You are on page 1of 1

MEDIUM VOLTAGE CABLES

CE

N2XSY 6/10 kV, 12/20 kV, 18/30 kV


PVC- jacket

Technical data:

Cable Structure:
Conductor:

circular bare cu-conductor of stranded


wires to HD 383

Temperature Range:

during installation up to - 5C

Insulation:

core insulation of cross-linked


polyethylene (XLPE), PE-compound
DIX8 to HD 620.1

Operating
temperature:

max. + 90C

Screen:

screen of copper wires and one or two


copper tape(s) applied helically.

Short circuit
temperature:

Outer jacket:

PVC-outer jacket black, compound DMV 6


to HD 620.1, jacket colour red.

Nominal voltages:

U /U 6/10 kV, 12/20 kV, 18/30 kV

Application

Operating voltages:

for

6/10 kV = max. 12 kV
12/20 kV = max. 24 kV
18/30 kV = max. 36 kV

Test voltages:

for

6/10 kV = 15 kV
12/20 kV = 30 kV
18/30 kV = 45 kV

Min. Bending Radius:

15 x d

Suitable for installation mostly for power supply


stations, in indoors and in cable ducts, outdoors,
underground, and in water as well as for installation
on cable trays for industries, switch-boards and power
stations. Due to the good laying characteristics, this
can also be laid easily in difficult line guideways.
See DIN VDE 0298 part 1 .
To avoid the influence of the outer interferences, an
adherent semi conductive layer is extruded between
the conductor and the VPE insulation and also a
concentric copper conductor wich guarantees the
field-limitation and the resistance to the partial
discharges 2 pC by a measuring volt of 2 U .
Installation notes:

Item no.
6/10 kV
20001064
20001065
20001066
20001067
20001068
200010691
20001069
200010701
20001070
200010711
20001071
20001072
20001073
20001074
12/20 kV
20002064
20002065
20002066
20002067
20002068
200020691
20002069
200020701
20002070
200020711
20002071
20002072
20002073
20002074

To guarantee an optimum on operating reliability


the extruded semi-conductive layer is spliced with
the insulation for long duration.
For this reason we reccomend a peeling tool for
installation.

No. of cores
x cross section
n x mm

Insulation PVC-jacket
Outer
Copper
AWG
Weight
thickness thickness min. - max. weight
mm
mm
mm ca.kg/km ca.kg/km no.*)
mm

Item no.

518
662
860
1098
1340
1622
1725
1958
2059
2486
2587
3163
4234
5194

905
2
1080
1
1310
2/0
1580
3/0
1860
4/0
2040
250 MCM
2210
250 MCM
2450
350 MCM
2580
350 MCM
3000
450 MCM
3130
450 MCM
3780
550 MCM
4670
750 MCM
5750 1000 MCM

32
2.5
518
27
5.5
33
2.5
28
662
5.5
2.5
35
30
854
5.5
2.5
36
31
1094
5.5
2.5
38
33
1334
5.5
2.5
39
34
1622
5.5
2.5
39
34
1723
5.5
2.5
41
36
1958
5.5
2.5
41
36
2059
5.5
2.5
39
44
2486
5.5
2.5
39
44
2587
5.5
2.5
41
46
3163
5.5
2.5
44
49
4234
5.5
47
2.5
52
5194
5.5
* For cables laying in earth a screen-cross section of 16 mm is permitted.

2
1110
1250
1
1510
2/0
1780
3/0
2070
4/0
2310 250 MCM
2420 250 MCM
2650 350 MCM
2810 350 MCM
3260 450 MCM
3360 450 MCM
4020 550 MCM
4930 750 MCM
6050 1000 MCM

1x35 rm/16
1x50 rm/16
1x70 rm/16
1x95 rm/16
1x120 rm/16
1x150 rm/16*
1x150 rm/25
1x185 rm/16*
1x185 rm/25
1x240 rm/16*
1x240 rm/25
1x300 rm/25
1x400 rm/35
1x500 rm/35

250C
(short circuit duration up to 5 sec.)

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

1x35 rm/16
1x50 rm/16
1x70 rm/16
1x95 rm/16
1x120 rm/16
1x150 rm/16*
1x150 rm/25
1x185 rm/16*
1x185 rm/25
1x240 rm/16*
1x240 rm/25
1x300 rm/25
1x400 rm/35
1x500 rm/35

2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5

23
24
26
27
29
30
30
32
32
34
34
36
40
43

28
29
31
32
34
35
35
37
37
39
39
41
45
48

18/30 kV
20003065
20003066
20003067
20003068
20003069
20003070
20003071
20003072
20003073
20003074

Outer
No. of cores
Copper
Insulation PVC-jacket
x cross section thickness thickness min. - max. weight Weight AWG
mm
mm ca.kg/km ca.kg/km no.*)
n x mm
mm
mm
1x50 rm/16
1x70 rm/16
1x95 rm/16
1x120 rm/16
1x150 rm/25
1x185 rm/25
1x240 rm/25
1x300 rm/25
1x400 rm/35
1x500 rm/35

8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0

2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5

33
35
36
38
39
41
43
46
49
52

38
40
41
43
44
46
48
51
54
57

662
854
1094
1334
1723
2059
2587
3163
4234
5194

1480
1730
2060
2330
2720
3100
3730
4000
5330
6480

1
2/0
3/0
4/0
300 MCM
350 MCM
500 MCM
600 MCM
750 MCM
1000 MCM

Other constructions and sizes are available on request.

D12
BAGNOLO IN PIANO (RE) - ITALY

TEL : +39 0522 958938 - FAX : +39 0522 951882 - www.elettrotekkabel.com

You might also like