Calculation sheet

xx
xxx
xx
xx
Staircase pressurization fans
xxx

Project
Project Consultant
Client
Contractor
Subject
Location
Fan Type
Design By

xx

Duct Size
(mm)
Item
No. Identification
1.00 Staircase pressurization shaft

Hydrolic
Dia - Dh
(mm)

Length
(m)

Air
Flow
Rate
(L/S)

Duct
Absolute
Renolds
Velocity
roughness Number
(m/s)
(mm)

f'

Darcy
Total
friction
Pressure
coefficient
Drop
Remarks
(f)
(Pa)

1.01 c-d

1550

800 1055.32

5 18632

15.03 1052906

1.3

0.02087

0.02087

13.40

1.02 d-e

1550

800 1055.32

4.9 16562

13.36 932850

1.3

0.02091

0.02091

10.39

1.03 e-f

1550

800 1055.32

4.9 14492

11.69 816255

1.3

0.02095

0.02095

7.97

1.04 f-g

1550

800 1055.32

4.9 12422

10.02 699661

1.3

0.02100

0.02100

5.87

1.05 g-h

1550

800 1055.32

4.9 10352

8.35 583073

1.3

0.02108

0.02108

4.09

1.06 h-i

1550

800 1055.32

4.9

8282

6.68 466478

1.3

0.02119

0.02119

2.63

1.07 i-j

1550

800 1055.32

4.9

6212

5.01 349890

1.3

0.02138

0.02138

1.49

1.08 j-k

1550

800 1055.32

5.95

4142

3.34 233295

1.3

0.02173

0.02173

0.82

1.09 k-l

1550

800 1055.32

4.55

2072

1.67 116707

1.3

0.02270

0.02270

0.16

Refer eq.21, ASHRAE


Fundamentals HB 1997
Refer eq.21, ASHRAE
Fundamentals HB 1997
Refer eq.21, ASHRAE
Fundamentals HB 1997
Refer eq.21, ASHRAE
Fundamentals HB 1997
Refer eq.21, ASHRAE
Fundamentals HB 1997
Refer eq.21, ASHRAE
Fundamentals HB 1997
Refer eq.21, ASHRAE
Fundamentals HB 1997
Refer eq.21, ASHRAE
Fundamentals HB 1997
Refer eq.21, ASHRAE
Fundamentals HB 1997

Calculation sheet

Item
No. Identification

Duct Size

2.00 Straight Duct Section


2.01 a-b
1350 1300
2.02 b-c
1350 1300
Duct Fittings
3.00 Bends & Elbows
b-90 degree
3.01 bend
1350 1300
c-90 degree
3.02 bend
1000 800

Length
(m)

No of
Fittings
&
Accesso
ries

5.84
5.98

Air
Flow
Rate
(L/S)

18632
18632

Duct Velocity
Loss
Equivalent
Velocity Pressure Coefficients
Dia (mm)
(m/s)
(Pa)
for Fittings

10.62
10.62

67.85
67.85

Pressure
Drop
(Pa/m)

1448.1
1448.1

0.74
0.74

Total
Pressure
Drop
(Pa)

Remarks

4.34
4.44

Refer Table 14-10-F, SMACNA

1 18632

10.62

67.85

0.21

1448.1

14.25 1990, R/W=1

1 18632

23.29 326.54

0.23

976.2

73.80 1990, R/W=1

4.00 Tees

Refer Table 14-10-F, SMACNA

Refer Table 14-14-Q SMACNA

4.01 d-main

1550

800

1 18632

15.03

135.92

0.01

1201.1

1.51 1990

4.02 e-main

1550

800

1 16562

13.36

107.39

0.01

1201.1

1.34 1990

4.03 f-main

1550

800

1 14492

11.69

82.23

0.01

1201.1

1.18 1990

4.04 g-main

1550

800

1 12422

10.02

60.41

0.02

1201.1

1.03 1990

4.05 h-main

1550

800

1 10352

8.35

41.96

0.02

1201.1

0.84 1990

4.06 i-main

1550

800

8282

6.68

26.85

0.03

1201.1

0.81 1990

4.07 j-main

1550

800

6212

5.01

15.11

0.05

1201.1

0.69 1990

4.08 k-main

1550

800

4142
2062

3.34

6.72

0.09

1201.1

0.60 1990

Refer Table 14-14-Q SMACNA


Refer Table 14-14-Q SMACNA
Refer Table 14-14-Q SMACNA
Refer Table 14-14-Q SMACNA
Refer Table 14-14-Q SMACNA
Refer Table 14-14-Q SMACNA
Refer Table 14-14-Q SMACNA

Calculation sheet

5.00 Transition
a - Transition
(1250x12505.01 1250)
a - Transition
(12505.02 1350x1300)
c - Transition
(1350x13005.03 1000x800)
c - Transition
(1000x800 5.04 1550x800)

Refer Table 14-12-A SMACNA

1250

1 18632

15.18

138.77

0.06

1250.0

7.82 1990

1250

1 18632

15.18

138.77

0.21

1250.0

29.56 1990

Refer Table 14-11-B SMACNA

Refer Table 14-12-A SMACNA

1000

800

1 18632

23.29

326.54

0.06

976.2

19.90 1990

1000

800

1 18632

23.29

326.54

0.23

976.2

74.86 1990

800

500

2072

5.18

16.15

0.52

686.7

8.40 1990

1 18632

11.92

85.60

0.52

1366.5

44.51 1990

Refer Table 14-11-B SMACNA

6.00 VCD/ damper


6.01 l-Airfoil blade
6.02 a-Airfoil blade

1250 1250

External Static Pressure of Staircase pressurization fan(Pa)


Add 20% safety factor
Total External Static Pressure of Staircase pressurization fan (External static pressure+20%SF+50) (Pa)

Refer Table 14-18-E SMACNA


Refer Table 14-18-E SMACNA

336.72
67.34
455.00

Notes
- Vertical duct section (from "c" to "l") - concreate construction
- Duct section in the roof - Sheet metal (GI)
- Absolute roughness () of concrete
1.3 mm
( pg. 32.7, ASHRAE Fundamentals HB 1997 )
- The size of virtical duct section (shaft) should be equal to the slab opening size (1550x800 mm) and finished using side walls.
9 numbers of wall openings (600x900 mm ) should be provided for the air terminals.
- Total External Static Pressure of Staircase pressurization fan = External static pressure + 20%SF + 50 (pa)