RTU560

ABB Utilities GmbH

Remote Terminal Unit


Connections and Settings
Power Supply Unit 560PSU81

Processing functions

Application, characteristics and technical data


have to be taken from the hardware data sheet:

The 560PSU81 board has a fixed location in the


housing. If an output voltage is lost the green LED
is off.

560PSU81 1KGT 150 494

Operation

Total power output

The power supply unit 560PSU81 is an AC/DC


converter for an input voltage 110 or 230 V AC. It
supplies an output voltage of 24 V DC and
5 V DC. With an optional battery the 560PSU81 is
a power backup system (UPS).

The 560PSU81 supplies a total outputs of:


U1
5 V DC = max. 2.5 A
U2

24 V DC = max. 0.5 A

Pout

24 V DC = max. 0.1 A

Pin

24 V DC = max. 0.15 A

F3

PO +24V

PG

24V

5V

GND

PE

TA/B

PO +24 V
PG

560PSU81

F4

F5

Ut2

Ut1

L1

PE

PI +24V

PG

Ub

F2

F1
5V
24V

GND

TA/B

F6

560MIO80

Fig. 1:

Block diagram power supply unit 560PSU81

Doc.-No.: 1KGT 150 511 V001 1

ABB Utilities GmbH


Connections and Settings 560PSU81

RTU560

Settings

560MIO80 (opt.)

560CMU80

560MIO80 (opt.)

Rack Address = 1
I/O Bus termination:
Set for TA and TB

Rack Address = 1
I/O Bus termination:
OFF for TA/TB

TA/TB

Rack Address = 2

560MIO80 (opt.)

560MIO80 (opt.)

560MIO80 (opt.)

560MIO80 (opt.)

560MIO80 (opt.)

560MIO80 (opt.)

560PSU80/81

Rack Address = 7
I/O Bus termination:
ON for TA/TB

RTU560E I/O Extension units

I/O Bus address and I/O Bus termination can be


set according to Fig. 4 I/O Bus can be connected
via 560PSU81 connector X6 TA and TB. For

560MIO80 (opt.)

Rack Address = 3

I/O Bus termination:


OFF for TA/TB

Fig. 3:

560MIO80 (opt.)

560PSU80/81

560MIO80 (opt.)

560MIO80 (opt.)

560MIO80 (opt.)

560PSU80/81

RS485 I/O Bus

560MIO80 (opt.)

560CMU80

560MIO80 (opt.)

560MIO80 (opt.)

560MIO80 (opt.)

RTU560E stand alone RTU

560PSU80/81

Fig. 2:

560MIO80 (opt.)

560PSU80/81

RTU560E can be used as stand alone RTU


(see Fig. 2). It is although possible to use
RTU560E as I/O Extension unit (see Fig. 3).

optical connections between the different


RTU560E housing 560FOC80 can be used.

Doc.-No.: 1KGT 150 511 V001 1

ABB Utilities GmbH


Connections and Settings 560PSU81

1 2

TB / X12

1 2

Termination for I/O = bus


TA / X11
1 2

1 2

1 2

1 2

1 2

1 2

1 2

1 2

1 2

1 2

1 2

1 2

1 2

Rack
address

Not
terminated

Terminated
1 2

RTU560

1 2

1 2

1 2

1 2

1 2

1 2

1 2

1 2

1 2

1 2

1 2

DA7 / X10 not used

Fig. 4:

DA6 / X9

not used

DA5 / X8

not used

DA4 / X7

not used

1 2

1 2

1 2

1 2

1 2

Configuration jumper X7 to X12

battery

battery

X3
Ut2

sensor

Ut1
-Ub
+Ub

560PSU81

Fig. 5:

Connection of battery and sensor

Doc.-No.: 1KGT 150 511 V000 1

ABB Utilities GmbH


RTU560

Connections and Settings 560PSU81

PE
N

X2

X2 = supply voltage

X3

X3 = battery and sensor

Ut2
Ut1
-Ub
+Ub
PO
PG
PG
PG
PG
PG

X4

X4 = process power for binary output

PG
PG
PG
PI
PI
PI
PI
PI
PI

X5

X5 = process power for binary inputs

X6

X6 = to fibre optic coupler 560FOC80

PI
PI
PG
+24V / U2
+5V / U1
GND
TB
TA

Fig. 6:

560PSU81

Connector assignment

Doc.-No.: 1KGT 150 511 V001 1

ABB Utilities GmbH


RTU560

Connections and Settings 560PSU81

PE
X2

N
L
F1 (fuse)

X12

X3

TB
X11

TA
X10

F2 (fuse)

DA7
X9
DA6
X8

TR1

X4

DA5
X7

X5
TR2

ABB 560PSU81R0001

DA4

F4 (24 V fuse
X6

F3 (5 V fuse)

Error
5 / 24 V DC

Fig. 7:

Board layout with setting positions

Doc.-No.: 1KGT 150 511 V000 1

ABB Utilities GmbH


Connections and Settings 560PSU81

RTU560

)**