4. Anti-Corrosion Treatment
4.1

Anti-Corrosion Treatment

4.1.1 Installation Atmosphere


Outdoor units with anti-corrosion specifications are designed specifically for use in areas which are subject to salt
damage and atmospheric pollution. The following anti-corrosion specifications are available.
This specification is recommended by Daikin and shall be used as a reference.
< Anti-Corrosion type>
Symbol

Type

Anticorrosion
type

Installation example

Conditions of Installation location

Where the distance between the outdoor unit and the


sea shore is more than 300m and less than 1km.

Remark:
1. The Anti-Corrosion specification means the specification which allows the unit to be installed in the atmosphere of sea wind but
not at the location where the sea wind directly blows on the unit.
2. The units with this specification are manufactured by customers request on mass production base.

< Heavy Anti-Corrosion type>


Symbol

Type

Heavy
Anticorrosion
type

Installation example

Conditions of Installation location

Where the distance between the outdoor unit and the


sea shore is less than 300m.

Remark:
1. The Heavy Anti-Corrosion specification means the specification which allows the unit to be installed in the atmosphere of sea
wind where the sea wind directly blows on the unit.
2. The units with this specification are manufactured by the customers request.

4.1.2 Standard Specification

Portions directly
exposed to
corrosive air

Portions directly
exposed to
corrosive
atmosphere

Portions

Others

Applicable model

Standard specification

Ceiling Panel

All models

Weather resistant polypropylene resin

Side panel
Outer panel

All models

Alloyed hot-dip zinc coated steel plate + powder polyester resin coating
on both inner and outer surfaces in thickness of 32 or more

Bottom frame

All models

Galbarium steel plate (alloyed hot-dip aluminium, Zinc, and silicone


coated steel plate)

Finned coil protective net

All models

Resin coating

Fan protective net

All models

Weather resistant polypropylene resin

Heat exchanger

All models

Copper pipe-aluminium fin (Special acrylic resin coated)

Fan

All models

Styrene-acrylonitrile resin (Glass fiber filled)

Fan motor

All models

Motor manufacturers standard specification

Support and Frame

All models

Alloyed hot-dip zinc coated steel plate

Control box

All models

Alloyed hot-dip zinc coated steel plate

Pressure vessel

All models

Hot-rolled steel plate + Normal dry painting (two coats)

Screws, bolts

All models

Zinc-nickel alloy plating

Guide Specifications

787

17

Anti-Corrosion Treatment

EDAU37-750

4.1.3 Anti-Corrosion Specification

Portions directly exposed to corrosive air

Portions directly
exposed to
corrosive atmosphere

Portions

Others

Ceiling panel
Side panel
Outer panel
Bottom frame
Finned coil
protective net
Fan protective net
Heat exchanger
Fan
Fan motor

Anti-Corrosion
specification (E)

Heavy Anti-Corrosion
specification ()

Weather resistant polypropylene resin


Alloyed hot-dip zinc coated steel
plate + corrosion protection
powder polyester resin coating
on both inner and outer surfaces
in thickness of 64 or more

Alloyed hot-dip zinc coated steel plate


+ powdered polyester resin
+ fluoroplastic internal and external
surfaces 48 or more

Resin coating containing


Ultraviolet ray absorbent
Weather resistant polypropylene resin
Copper pipe-aluminium fin
(special acrylic resin coated)
Styrene-acrylonitrile resin (Glass fiber filled)
Motor manufactures standard specification

Support and Frame

Hot-dip zinc coated steel plate + rust


preventive powder resin coating on
both inner and outer surfaces in
thickness of 64 or more.

Hot-dip zinc coated steel plate + thick


film epoxy 120 or more.

Control box

Hot-dip zinc coated steel plate + rust


preventive powder resin coating on
both inner and outer surfaces in
thickness of 64 or more.

Hot-dip zinc coated steel plate + thick


film epoxy 120 or more.

Pressure vessel

Hot-rolled steel plate + Rust preventive Hot-rolled steel plate + thick film
treatment: Rust inhibitor coating
modified epoxy 120 or more

Screws, bolts

SUS410 + Zinc-nickel alloy plating


+ Zinc chrome acid film treatment
+ Rust inhibitor coating

Notes:
Applicable Models as follows
REYQ8~48P : Standard
The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as REYQ8~48PY1E.
It is advisable to follow the installation and maintenance precautions below.
Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are
produced.
If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided
and choose an outdoor unit with anti-corrosion treatment.
Install the machine to the leeward of the building.
Even if it is unavoidable to install the machine on the seaside, set up a windbreak not to get it exposed to the sea
breeze.
Be careful not to confuse the setup direction. (Corrosion depends on whether the unit is placed parallel with or at
right angles to the sea.)
Select a well-drained spot.
When installing the machine on the seashore or in such an ambient condition, contact your DAIKIN dealer.
Models for Heavy Anti-Corrosion Specification Manufactured by Customers Request.

788