotherm STR U,


3. insert the STR cap to obtain an even plaster base,
4. plaster a new final rendering

Product range
Product name

Product code

(pieces/box)

Packaging

ejotherm STR tool

9151 900 000

ejotherm STR tool spare kit

9151 910 000

ejotherm STR renovation cutter

9151 940 000

21

EJOT H1 eco
Universal hammer-in anchor
l approved for concrete, solid and

perforated masonry

N ew
er -in
ham m or
a nch

l solid steel nail (break-proof)


l flush setting of the anchor washer
l plastic injection element to reduce thermal bridges
l installable with additional washer
l shortest anchorage depths, minimum drill hole depth
l high loads for your security
l economic anchor usage
l premounted nail for quick installation
l with EPD (Environmental Product Declaration)

Technical Data

Installation
8 mm

Washer diameter

60 mm

_
Drill hole depth h1 >

35 mm

_
Anchorage depth hef >

25 mm

Point thermal transmittance

0.001 W/K

Use categories acc. to ETA

t35
t30t35

Anchor diameter

A, B, C

European Technical Approval (ETA)

ETA-11/0192

hv25

Characteristic loads
Normal weight concrete C 12/15 acc. to EN 206-1

0.9 kN

Normal weight concrete C 16/20 - C 50/60 acc. to EN 206-1 0.9 kN


Clay bricks (Mz) acc. to DIN 105

0.9 kN

Solid lime sandstone (KS) acc. to DIN EN 106

0.9 kN

Vertically perforated clay bricks (Hlz) acc. to DIN 105,


bulk density 1,2 kg/dm3
Vertically perforated clay bricks (Hlz) acc. to DIN 105,
bulk density 0,9 kg/dm3
Sand-lime perforated bricks (KSL) acc. to DIN EN 106

hv25

0.75 kN
0.6 kN
0.9 kN

Please note: For calculation of design loads the national safety factors have to
be included (e.g. Germany: 3). Please observe the approval.

final mesch
mesh
old render
insulation board
wall construction
adhesive and levelling mortar

Product range

Insulation (mm)


)
)
New build. Renovation

Product name

Product code

and length (mm)

60

40

EJOT H1 eco 095

80

60

EJOT H1 eco 115

8746 115 400

100

80

EJOT H1 eco 135

8746 135 400

120

100

EJOT H1 eco 155

8746 155 400

140

120

EJOT H1 eco 175

8746 175 400

160

140

EJOT H1 eco 195

8746 195 400

180

160

EJOT H1 eco 215

8746 215 400

200

180

EJOT H1 eco 235

8746 235 400

220

200

EJOT H1 eco 255

8746 255 400

240

220

EJOT H1 eco 275

8746 275 400

260

240

EJOT H1 eco 295

8746 295 400

) 10 mm adhesive

) 10 mm adhesive and 20 mm old render

8746 095 400

Packaging: 100 pieces/unit

22

ejotherm NTK U
Telescope anchor
l approved for concrete, solid and perforated masonry
l defined move-in of the washer through the EJOT

telescope effect: with the last blow, the plate decouples


and moves on the sleeve while the expansion zone is
safely anchored
l safe and smooth installation with built-in setting control

through the EJOT telescope effect


l optimised thermal bridge
l minimised risk of breaking nails due to fibre-reinforced

composites
l premounted expansion nail for quick installation

Installation

Technical data

EJOT Telescope Effect

Anchor diameter

8 mm

Washer diameter

60 mm

_
Drill hole depth h1 >

50 mm

_
Anchorage depth hef >

40 mm

Use categories acc. to ETA


European Technical Approval (ETA)

Put the anchor into the borehole until


the washer bears on the insulation,
hammer the nail into the sleeve

A, B, C
ETA-07/0026

Characteristic loads

With the next blow the


washer decouples from
the sleeve and moves
into the insulation

Normal weight concrete C 12/15 acc. to EN 206-1

0.6 kN

Normal weight concrete C 16/20 - C 50/60 acc. EN 206-1

0.9 kN

Clay bricks (Mz) acc. to DIN 105

0.9 kN

Solid lime sandstone (KS) acc. to DIN EN 106

0.9 kN

Vertically peforated clay bricks (Hlz) acc. to DIN 105

0.6 kN

Sand-lime perforated bricks (KSL) acc. to DIN EN 106

0.9 kN

Please note: For calculation of design loads the national safety factors have to
be included (e.g. Germany: 3). Please observe the approval.

Product range

Insulation (mm)


)
)
New build. Renovation

40

Product name

Product Code

and length (mm)


ejotherm NTK U 090

8777 090 100

60 40

ejotherm NTK U 110

8777 110 100

80 60

ejotherm NTK U 130

8777 130 100

100 80

ejotherm NTK U 150

8777 150 100

120 100

ejotherm NTK U 170

8777 170 100

140 120

ejotherm NTK U 190

8777 190 100

160 140

ejotherm NTK U 210

8777 210 100

180 160

ejotherm NTK U 230

8777 230 100

) 10 mm adhesive

) 10 mm adhesive and 20 mm old render

Packaging: lengths 090-150: 200, otherwise 100 pieces/unit

23

ejotherm NT U
Universal hammer-in anchor
l approved for concrete, solid and

tinued
Discon
t
p r od u c

perforate masonry
l solid steel nail (break-proof)
l plastic injection moulding to reduce thermal bridges
l installable with additional washer
l shortest anchorage depths, minimum drill hole depth
l high loads for your security
l economic anchor usage
l premounted nail for quick installation

Technical data

Installation

Anchor diameter

8 mm

Washer diameter

60 mm

_
Drilll hole depth h1 >

35 mm

_
Anchorage depth hef >

25 mm

Use categories acc. to ETA

A, B, C

European Technical Approval (ETA)

ETA-05/0009

Characteristic loads
Normal weight concrete C 12/15 acc. to EN 206-1

1.2 kN

Normal weight concrete C 16/20 - C 50/60 acc. EN 206-1

1.2 kN

Clay bricks (Mz) acc. to DIN 105

1.5 kN

Solid lime sandstone (KS) acc. to DIN EN 106

1.5 kN

Solid masonry of lightweight concrete (V) acc. DIN 18152

0.5 kN

Vertically perforated clay bricks (Hlz) acc. to DIN 105

0.9 kN

Sand-lime perforated bricks (KSL) acc. to DIN EN 106

1.5 kN

Lightweight concrete hollow blocks (HbL) acc. DIN 18151

0.5 kN

Please note: For calculation of design loads the national safety factors have to
be included (e.g. Germany: 3). Please observe the approval.

Product range

Insulation (mm)


)
)
New build. Renovation

Product name

Product code

and length (mm)

60 40

ejotherm NT U 095

80 60

ejotherm NT U 115

8796 115 400

100 80

ejotherm NT U 135

8796 135 400


8796 155 400

8796 095 400

120 100

ejotherm NT U 155

140 120

ejotherm NT U 175

8796 175 400

160 140

ejotherm NT U 195

8796 195 400

180 160

ejotherm NT U 215

8796 215 400

200 180

ejotherm NT U 235

8796 235 400


8796 255 400

220 200

ejotherm NT U 255

240 220

ejotherm NT U 275

8796 275 400

260 240

ejotherm NT U 295

8796 295 400

) 10 mm adhesive

) 10 mm adhesive and 20 mm old render

Packaging: 100 piece/unit

24

EJOT additional plates


Additional plates

d
Modifiery
t
g eome e
h
t
of
r
washe

The washer diameter is enlarged through specially matched


additional washers. In this way the EJOT washer anchor is
perfectly fitted to the demands of different insulation materials. What additional washer is used in a specific case,
depends on the specifications of the ETIC system owner.
When combining our additional washers with ejotherm
STR U or ejotherm STR H for the installation flush with the
surface, the special STR closing plugs have to be mounted.
When using additional washers the STR principle cannot be
applied.

EJOT VT 90

EJOT SBL 140 plus

l washer diameter: 90 mm

l washer diameter: 140 mm

l specially for mineral wool boards with low tensile strength

l specially for mineral wool lamella boards

(please observe the approval)

l high washer solidness for smooth installation

l high washer solidness for smooth move-in of the washer

l high buckling loads thanks to additional plaster bonding

l smooth installation

Product range
Product name

Product code

Packaging
(pieces)

EJOT VT 90

8781 090 008

100

EJOT SBL 140 plus

8716 140 008

100

25

ejotherm anchors for rail fastenings

ejotherm anchors for


rail-fixed ETICS

A special kind of External Thermal Insulation Composite


Systems is the mechanical fixing of the insulation boards with
the help of holding rails. These systems are preferably used on
old facades with large tolerances (unevenness of the old
render) or significantly damaged old render (lose parts,
partially missing old render).
Holding rails of plastic or aluminium are directly fastened on
the substrate with special collar head anchors. Our spacers
EJOT AS balance tolerances and bridge missing parts.
Simply clip the chosen thickness onto the anchor between
wall and holding rail. System-specific insulation boards are
put into the profiles of holding rails through incorporated
grooves.
For additional anchoring of the insulation in the centre of the
board, we recommend our cap anchor ejotherm STR U (see
page 18).

26

ejotherm SDK U
Screw-in anchor for rails
l for installing holding and base rails
l approved for all categories of building materials
l shortest anchorage depths, minimum drill hole depths
l highest loads for maximum safety
l economic anchor usage
l premounted screw for quick installation
l to compensate facade tolerances use spacers EJOT AS

Technical data

Installation

Anchor diameter

8 mm

Collar diameter

16 mm

_
Drill hole depth h1 >

35 mm (75 mm)

_
Anchorage depth hef >

25 mm (65 mm)

Screw drive

TORX T30

Use categories acc. to ETA

A, B, C, D, E

European Technical Approval (ETA)

ETA-04/0023

Values in parentheses: anchoring in gas concrete (use category E)

Characteristic loads
Normal weight concrete C 12/15 acc. to EN 206-1

1.5 kN

Normal weight concrete C 16/20 - C 50/60 acc. EN 206-1

1.5 kN

Clay bricks (Mz) acc. to DIN 105

1.5 kN

Solid lime sandstone (KS) acc. to DIN EN 106

1.5 kN

Solid masonry of lightweight concrete (V) acc. DIN 18152

0.6 kN

Vertically perforated clay bricks (Hlz) acc. to DIN 105


Vertical coring reference bricks (Hlz) acc. NORM B 6124

1.2 kN
0.75 kN

Sand-lime perforated bricks (KSL) acc. to DIN EN 106

1.5 kN

Lightweight concrete hollow blocks (HbL) acc. DIN 18151

0.6 kN

Lightweight aggregate concrete (LAC)

0.9 kN

Autoclaved aerated concrete P2 - P7

0.75 kN

Please note: For calculation of design loads the national safety factors have to
be included (e.g. Germany: 3). Please observe the approval.

To compensate facade tolerances use


spacers EJOT AS (p. 29).

Product range

Max. tolerance

Product name

compensation (mm)

and length (mm)

Product code

20

ejotherm SDK U 045

8798 045 400

40

ejotherm SDK U 065

8798 065 400

60

ejotherm SDK U 085

8798 085 400

80

ejotherm SDK U 105

8798 105 400

Packaging: 100 pieces/unit, in box per 1,000 pieces

27

ejotherm NK U
Hammer-in anchor for rails
l for installing holding and base rails
l approved for concrete, solid and perforated masonry
l shortest anchorage depths, minimum drill hole depths
l high loads for high security
l premounted nail for quick installation
l to compensate facade tolerances use spacers EJOT AS

Installation

Technical data
Anchor diameter

8 mm

Collar diameter

16 mm

_
Drill hole depth h1 >

35 mm

_
Anchorage depth hef >

25 mm

Use categories acc. to ETA

A, B, C

European Technical Approval (ETA)

ETA-05/0009

Characteristic loads
Normal weight concrete C 12/15 acc. to EN 206-1

1.2 kN

Normal weight concrete C 16/20 - C 50/60 acc. EN 206-1

1.2 kN

Clay bricks (Mz) acc. to DIN 105

1.5 kN

Solid lime sandstone (KS) acc. to DIN EN 106

1.5 kN

Solid masonry of lightweight concrete (V) acc. DIN 18152

0.5 kN

Vertically perforated clay bricks (Hlz) acc. to DIN 105

0.9 kN

Sand-lime perforated bricks (KSL) acc. to DIN EN 106

1.5 kN

Lightweight concrete hollow blocks (HbL) acc. DIN 18151

0.5 kN

Please note: For calculation of design loads the national safety factors have to
be included (e.g. Germany: 3). Please observe the approval.

To compensate facade tolerances use


spacers EJOT AS (p. 29).

Product range

Max. tolerance

Product name

compensation (mm)

and length (mm)

Product code

20

ejotherm NK U 045

8797 045 400

40

ejotherm NK U 065

8797 065 400

60

ejotherm NK U 085

8797 085 400

Packaging: 100 pieces/unit, in box per 1,000 pieces

28

Accessories for rail fastenings


EJOT spacers AS
l for levelling out facade tolerances: lengths can be

combined individually (3, 5, 8, 10, 15 mm)


l simply clip onto the anchor between wall and rail
l for anchor diameters 6 mm, 8 mm and 10 mm
l sorted by colour

EJOT profile connector PV


l for connecting profile rails
l simply clip onto the rail elements to be connected
l facilitates the precise adjustment of base rails
l length: 30 mm each

EJOT nail anchors NDK 6 x 60 and 8 x 75


l premounted nail anchor to mount base rails
l diameters: 6 mm and 8 mm

_ 40 mm
l drill hole depth: >
_ 30 mm
l anchorage depth: >

EJOT installation set


l special composition of frequently used accessories for

installing base rails


l set comprises: 75 nail anchors ND-K 6 x 60,

10 profile connectors PV, 50 spacers AS 3

Product range
Product name

Product code

Content/box

Content/order

EJOT AS 3

8600 725 700

100

3,000
2,500

EJOT AS 5

8601 189 710

100

EJOT AS 8

8601 233 720

100

EJOT AS 10

8601 232 750

100

EJOT AS 15

8601 187 730

100

EJOT profile connector PV

8792 030 770

100

EJOT profile connector PV 1150

8792 115 770

10

100

EJOT ND-K 6 x 60

8561 660 400

100

1,000

2,500

EJOT ND-K 8 x 75

8561 875 400

100

1,000

EJOT installation set

8500 000 030

1 set

10 sets

29

EJOT anchors for clinker systems

EJOT anchors for prefabricated


ETICS with clinker

External Thermal Insulation Composite Systems open a


multitude of optical design scopes to significantly improve
energy efficiency and outlook at the same time when renovating a facade. Besides different renderings and colourings,
ceramic claddings have become increasingly popular.
Due to the significantly higher mass per unit area, clinker-built
ETICS are generally anchored.
ETICS with facing clinker that is already glued on the insulation board usually allow for a purely mechanical fastening with
special countersunk anchors directly to the facade. The holes
are almost invisible at the joint pattern.
If the ceramic cladding is glued on after the anchoring, either completely or in parts, it is recommended to
use ejotherm plate anchors. When using the cap anchor
ejotherm STR U with cap, an advantageous decoupling of
the facing clinker from the anchor plates is achieved.

30

EJOT SDFS plus 8UB


Clinker system anchor for concrete and masonry
l approved for concrete, solid and perforated masonry
l torsion-proof anchor tube
l anchor tube with small countersunk head for unobtrusive

installation in the joint


l universal expansion zone for safe anchoring
l high loads
l anchor with increased bending moment
l premounted screw for quick installation

Technical data

Installation

Anchor diameter

8 mm

Diameter of countersunk head


_
Drill hole depth h1 >

12 mm
80 mm

_
Anchorage depth hef >

70 mm

Screw drive

TORX T30

German DIBt Approval

Z21.2589

Design loads
_ C 12/15 acc. to EN 206-1
Normal weight concrete >
_ B 15
Weather shell of concrete >

1.0 kN
0.25 kN

_ Mz 12) acc. to DIN 105


Clay bricks (>
_ KS 12) acc. to DIN EN 106
Solid lime sandstone (>

0.4 kN

_ V 2) DIN 18152
Solid masonry of lightweight concrete (>

0.2 kN

0.4 kN

Vertically perforated clay bricks (Hlz) acc. to DIN 105

Vertical coring reference brick (Hlz) acc. NORM B 6124


_ KSL 6) acc. DIN EN 106
Sand-lime perforated bricks (>

0.25 kN

_ HbL 2) DIN 18151


Lightweight concrete hollow blocks (>

0.15 kN

Lightweight aggregate concrete

0.75 kN

0.3 kN

* according to approval to be determined through pull-out tests at the building


The design loads given are in accordance with the German building code.
National safety factors are already incorporated. Please observe the approval.

Product range
Insulation (mm)

Product name

Product code

zinc-plated steel steel with Deltaseal stainless steel A4


)

and length (mm)

)
New build. Renovation

20

EJOT SDFS plus 8UB x 100

8786 100 460

8786 100 692

40

20

EJOT SDFS plus 8UB x 120

8786 120 460

8786 120 692

8786 100 660


8786 120 660

60

40

EJOT SDFS plus 8UB x 140

8786 140 460

8786 140 692

8786 140 660


8786 160 660

80

60

EJOT SDFS plus 8UB x 160

8786 160 460

8786 160 692

100

80

EJOT SDFS plus 8UB x 180

8786 180 460

8786 180 692

8786 180 660

120

100

EJOT SDFS plus 8UB x 200

8786 200 460

8786 200 660

140

120

EJOT SDFS plus 8UB x 220

8786 220 460

) organic coating for higher corrosion resistance

) 20 mm old render

8786 220 660


Packaging: 100 pieces unit

31

EJOT SDPS plus 8


Clinker system anchor for gas concrete
l approved for gas concrete
l distort-proof anchor tube
l anchor tube with small countersunk head for unobtrusive

installation in the joint


l special expansion zone with hooks for form-fit anchoring
l high loads
l premounted screw for quick installation

Installation

Technical data
Anchor diameter
Diameter of countersunk head
_
Drill hole depth h1 >
_
Anchorage depth hef >

8 mm
12 mm
120 mm
110 mm

Screw drive

TORX T30

German DIBt Approval

Z21.2967

Design loads
Autoclaved aerated concrete acc. DIN (2 and 3.3 resp.)

0.2 kN

Autoclaved aerated concrete acc. DIN (4 and 4.4 resp.)

0.5 kN

Autoclaved aerated concrete acc. TGL (Lauig plant)

0.3 kN

Autoclaved aerated concrete acc. TGL (Parchim plant)

0.15 kN

The design loads given are in accordance with the German building code.
National safety factors are already incorporated. Please observe the approval.

Product range
Insulation (mm)

Product name

and length (mm)

Product code

zinc-plated steel

stainless steel

1)

New build. Renovation

EJOT SDPS plus 8 x 140

85588 14 456

85588 14 656

40 20 EJOT SDPS plus 8 x 160

85588 16 456

85588 16 656

20

60 40 EJOT SDPS plus 8 x 180

85588 18 456

85588 18 656

80 60 EJOT SDPS plus 8 x 200

85588 20 456

85588 20 656

) 20 mm old render

Packaging: 100 pieces/unit

32

Solutions for special applications


EJOT SDMT plus 8/60 U
tinued
Discon
t
p r od u c

Specialist for problematic


substrates
l approved for concrete, solid and

perforated masonry
l universal expansion zone for for problematic substrates

and high tolerances


l also available for very thick insulation (up to 340 mm)
l solid steel screw with plastic injection moulded head
l premounted screw for quick installation

Technical data

Installation

Anchor diameter

8 mm

Plate diameter

60 mm

_
Drill hole depth h1 >

80 mm

_
Anchorage depth hef >

70 mm

Screw drive

TORX T40

Use categories acc. to ETA

A, B, C

European Technical Approval (ETA)

ETA-04/0064

Characteristic loads
Normal weight concrete C 12/15 acc. to EN 206-1

1.5 kN

Normal weight concrete C 16/20 - C 50/60 acc. EN 206-1

1.5 kN

Clay bricks (Mz) acc. to DIN 105

1.5 kN

Solid lime sandstone (KS) acc. to DIN EN 106

1.5 kN

Solid masonry (V) of lightweight concrete acc. DIN 18152

0.9 kN

Vertically perforated clay bricks (Hlz) acc. to DIN 105

1.2 kN

Sand-lime perforated bricks (KSL) acc. to DIN EN 106


Lightweight concrete hollow blocks (HbL) acc. DIN 18151

1.5 kN
0.75 kN

Regarding design loads the national safety factors are to be incorporated.


Please observe the approval.

Product range

Insulation (mm)

Product name


New build. Renovation
1)

Product code

and length (mm)


)

40

EJOT SDMT plus 8/60 U x 120

8753 120 260

60

40

EJOT SDMT plus 8/60 U x 140

8753 140 260

80

60

EJOT SDMT plus 8/60 U x 160

8753 160 260

100

80

EJOT SDMT plus 8/60 U x 180

8753 180 260

120

100

EJOT SDMT plus 8/60 U x 200

8753 200 260


8753 220 260

140

120

EJOT SDMT plus 8/60 U x 220

160

140

EJOT SDMT plus 8/60 U x 240

8753 240 260

180

160

EJOT SDMT plus 8/60 U x 260

8753 260 260

200

180

EJOT SDMT plus 8/60 U x 280

8753 280 260

220

200

EJOT SDMT plus 8/60 U x 300

8753 300 260

240

220

EJOT SDMT plus 8/60 U x 320

8753 320 260

260

240

EJOT SDMT plus 8/60 U x 340

8753 340 260

300

280

EJOT SDMT plus 8/60 U x 380

8753 380 260

340

320

EJOT SDMT plus 8/60 U x 420

8753 420 260

) 10 mm adhesive

) 10 mm adhesive and 20 mm old render

Packaging: 100 pieces/unit

33

Solutions for special applications


Renovation of two-shell masonry
When renovating old building structures and before
installing ETIC systems legislation demands an inspection
of the structural safety of the wall. The structural safety
has to be restored where necessary. Double-leaf walls
with outer leafs, where the connection of the two leafs
is often compromised due to corrosion of the cavity wall
ties, can be restored to structural safety with the EJOT
VSD-8U V.

The zinc-plated steel screw of the EJOT VSD-8U V


with building authorities approval, enables a renovation
of the outer leaf of outdoor buildings, in an industrial
atmosphere and close to the coast. After renovation of
the outer leaf, an additional facade system with thermal
insulation (e.g. ETICS) with a thickness of at least 60 mm
has to be applied. Ventilation behind the outer leaf has to
be prevented also.

EJOT VSD-8U V*
Renovation anchor for prewall shells
l Building authorities approved anchor for renovating
double-leaf masonry
l Double expansion wall anchor: simultaneous fastening

in load-bearing wall and outer leaf


l Clean and fast installation (no mortar required)
l Universal expansion zone: secure installation into

concrete load-bearing shells, solid and perforated brick


masonry

*V: zinc-plated steel screw

Technical data

Installation

_
Anchorage depth hef >
70 mm
>
_
Drill hole depth h1 ld + 10 mm
Drill nominal diameter

8 mm

Screw drive

TORX T25

German DIBt Approval

Z21.21652

Approved substrates
Normal weight concrete C 12/15 acc. EN 206-1
Normal weight concrete C 16/20 - C 50/60 acc. EN 206-1
Clay bricks (Mz) acc. to DIN 105
Solid lime sandstone (KS) acc. to DIN EN 106
Solid masonry (V) of lightweight concrete acc. DIN 18152
Vertically perforated clay bricks (Hlz) acc. to DIN 105
Sand-lime perforated bricks (KSL) acc. to DIN EN 106
Lightweight concrete hollow blocks (HbL) acc. DIN 18151

The EJOT VSD is installed in the centre of the stone.


Minimum thickness of the facing shell: 115 mm.

Product range

Distance between

Product name

inner and outer shell (mm)

and length (mm)

Product code

20

EJOT VSD 8 x 205

8765 205 400

40

EJOT VSD 8 x 225

8765 225 400

60

EJOT VSD 8 x 245

8765 245 400

80

EJOT VSD 8 x 265

8765 265 400

100

EJOT VSD 8 x 285

8765 285 400

120

EJOT VSD 8 x 305

8765 305 400

Packaging: 100 pieces/unit

34

Solutions for special applications


Weather shells of prefabricated building elements (precast
concrete slab-type construction) were installed with steel
tie rods in front of the load-bearing wall. Due to corrosion
influences the stability can be endangered. Thus before
renovating the facade with ETICS, the stability needs to be
rebuilt. EJOT offers two convincing systems.

Renovation rods for weather shells


Renovation systems for rebuilding the stability
of weather shells

EJOT weather shell protection WSS


l to rebuild the stability of weather shells of three-layered

exterior wall panels


l high-grade renovation specifically for the precast concrete

slab-type construction
l dry drilling method applicable
l handling independent of the temperature (without mortar)
l immediately stressable
l with European Technical Approval (ETA-99/0007)

EJOT weather shell protection KERI


l cone anchor to rebuild the stability of weather shells of

three-layered exterior wall panels


l high-grade renovation specifically for the precast concrete

slab-type construction
l handling independent of the temperature (without mortar)
l immediately stressable
l approved by the German Deutsches Institut fr

Bautechnik (Z-21.8-1265)

Product range
Fastening thickness
_ mm
B<

Product name

Product code
8594 241 185

120

EJOT WSS 24 x 185

150

EJOT WSS 24 x 215

8594 241 215

128

EJOT KERI 40 x 205

9710 000 205

163

EJOT KERI 40 x 240

9710 000 240

Our service for you:

Packaging: 100 pieces/unit

For safety reasons, rebuilding the stability of a weather shell or a


facing shell should be calculated by an engineer. Our technical service is happy to help you choose the right renovation solution and
delivers all details necessary.

35

Solutions for special applications


EJOT special drill
For optimum buckling loads in perforated bricks
l special drill for perforated substrates
l aggressive cutting angle for fast drilling without

percussion
l avoids bursting drill holes
l with SDS-plus adapter
l not to be used with percussion or hammer drilling

Product range

Total length/

Product name

Product code

use length (mm)


210 / 150

EJOT special drill 8.0 x 210/150

9200 000 075

260 / 200

EJOT special drill 8.0 x 260/200

9200 000 069

310 / 250

EJOT special drill 8.0 x 310/250

9200 000 087

450 / 400

EJOT special drill 8.0 x 450/400

9200 000 076

EJOT spiral anchor


Fastening solution for light attachments on
ETICS facades
l recommended load: max. 5 kg per mounting point
l no thermal bridges
l simply screw through the final rendering into the insulation

(usually without pre-drilling), fasten a 4-5 mm screw (drive


TORX T40) and fix the attachment

Installation

Product range
Product name

Product code

EJOT spiral anchor

8788 000 002

Packaging: 10 pieces/unit, in box per 250 pieces

36

Fasteners for ceiling insulation

EJOT fastening solutions


for ceiling insulation

The energy optimisation of the building envelope is closely


intertwined with insulating the ceiling on the lowest level.
Especially next to unheated rooms like basements, garages,
warehouses or passages ...
Moreover ceiling insulation is employed to improve acoustics.
It is used for example as noise insulation in commercially used
rooms or halls or as noise protection in shooting ranges.

37

Fasteners for ceiling insulation


EJOT ceiling insulation screw DDS
l fastening of ceiling and acoustic insulation
l easy installation: drill, screw - done!
l short anchorage depth
l plastic injection moulded head with wood wool structure

in colours beige or white for unobtrusive fastening


l special service: coloured varnishing of the screw heads

according to your preferences

Technical data

Installation

Head diameter*

25 mm

Drill hole diameter


_
Drill hole depth h1 >

30 mm

6 mm

_
Anchorage depth hef >

20 mm

Screw drive

TORX T30

Recommended substrate

concrete

*incl. plastic injection moulding

Lieferprogramm

Use length

(mm)

Product name Product code


and length (mm)

Head with plastic Head with plastic

injection moulding white

injection moulding beige

Head coloured
varnishing white

20-30

EJOT DDS 050

8419 050 740

8419 050 780

5919 050 682

35-45

EJOT DDS 065*

8419 065 740

8419 065 780

5919 065 682

45-55

EJOT DDS 075

8419 075 740

8419 075 780

5919 075 682

55-65

EJOT DDS 085

8419 085 740

8419 085 780

5919 085 682

70-80

EJOT DDS 100

8419 100 740

8419 100 780

5919 100 682

80-90

EJOT DDS 110*

8419 110 740

8419 110 780

5919 110 682

95-105

EJOT DDS 125

8419 125 740

8419 125 780

5919 125 682

105-115

EJOT DDS 135

8419 135 740

8419 135 780

5919 135 682

120-130

EJOT DDS 150

8419 150 740

8419 150 780

5919 150 682

135-145

EJOT DDS 165*

8419 165 740

8419 165 780

5919 165 682

145-155

EJOT DDS 175

8419 175 740

8419 175 780

5919 175 682

170-180

EJOT DDS 200

8419 200 740

8419 200 780

5919 200 682

195-205

EJOT DDS 225*

8419 225 740

8419 225 780

5919 225 682

220-230

EJOT DDS 250*

8419 250 740

8419 250 780

5919 250 682

*Special length: available on request

Packaging: 100 pieces/unit

38

Fasteners for ceiling insulation


EJOT ceiling insulation washer DDT
l to combine with ceiling insulation screw

EJOT DDS to enlarge the washer


diameter when it comes to soft insulation
material
l lacquering of the entire surface on

both sides, including the edges

N ew e d
m is
o p t i s he r
wa

l optimised washer geometry for improved fit of

the EJOT DDS screw into the washer


l increased protection from corrosion and sharp edges
l washer diameter: 70 mm
l white lacquering - RAL 9002
l special service: coloured lacquering of the fastener heads

according to customer request

Product range

Product name

Product code

plate white

8721 070 782

EJOT DDT

Packaging: 100 pieces each.

EJOT ceiling insulation anchor DDA


l fastening of ceiling and acoustic insulation
l easy installation: drill, hammer - done!
l available in colours beige or white

Technical data
Head diameter

25 mm

Drill hole diameter


_
Drill hole depth h1 >

35 mm

_
Anchorage depth hef >
Recommended substrate

8 mm
25 mm
concrete

Product range

Insulation (mm)

Product name

Product code

and length (mm)

colour white

colour beige

50

EJOT DDA 075

8552 075 004

8552 075 000

75

EJOT DDA 100

8552 100 004

8552 100 000

100

EJOT DDA 125

8552 125 004

8552 125 000

125

EJOT DDA 150

8552 150 004

8552 150 000

150

EJOT DDA 175

8552 175 004

8552 175 000

Packaging: 400 pieces each.

39

EJOT anchor basics


Building laws background
To harmonise the EU single market the EU Commission
issued a directive on construction parts (89/106 EWG).
It determines which building parts need to comply with the
following essential requirements regarding their intended
use:
l mechanical resistance and stability
l safety in case of fire
l hygiene, health and the environment
l safety in use

are to be regarded. This way, member states may explicitly incorporate specific national or regional requirements
(e.g. different wind loads, safety factors, country-specific
construction methods).
In terms of the EC guideline on construction parts, external
thermal insulation composite systems are kits. The producer whose system receives an ETA is responsible for carefully choosing the single constituents. In accordance with
ETAG 004, components of an ETICS are:

l protection against noise


l energy economy and heat retention

l adhesive
l insulation product

Working groups of the European Organisation for Technical


Approvals (EOTA) have elaborated criteria on how to precisely prove these requirements are fulfilled for ETICS. These
criteria and corresponding testing methods are stated in the
European Technical Approval Guidelines (ETAG). For ETICS
the following guidelines are relevant:
l ETAG 004: external thermal insulation composite systems

with rendering
l ETAG 014: plastic anchors for fixing external thermal
insulation composite systems with rendering
l CUAP according to the relevant ETAG
These guidelines are mandatory for all member states of the
European Union (EU) as for well as those states of the European Free Trade Association (EFTA), that have signed the
agreements of the European Economic Area (EEA), Iceland,
Liechtenstein and Norway. The guidelines form the base for
awarding European Technical Approval (ETA) for individual
products. Construction parts with ETA and certificate of
conformity may carry the CE mark, which enables the free
movement of goods within the member states of the EEA.
This way a uniform appraisal of construction parts and their
fundamental technical specifications is ensured. Therefore
each member state can assume without further testing that
the construction part is generally suitable for the intended
use if planning and construction are done correctly. Nevertheless, the CE mark may not be regarded as a quality mark.

l rendering system (including mesh reinforcement)


l mechanical fixing devices (anchors, holding rails)
l ancillary materials (e.g. corner strips and base profile)

The approval lapses if components of various system


owners are used. This constitutes a breach of the building
code that leads to the loss of the warrantee by the owner
and may have legal consequences.
EJOT advises: Buy all system components
exclusively from the provider of an approved system!
An ETICS itself does not contribute to the structural stability of a building. Especially in renovation the stability of the
wall construction has to be checked if an ETICS shall be
installed. Since it has to carry the dead load of the insulation
system after renovation, the stability might have to be rebuilt
before attaching an ETICS. In particular this effects wall
constructions of multiple shells (buildings with a prewall shell
and precast concrete slab-type constructions).

The guidelines assume a prospective useful life of ETICS


of at least 25 years. In accordance with current practical
experiences, the actual useful life may be much longer without having to fear fundamental quality impairment. In spite
of that, a guarantee towards the system owner or single
components cannot be inferred.
When processing the products, national requirements

40

EJOT anchor basics


Good reasons for anchoring an ETICS
Safe installation on old facades
ETICS are often used for energy efficient refurbishment of
old buildings. Do you know how much load the old render
can actually carry? For decades it was exposed to weather
and emissions, soot, dirt and old paint reduce the bearing
strength of the glue. Or single components are not compatible with the composition of the glue (saponifying). After
installing a new ETICS building physics can change the
bearing capacity of the old render (failure of old render) even
after years. Regarding new buildings residues of release oil on
concrete may cause difficulties. Cleaning a facade is complex
and costly. Contaminated waste water has to be collected
and professionally disposed. Furthermore the old render is
imbued when thoroughly cleaned.

Highest structural stability


When insulation boards are solely glued, the deadweight of
an ETICS is passed onto the wall through shearing forces.
The used glue is therefore the only connection between wall
and insulation. Thanks to their specifically solid anchor plate
and high characteristic loads, ejotherm plate anchors give
your facade safe support. Through contact pressure the frictional bond between facade surface and adhesive as well as
between adhesive and insulation board is steadily increased.
This results in a higher stability of the whole system. Moreover anchors with steel screw or steel nail offer higher safety
reserves.

However if insulation boards are additionally anchored, usually no special treatment of the facade is necessary. Only
loose parts of the render, efflorescence and paint flaking off
need to be roughly removed. Possible holes are filled. Eventually anchors provide safe support

Weathered facade
Z

D
Q

Facade renovated
with an ETICS

Impact of anchoring:
dead load of the system is passed on via adhesive and
insulation
plate anchors provide additional contact pressure
Advantages:
highest stability for the hole system
anchor plates divert wind load
highest security in case of wind loads

41

EJOT anchor basics


Good reasons for anchoring an ETICS
Highest security against hygrothermal impacts
Hygrothermal influences like temperature changes and shrinkage lead to fluctuating material expansion that effect the
rigid adhesive joints. If solely glued there is a latent danger
of the insulation boards to bulge, due to lacking expansion
possibility at the joints. Additional anchoring in the area of the
joints as well as in the centre of the board results in a mechanical fixing of the system onto the wall and therefore reduces
the risk of cracking plaster.

warm outside

Highest security against wind loads


Wind loads affect in the opposite direction of the deadweight.
They provide for a vertical tensile load onto the adhesive joint.
Special importance is attached to the intersection of wall/
adhesive (new buildings) and of old render/adhesive (renovation) respectively as well as of adhesive/insulation.
Particularly high wind loads exist
l at higher buildings
l at building edges
l at free-standing buildings
l in exposed areas
l in coastal areas
l in stormy weather

cold outside

Therefore:

Climate scientists assume that the risk of heavy storms


and grave damages will increase worldwide. EJOT anchors
provide additional security!

Additional fixing of the insulation boards with


ETICS anchors by EJOT

42

EJOT anchor basics


Ways to perfect anchoring
Judginig the substructure
The expansion zone of an anchor has to perfectly fit the wall
substrate found at the building. It is the only way the anchor
can optimally fulfil its function within the ETIC system. This is
why carefully assessing the substructure is highly important.

Determining the anchor type for the substrate


After the substructure is determined, the proper anchor can
be assigned with its approval since anchors with ETA are
tested and approved for specific use categories. The following cases are possible:

ETAG 014 (guideline for anchors in external thermal insulation composite systems) distinguishes standard substrates
according to so-called use categories in order to facilitate the
assignment of the matching anchor.

Case 1: The anchor is approved for the determined building


material category. The identified substrate is mentioned in the
ETA of the anchor.
The anchor may be used on the building without further
testing. The loads given in the approval can be used offhand
for calculating the necessary number of anchors. Where
required, national safety factors need to be observed.

Substrates

Use category A:
Normal weight
concrete

Use category B:
Solid masonry

Example:
Solid lime sandstone was determined as wall substrate.
This corresponds to use category B. The anchor has an
ETA for use categories A and B. For solid lime sandstones,
the ETA mentions a characteristic load of 1.2 kN. National rules require a security value of 3 for use category B.
Therefore the anchor can be calculated having a design load of
1.2 kN : 3 = 0.4 kN without further testing on the building.
Case 2: The anchor has no approval for the determined building material category.

Use category C:
Hollow or perforated
masonry

Use category D:
Lightweight aggregate
concrete

If the determined substrate at the building does not belong to


a use category for which the anchor is approved according to
the ETA, the anchor may not be used on this object. In this
case, the usability of the anchor cannot be proven through
pull-out tests.
Example:
Vertical coring bricks were determined as wall substrate. This
corresponds to use category C. An anchor only approved for
use categories A and B may not be used.

Use category E:
Autoclaved aerated
concrete

43

EJOT anchor basics


Ways to perfect anchoring
Case 3: The anchor is generally approved for the determined
building material category, but the identified substrate is not
explicitly named in the ETA of the anchor.

If in principal several anchor types are applicable in the found


building material, further assessment criteria can be employed.

The anchor may be used if its usability is proven through tests


on the building. The object specific characteristic loads are
determined through pull-out tests as described in the ETA.
When deducting the design load national safety factors need
to be incorporated.

Additonal plates depending on the application

Example:
Perforated lime sandstone was determined as wall substrate.
This corresponds to use category C. The anchor has an ETA
for use categories A, B, C and D. Nevertheless, perforated
lime sandstone is not explicitly named in the ETA. Pull-out
tests with this anchor on the object result in a characteristic
load of 1.5 kN. National rules require a security value of 3
for use category C. The anchor can be calculated having an
design load of 1.5 kN : 3 = 0.5 kN.

Example ejotherm STR U

100% setting control

1)

Homogenous insulation surface

Even rendering

Permanent contact pressure

Less work thanks to premounted


expansion element

Installation behaviour

++

Loads

++

Reduction of thermal bridges

Range of use2 ++
Anchorage depth3 ++
When applying the STR principle for countersunk installation.

A bigger range of application offers more security regarding fluctuating

substrate qualities and mixed masonry.


Please note possible differences between effective and nominal anchorage

Case 4: The anchor is generally approved for the determined


building material category. The identified substrate is already
mentioned in the ETA of the anchor, but the gross density or
the compression strength of the stone differs from the declaration of the approval.
In principle this case corresponds to case 3. The usability for
the substructure can be proven through tests on the building.
Special case: Weather shells of concrete (precast concrete
slab-type construction) are assigned to use category A. With
any ejotherm anchor the loads may be calculated employing
tests on the building.

EJOT advises:
l The ejotherm STR U (as plate anchor) as well as the
ejotherm SDK U (for fastening rails) have a European
Technical Approval for all building material classes. Many
substrates are already tested for the approval and named
in the ETA. Therefore usually no additional tests are
necessary.
l Should tests on the building site be needed, you have
EJOTs service at your hand.

depth when comparing with other products.

Depending on the application, our ETICS anchors are combined with additional plates. The additional plates are very
simple to use and are available in various diameters. They are
put on the plate anchor like a washer. The further installation
is processed as usual. In which case a specific additional
plate is applied, depends on the used insulation and the
system configuration. Crucial are the specifications of the
system owner.
Note: Additional plates are system components of the
anchor. They are tested accordingly and described in the
approval of the anchor. Therefore plate anchors may only be
combined with the matching additional plates by the same
manufacturer.

Further criteria for choosing the perfect anchor

44

EJOT anchor basics


Ways to perfect anchoring
Determining the necessary anchor length
The correct determination of the anchor length is an important prerequisite to obtain the highest fastening safety possible. The object specific preconditions always have to be
taken into account, but determining the necessary anchorage
length itself is easy:

+
+
=

nominal anchorage depth hnom


tolerance compensation ttol
insulation thickness hD
necessary anchor length lD
h1

Determining the necessary number of anchors


The necessary number of anchors has to be determined
for each building individually. According to new European
and national wind load standards several factors have to be
incorporated. Amongst the most essential influences are the
building construction (height, ground plan, profile) as well
as the surroundings of the building. Exposed conditions in
coastal areas, on mountains or outside closed housing areas
normally lead to significantly higher wind loads. Details and
actual maps with zones of different wind loads are part of
national standards.

ttol

h ef = h nom

hD

From the system point of view the anchor usage is increased


by the bearing load of the used insulation board as well as
the characteristic load and the plate stiffness of the employed anchors. Therefore the working guidelines of the ETICS
provider have to be observed.
Generally speaking: the higher the building and the more
exposed its surrounding area, the higher the necessary
number of anchors. On the other hand high-quality anchors
often mean a lower usage of anchors per square metre and
thus save material cost and working hours.

h1 = drill hole depth


hef = effective anchorage depth
hnom = nominal anchorage depth (>_ hef)
ttol = tolerance compensation
hD = insulation thickness
Notes:
If no other specifications are given, the nominal anchorage
depth hnom is equal to the effective anchorage depth hef.
The tolerance compensation consists of:
thickness of old render (if existent, the old render often is
approx. 20 mm thick)
+ thickness of the adhesive joint after pressing the insulation boards against the wall (as a rule approx. 10 mm)*
+ additional compensation of facade unevenness*
= tolerance compensation ttol

Correct processing is crucial for the function of the


anchor
The position of the anchor results from the anchor scheme
of the ETIC system owner. Common anchorage alignments
are for example:
l alignment of anchors for insulation boards with formats

1000 x 500 mm, e.g. rigid foam plates of polystyrene and


800 x 625 mm, e.g. mineral wool plates (table 1)
l alignment of anchors for insulation boards with formats
1000 x 200 mm, e.g. lamella plates of mineral wool
(table 2)
Anchors should always be installed in the area of the adhesive, so that they can support the adhesive joint by means of
contact pressure in the best way possible.

If during the energetic renovation there is a larger facade


unevenness to compensate, it may be necessary to employ
different anchor lengths.

* Facade tolerances are eventually compensated through the actual total thickness
of the adhesive mortar.

45

EJOT anchor basics


Ways to perfect anchoring
Table 1
Anchors per
square metre

Table 2
Anchor alignment

Anchors per

Anchor alignment

square metre

4
4

6
8

10
8

12

10
14

46

EJOT anchor basics


Ways to perfect anchoring
Drilling methods
Depending on the drilling machine and the hammer drill
respectively, the following drilling methods are possible:
l rotary drilling - without percussion
l percussion drilling - many percussions with low energy
l hammer drilling - few percussions with high energy

rotary drilling

percussion drilling

hammer drilling

EJOT special drill for


clean rotary drilling

Standard carbide drill for


percussion and hammer drilling

The drilling method is dependent upon the individual anchorage substructure. It is given in the following table.

Use category
A B C D E
Drilling method

percussion/

rotary drilling without

hammer drilling

percussion

47

EJOT anchor basics


Ways to perfect anchoring
EJOT advises:
When drilling in rotary mode (without percussion), use our
special drills to achieve a clean hole in a short time.
Drills are wearing parts. Their durability depends on the
solidness of the substructure: The harder it is, the higher the
abrasion. To achieve an efficient work progress, drills should
be exchanged in time.
When drilling, please exactly follow the specified installation
values of the individual anchor type (especially the minimum
drilling hole depth). The exact geometry of the drill hole is
important for the bearing capacity of the anchor. Therefore
always drill on a 90 degree angle and never change direction
while drilling. This is especially important with regards to soft
substrates. Before inserting the anchor clean the hole from
drill dust by pulling out the drill several times.
With regards to plate anchors the anchor plates are either
installed countersunk into the insulation board following the
EJOT STR principle or plain with the surface on the insulation
exterior (always in combination with additional plates). When
installing plain with the surface it should be regarded that
the upper side of the anchor plate forms one level with the
upper side of the insulation. When the plate moves in too
deeply, the cavity needs to be levelled out before installing
the mesh. This leads to heightened plaster in the area of the
plate and bears the risk of cracking plaster. When the plate
does not enter deep enough, a thicker mesh layer has to be
installed over the whole facade in order to achieve the minimum render thickness over the anchor plates. This results in
higher costs.
EJOT advises: When using the EJOT STR principle, the
anchor plate is quickly and cleanly countersunk into the
insulation and covered with an STR cap. This way a smooth
and homogenous insulation surface as basis for an even
rendering is established. No additional work for levelling out
the anchor plates is needed. Moreover, the anchor plates are
detached from the rendering.

Plate moves in too deeply

Plate not deep enough

Perfect: installation of ejotherm STR with cap

48

EJOT Building Fasteners


There for you worldwide!
Austria

Germany

Slovakia

EJOT Austria GmbH & Co KG


Grazer Vorstadt 146
A8570 Voitsberg
phone: +43 (31 42) 2 76 000
fax: +43 (31 42) 2 76 0030
email: info@ejot.at
www.ejot.at

EJOT Baubefestigungen GmbH


In der Stockwiese 35
D57334 Bad Laasphe
phone: +49 (27 52) 9 080
fax: +49 (27 52) 9 087 31
email: bau@ejot.de
www.ejot.de

EJOT Slovakia, s.r.o.


Juzn trieda 82 (Arel VSS)
SK04001 Koice
phone: +4 21 (55) 6 22 17 60
fax: +4 21 (55) 6 78 09 57
email: info@ejot.sk
www.ejot.sk

Baltic States

Hungary

Spain

UAB EJOT Baltic


Titnago g. 19
LT02300 Vilnius
phone: +370 (5) 23 11437
fax: +370 (5) 23 11439
email: info@ejot.lt

EJOT Hungria Kft.


csai t 13
H1239 Budapest
phone: +36 1 289 3090
fax: +36 1 289 3091
email: ejot@ejot.hu
www.ejot.hu

EJOT Ibrica S. L.
Pol. P 29 - C/ Azuela 78, nave 4
E-28400 Collado Villalba (Madrid)
phone: +34 (91) 286 1020
fax: +34 (91) 286 1021
e-mail: info@ejot.es
www.ejot.es

Italy

Sweden

EJOT Italia srl.


Via Migliarone, n. 21/bis
I10091 AlpignanoTorino
phone: +39 (011) 9 68 29 00
fax: +39 (011) 9 78 67 41
email: agranero@ejot.it
www.ejot.it

EJOT & AVDEL System AB


Santagsvgen 9
S70236 rebro
phone: +46 (19) 20 65 00
fax: +46 (19) 20 65 14
email: info@ejotavdel.se
www.ejotavdel.se

Norway

Switzerland

EJOT Festesystem A/S


Aslakveien 20A
N0701 Oslo
phone: +47 (23) 25 30 40
fax: +47 (23) 25 30 41
email: festesystem@ejot.no
www.ejot.no

EJOT Schweiz AG
Uttwiler Strae 3
CH8580 Dozwil
phone: +41 (71) 4 14 52 22
fax: +41 (71) 4 14 52 50
email: info@ejot.ch

Poland

EJOT Tezmak
Cebeci Cad. No. 84
TR34100 KkkyIstanbul
phone: +90 (2 12) 5 38 00 01
fax: +90 (2 12) 5 38 00 93
email: info@ejottezmak.com
www.ejottezmak.com

EJOT Benelux bvba / sprl


Reedonk 19-1
B-2880 Bornem
phone: +32 (0)3 740 79 70
fax: +32 (0)3 740 79 79
email: info@ejot.be
www.ejot.be

Bulgaria
EJOT Bulgaria EOOD & Co. KD
Aleksandar Stamboliyski Blvd. 205
- Building B, office 326 BG-1309 Sofia
phone: +359 2 812 6569
fax: +359 2 812 6569
email: mail@ejot.bg

Bosnia and Herzegovina


EJOT d.o.o. Sarajevo
Rajlovacka b.b.
BiH-71000 Sarajevo
phone: +387 33 769 275
fax: +387 33 769 276
email: info@ejot.ba

Croatia
EJOT Spojna Tehnika d.o.o.
Franje Luc ic a 23/3
HR10090 Zagreb
phone: +385 (1) 3 49 86 12
fax: +385 (1) 3 49 89 63
email: ejot@ejot.hr

Czech Republic
EJOT CZ, s.r.o.
Zdebradsk 65
CZ25101 R ic anyJalovice
phone: +420 (3 23) 63 78 11
fax: +420 (3 23) 63 78 18
email: info@ejot.cz
www.ejot.cz

Denmark
EJOT Danmark ApS
Industrisvinget 8
DK-4683 Rnnede
phone: +45 (56) 39 08 42
fax: +45 (56) 39 91 06
email: info@ejot.dk
www.ejot.dk

France
EJOT France S.A.R.L.
Z.l. rue du Climont
F67220 Vill
phone: +33 388.58.92.00
fax: +33 388.58.92.01
email: info@ejot.fr
www.ejot.fr

EJOT The Quality Connection

EJOT Polska
Spka z ograniczon
odpowiedzialnoci Spka
komandyto
Ul. Jeowska 9
PL42793 Ciasna
phone: +48 (34) 3 51 06 60
fax: +47 (23) 3 53 54 10
email: ets@ejot.pl
www.ejot.pl

Turkey

United Arab Emirates

EJOT Romnia S.R.L.


Sos. Bucuresti-Pitesti nr.161 bis
RO-117715 Stefanesti
phone: +40 (2 48) 22 38 86
fax: +40 (2 48) 22 38 87
email: info@ejot.ro

EJOT Middle East FZE


Sharjah Airport International
Freezone
P.O. Box 120588 Sharjah
United Arab Emirates
phone: +971 6-55797-70
fax: +971 6-55797-75
email: mexner@ejot.ae
www.ejot.ae

Russia

United Kingdom

Romania

OOO EJOT Wostok


107497 Russia, Moscow
ul. Amurskaya 5, Bau 7
phone: +7 (495) 941 95 84
fax: +7 (495) 941 95 69
mobile: +7 (910) 002-82 36
email: tkaraduman@ejot.ru
www.ejot.ru

EJOT U.K. Ltd.


Hurricane Close
Sherburn Enterprise Park
SherburninElmet
GBLeeds LS25 6PB
phone: +44 (19 77) 68 70 40
fax: +44 (19 77) 68 70 41
email: info@ejot.co.uk
www.ejot.co.uk

Serbia
EJOT Tehnika spajanja d.o.o.
Autoput BeogradNovi Sad 296X
SCGSerbia, 11080 Zemun
phone: +381 (11) 848 60 82
fax: +381 (11) 848 60 82
email: info@ejot.rs

419E/06.11

Benelux

You might also like