You are on page 1of 480

Operating Manual

Amplifier system

MGCplus
with display and control panel

AB22A/AB32

B0534-18.0 en

sdjki

Contents

A Introduction
1

Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A-3

Notes on the documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A-8

System description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A-10

MGCplus housing versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A-13

Structure of the MGCplus device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A-15

Insert communications processor CP22/CP42 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A-17

Modules in the MGCsplit system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A-20

7.1

Measurement module, enclosure 1SH400 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A-21

7.2

Measurement module, enclosure 1SH650 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A-22

7.3

Processor modules 1SH400CP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A-23

7.4

LED display for modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A-24

7.5

Connecting to MGCplus systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A-27

7.6

Enclosure dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A-32

Conditions on site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A-35

Maintenance and cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A-36

MGCplus with AB22A/AB32

B Connecting
1

Connection: desktop housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-3

1.1

Mains connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-3

1.2

Battery connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-4

1.3

Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-6

Connecting the ABX22A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-8

Shielding design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-11

Connecting transducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-12

4.1

Connecting separate TEDS modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-13

4.2

Strain gage full bridges, inductive full bridges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-14

4.3

SG full bridges with AP810/AP815i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-15

4.4

Strain gage half bridges, inductive half bridges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-16

4.5

LVDT-Transducer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-17

4.6

SG half bridges with AP810/AP815i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-18

4.7

Connecting a single strain gage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-19

4.7.1

Compensating resistor external . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-19

4.7.2

Compensating resistor external with AP815i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-20

4.7.3

Single strain gage with AP14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-21

4.7.4

Single strain gage with AP814Bi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-22

4.7.5

Single strain gage with AP815i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-23

4.7.6

SG systems and rosettes on AP815i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-24

Torque flange T10FSF1, T10FSU2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-26

4.8.1

Torque measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-26

AP460i Pin assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-28

4.8

MGCplus with AB22A/AB32

Rotation speed measurement (symmetrical signals) . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.8.3

B-29

Rotation speed measurement (symmetrical signals) with reference signal . . . . . . . .

B-31

Torque transducers (T3...FN/FNA, T10FKF1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-33

4.9.1

Torque measurement (square-wave excitation voltage) . . . . . . . . . . . . . . . . . . . . . . . .

B-33

4.9.2

Rotation speed measurement (asymmetrical signals) . . . . . . . . . . . . . . . . . . . . . . . . . .

B-35

Torque transducers (T1A, T4A/WA-S3, T5, TB1A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-37

4.10.1 Torque measurement (slip ring or direct cable connection) . . . . . . . . . . . . . . . . . . . . . .

B-37

4.10.2 Rotation speed and angle of rotation measurement (T4WA-S3) . . . . . . . . . . . . . . . . .

B-38

4.10.3 Rotation speed measurement with inductive transducers . . . . . . . . . . . . . . . . . . . . . . .

B-41

4.11

Thermocouples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-42

4.12

DC voltage sources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-44

4.13

DC power source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-48

4.14

Resistors, Pt10, 100, 1000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-49

4.15

Frequency measurement without a direction of rotation signal . . . . . . . . . . . . . . . . . . . . . . . . . .

B-51

4.16

Frequency measurement with direction of rotation signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-52

4.17

Impulse counting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-53

4.18

Active and passive piezoelectric transducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-55

4.19

Piezoresistive transducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-56

4.20

Potentiometric transducers (singlechannel) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-57

4.21

Potentiometric transducers (Multichannel) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-58

4.22

Connection via distributor board VT814i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-59

4.23

Connection via distributor board VT810/815i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-60

Connecting the MGCsplit modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-62

4.9

4.10

4.8.2

5.1

Split-line-cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-62

5.2

Power supply units NT650/NT651 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-63

5.3

Amplifier modules and connection boards in the 1SH400 enclosure . . . . . . . . . . . . . . . . . . . .

B-73

5.3.1

Amplifier modules that can be connected . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-73

5.3.2

Connection boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-74

MGCplus with AB22A/AB32

5.4

Connecting the MGCsplit modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-75

5.5

Inputs/outputs for measurement modules SH400/SH650 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-76

5.6

AP409 connection boards in the 1SH650 enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-77

5.7

AP401 connection boards in the 1SH650 enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-78

5.8

AP815i connection boards in the 1SH650 enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-79

5.9

AP460i connection boards in the 1SH650 enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-80

5.10

AP13i connection boards in the 1SH650 enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-81

5.11

AP17 connection boards in the 1SH650 enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-85

5.12

AP71 connection boards in the 1SH650 enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-89

5.13

AP78 connection boards in the 1SH650 enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-90

5.14

AP75 connection boards in the 1SH650 enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-93

Connecting CANHEAD modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-96

6.1

ML74 communication module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-97

6.2

AP74 connection board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-98

Connecting the computer, PLC and printer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-99

Connecting a shunt resistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-100

Inputs, Outputs and remotes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-101

9.1

Inputs and Outputs CP22/CP42 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-101

9.2

Analogue output on the front panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-104

9.3

Connection boards AP01i...AP18i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-105

9.3.1

Pin assignment AP01i/03i/05/08/09/11i/14/17/18i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-106

AP02 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-111

AP07/1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-113

AP13i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-116

AP77 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-119

MGCplus with AB22A/AB32

9.3.2

Installing the EM001 final stage module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-120

AP07/1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-121

AP08/14/17/18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-122

AP09 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-124

C Commissioning
1

Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1

Devices in the desktop housing and rack frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

C-3
C-4

D Functions and symbols on the AB22A/AB32


1

Control elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

D-3

1.1

AB22A control elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

D-3

1.2

AB32 control elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

D-4

Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

D-5

2.1

The first display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

D-5

2.2

Display in measuring mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

D-6

2.3

Messages on the AB22A/AB32 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

D-10

AB22A/AB32 in set-up mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

D-11

3.1

Calling up menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

D-13

3.2

Quitting menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

D-14

3.3

Channel selection in measuring mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

D-15

3.4

Channel selection in set-up mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

D-16

MGCplus with AB22A/AB32

3.5

Saving the set-ups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

D-17

3.6

Selection menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

D-18

3.7

Elements in the set-up window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

D-19

E Measure
1

General notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-3

Basic measurement channel set-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-4

2.1

Adaptation to the transducer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-6

2.1.1

Extended functions of the ML38B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-7

2.2

TEDS transducer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-9

2.3

Signal conditioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-13

2.4

Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-16

2.5

Analogue outputs (one-channel modules only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-17

Adaptation to the transducer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-20

3.1

3.2
3.3

3.4

SG transducer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-20

3.1.1

Direct input of transducer characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-21

3.1.2

Calibrating the characteristic curve of the transducer . . . . . . . . . . . . . . . . . . . . . . . . . .

E-24

Strain gages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-27

3.2.1

Direct input of transducer characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-29

Inductive transducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-31

3.3.1

Direct input of transducer characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-32

3.3.2

Calibrating the characteristic curve of the transducer . . . . . . . . . . . . . . . . . . . . . . . . . .

E-34

Torque transducer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-37

3.4.1

Direct input of torque characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-39

3.4.2

Measuring with the built-in shunt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-41

MGCplus with AB22A/AB32

3.5

Adapting the rotation-speed channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-45

Thermocouples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-49

3.6.1

Direct input of transducer characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-50

Current and voltage measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-52

3.7.1

Direct input of transducer characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-53

Resistance temperature detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-55

3.8.1

Direct input of transducer characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-56

Resistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-58

3.9.1

Direct input of transducer characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-59

Impulse counting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-61

3.10.1 Direct input of transducer characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-62

Piezoelectric transducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-66

3.6
3.7
3.8
3.9
3.10

4.1

Connecting and measuring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-68

4.1.1

Direct input of transducer characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-70

4.1.2

Setting up the zero point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-72

4.1.3

Special case: initial charge is known . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-73

Drift balancing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-74

Current-fed piezoelectric transducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-75

4.2

5.1

Direct input of transducer characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-76

Piezoresistive transducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-78

6.1

Direct input of transducer characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-79

6.1.1

Measuring transducer characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-81

Potentiometric transducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-83

7.1

Direct input of transducer characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E-84

7.1.1

E-86

Measuring transducer characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

MGCplus with AB22A/AB32

10

F Additional functions
1

Remote (one-channel modules only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F-3

1.1

Switching on remote control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F-3

1.2

Assigning remote contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F-4

Limit switches (one-channel modules only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F-6

2.1

Activate limit switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F-7

2.2

Setting up limit switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F-8

2.3

Selection keys in the menu Limit switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F-11

Combine limit switches (one-channel modules only) . . . . . . . . . . . . . . . . . . . . . . .

F-12

Adjusting peak values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F-15

4.1

Peak value stores . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F-15

4.2

Combine peak value stores . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F-16

4.3

Controlling the peak value store . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F-18

4.4

Peak value operating mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F-19

4.5

Current value operating mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F-20

4.6

Envelope curve operating mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F-21

4.7

Clear peak value store . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F-22

Version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F-23

Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F-24

MGCplus with AB22A/AB32

11

G Display
1

Display format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

G-3

1.1

Select set-up window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

G-4

1.2

Set-up window Display format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

G-5

1.3

Set-up window components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

G-6

1.3.1

Numerical display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

G-7

1.3.2

Graphic display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

G-17

1.4

Status limit switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

G-21

1.5

Status data acquisition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

G-22

F-keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

G-23

2.1

F-keys in measuring mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

G-23

2.2

F-keys in set-up mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

G-26

Channel names . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

G-27

H System
1

Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

H-3

1.1

Define new user . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

H-4

1.2

Enable password protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

H-5

1.3

Set operator access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

H-6

1.4

Delete user . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

H-7

1.5

Change password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

H-8

Save/Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

H-9

MGCplus with AB22A/AB32

12

Recording measurement series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


3.1

H-14

Setting the measurement series parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

H-15

Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

H-32

Print . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

H-37

Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

H-38

Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

H-39

Menu structure

Specifications

Single-channel amplifier plug-in modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

J-3

1.1

General data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

J-3

1.2

Single-channel amplifier plug-in module ML01B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

J-5

1.3

Single-channel amplifier plug-in module ML10B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

J-8

1.4

Single-channel amplifier plug-in module ML30B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

J-11

1.5

Single-channel amplifier plug-in module ML35B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

J-13

1.6

Single-channel amplifier plug-in module ML38B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

J-15

1.7

Single-channel amplifier plug-in module ML50B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

J-17

1.8

Single-channel amplifier plug-in module ML55B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

J-19

1.9

Single-channel amplifier plug-in module ML55BS6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

J-21

1.10

Single-channel amplifier plug-in module ML60B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

J-24

MGCplus with AB22A/AB32

13

Connection boards for one-channel amplifiers . . . . . . . . . . . . . . . . . . . . . . . . . . . .

J-26

Multi-channel amplifier module ML455 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

J-34

Multi-channel amplifier plug-in module ML460 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

J-36

Multi-channel amplifier plug-in module ML801B . . . . . . . . . . . . . . . . . . . . . . . . . . .

J-41

Multichannel amplifier connection boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

J-51

Multichannel amplifier connection boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

J-52

Programmable plugin module ML70B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

J-53

Communication module ML71B/ML71BS6 with AP71 (CANbus) . . . . . . . . . . . . .

J-56

Communication module ML74 with AP74 (CANHEAD) . . . . . . . . . . . . . . . . . . . . . .

J-58

Communication module ML77B with AP77 (Profibus DP) . . . . . . . . . . . . . . . . . . .

J-59

10 Multi-channel I/O amplifier module ML78B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

J-60

11 System devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

J-63

K Index

MGCplus with AB22A/AB32

14

MGCplus with AB22A/AB32

A-1

Introduction

MGCplus with AB22A/AB32

A-2

MGCplus with AB22A/AB32

Introduction Safety instructions

A-3

Safety instructions

Use in accordance with the regulations


The amplifier system is to be used exclusively for measurement tasks and directly related control tasks. Use for any
purpose other than the above shall be deemed to be not in accordance with the regulations.
To ensure safe operation, the device may only be operated in accordance with the information given in the Operating Manual. It is also essential to comply with the legal and safety requirements for the application concerned during use. The same applies to the use of accessories.
General dangers due to non-observance of the safety instructions
The amplifier system is a state-ofthe-art device and is fail-safe. The device may give rise to further dangers if it is
inappropriately installed and operated by untrained personnel.
Any person instructed to carry out installation, commissioning, maintenance or repair of the device must have read
and understood the Operating Manual and in particular the technical safety instructions.
Remaining dangers
The scope of supply and list of components provided with the amplifier system cover only part of the scope of measurement technique. In addition, equipment planners, installers and operators should plan, implement and respond
to the safety engineering considerations of measurement technique in such a way as to minimise remaining dangers. Prevailing regulations must be complied with at all times. There must be reference to the remaining dangers
connected with measurement technique.
After setting up and password protected activities, care must be taken to ensure that any control units that may be
connected remain in a safe and secure state until the switching behaviour of the amplifier system has been
checked.

MGCplus with AB22A/AB32

A-4

Introduction Safety instructions

Any risk of remaining dangers when working with the amplifier system is pointed out in this introduction by means
of the following symbols:

Symbol:

DANGER

Meaning:
Maximum danger level
Warns of a decidedly dangerous situation in which failure to comply with safety requirements will lead to death or
serious physical injury.

Symbol:

WARNING

Meaning:
Dangerous situation
Warns of a potentially dangerous situation in which failure to comply with safety requirements can lead to death or
serious physical injury.

Symbol:

CAUTION

Meaning:
Possibly dangerous situation
Warns of a possibly dangerous situation in which failure to comply with safety requirements could cause damage
to property or result in some kind of minor physical injury.

MGCplus with AB22A/AB32

A-5

Introduction Safety instructions

Symbols indicating application notes and useful information:

Symbol:

NOTE

Means that important information about the product or its handling is being given.

Symbol:
Meaning: CE mark
The CE mark enables the manufacturer to guarantee that the product complies with the requirements of the relevant EC directives (the declaration of conformity is available at http://www.hbm.com/support/dokumentation).

Symbol:
Meaning: Component may be damaged by electrostatic discharge
This means that the PCMCIA hard disk (optional) must be protected against static discharges by securing it in
place with the fasteners provided (CP42 only).

MGCplus with AB22A/AB32

A-6

Introduction Safety instructions

Working safely
Error messages must only be acknowledged when the cause of the error has been removed and no further danger
exists.
Conversions and modifications
The amplifier system must not be modified from the design or safety engineering point of view except with our express agreement. Any modification shall exclude all liability on our part for any resulting damage.
In particular, any repair or soldering work on motherboards is prohibited (this includes changing components other
than EPROMs). When exchanging complete modules, use only original parts from HBM.
Qualified personnel
means persons entrusted with the installation, assembly, commissioning and operation of the product who possess
the appropriate qualifications for their function.
This instrument must only to be installed and used by qualified personnel, strictly in accordance with the technical
data and the safety requirements and regulations listed below. It is also essential to comply with the legal and
safety requirements for the application concerned during use. The same applies to the use of accessories.

MGCplus with AB22A/AB32

Introduction Safety instructions

A-7

Safety requirements
Before commissioning, find out whether the mains voltage and current type specified on the identification plate
match the mains voltage and current type at the place of use, and whether the circuit being used is adequately protected.
Insert the mains plug only into a socket with a protection switch (Protection Class I). When connecting electrical
devices to low voltage: connect to separated extralow voltage (SELV) only (safety transformer in accordance with
DINVDE 0551 / EN60742).
Use only the mains cable supplied, which has been provided with a ferrite core.
Before you open the device, make sure it is switched off; remove the mains plug from the socket.
Never pull the mains plug from the socket by the mains cable.
Do not operate the device, if the mains cable is damaged.
If an amplifier channel is to be withdrawn, close off the plug-in unit with a blank plate.
Built-in devices must only ever be operated whilst they are within the housing provided for them.
The device complies with the safety requirements of DIN EN 61010-Part 1 (VDE 0411-Part 1); Protection Class I.
To ensure adequate immunity from interference, use only Greenline shielded ducting (see HBM offprint Greenline
shielding design, EMC-compliant measuring cable; G36.35.0)
The port connections (50V) must have an insulating strength of at least 350V(AC).

MGCplus with AB22A/AB32

A-8

Introduction Notes on the documentation

Notes on the documentation

The total documentation for the MGCplus amplifier system covers the following publications:
The Operating Manual
explains how you can operate the device manually and use it to take measurements.
With each system device delivered, CD-ROMs containing the following documentation are also supplied:
Operation with computer or terminal
contains the commands for programming and measuring with a computer or terminal
MGCplus Assistant,
documentation about the program for assigning parameters and driving the MGCplus measurement amplifier
system.
Catman Demo,
which is a demo version of the data acquisition, display and analysis software from HBM.

MGCplus with AB22A/AB32

A-9

Introduction Notes on the documentation

This manual contains all the information you need to operate the MGCplus.
There are several guidelines available to you:

The column header tells you which chapter or sub-section you are currently reading.

Example:
Connections SG full bridges, induct. half bridges

B-15

The page numbering is linked to capital letters which correspond to the chapter headings.

Chapter D Functions and symbols on the AB22A/AB32 contains explanations about the AB22A/AB32 display
and control panel. All statements about the display and control panel refer to both variants (AB22A/AB32). For
reasons of space, however, most of the illustrations only show the AB22A.

Chapter I Menu structure gives you an overview of the selection and set-up menus on the display and control
panel.

MGCplus with AB22A/AB32

A-10

Introduction System description

System description

The MGCplus system is modular in construction. Depending on the enclosure variant concerned, up to 16 slots are
available for one-channel and multi-channel amplifier plug-in modules. This means that up to 128 measuring points
can be measured in one MGCplus.
Each amplifier plug-in module operates in standalone mode through the internal CPU. Data conditioning, such as
taring, filtering and measuring range adjustment, is carried out in digital form. The disadvantages of analogue conditioning, such as time and temperature related drift, errors due to component tolerances, limited flexibility and high
circuit complexity, can no longer arise. The prerequisite for this, however, is analogue-digital conversion free of information loss. The digitally conditioned signal is fed to the internal high-speed bus.
In the case of one-channel measurement modules, two analogue outputs (voltage or current) are available in addition to the digital measured values.
A credit-card format standard internal PC collects the data with a total sampling rate of up to 300 000 values per
second. All measurement signals can be captured in parallel, since each channel has its own A/D converter. No
Sample & Hold or multiplexer is used in the MGCplus. This ensures continuous digital filtering and highest possible
signal stability.
Using interfaces like Ethernet or USB, data is sent to an external computer or PLC.

MGCplus with AB22A/AB32

A-11

Further MGCplus

PC-Interface

PC-Card (optional)

Profibus

CAN

10V

...
1

Digit remote contacts, limit


switches

Introduction System description

2400Hz

Digital
signal conditioning
filtering, scaling, zero
balancing, etc.

Digital
signal
conditioning

...

...

filtering
scaling, zero
balancing,
etc.

CPU
8-channel
module

CPU

...

CPU

Display
and

Communikation
processor CPxx

control
panel

Synchronisation

2400Hz

2400Hz

...

CPU
Onechannel
module

Serial bus

MGCplus

Fig.3.1:

MGCplus block diagram

MGCplus with AB22A/AB32

Fig.3.2:

ON/Off

MGCplus with AB22A/AB32

MGCsplit block diagram


Embedded
PC with
memory

Multi-channel module

Bus communication

Display

PC Card

Communication

Power pack

On-board network
9V ... 58V

Digital signal
conditioning
Filtering
Scaling
Zero balance

Single-channel module
Dig. sign.
Filter.
Scal.
Zero
ML70B

Programmable module
10V
Digital I/O
CAN
RS 232 C/RS 485

10V
Remote contacts
Limit value switches

Ethernet
USB
RS 232 C

Hard disk

A-12
Introduction System description

A-13

Introduction MGCplus housing versions

MGCplus housing versions

The MGCplus system is supplied in various housing versions (dimensions in mm).

Desktop housing TG 009C (173x171x367)

Desktop housing TG 001C/002C (255x171x367)

Rack frame 19 ER 003C/004C (482x133x375)

Desktop housing TG 010B/003C/004C (458x171x367)

Desktop housing

Rack frame

Slots

Supply voltage
(V)

Weight, approx. (kg)


TG/ER

TG001C

230 (115)

TG010C

6 (with AB32)

230 (115)

TG002C

12/24 =

TG003C

ER003C

16

230 (115)

7/6

TG004C

ER004C

16

12/24 =

7.5/6

TG009C

230 (115)

MGCplus with AB22A/AB32

A-14

Introduction MGCplus housing versions

All basic versions of the device consist of the following components:


Display and control panel AB22A /AB32, AB12 (without link feature)
Amplifier plug-in modules (ML10B, ML30B, ML50B, ML55B, etc.)
Housing
Connection boards (AP01i, AP02, etc.)
Power pack
Options:
Final stage module (EM001)
Relay module (RM001)
CP22 (communications processor with Ethernet-on-board and USB-Interfaces)
CP42 (communications processor with data storage option)

MGCplus with AB22A/AB32

A-15

Introduction MGCplus device

Structure of the MGCplus device

Connection boards
(AP01i, AP02, etc.)

Final stage
modules
Power
pack

CPxx
Communications
processor

AB22A
display and
control panel
Amplifier plug-in modules
(ML30B, ML50B etc.)

Fig.5.1:

Device structure with display and control panel AB22A

MGCplus with AB22A/AB32

A-16

Introduction MGCplus device

Connection board
(AP01i to AP18i)

Final stage
modules
Power
pack

CPxx
Communications
processor

AB32 display and control panel

Amplifier plug-in modules


(ML30B, ML50B etc.)

Fig.5.2:

Device structure with display and control panel AB32

MGCplus with AB22A/AB32

A-17

Introduction MGCplus structure

Insert communications processor CP22/CP42

Requirements for operation of the communications processor:


The MGC/MGCplus system must not include any AB12 display and control panel.
The MGC/MGCplus/MGCsplit system must not include any modules of type MCxx. Only modules of type
MLxxB (with ML firmware or MC firmware) and MLxx (only with ML firmware) are permissible.
The display and control panels (AB22A, ABX22A, AB32) operated with the CP22 in the system unit must use
firmware P4.01 or higher. Any firmware upload has to be performed before installing the communication
processor.

MGCplus with AB22A/AB32

A-18

Introduction MGCplus structure

If you want to swap out an older type of communications processor for a CP22/CP42 communication processor,
you have to remove two guide rails from the MGCplus housing.

Upper

Lower

guide rail

guide rail

Fig.6: Guide rails in the MGCplus housing

1.

Disconnect the MGCplus device from the mains power supply.

2.

Remove the upper and lower covers from the housing.

3.

Withdraw the existing communications processor from the housing.

4.

CP12 only: Remove the BL01 blank plate next to the power pack (see page A-19).

5.

Remove the upper and lower guide rails.

6.

Slide the new communications processor into the housing.

7.

Put the upper and lower covers back onto the housing.

MGCplus with AB22A/AB32

A-19

Introduction MGCplus structure

CAUTION
Before swapping a CP12 communication processor for a CP22/CP42 you should also remove the blank
plate next to the power pack, in order to prevent damage to any PCB components when sliding the
processor into the housing.

Blank plate BL01

Power
pack

CP 12

AB22A
display and
control panel

Fig.6.1:

Removing the BL01 blank plate (view from above)

MGCplus with AB22A/AB32

A-20

Introduction MGCsplit

Modules in the MGCsplit system

The MGCsplit system is based on the components of the MGCplus measurement system and housed in robust
enclosures (protection class IP 40 or IP 65). The system makes it possible to build up a decentralized
measurement system from individual modules. Each enclosure has room for an amplifier module and a maximum
of two connector plates. The following module types are available, depending on the particular function required:
D

Measurement modules with one MLxx amplifier module and max. two connector plates

Processor modules with one communication processor

D Power pack module with power pack and CAN input


The modules are networked together using split-line connection cable and optionally may also be networked with
the MGCplus system via the AP20 connector plate.

Fig.7.1:

MGCsplit measuring amplifier system

Note
When the line length exceeds 10m or the total number of modules exceeds 8, we recommend the use of a
Link terminating resistor (1MGCsplit Term) for linking the MGCsplit modules.
MGCplus with AB22A /AB32

A-21

Introduction MGCsplit

7.1

Measurement module, enclosure 1SH400

This module has an enclosure which is open at the front and in which a conventional MGCplus MLxx amplifier
module and a maximum of two connector plates can be fitted. If you use one connector plate only, this must be
positioned in the outermost slot on the right and the empty slot must be closed off with a blank plate.

Three communications LEDs


Four module address LEDs
Split-line in
Split-line out

Amplifier module, e.g. ML801B


Connector plate 2, e.g. AP409
Subchannels 5 to 8
Connector plate 1, e.g. AP409
Subchannels 1 to 4
Fig.7.2:

Version IP40, typical configuration

MGCplus with AB22A /AB32

A-22

7.2

Introduction MGCsplit

Measurement module, enclosure 1SH650

This module is closed by a shared front panel. The MLxx amplifier module and a maximum of two connector plates
are fitted securely in the enclosure. The protection class IP65 enclosure is designed for outside use. The amplifier
module or connector plates can only be changed in the factory.

Three communications LEDs


Four module address LEDs
Split-line in
Split-line out

Amplifier, e.g. ML801B


Connection sockets (ODU)
Channels 5 to 8
Connection sockets (ODU)
Channels 1 to 4

Fig.7.3:

Version IP65, typical configuration

MGCplus with AB22A /AB32

A-23

Introduction MGCsplit

7.3

Processor modules 1SH400CP

The CP22 and CP42 communication processors in the 1SH400 enclosure handle the communication between
modules. They have the usual PC interfaces (RS232, USB, Ethernet) and ensure rapid synchronization with other
MGCplus systems. The CP42 communication processor can also accept a PC card which enables data to be
recorded without a PC.

NOTE
The CP22 communication processor has to be mounted rightaligned and the middle (free) slot has to be
covered by a dummy plate.

Interfaces

Three communications LEDs


Connection for indicator
PC card
Split-line in
Split-line out

Fig.7.4:

Synchronization

Enclosure 1SH400 with CP42 communication processor

MGCplus with AB22A /AB32

A-24

7.4

Introduction MGCsplit

LED display for modules

Rx/Tx
For monitoring the communication bus.
Green = OK
Off = communication signal fault
SYNC
For monitoring the synchronization signal.
Green = signal present
Off = no signal present
LINK
For monitoring the measurement data bus.
Green = OK
Off = link signal fault
If the measurement system consists of more than four modules, the LINK LED is darker due
to the increased data load from all the modules. If a link signal fault is suspected, the
modules should be tested individually.
ERROR
If a measurement module is removed while the system is operating, the series-connected
module detects this and its ERROR LED flashes red at approx. 1 Hz.
Once the system is restarted the error status is reset.

MGCplus with AB22A /AB32

A-25

Introduction MGCsplit

Display for other error situations (measurement modules only):


LED display

Error

Error + address LED1

Restart error

Error + address LED2

No address received

Error + address LED4

Faulty address signal

Error + address LED8

More than 16 channels present

Restart errors can occur if the supply voltage is quickly turned off and on again.
After switching off the supply voltage it is best to wait about 2 seconds before turning it on
again.
No address received is displayed if the cabling is faulty, e.g. if line in (IN) and line out
(OUT) have become switched.
To remedy this, reconnect the cabling correctly and restart the system.
When more than 16 measurement modules are connected, the measurement module
displays at address 16 the error More than 16 channels present and the following modules
show No address received. These measurement modules are ignored by the
communication processor.

MGCplus with AB22A /AB32

A-26

Introduction MGCsplit

ADDRESS (measurement modules only)


Module address, binary display (address 16 = all LEDs off).

NOTE
The address is displayed in error-free measuring mode only. In the event of an
error the address LEDs have a different meaning (see ERROR).
Address
LED

10

11

12

13

14

15

16

1
2
4
8

= LED on
= LED off
The module addresses result from the cabling of the measurement system. The
measurement module which has its split-line input (IN) connected to the split-line output
(OUT) on the processor module receives address 1. The next module, which is connected to
the output (OUT) of module 1, receives address 2, and so on. This gives continuous address
numbering without gaps.
In the event that MGCsplit modules are incorporated into an MGCplus system via the AP20
connector plate, the first MGCsplit measurement module receives the address of the AP20
slot (e.g. with an AP20 in slots 3 and 4, the measurement module receives address 3).

MGCplus with AB22A /AB32

A-27

Introduction MGCsplit

7.5

Connecting to MGCplus systems

Split-line connecting cable can also be used to connect the 1SH400 and 1SH650 measurement modules to
MGCplus systems. An AP20 connector plate is needed for this. A processor module is not necessary, since
communication is carried out by the processor on the MGCplus system.

MGCplus system

Connector plate

Connecting cable

AP20

1Kab265

MGCsplit system

1Kab2643

Fig.7.5:

MGCsplit measurement module connected to an MGCplus system

MGCplus system requirements:


D

CP22 or CP42 communication processor.

Hardware version 1.31 (or higher) of the MGCplus measuring amplifier (older MLxx amplifiers can be retrofitted
in the factory at Darmstadt).

MGCplus with AB22A /AB32

A-28

Introduction MGCsplit

Installing an AP20 connector plate


The AP20 connector plate is installed in the MGCplus instrument directly alongside the existing connector plates.
The remaining slots (to the right of the AP20 in Fig.7.6) must be kept free. The unoccupied channels in the
MGCplus (up to channel 16) are available to the MGCsplit system.
In the case of amplifier modules that do not need connector plates (e.g. the ML77B), the backing connector plate
slot must be kept free just the same (see Fig.7.7).

MGCsplit

Addresses 1 to 4

Address 5

Address 6

AP20

MGCsplit

APxx
APxx
APxx
APxx

MGCplus

CP22/
CP42

IN

IN
OUT

Not in use

MLxx
MLxx
MLxx
MLxx

AB22A
display and
control panel

Fig.7.6:

MGCsplit measurement module connected to an MGCplus system via an AP20 connector plate (top view)

MGCplus with AB22A /AB32

A-29

Introduction MGCsplit

MGCsplit

MGCsplit

Address 5

Address 6

CP22/

Not in use

APxx
APxx
APxx

AP20

MGCplus
Addresses 1 to 4

CP42

IN

IN
OUT

Not in use

MLxx
MLxx
MLxx
ML77B

AB22A
display and
control panel

Fig.7.7:

AP20 next to an amplifier module without a connector plate (top view)

MGCplus with AB22A /AB32

A-30

Introduction MGCsplit

Is the last MGCplus module (MLxx or APxx) is double-width (e.g. ML38B, AP03i, etc.), then a complete slot must
be kept free ahead of the AP20 connector plate (see Fig.7.8 and Fig.7.9).

MGCsplit

MGCsplit

Addresses 1 to 4

Address 6

Address 7

Not in use

APxx
APxx
APxx
APxx

AP20

MGCplus

CP22/
CP42

Not in use

Fig.7.8:

ML38B

MLxx
MLxx
MLxx

AB22A
display and
control panel

Special case of an ML38B with an AP20 connector plate

MGCplus with AB22A /AB32

IN

OUT

IN

A-31

Introduction MGCsplit

MGCsplit
Address 8

AP20

AP03i

MGCsplit
Address 7

APxx
APxx
APxx

MGCplus
Addresses 1 to 4

CP22/
CP42

Not in use

Not in use

OUT

IN

MLxx
MLxx
MLxx
MLxx

AB22A
display and
control panel

IN

Fig.7.9:

Special case of a double-width connector plate next to an AP20 connector plate

MGCplus with AB22A /AB32

A-32

7.6

Introduction MGCsplit

Enclosure dimensions

Mechanical linkage of the module enclosure


205.5
202.42
204.4

149.4

Raster 101.5

MGCplus with AB22A /AB32

Introduction MGCsplit

A-33

Dimensions in the case of lateral mounting

MGCplus with AB22A /AB32

A-34

Dimensions in the case of rear mounting

MGCplus with AB22A /AB32

Introduction MGCsplit

Introduction Conditions on site

A-35

Conditions on site

CAUTION
D
D
D
D
D

D
D

Protect desktop devices from moisture or atmospheric influences such as rain, snow etc.
Ensure that the ventilation openings on the sides, the openings for the electric fan on the back of the
device and the openings on the underside of the device are not covered up.
Protect the device from direct sunlight.
Comply with the maximum permitted ambient temperature specified for the system device in the technical data (chapter J).
When installed in 19 fitted cupboards, due to the poor heat dissipation suitable steps must be taken to
ensure that the maximum permissible ambient temperature is not exceeded (see page J-63). In all cases
we recommend forced exhaust ventilation and in particularly critical cases, clearances above and below the rack frame.
Permissible relative humidity at 31 5C is 80 % (non-condensing), reducing linearly to 50 % at 40 5C.
The devices are classed as overvoltage category II, pollution grade 2 equipment.

MGCplus with AB22A /AB32

A-36

Introduction Maintenance and cleaning

Maintenance and cleaning

MGCplus system devices are maintenance free. Please note the following points when cleaning the housing:

CAUTION
Withdraw the mains plug from the socket before carrying out any cleaning.
D
D

Clean the housing with a soft, slightly damp (not wet!) cloth. You should on no account use solvent, since it
may damage the labelling on the front panel and the display field.
When cleaning, ensure that no liquid gets into the device or connections.

MGCplus with AB22A /AB32

B-1

Connecting

MGCplus with AB22A/AB32

B-2

MGCplus with AB22A/AB32

B-3

Connecting Mains and battery operation: desktop housing

Connection: desktop housing

1.1

Mains connection

The NT010 power pack is designed for connection to 230 V (115 V) and
for the maximum configuration of 16 channels. It adapts automatically
to the 115 V/230 V mains supply voltage. The fan on the power pack is
temperature-controlled and automatically cuts out if necessary.
Chassis ground

The power pack is protected with an internal 3.15 A/ T micro-fuse.

CAUTION
The power pack fuse may be changed only by the manufacturers
service personnel.
Earthing switch
The earthing switch, in the factory setting (
), links zero operating
voltage to the protection circuit. If external devices (e.g. transducers,
computers) already make this link, and this causes ground circuits to
occur (hum-pickup), the earthing switch must be opened ( ).

Mains connection
Earthing switch

MGCplus with AB22A/AB32

B-4

Connecting Mains and battery operation: desktop housing

1.2

Battery connection

Chassis ground

The NT011 power pack is designed for mainsindependent battery


operation for a maximum of 16 channels. It adapts automatically to a
12 V/24 V DC supply voltage. The fan on the power pack is
temperature-controlled and automatically cuts out if necessary.

Connections

Earthing switch

Supply voltage (+)


12 V/24 V DC
()

To protect against electromagnetic interference, you must wrap the


connection cable round the ferrite ring supplied (3 turns). Position the
ferrite ring as close to the power pack as possible and make sure that
the coils are parallel and close together.

Ferrite ring
Connection cable

Connect the device to the battery via the screw terminals on the back of
the device.
Fuse

CAUTION
Be sure to make all connections with the correct polarity.
Use cable with a wire cross section of 2.5 mm2 to 4 mm2.

MGCplus with AB22A/AB32

Connecting Mains and battery operation: desktop housing

B-5

Fuse
Flat-pin fuse 25A F (Colour code colourless). The fuse also acts as a one-way fitting.
Changing the fuse

CAUTION
Disconnect the device from the battery before changing the fuse.
Voltage drop
If the battery voltage drops below 8.5 V (for instance battery low, connection cable too long), the MGCplus is in reset status and is not ready to take measurements (display and LEDs light up). If the voltage returns to more than
10.8 V you may take measurements again. If the battery voltage drops below 7.5 V, the MGCplus switches off (display and LEDs dark) and is only ready for service again if battery voltage returns to 10.8 V.
Earthing switch
), links zero operating voltage to the protection circuit. If external deThe earthing switch, in the factory setting (
vices (e.g. transducers, computers) already make this link, and this causes ground circuits to occur (hum-pickup),
the earthing switch must be opened ( ).

MGCplus with AB22A/AB32

B-6

Connecting Mains and battery operation: desktop housing

1.3

Synchronization

Synchronizing a CP22/CP42
Connected devices are automatically detected and synchronized by
dedicated SYNC sockets. The status (master/slave) is displayed by
means of a colorcoded LED.

CP42
RS 232
CARDBUS

USB DEVICE

USB HOST

LED
ETHERNET

YE SLAVE
RD ERROR
GN MASTER

IN
SYNC
CTRL I/O
OUT
24V 1 2 GND 1 2
OUT
IN

Synchronization sockets CP42

MGCplus with AB22A/AB32

LED

Status

Green

Master

Yellow

Synchronized slave

Red

Unsynchronized slave

Connecting Mains and battery operation: desktop housing

B-7

CP22
RS 232
CTRL I/O
IN
OUT
24Vext
GNDext

USB SLAVE
SYNCRON.
IN

LED

USB MASTER
YE SLAVE
RD
ERROR
GN MASTER

ETHERNET

OUT
SYNCRON.

Synchronization sockets CP22

MGCplus with AB22A/AB32

B-8

Connecting ABX22A

Connecting the ABX22A

Blank plate BL12A

Connect the male connector for the mobile ABX22A display and control
unit to the female connector on blank plate BL12A.
Field upgrade:
If you wish to replace an existing AB22A with a mobile ABX22A as
an upgrade, please take note of the following points:

Male connector for the ABX22A:


3-3312.0121, 8-pin,
Series 423 9956711508
Cable extension female connector:
3-3312.0120, 8-pin,
Series 432 9956721508

MGCplus with AB22A/AB32

Replace the AB22A with a blank plate BL12A.


Unscrew the cover from the housing
Check the position of the sliding switch and change it if necessary
(see figure below).

B-9

Connecting ABX22A

Plan de positionnement des


commutateurs dinterface
(botier ouvert, vue de dessus) :

Switch position
seen from above

Display and control


unit

position 1

Botier

S3 Commutateur CP
S2
S1

Commutateur
dinterfaces

TTL

S2

AB22A

Cble nappe

position 1

Bloc dalimentation secteur

RS485

position 2
ABX22A
position 2

S1

S2
X

S1

NOTE
If a CP... Communication Processor was subsequently installed,
the S3 CPswitch must be changed over!
Without CP...
seen from above

With CP...
seen from above

CP

CP
yes

S3
no

S3

yes
no

MGCplus with AB22A/AB32

B-10

Connecting ABX22A

NOTE
LOG OFF EXTERNAL DISPLAY

Log off

Cancel

When operating devices without a communications processor


but with an ML77B Profibus module, you must log off the
ABX22A before removing the connector cable.
1. Use the shift key
2. Press function key

to return to set-up mode.


.

3. Select Log off from the pull-up menu and confirm


with

4. Select the Log off button and confirm with

5. When the message Now you can disconnect the ABX22A! is


displayed, you can remove the connector cable.

MGCplus with AB22A/AB32

B-11

Connecting Shielding design

Shielding design

Until now:
gr

12
1*

* Pin assignment varies according to


the connection board (see table)

So far, the customary HBM shielding connection has used a male


connector to connect the shield.
This solution provides only limited EMC protection and should no longer
be used.
Earth pin

GREENLINE

AP01i/13i/14/17

AP03i

AP07/1

YE

New Greenline shielding design:


wh
bk
rd

HBM has developed the Greenline shielding design as an effective


means of improving EMC protection against electromagnetic
interference. The cable shielding is formed in such a way that the whole
of the measurement chain is completely enclosed in a Faraday cage.

bl
gn
gr

NOTE

ye

In the case of connection boards fitted with a terminal connector


(AP07/1), connect the cable shielding to the eyelet on the connection board.

MGCplus with AB22A/AB32

Connecting Transducers

B-12

Connecting transducers

Excitation voltage (+)

When using double-width connection boards (AP03i) only slots 1, 3, 5,


7, 9 and 11i can be occupied by an amplifier. This also applies when
using an AP01i connection board in conjunction with an AP02.

Measurement signal ()

IMPORTANT:

Measurement signal (+)


Excitation voltage ()
2

Transducer with four-wire connection

Cable shielding 1)
3

Sensor circuit (+)

Feedback
bridges

Sensor circuit ()

If you are connecting a transducer with 4-wire cable, you must connect
the sensor circuit to the appropriate bridge excitation circuit in the
transducer male connector (sensor circuit () to excitation voltage ()
and sensor circuit (+) to excitation voltage (+))*). Any cable extension
must only ever be carried out in six-wire connection.
*)

MGCplus with AB22A/AB32

For cable lengths >50 m, one resistor with half the bridge resistance value (BR/2)
must be wired into the transducer in place of each feedback bridge. If the
transducers are calibrated in six-wire connection, the resistors must be wired directly
into the sensor circuit.

Connecting Transducers

4.1

Amplifier:

B-13

Connecting separate TEDS modules

All MLxxB and ML460

AP01i
AP13i
AP455i
1

15

(+)
Operating voltage zero

()

15

Cable shielding

Geh.

TEDS
TEDS Data

4
9

Wire colors: WH= white; BK= black; BL= blue; RD= red; YE= yellow; GN= green; GR= grey

MGCplus with AB22A/AB32

Connecting Transducers

B-14

4.2

Strain gage full bridges, inductive full bridges

Amplifier:

Amplifier:

SG full bridge
ML30B, ML55B,
ML10B3), ML38B4)
Ind. full bridges
ML50B, ML55B

AP01i
AP13i
AP14
AP455i
1

15

AP03i

WH
BK
2

BL
RD

4
3

YE
GN
GR

Measurement
signal (+)
Excitation
voltage ()
Excitation
voltage (+)
Measurement
signal ()
Cable shielding 1)

E
D

1
2
3

5
4

15
Case

Case

Case

Sensor circuit (+)

13

Sensor circuit ()

12

1)

see page B-11

2)

SG full bridges only

3)

Full bridge and Lo must be


set up under bridge type
only use ML38B in connection
with AP01i and AP03i

4)

AP11i
AP455iS6

MGCplus with AB22A/AB32

Wire colors: WH= white; BK= black; BL= blue; RD= red; YE= yellow; GN= green; GR= grey

Connecting Transducers

4.3

B-15

SG full bridges with AP810/AP815i

Amplifier:

ML801B

AP810/AP815i
Sub-channel Sub-channel
1

14

Sub-channel

Sub-channel

1/5

2/6

3/7

4/8

11

Sub-channel 1...4

13

2
1

Measurement
signal (+)

BK

Excitation
voltage ()
Excitation
voltage (+)
Measurement
signal ()

BL

14

RD
1

Sub-channel 5...8
13

WH
25

25

4
3

YE
GN
GR

Cable shielding 1)

10

12

15

18

21

24

Case

Case

Case

Case

Sensor circuit (+)

16

19

22

25

Sensor circuit ()

14

17

20

23

1)

see also page B-11

Wire colours: WH= white; BK= black; BL= blue; RD= red; YE= yellow; GN= green; GR= grey

MGCplus with AB22A/AB32

Connecting Transducers

B-16

4.4

Strain gage half bridges, inductive half bridges

Amplifier:

SG half bridges
ML30B2), ML55B,
ML10B3)

Amplifier:

Ind. half bridges


ML50B, ML51,
ML55B

WH
BK
2

BL

YE
3

GN
GR

1)
2)
3)

AP01i
AP13i
AP14
AP455i
1

15

AP03i

Measurement signal (+)

E
D

AP11i
AP455iS6

1
2
3

5
4

Excitation voltage ()

Excitation voltage (+)

Cable shielding 1)

Case

Case

Case

Sensor circuit (+)

13

Sensor circuit ()

12

see page B-11


only in conjunction with AP14
Half bridge and Lo must be
set up under bridge type

MGCplus with AB22A/AB32

Wire colours: WH= white; BK= black; BL= blue; RD= red; YE= yellow; GN= green; GR= gray

Connecting Transducers

4.5

B-17

LVDT-Transducer

Amplifier: ML455
AP455i

AP455iS6

1
2
3

5
4

LVDT-Transducer
Measurement signal (+)

Excitation voltage ()

Excitation voltage (+)

Measurement signal ()

15

Cable shield 1)

case

Sensor circuit (+)

13

Sensor circuit ()

1
2
3

Case

12

5
6

MGCplus with AB22A/AB32

Connecting Transducers

B-18

4.6

SG half bridges with AP810/AP815i

Amplifier:

ML801B

AP810/AP815i

Subchannel Subchannel
14

1/5

2/6

Subchannel Subchannel
3/7

4/8

Subchannel
1...4
13

25
2

14

Subchannel 4

14

25

20

23

10

11

Case

Case

Case

18

21

24

12

22

25

Sensor circuit ()

WH/RD

Excitation voltage ()

WH/GN

Measuring signal (+)


Cable shielding

Case

GN

Measuring signal (); AP815ii only

15

WH/BR

Excitation voltage (+)

BN

Sensor circuit (+)

5...8
13

17

RD

16

1)

19

see page B-11

Wire colours: WH= white; BL= black; BL= blue; RD= red; YE= yellow; GN= green; GR= grey; BN= brown

MGCplus with AB22A/AB32

Connecting Transducers

B-19

4.7

Connecting a single strain gage

4.7.1

Compensating resistor external

Amplifier: ML55B, ML10B

AP01i
AP13i
AP455i
1

15

AP03i

WH
BK
2

BL

E
D

YE

GN
GR

1)

1
2
3

5
4

Measurement signal (+)

Excitation voltage ()

Excitation voltage (+)

AP11i

Cable shielding 1)

Case

Case

Case

Sensor circuit (+)

13

Sensor circuit ()

12

see page B-11

R - compensating resistor
Wire colors: WH= white; BK= black; BL= blue; RD= red; YE= yellow; GN= green; GR= grey

MGCplus with AB22A/AB32

Connecting Transducers

B-20

4.7.2

Compensating resistor external with AP815i

Amplifier:

ML801B

AP810/AP815i

Subchannel Subchannel
14

1/5

2/6

Subchannel Subchannel
3/7

4/8

Subchannel
1...4
13

25
2

14

Subchannel 4

14

25

20

23

10

11

Case

Case

Case

18

21

24

12

22

25

Sensor circuit ()

WH/RD

Excitation voltage ()

WH/GN

Measuring signal (+)


Cable shielding

Case

GN

Measuring signal (); AP815ii only

15

WH/BR

Excitation voltage (+)

BN

Sensor circuit (+)

5...8
13

17

RD

16

1)

19

see page B-11

Wire colours: WH= white; BL= black; BL= blue; RD= red; YE= yellow; GN= green; GR= grey; BN= brown

MGCplus with AB22A/AB32

Connecting Transducers

4.7.3

B-21

Single strain gage with AP14

Amplifier: ML30B, ML55B,


ML10B

AP14

Sensor circuit ()
Excitation voltage ()

SG

15

12
5

SG
Case

Excitation voltage (+)


Sensor circuit (+)

15
8

Three-wire connection* Four-wire connection*


*

Must be set up under bridge type

MGCplus with AB22A/AB32

Connecting Transducers

B-22

4.7.4

Single strain gage with AP814Bi

Amplifier:

ML801B

AP814Bi

Sub-channels

14

5
2

15

18

5
8

21

11

24

Case

Sub-channel 1...8

13

25

Excitation
voltage ()

SG
Cable shielding 1)

Case

Case

Case

Case

Case

Case

Case

Excitation
voltage (+)

15
14

16

17

19

15
20

22

23

25

8
1

8
7

10

12

Sensor circuit (+)

Three-wire connection

1)

see also page B-11

Wire colors: WH= white; BK= black; BL= blue; RD= red; YE= yellow; GN= green; GR= grey

MGCplus with AB22A/AB32

Connecting Transducers

4.7.5

B-23

Single strain gage with AP815i

Amplifier:

ML801B

AP815i
Subchannel
1

14

1/5

Subchannel Subchannel Subchannel


2/6

3/7

4/8

Subchannel
1...4
13

25

2
1

WH/RD
RD

Sensor circuit ()

10

14

17

20

23

Case

Case

11

21

24

14

S.G.
5...8

Case

Cable shield

Subchannel

13

Excitation voltage ()

WH/GN

Measuring signal (+)

GN

Excitation voltage (+)

15

25

1)

Case

5
18

see page B-11

Wire colors: WH= white; BK= black; BL= blue; RD= red; YE= yellow; GN= green; GR= grey

MGCplus with AB22A/AB32

Connecting Transducers

B-24

4.7.6

Amplifier:

SG systems and rosettes on AP815i

ML801B

sub-channel
1

AP815i
2
1

2
14

SG
sub-channel 5

SG
4/8

SG
3/7

SG
2/6

SG
1

Excitation voltage ()

Sensor circuit ()

14

Cable shielding

Case

sub-channel
2/6
sub-channel
3/7

1...4
13

25

Excitation voltage (+)

sub-channel

15

4/8

14

sub-channel
5...8
13

Measurement
signal (+)

25

sub-channel

5
18

5
8
21
11
24
2
15

You can operate a maximum of eight 120 W SGs on a 5 V feed. Make sure that sensor probe 2 on the SG system
is as close as possible to the single strain gages and that the gaps between the single strain gages are small.

MGCplus with AB22A/AB32

Connecting Transducers

B-25

If the gaps between the single strain gages cannot be kept small (for example two 90 rosettes at different places),
they should be connected as follows:

Amplifier:

ML801B

sub-channel
1

AP815i

2
2

SG
2

14

SG
1

sub-channel
1...4
13

Excitation voltage ()
Sensor circuit ()

14

Cable shielding

Case

Measurement
signal (+)

Excitation voltage (+)

25

sub-channel
2

2
15
5
18

14

sub-channel
5

sub-channel
5...8
13

25

SG
4

SG
3

Excitation voltage ()

Sensor circuit ()

14

Cable shielding

Geh.

Measurement
signal (+)

Excitation voltage (+)

sub-channel
6

2
15
5
18

MGCplus with AB22A/AB32

Connecting Transducers

B-26

4.8

Torque flange T10FSF1, T10FSU2

4.8.1

Torque measurement

Amplifier:

ML60B

Male
connector 1
Md

AP17

BK
BL

RD
4
1

WH

GR

1)

15

Supply voltage (18V ... 30V)

Measurement signal torque, frequency output (+)

12

Measurement signal torque, frequency output ()

13

Cable shielding
GN

Supply voltage (0V)

YE
7/56

1)

Case

Calibration signal trigger (approx. 5V)

14

Ground

see page B-11


Connection cable KT10F Option 5, Code V5, V6, W1, W2.

Wire colors: WH= white; BK= black; BL= blue; RD= red; YE= yellow; GN= green; GR= grey

For connection of version T10FKF1 see chapter 4.9

MGCplus with AB22A/AB32

Connecting Transducers

Amplifier:

B-27

ML460

AP460i
7

5
9 10
4

1
2

Male
connector1
Md
2

RD
4
1

WH
YE

7/5 6

Measurement signal torque, frequency output (+)


Measurement signal torque, frequency output ()

1
2

Cable shielding 1)

Case

Ground

10

GN
GR

1)

see page B-11

Wire colors: WH= white; BK= black; BL= blue; RD= red; YE= yellow; GN= green; GR= grey

For connection of version T10FKF1 see chapter 4.9

MGCplus with AB22A/AB32

Connecting Transducers

B-28

AP460i Pin assignment

LEMO) connector female

Pin

(Top view)

Frequency signal 1, Input a

Frequency signal 1, Input b

Frequency signal 2, Input a

Frequency signal 2, Input b

Zero index, Input a

Zero index, Input b

Transducer supply (0 V, 5 V, 8 V or 16 V, depending on jumper position, see


page B-40)

Transducer identification (Dallas protocol)

Supply mass

10

Signal mass

10

1
2

Function

Connection:
Symmetrical input signal (RS 422):

Input a / Input b

Asymmetrical input signal, bipolar:

Input a (Signal mass at Input b)

Asymmetrical input signal, unipolar:

Input a (Signal mass at Pin 10, Input b must stay open)

MGCplus with AB22A/AB32

Connecting Transducers

4.8.2

Amplifier:

B-29

Rotation speed measurement


(symmetrical signals)

ML60B

Male
connector 2
n

AP17

WH
6
7

GN

15

Measurement signal, rotation speed 0 (+)

12

Measurement signal, rotation speed 0 ()

13

Measurement signal, rotation speed 90 ()

14

Cable shielding

GR

1)

Ground

BK
and
BL
RD

1)

Measurement signal, rotation speed 90 (+)

Case

15

see page B-11


Connection cable KT10F Option 5, Code W1, W2.

Wire colors: WH= white; BK= black; BL= blue; RD= red; YE= yellow; GN= green; GR= grey

For connection of version T10FKF1 see chapter 4.9.

MGCplus with AB22A/AB32

Connecting Transducers

B-30

Amplifier:

ML460i
AP460i
7

5
9 10
4

1
2

Male
connector 2
n

YE
RD

WH
6
7

GN

GR

10
1

Measurement signal, rotation speed, 0 ()

Measurement signal, rotation speed, 90 ()


Cable shielding 1)

1)

Ground
Measurement signal, rotation speed, 0 (+)

Measurement signal, rotation speed, 90 (+)

4
Case

see page B-11

Wire colors: WH= white; BK= black; BL= blue; RD= red; YE= yellow; GN= green; GR= grey

MGCplus with AB22A/AB32

Connecting Transducers

4.8.3

Amplifier:

B-31

Rotation speed measurement


(symmetrical signals) with reference signal

ML60B

Male
connector 2
n

AP17

YE

WH
6
7

3 4

GN

BL
BK

GR

see page B-11

15

12

Measurement signal, rotation speed 0 ()

13

Measurement signal, rotation speed 90 ()

14

1)

Case.

Reference signal (+)

Reference signal ()

Measurement signal, rotation speed 90 (+)

5V (out)
1)

Measurement signal, rotation speed 0 (+)

Cable shielding

Ground
RD

15
11

Connection cable KT10FS option 6, Code W5, W6

Wire colors: YE= yellow; RD= red; WH= white; GN= green; BL= blue; BK= black; GR= grey

MGCplus with AB22A/AB32

Connecting Transducers

B-32

Amplifier:

ML460

AP460i
7

5
9 10
4

1
2

Male
connector 2
n

YE
RD

WH
6
7

3 4

GN

BK

GR

10
1

Measurement signal, rotation speed, 0 ()

Measurement signal, rotation speed, 90 ()


Cable shielding 1)

2
BL

1)

Ground
Measurement signal, rotation speedl, 0 (+)

4
Case

Reference signal (+)

Reference signal ()

Measurement signal, rotation speed, 90 (+)

see page B-11

Wire colors: YE= yellow; RD= red; WH= white; GN= green; BL= blue; BK= black; GR= grey

MGCplus with AB22A/AB32

Connecting Transducers

B-33

4.9

Torque transducers (T3...FN/FNA, T10FKF1)

4.9.1

Torque measurement
(square-wave excitation voltage)

Amplifier:

ML60B

AP07 /1
(MD)

B
C

E
D

with
T34FN
only

Transducer
shaft
Md

1)

GN

WH

YE

BK

PK

BL

WH

RD
YE

BN

GN

GR

GR

see page B-11

Zero operating voltage

Supply voltage preamplifier (15V)

Supply voltage preamplifier (+15V)

Measurement signal, torque,


12V (5...30V) peak, 5...15kHz
Cable shielding 1)

D
Case

Rotor square-wave excitation voltage 54V/81V

Rotor square-wave excitation voltage 0V

Connection cable Kab 139A with male MS connector

Wire colors: WH= white; BK= black; BL= blue; RD= red; YE= yellow; GN= green; GR= grey; PK= pink; BN= brown

For connection of version T10FSF1/SU2 see chapter 4.8

MGCplus with AB22A/AB32

Connecting Transducers

B-34

Amplifier:

ML460
AP460i
7

5
9 10
4

1
2
with
T34FN
only

Transducer
shaft
Md

1)

GN

WH

WH

RD
YE

Zero operating voltage

Measurement signal, torque,


12V (5...30V) peak, 5...15kHz
Cable shielding 1)

10

1
Case

see page B-11

Wire colors: WH= white; BK= black; BL= blue; RD= red; YE= yellow; GN= green; GR= grey

For connection of version T10FSF1/SU2 see chapter 4.8

MGCplus with AB22A/AB32

Connecting Transducers

4.9.2

Amplifier:

B-35

Rotation speed measurement


(asymmetrical signals)

ML60B

AP01i
AP13i

15

AP03i
AP07/1(N)

A
B
C

F
G

E
D

AP11i

1
2
3

5
4

with
T34FN
only

WH

Trans
ducer
shaft
n

BK

RD
YE

BL

1)

WH

GR

Zero operating voltage

Measurement signal, rotation speed,


25V (5...30V) peak-to-peak (90o out-ofphase for angle of rotation detection)

Cable shielding 1)

Case

Case

Case

Measurement signal, rotation speed,


25V (5 ...30V) peak-to-peak

12

15

see page B-11

Wire colors: WH= white; BK= black; BL= blue; RD= red; YE= yellow; GN= green; GR= gray

MGCplus with AB22A/AB32

Connecting Transducers

B-36

Amplifier:

ML460
AP460i
7

5
9 10
4

1
2
with
T34FN
only

Trans
ducer
shaft
n

WH

WH

BK

RD
YE

BL

1)

GR

Zero operating voltage

Measurement signal, rotation speed,


25V (5...30V) peaktopeak (90o outof-phase for angle of rotation detection)
Cable shielding 1)

Measurement signal, rotation


speed, 25V (5 ...30V) peaktopeak

10

3
Case

see page B-11

Wire colors: WH= white; BK= black; BL= blue; RD= red; YE= yellow; GN= green; GR= gray

MGCplus with AB22A/AB32

Connecting Transducers

B-37

4.10

Torque transducers (T1A, T4A/WA-S3, T5, TB1A)

4.10.1

Torque measurement
(slip ring or direct cable connection)

Amplifier:

ML30B, ML55B, ML10B

AP01i
AP13i
AP142)
AP455i
1

15

AP03i

WH
BK
2

BL
RD

YE

Measurement
signal (+)
Excitation
voltage ()
Excitation
voltage (+)
Measurement
signal ()
Cable shielding 1)

Case

Sensor circuit (+)

13

Sensor circuit ()

12

1
2
3

5
4

15

Case

Feedback bridges for


transducers in four-wire connection *

E
D

AP11i

Cas
e

5
6

1)

see page B-11


SG full bridge only
*) For transducers in six-wire connection:
see connection diagram Page B-14
2)

Wire colors: WH= white; BK= black; BL= blue; RD= red; YE= yellow; GN= green; GR= gray

MGCplus with AB22A/AB32

Connecting Transducers

B-38

4.10.2

Amplifier:

Rotation speed and angle of rotation


measurement (T4WA-S3)

ML60B

AP01i
AP13i

AP03i

9
A
B

15

BK
RD

Transducer
shaft
n

GR
YE

GN

Zero operating voltage


Supply voltage +5V
Measurement signal, rotation
speed, 25V (5...30V)
peak-to-peak 1) (90o out-of-phase
for angle of rotation detection)
Cable shield 2)
Measurement signal,
rotation speed, 25V (5
...30V) peak-to-peak

1)

for AP17 nominal voltage 5V (3...20V)

2)

see page B-11

MGCplus with AB22A/AB32

AP11i

F
G

E
D

AP17

15

1
2
3

5
4

13

11

15
Case

12

15

Case

Case

Case

12

Wire colors: WH= white; BK= black; BL= blue; RD= red; YE= yellow; GN= green; GR= gray

Connecting Transducers

Amplifier:

B-39

ML460
AP460i

10

Attention: You can connect a maximum of 3 Transducer


shafts T4WAS3 to each MGCplus device.

1
2

BK

Zero operating voltage


Jumper

RD

Transducer
shaft
n

GR
YE

GN

Supply voltage +5V 1)


Measurement signal, rotation
speed, 25V (5...30V) peaktopeak
(90o out-of-phase for angle of
rotation detection)
Cable shielding 2)

Measurement signal, rotation


speed, 25V (5 ...30V) peak to peak

1)

Change jumper on 5V, see page B-40

2)

see page B-11

9
10
7

3
Case

Wire colors: WH= white; BK= black; BL= blue; RD= red; YE= yellow; GN= green; GR= gray

MGCplus with AB22A/AB32

Jumper (Factory setting 0 V)

Connection board AP460i (Side view)

MGCplus with AB22A/AB32

Supply voltage +5 V

Supply voltage +8 V

No function (only for special versions)

No function (only for special versions)

Supply voltage +16 V

B-40
Connecting Transducers

Connecting Transducers

4.10.3

Amplifier:

B-41

Rotation speed measurement with inductive


transducers

ML460i
AP460i

10

4
2

Measurement signal,
rotation speed (+)

1
1 kW

Umax = 30 V

Measurement signal,
rotation speed ()

5 kW

5V

Inductive
rotation speed
measuring device
(TR coil)

Please refer to the setup instructions for TR coils on page E-38.

MGCplus with AB22A/AB32

Connecting Transducers

B-42

4.11

Thermocouples

Amplifier:

ML01B

AP09

AP409

AP809
+

1 2

Extension wire

Connect
shield here

Thermocouple

Case
Cas

Case

Case

Cable shield

Extension wire

MGCplus with AB22A/AB32

Type

1 (+)

2 ()

J
K
T
S

Iron
Nickel-chrome
Copper
Rhodium-platinum

Cupro-nickel
Nickel
Cupro-nickel
Platinum

Connecting Transducers

Amplifier:

B-43

ML801B

AP4091)

AP809
+

Miniature thermo-connector, uncompensated

Extension wire
Thermocouple

()

(+)

Extension wire

Miniature thermo-connector
(For compatible type see table)

Type

(+)

J
K
T
S

Iron
Cupro-nickel
Nickel-chrome
Nickel
Copper
Cupro-nickel
Rhodium-platinum Platinum

1)

()

Maximum common-mode voltage about earth 50V; channels 1 to 4 electrically isolated from each other and system.

MGCplus with AB22A/AB32

Connecting Transducers

B-44

4.12

Amplifier:

DC voltage sources

ML01B

Maximum input voltage relative


to earth ="12 V

AP01i
AP13i

15

AP03i

A
B
C

AP09

AP11i

F
G

1
2
3

E
D

5
4

1 2

(+)

Zero operating
voltage3)

()
Cable shield 1)

1
2)

15

Case

Case

Case

Case

1) see page B-11


Connect the negative pole of the voltage source to one of the pins 22...25 on the 25-pin female connector Bu2 (earth pin) (in the case of the AP13i, only pin 25 can be used)
3) In the case of a potential-free DC voltage source, you must connect pin 15 to pin 6.
2)

MGCplus with AB22A/AB32

Connecting Transducers

Amplifier:

ML801B

B-45

AP801

AP801S6

3
4

Maximum input voltage relative


to earth = "50 V

(+)
Case

()

2
1

(+)

()

Supply voltage 8 V/16 V*)

Supply voltage 0 V

4
Case

*)

Changeover supply voltage see page B-46

MGCplus with AB22A/AB32

Connecting Transducers

B-46

Supply voltage +16 V


No function (for special versions only)
Jumper

No function (for special versions only)


Supply voltage +8 V

Connection board AP801S6 (side view)

MGCplus with AB22A/AB32

Connecting Transducers

Amplifier:

ML801B

B-47

AP401
Sight of coupler socket
4x

(wiring side)

(+)
Case.

()

Pin assignment
1

+ In

not in use

not in use

In

MGCplus with AB22A/AB32

Connecting Transducers

B-48

4.13

Amplifier:

DC power source

ML01B

AP01i
AP13i

Maximum input voltage relative


to earth = 12 V

()

Zero operating voltage

15

AP03i

A
B
C

F
G

E
D

AP11i

1
2
3

5
4

Case

Case

I
(+)
Cable

1)

shielding 1)

see page B-11

MGCplus with AB22A/AB32

Case

Connecting Transducers

4.14

Amplifier:

B-49

Resistors, Pt10, 100, 1000

ML35B

AP01i
AP13i

15

AP03i

Three-wire
connection

E
D

AP11i

1
2
3

6
5
4

Four-wire connection
Excitation

Sensor circuit *

12

R
Cable shielding 1)

Case

Case

Case

Sensor circuit

13

Excitation

When connecting a two-wire sensor, wire bridges must be


soldered into the male connector (between the sensor circuit and
the excitation voltage)
1) see page B-11

MGCplus with AB22A/AB32

Connecting Transducers

B-50

Amplifier:

ML801B

AP835

Excitation

Sensor circuit

R
Cable shielding

Excitation

Pt100 with four wire circuit only

MGCplus with AB22A/AB32

Case

Sensor circuit

Connecting Transducers

4.15

Amplifier:

B-51

Frequency measurement without a


direction of rotation signal

ML60B

AP01i
AP13i
AP17
1

15

AP03i

A
B

Zero operating voltage

Frequency
generator /
Pulse
generator

Cable shielding 1)

Rotation speed/pulse signal 1 (frequency)

1)

see page B-11

F
G

E
D

AP11i

1
2
3

Case

Case

Case

12

6
5
4

Case = housing

In this operating mode, deactivate f2 signal evaluation (default: OFF), see page E-44.

MGCplus with AB22A/AB32

Connecting Transducers

B-52

4.16

Amplifier:

Frequency measurement with direction


of rotation signal

ML60B

AP01i
AP13i

15

AP03i

A
B

*)

see page B-11

E
D

1
2
3

Cable shielding 1)

Case

Case

Case

Speed/Impulse signal 1
(Frequency f1)

12

15

Rotation speed/pulse signal 1


(frequency f2)

1)

F
G

Zero operating voltage

Frequency
generator /
Impulse
generator

AP11i

6
5
4

Case = Housing

F2 signal evaluation has been deactivated by default. For measurements with signal of direction, you must activate the f2 signal, see
page E-44.

MGCplus with AB22A/AB32

Connecting Transducers

4.17

Amplifer:

B-53

Impulse counting

ML60B

AP01i
AP13i

15

AP03i

A
B

f2

f1

Industrial
pulse generator
Zero index
Transducer error

F
G

E
D

AP11i

AP460i

1
2
3

5
4

15

12

MGCplus with AB22A/AB32

Connecting Transducers

B-54

Amplifier:

ML60B
AP17

Zero index +
Zero index
f1+
Industrial
pulse generator

f1
f2
f2+
Transducer error

MGCplus with AB22A/AB32

15

AP460i

12

13

14

15

Connecting Transducers

4.18

B-55

Active and passive piezoelectric transducers

Passive piezoelectric transducer

Amplifier:

ML10B, ML01B
with AP08

Current-fed piezoelectric transducer

AP08

Amplifier:

ML10B,
ML01B with
AP18i/AP418i

AP18i

AP418 i

Adjustment
potentiometer for
current feed
Shield
Piezoelectric
transducer with
preamplifier
(with T-ID/
TEDS for
AP418i)

Piezoelectric
transducer

Input *

Shield

Input *

Use special coaxial cable see page E-66

Advice for connection boards AP08, AP18i, AP418i:


If the transducer connection cable is used outside of closed rooms or if the transducer connection cable is longer
than 30 m, then this cable must be protected against high voltage with an additional, separately grounded shield.
This can be achieved laying the cable in a metallic pipe or by using double shielded cables, where the external
shield near by the connection board must be grounded (connect to ground or ground wire). For this purpose
HBM recommend to use Triaxial cables.

MGCplus with AB22A/AB32

Connecting Transducers

B-56

4.19

Piezoresistive transducers

Amplifier: ML10B2)

AP01i
AP13i

AP03i

15

Measurement
signal (+)
Excitation
voltage ()
Excitation
voltage (+)

Measurement
signal ()
Cable shielding 1)

E
D

AP11i

1
2
3

5
4

15
Case

Case

Case

1)

Sensor circuit (+)

13

Sensor circuit ()

12

see page B-11

MGCplus with AB22A/AB32

Connecting Transducers

4.20

B-57

Potentiometric transducers (singlechannel)

Amplifier: ML10B2)

AP01i
AP13i

15

AP03i

Measurement
signal (+)
Excitation
voltage ()
Excitation
voltage (+)

E
D

AP11i

1
2
3

5
4

Cable shielding 1)

Case

Case

Case

1)

see page B-11

2)

You will need to set up

Sensor circuit (+)

13

Sensor circuit ()

12

and Hi under bridge type

MGCplus with AB22A/AB32

Connecting Transducers

B-58

4.21

Potentiometric transducers (Multichannel)

Amplifier: ML801B

AP836
Subchannels
1

2/6

3/7

4/8

14

Subchannel 1...4

13

1/5

25
2

Measuring signal (+)

11

Excitation voltage ()

10

Excitation voltage (+)

12

Cable shield 1)
3

Subchannel 5...8

Case

Case

Case

Case

Sensor circuit (+)

16

19

22

25

Sensor circuit ()

14

17

20

23

Wire colors: WH= white; BK= black; BL= blue; RD= red; YE= yellow; GN= green; GR= gray; BN= brown

MGCplus with AB22A/AB32

Connecting Transducers

4.22

B-59

Connection via distributor board VT814i

SingleS.G.; 3wire connection with AP814


1Kab1563
2

SingleS.G.; 3wire connection with AP814Bi


3

S.G.
1

RJ45 socket

WH/GN Excitation voltage (+)

S.G.
RD

Measuring signal (+)

Cable shield

1Kab1563

RJ45 socket

WH/GN Excitation voltage ()

RD

Cable shield

Case

WH/RD Excitation voltage (+)

Measuring signal

2
Case

WH/RD Excitation voltage ()

Wire colors: WH= white; BK= black; BL= blue; RD= red; YE= yellow; GN= green; GR= grey; BN= brown

Connection diagram
Measuring point

Distributor board VT814

Connection board
AP814Bi

S.G. 1
1Kab1563

RJ45
1
D-Sub25

S.G. 2

D-Sub25

1Kab2633

1AP814Bi

1Kab1563
2

S.G. 8
1Kab1563
8

A detailed connection diagram has been supplied with the distributor board.

MGCplus with AB22A/AB32

Connecting Transducers

B-60

4.23

Connection via distributor board VT810/815i

SingleS.G.; 4wire connection


1Kab1563
2

WH/RD

S.G. half bridge


RJ45 socket

Excitation voltage ()

1Kab1563

1
2

RD

Sensor circuit ()

2
1

RD

Sensor circuit ()

WH/RD

Excitation voltage ()

WH/GN

Measuring signal (+)

S.G.

Cable shield
Cable shield

Case

WH/GN

Measuring signal (+)

GN

Excitation voltage (+)

1Kab1563

Measuring signal (); only AP815i

WH/BN

Excitation voltage (+)

BN

Sensor circuit (+)

7
8

RD

Sensor circuit ()

WH/RD

Excitation voltage ()

GN

Measuring signal ()

WH/BN

Excitation voltage (+)

BN

Sensor circuit (+)

4
3

RJ45 socket

Measuring signal (+)

Cable shield

8
Case

Wire colors: WH= white; BK= black; BL= blue; RD= red; YE= yellow; GN= green; GR= grey; BN= brown

A detailed connection diagram has been supplied with the distributor board.

MGCplus with AB22A/AB32

3
Case

GN

S.G. full bridge

WH/GN

RJ45 socket

Connecting Transducers

B-61

Connection diagram

Measuring point

Distributor board VT810/815i

Connection board AP810/815i


D-Sub25

S.G. 1
1Kab1563

RJ45
1
D-Sub25

S.G. 2

1Kab2633

1Kab1563
2
D-Sub25
1Kab2633
1AP810
1AP815i
S.G. 8
1Kab1563
8

A detailed connection diagram has been supplied with the distributor board.

MGCplus with AB22A/AB32

B-62

Connecting MGCsplit

Connecting the MGCsplit modules

5.1

Split-line-cable

CAUTION
Only original split-line connecting cable that has been made up and tested by HBM must be used for
cabling MGCsplit systems.
If other cable is used it will be impossible to guarantee error-free operation and we accept no responsibility
for any resulting loss or damage.

MGCplus with AB22A/AB32

B-63

Connecting MGCsplit

5.2

Power supply units NT650/NT651

1NT650

ATTENTION
The power supply units have fine-wire fuses. The fuses may only
be replaced by the manufacturers service personnel.
Connecting the power supply
The power supply units NT650/NT651 supply the MGCsplit-modules
with a direct voltage of 28 V. The input voltage range is 10 V ... 50 V
(DC). The power supply units are not potentially isolated.
The power supply unit NT650 is specially designed for test drives and
can bridge voltage interruptions of up to 10 seconds 15 minutes after
being switched on (if 10 measurement modules are connected). The
buffer capacitors are automatically recharged as long as the power
supply unit is switched on.
Use a 4-wire cable for the supply line with a wire cross-section of 0.5
mm2. Always connect all 4 wires.
Avoid high contact resistances (e.g. due to corroded plug connectors)!

Voltage supply

Matching plug
(view of connection side)

Voltage supply (device plug POWER IN)


Pin

Function

Input voltage (1050V DC)

Input voltage (1050V DC)

Input voltage (0V DC)

Input voltage (0V DC)

Device plug:
G82BFCT04MPH00000
Recommended cable jack:
S32BFCT04LPH06000
(suitable for crimp mounting and cable diameter 5.5 mm ... 6 mm)

MGCplus with AB22A/AB32

B-64

Connecting MGCsplit

1NT650

Input

Output

You can connect a maximum of 10 modules (1x SH400CP and 9x


SH400 or SH650) or, if using a ABX22 display- and control panel, a
maximum of 9 modules. If more MGCsplit-modules (up to 1x SH400CP,
16x SH400 or SH650 and 1x ABX22) are to be operated, you will need
an additional power supply unit. Both power supply units should in this
case be arranged directly behind one another.

Connect the MGCsplit measuring system to the sockets SPLITLINE


IN and SPLITLINE OUT. Only use the Split Line cable from HBM.
You can connect the power supply unit at any point in the measuring
system. Just interrupt the SPLITLINE and connect the power supply
unit in between.
Connection at the start of the system (before the SH400CP):
Advantage: if there is a power failure, the communication processor
CPxx receives a warning signal from the NT650 if the energy only
suffices for another ca. 5 seconds. It can therefore finish the
measurement in a defined manner.
Connection in the middle (e.g. between two SH650 measurement
modules):
Advantage: Good power distribution (less losses in the supply lines).

MGCplus with AB22A/AB32

B-65

Connecting MGCsplit

Split-Line-connections
Matching plug
(view of connection side)

Pin

16

*)

Function

Output voltage (28V DC) for MGCsplit supply

Output voltage (28V DC) for MGCsplit supply

Output voltage (0V DC) for MGCsplit supply

Output voltage (0V DC) for MGCsplit supply

*)

*)

*)

*)

*)

10

*)

11

*)

12

*)

13

Power Down Signal at CP module (NT650 only)

14

Earth potential MGCsplit

15

*)

16

*)

Signal at these pins are looped through from SPLITLINE IN to SPLITLINE OUT.

Device connector:
G82B0CT16QF000000
Recommended cable connector:S32B0CT16MPFG07500
(suitable for crimp mounting and cable diameter 7 mm ... 7.5 mm)

MGCplus with AB22A/AB32

B-66

Connecting MGCsplit

1NT650

CAN-connections
Pin

CANinput
(**)

Function

CAN signal (Low)

CAN earth

Input for ext. CAN supply voltage (**)

CAN signal (High)

Digital input for remote control of NT650/NT651

Ground reference of digital input NT_ON

Currently not required

Device connector:
G82BACT06QPH000000
Recommended cable connector:S32BACT06MPH06000
(suitable for crimp mounting and cable diameter 5.5 mm ... 6 mm)

Matching plug
(view of connection side)

1
6
2

4
3

MGCplus with AB22A/AB32

With pin 5 you can switch the power supply unit on or off remotely. The
mains switch must be in the position REMOTE. A change in the level
from over 3V to under 1V or vice versa causes switching, either from
OFF to ON or from ON to OFF.
The CAN bus is connected to pins 1 and 4, the earth may also be
required. A CAN terminating resistor is not present in the power supply
unit, if necessary you must add one externally. Switching on and off is
implemented with two predefined messages (see Page B-67).
The galvanically isolated digital input NT_ON is related to GNDM.
GNDM can if necessary be connected with pin 6 (0V_IN).

B-67

Connecting MGCsplit

Switch settings
Switch
setting

Significance (with connected supply)

ON

The power supply unit is switched on, connected MGCsplit


measuring systems are supplied with 28 V DC. (*)

OFF

The power supply unit is switched off, connected MGCsplit


measuring systems are not supplied. (*)

REMOTE

a) Directly after switching from switch position OFF or after


deactivation via CAN or digital input:
The power supply unit is switched off, green LED flashes every 2s,
connected MGCsplit-measuring system is only supplied when it is
activated via the CAN or digital input.
b) After activation via CAN or digital input:
The power supply unit is switched on, green LED lights up,
connected MGCsplit measuring systems are supplied with 28 V DC.
(*)

(*) NT650 only: The buffer capacitors are automatically recharged when
necessary (additional power consumption up to ca. 8W).

Manual on/off switching


Turn the POWER switch to the ON or OFF position.
Remote on/off switching
In the switch position REMOTE, you can switch the power supply unit
on/off via the CAN bus. Standard CAN is supported as per ISO11898
(Transceiver PCA82C251). A switch on and switch off message are
defined.
CAN-message for switching on/off:
CAN-parameter

Significance

Baud Rate

250 kBit/s

ID

0x83

DLC

Data switch on message

0x79, 0x78

Data switch off message

0x79, 0x70
MGCplus with AB22A/AB32

B-68

Connecting MGCsplit

Ensure that a terminating resistor (120 Ohm) is present on both ends of


the CAN bus. The listed CAN parameters are preset but can be
adapted by HBM on request.
Remote control via digital input
In the switch position REMOTE, the power supply unit can be
switched on/off via a galvanically isolated digital input.
Switching on/off is flank controlled, i.e. switching occurs when a flank is
detected, either from OFF to ON or from ON to OFF.
A flank is detected when the actual level of the signal NT_ON
changes from < 1V to > 3V (rising flank) or from > 3V to < 1V (falling
flank).
Remote control via CAN and digital input
Both variants can be combined, e.g. switching on via CAN switch on
message, switching off with rising or falling flank at the digital input.
Bridging of voltage failures (NT650 only):
The power supply unit NT650 is equipped with so-called buffer
capacitors which are fully loaded within 15 minutes of the supply
voltage being connected. If the power fails (e.g. during the vehicle
starting procedure), the power supply unit is supplied by these
capacitors.
A connected MGCsplit system with maximum modules can be supplied
for at least 10 seconds, correspondingly longer if less modules are
connected.
If a CP module is directly connected to the Split Line output and the
capacitor feed is active, then the CP module will receive a warning
signal (PDWN_CP based on GNDD) ca. 5 seconds before the buffer
energy is exhausted and can therefore end a current measurement
data recording in a defined manner.

MGCplus with AB22A/AB32

Connecting MGCsplit

B-69

Once the input voltage is again available, discharged buffer capacitors


are recharged, regardless of the NT650 switch position. Recharging
can take up to 15 minutes if the buffer capacitors are fully discharged.
A drop in capacitor voltage through self-discharge is also detected and
compensated for by cyclical recharging. However, this requires that the
NT650 is continually supplied with voltage.
In order to achieve correct switching from external supply to capacitor
supply, the supply lines must be as short and as low impedance as
possible. Too many or poor plug connections can also affect the
bridging function due to transition impedance. This must be taken into
account when using numerous modules and low supply voltages.
Operating states and errors, LED displays:
Two LEDs are located on the front panel, these can display various
operating states and errors.

MGCplus with AB22A/AB32

B-70

Connecting MGCsplit

1NT650

Operating and error status display via status LEDs:


POWER STATUS
(green LED)

ERROR STATUS
(Red LED)

Significance

Operating states

Green LED
Red LED

MGCplus with AB22A/AB32

ON

OFF

Switch setting: ON or REMOTE, NT65x


ON, normal operation, no error

OFF

OFF

a) NT65x not supplied


b) Switch position OFF, NT65x OFF,
normal operation, no error

Flashes every 2s

OFF

Switch position REMOTE, NT65x OFF,


normal operation, no error

Error states
ON

Flashes once per


second

NT650 only:
Switch position ON or REMOTE, NT650
ON, supply voltage failure, power supply
unit operation via buffer capacitors.
Error rectification: Restore correct
supply.

ON

Flashes twice per


second

NT650 only: Switch position ON or


REMOTE, NT650 ON, voltage supply
failure, power supply unit operation via
buffer capacitors which are already
discharged to ca. 15 20% of their initial
energy level. Error rectification: Restore
correct supply.

OFF

ON

a) Switch position ON or REMOTE,


active NT65x is switched off due to
excess temperature.
Error rectification: Switch to OFF, check
load and allow device to cool, switch
NT65x back on.
b) Switch position ON or REMOTE,
NT65x switched off due to overload (e.g.
short circuit).
Error rectification: Switch to OFF, rectify
overload, switch NT65x back on.

B-71

Connecting MGCsplit

Schematic circuit diagram of battery cable


RL
RK
UBat

RL
RL

Iin =

Pin
Umin

NT650

SH400CP

Umin
Pin

RK

Terminal

RL
Cable

Equation for minimum battery voltage calculation

U Bat  U min  2  R K  2  l 

P
R L
 in
2
U min

Example:
Umin = 10V, Pin = 100W
RK = 20mW (estimated transition resistances of terminals and plug connectors)
R L = 24mW/m (cable resistance with cable cross-section of 0.75mm2)
l = 3m (cable length)
UBat  11.12V

ATTENTION
Keep the cable short and avoid unnecessary transition resistances to keep the voltage drop as small as
possible.

MGCplus with AB22A/AB32

B-72

Connecting MGCsplit

Battery voltage [V]

Minimum required battery voltage UBat [V]

Cable length [m]

MGCplus with AB22A/AB32

B-73

Connecting MGCsplit

5.3

Amplifier modules and connection boards in the


1SH400 enclosure

5.3.1

Amplifier modules that can be connected

The following amplifier modules from the MGCplus system can be used in the MGCsplit system (with effect from
hardware version 1.31 and higher):
Amplifier module

Software version

ML01B

P5.33

ML10B

P5.33

ML30B

P5.33

ML35B

P5.33

ML50B

P5.33

ML55B

P5.33

ML55BS6

P5.33

ML60B

P5.20

ML70B

P1.33

ML71B

P1.80

ML71S6

P1.28

ML77B

P2.02

ML78B

P1.53

ML460

P1.13

ML801B

P5.18

MGCplus with AB22A/AB32

B-74

5.3.2

Connecting MGCsplit

Connection boards

You can use any connection board from the MGCplus system. In the case of the transducer excitation the following
special features apply:
AP17
The torque transducers must be energized by means of an external power supply (except for T10FSF1 and SU2).
AP460i
The transducer excitation (DC) may be adjusted to 5 V, 8 V, 16 V. Maximum current per connection board is
50 mA.
AP801S6
The transducer excitation may be 8 V or 16 V. Maximum output current is 50 mA.

Note
In the event of higher loads the module concerned may be automatically shut down.

MGCplus with AB22A/AB32

B-75

Connecting MGCsplit

5.4

Connecting the MGCsplit modules

1SH400CP
ABX22A
external
display
and
control
panel
Input
Output

Suitable connector
Connection end view
1

16

*)

Pin

Input

Output

Power supply 24 32 V DC (typically


28 V)

Power supply 24 32 V DC (typically


28 V)

Power supply 24 32 V DC (typically


28 V)

Power supply 24 32 V DC (typically


28 V)

Power supply 0 V

Power supply 0 V

Power supply 0 V

Power supply 0 V

Not in use

Link1+

Not in use

Link1

Not in use

Link2+

Not in use

Link2

SDA_out *)

Rx_A

10

Not in use

Rx_B

*)

Tx_A

11

SDA_in

12

Not in use

Tx_B

13

ResIn*)

ResOut

14

GND digital *)

GND digital

15

SCL *)

Sync_A

16

Not in use

Sync_B

I2C interface and reset are only necessary when using the NT650 power pack

Device connectors:
Recommended male plug:

G82B0CT16LFG00000
S32B0CT16PFG07500

(suitable for crimp fit and cable diameters 7 mm to 7.5 mm)

MGCplus with AB22A/AB32

B-76

Connecting MGCsplit

5.5

Inputs/outputs for measurement modules


SH400/SH650

1SH400

Input
Output

1SH650

Pin

Input

Output

Power supply 24 32 V DC (typically


28 V)

Power supply 24 32 V DC (typically


28 V)

Power supply 24 32 V DC (typically


28 V)

Power supply 24 32 V DC (typically


28 V)

Power supply 0 V

Power supply 0 V

Power supply 0 V

Power supply 0 V

Link1+

Link1+

Link1

Link1

Link2+

Link2+

Link2

Link2

Rx_A

Rx_A

10

Rx_B

Rx_B
Tx_A

11

Tx_A

12

Tx_B

Tx_B

13

ResIn

ResOut

14

GND digital

GND digital

15

Sync_A

Sync_A

16

Sync_B

Sync_B

Input

Device connectors:
Recommended male plug:

Output

G82B0CT16LFG00000
S32B0CT16PFG07500

(suitable for crimp fit and cable diameters 7 mm to 7.5 mm)

Suitable connector
(Connection end view)
1

16

MGCplus with AB22A/AB32

B-77

Connecting MGCsplit

5.6

AP409 connection boards in the 1SH650


enclosure

1SH650ML801B409
1SH650ML801B2x409

Pin

Function

+ Input

Input

Device connectors:

Transducer
connections
AP409

GX0S0CP0200000002*)

Recommended male plugs:


SX0S0CP0200000002 (solder contacts, K-Type)
S30S0CT02PJD05000 (crimp contacts, gold)
S30S0CT02MJG05000 (solder contacts, gold)
(suitable for cable diameters 4.5 mm to 5 mm)
*)

Contacts made of K-type thermal material, to avoid measuring errors by temperature


gradients of the connector.

Suitable connector
(Connection end view)

1
S
2

MGCplus with AB22A/AB32

B-78

Connecting MGCsplit

5.7

AP401 connection boards in the 1SH650


enclosure

1SH650ML801B401
1SH650ML801B2x401

Transducer
connections
AP401

Function

+ Input

Not in use

Not in use

Input

Device connectors:
G80S0CT04LFD00000
Recommended male plug:
S30S0CT04MFD05000
(suitable for solder contacts and cable diameters 4.5 mm to 5 mm)

Suitable connector
(Connection end view)
2
1
3

Pin

MGCplus with AB22A/AB32

B-79

Connecting MGCsplit

5.8

AP815i connection boards in the 1SH650


enclosure

1SH650ML801B815
5

Transducer
connections

Pin

Half and Full bridge function

Quarter bridge function

Measurement signal (+)

Measurement signal (+)

Excitation voltage ()

Excitation voltage ()

Excitation voltage (+)

Not in use

Measurement signal ()

Excitation voltage (+)

GND (inner shield)

GND (inner shield)

Not in use

Not in use

Not in use

Not in use

Not in use

Not in use

Sensor circuit (+)

Not in use

10

Sensor circuit ()

Sensor circuit ()

Device connectors:
G82B0CT10QJ000000
Suitable connector
(Connection end view)

Recommended male plugs:


S32B0CT10PJD08000 (crimp contacts)

S32B0CT10MJD08000 (solder contacts)

10

(suitable for cable diameters 7.5 mm to 8 mm)


See also connection diagrams
SG full bridges with AP810/AP815i in chapter 4.3
SG half bridges with AP810/AP815i in chapter 4.6
Single strain gage with AP815i in chapter 4.7.5

MGCplus with AB22A/AB32

B-80

Connecting MGCsplit

5.9

AP460i connection boards in the 1SH650


enclosure

1SH650ML460460

1
2

Transducer
connections

3
4

Pin

Function

Frequency signal 1, input a

Frequency signal 1, input b

Frequency signal 2, input a

Frequency signal 2, input b

Zero index, input a

Zero index, input b

Transducer supply 5V*)

Transducer identification

Transducer supply ground

10

Signal ground

Device connectors:
G82B0CT10QJ000000
Suitable connector
(Connection end view)

10

Recommended male plugs:


S32B0CT10PJD08000 (crimp contacts)
S32B0CT10MJD08000 (solder contacts)
(suitable for cable diameters 7.5 mm to 8 mm)

*)

MGCplus with AB22A/AB32

Maximum total current for all subchannels is 50 mA

B-81

Connecting MGCsplit

5.10

AP13i connection boards in the 1SH650


enclosure

1SH650ML55BAP13i
1SH650ML10BAP13i
1SH650ML30BAP13i

Digital inputs

The following are valid for all single-channel connection boards:


Digital inputs:
(30 coded female connector)
Digital outputs:
(30 coded female connector)
Analog outputs:
(30 coded female connector)
Transducers:
(0 coded female connector)
Digital inputs:

Suitable connector
(Connection end view)
1

10

Pin

Function

Ground (control inputs 1/2/3/4)

Ground (control inputs 5/6/7/8)

Control input 1

Control input 2

Control input 3

Control input 4

Control input 5

Control input 6

Control input 7

10

Control input 8

Device connectors:
G82BACT10QJ000000 (30 coding)
Recommended male plugs:
S32BACT10PJD08000 (30 coding; crimp contacts)
S32BACT10MJD08000 (30 coding; solder contacts)
(suitable for cable diameters 7.5 mm to 8 mm)

MGCplus with AB22A/AB32

B-82

Connecting MGCsplit

AP13i connection boards in the 1SH650 enclosure

Digital outputs:

1SH650ML55BAP13i
1SH650ML10BAP13i
1SH650ML30BAP13i

Digital outputs

Pin

Function

24 V (limit value 1/2)

24 V (limit value 3/4)

Ground (limit value 1/2)

Ground (limit value 3/4)

Limit value output 1

Limit value output 2

Limit value output 3

Limit value output 4

Warning

10

Not in use

Device connectors:
G82BACT10QJ000000 (30 coding)
Suitable connector
(Connection end view)

10

MGCplus with AB22A/AB32

Recommended male plugs:


S32BACT10PJD08000 (30 coding; crimp contacts)
S32BACT10MJD08000 (30 coding; solder contacts)
(suitable for cable diameters 7.5 mm to 8 mm)

B-83

Connecting MGCsplit

AP13i connection boards in the 1SH650 enclosure

Analog outputs:

1SH650ML55BAP13i
1SH650ML10BAP13i
1SH650ML30BAP13i

Analog outputs

Pin

Function

Analog ground

Voltage output Ua1

Not in use

Voltage output Ua2

Not in use

Current output Ia1

Not in use

Not in use

Not in use

10

Not in use

Device connectors:
G82BACT10QJ000000 (30 coding)
Suitable connector
(Connection end view)
1

10

Recommended male plug:


S32BACT10PJD08000 (30 coding; crimp contacts)
S32BACT10MJD08000 (30 coding; solder contacts)
(suitable for cable diameters 7.5 mm to 8 mm)

MGCplus with AB22A/AB32

B-84

Connecting MGCsplit

AP13i connection boards in the 1SH650 enclosure

Transducers:

1SH650ML55BAP13i
1SH650ML10BAP13i
1SH650ML30BAP13i

Transducer
connection

Pin

Function

Measurement signal (+)

Bridge excitation voltage ()

Bridge excitation voltage (+)

Measurement signal ()

GND

+16 V

16 V

SDA

Sensor circuit (+)

10

Sensor circuit ()

Device connectors:
G82B0CT10QJ000000 (0 coding)
Suitable connector
(Connection end view)
1
2

8
9

10
4

6
5

MGCplus with AB22A/AB32

Recommended male plugs:


S32B0CT10PJD08000 (0 coding; crimp contacts)
S32B0CT10MJD08000 (0 coding; solder contacts)
(suitable for cable diameters 7.5 mm to 8 mm)

B-85

Connecting MGCsplit

5.11

AP17 connection boards in the 1SH650 enclosure

1SH650ML60BAP17

Digital inputs

The following are valid for all singlechannel connection boards:


Digital inputs:
(30 coded female connector)
Digital outputs:
(30 coded female connector)
Analog outputs:
(30 coded female connector)
Transducers:
(0 coded female connector)
Digital inputs

Suitable connector
(Connection end view)

10

Pin

Function

Ground (digital)

Control input 1

Control input 2

Control input 3

Control input 4

Control input 5

Control input 6

Control input 7

Control input 8

10

Not in use

Device connectors:
G82BACT10QJ000000 (30 coding)
Recommended male plugs:
S32BACT10PJD08000 (30 coding; crimp contacts)
S32BACT10MJD08000 (30 coding; solder contacts)
(suitable for cable diameters 7.5 mm to 8 mm)

MGCplus with AB22A/AB32

B-86

Connecting MGCsplit

AP17 connection boards in the 1SH650 enclosure

Digital outputs

1SH650ML60BAP17

Digital outputs

Suitable connector
(Connection end view)

10

MGCplus with AB22A/AB32

Pin

Function

Ground (digital)

Limit value output 1

Limit value output 2

Limit value output 3

Limit value output 4

Warning

Not in use

Not in use

Not in use

10

Not in use

Device connectors:
G82BACT10QJ000000 (30 coding)
Recommended male plugs:
S32BACT10PJD08000 (30 coding; crimp contacts)
S32BACT10MJD08000 (30 coding; solder contacts)
(suitable for cable diameters 7.5 mm to 8 mm)

B-87

Connecting MGCsplit

AP17 connection boards in the 1SH650 enclosure

Analog outputs

1SH650ML60BAP17

Analog outputs

Suitable connector
(Connection end view)

10

Pin

Function

Analog ground to Vo1

Voltage output Vo1 (Ra>5 kOhm)

Analog ground to Vo2

Voltage output Vo2 (Ra>5 kOhm)

Analog ground to Vo1 / Io1

Vo1 / Io1 (20 mA); Ra<500 Ohm

Analog ground to Vo2 / Io2

Vo2 / Io2 (20 mA); Ra<500 Ohm

Not in use

10

Not in use

Device connectors:
G82BACT10QJ000000 (30 coding)
Recommended male plugs:
S32BACT10PJD08000 (30 coding; crimp contacts)
S32BACT10MJD08000 (30 coding; solder contacts)
(suitable for cable diameters 7.5 mm to 8 mm)

MGCplus with AB22A/AB32

B-88

Connecting MGCsplit

AP17 connection boards in the 1SH650 enclosure

Transducers

1SH650ML60BAP17

Transducer
connection

Suitable connector
(Connection end view)

1
2

10

MGCplus with AB22A/AB32

Pin

Function

Frequency signal 1, input a

Frequency signal 1, input b

Frequency signal 2, input a

Frequency signal 2, input b

Zero index, input a

Zero index, input b

Transducer supply +5 V*)

Transducer identification

Transducer supply ground

10

Signal ground

Device connectors:
G82B0CT10QJ000000 (0 coding)
Recommended male plugs:
S32B0CT10PJD08000 (0 coding; crimp contacts)
S32B0CT10MJD08000 (0 coding; solder contacts)
(suitable for cable diameters 7.5 mm to 8 mm)
*)

Maximum output current is 50 mA. Please note that torque transducers cannot be fed
from this supply.

B-89

Connecting MGCsplit

5.12

AP71 connection boards in the 1SH650 enclosure

CAN connections 1 to 2

1SH650ML71BAP71
1

CAN
connections

Suitable connector
(Connection end view)

1
2

8
9

10
4

Pin

Function

Not in use

CAN_L

CAN_GND

CAN_V+

CAN_Shield

GND

CAN_H

Not in use

Not in use

10

Not in use

Device connectors:
G82B0CT10QJ000000 (0 coding)
Recommended male plugs:
S32B0CT10PJD08000 (0 coding; crimp contacts)
S32B0CT10MJD08000 (0 coding; solder contacts)
(suitable for cable diameters 7.5 mm to 8 mm)

MGCplus with AB22A/AB32

B-90

Connecting MGCsplit

5.13

AP78 connection boards in the 1SH650 enclosure

The AP78 connection board has a total of ten analog outputs, two of
which are looped through from the ML78B amplifier (VO1 and VO2).

1SH650ML78BAP78

Connection 1 (analog output VO1)


Analog outputs

Suitable connector
(Connection end view)

10

MGCplus with AB22A/AB32

Pin

Function

GND to Vo1

Analog output from amplifier VO1

Not in use

Not in use

Not in use

Not in use

Not in use

Not in use

Not in use

10

Not in use

Connection 2 (analog output VO2)


Pin

Function

GND to Vo2

Analog output from amplifier VO2

Not in use

Not in use

Not in use

Not in use

Not in use

Not in use

Not in use

10

Not in use

B-91

Connecting MGCsplit

AP78 connection boards in the 1SH650 enclosure

Connection 3 (analog outputs AO3 to AO6)

1SH650ML78BAP78

Analog outputs

Pin

Function

GND to AO3

Analog output AO3

GND to AO4

Analog output AO4

GND to AO5

Analog output AO5

GND to AO6

Analog output AO6

Not in use

10

Not in use

Connection 4 (analog outputs AO7 to AO10)


Suitable connector
(Connection end view)

1
2

8
9

10
4

6
5

Pin

Function

GND to AO7

Analog output AO7

GND to AO8

Analog output AO8

GND to AO9

Analog output AO9

GND to AO10

Analog output AO10

Not in use

10

Not in use

MGCplus with AB22A/AB32

B-92

Connecting MGCsplit

AP78 connection boards in the 1SH650 enclosure

1SH650ML78BAP78

Device connectors:
G82B0CT10QJ000000 (0 coding)

Recommended male plugs:


S32B0CT10PJD08000 (0 coding; crimp contacts)
S32B0CT10MJD08000 (0 coding; solder contacts)
(suitable for cable diameters 7.5 mm to 8 mm)

Suitable connector
(Connection end view)

1
2

8
9

10
4

6
5

MGCplus with AB22A/AB32

B-93

Connecting MGCsplit

5.14

AP75 connection boards in the 1SH650 enclosure

Connection 1 (digital outputs 1 to 4, analog output 1)

1SH650ML78BAP75

Digital outputs
and
analog outputs

Pin

Function

GND OUT

OUT1

OUT2

OUT3

OUT4

24 V IN

Not in use

Not in use

GND VO1

10

VO1

Connection 2 (digital outputs 5 to 8, analog output 2)


Suitable connector
(Connection end view)

Pin

Function

GND OUT

OUT5

OUT6

OUT7

10

OUT8

24 V IN

Not in use

Not in use

GND VO2

10

VO2

MGCplus with AB22A/AB32

B-94

Connecting MGCsplit

AP75 connection boards in the 1SH650 enclosure

Connection 3 (digital inputs 1 to 4):

1SH650ML78BAP75

Digital inputs

Pin

Function

GND IN

IN1

IN2

IN3

IN4

Not in use

Not in use

Not in use

Not in use

10

Not in use

Connection 4 (digital inputs 5 to 8):


Suitable connector
(Connection end view)

1
2

10
4

MGCplus with AB22A/AB32

Pin

Function

GND IN

IN5

IN6

IN7

IN8

Not in use

Not in use

Not in use

Not in use

10

Not in use

B-95

Connecting MGCsplit

AP75 connection boards in the 1SH650 enclosure

Device connectors:
G82BACT10QJ000000 (30 coding)

1SH650ML78BAP75

Recommended male plugs:


S32BACT10PJD08000 (30 coding; crimp contacts)
S32BACT10MJD08000 (30 coding; solder contacts)
(suitable for cable diameters 7.5 mm to 8 mm)

Suitable connector
(Connection end view)

10

MGCplus with AB22A/AB32

B-96

Connecting CANHEAD

Connecting CANHEAD modules

The ML74 communication card and the AP74 connector plate are required for connecting CANHEAD modules to
the MGCplus systems. A maximum of 12 modules per plugin amplifier and 24 modules per MGCplus device can
be connected, this amounts to a total of 240 measuring points (a maximum of 256 channels per CP22/CP42 can be
managed in the device). For more information on connection and operation please refer to the CANHEAD Measurement electronics mounting instructions.

MGCplus with AB22A/AB32

B-97

Connecting CANHEAD

6.1

ML74 communication module

ML74

LED

Labeling

Color

Meaning

CHAN.

Yellow

Channel has been selected

ERROR/
WARN.

Red

Error/Warning

Rx

Yellow

Receiving CAN protocol

Tx
OVRN

Yellow
Red

Transmitting CAN protocol


Overrun

BUS/ERR

Red

Bus error

CONFIG

Yellow

Configuring allocated CANHEADS

AP74
STATUS

Yellow
Off
Red

Voltage supply via AP74


No voltage supply via AP74
Error during voltage supply via AP74

SCAN

Yellow

Executing bus scan

MGCplus with AB22A/AB32

B-98

6.2

Connecting CANHEAD

AP74 connection board

AP74

MGCplus with AB22A/AB32

LED color

Meaning

Green

Normal state during operation

Red

Short circuit or overload

None

Voltage supply switched off

B-99

Connecting Interfaces

Connecting the computer, PLC and printer

The MGCplus can optionally be fitted with the following interfaces:


Serial interfaces for computer port (CP22/CP42):
RS 232 C
USB
Ethernet

MGCplus with AB22A/AB32

B-100

Connecting Shunt resistor

Connecting a shunt resistor

For connection boards there also exists, as an optional solution, a facility for switching the shunt on. An off-the-shelf
shunt on-switch is provided for the AP14 connection board. This compensating resistor creates a bridge mismatch
of 1 mV/V.

MGCplus with AB22A/AB32

B-101

Connecting Outputs and remotes

Inputs, Outputs and remotes

9.1

Inputs and Outputs CP22/CP42

The CP22 communication processor provides one digital input and output each. The CP42 communication processor provides two digital inputs and outputs each.
The digital In and Outputs must be operated with an external feeding
(12 V ... 24 V).

CP42
RS 232
CARDBUS

Inputs (0 V ... 24 V)
The following functions can be assigned to the digital inputs:
USB DEVICE

Start data acquisition by external trigger (only with CP42)


Print measured values (with direct connection via USB interface)
Formfeed

USB HOST

ETHERNET

The MGCplus terminal commands can also be used to query the status
of the inputs and outputs.

YE SLAVE
RD ERROR
GN MASTER

IN
SYNC
CTRL I/O
OUT
24V 1 2 GND 1 2
OUT
IN

Outputs (0 V ... 24 V)
The digital outputs are allocated to the Disc full function. If the
remaining storage space on the PC card harddisk in the CP42 unit is
lower than 1 MByte, the output will be set to high.
No function is assigned to the digital outputs. The MGCplus terminal
commands can be used to modify the status.

Inputs and outputs

MGCplus with AB22A/AB32

B-102

Connecting Outputs and remotes

Wiring example for the Start Trigger function at the CP42 control inputs
CP42

COM
NO

NC

CTRL I/O

+
24V DC

MGCplus with AB22A/AB32

24V

GND1
IN

B-103

Connecting Outputs and remotes

Wiring example for the Print measured values function at the CP22 control inputs

COM
CP22

NO

NC

IN
24Vext
GNDext
CTRL I/O

+
24V DC

MGCplus with AB22A/AB32

B-104

9.2

Connecting Outputs and remotes

Analogue output on the front panel

The front panel of a one-channel module includes a female BNC connector for analogue
output signal VO1. (This female connector is for test purposes. The fixed wiring should
always go through the connection boards, since the noise voltage is smaller here).

NOTE
Please note: the input resistance of the connected device must be greater than 1 MW.
When connecting a coaxial cable to the analog output of the ML60B preamplifier module for
use in Class B environments, acc. to EN55011 or EN55022 (residential premises, business
and trade, and small businesses), a ferrite (Wrth, art. No. 742 711 72 or similar) must be
attached to the cable.

MGCplus with AB22A/AB32

Connecting Outputs and remotes

9.3

B-105

Connection boards AP01i...AP18i

Connection boards for the amplifier channels are plugged in at the back of the desktop housing, respectively on the
right-hand side of the wall-mounted housing. The female connector on these connection boards provide you not
only with connection facilities for the transducer, but also with several output and control signals, depending on the
chosen option. These are explained in greater detail in the following chapters.

MGCplus with AB22A/AB32

B-106

Connecting Outputs and remotes

9.3.1

Pin assignment AP01i/03i/05/08/09/11i/14/17/18i

PIN

13

14

25

Bu 2
Outputs
OUTPUT

Function

Digital

Remote 1

Input

Remote 2

Input

Remote 3

Input

Remote 4

Input

Remote 5

Input

Remote 6

Input

Remote 7

Input

Remote 8

Input

10

VO2/IO2 (20 mA); Ro<500

Output

11

VO1/IO1 (20 mA); Ro<500

Output

12

VO2 (Ro>5 k)

Output

13

VO1 (Ro>5 k)

Output

16

Digital

Input

17

Output of LIV1

Output

18

Output of LIV2

Output

19

Output of LIV3

Output

20

Output of LIV4

Output

21

Warning

Output

22

to pin10
to pin 11

23
24
25

Table 9.1 Bu2

MGCplus with AB22A/AB32

Analogue

to pin 12
to pin 13

Connecting Outputs and remotes

B-107

Output pin assignments


Analogue output

Pin 10 is only used if the connection board is fitted with the EM001 final stage module. This must be installed
as described in chapter 9.3.2. The switch position determines whether the output signal is made available as a
voltage signal or as a current signal.
Vo= 0...10 V, Ro >500 W
Io = 0...20 mA or +4...20 mA; Ro <500 W

Pin 11 is only used if the connection board is fitted with the EM001 final stage module. This must be installed
as described in chapter 9.3.2. The switch position determines whether the output signal is made available as a
voltage signal or as a current signal.
Vo=0...10 V, Ro500 W
Io=0...20 mA or +4...20 mA, Ro<500 W

NOTE
Connection boards AP08/14/17/18i may only be fitted with one final stage module. In this case pin 11 is
used and pin 10 is left free.

On pin 12 you will find analogue output signal VO2.


The connected load resistance must be greater than 5 kW.

On pin 13 you will find analogue output signal VO1 exactly as on the BNC female connector on the front panel.
Signals S1 to S4 are to be assigned as required to outputs V01 (Bu2 and BNC) and V02 (Bu2 only).
Bu2:
Ro >5 kW
BNC:
Ro >1 MW

MGCplus with AB22A/AB32

B-108

Connecting Outputs and remotes

On pins 17 to 20 you will find the connection states for limit switches 1 to 4. Their connection states are indicated by two different HCMOS voltage levels:
Positive logic:
Level 0V: Limit switch OFF
Level 5V: Limit switch ON

Pin 21 carries a level of 5 V (high level), which can be used as a warning signal. In the event of a fault for example a break in the transducer cable the output signal is set to 0 V (low). On the other hand, this signal is
also set to zero during the autocalibration cycle (every 5 min., for approx.1 s).

Remotes
On pins 2 to 9 of female connector 2 you will find remotes Ctrl 1 to 8 for controlling certain of the amplifiers functions. These remotes are active if they have been enabled via an AB22A/AB32 display and control panel, i.e. in REMOTE operating mode. The tasks assigned to these remotes can be freely selected. The available functions are
shown in chapter F Additional functions together with their descriptions.
In the factory preset, the remotes are not defined.

External triggering
Remote 7 is used as an external trigger input. For AP13i (Remote contact 7) see page B-49.

MGCplus with AB22A/AB32

B-109

Connecting Outputs and remotes

Additional notes on the AP17:


Pin assignment of the input socket
PIN

*)

Function

I/O

Shield

Zero-Index (+)

Input

Zero-Index ()

Input

Ground

Supply voltage transducer 16 V (max. 500 mA) *)

Output

Supply voltage transducer +16 V (max. 500 mA) *)

Output

no function

Ground

SDA for the XM001 external memory module

Input

10

SLC for the XM001 external memory module

Output

11

Supply voltage transducer 5 V (max. 300 mA) *)

Output

12

F1+ rotation speed 0, angle of rotation, torque, frequency

Input

13

F1 rotation speed 0, angle of rotation, torque, frequency

Input

14

F2 rotation speed 90, calibration signal trigger

Input/Output

15

F2+ rotation speed 90, calibration signal trigger

Input/Output

The data on current indicates the maximum continuous currents which are permissible on the AP17. There is no restriction on the number
of connection boards per enclosure, but a maximum of four connection boards can be used for the transducer power supply (for instance
5 V/16 V for the T10FSF1 torque flange).

MGCplus with AB22A/AB32

B-110

Connecting Outputs and remotes

When there are long cables (>100 m) and high frequencies (>200 kHz) it is necessary to switch on terminating
resistances. For this purpose the AP17 motherboard has a triple DIP switch S2, which must be switched to the
ON position.

AP17

ON

3
2
1
Switch S2

Component layout AP17

MGCplus with AB22A/AB32

Connecting Outputs and remotes

B-111

AP02

Relay contacts
Another possible option is to use RM001 relay modules in conjunction with the AP02 connection board (with or
without front panel). Depending how the relay modules are fitted to this connection board, they are available to
relay contacts Limit1/2 or Limit3/4. These signals are carried on 37-pin female connector Bu3 (see Table 9.2).

MGCplus with AB22A/AB32

B-112

Connecting Outputs and remotes

Function

PIN

20

37

19

Bu 3

Analogue

Digital

29

+10 V excitation pot. LV

20

10 V excitation pot. LV

36

HCMOS Limit1

HCMOS Limit2

17

HCMOS Limit3

10

HCMOS Limit4

37

Central contact

Normally open contact

19

Normally closed contact

Central contact

18

Normally open contact

Explanations about the table:

Normally closed contact

Control signal for relay modules


1 to 4: HCMOS Limit1...4

16

Central contact

11

Normally open contact

15

Normally closed contact

12

Central contact

14

Normally open contact

13

Normally closed contact

33

no function

32

no function

31

no function

30

no function

26

no function

25

no function

24

no function

23

no function

Table 9.2 Bu3

MGCplus with AB22A/AB32

>5k

Limit1
RM001
(BU404)
Limit2

Limit3

Limit4

RM001
(BU403)

Connecting Outputs and remotes

B-113

AP07/1

If you wish to take measurements with torque transducers in the T3..FN/FNA and T10FKF1 series, you have
AP07/1 connection board available. The AP07/1 has only one female connector for torque.
Outputs torque, rotation speed, performance (scaled)
The pin assignment for female connectors MD, N and P (scaled) is shown in Table 9.3.

MGCplus with AB22A/AB32

B-114

Connecting Outputs and remotes

Function (MD, N, P scaled)

PIN

13

14

25

Female connector
MD, N, P scaled

Digital

Remote 1

Remote 2

Remote 3

Remote 4

Remote 5

Remote 6

Remote 7

Remote 8

10

Limit switch Limit1, normally open contact

11

Vo1=  10 V; Io1= 20 mA/+4...+20 mA

12

Voltage output Vo2 = 10 V; Ro>5 k

13

Voltage output Vo1 = 10 V; Ro>5 k

14

Limit switch Limit1, normally closed contact

15

Limit switch Limit1, central contact

17

Limit switch 1; status

18

Limit switch 2; status

19

Limit switch 3; status

20

Limit switch 4; status

21

Warning

22

Limit switch Limit2, normally closed contact

23

Limit switch Limit2, normally open contact

24

Limit switch Limit2, central contact

25

Zero operating voltage, analogue

Table 9.3 Female connector MD, N, P

MGCplus with AB22A/AB32

HCMOS 5 V logic

B-115

Connecting Outputs and remotes

The outputs torque, rotation speed and scaled performance can only be fitted with one final stage module each.
The analogue output signal is carried on pin 11 if the final stage module is fitted. Sliding switches and DIP switches
are used to make the choice between voltage output and current output. The switch positions are described in
chapter 9.3.2. The relay contacts for limit switches Limit1 and Limit2 are available on pins 10, 14, 15 or 22, 23, 24
if the relay module is fitted. There is only provision for fitting with one relay module.
Output multiplier
The pin assignment for female connector P (unscaled) is shown in the table below. The analogue output signal is
carried on pin 11 if the final stage module is fitted. There is only provision for this option.
PIN

Function (P unscaled)

110,12,1421

no function

11

Vo1 = 10 V; Io1 =  20 mA/+4...+20 mA

13

Voltage output Vo1 = 10 V; Ro>5 k

MGCplus with AB22A/AB32

B-116

Connecting Outputs and remotes

AP13i

Input assignments
(Pin-assignments for remote contact 1):
PLC

Output
Ground

(1)

(14)

External

AP13i

Remote contact
Associated ground

HBM

AP13i connection board makes remote contacts and limit switch


outputs, as well as the 24 V-level warning output, available for direct
connection to I/Os on programmable logic controllers.
Control I/Os are potential-segregated by optical coupler and arranged
in a number of groups, each with its own grounding system. These
groups are identified by shading in the AP13i connection diagram.
Functions of remote contacts shown between brackets refer to the
factory preset. You are free to allocate these functions to whichever
remote contacts you please.
In the case of the AP13i, the only available option is an EM001 final
stage module.

Output assignments
(Pin-assignments for output of LIV1):

CAUTION
Input
Ground

Power
supply

24V
Output of LIV

Ground

24V
0V

External

MGCplus with AB22A/AB32

HBM

AP13i connection boards are specially adapted for ML30B or


ML50B/55B amplifiers. Please do not interchange these amplifier
types.

B-117

Connecting Outputs and remotes

Pin assignment for the AP13i:


1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25

Remote contact 1
Remote contact 2
Ground (Remote contacts 3/4)
Remote contact 5
Remote contact 6
Ground (Remote contacts 7/8)
24V (Limit switch 1/2)
Ground (Limit switch 1/2)
24V (Limit switch 3/4, warning)
Ground (Limit switch 3/4, warning)
Current output Io1
Voltage output Vo2
Voltage output Vo1
Ground (Remote contacts 1/2)
Remote contact 3
Remote contact 4
Ground (Remote contacts 5/6)
Remote contact 7
Remote contact 8
Output of LIV1
Output of LIV2
Output of LIV3
Output of LIV4
Warning
Analogue earth

1
14

25

13

Bu 2

MGCplus with AB22A/AB32

B-118

Connecting Outputs and remotes

Remote contacts:
On the remote contacts the logic in relation to HCMOS levels is reversed in the case of the other connection
boards.
Function

Level 0 V

Level 24 V

ACAL

Autocal ON

Autocal OFF

TARE

taring starts on transition 0 V 24 V

CPV1/2

Peak value 1/2 is stored

Peak value 1/2 is cleared from current value

HLD1/2

Peak value stores 1/2 not frozen

Contents of peak value stores 1/2 frozen

ZERO

Current measuring signal is set to zero on transition 0 V 24 V

REMT

Remote control contacts inactive

SHNT

Shunt off

Shunt on

PRNT

When printing is enabled the channel is


taken into account

When printing is enabled the channel is not


taken into account

CAL

Remote control contacts active

Input is switched to internal calibration source

ZERO

Input is switched to zero signal

INV

Polarity is switched over (ML60B only)

PSEL1
PSEL2
PSEL3
PSEL4
REMT

Remote control contacts inactive

Remote control contacts active

Remote control outputs:


Function

Level 0 V

Level 24 V

Limit switches

Limit switches OFF

Limit switches ON

Warning

Device not ready or error (e.g. overflow)

No error

MGCplus with AB22A/AB32

B-119

Connecting Outputs and remotes

AP77

Profibus

The pin assignment of the 9-pin female D-Sub connector conforms to


the Profibus standard.

Pin
6

Function

RS485B

RS485RTS

GND

VCC

RS485A

GND

You can find more information in the Operating Manual MGCplus


Profibus Interface.

MGCplus with AB22A/AB32

B-120

Connecting Outputs and remotes

9.3.2

Installing the EM001 final stage module

Output stage
module EM001

The EM001 final stage module can only be used with connection
boards without transducer recognition.
For correct positioning on the connection boards mother board the
EM001 final stage module has been marked with the numeral 1 on the
bottom left corner and a triangle on the left side. These symbols have
also been printed onto the mother board.
After having inserted the final stage module, you have to select the
switch and bridge positions according to the desired output signal (see
tables).

Mother board

MGCplus with AB22A/AB32

B-121

Connecting Outputs and remotes

AP07/1

The AP07/1 has slots for one EM001 final stage module and one
RM001 relay module.
Output stage module
EM001

The chart shows the arrangement on the motherboard. The final stage
module is assigned to a sliding switch and a DIP switch. The switch
position necessary for the output signal you require is shown in the
following table.

Relay module RM001*)


Output signal

DIP switches

1
10 V

2
*)

Switch

Output P has no slot for RM001


1
20 mA

1
+4...20 mA

MGCplus with AB22A/AB32

B-122

Connecting Outputs and remotes

AP08/14/17/18

These connection boards are all equipped with a slot for an EM001.
2
EM001

The accompanying chart shows the motherboard layout for the


AP08/17/18.

The accompanying chart shows the motherboard layout for the


AP14.

NOTE
1
EM001
2

MGCplus with AB22A/AB32

Pay careful attention to the name (numbering) on the switch.


The deciding factor for the switch position in Table 9.4 is the numbering
on the switch and not its location.

B-123

Connecting Outputs and remotes

This table shows the switch position necessary for the output signal you require.

Output signal

Switch

DIP switches

1
10 V

1
20 mA

1
+4...20 mA

Table 9.4: AP08/14/17/18

MGCplus with AB22A/AB32

B-124

Connecting Outputs and remotes

AP09

AP09 connection board can have two slots for final stage modules of
the EM001 type.
EM001

slot

EM001

slot

for

for

If these connection boards are ordered without final stage modules,


they are supplied without slots.

The accompanying chart shows the arrangement on the motherboards.


Each final stage module is assigned to a sliding switch and a DIP
switch. The switch position necessary for the output signal you require
is shown in the following table.

for

2
Output signal

Switch

for

1
1

10 V

1
20 mA

1
+4...20 mA

MGCplus with AB22A/AB32

DIP switches

C-1

Commissioning

MGCplus with AB22A /AB32

C-2

MGCplus with AB22A /AB32

Commissioning Switching on

C-3

Commissioning

This chapter shows you the necessary steps to take in order to make your measurement chain (amplifier system
and transducer) ready for use.
You will then be in a position to carry out a function test of all components. The various steps are deliberately explained in very general terms, without going into detail about specific transducers or amplifier plug-in modules.
However, it is very easy to apply the description to your own measurement chain. In some instances especially to
do with connecting transducers reference will be made to later chapters. We also warn about certain errors which
can typically occur during commissioning.
After initial commissioning and adapting the amplifier plug-in module to your transducer, you are in a position to get
to know the other functions and facilities of the MGCplus amplifier system.

Unpack the MGCplus.


Check that the MGCplus is undamaged.
Is the delivery complete?
Compare the contents of packages with the accompanying documentation list. Is the documentation complete?

MGCplus with AB22A /AB32

C-4

1.1

Commissioning Switching on

Devices in the desktop housing and rack frame

If you have not yet received your complete amplifier system, you should take note of the following points when
putting the system together:
The amplifier plug-in units are plugged in at the front panel and the associated connection boards are plugged
in at the back.
It is important to ensure correct allocation during this step:
If using wide connection boards (8 divisions), you must plug these into slots 1, 3, 5 etc. Slots 2, 4, 6 etc. on the
front panel must be left free or with fitted blank plates.
On safety grounds, all unused slots (amplifiers or connection boards) must be covered over with blank plates.

Check that all amplifiers and connection boards are firmly plugged in.
Connect the device to the mains supply with the mains cable provided.
Connect your transducer to the female connector provided on the connection board (reference BU01). If you
use a cable you have made up yourself, please adhere to the pin assignment for your transducer as shown in
chapter B.

Please note the safety instructions on page A-3.

MGCplus with AB22A /AB32

C-5

Commissioning Switching on

Switch the device on with the POWER button on the front panel of
the device (in the case of the MGCCompact 2-channel housing,
there is a toggle switch on the back of the device).
When the AB22A/AB32 is initialized (at which time all LEDs light up
for a moment) it makes a note of the components that are present.

MGCplus Start-up

Switching on

If no transducer is connected, an overflow is displayed.


The opening display is followed in the standard version by a value display of the 1 value type (factory setting). Pressing the shift key
takes you to the set-up mode, in which you can configure the system,
the display, the amplifier and the additional functions.

MGC Compact
Back of the device NP05:

Switching on

MGCplus with AB22A /AB32

C-6

Commissioning Switching on

We recommend that you set up the language first if you require a language other than German.

System

Display

Password
Save/Recall
Data acquisition
Interface
Print
Language
Time

LANGUAGE
Language: Deutsch

Deutsch
English
Francais

MGCplus with AB22A /AB32

Amplifier

Options

D-1

Functions and symbols on the AB22A/AB32

MGCplus with AB22A /AB32

D-2

MGCplus with AB22A / AB32

D-3

Functions and symbols on the AB22A / AB32 Control elements

Control elements

1.1

AB22A control elements

All settings on your device are carried out with the keys on the AB22A/AB32 display and control panel. Using the
shift key (SET) you can select the Measure or Set-up operating modes.

Function keys F1...F4


Effective in measurement
mode and set-up mode
Delete key
Clears the last entries to input
fields
Help key
Activates online help texts for
certain functions
Cancel (Escape) key
Resets last entry in menus
and selection fields; closes
help texts
Alphanumeric
keypad
For entering numbers, letters
or special characters into the
Power switch
edit fields

Display

Channel selection keys


Selecting the active channel
Shift key
Switches between measuring mode
and set-up mode.

Cursor keys
Measuring mode:
Cursor control
Set-up mode:
Moving through the menu

Confirmation key
Activates the settings that have
been entered

MGCplus with AB22A /AB32

D-4

Functions and symbols on the AB22A / AB32 Control elements

1.2

AB32 control elements

Display
Channel selection keys
Selecting the active channel

Power switch

Help key
Activates online help for
the active functions.

Function keys
Effective in measurement
mode and set-up mode;
freely assignable for
measuring mode

Shift key
Switches between
measuring mode
and set-up mode.

Delete key
Clears the entire
entry in edit fields

Confirmation key
Activates the settings that have
been entered

Alphanumeric
keypad
For entering numbers,
letters or special
characters into the edit
fields in the display

Cursor keys
Measuring
mode:

Set-up mode:

MGCplus with AB22A / AB32

Select signal (Gross, Net,


Peak values)
Selecting display mode
(one or multi-channel)
Moving through the
selection and set-up
menus

Cancel (Escape) key


Resets the last entry in menus or
selection fields and closes help texts.

D-5

Functions and symbols on the AB22A / AB32 Display

Display

2.1

The first display

MGCplus Start-up

When the power is switched on, a progressively moving horizontal bar


is displayed to indicate that the device is initialising.
The opening display is followed in the standard version by a value
display of the 1 value type (factory setting). Pressing the shift key
takes you to the set-up mode, in which you can configure the system,
the display, the amplifier and the additional functions. We recommend
that you set up the language first if you require a language other than
German.

MGCplus with AB22A / AB32

D-6

2.2

Functions and symbols on the AB22A / AB32 Display

Display in measuring mode

Display for 1 value type


The chapter called Display deals fully with setting up the various screen types. The following section gives you an
overview of the factory preset display types.

Channel name
(freely definable)

Output signal
Gross
Net
Peak values
Limit switches

Gross

Channel

Status line
Function keys
(in this example, in measuring
mode, 1st level)

MGCplus with AB22A / AB32

Status
limit switch

Measure

Measure
Measurement value

Unit

Number of the
selected channel
(maximum 16 or
16.8 in the case
of multi-channel
modules)

D-7

Functions and symbols on the AB22A / AB32 Display

Display with 3 values type

Gross
Gross

Use

to go to the next type

Gross
Measure
Gross

Gross

Gross

Gross

Gross

Gross

Display for 6 values type


Use

to go to the next type

Measure
1ML55B

Gross

Display for YT-Diagram type


Use

to go to the next type

Measure
1ML55B

1ML55B

Gross

Gross

Display for XY-Diagram type


Use

to go to the next type

Measure

Limit switches
1Limit1
1Limit2
1Limit3
1Limit4

Display for Status limit switch type

LIVOn
LIVOff
LIVOn
LIVOff

Use

to go to the next type

Measure
DATA ACQUISITION

SAMPLERATE: 50Hz
PERIODS: 100

TIME: 00: 00: 00

Use

1
4.0S

to go to the next type

16.0S

FILE NAME: MGCP0000.MEA

Get DAQ1

Display for Data acquisition type

120 MB FREE

Acal

MGCplus with AB22A / AB32

D-8

Functions and symbols on the AB22A / AB32 Display

Symbols in the display


The status line tells you about the status of a measuring device at that instant:

Gross

Channel

Measure

Status line

Measure
Measure,
Zero,
Calibrate

Acal

Amplifier input status


Status display of parameter set memory
Numbers 1...8 Number of the current parameter set
S

Factory setting

User-defined set-up; displayed when a parameter set has been modified

/

Read next/previous parameter set

Acal

Automatic calibration on (function Acal)

Computer interface is active


Data transmission over link

MGCplus with AB22A / AB32

Functions and symbols on the AB22A / AB32 Display

D-9

Status of limit switches. If the On level that has been set for a limit switch is exceeded, the number
of the switch concerned is underlined in black in the display.
Example: On level of limit switch 1 is exceeded
Local

Remote off

Remote

Remote on

Channel

Channel number of a one-channel module


1

Channel
3.2

Channel number of a multi-channel module

Number of the sub-channel


Slot number in the system enclosure

MGCplus with AB22A / AB32

D-10

2.3

Functions and symbols on the AB22A / AB32 Display

Messages on the AB22A/AB32

The following messages may be displayed on devices fitted with a CP42 communications processor:
Message in the display

Cause

Remedy

CP42 hard disk full!

The capacity of the PCMCIA hard disk has been


exceeded.

Install a new hard disk or delete data.

Error configuring channels x, y, z!

a) The measuring amplifier types x, y,


z do not agree with the types in the
configuration file (modules
changed).

Check the equipment of the MGCplus device.

b) There is no amplifier plug-in module


present.
The following channels have been
configured: x, y, z

Information about a successful configuration of


channels x, y, z

Wrong hard disk!

The PCMCIA hard disk contains a file (Ident.txt)


in which the Serial No. of a CP42 is stored. This
Serial No. does not match the Serial No. of the
existing CP42.

Check the assignment of the CP42 hard disk, and


if necessary delete file Ident.txt (see also
Operating Manual MGCplus Assistant; CP42
serial number).

Overflow

The measuring range has been exceeded


(Gross, Net or both).

a) Check the values in the zero buffer


and/or tare buffer.

(In status mode the red


ERROR/WARN. LED lights up on
the front panel of the amplifier plug-in
module).
Calibration error
(In status mode the red
ERROR/WARN. LED lights up on
the front panel of the amplifier plug-in
module).

b) Carry out taring or a zero balance.


c) Increase the measuring range.
a) No feedback circuits connected and
Autocal has been triggered.

a) Check the transducer connection,


then trigger autocalibration.

b) Connection board has been


changed.

b) Carry out a set-up.

c) RAM/EEPROM error

d) Check the transducer settings


(transducer type, excitation voltage,
output characteristics).

d) Calibration curve not in order

c) Carry out a set-up.

(In status mode, the red ERROR/WARN. LED on the front panel of the amplifier module lights up)

MGCplus with AB22A / AB32

D-11

Functions and symbols on the AB22A / AB32 Set-up mode

AB22A/AB32 in set-up mode

The set-ups for the MGCplus unit are subdivided into groups according to their function. Pressing the shift key
takes you to the set-up dialogue. Ihe selection bar and the number of the channel, the settings will have an effect
on, is displayed.

Display in set-up mode

Settings for channel:


System

Display

System

Display

System-specific
settings that in most
cases are only
carried out during the
initial start-up or for a
new measurement
task.

User-defined display
settings such as the
required method of
representing values,
function key
assignment, or the
specification of
channel names.

3.2 ...

Amplifier

Options

Amplifier

Options

Selection bar

Amplifier set-ups for


Additional set-ups for
each channel, taking each individual
into account such
amplifier.
things as transducer
type, amplifier plug-in
module or
conditioning.

MGCplus with AB22A / AB32

D-12

Functions and symbols on the AB22A / AB32 Set-up mode

Switch to the set-up dialogue by pressing the shift key

. The lower part of the display is a selection bar showing

the topics to which the function keys immediately below them (F1...F4) are assigned (selection level 1).
You can set up your unit in various menus which you call up from the selection bar in the display. Depending on the
function, you can call up to 4 menu levels (selection and setup levels). In the first two levels you select topics; you
are in the selection levels. In the next levels you set up certain values or switch functions on/off. You are then in
the setup levels.
Example: Setting up a system password
Selection level 1
Selection level 2
Password
Password
System

Display

Selection bar

Save/Load
Data acquisition
Interface
Print
Language

System

Pop-up menu

Setup level 1

Password
new

User:

Display

Amp Password:
Access:

Set-up window

System

delete

Setup level 2

chang
Add
e user
set
User:

Display

Amp Password:
Access:

Set-up window

MGCplus with AB22A / AB32

Operator
OK

Cancel

D-13

Functions and symbols on the AB22A / AB32 Set-up mode

3.1

Press the shift key

Calling up menus

. At first only the selection bar is displayed. If you now press one of the function keys

F1...F4, the corresponding pull-up menu appears above the topic concerned (in this example System). Move the
bright bar through the pull-up menu with the cursor keys

to the required topic (in this case Language) and

press the confirmation key


. You are now in the setup level for the selected topic. The current setup window can
take you to other setup levels.

Selection level 1
Selection bar
Selection level 2
Pull-up menu

Setup level 1
Selection window

System

Display

Password
Save/Load
Data acquisition
Interface
Print
Language
Time

English

Amplifier

Options

Bright bar

Deutsch
English
English
Francais

MGCplus with AB22A / AB32

D-14

Functions and symbols on the AB22A / AB32 Set-up mode

3.2

Quitting menus

If you want to quit a menu level, press the shift key

Result: You return to measuring mode

or one of the function keys F1...F4

Result: You return to selection level 2

or (if present) the key symbol

Cancel

or

Result: You return to the previous menu level

OK

Measuring mode
1ML30B

Gross
Channel

Selection level 1

Selection level 2
System

Password
Displa Password
Save/Load
Data acquisition
Interface
Print
Language

System

Setup level 1
Password

Displa User:
Password:
Access:

System

....

new

....

change

....

set

Add user
Displa

delete

Setup level 2

User:

....

Password:

....

Access:

Operator
OK

Before quitting a menu widow and returning to measuring mode, you


are still able to save or clear the set-ups you have entered, or cancel
your intention to quit the dialogue window. A security prompt is therefore displayed alongside.

Save set-up?
Yes

No

Cancel

Cancel

In this case the factory preset is Yes. Confirm with

MGCplus with AB22A / AB32

D-15

Functions and symbols on the AB22A / AB32 Set-up mode

3.3

Channel selection in measuring mode

There are two ways in which you can select a channel in measuring mode:
1. By using the channel selection keys

2. By directly inputting the channel number using the alphanumeric keypad (recommended for multi-channel
modules).
Here are two examples of method 2:
Example 1: Selecting a channel on a one-channel module

Press the numeric key for the desired channel (for example 7)

The indicator then displays the channel text box showing the channel number requested:
Channel 7

Confirm with

Example 2: Selecting a sub-channel on a multi-channel module

Press the numeric key for the required slot (for example 3)

The indicator then displays the channel text box showing the slot number requested:
Channel 3

(If you then use

to confirm, the first sub-channel is automatically selected, which in this case is 3.1).

Type in a point and then the required sub-channel number:


Channel 3.2

Confirm with

.
MGCplus with AB22A / AB32

D-16

Functions and symbols on the AB22A / AB32 Set-up mode

3.4

Channel selection in set-up mode

In most of the set-up windows on the AB22A/AB32, the column header shows the name of the currently selected
set-up menu and the channel selected.
Channel text box
CHANNEL NAME

Channel

Channel name:

3.2

2ML55B

There are two ways in which you can select a channel in set-up mode:
1. By using the channel selection keys

(select the channels one after another).

2. By entering the channel number in the channel text box. You have the option to skip directly from one channel
to any other channel of your choice.

Press the cursor key

Type in the required channel number (for instance 3.2 in the case of a multi-channel module).

Confirm with

MGCplus with AB22A / AB32

, to go to the channel text box in the column header.

D-17

Functions and symbols on the AB22A / AB32 Set-up mode

3.5

Saving the set-ups

All settings that you enter before the security prompt are temporarily stored in working memory (RAM) as soon as
. The data are permanently saved as soon as you quit set-up
you make an amendment and confirm it with
mode and confirm the security prompt with Yes.

Amplifier

Volatile memory (8h)


RAM

Factory
settings
EPROM

save
load
EEPROM

Permanent save
parameter set 1...8

MGCplus with AB22A / AB32

D-18

Functions and symbols on the AB22A / AB32 Set-up mode

3.6

Selection menus

Example:
Password
Save/Load
Data acquisition
Interface
Print
Language

You select topics from the first two selection levels. You do this in the first level (menu bar) by
pressing the corresponding function keys, and in the second level by selecting from pop-up
menus.

Select and confirm in selection fields (pull-up menu)

The selected field is shown in reverse highlight. Confirm the selection with

Time

MGCplus with AB22A / AB32

D-19

Functions and symbols on the AB22A / AB32 Set-up mode

3.7

Elements in the set-up window

At set-up level you enter the parameters via set-up windows. The set-up windows contain dialogue boxes, of
which there can be vier different types.
SETUP WINDOW

Activation fields
Dialogue boxes

Selection field
1V
Excitation 2.5V
5V

Abs
Gross
Net

Edit field
User:

Button
Cancel

Switching on or off in activation fields

Example:

Abs
Gross
Net

The selected field is shown in reverse highlight. Confirm the selection with
. A tick appears in the selected box
(activated). Pressing the confirmation key again cancels the activated status.
Channel-related activation fields
Example:

SELECT SIGNALS FOR PRINTOUT


OK

Cancel

All channels

All signals

Channel 1 2 3 4 5 6 7 8 9 10111213141516
Gross
Net
Store1
Store2
Store12
LIV-Status

MGCplus with AB22A / AB32

D-20

Functions and symbols on the AB22A / AB32 Set-up mode

Multi-channel modules are identified by two points below the channel number (channel 8 in the example). If you
to enable it, a new set-up window opens with

select the activation field for a multi-channel module and use


activation fields for the various sub-channels.
Example:

SELECT SIGNALS FOR PRINTOUT


OK

Cancel

All channels

All signals

1 2 3 4 5 6 7 ..
8 9 10111213141516
Channel
Gross
Net
Store1
Store2
Store12
LIV-Status

1 2 3 45 6 78

8.

All
OK

Cancel

Opening and selecting from selection fields

Example:

Excitation:

5V

Excitation:

1V
2.5V
5V

The selected field is shown in reverse highlight. When you press the confirmation key
to select your set-up and confirm with
Use the cursor keys
such fields are identified with a downward pointing arrow .

the selection field opens.

. In the documentation (but not in the display)

NOTE
Doubleclick

to edit the Unit selection field in the Transducer setup window. Then, you can enter

up to four characters (e.g. min1, with 1 representing an individual character assigned to the button

MGCplus with AB22A / AB32

).

D-21

Functions and symbols on the AB22A / AB32 Set-up mode

Edit fields

You may input numbers or letters in the edit fields. In certain edit fields you can only enter numbers (e.g. Zero
value), since it would serve no purpose to enter letters in such cases.
Example:

a) Edit field without contents

User:

The selected field is shown in reverse highlight. Confirm your input with
Example:

b) Edit field with contents

An edit field with contents can be

Zero point:

0.000

directly overwritten
partially edited
completely deleted with the clear key

Inputting numbers and letters


The keys in the alphanumeric input field are assigned seven ways: 1 number, 3 capital letters, 3 small letters. On
the first keystroke a number is displayed; further keystrokes produce letters.
When entering letters one after another that are located on the same key, you must press the cursor key

For example: entering the letters FE:

Step 1

Step 2

4x
The minus sign on the

Step 3

1x

3x

key can also be used as a separator in text boxes.

MGCplus with AB22A / AB32

D-22

Functions and symbols on the AB22A / AB32 Set-up mode

The special characters , W, m have been assigned to button

, in addition.

The superscript numerals 2, 3, and the special character @ have been assigned to button
The superscript numeral 1 has been assigned to button
w

, in addition.

, in addition.

Buttons

Example:

Cancel

or

change...

The selected field is shown in reverse highlight. Confirm with


. The button label is followed by three dots
(change...) and a new set-up window is displayed when confirmation is given.

MGCplus with AB22A / AB32

E-1

Measure

MGCplus with AB22A / AB32

E-2

MGCplus with AB22A / AB32

Measure General Notes

E-3

General notes

This chapter shows you the steps involved in taking a measurement with the MGCplus. At the beginning of each
section an example explains the details specific to each transducer with regard to adapting the amplifier plug-in
modules. Once the amplifier plug-in modules are matched you can proceed with taking measurements. For
information on other functions such as limit switches or peak value stores, see chapter F Additional functions.
Steps in setting up the measurement chain
1

Settings specific to the transducer: bridge type, excitation voltage, sensitivity, k-factor.

Settings for conditioning: zero balance, zero offset, tare value, filter settings.

Settings specific to the display: unit, decimal places, scale range, step.

Settings for analogue output: gross, net, peak value, output characteristics.
You can set up the zero point and measuring range in two ways, depending on the requirement:
a) by inputting the given transducer characteristics
b) by calibration with direct loading

MGCplus with AB22A / AB32

E-4

Measure Setting up the amplifier

Basic measurement channel set-up

The Amplifier pull-up menu is adapted to the signal flow of a measurement chain and is used to balance the
whole system.
Basic unit
(e.g. mV/V)

Transducer

Analogue output
Amplifier

(V)

Display

(User-specific unit
e.g. kg)

The following basic steps are needed to set up a measurement channel:


1. Select set-up mode with shift key

TRANSDUCER

CHANNEL1

Type
SG full bridge
5V
Excitation
kg
Unit:
mV/V
0.0000 ...
0.0000 ...
Zero pt:
2.0000 ...
Nom. val.: 50.0000 ...
measure...
K-Factor:

Adjust amplifier
0.0000 ...

2. If necessary: Set up the language you want for the menus in


the system set-up (see chapter H; System Language)
3. Settings specific to the transducer:
Bridge type and excitation voltage

measure

Unit
Characteristics (zero point and nominal value)
4. Adjust amplifier
Having carried out these steps you will have completed the most
essential settings and adjustments, and will be able to carry out
simple measurements. The following steps are optional.

MGCplus with AB22A / AB32

E-5

Measure Setting up the amplifier

CONDITIONING

CHANNEL1

0.0000 ... V
Zero reference:
>0<
0.0000 ... V
Zero offset:
>T<
0.0000 ... V
Tare:
Disable zeroing: 3
Disable taring: 3
Bessel V
Low pass 100
Hz
High pass Off

DISPLAY

CHANNEL1

kg
Unit
Decimal places 3 ...
Display range
from 50.000 kg
50.000 kg
to
Step
1

ANALOGUE OUTPUTS

CHANNEL1

Output Vo1: Gross


Output Vo2: Net
Output characteristics ppm
V
Point 1: 0.0000 ...
0.0000 ...
Point 2: 100.0000 ...
0.0000 ...

5. Settings for conditioning:


Zero balance (zero offset)
Tare
Filter

6. Setting up the display format


Unit
Decimal places
Display range
Step

7. Setting up analogue outputs


Gross/Net/Peak value
Output characteristics
8. Setting up additional functions (if necessary)
Limit switches, Peak values
Remote contacts, ...

MGCplus with AB22A / AB32

E-6

Measure Setting up the amplifier

2.1

Adaptation to the transducer

TRANSDUCER
Type
Excitation
Unit:
Zero pt.:
Nom.val.:

5V
kg

mV/V

0.0000 ...

0.0000 ...

50.0000 ...

2.0000 ...

Adjust amplifier
0.0000 ...

Type
Selection field for the transducer types which can be attached. The
selection depends on the type of amplifier and connection board.

SG full bridge

measure...
K-Factor:

CHANNEL1

measure

Excitation
Selection field for available excitation voltages (not available with all
amplifier types). The selection depends on the type of amplifier and
connection board. You will find more hints in later chapters.
Unit
Selection field for the physical unit. The basic unit mV/V cannot be
changed.
Zero pt.
Edit field for entering the zero point. The lefthand field refers to the
physical unit and the righthand field to the basic unit. By activating the
button labelled measure you can measure the current zero signal. The
value in mV/V is then displayed in the righthand edit field.
Nom.val.
Edit fields for the nominal value. The lefthand field refers to the physical
unit and the righthand field to the basic unit (you can find this nominal
value on the identification plate for the transducer).
measure...

Button for opening the Two point calibration set-up window, in which
you can measure the characteristic points 1 and 2.
Adjust amplifier

Button for matching the amplifier to the inputs of zero point and nominal
value.

MGCplus with AB22A / AB32

E-7

Measure Setting up the amplifier

2.1.1

Extended functions of the ML38B

TRANSDUCER
Type
Excitation
Unit:
Zero pt.:
Nom. val.:

CHANNEL1

SG full bridge

Ex.Ftn...

5V
kg

mV/V

0.0000 ...

0.0000 ...

50.0000 ...

2.0000 ...

measure...

Nominal value
Enter the rated value. The value can be found in the table for linear interpolation comparison (in the calibration certificate); if this is not available, enter the value for the maximum calibration stage with the corresponding arithmetic mean in electric units.

measure

Adjust amplifier

NOTE

0.0000 ...

Kfactor:

These values used for the rated value must not be changed after
entering the coefficient of the polynomial curve!

Polynomial curve
Ex. Ftn...
Active
Standardized

Coeffizients
A0:
A1:
A2:
A3:

0.0000 ...
0.0000 ...
0.0000 ...
0.0000 ...

OK

C0:
C1:
C2:
C3:

0.0000 ...
0.0000 ...
0.0000 ...
0.0000 ...

Aktive
Press the confirm key to activate the curve (a checkmark will appear in
the activate field)

Cancel

Coefficients/Standardized
The cubic polynomial curve is used to correct the signal of the transducer (in mV/V). The measured values are thereby adapted to the actual curve of the transducers. To do this, enter the coefficients A0, A1,
A2 and A3 of the third order polynomial, which is described by the following equation:
YPh = A3Yel3 + A2Yel2 + A1Yel + A0
YPh: Display in physical units with polynomial curve
Yel: Measured value in electric units

The coefficient values can be found in the transducer calibration certificate.

MGCplus with AB22A / AB32

E-8

Measure Setting up the amplifier

The amplifier itself requires standardized coefficients (C0C3) for


value 1, the coefficients from the calibration certificate (A0A3) are automatically converted before being transferred to the amplifier (also in
the MGCplus assistant).
Conversion: C A 

Rated value electrical unit (right input field)


Rated value physical unit (left input field)

Example: Enter the coefficients from a Force DKD calibration certificate from HBM.
The following equivalencies apply:
DKD calibration certificate

Polynomial equation

A1

A2

A3

ATTENTION
During calibration, the measured values must be entered as the
electric unit (mV/V) without changing the read-out!

MGCplus with AB22A / AB32

E-9

Measure Setting up the amplifier

2.2

TEDS transducer

F-keys-level 1
1ML30B

Gross
Channel

measure

> 0 <

> T <

II

F-keys-level 2
Acal

TEDS

Unit

...

TEDS (Transducer Electronic Data Sheet) is the designation for an


electronic data sheet in the transducer. It is stored in an electronic module that is inseparably connected to the transducer. It can be located
in the transducer housing, in the inseparable cable or connector plug.
Many components in the MGCplus amplifier system are capable of reading the transducer information stored in the data sheet and to convert
it into amplifier settings so that measurements can be started immediately.
MGCplus supports TEDS-transducers that comply with the data protocol (One-Wire-Protocol) and data structure in the IEEE 1451.4 standard.
This means that the same cables can be used as for transducers that
do not have TEDS.
Some MGCplus system connection plates, e.g. AP01i, also offer the
possibility of inputting TEDS data signals to two separate pins (ground
and TEDs data signal).
Loading TEDS data into the amplifier
In the default setting, the TEDS key F2 is in level 2 of the function keys.
1. Press it in measuring mode
2. Press the TEDS-key

The actual amplifier will then be parameterised with the transducer settings from the TEDS chip if it supports this functionality.

MGCplus with AB22A / AB32

E-10

Measure Setting up the amplifier

TEDS supports the following combinations of single-channel amplifiers with corresponding connection plates as per
IEEE 1451.4. All single-channel amplifier MLxxB are suitable for TEDS, however they must be equipped with up to
date firmware. This firmware and the corresponding firmware download program can be downloaded free of charge
from the HBM homepage (www.hbm.com/support/downloads).
ML01B

ML10B

TEDS

ML50B

ML55B
ML55BS6

ML60B

nR

1,4,5,B1

1,4,5,B1

AP03i

ML38B

1,4,5,B1

TEDS

ML35B

nR
1,4,5,B1

AP01i

ML30B

T3...T10

AP07/1

min1
T4WA

AP08
AP09
TEDS

min1
T4WA

nR

1,4,5,B1

1,4,5,B1

AP13i

1,4,5,B1

TEDS

1,4,5,B1

AP12

T3...T10

nR

T3...T10

1,4,5,B1

1,4,5,B1

AP11i

nR

AP14
TEDS

AP17
AP18i
MGCplus with AB22A / AB32

T10F(S)

E-11

Measure Setting up the amplifier

The following amplifier connection plate combinations are TEDS capable for multi-channel amplifiers.
ML801B

ML455

ML460

TEDS

AP401
AP402i (1)

TEDS

TEDS

TEDS

AP409
AP418i

AP455i
AP455iS6

AP460i
AP801
AP801S6

TEDS

TEDS TEDS

AP809
AP810i (2)
AP814Bi

AP815i

TEDS

AP835
AP836i (2)
(1)
(2)

available from December 2005


available from October 2005
MGCplus with AB22A / AB32

E-12

Measure Setting up the amplifier

Legends
Voltage

SG (resistance)-half bridge

Current

SG (resistance)-quarter bridge

Passive piezo-electric transducer

Inductive half bridge

Current-fed piezo-electric
transducer

Pulse counter/frequency

T3...T10

Torque/speed
T3..., T10

Potentiometer
200 5000

1,4,5,B1

Torque
T1, T4, T5, TB1

LVDT

Inductive full bridge


nR

SG (resistance)-full bridge

Piezoresistive transducer

MGCplus with AB22A / AB32

Thermo-resistors
PT100, PT 1000
Thermocouples

min1

T4WA

T4WA speed

E-13

Measure Setting up the amplifier

2.3

CONDITIONING

Signal conditioning

CHANNEL1

0.0000 ... V
Zero reference:
>0<
0.0000 ... V
Zero offset:
>T<
0.0000 ... V
Tare:
3
Disable zeroing:
Disable taring: 3
Bessel V
Low pass 100
Hz
High pass Off

Zero reference
Amount by which the relative zero point is offset in relation to the
absolute zero.
Example: A displacement transducer (nominal displacement 20 mm)
is intended to be measured from an engine seating and is fastened at a
height of 1 m above. The display is intended to show the displacement
as an absolute value.
Displacement transducer

20mm
CONDITIONING

Relative zero point

CHANNEL1

1000.00 mm
Zero reference:
0.0000 ... mm >0<
Zero offset:
0.0000 ... mm >T<
Tare:
Disable zeroing: 3
Disable taring: 3
Bessel V
Low pass 100
Hz
High pass Off

Zero reference=1000mm

Absolute zero point

Engine seating

Zero offset
By activating the button labelled >0< you trigger zero balancing. If
the value of the zero offset is known, you can input it directly in the edit
field. Zero balancing affects how the gross value is displayed.
Tare
By activating the button labelled >T< you trigger taring. If the tare
value is known, you can input it directly in the edit field. Taring affects
how the gross value is displayed.

MGCplus with AB22A / AB32

E-14

Measure Setting up the amplifier

Disable zero/Disable tare


You can disable Zero Balance and/or Taring. Disabling applies to all
triggering mechanisms (F-keys, remote contacts, software).
The following brief example will make clear the difference between zero
balancing and taring:
Container
Platform

Load cells

Action
Platform
55 kg

>0<

Container
6 kg
Component 1
7 kg
Component 2
8 kg

MGCplus with AB22A / AB32

>0<

>T<

A platform which stands on three load cells is to be used for weighing a


container. Two different components are tipped into the container one
after the other, and the weight of each is to be displayed (net).
The table shows the status before and after zero balancing and taring
are triggered.

Set-up window

Display

Zero offset

Tare

55 kg

61 kg
61 kg
61 kg

0
7 kg
15 kg

Gross

Net

before 55 kg

before 55 kg

after 0 kg

after 0 kg

before 6 kg

before 6 kg

after 0 kg

after 0 kg

before 7 kg

before 7 kg

after 7 kg

after 0 kg

15 kg (total contents of
container)

8 kg (component 2
only)

E-15

Measure Setting up the amplifier

Impulse response

Low pass
Low-pass filters are used to suppress unwanted high-frequency
interference above a defined cut-off frequency.
Amplitude response, phase delay and impulse response are dependent
on the filter characteristics. You can choose between the Butterworth
characteristic and the Bessel characteristic.

Impulse response

The Butterworth characteristic exhibits a linear amplitude response


which then falls away steeply above the cut-off frequency. There is an
overshoot of approx. 10 %.
The Bessel characteristic exhibits an impulse response with very little
(<1 %) or no overshooting. The amplitude response falls away less
steeply.
High pass
High-pass filters are used to suppress unwanted low-frequency
interference below a defined cut-off frequency. You can use high-pass
to suppress slow fluctuations such as those due to the influence of
temperature and drift over time.
The high-pass filter has no function when connected to resistance
thermometers and thermocouples.

NOTE
In order for high-pass to function, the low-pass setting must not
fall below the following limits:
Bessel:

5 Hz

Butterworth:

10 Hz

MGCplus with AB22A / AB32

E-16

Measure Setting up the amplifier

2.4

Display

Unit3

System

Display

DISPLAY

Amplifier

Options

CHANNEL1

V
3 Abs
Unit
Decimal places 3 ...
Display range
from 10.000 V
10.000 V
to
Step
100

Selecting the required unit for the display. You may choose between the
basic unit (mV/V), the user-specific unit (e.g. kg) and the unit for
analogue output (V). The associated measured value is then displayed.
You can achieve the same effect with the function Unit (factory
settings: F3/level 2; see also page G-23).
Abs
If the absolute display is activated ( 3 ), the display shows the signal at
the amplifier input without any conditioning (such as zero offset or
taring).
Decimal places
Number of decimal places.
Display range
Display range in the selected unit (automatically displayed).
Step
The step defines the size of the display increments. It refers to the last
decimal place in the nominal value.

Example: Nominal value 20 kg


Decimal places 1 (20.0 kg)
Step 1 means the display is in steps of 100 g
Step 5 means the display is in steps of 500 g
Decimal places 3 (20.000 kg)
Step 1 means the display is in steps of 1 g
Step 5 means the display is in steps of 5 g

MGCplus with AB22A / AB32

E-17

Measure Setting up the amplifier

2.5

Analogue outputs (one-channel modules only)

Output VO1
Select signal for analogue output 1 (BNC female connector front panel).
System

Display

Amplifier

Options

Output VO2
Select signal for analogue output 2 (female connector Bu2 back of the
device).

Transducer
Conditioning
Display
Analogue outputs
Switch

ANALOGUE OUTPUTS

CHANNEL1

Output Vo1: Gross


Output Vo2: Net
Output characteristics ppm
V
Point 1: 0.0000 ...
0.0000 ...
Point 2: 100.0000 ...
0.0000 ...

Output characteristics
The edit fields for calibration points 1 and 2 are automatically updated
as soon as you go to the Transducer input window and activate the
. However, you can also change the
button labelled Adjust amplifier
characteristics of the analogue output by direct input.

User-specific unit
(e.g. ppm)

Pnt.2
Gross
Net
Store1
Store2
OFF

Pnt.1
Analogue output (V)

MGCplus with AB22A / AB32

E-18

Measure Setting up the amplifier

Example: Minimum set-up for first measurement

System

Display

Amplifier

The transducer is a load cell with the following nominal data:

Options

Nominal load 50 kg
Nominal sensitivity 2 mV/V
Transducer
Conditioning
Display
Analogue outputs
Switch

1. Select the channel you want using the channel selection keys
by directly inputting the channel you want (see D-15).
to return to set-up mode.

2. Use the shift key

, use the cursor keys

3. Press the function key


TRANSDUCER
Type
Excitation
Unit:
Zero pt.:
Nom.val.:

K-Factor:

Transducer and confirm with

5V
kg

4. Use the cursor keys

mV/V

0.0000 ...

0.0000 ...

50.0000 ...

2.0000 ...

to select

CHANNEL1

SG full bridge

measure...

or

Adjust amplifier
0.0000 ...

measure

confirm with

to select Strain gage full bridge and

5. Use
to go to the Excitation selection field, press
select 5V.
6. Confirm with
7. Use

to go to the Unit selection field. Press

kg and confirm with


8. Use

. Select the unit

to go to the Zero pt. edit field and enter the value 0 in

the lefthand edit field. Confirm with

MGCplus with AB22A / AB32

and

E-19

Measure Setting up the amplifier

9. Unload the load cell.

System

Display

Amplifier

10. Use
to go to the button labelled measure... and confirm with
(the measured value is displayed in the righthand edit field of Zero
pt.)

Options

11. Use

Confirm with

Transducer
Conditioning
Display
Analogue outputs
Switch

12. Use

to go to the righthand edit field (column mV/V) and enter

the value 2. Confirm with


13. Use
with

TRANSDUCER

to go to the Nom.val. edit field and enter the value 50.

to select the button labelled

Adjust amplifier

CHANNEL1

14. To return to measuring mode, press the shift key


Type
Excitation
Unit:
Zero pt.:
Nom.val.:

and confirm

SG full bridge

the security prompt with

5V
kg

0.0000 ...

50.0000 ...

2.0000 ...

mV/V

0.0000 ...

measure...
K-Factor:

and confirm

measure

Adjust amplifier
0.0000 ...

MGCplus with AB22A / AB32

E-20

Measure Adaptation to the transducer

Adaptation to the transducer

3.1

SG transducer

SG transducers (HBM load cells, force transducers) are passive transducers with the following characteristics:

they must be fed with an excitation voltage (carrier frequency or DC voltage)


they are SG full bridges

The transducer has the following characteristic data:


Nominal load (e.g. 20kg)
Nominal sensitivity (e.g. 2mV/V)
These values must be taken into account during adaptation to the amplifier.
The standard set-up for excitation voltage UB in the case of an SG full bridge is 5V. If higher measuring ranges are
required or if several transducers are connected in parallel, a lower excitation voltage must me selected. The individual values depend on the type of plug-in module used.
Amplifier

Limits of the measuring range (mV/V)


UB=5 V

UB=2.5 V

UB=1 V

ML10B

0.2...6.12

0.4...12.24

1.0...30.6

ML30B

0.1...3.06

0.2...6.12

0.5...15.3

ML38B

0.2...5.1

0.4...10.2

ML55B

0.1...3.06

0.2...6.12

0.5...15.3

With these measuring range limits, a voltage of 1 V to 10 V can be generated at the analogue output, depending on
the setting.

NOTE
The specified full scale values are peak values and cannot be affected by adjusting the analogue output
settings.

MGCplus with AB22A / AB32

E-21

Measure Adaptation to the transducer

3.1.1 Direct input of transducer characteristics

The following example explains the settings:


Load cell with the following characteristics: nominal load 20 kg,
excitation voltage 5 V, nominal sensitivity 2 mV/V
System

Display

Amplifier

Options

Transducer
Conditioning
Display
Analogue outputs
Switch

Measurement is to be to a maximum of 10 kg, i.e. the display range for


the amplifier is 10.00 kg (displayed to 2 decimal places). A value of
10 V is to be generated at the analogue output for a 10 kg load.
1. Select the channel you want using the channel selection keys
by directly inputting the channel you want (for example 3.2

Type
Excitation
Unit:
Zero pt.:
Nom.val.:

3. Press function key

SG full bridge
5V
kg

0.0000 ...

20.0000 ...

4. Select Transducer from the pull-up menu and confirm with

mV/V

0.0000 ...

measure...
K-Factor:

CHANNEL1

).

to return to set-up mode.

2. Use the shift key


TRANSDUCER

or

2.0000 ...

measure

5. Use

to select SG full bridge and confirm with

Adjust amplifier
0.0000 ...

to go to the Excitation selection field, press


6. Use
select 5V.
7. Confirm with
8. Use

to switch to the Unit selection field and press

the unit kg and confirm with


9. Use

and

. Select

to go to the Zero pt. edit field and enter the value 0 in

the lefthand edit field. Confirm with

MGCplus with AB22A / AB32

E-22

Measure Adaptation to the transducer

10. Unload the load cell.

System

Display

Amplifier

Options

11. Use
to go to the button labelled measure and confirm with
(the measured value is displayed in the righthand edit field of Zero
pt.)
12. Enter the value 20 in the lefthand Nom.val. edit field.

Transducer
Conditioning
Display
Analogue outputs
Switch

13. Enter the value 2 in the righthand Nom.val. edit field (below the
unit mV/V).
14. Use
with

to select the button labelled

Adjust amplifier

and confirm

. If you wish to make no further changes to the display

and output characteristics, you may continue with point 24. .


DISPLAY

CHANNEL1

kg
Unit
Decimal places 2 ...
Display range
from 20.000 kg
20.000 kg
to
Step
1

15. Use

to return to the pull-up menu.

16. Select Display from the pull-up menu and confirm with

17. Specify the required number of decimal places in the Decimal


places edit field and confirm with

18. Select the value 2 from the Step*) selection field and confirm with
.

NOTE
The step width refers to the last decimal place of the input range.
Example: Input 10.0 kg
Step 1 means the display is in steps of 100 g
Step 5 means the display is in steps of 500 g
Input 10.000 kg
Step 1 means the display is in steps of 1 g
Step 1 means the display is in steps of 5 g
MGCplus with AB22A / AB32

E-23

Measure Adaptation to the transducer

19. Use

to return to the pull-up menu.

20. Select Analogue outputs from the pull-up menu and confirm with
System

Display

Amplifier

Options

.
21. Select the required signal from the Output Vo1 selection field and

Transducer
Conditioning
Display
Analogue outputs
Switch

ANALOGUE OUTPUTS

CHANNEL1

Output Vo1: Gross


Output Vo2: Net
Output characteristics kg
V
Point 1: 0.0000 ...
0.0000 ...
Point 2: 10.0000 ...
10.0000 ...

confirm with

22. Select the required signal from the Output Vo2 selection field and
confirm with

23. Use
to go to the Output characteristics Point 2 edit field, and
enter the required value (left for the display, right for the analogue
output). Confirm with

24. To return to measuring mode, press the shift key


the security prompt with

and confirm

MGCplus with AB22A / AB32

E-24

Measure Adaptation to the transducer

3.1.2 Calibrating the characteristic curve of the transducer

By transferring the signals produced by the transducer when a


defined loading occurs.
System

Display

Amplifier

Options

Example:
A 4 kg calibration weight is used for calibrating a 10 kg load cell.

NOTE

Transducer
Conditioning
Display
Analogue outputs
Switch

If zero point and nominal value are not modified (for instance in
the case of recalibration), you may omit points 110.
1. Select the channel you want using the channel selection keys

TRANSDUCER
Type
Excitation
Unit:
Zero pt.:
Nom.val.:

by directly inputting the channel you want (for example 3.2

).

SG full bridge

to return to set-up mode.

2. Use the shift key

5V
kg

mV/V

0.0000 ...

0.0000 ...

10.0000 ...

2.0000 ...

measure...
K-Factor:

CHANNEL1

or

measure

3. Press

Adjust amplifier

4. Select Transducer from the pull-up menu and confirm with

0.0000 ...

5. Use

Two point calibration


kg

mV/V

1st pt.:

0.0000

0.0021

Measure

2nd pt.:

4.0000

0.8032

Measure

OK

Cancel

Shunt off

to select SG full bridge and confirm with

8. Use

and

to switch to the Unit selection field and press

the unit kg and confirm with

MGCplus with AB22A / AB32

6. Use
to go to the Excitation selection field, press
select 5 V.
7. Confirm with

. Select

E-25

Measure Adaptation to the transducer

9. Use

to go to the Zero pt. edit field and enter the value 0 in

the lefthand edit field. Confirm with


10. Use

to go to the Nom.val. edit field and enter the value 10 in

the lefthand edit field. Confirm with


11. Use
with

to select the button labelled

.
and confirm

Adjust amplifier

12. Use the cursor keys


and confirm with

to select the button labelled

measure...

13. Unload the transducer.


14. Enter the value 0 in the lefthand edit field of calibration
1st pt. and confirm with
15. Use cursor key

to select the button labelled

pt. line and confirm with


16. Use cursor key

.
Measure

in the 1st

to select the lefthand edit field from the 2nd pt.

line, enter the value 4 and confirm with

17. Load the transducer with the 4kg calibration weight.


18. Use cursor key

to select key symbol

Measure

from the 2nd pt.

line. If you now press


measurement starts, and the current
measured value is displayed in mV/V on the left alongside the
Measure button.

MGCplus with AB22A / AB32

E-26

Measure Adaptation to the transducer

19. Use cursor key


to select the OK button and confirm with
(the amplifier converts the nominal value to 10kg; the calibration
data for 4kg stays unchanged).
20. To return to measuring mode, press the shift key
the security prompt with

MGCplus with AB22A / AB32

and confirm

E-27

Measure Strain gages

3.2

Strain gages

The variable to which reference is to be made for assessment of the material loading is the mechanical stress to
which the material is exposed. A practical method for experimental determination of material stresses is based on
strain gages. A detailed description of the strain gage technique may be found in the book An Introduction to the
Technique of Measuring with Strain Gauges (Author: Karl Hoffmann, published by HBM Darmstadt).
The resistance of the SG is changed by straining. This change lies in the mW and mW range, which is why the
Wheatstone bridge is used for measuring with great accuracy.

e1

UA
k e
4
UB

e4

UB
UB = bridge excitation voltage
e2

e3

UA

UA = bridge output voltage


ML10B
ML30B
ML55B

UA
relative change of excitation voltage
UB
total strain
e = e1e2+e3e4
k = gage sensitivity (k-factor)

Fig.3.1:

Wheatstone bridge

MGCplus with AB22A / AB32

E-28

Measure Strain gages

With the MGCplus measurement system you can measure the strain of one strain gage or the total strain of several
strain gages. The possible bridge circuits and the necessary device configuration are combined in the following
table:
bridge type

Number of
active SGs

total strain

Connection board

Amplifier

Quarter bridge

AP14

ML10B, ML30B, ML55B

e = e1e2

AP01i, AP03i, AP11i,


AP13i, AP14

ML10B, ML55B

e
Half bridge

e1

ML30B (with AP14 only)

e2
4
Full bridge

1)

e1

e4

e2

e3

e = e1e2+e3e4

AP01i, AP03i, AP11i,


AP13i, AP14

ML10B, ML30B, ML55B,


ML38B1)

In connection with AP01i and AP03i

The measurement system always measures the total strain (e) of the individual strain gages in the Wheatstone
bridge. In practice individual strain gages are generally used for mechanical stress analysis.
Due to the temperature compensation, the larger measuring signal, better cable resistance compensation and in
some tension states the half bridge and the full bridge are used (e.g. for measuring on a bent rod).
The most important characteristic of an SG is the k-factor (strain sensitivity). The MGCplus measurement system
automatically switches over to strain measurement when a k-factor >0 is input. Scaling of the zero point and measuring range is carried out in mm/m. By changing the unit and input range, other physical variables (e.g. mechanical
stress in N/mm2) can be derived. If zero is entered as the k-factor the system switches over to mV/V.
Example:

A strain of up to 1000 mm/m is to be measured with 120 W single strain gages. The k-factor of the
SG is 2.05. The excitation voltage plays no part in this example. The setup for 2.5 V will be described.

MGCplus with AB22A / AB32

E-29

Measure Strain gages

3.2.1 Direct input of transducer characteristics

1. Select the channel you want using the channel selection keys
by directly inputting the channel you want (for example 3.2
System

Display

Amplifier

or
).

Options

2. Use the shift key


.

3. Press

Transducer
Conditioning
Display
Analogue outputs
Switch

to return to set-up mode.

4. Select Transducer from the pull-up menu and confirm with

5. Select Type in the pop-up menu.

TRANSDUCER
Type
Excitation
Unit:
Zero pt.:
Nom.val.:

SG1/4Bridge 120Ohm 4-wire

7. Use

2.5V
%

m/m

0.0000 ...

0.0000 ...

100.000 ...

1000.000 ...

measure...
K-Factor:

CHANNEL1

Adjust amplifier
2.0500 ...

6. From the type selection field, select SG-1/4-Bridge 120 Ohm


4-wire and from the excitation selection field select 2.5 V.
to select the K-Factor edit field and enter the value

2.05. Press the confirmation key

measure

Since the amplifier automatically changes the native unit from mV/V
into m/m once the k-factor is input, the physical unit plays no role
in this example. The menu window shown here is based on the
display using factory settings.
8. Use

to go to the righthand Zero pt. edit field and enter the

value 0. Confirm with


9. Use

to go to the righthand Nom.val. edit field and enter the

value 1000. Confirm with


10. Use
with

to select the button labelled

Adjust amplifier

and confirm

MGCplus with AB22A / AB32

E-30

Measure Strain gages

11. Press

12. Select Display from the pull-up menu and confirm with
System

Display

Amplifier

Options

13. Select m/m from the selection field Unit and confirm with
Transducer
Conditioning
Display
Analogue outputs
Switch

14. Use

to go to the Abs activation field and disable the absolute

display with the aid of

15. Specify the required number of decimal places in the Decimal


places edit field and confirm with

DISPLAY

CHANNEL1

m/m
Unit
Abs
Decimal places 1 ...
Display range
from 1000.000 m/m
1000.000 m/m
to
Step
1

16. Go to the Step*) selection field, choose the required step and
confirm with

NOTE
The step width refers to the last decimal place of the input range.
Example: Input 1000.0 m/m
Step 1 means the display is in steps of 100 nm/m
Step 5 means the display is in steps of 500 nm/m
Input 10.000 m/m
Step 1 means the display is in steps of 1 nm/m
Step 5 means the display is in steps of 5 nm/m
17. To return to measuring mode, press the shift key
the security prompt with

and confirm

18. Carry out a zero balance in no-load status (function key


factory settings).
MGCplus with AB22A / AB32

in

Measure Inductive transducers

3.3

E-31

Inductive transducers

Inductive transducers (HBM displacement transducers) are passive transducers with the following characteristics:

they must be fed with an excitation voltage (carrier frequency)


they are inductive half bridges

The transducer has the following characteristic data:


Nominal displacement (e.g. 20 mm)
Nominal sensitivity (e.g. 10 mV/V)
The standard set-up for the excitation voltage UB in the case of inductive transducers is 2.5V. If higher measuring
ranges are required or if several transducers are connected in parallel, a lower excitation voltage must me selected.
The individual values depend on the type of plug-in module used.
Amplifier

Limits of the measuring range (mV/V)


UB=5V

UB=2.5V

UB=1V

ML50B

6.0...183.6

15.0...459.0

ML51B

0.1...3.06

0.5...15.3

ML55B

1.5...45.9

3.0...91.8

7.5...229.5

With these measuring range limits, a voltage of 1 V to 10 V can be generated at the analogue output, depending on
the setting.

NOTE
The specified full scale values are peak values and cannot be affected by adjusting the analogue output
settings.

MGCplus with AB22A / AB32

Measure Inductive transducers

E-32

3.3.1 Direct input of transducer characteristics

The following example explains the settings for a displacement


transducer with the following characteristics:
System

Display

Amplifier

Options

Nominal displacement 20 mm, excitation voltage 2.5 V, nominal


value 10 mV/V. The display range from 15 mm shall correspond to an
output of 10 V.
1. Select the channel you want using the channel selection keys

Transducer
Conditioning
Display
Analogue outputs
Switch

by directly inputting the channel you want (for example 3.2


2. Use

Type
Excitation
Unit:
Zero pt.:
Nom.val.:

IND half bridge

mV/V

0.0000 ...

0.0000 ...

20.0000 ...

10.0000 ...

Adjust amplifier

measure

4. Select Transducer from the pull-up menu and confirm with


5. Use

2.5V
mm

measure...
K-Factor:

CHANNEL1

).

to return to set-up mode.

3. Press function key


TRANSDUCER

or

to select IND half bridge and confirm with

6. Use
to go to the Excitation selection field, press
select 2.5 V.
7. Confirm with

.
and

0.0000 ...

8. Use

to switch to the Unit selection field and press

the unit mm and confirm with


9. Use

to go to the Zero pt. edit field and enter the value 0 in

the lefthand edit field. Confirm with

10. Position the transducer in the zero position.

MGCplus with AB22A / AB32

. Select

Measure Inductive transducers

System

Display

Amplifier

Options

Transducer
Conditioning
Display
Analogue outputs
Switch

E-33

11. Use
to go to the button labelled measure and confirm with
(the measured value is displayed in the righthand edit field of Zero
pt.)
12. Enter the value 20 in the lefthand Nom.val. edit field.
13. Enter the value 10 in the righthand Nom.val. edit field (below the
unit mV/V).
14. Use
with

CHANNEL1

mm
Unit
Decimal places 3 ...
Display range
from 20.000 mm
20.000 mm
to
Step
1

and confirm

Adjust amplifier

. If you wish to make no further changes to the display, you

may continue with point 20. .


15. Use

DISPLAY

to select the button labelled

to return to the pull-up menu.

16. Select Display from the pull-up menu and confirm with

17. Specify the required number of decimal places in the Decimal


places edit field and confirm with

18. Go to the Step*) selection field, choose the required step and
confirm with

NOTE
The step width refers to the last decimal place of the input range.
Example: Input 10.0 mm
Step 1 means the display is in steps of 0.1 mm
Step 5 means the display is in steps of 0.5 mm
Input 10.000 kg
Step 1 means the display is in steps of 0.001 mm
Step 5 means the display is in steps of 0.005 mm
19. Use

to return to the pull-up menu.

20. To return to measuring mode, press the shift key


the security prompt with

and confirm

.
MGCplus with AB22A / AB32

Measure Inductive transducers

E-34

3.3.2 Calibrating the characteristic curve of the transducer

By transferring the signals produced by the transducer when a defined


displacement occurs
System

Display

Amplifier

Options

Transducer
Conditioning
Display
Analogue outputs
Switch

Example: A displacement transducer with a nominal displacement of


20 mm (nominal value 10 mV/V) is set with a gauging block of 10 mm,
but the measuring range should be 15 mm.

NOTE
If zero point and nominal sensitivity are not modified (for instance
in the case of recalibration), you may omit point 1.12..
1. Position the transducer in the zero position.

TRANSDUCER
Type
Excitation
Unit:
Zero pt.:
Nom.val.:

IND half bridge


mm

mV/V
measure

0.0000 ...

0.0000 ...

20.0000 ...

10.0000 ...

Adjust amplifier

or by directly inputting the channel you want


).

3. Use
4. Press

to return to set-up mode.


.

5. Select Transducer from the pop-up menu and confirm with

0.0000 ...

2. Use

(for example 3.2

2.5V

measure...
K-Factor:

CHANNEL1

to go to the Excitation selection field, press


6. Use
select 2.5 V.
7. Confirm with

Two point calibration


mm

mV/V

1st pt.:

0.0000

0.0021

Measure

2nd pt.:

10.000

5.1032

Measure

OK

Cancel

Shunt off

8. Use

to switch to the Unit selection field and press

. Select

to go to the Zero pt. edit field and enter the value 0 in

the lefthand edit field. Confirm with

MGCplus with AB22A / AB32

and

the unit mm and confirm with


9. Use

Measure Inductive transducers

System

Display

Amplifier

Options

E-35

10. Use
to go to the button labelled measure and confirm with
(the measured value is displayed in the righthand edit field of Zero
pt.)
11. Enter the value 20 in the lefthand Nom.val. edit field (below the
unit mm) and confirm with
12. Use

Transducer
Conditioning
Display
Analogue outputs
Switch

with

to select the button labelled

Type
Excitation
Unit:
Zero pt.:
Nom.val.:

measure...

14. Position the transducer in the zero position.


15. Enter the value 0 in the lefthand edit field of calibration point 1
and confirm with

IND half bridge

2.5V
mm

16. Use cursor key

mV/V

to select the button labelled

Measure

in the 1st

measure

0.0000 ...

0.0000 ...

20.0000 ...

10.0000 ...

measure...
K-Factor:

to select the button labelled

13. Use the cursor keys

CHANNEL1

and confirm

Adjust amplifier

and confirm with


TRANSDUCER

Adjust amplifier

pt. line and confirm with


17. Use cursor key

to select the lefthand edit field from the 2nd pt.

0.0000 ...

line, enter the value 10 and confirm with

18. Position the gauging block below the probe tip of the displacement
transducer.
19. Use cursor key

Two point calibration


mm

mV/V

1st pt.:

0.0000

0.0021

Measure

2nd pt.:

10.000

5.1032

Measure

OK

Shunt off

to select key symbol

Measure

from the

2nd pt. line. If you now press


measurement starts, and the
current measured value is displayed in mV/V on the left alongside
the Measure button.

Cancel

MGCplus with AB22A / AB32

Measure Inductive transducers

E-36

20. Use
to select the OK button and confirm with
(the
amplifier converts the nominal value to 20mm; the calibration data
for 10mm stays unchanged).
System

Display

Amplifier

Options

21. Use

to return to the pull-up menu.

22. Select Analogue outputs from the pull-up menu and confirm with
Transducer
Conditioning
Display
Analogue outputs
Switch

.
23. Select the gross signal from the Output Vo1 selection field and
confirm with

24. Select the required signal from the Output Vo2 selection field and
confirm with
ANALOGUE OUTPUTS

CHANNEL1

Output Vo1: Gross


Ouput Vo2: Net
Output characteristics mm
V
Point 1: 0.0000 ...
0.0000 ...
Point 2: 15.0000 ...
10.0000 ...

to go to the Output characteristics Pnt.2 edit field, and


25. Use
enter the required value (15 on the left for the display, 10 on the
right for the analogue output). Confirm with

26. To return to measuring mode, press the shift key


the security prompt with

MGCplus with AB22A / AB32

and confirm

Measure Torque transducers

3.4

E-37

Torque transducer

Torque transducers with different measurement principles require different amplifier modules in the MGCplus-system and therefore different operating steps.
The HBM torque transducers in the type series TB1A and TB2 work with SG full bridges. The procedure described
in Section 3.1 (SG transducer) must be followed to adapt the torque channels (ML10B, ML30B, ML38, ML55B) of
these transducers.
The adaptation of the speed channels (ML60B/ML460) corresponds to the procedure described in this chapter.
The HBM-torque transducers in type series T3_FNA and T10FKF1 work with a frequency modulation procedure
(TF ca. 10kHz corresponds to unloaded shaft, modulation through load 5kHz). You will need the connection
plates AP07 or AP07/1 for processing measured values.
The HBM-torque flanges in type series T10F/T10FSSF1/SU2 and T10FM require connection plate AP17 for operation with the amplifier modules ML60B (one amplifier module each for torque and speed).
When using the amplifier modules ML460 (multi-channel module) with the connection plates AP6401, the T10..
transducers must be powered externally.
For calculating additional parameters, such as the rotation output (product of speed and torque), the freely programmable module ML70B is recommended for MGCplus. Another option is the use of online calculation channels in the HBM measured data recording software catman.

MGCplus with AB22A / AB32

E-38

Measure Torque transducers

TRANSDUCER
Type:
Excitation:
Unit:
Zero pt.:
Nom. val.:

CHANNEL1

Special features of the ML460/AP460i:

Ext.fct...

The Transducer setup menu is expanded to include the PWM and


Duration types.

Freq.0..20kHz
Direct
Nm

kHz

0.0000 ...

10.0000 ...

50.0000 ...

measure...

5.0000 ...

Adjust amplifier

measure

When inductive rotation speed transducers are connected (T-R coils)


select from the setup menu Type: Freq. 0 ...x kHz and Link:
Integrating.

Freq.0..2kHz
Freq.0..20kHz
Freq.0..200kHz
Freq.0..500kHz
Pulse counter
PWM
Duration

PWM (pulse width modulation)


THigh

When pulse width modulation is in use, the ratio of the pulse duration
(THigh) to the time interval (T) is evaluated (duty ratio).
The measuring range is 0 % ... 100 % duty ratio.
Duration
When pulse duration is in use only the absolute pulse duration (THigh) is
evaluated. The measuring range is 0 ... 2500 ms.

MGCplus with AB22A / AB32

E-39

Measure Torque transducers

3.4.1 Direct input of torque characteristics

The following example explains the procedures for setting up the


torque, rotation-speed and performance channels (valid for the T3_FNA
type series):
System

Display

Amplifier

Options

Transducer
Conditioning
Display
Analogue outputs
Switch

Nominal torque of the shaft:


Nominal sensitivity:
Calibration characteristics:
Nominal speed:

50 Nm
5 kHz
24.22 Nm
3000 rpm

Rotation speed range to be displayed


for the application:
Display range for performance:

2000 rpm
10 kW

1. Use
TRANSDUCER
Type
Excitation
Unit:
Zero pt.:
Nom.val.:

CHANNEL1

Freq.0..20kHz

Ext.fct...

5V
Nm

(for example 3.2


2. Use

).

to return to set-up mode.

kHz

0.0000 ...

10.0000 ...

50.0000 ...

5.0000 ...

measure...

or by directly inputting the channel you want

measure

3. Press function key

Adjust amplifier

4. Select Transducer from the pull-up menu and confirm with


5. Use

to select Freq.0..20 kHz and confirm with

6. Use

to go to the Excitation selection field, press

select 5 V. Confirm with


7. Use

.
and

to switch to the Unit selection field and press

the unit Nm and confirm with

. Select

8. Enter the value 0 in the lefthand Zero pt. edit field.


9. Enter the value 10 in the righthand Zero pt. edit field (or if the
transducer is not under load, activate the button labelled measure ).

MGCplus with AB22A / AB32

E-40

Measure Torque transducers

10. Enter the value 50 in the lefthand Nom.val. edit field.


11. Enter the value 5 in the righthand Nom.val. edit field.
System

Display

Amplifier

Options

12. Use
with

to select the button labelled

and confirm

Adjust amplifier

. If you wish to make no further changes to the display, you

may continue with point 17. .


Transducer
Conditioning
Display
Analogue outputs
Switch

13. Use

to return to the pull-up menu.

14. Select Display from the pull-up menu and confirm with

15. Specify the required number of decimal places in the Decimal


DISPLAY

CHANNEL1

Nm
Unit
Decimal places 3 ...
Display range
from 50.000 Nm
50.000 Nm
to
Step
1

places edit field and confirm with

16. Go to the Step*) selection field, choose the required step and
confirm with

17. To return to measuring mode, press the shift key


the security prompt with

and confirm

*)NOTE
The step width refers to the last decimal place of the input range.
Example:
Input 50.0 Nm
Step 1 means the display is in steps of 0.1 Nm
Step 5 means the display is in steps of 0.5 Nm
Input 50.000 Nm
Step 1 means the display is in steps of 0.001 Nm
Step 5 means the display is in steps of 0.005 Nm

MGCplus with AB22A / AB32

E-41

Measure Torque transducers

3.4.2 Measuring with the built-in shunt

System

Display

Amplifier

NOTE

Options

If zero point and nominal torque are not modified (for instance in
the case of recalibration), you may omit point 1.9..
1. Use

Transducer
Conditioning
Display
Analogue outputs
Switch

(for example 3.2


2. Use

TRANSDUCER
Type
Excitation
Unit:
Zero pt.:
Nom.val.:

or by directly inputting the channel you want

CHANNEL1

).

to return to set-up mode.

3. Press function key

Freq.0..20kHz

4. Select Transducer from the pull-up menu and confirm with

5V
Nm
0.0000 ...

10.0000 ...

50.0000 ...

5.0000 ...

measure...

kHz
measure

5. Use

to select Freq.0..20kHz and confirm with

6. Use

to go to the Excitation selection field, press

Adjust amplifier

select 5V. Confirm with


7. Use
Nm

kHz

1st pt.:

0.0000

10.056

Measure

2nd pt.:

24.220

2.4210

Measure

OK

to switch to the Unit selection field and press

the unit Nm and confirm with

Two point calibration

and

. Select

Shunt on

8. Enter the value 50 in the lefthand Nom.val. edit field.

Cancel

MGCplus with AB22A / AB32

E-42

System

Measure Torque transducers

Display

Amplifier

Options

9. Use

to select the Adjust amplifier button and confirm with

10. Use

to select the button labelled

measure...

and confirm with

.
11. Unload the transducer.
Transducer
Conditioning
Display
Analogue outputs
Switch

12. Enter the value 0 in the lefthand edit field of calibration point 1
and confirm with
13. Use cursor key

.
to select the button labelled

pt. line and confirm with


TRANSDUCER
Type
Excitation
Unit:
Zero pt.:
Nom.val.:

in the 1st

CHANNEL1

14. Use

Freq.0..20kHz
5V
Nm

to go to the Shunt off selection field, press

select Shunt on. Confirm with

kHz

0.0000 ...

10.0000 ...

50.0000 ...

5.0000 ...

measure...

Measure

and

measure

15. Use

Adjust amplifier

to select key symbol

Measure

from the 2nd pt. line. If you

now press
, measurement starts and the present value in kHz
is displayed on the left next to the Measure key symbol.
16. Use

to select the lefthand edit field in the 2nd pt. line. Enter

the calibration characteristics 24.22 and confirm with


Two point calibration
Nm

kHz

1st pt.:

0.0000

0.0000

Measure

2nd pt.:

24.220

2.4210

Measure

OK

Shunt on

17. Use
to select the key symbol OK and confirm with
(the
amplifier converts the nominal value to 50 Nm; the calibration data
for 25 Nm stays unchanged).

Cancel

18. Select Display from the pull-up menu and confirm with

MGCplus with AB22A / AB32

E-43

Measure Torque transducers

19. Specify the required number of decimal places in the Decimal


places edit field and confirm with

20. Go to the Step selection field, choose the required step and
confirm with

*)NOTE
The step width refers to the last decimal place of the input range.
Example:
Input 50.0 Nm
Step 1 means the display is in steps of 0.1 Nm
Step 5 means the display is in steps of 0.5 Nm
Input 50.000 Nm
Step 1 means the display is in steps of 0.001 Nm
Step 5 means the display is in steps of 0.005 Nm
21. To return to measuring mode, press the shift key
the security prompt with

and confirm

MGCplus with AB22A / AB32

E-44

Measure Torque transducers

Extended functions setup window for ML60B:


Glitch filter
System

Display

Amplifier

Options

If this filter has been switched on, interfering signals with pulse widths
below 1.6 ms will be suppressed.
LIV1 switch output
The frequency signal F1 or the counter signal can be applied to the
switching output of limit value switch 1 (see figure).

Transducer
Conditioning
Display
Analogue outputs
Switch

TRANSDUCER
Typ:
Excitation:
Unit:
Zero pt.:
Nom. val.:

LIV1 switch output states

CHANNEL1

Freq.0..20kHz

Ext.fct...

5V
Nm

F1

kHz

0.0000 ...

10.0000 ...

50.0000 ...

5.0000 ...

measure...

measure

1.6 ms

Adjust amplifier

Extended functions

Glitch filter (min. pulse width 1.6ms)


Frequency quadrupling
Evaluate F2 signal
Zero index input active
Transd. error input active

LIV1 switch output:

F1 Counter signal to LIV1

LIV2 switch output:

Off

OK

Cancel
Off
F2 to LIV2
Direction of rotation to LIV2

Off
F1 to GW1
F1 Counter signal to GW1

MGCplus with AB22A / AB32

Counter
signal to
LIV1

All extended functions that have not been mentioned here are
insignificant for torque measurements and must be deactivated (default
settings).

E-45

Measure Torque transducers

3.5

Adapting the rotation-speed channel

The following calculation is needed for setting up the speed channel:


Nominal speed: nA = 3000 rpm
Number of impulses/revolution: i = 30 (see table below, type T30FNA)
nA x i
Impulse frequency
60
In this example:
3000 x 30 =
1500 Hz
60
i.e. a frequency of up to 1500Hz is to be measured.

*)

Torque transducer

Number of impulses per revolution


(two outputs shifted by 90o)

T4WA

90

T30FNA

30

T32FNA

15

T34FNA

15

T10F

15...720*)

See T10F documentation.

MGCplus with AB22A / AB32

E-46

Measure Torque transducers

1. Use
System

Display

Amplifier

Options

3.2

or by directly inputting the channel you want (for example


).

2. Use the shift key


Transducer
Conditioning
Display
Analogue outputs
Switch

TRANSDUCER
Typ:
Excitation:
Unit:
Zero pt.:
Nom. val.:

3. Press function key

Freq.0..20kHz

Ext.fct...

Nm

5. Use

to select Freq.0..2 kHz and confirm with

6. Use

to go to the Excitation selection field, press

select 5 V. Confirm with

.
and

kHz

0.0000 ...

10.0000 ...

50.0000 ...

5.0000 ...

measure...

4. Select Transducer from the pull-up menu and confirm with

CHANNEL1

5V

to return to set-up mode.

measure

Adjust amplifier

Extended functions
Glitch filter (min. pulse width 1.6ms)
Frequency quadrupling
Evaluate F2 signal
Zero index input active
Transd. error input active

7. Use

to switch to the Unit selection field and press

the unit rpm and confirm with

. Select

8. Enter the value 0 in the Zero pt. edit field (lefthand column rpm
and righthand column kHz).
9. Enter the value 3000 in the lefthand Nom.val. edit field.
10. Enter the value 1.5 in the righthand Nom.val. edit field.

LIV1 switch output:

Off

LIV2 switch output:

Off

OK

11. Use

to select the button labelled

with

and confirm

. If you wish to make no further changes to the display, you

may continue with point 16. .

MGCplus with AB22A / AB32

Adjust amplifier

Cancel

E-47

Measure Torque transducers

12. Use

to return to the pull-up menu.

13. Select Display from the pull-up menu and confirm with

14. Specify the required number of decimal places in the Decimal


places edit field and confirm with

15. Go to the Step selection field, choose the required step and
confirm with

*)NOTE
The step width refers to the last decimal place of the input range.
Example:
Input 1000.0 rpm
Step 1 means the display is in steps of 0.1 rpm
Step 5 means the display is in steps of 0.5 rpm
Input 1000.000 rpm
Step 1 means the display is in steps of 0.001 rpm
Step 5 means the display is in steps of 0.005 rpm
16. To return to measuring mode, press the shift key
the security prompt with

and confirm

MGCplus with AB22A / AB32

E-48

Measure Torque transducers

Extended functions setup window for ML60B:


Glitch-Filter
System

Display

Amplifier

Options

If this filter has been switched on, interfering signals with pulse widths
below 1.6 ms will be suppressed.
LIV1 switch output
The frequency signal F1 or the counter signal can be applied to the
switching output of limit value switch 1 (see figure).

Transducer
Conditioning
Display
Analogue outputs
Switch

TRANSDUCER
Typ:
Excitation:
Unit:
Zero pt.:
Nom. val.:

LIV1 switch output states

CHANNEL1

Freq.0..20kHz

Ext.fct...

5V
Nm

F1

kHz

0.0000 ...

10.0000 ...

50.0000 ...

5.0000 ...

measure...

measure

Adjust amplifier

Extended functions

Glitch Filter (min. pulse width 1.6ms)


Frequency quadrupling
Evaluate F2 signal
Zero index input active
Transd. error input active

LIV1 switch output:

F1 Counter signal to LIV1

LIV2 switch output:

Off

OK

Cancel
Off
F2 to LIV2
Direction of rotation to GW2

Off
F1 to LIV1
F1 Counter signal to LIV1

MGCplus with AB22A / AB32

Counter
signal to
LIV1

1
.
6
m
s

All extended functions that have not been mentioned here are
insignificant for torque measurements and must be deactivated (default
settings).

E-49

Measure Thermocouples

3.6

Thermocouples

Thermocouples are active transducers. For measurements using


thermocouples you need the ML01B amplifier plug-in module and the
AP09 connection board. The AP09 has a built-in reference temperature
measuring point. The amplifier plug-in module carries out cold-spot
compensation and linearisation for type J, T, K and S thermocouples.
With the Thermocouples operating mode and units C or F selected,
the temperature will be displayed appropriately in the required unit.
With Volt selected as the unit, scaling is carried out in accordance with
the output voltage1).
The following example explains the settings:
Type K thermocouple, the temperature is to be displayed in C , with a
temperature of 50C corresponding to an output signal of 0 V. The
temperature of 70C corresponds to an output signal of +10 V.

Display
(C)

70
50

Nom.val.

Upon switching to another thermocouple type, the values for the


following functions are reset to their default values:
Cut-off frequency; limit switches; peak values; unit of measure; zero
balance

10

10

Amplifier
Output signal (V)

1)

If you wish to measure the output voltage of the thermocouple directly (without
linearisation and cold-spot compensation), you must set up under 75 mV operating
mode.

MGCplus with AB22A / AB32

E-50

Measure Thermocouples

3.6.1 Direct input of transducer characteristics

1. Use
System

Display

Amplifier

Options

3.2
2. Use

Transducer
Conditioning
Display
Analogue outputs
Switch

TRANSDUCER
Type
Excitation
Unit:
Zero pt.:
Nom.val.:

to return to set-up mode.


.

4. Select Transducer from the pull-up menu and confirm with

Thermocpl.K

5. Use

to select Thermocpl.K and confirm with

6. Use

to switch to the Unit selection field and press

the unit C and confirm with


C

50.0000 ...

50.0000 ...

20.0000 ...

20.0000 ...

measure...

).

3. Press function key

CHANNEL1

no
C

or by directly inputting the channel you want (for example

Adjust amplifier

measure

.
. Select

7. Enter the value 50 in the lefthand Zero pt. edit field.


8. Enter the value 20 in the lefthand Nom.val. edit field
(70C50C=20C).
9. Use
with

to select the button labelled

Adjust amplifier

and confirm

. If you wish to make no further changes to the display, you

may continue with point 14. .


10. Use

to return to the pull-up menu.

11. Select Display from the pull-up menu and confirm with

MGCplus with AB22A / AB32

E-51

Measure Thermocouples

12. Specify the required number of decimal places in the Decimal


places edit field and confirm with

13. Go to the Step*) selection field, choose the required step and
confirm with

NOTE
The step width refers to the last decimal place of the input range.
Example:
Input 10.0C
Step 1 means the display is in steps of 0.1C
Step 5 means the display is in steps of 0.5C
Input 50.000C
Step 1 means the display is in steps of 0.001C
Step 5 means the display is in steps of 0.005C
14. To return to measuring mode, press the shift key
the security prompt with

and confirm

MGCplus with AB22A / AB32

Measure Current and voltage measurement

E-52

3.7

Current and voltage measurement

To measure current signals and voltage signals you need the ML01B amplifier plug-in module or the ML801B multichannel module with the AP801 connection board.
The following example explains the set-ups:
A torque transducer with integral amplifier delivers a maximum output signal of 3 V, corresponding to a nominal
torque of 20 Nm. A display range of 20.000 Nm is to be set up. For control purposes an output signal of 10 V is
required.

MGCplus with AB22A / AB32

Measure Current and voltage measurement

3.7.1

E-53

Direct input of transducer characteristics

1. Use
System

Display

Amplifier

Options

3.2
2. Use

Transducer
Conditioning
Display
Analogue outputs
Switch

TRANSDUCER
Type
Excitation
Unit:
Zero pt.:
Nom.val.:

or by directly inputting the channel you want (for example


).
to return to set-up mode.

3. Press function key

4. Select Transducer from the pull-up menu and confirm with

Channel 1

5. Use

to select 10 V and confirm with

6. Use

to switch to the Unit selection field and press

.
. Select

10V

the unit Nm and confirm with

no
Nm
0.00000 ...

Vi
50.0000 ...

20.0000 ...

3.0000 ...

measure...

Adjust amplifier

measure

7. Enter the value 0 in the lefthand Zero pt. edit field.


8. Enter the value 0 in the righthand Zero pt. edit field.
9. Enter the value 20 in the lefthand Nom.val. edit field.
10. Enter the value 3 in the righthand Nom.val. edit field.
11. Use
with

to select the button labelled

Adjust amplifier

and confirm

. If you wish to make no further changes to the display, you

may continue with point 16. .


12. Use

to return to the pull-up menu.

13. Select Display from the pull-up menu and confirm with

14. Specify the required number of decimal places in the Decimal


places edit field and confirm with

MGCplus with AB22A / AB32

Measure Current and voltage measurement

E-54

15. Go to the Step*) selection field, choose the required step and
confirm with
System

Display

Amplifier

Options

NOTE
Transducer
Conditioning
Display
Analogue outputs
Switch

DISPLAY

CHANNEL1

Nm
Unit
Decimal places 3 ...
Display range
from 20.000 Nm
20.000 Nm
to
Step
1

MGCplus with AB22A / AB32

The step width refers to the last decimal place of the input range.
Example:
Input 10.0 Nm
Step 1 means the display is in steps of 0.1 Nm
Step 5 means the display is in steps of 0.5 Nm
Input 10.000 Nm
Step 1 means the display is in steps of 0.001 Nm
Step 5 means the display is in steps of 0.005 Nm
16. To return to measuring mode, press the shift key
the security prompt with

and confirm

Measure Resistance temperature detectors

3.8

E-55

Resistance temperature detectors

Resistance temperature detectors are passive transducers. For this transducer you need the ML35B one-channel
amplifier plug-in module or the ML801B multi-channel module with the AP835 connection board. They carry out
automatic linearisation and display the temperature in correct digits.
With resistance temperature detector operating mode and unit C or F selected, the corresponding temperature
will be displayed in degrees of the required unit. With Volt selected as the unit, scaling is carried out in accordance
with the output voltage1).
The following example explains the set-ups:
Type Pt100 resistance temperature detector, the temperature is to be displayed in C , with a temperature of 50C
corresponding to an output signal of 0 V. The output signal at 70C is to be +10 V.
1)

The permissible ranges depend on the bridge excitation voltage. If a measuring range is set up that exceeds the amplifiers adjustment
range, the maximum or minimum possible value is adopted.

MGCplus with AB22A / AB32

Measure Resistance temperature detectors

E-56

3.8.1

Direct input of transducer characteristics

1. Use
System

Display

Amplifier

3.2

Options

2. Use
Transducer
Conditioning
Display
Analogue outputs
Switch

measure...

Adjust amplifier

to return to set-up mode.


.

4. Select Transducer from the pull-up menu and confirm with

CHANNEL1

Type:
Pt100
Connection: 4-wire
C
Unit:
C
50.0000 ...
Zero pt.: 50.0000 ...
20.0000
...
20.0000 ...
Nom.val.:

).

3. Press function key

5. Use
TRANSDUCER

or by directly inputting the channel you want (for example

to select Pt100 and confirm with

6. Select the required connection mode from the Connection


selection field.*)
7. Use

to switch to the Unit selection field and press

. Select

measure

the unit C and confirm with

8. Enter the value 50 in the lefthand Zero pt. edit field.


9. Enter the value 20 in the lefthand Nom.val.: edit field
(70C50C=20C).
10. Use
with

to select the button labelled

Adjust amplifier

and confirm

. If you wish to make no further changes to the display, you

may continue with point 15. .


11. Use

to return to the pull-up menu.

12. Select Display from the pull-up menu and confirm with
*)

MGCplus with AB22A / AB32

In 4-wire technology, compensation is made for cable resistance up to a length of


500 m.

Measure Resistance temperature detectors

E-57

13. Specify the required number of decimal places in the Decimal


places edit field and confirm with
System

Display

Amplifier

Options

14. Go to the Step*) selection field, choose the required step and
confirm with

Transducer
Conditioning
Display
Analogue outputs
Switch

DISPLAY

CHANNEL1

C
Unit
Decimal places 3 ...
Display range
from 30,000 C
30,000 C
to
Step
1

NOTE
The step width refers to the last decimal place of the input range.
Example:
Input 10.0C
Step 1 means the display is in steps of 0.1C
Step 5 means the display is in steps of 0.5C
Input 50.000C
Step 1 means the display is in steps of 0.001C
Step 5 means the display is in steps of 0.005C
15. To return to measuring mode, press the shift key
the security prompt with

and confirm

MGCplus with AB22A / AB32

Measure Resistors

E-58

3.9

Resistors

Resistors are passive transducers. These transducers require the ML35B , amplifier plug-in module, which has two
coarse measuring ranges available (0...500 and 0...5 k).
The following example explains the set-ups:
Resistance value 400 , Input range 400.00
The input range of 400 corresponds to an output signal of 10 V.

MGCplus with AB22A / AB32

Measure Resistors

3.9.1

E-59

Direct input of transducer characteristics

1. Use
System

Display

Amplifier

3.2

Options

2. Use
Transducer
Conditioning
Display
Analogue outputs
Switch

measure...

400.0000 ...

.
.

to select 500Ohm (this is the input range of the amplifier)

and confirm with

6. Select the required connection mode from the Connection


selection field.*)

Ohm
0.00000 ...

to return to set-up mode.

4. Select Transducer from the pull-up menu and confirm with

CHANNEL1

Type:
500 Ohm
Connection: 4-wire
Ohm
Unit:
Zero pt.: 0.00000 ...
Nom.val.: 400.0000 ...

).

3. Press function key

5. Use
TRANSDUCER

or by directly inputting the channel you want (for example

measure

7. Use

Adjust amplifier

to switch to the Unit selection field and press

the unit Ohm and confirm with

. Select

8. Enter the value 0 in both the Zero pt. edit fields.


9. Enter the value 400 in the lefthand Nom.val. edit field.
10. Use
with

to select the button labelled

Adjust amplifier

and confirm

. If you wish to make no further changes to the display, you

may continue with point 15. .


11. Use
*)

to return to the pull-up menu.

In 4-wire technology, compensation is made for cable resistance up to a length of


500 m.

MGCplus with AB22A / AB32

Measure Resistors

E-60

12. Select Display from the pull-up menu and confirm with

13. Specify the required number of decimal places in the Decimal


System

Display

Amplifier

Options

places edit field and confirm with

14. Go to the Step*) selection field, choose the required step and
Transducer
Conditioning
Display
Analogue outputs
Switch

confirm with

NOTE
The step width refers to the last decimal place of the input range.
DISPLAY

CHANNEL1

Ohm
Unit
Decimal places 3 ...
Display range
from 400.000 Ohm
400.000 Ohm
to
Step
1

Example:
Input 10.0
Step 1 means the display is in steps of 0.1
Step 5 means the display is in steps of 0.5
Input 10.000
Step 1 means the display is in steps of 0.001
Step 5 means the display is in steps of 0.005
15. To return to measuring mode, press
prompt with

MGCplus with AB22A / AB32

and confirm the security

Measure Impulse counting

3.10

E-61

Impulse counting

The ML60B amplifier is required for impulse counting purposes. It enables a maximum impulse-sequence frequency of 1 MHz to be processed. For more details on further amplifier setup options refer to chapter 3.4, page
E-44. Incremental transducers e.g. for angle measurement deliver two square-wave signals which are 90 out
of phase. The clock ratio between High and Low for both signals must be approx. 1:1.

The following example explains the set-ups:


An angle of rotation transducer delivers 180 impulses per revolution. These impulses are to be displayed as 360 .
Due to the number of impulses per revolution the value 2 is specified as Step, since a higher resolution would make
no sense. The levels of the square-wave signal amount to 10 V.
A frequency signal with quadrupled counter impulses is required at the output in addition to the measured value.

MGCplus with AB22A / AB32

Measure Impulse counting

E-62

3.10.1 Direct input of transducer characteristics

1. Use
System

Display

Amplifier

Options

3.2
2. Use

Transducer
Conditioning
Display
Analogue outputs
Switch

TRANSDUCER
Type:
Excitation:
Unit:
Zero pt.:
Nom.val.:

5V
deg

Ext.fct...

0.00000 ...

kImp
0.00000 ...

360.0000 ...

0.18000 ...

measure...

).
to return to set-up mode.

3. Press function key

CHANNEL1

Impuls counter

or by directly inputting the channel you want (for example

measure

Adjust amplifier

4. Select Transducer from the pull-up menu and confirm with

5. Use

to select the Impuls counter type and confirm with

6. Use

to go to the Excitation selection field, press

select 5 V. Confirm with

and

7. Use
to switch to the Ext.fct...
button and confirm with
(For details on the extended functions refer to page E-64).
8. Use

to select the Frequency quadrupling and Evaluate F2

Extended functions

!
!

Glitch filter (min. pulse width 1.6ms)


Frequency quadrupling
Evaluate F2 signal
Zero index input active
Transducer error input active

LIV1 switch output :

F1 Counting signal to LIV1

LIV2 switch output :

Off

OK

MGCplus with AB22A / AB32

Cancel

signal activation fields and press


9. Use

to activate them.

to change to the LIV1 switch output selection field, select

F1 counter signal to LIV1 and confirm with


10. Use

to switch to the

OK

button and confirm with

Measure Impulse counting

E-63

11. Use

to change to the Unit selection field and press


.

Select the unit deg and confirm with


System

Display

Amplifier

Options

12. Enter the value 0 in both the Zero pt. edit fields.
13. Enter the value 360 in the lefthand Nom.val. edit field.

Transducer
Conditioning
Display
Analogue outputs
Switch

14. Enter the value 0.180 in the righthand Nom.val. edit field.
15. Use
with

to select the button labelled

Adjust amplifier

and confirm

. If you wish to make no further changes to the display, you

may continue with point 20.


DISPLAY

CHANNEL1

deg
Unit
Decimal places 3 ...
Display range
from 360.000 deg
360.000 deg
to
Step
2

16. Use

to return to the pull-up menu.

17. Select Display from the pull-up menu and confirm with

18. Specify the required number of decimal places in the Decimal


places edit field and confirm with

19. Select Display from the pull-up menu and confirm with

20. Specify the required number of decimal places in the Decimal


places edit field and confirm with

21. Select Value 2 from the Step*) selection field (1 impulse


corresponds to 2; 180 impulses/revolution corresponds to 360)
and confirm with

22. To return to measuring mode, press


prompt with

and confirm the security

Assign a free F-key to the function Zeroing (factory settings: Level 1/F1). Then return to
measuring mode. If you then press the appropriate F-key, the impulse counter is set to
0. See also chap. Assigning F-keys; page G-24.
MGCplus with AB22A / AB32

Measure Impulse counting

E-64

Extended functions setup window for ML60B:


Glitch filter
System

Display

Amplifier

Options

If this filter has been switched on, interfering signals with pulse widths
below 1.6ms will be suppressed.
Frequency quadrupling
The frequency quadrupling results in an increased signal resolution by
counting of both the positive and the negative signal edges. With both
frequency inputs (F1 and F2) having been connected, the measuring
frequency is quadrupled. If F2 has not been connected,the measuring
frequency is doubled.

Transducer
Conditioning
Display
Analogue outputs
Switch

Evaluate F2 signal (recognition of direction)


TRANSDUCER
Typ:
Excitation:
Unit:
Zero pt.:
Nom. val.:

CHANNEL1

The phaseshifted signal F2 is evaluated thus enabling the direction of


rotation or motion to be displayed.

Ext.fct...

Zero index input active

Freq.0..20kHz
5V
Nm

kHz

0.0000 ...

0.0000 ...

360.0000 ...

0.1800 ...

measure...

measure

Adjust amplifier

Extended functions

!
!

Glitch filter (min. pulse width 1.6ms)


Frequency quadrupling
Evaluate F2 signal
Zero index input active
Transducer error input active

LIV1 switch output :

Off

LIV2 switch output :

Off

OK

Transducer error input active (only with AP01i)


If a signal is connected (0V level), the amplifier interprets the measured
value as an error (e.g. in the case of a failure of the luminescent source
with optical systems).
LIV1 switch output
The frequency signal F1 or the counter signal can be applied to the
switching output of limit value switch 1.

Cancel
Off
F2 to LIV2
Direction of rotation to LIV2

Off
F1 to LIV1
F1 Counting signal to LIV1

MGCplus with AB22A / AB32

With incremental transducers this input is used for resetting the counter
in counting mode.

LIV2 switch output


The frequency signal F2 or the signal for the direction of rotation can be
applied to the switching output of limit value switch 2.

Measure Impulse counting

E-65

F1

F2

Counting signal to
LIV1 with activated
quadruple evaluation

MGCplus with AB22A / AB32

Measure Piezoelectric transducers

E-66

Piezoelectric transducers

Piezoelectric transducers are active transducers that emit a charge in the event of mechanical loading. When using
these transducers, please observe the following instructions:

For transducer connection, special cable with high isolation resistance, low capacitance, low noise and a wide
temperature range is essential. Standard coaxial cable is unsuitable for this type of application.
For quasi-static measurements a very high isolation resistance (>100T ) is required. For this reason all input
plugs must be kept clean and should not be touched by hand. Please use a suitable cleaning agent for cleaning
(e.g. pure petroleum spirit).

To operate piezoelectric transducers you need the AP08 connection board with the charge amplifier and an ML10B
or ML01B DC amplifier.
A piezoelectric transducer can be thought of as a capacitor that is charged by mechanical loading. In all cases, discharging is via the input and isolation resistor on the amplifier. The time constant determines the speed of discharge. There are three time constants from which to choose:
SHORT
MEDIUM
LONG

for dynamic measurement


for dynamic measurement with a limited frequency range
for quasi-static measurement

Coarse and fine adjustment can be chosen for the measuring range selection. There are four input ranges for
coarse adjustment: 100 pC; 1; 10 and 100 nC.
Example: If the measuring range 6000 pC is wanted, set up the next higher input range of 10 nC.

MGCplus with AB22A / AB32

Measure Piezoelectric transducers

E-67

With a constant transducer loading the value in the display or at the output signal may drift. This may result from
insufficient cable isolation resistance or incorrect drift balance on the amplifier.
We recommend that all male connectors should first be cleaned. If the problem persists, the drift needs to be readjusted (see chap.4.2).
The following example explains the set-ups:
You wish to use a piezoelectric acceleration transducer for measurement. Transducer nominal value is 100 pC/g.
Dynamic measurement is to be taken, up to 60 g = 10 V.
Measuring range 60 g 100 pC/g = 6000 pC
Dynamic measurement, i.e. time constant SHORT.

MGCplus with AB22A / AB32

Measure Piezoelectric transducers

E-68

4.1

Connecting and measuring

Resetting the charge amplifier (RESET):

Gross

1ML10B

Channel

Measure

1. Assign an F-key (in this case factory setting F2) to the


Zero/Cal/Measure function (see page G-23ff).
2. Select screen type 1 value (with status line) (see page G-3ff).

Measure

3. Reset the charge amplifier:


Now press the F-key assigned under point 1 until Zero appears on
the status line.

AP08

NOTE
Transducer connection
(BNC female connector)

When you have just switched the unit on this step is not
necessary, since the input is automatically set to zero.
4. Unloading the transducer:
Immediately before connecting the transducer, the cable must be
short-circuited.
a) Connect the centre pin of the BNC male connector for a moment to
the connector housing.
b) Connect the transducer to the BNC female connector of the AP08.
5. Starting to measure:
Now press the F-key assigned under point 1 until Measure
appears in the status line.
6. We recommend selecting the ZERO position with the F-key when
measurement is not in progress.

MGCplus with AB22A / AB32

Measure Piezoelectric transducers

E-69

If the error message OVERFLOW occurs during set-up:

Press the Zero/Cal/Measure F-key until Zero appears on


the status line.

Wait until the display comes to a stop.


Press the Zero/Cal/Measure F-key until Measure is
displayed.

MGCplus with AB22A / AB32

Measure Piezoelectric transducers

E-70

4.1.1 Direct input of transducer characteristics

1. Use
System

Display

Amplifier

Options

3.2
2. Use

Transducer
Conditioning
Display
Analogue outputs
Switch

TRANSDUCER

Zero pt.: 0.00000 ...


Nom.val.: 60.0000 ...
measure...

).
to return to set-up mode.

3. Press function key

4. Select Transducer from the pull-up menu and confirm with

CHANNEL1

Type
< 10nC
Time constant short
g
Unit:

or by directly inputting the channel you want (for example

5. Use

to select transducer type < 10 nC and confirm with

6. Use

to go to the Decay time selection field, press

select Short. Confirm with


nC
0.00000 ...
6.00000 ...

Adjust amplifier

measure

7. Use

and

to switch to the Unit selection field and press

the unit g and confirm with

. Select

8. Enter the value 0 in both the Zero pt. edit fields.


9. Enter the value 60 in the lefthand Nom.val. edit field.
10. Enter the value 6 in the righthand Nom.val. edit field.
11. Use
with

to select the button labelled

Adjust amplifier

. If you wish to make no further changes to the display, you

may continue with point 16. .


12. Use

MGCplus with AB22A / AB32

and confirm

to return to the pull-up menu.

Measure Piezoelectric transducers

E-71

13. Select Display from the pull-up menu and confirm with

14. Specify the required number of decimal places in the Decimal


System

Display

Amplifier

Options

places edit field and confirm with

15. Go to the Step*) selection field, choose the required step and
Transducer
Conditioning
Display
Analogue outputs
Switch

confirm with

*)NOTE
The step width refers to the last decimal place of the input range.

DISPLAY

CHANNEL1

deg
Unit
Decimal places 3 ...
Display range
from 360.000 deg
360.000 deg
to
Step
2

Example:
Input 10.0 nC
Step width 1 means the display is in steps of 0.1 nC
Step width 5 means the display is in steps of 0.5 nC
Input 10.000 nC
Step width 1 means the display is in steps of 0.001 nC
Step width 5 means the display is in steps of 0.005 nC
16. To return to measuring mode, press
prompt with

and confirm the security

MGCplus with AB22A / AB32

Measure Piezoelectric transducers

E-72

4.1.2 Setting up the zero point

Zero point is set up in measuring mode with the Measure and


Zeroing functions.
Time constant Short
1. Press function key
(factory setting: Measure, 2nd level) until
Measure appears in the status line.
2. Press the function key to which you have assigned the function
Zeroing ( >0< ) (factory setting F1/Level 1).
Time constant Medium/Long
a few times (factory setting: Measure, 2nd level) until
1. Press
Zero is displayed on the status line.
2. Press the function key to which you have assigned the function
Zeroing ( >0< ) (factory setting F1/Level 1).
3. Press
a few times (Measure, 2nd level) until Measure is
displayed on the status line.

MGCplus with AB22A / AB32

Measure Piezoelectric transducers

E-73

4.1.3 Special case: initial charge is known

In this case zero point setting is omitted for one measurement.


1. Use
System

Display

Amplifier

or by directly inputting the channel you want (for example

Options

3.2

).
to return to set-up mode.

2. Use

Transducer
Conditioning
Display
Analogue outputs
Switch

3. Press function key

4. Select Transducer from the pull-up menu and confirm with

TRANSDUCER

CHANNEL1

Type
< 10nC
Time constant short
g
Unit:
Zero pt.: 0.00000 ...
Nom.val.: 60.0000 ...
measure...

nC
0.12000 ...

measure

5. Use

to select transducer type < 10nC and confirm with

6. Use

to go to the Time constant selection field, press

select Short. Confirm with

.
and

6.00000 ...

Adjust amplifier

7. Use

to switch to the Unit selection field and press

the unit g and confirm with

. Select

8. Enter the value 0 in the lefthand Zero pt. edit field.


9. Enter the value of the initial load in the righthand Zero pt. edit field
(e.g. 0.12).
10. Use
with

to select the button labelled

Adjust amplifier

and confirm

11. To return to measuring mode, press


prompt with

and confirm the security

MGCplus with AB22A / AB32

Measure Piezoelectric transducers

E-74

4.2

Drift balancing

The drift will have been balanced at the factory. However, the balancing
procedure must be repeated from time to time due to the effects of
aging and temperature.

AP08

ZERO-potentiometer
for setting the drift

Connect the unladen transducer to the amplifier before it is


switched on
Switch the instrument on and wait 30min.

Set-up mode:

Select nC as the unit of measure

Set input range and measuring range to <100 pC

Set time constant to Long

Measuring mode:

Use

to select gross signal

Press the Zero/Cal/Measure F-key a few times until Measure is


displayed on the status line.
Turn the set-up potentiometer (see accompanying figure) until the
value stops.

If the error message OVERFLOW occurs during set-up:

MGCplus with AB22A / AB32

Press the Zero/Cal/Measure F-key a few times until Zero is


displayed on the status line.
Wait for the display to come to a stop
Press the Zero/Cal/Measure F-key a few times until Measure is
displayed on the status line.

Measure Current-fed piezoelectric transducers

E-75

Current-fed piezoelectric transducers

Piezoelectric transducers with a built-in preamplifier are often used for acceleration and force measurement. These
transducers need a constant current for the power supply. The measurement signal corresponds to the modulated
voltage at the power line. A typical example of this product family is the DeltaTronT acceleration transducer from
Brel&Kjaer.
To operate current-fed piezoelectric transducers you will need connection board AP18i and an ML10B or ML01B
DC amplifier. You can select rough and fine adjustment for the measuring range. 3 input ranges are available for
coarse adjustment: 0.1 V; 1 V; 10 V.
Example: If you want a measuring range of 7 V the next input range up 10 V is set.
The zero point defines the voltage which generates 0 V at the output of the amplifier. The nominal value is always
defined relative to this zero point.
Analogue outputs are used to define the display scaling, i.e. they are used to define the value that is displayed for
an output signal of 10 V.
The following example explains the set-ups:
An acceleration of up to 300 m/s2 is to be measured with a DeltaTronT transducer. The nominal value of the transducer is 1 mV/ m/s2.
Measuring range (fine adjustment):
300 m/s2 x 1 mV/m/s2 = 0.3 V
Input range (coarse adjustment):
1 V ( > 0.3 V)

MGCplus with AB22A / AB32

Measure Current-fed piezoelectric transducers

E-76

5.1

Direct input of transducer characteristics

1. Use
System

Display

Amplifier

Options

3.2

).

2. Use
Transducer
Conditioning
Display
Analogue outputs
Switch

Type
Excitation:
Unit:
Zero pt.:
Nom.val.:

to return to set-up mode.

3. Press function key

4. Select Transducer from the pull-up menu and confirm with


5. Use

TRANSDUCER

or by directly inputting the channel you want (for example

CHANNEL1

to select transducer type Deltatron 1V and confirm with

Deltatron 1V

6. Use

220mA
m/s2
0.00000 ...

Vi
0.00000 ...

300.0000 ...

0.30000 ...

measure...

Adjust amplifier

measure

to switch to the Unit selection field and press

the unit m/s2 and confirm with

. Select

7. Enter the value 0 in both the Zero pt. edit fields.


8. Enter the value 300 in the lefthand Nom.val. edit field.
9. Enter the value 0.3 in the righthand Nom.val. edit field.
10. Use
with

to select the button labelled

Adjust amplifier

. If you wish to make no further changes to the display, you

may continue with point 15. .


11. Use

MGCplus with AB22A / AB32

and confirm

to return to the pull-up menu.

Measure Current-fed piezoelectric transducers

E-77

12. Select Display from the pull-up menu and confirm with

13. Specify the required number of decimal places in the Decimal


System

Display

Amplifier

Options

places edit field and confirm with

14. Go to the Step*) selection field, choose the required step and
Transducer
Conditioning
Display
Analogue outputs
Switch

confirm with

*)NOTE
The step width refers to the last decimal place of the input range.

DISPLAY

CHANNEL1

m/s2
Unit
Decimal places 3 ...
Display range
from 300.000 m/s2
300.000 m/s2
to
Step
1

Example:
Input 10.0 m/s2
Step 1 means the display is in steps of 0.1 m/s2
Step 5 means the display is in steps of 0.5 m/s2
Input 10.000 m/s2
Step 1 means the display is in steps of 0.001 m/s2
Step 5 means the display is in steps of 0.005 m/s2
15. To return to measuring mode, press
prompt with

and confirm the security

MGCplus with AB22A / AB32

E-78

Measure Piezoresistive transducers

Piezoresistive transducers

Piezoresistive transducers are passive transducers.


The following example explains the set-ups:
Pressure transducer with the following characteristics:
Rated pressure 300 bar, excitation 10 V, rated sensitivity 200 mV/V,
Display range 300 bar, test pressure 250 bar (partial load)
Due to the high sensitivity you must use the ML10B amplifier.
Zero point and measuring range can be set up directly with the transducer characteristics or by means of a test
pressure. Both methods are described below.

MGCplus with AB22A / AB32

E-79

Measure Piezoresistive transducers

6.1

Direct input of transducer characteristics

1. Use
System

Display

Amplifier

Options

3.2
2. Use

Transducer
Conditioning
Display
Analogue outputs
Switch

TRANSDUCER
Type
Excitation:
Unit:
Zero pt.:
Nom.val.:

or by directly inputting the channel you want (for example


).
to return to set-up mode.

3. Press function key

4. Select Transducer from the pull-up menu and confirm with

CHANNEL1

5. Use

and confirm with

6. Use

to switch to the Excitation selection field and press

Full bridge high level

Select 10V and confirm with

10V
bar
0.00000 ...

mV/V
0.00000 ...

300.0000 ...

200.0000 ...

measure...

Adjust amplifier

measure

7. Use

to switch to the Unit selection field and press

the unit bar and confirm with

. Select

8. Enter the value 0 in both the Zero pt. edit fields.


9. Enter the value 300 in the lefthand Nom.val. edit field.
10. Enter the value 200 in the righthand Nom.val. edit field.
11. Use
with

to select the button labelled

Adjust amplifier

and confirm

. If you wish to make no further changes to the display, you

may continue with point 16. .

MGCplus with AB22A / AB32

E-80

Measure Piezoresistive transducers

12. Use

System

Display

Amplifier

Options

to return to the pull-up menu.

13. Select Display from the pull-up menu and confirm with

14. Specify the required number of decimal places in the Decimal


places edit field and confirm with
Transducer
Conditioning
Display
Analogue outputs
Switch

15. Go to the Step*) selection field, choose the required step and
confirm with

16. To return to measuring mode, press


prompt with
DISPLAY

and confirm the security

CHANNEL1

bar
Unit
Decimal places 3 ...
Display range
from 300.000 bar
300.000 bar
to
Step
1

*)NOTE
The step width refers to the last decimal place of the input range.
Example:
Input 10.0 bar
Step 1 means the display is in steps of 0.1 bar
Step 5 means the display is in steps of 0.5 bar
Input 10.000 bar
Step 1 means the display is in steps of 0.001 bar
Step 5 means the display is in steps of 0.005 bar

MGCplus with AB22A / AB32

E-81

Measure Piezoresistive transducers

6.1.1

Measuring transducer characteristics

Transferring the signals produced by the transducer when a


defined test pressure occurs.
System

Display

Amplifier

Options

NOTE
If zero point and nominal value are not modified (for instance in
the case of recalibration), you may omit point 1.10..

Transducer
Conditioning
Display
Analogue outputs
Switch

1. Use
3.2

TRANSDUCER
Type
Excitation
Unit:
Zero pt.:
Nom.val.:

CHANNEL1

2. Use

or by directly inputting the channel you want (for example


).
to return to set-up mode.

Full bridge high level


5V
bar

3. Press

mV/V
measure

0.0000 ...

0.0000 ...

300.0000 ...

200.000 ...

measure...

4. Select Transducer from the pull-up menu and confirm with

Adjust amplifier

5. Use
to go to the Excitation selection field, press
select 10V.

0.0000 ...

K-Factor:

6. Confirm with
Two point calibration
bar

mV/V

1st pt.:

0.0000

0.0021

Measure

2nd pt.:

250.000

166.67

Measure

OK

Cancel

Shunt off

7. Use

to switch to the Unit selection field and press

the unit bar and confirm with


8. Use

. Select

to go to the Zero pt. edit field and enter the value 0 in

the lefthand edit field. Confirm with


9. Use

and

to go to the Nom.val. edit field and enter the value 300

in the lefthand edit field. Confirm with

MGCplus with AB22A / AB32

E-82

Measure Piezoresistive transducers

10. Use
with
System

Display

Amplifier

to select the button labelled


.

Options

to select the button labelled

11. Use the cursor keys


and confirm with
Transducer
Conditioning
Display
Analogue outputs
Switch

TRANSDUCER

measure...

12. Unload the transducer.


13. Enter the value 0 in the lefthand edit field of calibration point 1
and confirm with
14. Use

Type
Excitation
Unit:
Zero pt.:
Nom.val.:

and confirm

Adjust amplifier

CHANNEL1

to select the button labelled

confirm with

Measure

in the 1st pt. line and

Full bridge high level


5V
bar

15. Use

0.0000 ...

0.0000 ...

10.0000 ...

2.0000 ...

measure...

measure

Adjust amplifier
0.0000 ...

K-Factor:

the value 250 and confirm with

16. Set up the transducer with the test pressure.


17. Use cursor key

to select the button labelled

Measure

from the

Point 2 line. If you now press


measurement starts, and the
current measured value is displayed in mV/V on the left alongside
the Measure .

Two point calibration


bar

mV/V

1st pt.:

0.0000

0.0021

Measure

2nd pt.:

250.000

166.67

Measure

OK

to select the lefthand edit field from the 2nd pt. line, enter

mV/V

Shunt off

18. Use
to select the button labelled OK
and confirm with
(the amplifier converts the nominal value to 300 bar; the calibration
data for 250 bar stays unchanged).

Cancel

19. To return to measuring mode, press


prompt with

MGCplus with AB22A / AB32

and confirm the security

E-83

Measure Potentiometric transducers

Potentiometric transducers

Resistors are passive transducers. These transducers require the ML35B , amplifier plug-in module, which has two
coarse measuring ranges available (0...500 and 0...5 k).
Potentiometric transducers are passive transducers that have to be supplied with an excitation voltage. To operate
a potentiometric transducer you require the ML10B amplifier. Please note that the maximum resistance value is
5 k.
The following example explains the set-ups:
A potentiometric displacement transducer with a nominal displacement of 10 mm is used for measurement. The
whole nominal displacement is to be used. The display range is 10 mm.
Due to the interdependence between excitation voltage and nominal input voltage (mV/V), in the case of an excitation voltage of 2.5 V, the measuring range needs to be set up in accordance with the following correlation:
Nominal value to be set up =
(RANGE)

Rated voltage (displacement)


Excitation voltage

Nominal value (range) = 2.5 V / 2.5 V = 1000 mV/V


This value of 1000 mV/V or 1 V/V only changes if a potentiometric transducer is used in a section.
As the second method, partial calibration with end values of 7 mm is performed for calibration of the zero point and
range with a defined displacement.

MGCplus with AB22A / AB32

E-84

Measure Potentiometric transducers

7.1

Direct input of transducer characteristics

1. Use
3.2
System

Display

Amplifier

TRANSDUCER

to return to set-up mode.

3. Press function key

Transducer
Conditioning
Display
Analogue outputs
Switch

4. Select Transducer from the pull-up menu and confirm with

CHANNEL1

5. Use

and confirm with

6. Use

to switch to the Excitation selection field and press

Select 2.5 V and confirm with

Full bridge high level

2.5V
mm

mV/V

0.0000 ...

0.0000 ...

10.0000 ...

1000.000 ...

measure...
K-Factor:

).

Options

2. Use

Type
Excitation
Unit:
Zero pt.:
Nom.val.:

or by directly inputting the channel you want (for example

measure

7. Use

to switch to the Unit selection field and press

the unit mm and confirm with

. Select

Adjust amplifier
0.0000 ...

8. Enter the value 0 in both the Zero pt. edit fields.


9. Enter the value 10 in the lefthand Nom.val. edit field.
10. Enter the value 1000 in the righthand Nom.val. edit field.
11. Use
with

to select the button labelled

Adjust amplifier

. If you wish to make no further changes to the display, you

may continue with point 16. .


12. Use

MGCplus with AB22A / AB32

and confirm

to return to the pull-up menu.

E-85

Measure Potentiometric transducers

13. Select Display from the pull-up menu and confirm with

14. Specify the required number of decimal places in the Decimal


places edit field and confirm with

15. Go to the Step*) selection field, choose the required step and
confirm with

16. To return to measuring mode, press


prompt with

and confirm the security

*)NOTE
The step width refers to the last decimal place of the input range.
Example:
Input 10.0 mm
Step 1 means the display is in steps of 0.1 mm
Step 5 means the display is in steps of 0.5 mm
Input 10,000 mm
Step 1 means the display is in steps of 0.001 mm
Step 5 means the display is in steps of 0.005 mm

MGCplus with AB22A / AB32

E-86

Measure Potentiometric transducers

7.1.1

Measuring transducer characteristics

Transferring the signals produced by the transducer when a


defined displacement occurs.
System

Display

Amplifier

Options

NOTE
If zero point and nominal value are not modified (for instance in
the case of recalibration), you may omit point 1.10..

Transducer
Conditioning
Display
Analogue outputs
Switch

1. Use
3.2

TRANSDUCER
Type
Excitation
Unit:
Zero pt.:
Nom.val.:

CHANNEL1

2. Use

or by directly inputting the channel you want (for example


).
to return to set-up mode.

Full bridge high level


2.5V
mm

3. Press

0.0000 ...

0.0000 ...

10.0000 ...

1000.000 ...

measure...

measure

4. Select Transducer from the pull-up menu and confirm with


5. Use
to go to the Excitation selection field, press
select 2.5 V.
6. Confirm with

Two point calibration


mm

mV/V

1st pt.:

0.0000

0.0021

Measure

2nd pt.:

7.0000

699.23

Measure

OK

Adjust amplifier
0.0000 ...

K-Factor:

mV/V

Cancel

Shunt off

7. Use

to switch to the Unit selection field and press

the unit mm and confirm with


8. Use

to go to the Zero pt. edit field and enter the value 0 in


.

to go to the Nom.val. edit field and enter the value 10 in

the lefthand edit field. Confirm with

MGCplus with AB22A / AB32

. Select

the lefthand edit field. Confirm with


9. Use

and

E-87

Measure Potentiometric transducers

10. Use

to go to the righthand Nom.val.: edit field and enter the

value 1000. Confirm with


System

Display

Amplifier

Options

11. Use

to select the button labelled

and confirm with

measure...

.
Transducer
Conditioning
Display
Analogue outputs
Switch

12. Slide the core into the transducer until zero is displayed.
13. Enter the value 0 in the lefthand edit field of calibration point 1
and confirm with
14. Use

TRANSDUCER
Type
Excitation
Unit:
Zero pt.:
Nom.val.:

CHANNEL1

to select the button labelled

and confirm with

Measure...

in the 1st pt. line

Full bridge high level

15. Use cursor key

2.5V
mm
0.0000 ...

0.0000 ...

10.0000 ...

1000.000 ...

measure...

to select the lefthand edit field from the Point

mV/V

Adjust amplifier

measure

2 line, enter the value 7 and confirm with

16. Position the gauging block below the probe tip of the displacement
transducer.

0.0000 ...

K-Factor:

17. Use

Measure

from the 2nd pt. line.

If you now press


measurement starts, and the current
measured value is displayed in mV/V on the left alongside the
Measure .

Two point calibration


mm

mV/V

1st pt.:

0.0000

0.0021

Measure

2nd pt.:

7.0000

699.23

Measure

OK

to select the button labelled

Cancel

Shunt off

18. Use
to select the button labelled OK
and confirm with
(the amplifier converts the nominal value to 10mm; the calibration
data for 7mm stays unchanged).
19. To return to measuring mode, press
prompt with

and confirm the security

MGCplus with AB22A / AB32

E-88

MGCplus with AB22A / AB32

Measure Potentiometric transducers

F-1

Additional functions

MGCplus with AB22A / AB32

F-2

MGCplus with AB22A / AB32

F-3

Additional functions Remotes

Remote (one-channel modules only)

1.1

Switching on remote control

The remote contacts are used to control important functions of the


amplifier by means of digital inputs. These remotes are only active
when remote control is switched on.
System

Display

Amplifier

Options

There are three ways in which you can switch remote control on or off.

In measuring mode: Press function key

twice followed by

Remote contacts

function key
Remote contacts
Remote control
Input 1
Input 2
Input 3
Input 4
Input 5
Input 6
Input 7
Input 8

Channel 1
On

no function

no function

no function

no function

no function

no function

no function

no function

On
Off

(factory setting).

In set-up mode: press function key

. The Switch set-up

window lets you switch remote control on or off.

By means of the remote contacts (with function REMT).

No function
ACALautocal
TARAtare
CPV1clear store 1
HLD1hold store 1
CPV2clear store 2
HLD2hold store 2
ZEROzero balance
SHNTShunt ON/OFF
PRNTselect for printing
CALinput to cal. signal
ZEROinput to zero signal
INVchange sign
PSEL1select line param. set 1
PSEL2select line param. set 2
PSEL4select line param. set 4
REMTRemote ON/OFF
INTStart/Stop Integration

MGCplus with AB22A / AB32

F-4

Additional functions Remotes

1.2

Assigning remote contacts

Remotes can be assigned freely and are not defined in the factory setup. The available functions and a description
of each are shown in the following table:
Function

Level 5 V
(Level 0V for AP13i)

Level 0 V
(Level 24 V for AP13i)

ACAL

Autocalibration ON

Autocalibration OFF

TARA

Taring starts on transition 5 V0 V (0 V24 V for AP13i)

CPV1/2

Peak value 1/2 is


stored

Peak value 1/2 is cleared from current value

HLD1/2

Peak value store 1/2 free

Contents of peak value store 1/2


frozen

ZERO

Current measuring signal is set to zero on transition 5 V0 V (0 V24 V for AP13i)

SHNT

Shunt off

Shunt on

PRNT

When printing is enabled the channel is


taken into account

When printing is enabled the channel is not


taken into account

CAL

Input is switched to internal calibration


source

ZERO

Input is switched to zero signal

INV

Polarity is switched over


(ML60B only)

PSEL1

Parameter set select code line 1(see Table 1.1)

PSEL2

Parameter set select code line 2 (see Table 1.1)

PSEL4

Parameter set select code line 4 (see Table 1.1)

REMT
INT

Remote control contacts inactive

Remote control contacts active

All connection boards (except AP13i):


Integration starts at the transition from 5 V 0 V and stops at the transition from 0 V 5 V.
Connection boards AP13i:
Integration starts at the transition from 0 V 24 V and stops at the transition
from 24 V 0 V.

MGCplus with AB22A / AB32

F-5

Additional functions Remotes

Parameter set selection


PSEL1

PSEL2

PSEL4

Parameter set selected

Table 1.1

0: Remote contacts not driven; Level 5 V (level 0 V in the case of 13i).


1: Remote contacts driven; Level 0 V; connected to digital ground (level 24 V in the case of 13i).

MGCplus with AB22A / AB32

F-6

Additional functions Limit switches

Limit switches (one-channel modules only)

In order to assess mass or weight tolerances, or when monitoring


forces, pressures etc., it is often necessary to comply with certain target
values or limit switches. Each amplifier plug-in module therefore has
four limit switches available (in ex-factory status these are OFF).
They can be used to specify the level, the hysteresis and the direction
of each for limit switch monitoring. The hysteresis value prevents
fluttering of the limit switches upon reaching the switching threshold.
The prevailing connection state is indicated by an LED on the front
panel of the amplifier plug-in module when the STATUS display format
is enabled.
Displays
limit switches status

MGCplus with AB22A / AB32

Please note the following points when working with limit switches:

The measuring signal must last for at least 1 ms. The measurement
voltage delivered by the amplifier is compared internally with the
reference voltage. If the measurement voltage reaches or exceeds
the reference voltage that has been set, the associated logic output
is switched and the appropriate LED indicates the connection state.

If you are using the AP02 connection board, you also have relay
contacts available.

Connection board AP13i has 24 V PLCcompatible, optically


decoupled limit switch outputs.

F-7

Additional functions Limit switches

2.1

Activate limit switches

In the ex-factory setting, the limit switches are not enabled (Enable limit
switch Off).
System

Display

Amplifier

1. Use the shift key

Options

to return to set-up mode.

2. Press
Limit switches

3. Select Limit switches from the pop-up menu and confirm with
4. Select Yes from the Enable selection field and confirm with

Limit switch 1
Limit switches

Channel 1
1 ...

Name

1-Limit1 ...

Enable
Input signal
Level

No
100.000 ...

Hysteresis

1,000 ...

Direction
Output logic

Over limit

Delay

define...

Input
Message when ON

free
1-Limit1 ON...

Normal

Message when OFF

1-Limit1 OFF...

Normal

free
disabled

NOTE

Gross

The screen type Status limit switch, which enables the status of
limit switches to be displayed, is set up under Screen No. 5
ex-factory (see also chap.1.4, Status limit switch ; page G-21).
The limit switches must be enabled in advance (see chap. 2.2;
page F-8).

Positiv logic

No
Yes
Positive logic
Negative logic

Over limit
Below limit

Gross
Net
Store1
Store2
Store12

Normal
Inverse

MGCplus with AB22A / AB32

F-8

Additional functions Limit switches

2.2

Setting up limit switches

Limit switch 1
Limit switches

Set-up window Limit switches

Channel 1
1 ...

Setting up and activating the limit switches (Enable).

Name

1-Limit1 ...

Enable
Input signal
Level

No
100.000 ...

Hysteresis

1,000 ...

Direction
Output logic

Over limit

Gross

to go to the required
Enter a number (1 to 4) and confirm with
set-up range; this saves you having to run through all the edit fields
or selection fields with the cursor keys.

Positiv logic

Delay

define...

Input
Message when ON

free
1-Limit1 ON...

Normal

Message when OFF

1-Limit1 OFF...

Normal

free
disabled

Gross
Net
Store1
Store2
Store12

Positive logic
Negative logic

Normal
Inverse

Enable
Switches limit switch monitoring on or off.

Input signal
Selects the source of the signal that you want to monitor
(Gross/Net/Peak values/Peak value combine).

No
Yes

Level
Input the operate value in displayed units (e.g. kg).

LIV-Delay
12 3 4
LIV-On

Delay time

LIV-Off

0ms

OK
OK

Name
Name of the limit switch or its function, depending on your choice
(for example Emergency Off).

Over limit
Below limit

Limit switches

Cancel
OK

MGCplus with AB22A / AB32

Hysteresis
Hysteresis is understood to mean the changed onset of the
switching effect between the On and Off states. The hysteresis
prevents fluttering of the limit switch when the switching level is
reached.

F-9

Additional functions Limit switches

Direction
Input the operating direction of the limit switch.
a) Switching when Over the switching level limit

Level

Hysteresis
Amplifier output signal
Limit switch On
Limit switch Off

1
0

LED
LED

b) Switching when Below the switching level limit


Hysteresis

Level
1

Limit switch On
Limit switch Off

LED
LED

Limit switch delay


You can enter a limit switch delay time of 0 99999 ms.
Switch at Delay time of 60 ms
30ms

Level
Hysteresis

1
0
60 ms
Delay time
MGCplus with AB22A / AB32

F-10

Additional functions Limit switches

The limit switch should only operate if the signal has been above
the level for a long time (here 60 ms). The limit switch should not
operate if the signal has only been above the level for a short time
(here 30ms).

Output logic
You can change the output logic of the remotes as required.

Positive logic

Negative logic

On =High

On =Low

Off=Low

Off=High

Input
Enable or disable use of function keys to input limit switches.

Message when ON
Edit field for a message that will be displayed when switching to on
(e.g. below 20kg, see also the figure on page F-14). You may also
select the display mode (Standard=black font on a light
background; Inverse=light font on a dark background).

Message when OFF


Edit field for a message that will be displayed when switching to off
(e.g. below 20kg). You may also select the display mode
(Standard=black font on a light background; Inverse=light font on a
dark background).

MGCplus with AB22A / AB32

F-11

Additional functions Limit switches

2.3

Limit switch 1
Limit switches
Name
Enable
Input signal
On level
Off level
Input
Hysteresis

Selection keys in the menu Limit switches

NOTE

Channel 1
1 ....

It may be an advantage to use the horizontal cursor keys when


enabling. As soon as you have entered your set-up in the required

1-Limit1 ...
No

selection box or edit field (in this case Enable), confirm it with

Gross
10.000 ...
9.9000 ...
disabled
variable

V
V

(Edit fields)

and press
. By doing this you stay in the required selection
box (edit field), but skip to the next limit switch.

MGCplus with AB22A / AB32

F-12

Additional functions Combine limit switches

Combine limit switches (one-channel modules


only)

Using this function you can logically combine selected limit switches to
a limit switch output.
System

Display

Amplifier

Options

Combine LIV

Combine LIV
LIV output:
Comb.:
Input 1:
Input 2:
Input 3:
Input 4:

Channel 1
3
AND
LIV 1
LIV 2

LIV 4
LIV 4 inverted
Remote contact 4
Remote contact 4 inverted
AND
OR
EXOR
NAND
NOR
NEXOR

1
2
3
4

MGCplus with AB22A / AB32

LIV output
Input the required limit switch output (, 1, 2, 3, 4).
Comb.
Logical combination of the input signals (AND, OR, EXOR, NAND,
NOR, NEXOR).
Input 1...4
Choose the inputs to be combined (Limit1 (LIV1) to Limit4 (LIV4) or
remote contact).

F-13

Additional functions Combine limit switches

Limit switch 1
Limit switches

Example:

Channel 1
1

Task: To monitor the range between 10 kN and 20 kN, and evaluate it


as OK. The evaluation will be displayed as OK or NOK.

Name

1-Limit1

Enable
Input signal
Level

Yes
10,000 ...

kN

Hysteresis

0.010 ...

kN

Direction
Output logic

Over limit

Solution: Limit switch 1 monitors the 10 kN limit, whilst limit switch 2


monitors the 20 kN limit. Both are combined to one another by AND.
The result from this combination controls the output of limit switch 3.

Gross

Positiv logic

kN

Delay

define...

Input
Message when ON

free
Over 10kN...

Normal

Message when OFF

Under 10kN...

Invers

20

OK
Limit switch 2
Limit switches

Channel 1

10

2...

Name

1-Limit2 ...

Enable
Input signal
Level

Yes
20,000...

kN

Hysteresis

0.010 ...

kN

Direction
Output logic

Below limit

Delay

define...

Input
Message when ON

free
Below 20kN ...

Normal

Message when OFF

Over 20kN...

Invers

Gross

1
0

Negative logic

Limit switch 3
Limit switches

Channel 1

1
0
1
0

Limit1
Limit2
Limit3

Name

1-Limit3

Enable
Input signal
Level

Yes
0,000 ...

kN

Hysteresis

0.010 ...

kN

Direction
Output logic

Over limit

Gross

Positiv logic

Delay

define...

Input
Message when ON

free
OK

Normal

Message when OFF

NOK

Invers

MGCplus with AB22A / AB32

F-14

Additional functions Combine limit switches

Combine LIV
LIV output:
Comb.:
Input 1:
Input 2:
Input 3:
Input 4:

Channel 1

If limit switch 1 is undershot, the settings shown in this example give


rise to the following display (screen type 7Status limit switch):

3
AND
LIV 1
LIV 2

MGCplus with AB22A / AB32

LIMIT VALUE
1ML30B
Gross
8.483 kN
1Limit
Below 10kN
1
1Limit
Below 20kN
2
1Limit
NOK
3
Measure

F-15

Additional functions Adjusting peak values

Adjusting peak values

4.1

Peak value stores

Measured
peak value

You can use the Peak values function to record and save isolated
signal peaks and minimum/maximum signal amplitudes. All amplifiers
have two peak value stores each.
You can use these to save:

26 sec

Maxima

Minima or

Peak-to-peak amplitudes

Gross
Peak value stores
Net

(envelope)

Display

Peaktopeak

In the case of rapid dynamic signals, you must taken into account that
the peak values are defined in a fixed time raster. If filter cut-off
frequencies are set up > 5 Hz Bessel or 10 Hz Butterworth, the raster is
scanned 38400 times per second, corresponding to 26 sec.
The peak value stores are abbreviated to Store1 and Store2 in the
set-up windows because this form of notation is shorter.
Setting up peak value stores
From the Function selection fields, select the minimum or maximum
signal for which you want the peak value to be saved.
In the Envelope selection fields, switch on the envelope function. In
the right-hand edit field, enter the decay time in milliseconds.

MGCplus with AB22A / AB32

F-16

Additional functions Adjusting peak values

4.2

Combine peak value stores

Combine peak value stores


Gross
System

Display

Amplifier

Net

Options

Store1
Store12
Store2

Peak value stores

Peak value stores (PVS)

Channel 1

Maximum gross
Store1 Function
Store1 Envelope curve
Off
0 ... ms
Store2 Function
Maximum gross
Off
0 ... ms
Store 2 Envelope curve

Comb. PVS 12

There are four possible ways to combine peak value stores:


1. Difference generation:
Store1 Store2 (used as Peak/Peak).
F

Store1

Off
On

Difference PVS1, PVS2


Mean PVS1,PVS2
Integrate gross
Integrate net

Signal curve
Maximum, gross

Maximum gross
Maximum net
Minimum gross
Minimum net

Peak-to-peak value
t
Minimum, gross

Fig.4.1:

MGCplus with AB22A / AB32

Peak value combination when calculating difference

Store2

F-17

Additional functions Adjusting peak values

2. Mean generation:
(PVS1PVS2)
2
System

Display

Amplifier

Options

Store1
Peak value stores

Mean value
Store2

Peak value stores (PVS)


Store1 Function
Store1 Envelope curve
Store2 Function
Store 2 Envelope curve
Comb. PVS 12

Channel 1

Maximum gross
Off

0 ...

ms

Fig.4.2:

Maximum gross
Off

0 ...

Peak value combination when calculating mean value

ms

3. Integrate gross:

B/n

n = number of points

Off
On

Difference PVS1, PVS2


Mean PVS1,PVS2
Integrate gross
Integrate net

B = gross signal

Maximum gross
Maximum net
Minimum gross
Minimum net

4. Integrate net:
N/n

N = gross signal
n = number of points

The mean value of the gross/net signal is generated for your choice
of time interval. The values are added at a sample rate of 1200 Hz
(for filter frequencies >5 Hz: Bessel; >10 Hz: Butterworth).

You can allocate a F-key (function Start/Stop integration; see page


G-25) or use a remote contact (INT) to set the start/end of
integration.

MGCplus with AB22A / AB32

F-18

4.3

Additional functions Adjusting peak values

Controlling the peak value store

Three remote contacts have an effect on the peak value store:


CPV:
HLD:
INT:

Used to clear the peak value store


Freezes or unfreezes the current contents of the memory
Starts and stops integration for a particular time interval

You can use these remote control elements to carry out other functions, such as storing current values.

MGCplus with AB22A / AB32

F-19

Additional functions Adjusting peak values

4.4

Vi, Vo

Peak value operating mode

Output

Measurement
signal

In Peak value operating mode you can save the minimum value, the
peak value or the peak-to-peak value (function Run). Use the Hold
function to hold the contents of the store.
For all connection boards except AP13i

Function
Operating
mode

Run
Peak value

t
Hold
Run
Current value

Function

Control circuit for CPV


Peak/Current value

Control circuit for HLD


Run/Hold

Peak value:
Memory runs in chosen
direction

5V

5V

Freeze value

Any

0V

Function

Control circuit for CPV


Peak/Current value

Control circuit for HLD


Run/Hold

Peak value: Memory


runs in chosen direction

0V

0V

Freeze value

Any

24 V

For connection boards AP13i

MGCplus with AB22A / AB32

F-20

Additional functions Adjusting peak values

4.5

Current value operating mode

Measurement signal
Vi, Vo

Output

In Current value operating mode, the memory is constantly updated


(function Run). Use the Hold function to hold the contents of the
store. You can use the remote contacts to switch the peak value store
to current value operating mode.
For all connection boards except AP13i

t
Function
Operating
mode

Run
Hold
Current value

Function

Control circuit
Peak/Current value

Control circuit
Run/Hold

Current value: Memory


runs in each direction

0V

5V

Freeze value

Any

0V

Function

Control circuit for CPV


Peak/Current value

Control circuit
Run/Hold

Current value: Memory


runs in each direction

24 V

0V

Freeze value

Any

24 V

Run

For connection boards AP13i

MGCplus with AB22A / AB32

F-21

Additional functions Adjusting peak values

4.6

Envelope curve operating mode

Output signal
100%
30%

Input signal

Time constant

Time constant: OK

Peak value stores can also be used to provide an envelope display. The
envelope function is suitable for measuring amplitude modulated
vibration. Inputting a decay time defines how quickly the peak value
store is discharged to 30 % of the peak value when the latter is no
longer present at memory input. The choice of decay time depends on
the basic vibration frequency f0 and the modulation frequency. Usable
envelopes are obtained in most cases with a decay time which is about
a multiple of 10 of the basic frequency period (t= 10 / f0).

Time constant: too long

Time constant: too short

MGCplus with AB22A / AB32

F-22

Additional functions Adjusting peak values

4.7

Clear peak value store

The peak value stores are abbreviated to Store1 and Store2 in the
set-up windows because this form of notation is shorter.

System

Display

Amplifier

Options

Clear peak value store


There are three ways in which you can clear a peak value store:
1. By means of a function key (factory setting

/level3).

Peak value stores

2. With the remote contacts CPV1/CPV2 (in the pull-up menu


Amplifier/ set-up window Switch, ON must be selected in the
Remote selection field).
Peak value stores (PVS)
Store1 Function
Store1 Envelope curve
Store2 Function
Store 2 Envelope curve
Comb. PVS 12

Channel 1

Maximum gross
Off

0 ...

ms

Maximum gross
Off

0 ...

ms

Off
On

Difference PVS1, PVS2


Mean PVS1,PVS2
Integrate gross
Integrate net

MGCplus with AB22A / AB32

Maximum gross
Maximum net
Minimum gross
Minimum net

3. From a computer, with the command CPV.

F-23

Additional functions Version

Version

System

Display

Amplifier

Options

You may use the channel selection keys to display information about
the version of your device components one after another. In the header
on the right is the name of the device components (e.g. AB, CP,
Channel 1, etc.) and their version is displayed. The first line of the box
below gives information on device identification and the second line
gives the serial number.
You may enter any text you wish in the comment line.

Version

Version

KANAL 1

Identification:
Comments:

HBM, RD002ML50B, P4.0A


...

Serial and revisionnumber

ML801B

Serial No.
xxxx

Rev.No.
xxxx

MGCplus with AB22A / AB32

F-24

Additional functions Switch

Switch

The first things you find in the Switch set-up window are three buttons,
which you can use for
>T<
System

Display

Amplifier

Options

>0<

You can use the selection fields that come after, to switch between the
possible states of the functions Autocalibration, Parameter set,
Amplifier input, Remote and Channel-LED.

Channel 1

>T<

Autocal

>0<

Autocal

Off

Param.set

1internal

Ampl. Input

Zero

Remote control

zero balancing
clearing the peak value store.

Switch

Switch

taring

Off

ChannelLED Status

Switching automatic calibration on and off. When AUTOCAL is On,


this improves the temperature tracking of zero point and the long term
stability of the amplifier. If you need the analogue output signal for
continuous monitoring, you must switch autocalibration off. This is
because during calibration no data is acquired, giving rise to a gap in
the measurement output (at intervals of approx. 5 minutes, lasting
about 1 second, depending on the filter setting.
Parameter set
Selecting stored parameter sets (see also H-9).
Ampl. Input

MGCplus with AB22A / AB32

Zero:

Zero signal; input internal to zero potential

Cal:

Calibration signal

Measure:

The current measurement signal is present at the input

Shunt:

Shunt resistor on (shunt calibration)

F-25

Additional functions Switch

Switch

Remote control

Channel 1

>T<

Switching Remote on/off (activates the remote contacts)

>0<

Param.set

Off

Remote control Off


1internal

Ampl. Input

Zero

Autocal

Off
5 Min
once

ChannelLED

ChannelLED Status

This switches the function of the LEDs on the front panel of the
amplifier.
Status:
Status display (Amplifier active, Error, Limit switches)

Zero
Cal
Measure

1internal
2internal
3internal
4internal
5internal
6internal
7internal
8internal

Status
Level

Level:
Amplifier level control coefficient

Off
On

MGCplus with AB22A / AB32

F-26

MGCplus with AB22A / AB32

Additional functions Switch

G-1

Display

MGCplus with AB22A / AB32

G-2

MGCplus with AB22A / AB32

G-3

Display Display format

Display format

1 value

Gross
Channel

The settings determine how the selected signals are displayed. You can
basically select four different signals (Gross, Net, Limit switches, Peak
values) per channel.

Measure

Measure

Values can be represented numerically or graphically. A maximum of


six values can be displayed simultaneously in numerical representation.

Acal

3 values
Gross

The display states shown on the left are described as types and can be
selected from the setup menu.

Gross
Gross
Measure

6 values

Acal

Representation as a numerical value

Gross

Gross

Gross

Gross
Gross

Gross

Acal

Measure

1 value (with/without status line)

3 values

6 values

Graphical representation

YT-Diagram
Gross

YT-Diagram

XY-Diagram

XY-Diagram
Gross

Gross

Display four limit switch states

Status limit switch

Status limit switch

Limit switch
1ML30B
Gross
1Limit1
Below 10kN
1Limit2
Below 20kN
1Limit3
NOK
Acal
Measure

8.483 kN

Display with Data acquisition type

Recording status
Test sequence 3

Pre trigger status

Post trigger status

MEAS. RATE: 50Hz


PERIODS: 100

TIME: 00: 00: 00


1

16.0S

4.0S
FILE NAME: MGCP0000.MEA

Get DAQ1

Acal

120 MB FREE

... ...

MGCplus with AB22A / AB32

G-4

Display Display format

1.1

Select set-up window

1. Use the shift key


2. Press
System

Display

Amplifier

to return to set-up mode.

Options

3. Select Display format from the pull-up menu and confirm with
You are now in the Display format set-up window.

Display format
F-keys
Channel names

Display Format
Screen No:
Type:

one value
0 ...
one value

Channels/Signals: all
Off
Status line

MGCplus with AB22A / AB32

define...

G-5

Display Display format

1.2

Set-up window Display format

Display format

The structure of the Display format set-up window depends on the


selected Type. The window mask changes according to the selected
Type. For instance the Status line selection field is only present for the
1 value type.

one value
0 ...
one value

Screen No:
Type:

Channels/Signals: all
Off
Status line

define...

Off
On

Display format

Menu for 1 value type

all
Selection
free
One value
3 values
6 values
YT-Diagram
XY-Diagram Limit_V. status
Status data acquisition

Display format

Channel
Gross
Net
Store1
Store2
Store12
Limit1
Limit2
Limit3
Limit4

define...

3 values
0 ...

Screen No:
Type:

3 values

Value 1 (Base):

Select channel/signal
Cancel

Channels/Signals: all
Off
Status line

0...9

Menu for 3 values type


OK

one value
0 ...
one value

Screen No:
Type:

All channels

All signals

1 2 3 4 5 6 7 8 9 10111213141516

Channels/Signals: Selection
Value 2:

Value 3:

define...

relativ to base
Channel 2
Signal Gross
relativ to base
Channel 1
Signal Gross

MGCplus with AB22A / AB32

G-6

Display Display format

1.3

Set-up window components

Dsplay format

Number

one value

You can enter the numbers 1...9 in this edit field. In this way you can
store your current display settings under a number or recall the factory
presets. In the same way you can determine the sequence in which the

0 ...
one value

Screen No:
Type:

Channels/Signals: all
Off
Status line

define...

types are selected in measuring mode with the

Off
On

The following sequence is preset at the factory:


Number

all
Selection
free
One value
3 values
6 values
YT-Diagram
XY-Diagram
Limit_V. status
Status data acquisition

0...9

Select channel/signal
OK
Channel
Gross
Net
Store1
Store2
Store12
Limit1
Limit2
Limit3
Limit4

Cancel

cursor keys.

All channels

All signals

1 2 3 4 5 6 7 8 9 10111213141516

MGCplus with AB22A / AB32

Type

Channels/Signals

Status line

1 value

All

On

3 values

All

6 values

All

YT-Diagram

All

XY-Diagram

All

Status limit switch

DAQ status

Free

Free

Free

Type
Use the Type to define the number of measurement signals that can be
displayed simultaneously (numerical value only) or the representation
mode (graphic only) in the display. You can also display the status of
four selected limit switches.

G-7

Display Display format

1.3.1 Numerical display

Display format

Channels/Signals

3 values

At this point you define which channels and signals are to be shown on
the first display line. You can define your settings for all channels or just
for certain ones (Selection) (key symbol define...
). You can recall a
maximum of six signals per channel one after the other.

0 ...

Screen No:
Type:

3 values

Value 1 (Base):
Channels/Signals: Selection
Value 2:

none
Gross
Net
Store1
Store2
Store12
Limit1
Limit2
Limit3
Limit4
as base

define...

relativ to base
Channel 2
Signal Gross
0...9

0...9
all
Selection

Absolute
relativ to base

At this point, 3/6 values types are used to define the basic channels
(Value 1).
Define...
The key symbol opens a new window Select channel/signal.
Status line

Free
One value
3 values
6 values
YT-Diagram
XY-Diagram

With the 1 value type, the status line can be superimposed on the
display.

Value1 (Base)
Select channel/signal
OK
Channel
Gross
Net
Store1
Store2
Store12
Limit1
Limit2
Limit3
Limit4

Cancel

All channels

All signals

1 2 3 4 5 6 7 8 9 10111213141516

6 values

3 values
Gross
Gross
Gross
Measure

Gross

Gross

Gross

Gross

Gross

Gross

Measure

MGCplus with AB22A / AB32

G-8

Display Display format

Value (2...6): Channel


The value entered depends on the absolute/relative selection.
This setting lets you use 3 values and 6 values types to define which
reference to the basic channel is produced.
Absolute/relativ to base
This setting lets you use 3 values and 6 values types to define
whether a reference to the channel number of the basic channel is
produced.
Absolute: The measured value and signal of the selected channel are
displayed independently of the basic value. The number entered
corresponds to the actual channel number. Changing channels in
measuring mode has no effect on this display value.
relativ to base: The number entered refers to the basic channel
(display value 1). Channels to the left of the basic channel are entered
with a negative sign and those to the right of it are entered with a
positive sign.
Caution: This value does not correspond to the actual (absolute)
channel number.

MGCplus with AB22A / AB32

G-9

Display Display format

Set-up window
Display format
0 ...

Screen No:
Type:

Select channel/signal

3 values

OK

Value 1 (Base):
Channels/Signals: Selection

define...

Value 2:

relativ to base
Channel 1
Signal Gross

Value 3:

relativ to base
Channel 2
Signal Gross
Basic channel C3

C1 C2 C3 C4 C5 C6

()

Channel
Gross
Net
Store1
Store2
Store12
Limit1
Limit2
Limit3
Limit4

Cancel

All channels

All signals

1 2 3 4 5 6 7 8 9 10111213141516
4

4
4

MGCplus device

(+)

Display

+2

Channel 3

Net

Value 1

Channel 2

Gross

Value 2

Channel 5

Gross

Value 3

Basic value

MGCplus with AB22A / AB32

G-10

Display Display format

DISPLAY FORMAT

3 values

0 ...

Screen No:
Type:

The setting in the Channels/Signals selection field and the relative


channel number affect the sequence of the values displayed in
measuring mode.

3 values

Value 1 (Base):
Channels/Signals: Selection
Value 2:

Value 3:

define...

relativ to base
Channel 2
Signal Gross
1

Example 1: 6-channel module; 3 values type

relativ to base

Channel
Signal Gross

a) Channels/Signals: + All
The channel selection keys

are used to select all channels in turn,

starting with the basic channel.


Display
Basic value
C3 Value 1
Value 2: Channel+2 rel. C5 Value 2
Value 3: Channel 1 rel. C2 Value 3

C6
C2
C5

Value 1
Value 2
Value 3

C4
C6
C3

Value 1
Value 2
Value 3

C5
C1
C4

Value 1
Value 2
Value 3

C1
C3
C6

Value 1
Value 2
Value 3

C2
C4
C1

Value 1
Value 2
Value 3

Use the cursor keys


(SIGNAL) to display all signals from the
basic channel that were set up in the Select channel/signal menu.

MGCplus with AB22A / AB32

G-11

Display Display format

Display format

3 values
0 ...

Screen No:
Type:

b) Channels/Signals: + select

3 values

Value 1 (Base):
Channels/Signals: Selection

Example 1 (Continued): 6-channel unit; 3 values type

The channel selection keys

are used in measuring mode to select

define...

Value 2:

relativ to base
Channel 2
Signal Gross

Value 3:

relativ to base
Channel 1
Signal Gross

the required channels for the basic channel (in this example 1, 3, 5) one
after the other. The display fields of non-selected channels stay blank.

C3
Value 2: Channel+2 C5
Value 3: Channel 1 C2

Display
Value 1
Value 2
Value 3

C5

Value 1

C4

Value 3

C1
C3

Value 1
Value 2

Use the cursor keys


(SIGNAL) in measuring mode displays all
signals from the basic channel that were set up in the Select
channel/signal menu (in the first display line).

affects
Select channel/signal

Channel 1 2 3 4 5 6 7 8 9 10111213141516
Gross
Net
Store1
Store2
Store12
Limit1
Limit2
Limit3
Limit4

affects

Channel
Channel
Channel

Value 1
Value 2
Value 3

MGCplus with AB22A / AB32

G-12

Display Display format

Display format

Example 2: The net weights of three containers are to be displayed


simultaneously. The following assignment is to apply:

3 values
0 ...

Screen No:
Type:

Container 1 Channel 1

3 values

Value 1 (Base):
Channels/Signals: Selection
Value 2:

Value 3:

Channel
Signal

Channel
Signal

Container 2 Channel 2

define...

Container 3 Channel 3

absolute

Net
absolute

Net

First of all the channel names are specified.


to return to set-up mode.

1. Use the shift key


2. Press

3. Select Channel names from the pull-up menu


and confirm with

4. Enter CONTAINER 1 in the Channel 1 edit field


and confirm with

5. Enter CONTAINER 2 in the Channel 2 edit field


and confirm with

6. Enter CONTAINER 3 in the Channel 3 edit field


and confirm with
7. Press

8. Select Display format from the pull-up menu


and confirm with
9. Use

to select 3 VALUES from the Type selection field and

confirm with

MGCplus with AB22A / AB32

G-13

Display Display format

10. Use

to choose Selection from the Channels/Signals selection

field and confirm with

11. Use

to choose the define... symbol and confirm with

12. Use

to choose the Channel1/Net control field and confirm with

(the control field displays n).


13. Use

to select the key symbol OK and confirm with

14. Use

to choose the Value2:Channel edit field and enter 2.

15. Select the Absolute/relative selection field with


absolute and confirm with
16. Use

to choose the Value3:Channel edit field and enter 3.

18. Select the Absolute/relative selection field with


absolute and confirm with
19. Use

, select

to choose the Signal selection field, select Net and

confirm with
17. Use

, select

to choose the Signal selection field, select Net and

confirm with

To return to measuring mode, press the shift key


security prompt with

and confirm the

MGCplus with AB22A / AB32

G-14

Display Display format

Example 3: One force and one path are to be measured on each of


two presses. The following assignment is to apply:
Force on press 1

Channel 1

Path for press 1

Channel 2

Force on press 2

Channel 3

Path for press 2

Channel 4

A display with three values is required, for which a comparison of the


same signals will have to be made between press 1 and press 2.

Path P1

Store1

Path P2

Store1

Force P1

Store1

Force P2

Store1

Force P1

Store2

Force P2

Store2

First of all the channel names are specified.

CHANNEL NAMES

Channel1:
Channel 2:
Channel 3:
Channel 4:
Channel 5:
Channel 6:

Force P1
Path P1
Force P2
Path P2

to return to set-up mode.

1. Use the shift key


2. Press

3. Select Channel names from the pull-up menu


and confirm with

.
.

4. Enter FORCE P1 in the Channel 1 edit field and confirm with


5. Enter PATH P1 in the Channel 2 edit field and confirm with

MGCplus with AB22A / AB32

G-15

Display Display format

Channel names

6. Enter FORCE P2 in the Channel 3 edit field and confirm with

Channel 1:
Channel 2:
Channel 3:
Channel 4:

7. Enter PATH P2 in the Channel 4 edit field and confirm with

Force P1
Path P1
Force P2
Path P2

Display format

3 values
1

Screen No:
Type:

8. Press

.
.

9. Select Display format from the pull-up menu and confirm with

3 values

Value 1 (Base):
Channels/Signals: Selection
Value 2:

Value 3:

Channel
Signal

Channel
Signal

define...

Channel
Gross
Net
Store1
Store2
Store12
Limit1
Limit2
Limit3
Limit4

Cancel

absolute

Net

11. Use
absolute

12. Use
All channels

to select 3 VALUES from the Type selection field and

confirm with

Net

Select channel/signal
OK

10. Enter 1 in the Number edit field and confirm with

All signals

to choose select from the Display format :

Channels/Signals selection field and confirm with

1 2 3 4 5 6 7 8 9 10111213141516

13. Use

to choose the define... symbol and confirm with

14. Use

to choose the Channel2/Store1 control field and confirm

with
15. Use
with
16. Use

(the control field displays n).


to choose the Channel4/Store1 control field and confirm
(the control field displays n).
to select the key symbol OK and confirm with

MGCplus with AB22A / AB32

G-16

Display Display format

Display Format

3 values
3 values

18. Use

Value 1 (Base):
Channels/Signals: Selection
Value 2:

Value 3:

17. Enter 1 in the Value 2: Channel edit field and confirm with

Screen No:
Type:

Channel
Signal

Channel
Signal

define...

to select relative from the absolute/relative selection field

and confirm with

relative

Store1
relative

Store2

19. Use

to select Store1 from the Signal selection field and

confirm with

20. Enter 1 in the Value 3: Channel edit field and confirm with
21. Use

to select relative from the absolute/relative selection field

and confirm with


22. Use

to select Store2 from the Signal selection field and

confirm with
23. Press shift key

MGCplus with AB22A / AB32

.
and confirm the security prompt with

G-17

Display Display format

1.3.2 Graphic display

YT-Diagram

Type YT-Diagram

This diagram is used to examine changes in measured values over


time.

Gross

Sampling rate
Signal sampling interval.
Channels/Signals

Set-up window
Display Format

YT-Diagram

Screen No:
Type:

0 ...
YT-Diagram

Sampling rate

1s

At this point you define which channels and signals are to be


represented in the display. You can define your settings for all channels
or just for certain ones (Selection) (key symbol define...
). You can
recall a maximum of six signals per channel one after the other.
Define...
The key symbol opens a new window Select channel/signal.

Channels/Signals: Selection
YMax

100...

YMin

100...

define...

MGCplus with AB22A / AB32

G-18

Display Display format

YMax

Set-up window
Display format

YT-Diagram

Maximum display value by reference to present Range 1 (in %).

Screen No:
Type:

0 ...
YT-Diagram

YMin

Sampling rate

1s

Minimum display value by reference to present Range 1 (in %).

Channels/Signals: all

define...

YMax

100...

YMin

100...

Present channel Present measurement signalPresent value


YMax

Gross

Zero point

y-Raster
1 division

YMin
y-Raster
Scale

MGCplus with AB22A / AB32

Time raster Time raster


1 division Scale

G-19

Display Display format

XY-Diagram

Type XY-Diagram
Gross

Sampling rate

Gross

Signal sampling interval.


Channels/Signals
At this point you define which channels and signals are to be
represented in the display. You can define your settings for all channels
). You can
or just for certain ones (Selection) (key symbol define...
recall a maximum of six signals per channel one after the other.
Define...

Setup menu

The key symbol opens a new window Select channel/signal.

Screen
DisplayNo:
format

XY-Diagram

Type:

0 ...
XY-Diagram

Sampling rate:

1s

Value 1 (Base):
Channels/Signals: all

Value 2:

define...

XMax

100...

XMin

100...

Channel
Signal

absolute

Net

YMax

100...

YMin

100...

MGCplus with AB22A / AB32

G-20

Display Display format

YMax

Setup menu
Display format

XY-Diagram

Screen No:
Type:

0 ...
XY-Diagram

Sampling rate:

1s

YMin

Value 1 (Base):
Channels/Signals: all

Value 2:

define...

XMax

100...

XMin

100...

Channel
Signal

absolute

Maximum value on the vertical axis by reference to the present


measuring range (%).

Net

YMax

100...

YMin

100...

Minimum value on the vertical axis by reference to the present


measuring range (%).
XMax
Maximum value on the horizontal axis by reference to the present
measuring range (%).
XMin
Minimum value on the horizontal axis by reference to the present
measuring range (%).
Present channel Present measurement signal
x-Raster
Gross
Scale

YMax
y-Raster 1 division

x-Raster
1 division

YMin

XMin

MGCplus with AB22A / AB32

Gross

XMax

Present
value (x)
y-Raster
Scale
Present
value (y)

G-21

Display Display format

1.4

Status limit switch

Type: Status limit switch

Title
Any user-specific name; it appears in the header (factory setting Limit
switch).

Title

LIMIT SWITCH
1ML30B

Gross

1Limit1

Below 10kN

1Limit2

Below 20kN

1Limit3

NOK

8.483 kN

Status line 1 (base): channel


At this point you define which channels and signals are to be displayed
on the first status line. You can define your settings for all channels or
). You can
just for certain ones (Selection) (key symbol define...
recall a maximum of six signals per channel one after the other.

Measure
Set-up window
Display format

Status limit switch

Screen No:
Type:

0 ...
Status limit switch

Title

Limit switch

Status line 1 (base):


Channels/Signals: all

define...

Status line 2:

Channel 2
LV
1

relativ to base

Status line 3:

Channel 2
1
LV

absolute

Status line 4:

Channel 2
LV
1

absolute

Define...
The key symbol opens new Menu Select channel/signal.
Absolute/relativ to base
This setting lets you define whether a reference to the basic channel is
produced.
Absolute: The measured value and signal of the selected channel are
displayed independently of the basic value. The number entered
corresponds to the actual channel number. Changing channels has no
effect.
Relativ to base: The number entered refers to the basic channel. The
basic channel number is 0. Channels to the left of the basic channel are
entered with a negative sign and those to the right of it are entered with
a positive sign. Caution: This value does not correspond to the actual
(absolute) channel number!

NOTE
Enter the description of the limit switches in the menu.
Options

Limit switches

MGCplus with AB22A / AB32

G-22

Display Display format

1.5

Status data acquisition

Type: Status data acquisition

Bar chart
This diagram shows the current state of data acquisition.
Data acquisition comment

Data acquisition
comment

Bar chart

Test sequence 3

MEAS. RATE: 50Hz


PERIODS: 100

TIME: 00: 00: 00


1
4.0S

16.0S

FILE NAME: MGCP0000.MEA

Get DAQ1

120 MB FREE

Acal

User note (e.g. measurement sequence number).


Measuring rate
The current measuring rate for all the defined channels is shown here.
Time
Time elapsed since the start of the period.
Periods
Number of periods.
File name

Pre trigger

Post trigger

Name of the stored file. When you restart the program, the file is not
overwritten, instead the counter (last four places) is incremented.
xxx MB FREE:

Current period

Shows the amount of free memory on the hard disk.

NOTE
The MGCplus computer detects when the storage capacity on the
hard disk falls below 1 MB. In this case, data acquisition is
cancelle0d and the file is closed.

MGCplus with AB22A / AB32

G-23

Display F-keys

F-keys

2.1

F-keys in measuring mode

F-keys Level 1

Function keys F1...F4 operate in both measuring mode and set-up


mode.

Gross
Channel

Measure

> 0 <

> T <

1st level

II

F-keys Level 2
Acal

Measure

Unit

...

F-keys Level 3
Rem/Loc

Limit_V

In measuring mode you can switch between a total of 9 functions on


three levels:

Start/Stop

F-key field
...

...

F1

Zeroing

F2

Tare

F3

Clear peak value store

2nd level

F1

Autocalibration

F2

Ident (import transducer characteristics)

F3

Switch display unit (see also page E-16)

3rd level

F1

Remote on/off

F2

LIV level

F3

Start/Stop

Key assignment is freely selectable. The assignment listed above is the


factory setting. Key F4 toggles between factory setting and the next
level (...F-level).
You can make the effect of functions apply to all channels or restrict it to
one (of those selected).
In measuring mode the current key assignment is displayed in the lower
display line for all screen types. If you have set the function for all
channels, this is indicated by the ... symbol in the upper right corner
of the F-key field.

MGCplus with AB22A / AB32

G-24

Display F-keys

Function

Effect

Tare

Taring is triggered.

Zeroing

A zero balance is carried out.

Clear stores

Clears the peak value store

Zero/Cal/Measure

Switches between the zero signal, the calibration signal and the measurement signal.

Autocal

Autocalibration is switched on or off.

LED Status/Level

Switches between the Status and Level LED displays.

LIV level

Call the LIV level menu.

Remote/Local

Remote On/Off.

Shunt On/Off

Switches shunt (transducer, AP14) on or off.

Start/Stop display

The measured value currently being displayed is frozen in the indicator (pause function).

Print display

Prints the current display (except for graphics).

Print values

Prints the current measured values.

Print setup

Prints the stored parameter sets.

Load next P-set

Reads the next parameter set from the amplifier(s) (1 to 8).

Load previous P-set

Reads the previous parameter set from the amplifier(s) (1 to 8).

Switch display unit

Switches between the native unit (mV/V), the user-defined unit (for instance kg) and the analogue output
(V).

Start/Stop integration

Integration of peak values is switched on or off.

Start/Stop data acquis.

Data acquisition is switched on or off.

Load data acquis. set

Reads parameter sets from RAM (parameter set 0) or the hard disk (parameter sets 1 to 16).

Load DAQ comments

Reads data acquisition comments from hard disk.

Linearization on/off

Linearization of the transducers characteristic on/off

Ident

Imports transducer characteristic data

Tab 2.1:

Function key shortcuts

MGCplus with AB22A / AB32

G-25

Display F-keys

Select setup window

Set-up window
F-Keys setup

Level 1

1. Use the shift key


Level

to return to set-up mode.

1 ...

F1: Tare
F2: Zero/Cal/Measure One channel
F3: Autocal
One channel
F4: ...F-level
One channel

2. Press

3. Select F-keys from the pop-up menu and confirm with

You are now in the F-keys set-up window.


1
2
3

not assigned
Tare
Zeroing
Clear stores
Zero/Cal/Measure
Autocal
LED Status/Level
LIV level
Remote/Local
Shunt On/Off
Start/Stop display
Print display
Print values
Print setup
Load from XM001
Load next P-set
Load previous P-set
Switch display unit
Start/Stop integration
Start/Stop data acquis.
Load DAQ param. set
Load DAQ comments

One channel
All channels

MGCplus with AB22A / AB32

G-26

2.2

Password
Save/Load
Data acquisition
Interface
Print
Language
Display
System

Display F-keys

F-keys in set-up mode

In set-up mode use the function keys to call the pull-up menus from
the menu bar.
Amplifier

MGCplus with AB22A / AB32

Options

G-27

Display Channel names

Channel names

Select set-up window

Set-up window

1. Use the shift key

Channel name

Channel 3.1

2. Press

to go to setup mode

3. Select Channel names from the pull-up menu and confirm with
Channel name:
System

Force ...

Display

Amplifier

Options

In the set-up window all existing channels have the factory specified
channel names in the first instance.
(e.g.: Empty edit fields indicate free card slots on your unit.)

NOTE
If you wish to apply a new description to an edit field that has
already been described, you can delete the whole of the old entry
using the clear key

MGCplus with AB22A / AB32

G-28

MGCplus with AB22A / AB32

Display Channel names

H-1

System

MGCplus with AB22A / AB32

H-2

MGCplus with AB22A / AB32

H-3

System Password

Password

You can protect all the settings on your unit with a password. In factory setting this password protection is disabled.
Once password protection is activated, the password must be entered each time Setup mode is called (and whenever the unit is switched on again). Only then can the settings be changed. There is no need to enter a password
just for measuring mode.
Access authorisation is linked to the password:

System (all settings can be changed)

Operator (only enabled settings can be changed)

You can define a password and access authorisation for a maximum of nine users.
Important: When the equipment is in ex-factory status, password protection cannot be enabled until a new user
with System access authorisation has been defined.

MGCplus with AB22A / AB32

H-4

System Password

1.1

Define new user

1. Use the shift key


System

Display

Amplifier

Options

2. Press

to go to setup mode

3. Select Password from the pull-up menu and confirm with


Password
Save/Recall
Data acquisition

4. Select the new key symbol with

Interface
Print

and confirm with

.
6. Select the Password edit field with
confirm with

Password
new...

Password:

change...

Access:

set...

delete...

User:
Password:
Access:
OK

Operator
Cancel
Operator
System

MGCplus with AB22A / AB32

, enter your password and

7. Choose the Access: selection field with


access authorisation and confirm with
8. Select the OK key symbol with

Add user

5. Enter the new user names in the User: edit field and confirm with

Language
Time

User:

, select the required


.

and confirm with

H-5

System Password

1.2

Enable password protection

If you are already in the Password setup window, go straight to


point 4.

Password
User:

new...

Password:

change...

Access:

set...

delete...

1. Use the shift key


2. Press

to return to set-up mode.

3. Select Password from the pull-up menu and confirm with


4. Select the set...... key symbol with

and confirm with

Authorisation of the operator

System

Display

Amplifier

Options

Password
Save/Recall
Data acquisition
Interface
Print
Language
Time
Display format
F-keys
Channel names

Yes
No
No
No
No
No
No
No
No
No

Transducer
Conditioning
Display
Analogue output
Switch
Remote contacts
Limit switches
Tie limit switches
Peak value stores
Version

No
No
No
No
No
No
No
No
No
No

OK

Cancel

5. Press

Off

Password protection

6. Use

to choose selection field Password protection

confirm with

Off
On

On

and

If the error message No user with System access is displayed at this


point, press the Cancel key
Off

and press to select

to delete the error message. Use


again. Press

twice. You are now in

the PASSWORD setup window. Now define a user with system


privileges, as described in Chap.1.1.

7. Press
with

(which takes you straight to the OK key) and confirm


.

MGCplus with AB22A / AB32

H-6

System Password

1.3

Set operator access

Password
User:

new...

Password:

change...

Access:

set...

delete...

If you are already in the Password setup window, go straight to


point 4.
1. Use the shift key
2. Press

to go to setup mode

3. Select Password from the pull-up menu and confirm with


4. Select the set... key symbol with

and confirm with

.
.

Authorisation of the operator


Off

Password protection
System

Display

Amplifier

Options

Password
Save/Recall
Data acquisition
Interface
Print
Language
Time
Display format
F-keys
Channel names

Yes
No
No
No
No
No
No
No
No
No

Transducer
Conditioning
Display
Analogue output
Switch
Remote contacts
Limit switches
Tie limit switches
Peak value stores
Version

No
No
No
No
No
No
No
No
No
No

OK

Cancel

MGCplus with AB22A / AB32

and confirm

5. Choose the required No/Yes selection field with


with

6. Select the required set-up with


7. Press
with

and confirm with

(which takes you straight to the OK key) and confirm


.

To return to measuring mode, press the shift key


security prompt with

and confirm the

H-7

System Password

1.4

Delete user

If you are already in the Password setup window, go straight to


point 4.
System

Display

Amplifier

Options

1. Use the shift key


2. Press

Password
Save/Recall
Data acquisition

to return to set-up mode.

3. Select Password from the pull-up menu and confirm with

Interface
Print

You are now in the Password setup window.

Language
Time

4. Select the delete... key symbol with


5. Use

and confirm with

to select the delete... key symbol next to the required

Password
User:

new...

Password:

change...

Access:

set...

delete...

user and confirm with


6. Press
with

(which takes you straight to the OK key) and confirm


.

Delete user
User1:

Miller

delete

User2:

Morgan

delete
delete

User3:
OK

Cancel

MGCplus with AB22A / AB32

H-8

System Password

1.5

Change password

If you are already in the Password setup window, go straight to


point 4.
System

Display

Amplifier

Options

1. Use the shift key

to go to setup mode

2. Press
Password
Save/Recall
Data acquisition

3. Select Password from the pull-up menu and confirm with

Interface
Print

You are now in the Password setup window.

Language
Time

4. Select the change... key symbol with

and confirm with

5. Enter the password in the New password edit field and confirm
Password

with

User:

new...

Password:

change...

Access:

set...

Change password
New password:
OK

Cancel

MGCplus with AB22A / AB32

delete...

6. Press
with

(which takes you straight to the OK key) and confirm


.

System Save/Load

H-9

Save/Load

System

Display

Amplifier

Options

With the Save/Load function you can save the current set-ups for the
AB22A/AB32/CP42 or the amplifier plug-in modules (up to 8 parameter
sets per channel), or load saved setups. You may use Factory setting
to load the ex-factory settings as delivered.
You may even copy settings from one amplifier to another.

Password
Save/Load
Data acquisition

Volatile memory (8h)

Interface
Print
Language

RAM
save

Factory setting

Time

load

EPROM
Save/Load setup
save

load

Factory setting

Internal EEPROM
(8 parameter sets)
Permanent save

Copy

OK
Load parameter
Channel
Param.set
CP

1 2 3 4 5 6 7 8 910111213141516
1 1 1

Automatically from disk

OK

Cancel

Save parameter
1 2 3 4 5 6 7 8 910111213141516

Channel
Param.set

1 1 1

CP

OK

Cancel

MGCplus with AB22A / AB32

System Save/Load

H-10

Save parameter
1. Use the shift key

to go to setup mode

2. Press
3. Select Save/Load from the pull-up menu and confirm with

This takes you to the Save/Load setup set-up window.


4. In the Copy from channel edit field, use
button and confirm with

to choose the save

5. In the Param.set check box, specify the channel number of the


parameter set under which you want your settings to be saved and
confirm with

6. In the Copy from channel edit field, use


symbol OK and confirm with

To return to measuring mode, press the shift key


security prompt with

MGCplus with AB22A / AB32

to select the key

and confirm the

System Save/Load

H-11

Load parameter
1. Use the shift key
System

Display

Amplifier

to return to set-up mode.

Options

2. Press
3. Select Save/Load from the pull-up menu and confirm with

Password
Save/Load
Data acquisition
Interface
Print
Language

button and confirm with

to choose the load

5. In the Param.set check box, specify under the channel number the
parameter set with the settings you want to load and confirm with

Save/Load setup
save

This takes you to the Save/Load setup set-up window.


4. In the Copy from channel edit field, use

Time

load

Factory setting

.
6. In the Copy from channel edit field, use

Copy

symbol OK and confirm with

OK

to select the key

Load parameter
Channel
Param.set
CP

1 2 3 4 5 6 7 8 910111213141516

To return to measuring mode, press the shift key

1 1 1

and confirm the

Automatically from disk

OK

Cancel

security prompt with

Automatically from disk

When the MGCplus is powered up or the hard disk is connected, the


amplifier settings that are stored on the PCMCIA hard disk (CP42) are
automatically loaded into a device that is switched on and standing by.

MGCplus with AB22A / AB32

System Save/Load

H-12

Factory setting

System

Display

Amplifier

Options

A new set-up window opens under Factory setting, and you can then
define whether all amplifiers or only particular ones are to be set to
ex-factory status. You may also load the factory set-ups for the display
and control panel (AB) and communications processor (CP).
1. Use the shift key

to return to set-up mode.

Password
Save/Load
Data acquisition

2. Press

Interface
Print
Language

3. Select Save/Load from the pull-up menu and confirm with


This takes you to the Save/Load setup set-up window.

Time

4. In the Copy from channel edit field, use


Factory setting button and confirm with

Save/Load setup
save

load

to choose the
.

Factory setting

to select the required


5. In the Copy from channel edit field, use
channels (or even AB, CP) from control fields 1 to 16 and confirm

Copy

with
labelled

(a tick appears in the selection box). With the button


All

select all the control fields at once.

OK

6. In the Copy from channel edit field, use


Load factory setup
AB CP

symbol OK and confirm with

to select the key

1 2 3 4 5 6 7 8 910111213141516

All

OK

Cancel

To return to measuring mode, press the shift key


security prompt with

MGCplus with AB22A / AB32

and confirm the

System Save/Load

H-13

Copy setup
System

Display

Amplifier

Options

Some or all of the settings can be sent as required from one channel to
another (or to several). The Copy button is used for this.
1. Use the shift key

Password

to return to set-up mode.

2. Press

Save/Load
Data acquisition

3. Select Save/Load from the pull-up menu and confirm with


This takes you to the Save/Load setup set-up window.

Interface
Print
Language
Time

4. Use

5. In the Copy from channel edit field, use


to select the number
of the channel from which you want to copy the setups and confirm

Save/Load setup
save

to choose the Copy button and confirm with

load

Factory setting

with

Copy

6. In the Copy from channel edit field, use


to select from control
fields 1 to 16 the required channels from which you want to import

OK

settings and confirm with


(a tick appears in the selection box).
If you wish to accept settings from all channels, select the All

Copy setup
Copy from channel:

button and confirm with

to amplifier channels 1 2 3 4 5 6 7 8 910111213141516


All
Whole setup
Remote contacts
Limit switches
Peak values

Transducer
Conditioning
Display
Analogue outputs

OK

7. In the Copy from channel edit field, use


to select from the
vertical control fields the channels from which you want to import
settings, and confirm with

(a tick appears in the selection box).

Cancel

8. In the Copy from channel edit field, use


symbol OK and confirm with

To return to measuring mode, press the shift key


security prompt with

to select the key

and confirm the

.
MGCplus with AB22A / AB32

H-14

System Data acquisition

Recording measurement series

With MGCplus, to record measurement series, you can configure and


save up to 17 data acquisition programs (16 on the hard disk).

PC card harddisk

Saved data is stored in the RAM of communications processor CP42,


or on its PC card harddisk (optional). The following types of harddisks
are supported:

CP42
RS 232
CARDBUS

USB DEVICE

USB HOST

ETHERNET

Harddisk type ATA standard, Type 2 (narrow design, approx. 5 mm


thick)
The maximum capacity is in principle not limited. At the moment the
PC card harddisks up to 5 GB have been tested.
Formatted in FAT-16 or FAT-32 data systems. Other data systems
(e.g. NTFS) are not supported.

As the data rates of these hard disks are generally limited to 1 MB/s, a
maximum of 13 channels of the MGCplus in 4 byte format with a
maximum measurement rate of 19.2 kHz can be recorded.
YE SLAVE
RD ERROR
GN MASTER

IN

CAUTION

SYNC
CTRL I/O
OUT
24V 1 2 GND 1 2
OUT
IN

Avoid electrostatic discharge! The PCMCIA hard disk might be


damaged by static discharge. Touch a grounded object before
installation or wear an approved grounding wristband.
To set the measurement series parameters, use either display and
control panel AB22A/AB32, or the PC software HBM MGCplus
Assistant.

MGCplus with AB22A / AB32

H-15

System Data acquisition

3.1

Setting the measurement series parameters

Select setup window


1. Use the shift key
System

Display

Amplifier

to return to set-up mode.

Options

2. Press the function key

, use the cursor keys to select

Data acquisition and confirm with

Data acquisition

Measuring rate/interval
Required measuring rate (above 1Hz select in Hz) or measuring
interval (below 1Hz select in seconds) for all the defined channels.

DATA ACQUISITION PARAMETERS


50Hz

Measuring rate/interval:
Values: 1000 ...
Periods:

20.00 s...

Time:

Number of values to be measured per period.

10 ...

Channels/Signals:
Trigger:

define...

Length of the period in seconds, minutes or hours.

define...
20.00 % ...

Start condition:

Immediate

Stop condition:

Number of values

NOTE

file on HD
MGCP0000.MEA ...

File name:

change

DAQ comments:

4 Byte Integer LSB...MSB

Format:
Reduction factor:

480

save

Values and Time affect each other. If you define the number of
values for a given period, the time will be calculated and vice
versa.
Periods
Number of periods. If zero is selected here, once the period is started
by an F-key, it will be repeated endlessly.

No

Auto start:
Param. set:

Time

Time stamp:

Pre trigger:

Save to:

Values

read

Example:
s
min
h

50 values
1sec

1000 values
t
20sec
Period 1

20sec
Period 2
MGCplus with AB22A / AB32

H-16

System Data acquisition

Time stamp

System

Display

Amplifier

Options

If time stamp is selected (


the files.

), two additional time columns appear in

Example:
You have selected: Channel 2: Gross; Channel 4: Net, Store1; and
Time stamp.

Password
Save/Recall
Data acquisition
Interface
Print
Language

File name:
Channel2
Gross

Time

Channel4
Net

Channel4
Store1

Time
stamp 1

Carry
Time stamp

DATA ACQUISITION PARAMETERS


Measuring rate/interval:
1:

2400 Hz

Values: 1000 ...


Periods:

50Hz

2: 2400 Hz

100 Hz

3:

20.00 s...

Time:
1000 ...

Channels/Signals:

define...

Trigger:

define...

Time stamp:

Pre trigger:

20.00 % ...

Start condition:

Immediate

Stop condition:

Number of values

No

OK
Param.set:

Cancel
save

If several ( 2) signals are chosen for a channel (e.g Gross and


Net), the maximum measuring rate is reduced to 2400 Hz!
all channels
read

Channel 1 2 3 4 5 6 7 8 9 10111213141516
Gross
Net
Store1
Store2
Comb.PV
Remote

MGCplus with AB22A / AB32

Select channels and signals (Gross, Net Store1, Store2) for the current
measurement series. With all channels, all channels are activated and
deactivated and the signal selection from the first column is retained.

NOTE

file on HD

Save to:
Channel select
Auto start:

Channels/Signals8

2400Hz

H-17

System Data acquisition

Trigger function

DATA ACQUISITION PARAMETERS


50Hz

Measuring rate/interval:
Values: 1000 ...
Periods:

20.00 s...

Time:

Three types of trigger are available:

10 ...

Channels/Signals:

define...

Trigger:

define...

Time stamp:

20.00 % ...

Start condition:

Immediate

Stop condition:

Number of values

3. Measuring rate trigger (with Start and Stop)


A Start or Stop condition (Trigger condition) can be:

file on HD
MGCP0000.MEA ...

File name:

change

DAQ comments:

4 Byte Integer LSB...MSB

Format:
Reduction factor:

Param. set:

No

save

a measurement level

a limit switch

a measurement band

an external input signal

These Start/Stop conditions can be defined independently and


combinated together. The functions AND or OR are available for this
(also see page H-19):

480

Auto start:

1. Start trigger (with a maximum of four trigger conditions)


2. Stop trigger (with a maximum of four trigger conditions)

Pre trigger:

Save to:

If you want to use the Trigger function, you must first define the trigger
conditions.

read

Example
STARTTr. 1

STARTTr. 2

STARTTr. 3

STARTTr. 4

OR

STOP-T
r. 1

STOP-T
r. 2

STOP-T
r. 3
AND

STOP-T
r. 4

Define
Trigger conditions

OR combination
defines Start trigger

AND combination defines

event

Stop trigger event

Setup
Measure

Pre trigger

Time
Get DAQ
(F-key)

Start DAQ

Data acquisition
of a period

Initialise Trigger measurement

DAQ= Data acquisition program

MGCplus with AB22A / AB32

H-18

System Data acquisition

In the example on page H-17, the Start condition could be defined as:

Start-Trigger 1
Start-Trigger 2
Start-Trigger 3
Start-Trigger 4
Stop-Trigger 1
Stop-Trigger 2
Stop-Trigger 3
Stop-Trigger 4
Start-Meas.rate-Trg.
Stop-Meas.rate-Trg.

start measurement if force higher than 5 kN


or
if pressure lower than 5 bar
or
if the temperature is higher than 22oC

Start-Trigger 1

Define trigger
Trigger:

Start-Trigger 1

Type:

Off

Channel:

Mode:

higher

Level:

0.000000% ...

Define trigger
This is where you define whether data acquisition starts immediately or
whether a particular trigger event starts or stops data acquisition.

Signal:

OK

Gross

0.000000% ...

Cancel

Trigger
You can set up to four different Start and Stop triggers and one
measuring rate trigger.
Measuring rate trigger
The Start-Meas.rate-Trigger changes the measuring rate when the
trigger event occurs.
Example:

Off
Measurement level
Measurement band
Limit1
Limit2
Limit3
Limit4
External trigger

MGCplus with AB22A / AB32

The Trigger event will cause a switch from long-term measurement


(e.g. measuring interval = 10000 sec) to dynamic measurement (e.g.
measuring rate = 1200 Hz).
Setting the trigger functions of the des CP22/CP42 digital inputs via the
display and control units AB22A, ABX22A or AB32 is not possible.

H-19

System Data acquisition

Mode

Start-Trigger 1
Start-Trigger 2
Start-Trigger 3
Start-Trigger 4
Stop-Trigger 1
Stop-Trigger 2
Stop-Trigger 3
Stop-Trigger 4
Start-Meas.rate-Trg.
Stop-Meas.rate-Trg.

Off: Trigger inactive


Measurement level:

Trigger:

Start-Trigger 1

Type:

Off

Channel:

Mode:

higher

Level:

0.000000% ...

Trigger condition initiated by measurement


signal when over or below level value.

Example:

Signal:

lower

higher

Measurement level:

Start-Trigger 1

Define trigger

OK

Configure the Start/Stop conditions.

Gross

Level
0.000000% ...

Cancel

Time
Start of the data acquisition
program

Condition met

Example:

Off
Measurement level
Measurement band
Limit1
Limit2
Limit3
Limit4
External trigger

Measurement level: higher

Level

Time
Start of the data acquisition
program

Condition met

MGCplus with AB22A / AB32

H-20

System Data acquisition

Measurement band:

Start-Trigger 1
Start-Trigger 2
Start-Trigger 3
Start-Trigger 4
Stop-Trigger 1
Stop-Trigger 2
Stop-Trigger 3
Stop-Trigger 4
Start-Meas.rate-Trg.
Stop-Meas.rate-Trg.

Trigger condition initiated by


measurement signal when over or
below band limits. The band lies
between Level 1 and Level 2.

Measurement band:

outside

Example:

inside

Start-Trigger 1

Define trigger
Trigger:

Start-Trigger 1

Type:

Off

Channel:

Mode:

higher

Level:

0.000000% ...

Level 2
Signal:

OK

Gross

Level 1
Time

0.000000% ...

Cancel

Start of the data


acquisition program

Condition met

Example:

Measurement band: inside


Off
Measurement level
Measurement band
Limit1
Limit2
Limit3
Limit4
External trigger

Level 2

Level 1
Time
Start of the data
acquisition program

MGCplus with AB22A / AB32

Condition met

H-21

System Data acquisition

Start-Trigger 1
Start-Trigger 2
Start-Trigger 3
Start-Trigger 4
Stop-Trigger 1
Stop-Trigger 2
Stop-Trigger 3
Stop-Trigger 4
Start-Meas.rate-Trg.
Stop-Meas.rate-Trg.

Start-Trigger 1

Define trigger
Trigger:

Start-Trigger 1

Type:

Off

Channel:

Mode:

higher

Level:

0.000000% ...

OK

Limit1-Limit4:

The trigger is initiated by a limit switch


(High: LED on, data acquisition program
starts; Low: LED off).

External trigger:

Trigger initiated by an external signal


(remote contact 7 on the connection
board).

Channel
Source channel for the trigger definitions.

Signal:

Gross

0.000000% ...

Signal
Source signal for the trigger definitions.

Cancel

Off
Measurement level
Measurement band
Limit1
Limit2
Limit3
Limit4
External trigger

MGCplus with AB22A / AB32

H-22

System Data acquisition

Mode:

higher

Level:

0.000000% ...

Signal:

1
2
3
4
5
7
8

Cancel

high, low; low

External trigger

high, low; low

high; high
high; high

Limit switches

inside; outside; outside

lower

inside; inside
low
low

outside

Example: higher
The trigger condition is met if the measurement signal is higher than the
trigger level.

Level 1

Measurement
band

higher; higher

0.000000% ...

OK

higher
lower
lower
higher

Gross

higher; lower; lower

Channel:

Mode

Measurement level

Off

Type

Type:

The trigger type set will determine the different edges you can set:

Trigger:

Start-Trigger 1

Use Mode to define when a trigger condition is met.

Start-Trigger 1

Define trigger

Mode

Gross
Net
Store1
Store2

higher
lower

Off
Measurement level
Measurement band
Limit1
Limit2
Limit3
Limit4
External trigger

MGCplus with AB22A / AB32

Level 2

Level
The level determines the difference value, for comparing with the
measurement signal.
0, 1 or 2 trigger levels are active, depending on the trigger type set.
Type

which level is significant?..

Measurement level

level 1 only

Measurement
band

level 1 and level 2

Limit switches

External trigger

H-23

System Data acquisition

Pre trigger:

System

Display

Amplifier

Options

The Pre trigger input field establishes how many values are recorded
before the trigger event (dividing measurement recording into a Pre
trigger range and a Post trigger range). The entry refers to the Values
input field in the setup dialogue.
Example:

Password

Values: 1200

Save/Recall
Data acquisition

Pre trigger: 20 %

Interface
Print
Language

120 values are recorded in the Pre trigger range and


1200120 = 1080 values are recorded in the Post trigger range.

Time

4
DATA ACQUISITION PARAMETERS

Values: 1200 ...


Periods:

Time:

4.0

define...

Trigger:

define...

Start condition:

Immediate

Stop condition:

Number of values
file on HD

Reduction factor:

Immediate:

Ignore Start trigger. Data acquisition starts


immediately.

AND-combined:

All Start conditions must be met, to start data


acquisition.

OR-combined:

Data acquisition starts if one of the start


conditions is met.

MGCP0000.MEA ...
change

DAQ comments
Format:

Time 4 sec

Start condition:

20.00 % ...

File name:

Pre trigger
in %:

Time stamp:

Pre trigger:

Save to:

s...

1 ...

Channels/Signals:

3.2 sec

0.8 sec

300Hz

Measuring rate/interval:

Post trigger

4 Byte Integer LSB...MSB


480

Auto start:
No
Number
of values
Param.
set:
save
1
Trigger AND-combined
Trigger OR-combined

read

Immediate
Trigger AND-combined
Trigger OR-combined

NOTE
If only 1 trigger is on (e.g. Start-Trigger 1), you must select
AND/OR (although a combination is not possible).

MGCplus with AB22A / AB32

H-24

System Data acquisition

Stop condition:

System

Display

Amplifier

Options

Password

Number of values: Measurement ends, if the given number (entered


under Values) of values is reached.
AND-combined:

All Stop conditions must be met, to end data


acquisition.

OR-combined:

Data acquisition ends, if one of the Stop conditions


is met.

Save/Recall
Data acquisition

Save to:

Interface
Print
Language

file on HD:

Time

NOTE

DATA ACQUISITION PARAMETERS


300Hz

Measuring rate/interval:
Values: 1200 ...
Periods:

Time:

4.0

define...

Trigger:

define...

Time stamp:

Pre trigger:

20.00 % ...

Start condition:

Immediate

Stop condition:

Number of values

Save to:
File name:

Several files:

Save to several files on the hard disk of the


MGCplus (max. 999). If you compress the file, only
one file will be created

Internal RAM:

Save to internal RAM of CP42

If you have chosen Save to file on HD, allocate the file name here.
change

4 Byte Integer LSB...MSB

Reduction factor:
Auto start:

Re-starting the measurement program does not overwrite the file,


instead it increments the counter in the file name (the first four
letters are retained, the last four are incremented).

File name:

file on HD
MGCP0000.MEA ...

DAQ comments
Format:

s...

1 ...

Channels/Signals:

Save to one file on the hard disk of MGCplus.


Enter the name under File name.

480

NOTE

No

Param.
set:
save
1
Number
of values
Trigger ANDcombined
Trigger ORcombined

read

Immediate
Trigger ANDcombined
Trigger ORcombined

MGCplus with AB22A / AB32

Measurement files larger than 2 GB can not be operated on PCs


with the Windows) operating system. The CP42 communication
processor closes files with a file size of 2 GB and then continues
recording in a new file.

H-25

System Data acquisition

Data acquisition comment

System

Display

Amplifier

Options

You may assign any comment you like to a data acquisition. Comments
can be viewed when the Data acquisition type is showing in the upper
left part of the display.
Data acquisition comment: Change
You may change an existing comment, that is, you may enter new or
amended information.

Password
Save/Recall
Data acquisition

Data acquisition comment: Select

Interface
Print
Language

You can select from the comments stored on the PCMCIA hard disk
(see also page G-23, Load data acquisition comment).

Time

Format
Subsequent processing of the values determines the data acquisition
format. You can select three different formats:
4 Byte INT, 2 Byte INT and 4 Byte FLOAT.

DATA ACQUISITION PARAMETERS


50Hz

Measuring rate/interval:
Values: 1000 ...
Periods:

20.00 s...

Time:
10 ...

Channels/Signals:

define...

Trigger:

define...

Time stamp:

NOTE

Pre trigger:

20.00 % ...

Start condition:

Immediate

Stop condition:

Number of values
file on HD

Save to:

MGCP0000.MEA ...

File name:

change

DAQ comments:

4 Byte Integer LSB...MSB

Format:
Reduction factor:

480
No

Auto start:
Param. set:

HBM Software packages such as MGCplus Wizard or catman can


automatically detect all three formats and scale the values
accordingly. If an accuracy of 32767 parts (i.e. measuring range
divided into 32767 parts) is sufficient for your data acquisition, the
2 Byte INT format is advisable, as it only needs half as much
storage space as the two other formats.

save

read

MGCplus with AB22A / AB32

H-26

System Data acquisition

Reduction factor

System

Display

Amplifier

Options

When you activate data reduction (


), an additional data set is
created on the PCMCIA hard disk during data acquisition. This data set
does not store all measured values, but only the extreme values
(Min/Max) recorded at specified intervals.
The interval is determined by the reduction factor in relation to the
measuring rate used.

Password
Save/Recall
Data acquisition

You may input a reduction factor in the range 480 to 32767.

Interface
Print
Language

Example:
MEAS. RATE: 2400 Hz

Time

Reduction factor: 480


2400 Hz 5 Hz
^
200 ms interval
480
DATA ACQUISITION PARAMETERS
50Hz

Measuring rate/interval:
Values: 1000 ...
Periods:

20.00 s...

Time:
10 ...

Channels/Signals:

define...

Trigger:

define...

Time stamp:

NOTE

Pre trigger:

20.00 % ...

Start condition:

Immediate

Stop condition:

Number of values

A reduced data set can only be created if only one signal is being
acquired per channel (Select Gross/Net/Store1/Store2, see page
H-16).

file on HD

Save to:

MGCP0000.MEA ...

File name:

change

DAQ comments:

4 Byte Integer LSB...MSB

Format:
Reduction factor:

480
No

Auto start:
Param. set:

Extreme values will be recorded at 200 ms intervals (acquisition rate


5 Hz).

save

MGCplus with AB22A / AB32

read

System Data acquisition

H-27

. . . format:
Reading a CP42 file
You must know the internal file format to be able to read and interpret the data in the file. A CP42 file is a binary file,
with the following structure:
The following header data precedes the actual data area:
File ID (4 Byte LONG) // currently = 6001
Channel values (4 Byte LONG)
Length of a data row (i.e. one value for all channels/signals) in bytes (4 Byte LONG)
Values of data rows (i.e. values/channel) in the file (4 Byte LONG)
Data format used to save the values ( 4 Byte LONG)
Measuring rate used for recording (4 Byte LONG)
Size of the header area in bytes (4 Byte LONG) // currently = 512
Reserved (4 Byte LONG)
Followed, for each channel, by:
Channel number (4 Byte LONG)
Scaling info: measuring range MR (4 Byte FLOAT)
Scaling info: Offset (zero offset) OS (4 Byte FLOAT)
Unit (4 Byte CHARACTER)
Signal mask (4 Byte LONG)
The signal mask specifies how many values appear in the data row for each channel:
Bit 0 set: GROSS signal
Bit 1 set: NET signal
Bit 2 set: Peak value 1
Bit 3 set: Peak value 2

MGCplus with AB22A / AB32

H-28

System Data acquisition

This means that a maximum of 4 successive values may be displayed for each individual channel.
This channel block is followed by information on date and time:
TimeDate (30 Byte CHARACTER)
The subsequent bytes to the end of the header area are reserved for future use and can be omitted. They are followed, data row by data row (in the example, we assume that Bit 0 (Gross) and Bit 2 (Peak value 1) are set), by the
values:
C1, 1 (Gross)
C1: Channel 1
C1, 1 (PV1)
C2, 1 (Gross)
C2, 1 (PV 1)
________________________________
New data row
C1, 2 (Gross)
C1, 2 (PV 1)
C2, 2 (Gross)
C2, 2 (PV 1)
Each value (measurement) occupies 4 bytes (data formats 1253=LONG and 1257=FLOAT) or 2 bytes (data format
1255=INT). Integer formats are stored in INTEL (TM) format, i.e. MSB > LSB.
The data format used for recording will determine how the source values are re-scaled for
each channel:
1253 (LONG): physical value = (binary source value) / (256*7680000) * MR + OS
1255 (INT): physical value = (binary source value) * 256 / 7680000) * MR + OS
1257 (FLOAT): physical value = (binary source value)
MR: measuring range
OS: offset

NOTE
the 1253 LONG format includes status information in the least significant byte. To call this status, you
should check this byte, before (!) you scale, as dividing by 256 will cause the least significant byte to be
lost.

MGCplus with AB22A / AB32

H-29

System Data acquisition

The structure of the Status byte is given below:


Bit 0:
Output of LIV 1 active, if set
Bit 1:
Output of LIV 2 active, if set
Bit 2:
Output of LIV 3 active, if set
Bit 3:
Output of LIV 4 active, if set
Bit 4:
Gross signal overflow, if set
Bit 5:
Net signal overflow, if set
Bit 6:
Calibration error, if set
Bit 7:
Amplifier settings changed during measurement (e.g. by remote control), if set

MGCplus with AB22A / AB32

H-30

System Data acquisition

Auto start:

System

Display

Amplifier

Options

NOTE
You can store and recall all the settings (Start/Stop conditions
etc.,) in a data acquisition parameter set. To be able to use the
parameter set, you must assign two Function keys:

Password
Save/Recall
Data acquisition

a) Assign the function Recall data acquisition parameters to one


Function key.
Press the F-key to recall the parameter set.

Interface
Print
Language
Time

b) Assign the function Start/Stop data acquisition ( ) to


a second Function key.
Press the F-key to start the data acquisition program.

DATA ACQUISITION PARAMETERS


50Hz

Measuring rate/interval:
Values: 1000 ...
Periods:

20.00 s...

Time:
10 ...

Channels/Signals:

define...

Trigger:

define...

Time stamp:

Pre trigger:

20.00 % ...

Start condition:

Immediate

Stop condition:

Number of values
file on HD

Save to:

MGCP0000.MEA ...

File name:

4 Byte Integer LSB...MSB

Reduction factor:

Param. set:

480
No

Auto start:

YES:

After the data acquisition parameter set has been recalled data
acquisition starts automatically.
A second Function key is not needed.

NO:

After the data acquisition parameter set has been recalled a


second Function key must be used to start
data acquisition ( ).

change

DAQ comments:
Format:

The Auto start function defines what happens after a data


acquisition parameter set has been recalled.

save

MGCplus with AB22A / AB32

read

Param.set:
You can enter parameter set numbers between 0 and 16 (0: parameter
set is stored in the CP42 Flash-PROM; 1 16: parameter set is stored
on the MGCplus hard disk). Numbers must first be assigned, for the
next highest to be displayed.

H-31

System Data acquisition

Save
Data acquisition parameters are stored in the chosen parameter set.
System

Display

Amplifier

Options

You can store up to 16 measurement value data acquisition programs


on the MGCplus hard disk.
Recall

Password
Save/Recall
Data acquisition

A data recording configuration, stored under a ParamSetNo., will be


imported into the MGCplus. You can then view this data acquisition
parameter set, or change it and re-save it, as required.

Interface
Print
Language
Time

DATA ACQUISITION PARAMETERS


50Hz

Measuring rate/interval:
Values: 1000 ...
Periods:

20.00 s...

Time:
10 ...

Channels/Signals:

define...

Trigger:

define...

Time stamp:

Pre trigger:

20.00 % ...

Start condition:

Immediate

Stop condition:

Number of values
file on HD

Save to:

MGCP0000.MEA ...

File name:

change

DAQ comments:

4 Byte Integer LSB...MSB

Format:
Reduction factor:

Param. set:

480
No

Auto start:

save

read

MGCplus with AB22A / AB32

H-32

System Interface

Interface

Use the Interface (Schnittstelle) function to set up the characteristics


of the interfaces:
System

Display

Amplifier

Options

Baud rate

Format (word length, parity, stop bit)

Device address

Password

The CP42 communication processor provides you with RS232, USB


and Ethernet interfaces as standard.

Save/Recall
Data acquisition
Interface
Print
Language

Example 1:

RS232
Format: 8N2 (meaning 8 bits, no parity, 2 stop bits)

Time

Example 2:

The IP addresses and the net mask

Interface setup

RS232 ...

Ethernet ...

USB ...

IEC ...

AB locked during computer control

RS232 setup
Baudrate:

9600 Baud

Format:

8E1

OK

Ethernet

cancel

MGCplus with AB22A / AB32

An IP address always consists of 4 numbers. Each number must be in


the range 1 to 254. Absolute exceptions are the numbers 127.x.x.x and
192.168.x.x. The first of these always designates the local host, i.e.
your own machine. The numbers 192.168.x.x refer to special IP
addresses which are not forwarded over a router. Thus if a network is
numbered 192.168.x.x this automatically ensures that the network
cannot be accessed from outside. The net mask can be used to
determine and define which nodes form part of the in-house network.
This net mask uses a bit pattern to indicate where the network ends
and the computers in the network begin.

H-33

System Interface

Examples:

System

Display

Amplifier

Options

IP:
192.168.001.001
Mask: 255.255.255.000
This refers to a network with the number 192.168.1 and computer
number 1 within that network
IP:
206.001.210.124
Mask: 255.255.000.000

Password
Save/Recall
Data acquisition

This refers to a network with the number 206.1 and the computer with
the number 210.124

Interface
Print
Language
Time

Interface setup
RS232 ...

Ethernet ...

USB ...

IEC ...

Networks are divided into classes. Net mask 255.000.000.000


designated a Class A network. A total of 16,581,375 different
computers can be included in this network. In the case of 255.255.0.0
there are still 65,025. This is called a Class B network. The most usual
form of network is known as Class C. This has the net mask
255.255.255.0 and makes up some 99 % of all the commonly
encountered networks. Up to 254 computers can be connected
together.

AB locked during computer control

Ethernet setup
Adress:

192.168.169.134

SubNetMask:

255.255.255.0

Routeradress:

0.0.0.0

OK

cancel

MGCplus with AB22A / AB32

H-34

System Interface

Router
If data packets are sent via node points, e.g. from the in-house network
to the Internet or a WAN/LAN, a router is needed. This distributes data
packets in different directions on the basis of their addresses.
Routers are computers that have been specially designed for this
purpose, and have their own operating system. It is their task to
analyze millions of IP packets, read their headers and then forward
them in the right direction.

IP address
Subnet mask
Router A address

Computer

Computer

Ethernet

Router A

Worldwide

Computer

Computer

Ethernet

MGCplus with AB22A / AB32

Computer

Router B

H-35

System Interface

If you use a router to access an MGCplus measuring amplifier system


from your PC, the address of its router must be specified in the MGC.
System

Display

Amplifier

Options

Direct Ethernet connection between a PC and MGCplus


Cross cable

Password
Save/Recall
Data acquisition
Computer

Interface
Print
Language

MGCplus

Time

This is by far the most common type of connection. It requires a


crossed patch cable, also known as a cross cable for short.

Interface setup
RS232 ...

Ethernet ...

USB ...

IEC ...

AB locked during computer control

When connecting an MGCplus to a PC through a hub, you need to use


a patch cable.
As delivered, the Ethernet interface for your CP42 is configured as
follows:

Ethernet setup
Adress:

192.168.169.134

SubNetMask:

255.255.255.0

Routeradress:

0.0.0.0

OK

If your computer has an IP address of, say, 172.34.24.13, your


MGCplus should have the IP address 172.34.24.x (x13, x255) if you
are using a subnet mask of 255.255.255.0.

cancel

IP address = 192.168.169.134
Subnet mask = 255.255.255.0
Router = 0.0.0.0

MGCplus with AB22A / AB32

H-36

System Interface

IEEE 488 Settings


Adress:

card type:

NI PCMCIA GPIB

OK

IEC
Settings for the IECbus connection with a
PCMCIAGPIBcard (PCMCIAGPIB, NI488.2).

cancel

Display and control panel in computer operating mode


The display and control panel may be disabled whilst the computer is
operating (factory setting) or can be active. In disabled mode only
status information and measured values are updated.

MGCplus with AB22A / AB32

H-37

System Print

Print

System

Display

Amplifier

Options

Use the Print function to print out the settings for the AB22A/AB32 or
the amplifier module and measured values. You can specify the
required channels and signals for printing out the measured values
under Selection.
1. Use the shift key to switch to

the settings mode.

Password

2. Print

Save/load
Recording

3. In the Pull-Up-menu select Print and confirm with

Interface
Print
Language

You will then be in the Print settings window.


4. In the selection field, select Print via: the required interface and

Time

confirm with

A new settings window is opened under Format..., where the print


format can be set.

PRINT
Print settings via:

USB

AB

Amplifier

Format...

A new settings window is opened under Selection....

Selection...

6. Use

OK

Gross
Net
SPW 1
SPW 2
SPW 12
GW Status

to select the device with which the settings should be

printed out (AB or amplifier) and confirm with

Settings for signals to be printed

SIGNAL PRINTING SELECTION

5. Use

Channel 3
OK

to select the buttons whose settings are to be printed out.

Confirm with
7. Use

(nappears in the selection field).

to select the button OK and confirm with

Abort
All signals

MGCplus with AB22A / AB32

H-38

System Language

Language

Use this function to select the language for the display, the menus and
the Help texts.

System

Display

Amplifier

Password
Save/Recall
Data acquisition
Interface
Print
Language
Time

LANGUAGE
Language: English

English
Deutsch
Francais

MGCplus with AB22A / AB32

Options

H-39

System Time

Time

Use this function to set the date, the day and the time.

System

Display

Amplifier

Options

Password
Save/Recall
Data acquisition
Interface
Print
Language
Time

DATE/TIME SET-UP
Date:

Day ...

Day:

Friday

Time

Hour ...

Month

Min ...

Year ...

Sec ...

MGCplus with AB22A / AB32

H-40

MGCplus with AB22A / AB32

System Time

I-1

Menu structure

MGCplus with AB22A / AB32

I-2

MGCplus with AB22A / AB32

I-3

Menu structure

The menu structure shown below is intended to help you find the set-up menus you are looking for more quickly. At
the same time the necessary sequence of keys is specified for you.
Structural components

F-key assignment in measuring mode (output status)

This key takes you to the first selection menu

Selection bar

or

The lines in the


pull-up menu are
displayed in tiled format.

If a menu does not fit on a


page, it is divided. The
letters in circles guide you
to the next page.

Set-up window

Selection field

MGCplus with AB22A / AB32

I-4

Menu structure

Symbols
mV/V

Selection field

0.000000...

Edit field

measure

measure...

Button (starts action)


Button (opens new set-up window)
Activation fields

Cursor keys
Arrows show the direction in which the keys work

MGCplus with AB22A / AB32

I-5

Menu structure

Measure

System

Display

Amplifier

Options

or

Password

Password
new...

User:
Password:

delete...

change...
set...

Access:

Authorisation of the operator


Off

Password protection
System

Display

Amplifier

Options

Password
Save/Load
Data acquisition
Interface
Print
Language
Time
Display format
F-keys
Channel names

Yes
No
No
No
No
No
No
No
No
No

Transducer
Conditioning
Display
Analogue outputs
Switch
Remote contacts
Limit switches
Combine LIV
Peak value stores
Version

No
No
No
No
No
No
No
No
No
No

OK

Add user
Change password
User:
New password:
OK

Delete user

Password:
Cancel

Access:
OK

Operator
Cancel

User1:

Miller

delete

User2:

Morgan

delete
delete

User3:
Operator
System

OK

Cancel

Cancel

MGCplus with AB22A / AB32

I-6

Menu structure

Measure

System

Display

Amplifier

Options

or

or

Save/Load

Save/Load setup
Save...

Load...

Factory setup...

Copy

OK
Load parameter
Channel
Param.set
CP

1 2 3 4 5 6 7 8 910111213141516
1 1 1

Automatically from disk

OK

Cancel

Copy setup

Load factory setup

Copy from channel:

AB CP 1 2 3 4 5 6 7 8 910111213141516

to amplifier channels 1 2 3 4 5 6 7 8 910111213141516


All
Whole setup
Remote contacts
Limit switches
Peak values

Transducer
Conditioning
Display
Analogue outputs
OK

Save parameter
1 2 3 4 5 6 7 8 910111213141516

Channel
Param.set

1 1 1

CP

OK

MGCplus with AB22A / AB32

Cancel

Cancel

All
OK

Cancel

I-7

Menu structure

Measure

System

Display

Amplifier

Options

or

or

Data acquisition

Data acquisition parameters


Measuring rate/interval:
1: 2400 Hz

2: 2400 Hz

3: 100 Hz
20.00 s...

Values: 1000 ...


Time:
Periods:
10 ...
Channels/Signals:
define...
Trigger:

Time stamp:

define...

s
min
h

1Hz

150Hz 10000s

2Hz

160Hz

5000s

3Hz

200Hz

2000s

4Hz

240Hz

1000s

5Hz

300Hz

500s

6Hz

400Hz

200s

8Hz

480Hz

100s

Pre trigger:
Start condition:

20.00 % ...
Immediate

10Hz

600Hz

50s

15Hz

1200Hz

20s

Stop condition:

Number of values

20Hz

2400Hz

10s

file on HD

25Hz

4800Hz

5s

30Hz

9600Hz

2s

Save to:

MGCP0000.MEA ...

File name:

change

Acq. comment:

48Hz
50Hz

4 Byte Integer LSB...MSB

Format:
Reduction factor:

save

60Hz
75Hz

No

Auto start:
Param. set:

480

80Hz
load

100Hz
120Hz

Channel select
OK

Cancel

all channels

Channel 1 2 3 4 5 6 7 8 910111213141516
Gross
Net
Store1
Store2
Comb.PV

2400Hz

4 Byte Integer MSB .. LSB


4 Byte Integer LSB..MSB
2 Byte Integer MSB..LSB
2 Byte Integer LSB..MSB
4 Byte Float MSB..LSB
4 Byte Float LSB..MSB

Immediate
Trigger AND-combined
Trigger OR-combined

Number of values
Trigger AND-combined
Trigger OR-combined

Remote

MGCplus with AB22A / AB32

I-8

Menu structure

Measure

System

Display

Amplifier

Options

or

or

Data acquisition

Data acquisition parameters


Measuring rate/interval:
1: 2400 Hz

2: 2400 Hz

20.00 s...

Values: 1000 ...


Time:
Periods:
10 ...
Channels/Signals:
define...
Trigger:

3: 100 Hz

Time stamp:

define...

Pre trigger:
Start condition:

20.00 % ...
Immediate

Stop condition:

Number of values
file on HD

Save to:

change

Acq. comment:

4 Byte Integer LSB...MSB

Format:
Reduction factor:

480
No

Auto start:
Param. set:

Define trigger
Trigger:

save

No
Yes

load

Start-Trigger 1

Start-Trigger 1
Off
1

Signal:

Gross

higher

higher
lower
lower
higher

file on HD
internal RAM

MGCP0000.MEA ...

File name:

1
2
3
4
5
7
8

higher
lower

MGCplus with AB22A / AB32

s
min
h

0.000000% ...
OK

0.000000% ...
Cancel

Gross
Net
Store1
Store2

Off
Measurement level
Measurement band
LIV1
LIV2
LIV3
LIV4
External trigger

Start-Trigger 1
Start-Trigger 2
Start-Trigger 3
Start-Trigger 4
Stop-Trigger 1
Stop-Trigger 2
Stop-Trigger 3
Stop-Trigger 4
Start-Meas.rate-Trg.
Stop-Meas.rate-Trg.

I-9

Menu structure

Measure

System

Display

Amplifier

Options

or

or

Interface

Interface setup
RS232...

Ethernet...

USB...
3

AB locked during computer control

OK
Ethernet-setup

OK

USB-setup
Address:

CP42p 00002

OK

Cancel

Address:

172.20.14.182

SubNetMask:

255.255.0.0

Router address:

0.0.0.0

OK

Cancel

RS232-setup
Baud rate:

9600 Baud

Format:

8E1

OK

Cancel

8N1
801
8E1
8N2
802
8E2

300 Baud
600 Baud
1200 Baud
2400 Baud
4800 Baud
9600 Baud
19200 Baud
38400 Baud
57600 Baud

MGCplus with AB22A / AB32

I-10

Menu structure

Measure

System

Display

Amplifier

Options

or

E
Print

RS232

Print setup through :

or

AB

Language

Date/Time setup

Language: English

Date:

Amplifier

Setup of the signals to be printed


Select...

English
Deutsch
Francaise

OK

Select signals for printout


Gross
Net
Store1
Store2
Store12
LIV-Status

Channel 3
OK
Cancel
All signals

MGCplus with AB22A / AB32

Time

Language

Print

RS232
RS485
Printer

Day ...

Day:

Friday

Time

Hour ...

Month

Min ...

Year ...

Sec ...

I-11

Menu structure

Measure

System

Display

Amplifier

Options

or

or

Display format

Display Format

one value
0 ...
one value

Screen No:
Type:

Channels/Signals: all
Off
Status line

define...

Off
On
all
Selection

Select channel/signal
OK
Channel
Gross
Net
Store1
Store2
Store12
LIV1
LIV2
LIV3
LIV4

Cancel

All channels

Channel names

F-keys

All signals

1 2 3 4 5 6 7 8 910111213141516

0...9

free
one value
3 values
6 values
YT-Diagram
XY-Diagram
Status limit switch
Data acquisition

F-keys setup
Level

Level 1

1 ...

F1: Tare
F2: Zero/Cal/Measure One channel
F3: Autocal
One channel
One channel
F4: ...F-level

not assigned
Tare
Zeroing
Clear stores
Zero/Cal/Measure
Autocal
LED Status/Level
LIV level
Remote/Local
Shunt On/Off
Start/Stop display
Print display
Print values
Print setup
Load from XM001
Load next P-set
Load previous P-set
Switch display unit
Start/Stop integration
Start/Stop data acquis.
Load DAQ param. set
Load DAQ comments
Linearisation on/off
Ident

Channel Name

Channel 1

Channel name:

2ML55B

1
2
3
One channel
All channels

MGCplus with AB22A / AB32

I-12

Menu structure

Measure

System

Display

Amplifier

Options

or

or

Transducer

Conditioning

Transducer

Type
SG full bridge
Excitation
5V
kg
Unit:
mV/V
0.0000 ...
0.0000 ...
Zero pt.:
50.0000
...
2.0000 ...
Nom. val.:
measure...
K-Factor:

Conditioning

Channel1

Zero reference:
Zero offset:
Tare:
Disable zeroing:
Low pass 100
High pass Off

measure

Adjust amplifier

Display

Channel1
0.0000 ...
0.0000 ...

V
>0<

V
V >T<
Disable taring: 3
Bessel V

0.0000 ...

3
Hz

Display

Channel1

V
Unit
3 Abs
Decimal places 3 ...
Display range
from 10.000 V
10.000 V
to
Step
100

mV/V
V
%

0.0000 ...

Bessel
Butterworth

OK
1V
2.5V
5V

Two point calibration


1st pt.:
2nd pt.:

kg
0.0000
0.0000
OK

mV/V Shunt off


0.0000 Measure
0.0000 Measure
Cancel

MGCplus with AB22A / AB32

V
g
kg
t
kt
tons
lbs
N
kN
bar
mbar
Pa
pas
.
.

Off
On

100
40
20
10
5
2.5
1.25
0.5
0.2
0.1
0.05

1
2
5
10
20
50
100
200
500
1000

I-13

Menu structure

Measure

Display

System

Amplifier

Options

or
Analogue outputs

Analogue outputs

Switch

Channel1

Switch

Output Vo1: Gross


Output Vo2: Net
Output characteristics ppm
V
0.0000 ...
0.0000 ...
Point 1:
100.0000 ...
0.0000 ...
Point 2:

Gross
Net
Store1
Store2
Comb. PV

Channel 1

>T<

Off
5 Min
once

>0<

Autocal

Off

Param.set

1intern.

Ampl. Input

Zero

Zero
Cal
Measure

Remote

LED display

1intern.
2intern.
3intern.
4intern.
5intern.
6intern.
7intern.
8intern.

Status
Level

Off
Status

Off
On

MGCplus with AB22A / AB32

I-14

Menu structure

Measure

System

Display

Amplifier

Options

or

or
Remote contacts

Remote contacts
Remote
Input 1
Input 2
Input 3
Input 4
Input 5
Input 6
Input 7
Input 8

Limit switches

Combine LIV

Channel 1
On

no function

no function

no function

no function

no function

no function

no function

no function

no function
ACALautocal
TARAtare
CPV1clear store1
HLD1hold store 1
CPV2clear store2
HLD2hold store 2
ZEROzero balance
SHNTShunt ON/OFF
PRNTselect for printing
CALinput to cal. signal
NULLinput to zero signal
INVchange sign
PSEL1select line param. set 1
PSEL2select line param. set 2
PSEL4select line param. set 4
REMTRemote ON/OFF
INTStart/Stop Integration

Off
On

Limit switch 1
Limit switches
Name

1-LIV1 ...

Enable
Input signal

No

Level
Hysteresis

100.000 ...

1.000 ...

Direction
Output logic

Over limit

Delay

LIV output:
Comb.:
Input 1:
Input 2:
Input 3:
Input 4:

Gross

Channel1

AND
LIV 1
LIV 2
LIV 3
LIV 4

Positive logic

define...

Input
Message when ON
Message when OFF

LIV 4
LIV 4 inverted
Remote contact 4
Remote contact 4 inverted

free
1-LIV1 ON...
1-LIV1 OFF...

Normal
Normal

free
disabled
Positive logic
Negative logic
Over limit
Below limit

No
Yes
Gross
Net
Store1
Store2
Store12

LIV-Delay
12 3 4
LIV-On

Delay time

LIV-Off

0ms

OK
OK

MGCplus with AB22A / AB32

Combine LIV

Channel 1
1 ....

Cancel
OK

Normal
Inverse

AND
OR
EXOR
NAND
NOR
NEXOR

1
2
3
4

I-15

Menu structure

Measure

System

Display

Amplifier

Options

or

or
Peak value stores

Peak value stores (PVS)


Store 1 Function
Store 1 Envelope curve
Store 2 Function
Store 2 Envelope curve
Comb. PVS 1-2

Channel 1

Version

Version

KANAL 1

Maximum gross
Off

0.000... s

Maximum gross
Off

0.000... s

Identification:
Comments:

HBM, RD002ML50B, P4.0A


...

Serial and revisionnumber

Off
On

Difference PVS1, PVS2


Mean PVS1,PVS2
Integrate gross
Integrate net

Maximum gross
Maximum net
Minimum gross
Minimum net

MGCplus with AB22A / AB32

I-16

MGCplus with AB22A / AB32

Menu structure

J-1

Specifications

MGCplus with AB22A / AB32

J-2

MGCplus with AB22A / AB32

Specifications Single-channel amplifier plug-in modules

J-3

Single-channel amplifier plug-in modules

1.1

General data

Width
Maximum sampling rate without linearisation

mm
Measured
values/s

20.3 (4 divs)1)
19200

Limit switches
Number
Reference level
Reference value (freely adjustable)
Hysteresis factory setting
Adjustment accuracy

%
%
%

Response time

ms

4
Gross, net, peak values
100 to +100 of the range
1 of the range
0.0033 of the range
1.0
with Butterworth filter > 5Hz
and Bessel filter > 1.25 Hz

Peak value stores


2
Maximum; Minimum
Peak-to-peak; Mean

Number
Function
Tie
Update rate

Clearing the peak value stores (switching to current


measured value)

inside 1ms, through remote contacts

Recording of the current value/peak value


Time constant for envelope function

30
with Butterworth filter > 250Hz
and Bessel filter > 100 Hz

inside 1ms, through remote contacts


s

0.01 ... 10000

V
V
V
V
k

0.5 to +5.5
min. +4.0
max. +0.7
> 1.1
100

V
V
k

> 4.0
< 0.7
1

Remotes (HCMOS)
Inputs (8 lines, connectable as desired)
Permissible input voltage
HIGH level
LOW level
Schmitt trigger, hysteresis
Pull up resistances (internal)

Outputs (Limit switches, Error)


HIGH level with max. 1mA
LOW level with max. 0.7mA
Internal resistance
1)

For the ML38B: 40.6mm (8divs)

MGCplus with AB22A / AB32

Specifications Single-channel amplifier plug-in modules

J-4

Nominal (rated) temperature range


Service temperature range
Storage temperature range

C [F]
C [F]
C [F]

Operating voltages

Card format (Euro)


Weight

mm
g

Connection plug

14.6...17.0; (< 120mA)


7.7...8.3; (< 120mA)2)
+4.9...5.1; (< 150mA)
100 x 160
300
IEC 603-2 indirectly

Analogue outputs Vo1 and Vo2


V
k

10V (asymmetrical)
>5
<5
Amplifier output with zero balance
Output staggered by the tare value
Peak value store 1 output (maximum or minimum)
Peak value store 2 output (maximum or minimum)
Peak value store 3 output (peak combine of 1 and 2)

Monitor output for Vo1 via BNC plug on front panel


Nominal (rated) voltage
Permissible load resistance
Internal resistance

V
k
k

10 (asymmetrical)
> 1000
1

Effect of a 10K-change of the ambient temperature


(effect additional to digital value)
on the outputs Vo1 and Vo2:
sensitivity
zero point

%
mV

< 0.08, typ. 0.04


< 3 typ. 2

Nominal (rated) voltage


Permissible load resistance
Internal resistance
The two output voltages can be used to display the five
signal voltages.

2)

20 ...+60 [4 ... +140]


20 ...+60 [4 ... +140]
25 ...+70 [13 ... +158]

also connectable to 16V

MGCplus with AB22A / AB32

Specifications Single-channel amplifier plug-in modules

1.2

J-5

Single-channel amplifier plug-in module ML01B

Accuracy class

0.03

DC amplifier
Input for voltage measurement
Input signal range (selectable)
Measuring range (digitally adjustable)
Zero offset
Measurement frequency range
Internal resistance of the signal voltage source
Input for thermocouple measurement
Measuring range (digitally adjustable)
Linearisation error (with AP09 connection board)
Linearisation range
NiCr-Ni (K)
Fe-CuNi (J)
Cu-CuNi (T)
NiCr-CuNi (E)
NiCrSi-NiSi (N)
Pt10Rh-Pt (S)
Pt30Rh-Pt6Rh (B)
Pt13RhPt(R)
Max. internal resistance
Temperature range for cold junction 2)
Max. permissible common-mode voltage

symmetrical
V
V
V
Hz

1)
2)

0.0765 ...+0.0765
0.002 ... 0.0765
0.075
0 ... 250 1dB
 1.3

k
oC, [F]
oC
oC
oC
oC
oC
oC
oC
oC
oC
oC

< 0.06

10 ... 3275, [50 ... 5927]


< 0.25 (K, J, T, E, N)
< 0.6 (S, B, R)

158 ... +1414


167 ... +1192
210 ... +393
161 ... +1005
186 ... +1300
+181 ... +1755
+570 ... +1814
+178 ... +1769

191 ... +1414


190 ... +1192
237 ... +393
205 ... +1005
219 ... +1300
50 ... +1755
+160 ... +1814
50 ... +1769

1.3

C, [F]

20 ...+ 60, [4 ...+140]

Input for current measurement


Input signal range
Measuring range (digitally adjustable)
Max. measuring frequency range
Zero offset, adjustable (living zero point)

10.2 ...+10.2
0.4 ... 10.2
10
0 ... 2400 -1dB 1)

62
asymmetrical (to an internal 50 standard resistor)

mA
mA
Hz
mA

50 ...+50
4 ... 50
0 ... 2400 -1dB
0 ...50

With VI > 2.5 Vpp, note limited measuring frequencies


Cold junction included in AP09 connection board

MGCplus with AB22A / AB32

Specifications Single-channel amplifier plug-in modules

J-6

Measuring frequency range


Butterworth low pass

Nom. val. fc
(Hz)
2400 3)
2000 3)
1000 4)
500
250
80
40
20
10
5

1dB
(Hz)
2400
2050
1050
500
246
79
37.5
19
8.9
4.5

3dB
(Hz)
3250
2350
1190
588
291
99
49.5
25.5
12.4
6.2

Phase del.
(ms)
0.28
0.40
0.66
0.90
1.45
3.65
6.0
11
20
42

Rise time
(ms)
0.105
0.170
0.336
0.64
1.3
3.8
7.0
13.3
26
50

Overshoot %
5.2
12
12
11
10
9
7
6
5
4

Bessel low pass

Nom. val. fc
(Hz)
11004)
400
200
100*
40
20
10
5
2.5
1.25
0.5
0.2
0.1
0.05

1dB
(Hz)
1100
445
235
117
38.5
22.0
10.5
5.1
2.6
1.35
0.7
0.17
0.08
0.043

3dB
(Hz)
1780
805
410
210
68
37.5
19.0
9.6
4.8
2.4
1.2
0.3
0.15
0.075

Phase del.
(ms)
0.45
0.7
1.1
1.8
4.3
7.4
12
22
50
100
200
650
1400
3000

Rise time
(ms)
0.23
0.45
0.86
1.7
5.1
9.4
19.0
35.5
70
135
280
1100
2200
4600

Overshoot %
1.3
1.3
1.3
1.3
1
1
0
0
0
0
0
0
0
0

High-pass5)

from 0.2Hz Be; 5Hz Bu


from 2.5Hz Be; 5Hz Bu
from 20Hz Be; 40Hz Bu

Hz
Hz
Hz

0.1
1.0
10

Absolute calibration deviation

0.16)

Linearity deviation

< 0.02 typ. 0.01 % of full scale 7)

Hz

1.25

100

3
40

75
120

Noise rel. to input with filter setting


MR: 75mV
MR: 10V
Thermocouples
Type K, J, T, E, N
Type S, B, R

VPP
VPP
K
K

*) Factory setting
3) Valid for Vipp < 2.5V with Range = 10V (corresp. to 25% modulation of range)
4) Valid for V pp < 5V with Range = 10V (corresp. to 50% modulation of range)
I
5) In the case of resistance thermometers and thermocouples: no function
6) 0.2 % during current measurement
7) For measuring ranges > 3V or > 25mV or > 10mA; otherwise < 0.1% of full scale

MGCplus with AB22A / AB32

typ. 0.1
typ. 1

Specifications Single-channel amplifier plug-in modules

J-7

Long-term drift over 48 hours (Autocalibration on / off)


Meas. range 75 mV
Meas. range 10V
Thermocouples (Autocalibration on / off)
Type J, T
Type E, K, N
Type S, B, R
Effect of a 10K-change of the ambient temperature on the
digital signals S1 and S2
with autocalibration on / off
Sensitivity
Zero point
10V range
75mV range
20mA range
Thermocouples
Type J, T
Type E, K, N
Type S, B, R

V
mV

5 / 10
0.5 / 1

K
K
K

0.25 / 0.5
0.5 / 1
1/2

< 0.02 typ. 0.01 / < 0.2 typ.0.1

mV
V
A

< 0.2 / < 6


< 5 / < 50
< 4 / < 120

K
K
K

0.25 / 2.5
0.5 / 5
1 / 10

Analogue outputs Vo1 and Vo2


Residual carrier voltage (38.4 kHz)
Long-term drift (over 48h)

mVPP
mV

< 12
<3

MGCplus with AB22A / AB32

Specifications Single-channel amplifier plug-in modules

J-8

1.3

Single-channel amplifier plug-in module ML10B

Accuracy class
Excitation voltage ( 5%)
Transducer
SG full and half bridge, potentiometer, piezoresistive
transducer

0.03
V

10

220...5000

2.5

110...5000

60...5000

30...5000

SG quarter bridge

In conjunction with AP14 connection board

Piezoelectric transducer

In conjunction with AP08 connection board

Current-fed piezoelectric transducers (e.g. DeltatronR from


Brel&Kjaer)

In conjunction with AP18i connection board

Perm. cable length between transducer and amplifier


DC amplifier
Measuring ranges
Strain gages (Low)
potentiometer, piezoresistive transducer (High)

max. 5001)

mV/V
mV/V

 0.10...3.06
 10...306

Bridge balance range


Strain gages (Low)
potentiometer, piezoresistive transducer (High)
Charge amplifier

mV/V
mV/V

 3.06
 306

 0.40...12.2
4
 40...1224

6.12
 612

 1.0...30.6
 100...3060

Factory setting
100 m max. distance between connection board and TID/TEDS module
For a max. of 25% modulation (UAPPmax=5V)

12.24
 1224

30.6
 3060

 2.5V

Measuring frequency range


Butterworth low pass

MGCplus with AB22A / AB32

 0.20...6.12
 20...612

Voltage input with max.  2.5V amplitude

Charge amplifier

*)
1)
2)

5 *)

(Hz)
10000
3000
2000
1000
500
250
80
40
20
10
5

(Hz)
8900
2920
2160
1010
500
246
79
37.5
19
8.9
4.5

(Hz)
9900
3480
2500
1165
588
291
99
49.9
25.5
12.4
6.2

(ms)
0.13
0.16
0.24
0.66
0.9
1.45
3.65
6
11
20
42

(ms)
0.05
0.116
0.15
0.35
0.64
1.3
3.8
7
13.3
26
50

%
19 1)
13
12
12
11
10
9
7
6
5
4

Specifications Single-channel amplifier plug-in modules

J-9

Measurement frequency range


Bessel low pass

Nom.val. fc 1dB
(Hz)
100000
100000
50000

Analog output only


(Digital Interface 5000 Hz Butterworth)

1000
400
200
100*)
40
20
10
5
2.5
1.25
0.5
0.2
0.1
0.05
High-pass

(Hz)

111000 188000 0.0027


104000 145000 0.0027
49000 84000 0.0044
900
400
230
117
38.5
22
10.5
5.1
2.6
1.35
0.7
0.17
0.08
0.043

1800
800
405
210
68
37.5
19
9.6
4.8
2.4
1.2
0.3
0.15
0.075

0.27
0.47
0.82
1.58
4.21
7.2
13.9
25
50
100
200
650
1400
3000

Overshoot
%

0.0025
0.0025
0.004

10.8
10.8
6.6

0.2
0.44
0.96
1.8
5.4
9.3
19
37
75
155
300
1200
2300
4600

0.6
0.5
0.4
0.4
0
0
0
0
0
0
0
0
0
0

from 0.2Hz Be; 5Hz Bu


from 2.5Hz Be; 5Hz Bu
from 20Hz Be; 40Hz Bu

Hz
Hz
Hz

0.1
1.0
10

Max. permissible common-mode voltage

6

dB
dB
%
V/V

>120 (DC)
> 95 (DC)
< 0.03 typ. 0.02 full scale
< 0.1/0.2
Strain gage
Potentiometer
(0.2...6.12mV/V)
(20...612mV/V)

Common-mode-rejection
Strain gages
Potentiometers
Linearity deviation
Long-term drift over 48 hours (Autocalibration on/off)
Interference voltages at the output
Noise related to the input
with Bessel low pass

*)
3)

3dB Phase Rise time


del.
(Hz)
(ms)
(ms)

1000 00Hz
50 000Hz
10 000Hz
1000Hz
100Hz

V/Vpp

4
3 3)
3
1.3
0.35

(High)
(Low)

300
300
300
100
35

Factory setting
For half bridge 20V/V. We recommend that you measure only up to a cut-off frequency of 10kHz.

MGCplus with AB22A / AB32

Specifications Single-channel amplifier plug-in modules

J-10

Effect of 10K change in ambient temperature


on digital signals S1 and S2
SG (Low):
Sensitivity
Zero point
Potentiometer (High):
Sensitivity
Zero point
Long-term drift (over 48 h)
SG (Low):
Potentiometer (High):

V/V

When autocalibration
on:
<0.03
<0.6
<0.03
<30

When autocalibration
off:
<0.2
<10
<0.2
<500

V/V
V/V

<0.25
<20

<5
<400

V/V
%

Analogue outputs Vo1 and Vo2


Residual carrier voltage

mVPP

<5

Max. deviation of the analogue outputs from the digital


value

mV

<10

Long-term drift (over 48 h)

mV

<3

MGCplus with AB22A / AB32

Specifications Single-channel amplifier plug-in modules

1.4

J-11

Single-channel amplifier plug-in module ML30B

Accuracy class

0.03
600.15 0.06 (synchronised)
600.00 0.04 (unsynchronised)

Carrier frequency

Hz

Excitation voltage (  5%)

Transducer
SG full bridge

110...5000 (VB= 5V)


60...5000 (VB= 2.5V)
30...5000 (VB= 1V)
In conjunction with AP14 connection board

500 max.

Measuring ranges

mV/V

0.1000 ... 3.0600 (VB = 5V)


0.2000 ... 6.1200 (VB = 2.5V)
0.5000 ... 15.3000 (VB = 1V)

Bridge balance range

mV/V

3.06 (VB = 5V)


6.12 (VB = 2.5V)
15.3 (VB = 1V)

5*)

SG quarter bridge
Permis. cable length between transducer and amplifier

2.5

Carrier frequency amplifier

Measuring frequency range


Butterworth low pass

Nom. val. fc 1dB


(Hz) (Hz)
200
80
40
20
10
5

Bessel low pass

Nom. val. fc 1dB


(Hz)
(Hz)
100*
40
20
10
5
2.5
1.25
0.5
0.2
0.1
0.05

High-pass

*)

from 0.2Hz Be; 5Hz Bu


from 2.5Hz Be; 5Hz Bu
from 20Hz Be; 40Hz Bu

235
88
43
22
10.6
5.3

Hz
Hz
Hz

99
40
20
9.8
4.4
2.35
1.2
0.6
0.17
0.087
0.042

3dB
(Hz)

Phase del. Rise time Over(ms)


(ms)
shoot %

277
103
51
26
12.7
6.3

2.5
4.6
8.2
14
27
52

3dB
(Hz)

Phase del. Rise time Over(ms)


(ms)
shoot %

180
72
35.5
18
8.6
4.4
2.15
1.15
0.31
0.155
0.08

2.7
5.2
9.8
18
35
65
125
220
640
1400
3000

1.4
3.8
7.4
14
30
56

2
4.8
10
20
40
80
160
300
1100
2200
4600

10
9
7
6
5
4

1
1
1
0
0
0
0
0
0
0
0

0.1
1.0
10

Factory settings

MGCplus with AB22A / AB32

Specifications Single-channel amplifier plug-in modules

J-12

Max. permissible commonmode voltage

6V

Commonmode rejection

dB

> 50 (0 ... 600Hz)

Max. differential voltage DC

0.1

V/VPP

< 0.3 1)

Residual carrier voltage (600Hz)


Noise voltage
Effect of 10K change in ambient temperature on digital
signals S1 (gross) and S2 (net):
with autocalibration on
Sensitivity
Zero point
with autocalibration off:
Sensitivity
Zero point
Linearity deviation
Long-term drift over 48 hours (Autocalibration on / off)

V/VPP

< 0.3 (0...200Hz)


< 0.03 (0...1.25Hz)

%
V/V

< 0.01 typically 0.005%


< 0.1

%
V/V

< 0.2
<2

< 0.02, typically 0.01 of full scale 2)

V/V

<0.1/2

mVPP
mV

<3
<3

Analogue outputs Vo1 and Vo2


Residual carrier voltage
Longterm drift (over 48 h)
1)
2)

Measured with UB = 5V and input signal 2mV/V


For ranges > 1mV/V (UB = 5V); otherwise <0.2%

MGCplus with AB22A / AB32

Specifications Single-channel amplifier plug-in modules

1.5

J-13

Single-channel amplifier plug-in module ML35B

Accuracy class

0.03

Carrier frequency

Hz

75

Transducer
Resistors
Resistance thermometers

0...5000
Pt10, Pt100, Pt1000

2001) to 5000 , PT1000


5001) to 500 , PT10, PT100

20 ... 500; 200 ... 5000

Permissible cable length between transducer and


amplifier

Carrier frequency amplifier


Measuring ranges
Supply current

mAeff

Measurement frequency range


Butterworth low pass

1; 0.1
Nom.val. fc 1dB
(Hz)
15
10
5

Bessel low pass

from 0.2Hz Be; 5Hz Bu


from 2.5Hz Be; 5Hz Bu
from 20Hz Be; 40Hz Bu

Linearity variation
0...500
0...5000
Pt10
Pt100
Pt1000
1)
2)

Rise time

3dB Phase
del.
(Hz) (Hz)
(ms)
15
27
18
9.8
18
24
4.4
8.6
35
2.35
4.4
65
1.2
2.15
125
0.6
1.15
220
0.17
0.31
640
0.087 0.155
1400
0.042
0.08
2700

Rise time

(Hz)
16
8.6
5.3

Nom.val. fc 1dB
(Hz)
15
10
5
2.5
1.25
0.5
0.2
0.1
0.05

High-pass2)

3dB Phase
del.
(Hz)
(ms)
23
22
12.2
30
6.3
52

Hz
Hz
Hz

0.1
1.0
10

K
K
K

 0.1
1
 2.5
 0.25
 0.25

(ms)
16
30
56

(ms)
15
20
40
80
160
300
1100
2200
3700

Overshoot
%
7
5
4
Overshoot
%
1.2
0
0
0
0
0
0
0
0

100 m max. distance between connection board and TID/TEDS module


No function available with resistance thermometers and thermocouples

MGCplus with AB22A / AB32

Specifications Single-channel amplifier plug-in modules

J-14

Effect of a 10K-change of the ambient temperature on the


digital signals S1 (gross) and S2 (net):
with autocalibration on:
sensitivity
zero point
with autocalibration off:
sensitivity
zero point
Long-term drift (over 48 h) (Autocalibration on)

%
m
m

< 0.015 typ. 0.0075 %


< 10 (Measuring range 500 )
< 100 (Measuring range 5000 )

< 0.2
< 0.5 (Measuring range 500 )
< 5 (Measuring range 5000 )

< 10 (Measuring range 500 )


< 100 (Measuring range 5000 )

mVpp
mV

<3
<3

Analogue outputs Vo1 and Vo2


Residual carrier voltage
Long-term drift (over 48 h)

MGCplus with AB22A / AB32

Specifications Single-channel amplifier plug-in modules

1.6

J-15

Single-channel amplifier plug-in module ML38B

0.00251)

Accuracy class
Accuracy

%
%

Carrier frequency

Hz

Excitation voltage (5%)

Transducer
SG full bridge

Permissible cable length between transducer and


amplifier

(0.0025 of measured value + 0.0025 of fullscale value)


225.05 0.02
5*)

2.5
30...4000; typ.350
500 max.

Carrier frequency amplifier


Measuring ranges

mV/V

0.2 ... 5.1 (VB = 5V)


0.4 ... 10.2 (VB = 2.5V)

Bridge balance range

mV/V

5.1 (VB = 5V)


10.2 (VB = 2.5V)

Measurement frequency range


Butterworth low pass

Filter levels

Nominal (rated) value

Hz

f1
1.0

f2
1.5

f3
2.5

f4
3

f5
5

f6
6

f7
9

f8
10

f (3dB)

Hz

1.1

1.6

2.3

3.2

4.6

6.3

8.3

10

f (attenuation=1000)

Hz

18.9

21.6

24.5

27.4

30.5

33.8

37.3

41

f (attenuation=1 000 000)

Hz

50

54

57

61

65

68

70

72

Settling time to 99%

0.7

0.5

0.37

0.26

0.2

0.16

0.13

Settling time to 99.999%

2.3

1.6

1.14

0.82

0.58

0.42

0.30

0.23

Nominal (rated) value

Hz

f1
0.03

f2
0.05

f3
0.1

f4
0.2

f5
0.5

f6
0.9

f7
1.5

f (3dB)

Hz

0.03

0.05

0.1

0.22

0.45

0.9

1.7

f (attenuation=1000)

Hz

0.125

0.25

0.5

f (attenuation=1000000)

Bessel low pass

Hz

0.2

0.4

0.8

1.7

3.5

14

Settling time to 99%

32

16

0.5

Settling time to 99.999%

48

24

12

1.5

0.75

digit

1 000 000

Commonmode rejection

dB

> 100

Input resistance

1000

Display resolution

*)
1)

Filter levels

Factory setting
In the event of irradiation, in accordance with EN 61326, table 1
MGCplus with AB22A / AB32

Specifications Single-channel amplifier plug-in modules

J-16

Effect of 10K change in ambient temperature on digital


signals S1 (gross) and S2 (net):
Sensitivity
Zero point (related to full scale value)

%
%

< 0.002 of measured value


< 0.001 of fullscale value

Linearity variation

< 0.002

Longterm drift (over 24 h)

ppm

max. 20, typ. 8

Shortterm drift over 5 min, from 2 h after switchon

ppm

Measuring rate

1/s

max. 10, typ. 3


1.18 / 2.34 / 4.69 / 9.38 / 18.75 / 37.5 / 75

Analogue outputs Vo1 and Vo2


Residual carrier voltage
Longterm drift (over 48 h)

MGCplus with AB22A / AB32

mVPP
mV

<3
<3

Specifications Single-channel amplifier plug-in modules

1.7

J-17

Single-channel amplifier plug-in module ML50B

Accuracy class

0.03
4801.2  0.48 (synchronised)
4800.0  0.32 (not synchronised)

Carrier frequency

Hz

Excitation voltage (5%)

Transducer
Inductive half and full bridge

mH

2.5 ... 30 (VB= 2.5V)


1 ... 30 (VB= 1V)1)

500 max.

Measuring ranges

mV/V

6.00 ... 183.60 (VB = 2.5V)


15.00 ... 459.00 (VB = 1V)

Bridge balance range

mV/V

 183.6 (VB = 2.5V)


 459 (VB = 1V)

Perm. cable length between transducer and amplifier

2.5*)

Carrier frequency amplifier

Measurement frequency range


Butterworth low pass

Nom.val. fc 1dB
(Hz)
1500
1000
500
250
80
40
20
10*)
5

Bessel low pass

Nom.val. fc 1dB
(Hz)
900
400
200
100*)
40
20
10
5
2.5
1.25
0.5
0.2
0.1
0.05

*)
1)

3dB Phase
del.
(Hz) (Hz) (ms)
1600 2180
0.32
1010 1165
0.66
500
588
0.9
246
291
1.45
79
99
3.65
37.5
49.5
6
19
25.5
11
8.9
12.4
20
4.5
6.2
42

(Hz)
900
445
235
117
38.5
22
10.5
5.1
2.6
1.35
0.7
0.17
0.08
0.043

3dB Phase
del.
(Hz)
(ms)
1550
0.47
805
0.7
410
1.1
210
1.8
68
4.3
37.5
7.4
19
12
9.6
22
4.8
50
2.4
100
1.2
200
0.3
650
0.15
1400
0.075
3000

Rise time
(ms)
0.17
0.35
0.64
1.3
3.8
7
13.3
26
50
Rise time
(ms)
0.25
0.45
0.86
1.7
5.1
9.4
19
35.5
70
135
280
1100
2200
4600

Overshoot.
%
7
12
11
10
9
7
6
5
4
Overshoot.
%
4.1
1.3
1.3
1.3
1
1
0
0
0
0
0
0
0
0

Factory setting
with Zener barriers only VB = 1V

MGCplus with AB22A / AB32

Specifications Single-channel amplifier plug-in modules

J-18

High-pass

from 0.2Hz Be; 5Hz Bu


from 2.5Hz Be; 5Hz Bu
from 20Hz Be; 40Hz Bu

Hz
Hz
Hz

0.1
1.0
10

Max. permissible commonmode voltage

6V

Commonmode rejection

dB

> 50 (0 ... 4800Hz)

Max. differential voltage DC

1

Linearity variation

< 0.02, typ. 0.01 of full scale 2)

Residual carrier voltage (4800Hz)


Noise voltage

Long-term drift over 48 hours (Autocalibration on / off)


Effect of a 10K-change of the ambient temperature on the
digital signals S1 (gross) and S2 (net):
with autocalibration on:
sensitivity
zero point
with autocalibration off:
sensitivity
zero point

V/VPP
V/VPP

< 0.33)
< 100 (0...1500Hz)
< 50 (0...100Hz)
< 5 (0...1.25 Hz)

V/V

< 20 / 60

%
V/V

< 0.03 typ.0.002%


< 20

%
V/V

< 0.2
< 120

mVPP
mV

<5
<3

Analogue outputs Vo1 and Vo2


Residual carrier voltage (38.4kHz)
Longterm drift (over 48 h)
2)
3)

for measuring ranges > 60mV/V (VB = 2.5V); otherwise < 0.2%
measured with VB = 2.5V and input signal 80mV/V

MGCplus with AB22A / AB32

Specifications Single-channel amplifier plug-in modules

1.8

J-19

Single-channel amplifier plug-in module ML55B

Accuracy class

0.03

Carrier frequency

Hz

4801.2  0.48 (synchronised)


4800.0  0.32 (not synchronised)

Excitation voltage (5%)

5*)

Transducers
Strain-gage half and full bridge

Inductive half and full bridge

mH

S.G. quarter bridge


Perm. cable length between transducer and amplifier

2.5

110 ... 5000 (VB=5V)


60 ... 5000 (VB= 2.5V)
30 ...5000 (VB= 1V)
2.5 ... 30 (VB= 2.5V)
1 ... 30 (VB= 1V)
In conjunction with AP14 connection board

5001) max.

Carrier frequency amplifier


Measuring ranges
Strain gage

mV/V

Inductive

Bridge balance range


Strain gage

mV/V

Inductive

*)
1)

0.1000 ... 3.0600


0.2000 ... 6.1200
0.5000 ... 15.3000

(VB = 5V)
(VB = 2.5V)
(VB = 1V)

1.5000 ... 45.9000


3.0000 ... 91.8000
7.500 ... 229.500

(VB = 5V)
(VB = 2.5V)
(VB = 1V)

3.0600
6.1200
15.3000

(VB = 5V)
(VB = 2.5V)
(VB = 1V)

45.900
91.8000
229.500

(VB = 5V)
(VB = 2.5V)
(VB = 1V)

Factory setting
100 m max. distance between connection board and TID/TEDS module

MGCplus with AB22A / AB32

Specifications Single-channel amplifier plug-in modules

J-20

Measuring frequency
Butterworth/Bessel low pass
High-pass

from 0.2Hz Be; 5Hz Bu


from 2.5Hz Be; 5Hz Bu
from 20Hz Be; 40Hz Bu

see technical data ML50B

Hz
Hz
Hz

0.1
1.0
10

Max. permissible commonmode voltage

6V

Commonmode rejection

dB

> 50 (0 ... 4800Hz)

Max. differential voltage DC

1

Linearity deviation

< 0.02 typ. 0.01 2)

Noise

Longterm drift over 48 hours (Autocalibration on / off)


Effect of 10K change in ambient temperature on digital
signals S1 and S2
with autocalibration on
Sensitivity
Zero point
with autocalibration off
Sensitivity
Zero point

V/VPP

V/V

Strain gage
< 2 (0...1500Hz)
< 1 (0... 100Hz)
< 0.2 (0...1.25 Hz)

Inductive
< 100 (0...1500Hz)
< 50 (0..100Hz)
< 5 (0...1.25Hz)

< 0.2 / 4

< 20 / 60

Strain gage

Inductive
< 0.02

%
V/V

0.2

%
V/V

<4
< 0.2
60

Analogue outputs Vo1 and Vo2


Residual carrier voltage
Longterm drift (over 48h)
2)

mVPP
mV

for measuring ranges > 1mV/V strain gage (VB = 5V) or > 30mV/V inductive; otherwise < 0,2%

MGCplus with AB22A / AB32

<5
<3

Specifications Single-channel amplifier plug-in modules

1.9

J-21

Single-channel amplifier plug-in module ML55BS6

Accuracy class

0.03

Carrier frequency

Hz

9602.4  0.96 (synchronised)


9600.0  0.32 (not synchronised)

Excitation voltage (5%)

5*)

Transducer
Strain gage half and full bridge

2.5

110 ... 5000 (VB=5V)


60 ... 5000 (VB= 2.5V)
30 ...5000 (VB= 1V)
2.5 ... 20 (VB= 2.5V)
6 ... 19 (VB= 1V)

Inductive half and full bridge

mH

Absolute calibration accuracy

better than 0.5

Permissible cable length between transducer and amplifier

5001) max.

Carrier frequency amplifier


Measuring ranges
Strain gage

mV/V

Inductive

Bridge balance range


Strain gage

mV/V

Inductive

*)
1)

0.1000 ... 3.0600


0.2000 ... 6.1200
0.5000 ... 15.3000

(VB = 5V)
(VB = 2.5V)
(VB = 1V)

1.5000 ... 45.9000


3.0000 ... 91.8000
7.500 ... 229.500

(VB = 5V)
(VB = 2.5V)
(VB = 1V)

3.0600
6.1200
15.3000

(VB = 5V)
(VB = 2.5V)
(VB= 1V)

45.900
91.8000
229.500

(VB = 5V)
(VB = 2.5V)
(VB= 1V)

Factory setting
100 m max. distance between connection board and TID/TEDS module

MGCplus with AB22A / AB32

Specifications Single-channel amplifier plug-in modules

J-22

Measurement frequency range


Butterworth low pass

Nom.val. fc 1dB

Bessel low pass

Nom.val. fc 1dB

(Hz)
3000
1000
500
250
80
40
20
10
5

(Hz)
900
400
200
100*)
40
20
10
5
2.5
1.25
0.5
0.2
0.1
0.05
High-pass

*)

from 0.2Hz Be; 5Hz Bu


from 2.5Hz Be; 5Hz Bu
from 20Hz Be; 40Hz Bu

Factory setting

MGCplus with AB22A / AB32

Hz
Hz
Hz

3dB Phase
del.
(Hz)
(ms)
3600 0.33
1165 0.66
588
0.9
291
1.45
99
3.65
49.5
6
25.5
11
12.4
20
6.2
42

Rise time

3dB Phase
del.
(Hz) (Hz) (ms)
900
1550 0.47
445
805
0.7
235
410
1.1
117
210
1.8
38.5
68
4.3
22
37.5
7.4
10.5
19
12
5.1
9.6
22
2.6
4.8
50
1.35
2.4
100
0.7
1.2
200
0.17
0.3
650
0.08
0.15
1400
0.043 0.075 3000

Rise time

(Hz)
3100
1010
500
246
79
37.5
19
8.9
4.5

0.1
1.0
10

(ms)
0.13
0.35
0.64
1.3
3.8
7
13.3
26
50

(ms)
0.25
0.45
0.86
1.7
5.1
9.4
19
35.5
70
135
280
1100
2200
4600

Overshoot.
%
16
12
11
10
9
7
6
5
4
Overshoot
%
4.1
1.3
1.3
1.3
1
1
0
0
0
0
0
0
0
0

Specifications Single-channel amplifier plug-in modules

J-23

Max. permissible commonmode voltage

6V

Commonmode rejection

dB

> 77 (0 ... 9600Hz)

Max. differential voltage DC

1

Linearity variation

< 0.02, typically 0.01 2)


Strain gage

Noise

Long-term drift over 48 hours (Autocalibration on / off)


Effect of 10K change in ambient temperature on the digital
signals S1 (gross) and S2 (net):
with autocalibration on
Sensitivity
Zero point
with autocalibration off
Sensitivity
Zero point

V/VPP

Inductive

< 2 (0...1500Hz)
< 1 (0... 100Hz)
< 0.2 (0... 1.25 Hz)

V/V

< 100 (0...1500Hz)


< 50 (0..100Hz)
< 5 (0...1.25Hz)

< 0.2 / 0.4

< 20 / 60

Strain gage

Inductive
< 0.02

%
V/V

0.2

%
V/V

< 20
< 0.2
60

Analogue outputs Vo1 and Vo2


Residual carrier voltage
Longterm drift (over 48 h)
2)

mVPP
mV

<6
<3

For measuring ranges > 1mV/V SG (VB = 5V) or > 30mV/V inductive; otherwise < 0.2%

MGCplus with AB22A / AB32

Specifications Single-channel amplifier plug-in modules

J-24

1.10

Single-channel amplifier plug-in module ML60B

Accuracy class

0.01

Input signal
Frequency F1
Direction of rotation F2
Zero index
Transducer error (with AP01i only)
Transducers that can be connected
HBM torque transducers
with AP07/1
with AP17
Frequency signal sources with square wave or sinusoidal
voltage, incremental transducers

Inputlevel
0.1 .. 30 Vp (with control amplifier) or CMOSlevel
0.1 .. 30 Vp (with control amplifier) or CMOSlevel
CMOSlevel
CMOSlevel
T3...FN/FNA, T10FKF1
T10FSF1, T10FSU2
kHz

0.0001 ... 1000

70

Input level
5V set-up
100mV set-up (automat. gain control)

VPP
VPP

5...30
0.1...30

Input impedance

typ. 20

Permissible cable length between transducer and


amplifier

Detection of the direction of rotation

via additional frequency signal (phase-shifted by 90)

Ranges
Frequency measurement

Impulse counting
Maximum impulse counting when pulse counting
Zero point balance range
Ranges to 2kHz
Ranges to 20kHz
Ranges to 200kHz
Ranges to 1 MHz
Noise (10 kHz input signal)
Filter Off
1 kHz LPFilter, Butterworth
100 Hz LPFilter, Bessel
Input filter

MGCplus with AB22A / AB32

Hz

Pulses

100...2000
1 000 ... 20 000
10 000... 200 000
100 000 ... 1 000 000
100 ... 1 000 000

Imp./s

1 000 000

Hz
Hz
Hz
Hz

2000 ...+2000
20 000... +20 000
200 000 ... +200 000
1 000 000 ... +1 000 000

Hz
Hz
Hz

3
1
 0.2
disconnectable Glitch filter

Specifications Single-channel amplifier plug-in modules

J-25

Measuring frequency range

Nom.val. fc 1dB
(Hz)

2000
1000
500
250
80
40
20
10
5

Without filter
Butterworth low pass

Bessel low pass

from 0.2Hz Be; 5Hz Bu


from 2.5Hz Be; 5Hz Bu
from 20Hz Be; 40Hz Bu

2500
2000
1000
470
246
79
37.5
19
8.9
4.5

3100
2400
1200
570
291
99
49.5
25.5
12.4
6.2

Rise time
(ms)

0.4
0.5
0.8
0.9
1.45
3.65
6
11
20
42

Nom.val. fc 1dB
(Hz)
900
400
200
100*)
40
20
10
5
2.5
1.25
0.5
0.2
0.1
0.05

High-pass

3dB Phase
del.
(Hz) (Hz) (ms)

3dB Phase
del.
(Hz) (Hz) (ms)
900 1800
0.6
400
800
0.8
235
410
1.1
117
210
1.8
38.5
68
4.3
22
37.5
7.4
10.5
19
12
5.1
9.6
22
2.6
4.8
50
1.35
2.4
100
0.7
1.2
200
0.17
0.3
650
0.08
0.15
1400
0.043 0.075
3000

Hz
Hz
Hz

0.1
1.0
10

Absolute calibration accuracy

0.005

Long-term drift over 90d

<0.005

Effect of 10K change in ambient temperature on the


digital signals S1 (gross) and S2 (net):

0.005

mVPP
mV

<5
<3

0.12
0.18
0.35
0.70
1.3
3.8
7
13.3
26
50
Rise time
(ms)
0.35
0.52
0.86
1.7
5.1
9.4
19
35.5
70
135
280
1100
2200
4600

Over
shoot
%
8
10
8
11
10
9
7
6
5
4
Over
shoot
%
0
1.0
1.3
1.3
1
1
0
0
0
0
0
0
0
0

Analogue outputs Vo1 and Vo2


Residual carrier voltage (38.4kHz)
Long-term drift (over 48 h)
*)

Factory setting

MGCplus with AB22A / AB32

Specifications Connection boards

J-26

AP01i

Connection boards for one-channel amplifiers

AP 02

AP01i (connection board with D-female receptacle)


Width

mm

20.3 (4 divs)

Transducer connection

D15 female receptacle, DA-15P 1)

Output-signal connection

D25 female receptacle, DB-25P 2)

Option

2x EM001; 2x RM001 with AP02

Weight, approx.

kg

0.3

mm

20.3 (4 divs)

AP02 (connection board for 2 relay modules)


Width

37-pin D-Sub male connector, DC-37P 3)

Output-signal connection
Option
Weight, approx.

2x RM001
kg

0.3

AP03i
AP03i (connection board with MS-female device receptacle)
Width

mm

D25 female receptacle, DB-25P 2)

Output-signal connection
Option
Weight, approx.
1)
2)
3)
4)

MGCplus with AB22A / AB32

HBM-order number 3-3312.0182


HBM-order number 2-9278.0293
HBM-order number 2-9278.0294
HBM-order number 1-MS3106 PEMV

40.6 (8 divs)
7-pin MSfemale receptacle, MS3106A 16S-1P 4)

Transducer connection

2x EM001, 2x RM001 with AP02


kg

0.3

Specifications Connection boards

AP07/1

J-27

AP07/1 for connection of T3..FNA and T10.. torque transducers


Width

mm

40.6 (8 divs)

Supply during measurement


Supply for calibration
Frequency

VPP
VPP
kHz

54
81
15 ... 20
7-pin MSfemale receptacle, MS3106A 16S-1P 4)

Transducer connection

D25 female receptacle, DB-25P 2)

Output-signal connection
Option
Weight, approx.
2)
4)

EM001; RM001
kg

0.5

HBM-order number 2-9278.0293


HBM-order number 1-MS3106 PEMV

MGCplus with AB22A / AB32

Specifications Connection boards

J-28

AP08

AP08 for piezoelectric transducers


Width

mm

20.3 (4 divs)

Connections
Transducer*)
Range capacitors Cg
Measuring ranges
Accuracy
Measuring range 100 pC
Measuring range 100 pC
Measuring frequency range
1000 pC/Cg=100 pF, 1 nF
10000 pC/Cg=10 nF
100000 pC/Cg=100 nF
Linearity deviation

BNC-female receptacle, isolated


D25 female receptacle
nF
pC

0.1
30...100

1
50...1000

10
500...10 000

100
5000...100 000

%
%

2.5
1

kHz
kHz
kHz
%

100 (1dB)
15 (1dB)
1.5 (1dB)
0.25 full scale

Low pass filter

according to the data sheets of ML01B and ML10B

Option

1xEM001; 2xRM001 with AP02

s
s

10...10 000
0.1...100

m
m

100
200

pC
pC/s

< 1
0.1

%
%
C [F]

0.2 full scale


0.1 full scale
20...+60 [4...+140]

Low pass filter

according to the data sheets of ML01B and ML10B

Weight, approx.

kg

0.3

Time constant ( t = Cg Rg)


Long
Medium (Rg=100G)
Short (Rg=1G)
Maximum cable length
Range capacitor Cg=100 pF
Range capacitor Cg 1 nF
Zero offset (during zero/measure
changeover)
Drift (at 20C)
Effect of a 10K-change of the ambient
temperature
on the sensitivity
on the zero point
Operating temperature range

*)

MGCplus with AB22A / AB32

Please note the advices on page B-55, if the transducer connection cable is used outside of closed rooms.

Specifications Connection boards

AP09

AP11i

J-29

AP09 for connection of thermocouples


Width

mm

20.3 (4 divs)

Accuracy
with 25C
with 20 ... 60C

C
C

0.3
1
Terminal screws (0.5...1.5mm2)

Transducer connection
Temperature cold junction
Reference-point measuring range

Semiconductor temperature-sensor at the


terminal screw
C [F]

Option
Weight, approx.

20...+60 [4...+140]
2x EM001; 2x RM001 with AP02

kg

0.3

AP11i (connection board with LemoR-female device receptacle)


Width

mm

D25 female receptacle, DB-25P 2)

Output-signal connection
Option
Weight, approx.
1)
2)

20.3 (4 divs)
6-pin LemoR FGG.1B.306 1)

Transducer connection

2x EM001; 2xRM001 with AP02


kg

0.3

HBM-order number 3-3312.0126


HBM-order number 2-9278.0293

MGCplus with AB22A / AB32

Specifications Connection boards

J-30

AP13i

AP13i for PLC I/O cards; all inputs and outputs are electrically isolated by optical couplers
Width

mm

20.3 (4 divs)

Outputs (short-circuit proof; protective circuit for inductive loads)


Values
Separate grounding systems
Nominal (rated) voltage (ext. supply)
Permitted voltage range
Output current
Short-circuit current
Permissible short-circuit period
Switching frequency on resistive load

V
V
A
A
Hz

Input/Output

5
2
24
6 ... 48
max. 0.5
0.8
unlimited
max. 500
D-female receptacle 15/25-pin

Option

1x EM001

Inputs
Values
Separate grounding systems
Input voltage for
Low level
High-level
Input current at 24V
Current consumption internal 5V
external 24V
Maximum power loss
Permissible short-circuit period

8
4
V
V
mA
mA
mA
W

<5
> 10
12
13
7.5 (without load)
10.5
unlimited

Permissible lead length

approx. 1000

Weight, approx.

kg

0.3

MGCplus with AB22A / AB32

Specifications Connection boards

AP14

J-31

AP14 for Single SG


Width
Options
Accuracy class
Full bridge
Half bridge
Quarter bridge

mm

20.3 (4 divs)
1 EM001 output stage module, 2xRM001 with AP02

%
%
%

0.1
0.5
0.5

Connectable transducer

Half and full bridges, single strain gage


in 3-wire or 4-wire technology

to use with following amplifier plug-in


modules
Connections
Transducer
Analogue output, control signals
Internal completion resistors

ML10B, ML30B, ML55B


D15 female receptacle, DB25P
D25 female receptacle, DB25P

120, 350, 700

Max. permissible cable length between


transducer and connection board

500

Linearity deviation

0.05

kHz

0...50

Measurement frequency range


Effect of 10K change
of ambient temperature
on zero point
on measurement sensitivity
Operating temperature range
Weight, approx.

%
%

Full bridge

Quarter bridge, half bridge

0.05
0.05

0.5
0.1

C [F]

20...+60[4...+140]

kg

0.3

MGCplus with AB22A / AB32

Specifications Connection boards

J-32

AP17

AP17 for connecting torque flanges T10FSF1, T10FSU2 and frequency signals to ML60B
Width

mm

20.3 (4 divs)

Transducer connection

D15 female receptacle, DA-15P 1)

Analogue output/remotes

D25 female receptacle, DB-25P 2)

Nominal (rated) temperature range

C [F]

Option
Weight, approx.

20 ...+ 60 [4 ... +140]


1x EM001, 2x RM001 with AP02

kg

0.3

V (DC)
V (DC)
V (DC)
V (DC)

+16 (max. 500mA)3)


16 (max. 500mA)3)
+5 (max. 300mA)3)
approx. 5 (max. 100mA)

VPP
VPP

10
5

VPP
V0P
V
kHz

0.3 / 14
3 / 20
5 ...+ 4
1000 (with ML60B max. 200)

Outputs
Transducer supply

Release of calibration signal


Inputs
Nominal (rated) input voltage
symmetrical
asymmetrical
Minimum/maximum voltage swing
symmetrical
asymmetrical
Common-mode voltage range
Maximum input frequency
1)
2)
3)

MGCplus with AB22A / AB32

HBM order number 3-3312.0182


HBM order number 2-9278.0293
The specified current values are the maximum permissible permanent currents for AP17. The number of con
nection boards per housing is not limited, however, a maximum of four connection boards can be used for the
transducer supply (5V/16V e.g. for T10FSF1 torque flange).

Specifications Connection boards

AP18i

J-33

AP18i for current-fed piezoresistive transducers


Accuracy class

Width

mm

20.3 (4 divs)

Transducer excitation*)

mA

2.5...20 (adjustable); 4 (factory setting)

Current source dynamic impedance

30 typ.

Input voltage range

12 9 (3...21V)

Load resistance

>5

Input sensitivity

0.1; 1V; 10V ( 0.05 dB )

Hz
Hz
Hz
Hz
Hz
Hz

0.18...15 000
0.10...25 000
0.18...17 000
0.10...31 000
0.18...22 000
0.10...43 000

0.04 of full scale

Vms
Vms
Vms

30
30
75

dB
dB

70 (typically)
60 (typically)

Frequency response
Input sensitivity 0.1V
Input sensitivity 1V
Input sensitivity 10V

for 1 dB
for 3 dB
for 1 dB
for 3 dB
for 1 dB
for 3 dB

Effect of 10K change


in ambient temperature
Noise referred to the input (2Hz...22.4kHz)
Input sensitivity 0.1V
Input sensitivity 1V
Input sensitivity 10 V
Distortion

at 1kHz
at 8 kHz

Option
Weight, approx.
*)

Current output stage


kg

0.3

Please note the advices on page B-55, if the transducer connection cable is used outside of closed rooms.

MGCplus with AB22A / AB32

Specifications Multi-channel amplifier plug-in modules

J-34

Multi-channel amplifier module ML455

ML455 + Connection board

AP455i/AP455iS6

Accuracy class

0.1

Accuracy

(0.1 of measured value+0.1 of fullscale value)

Carrier frequency

Hz

4801.20.48

Bridge excitation voltage (5%)

2.5

Connectable

transducers*)

in 6- (5) wire technique

Permissible cable length between transducer and connection board1)

Strain-gage half- or full bridge


Inductive half- or full bridge
LVDT
m

100

Measuring ranges
Strain-gage

mV/V

4

Inductive

mV/V

100

LVDT

mV/V

1000

120 ... 1000

mH

4 ... 330

Transducer impedance
Strain-gage half- or full bridge
Inductive half- or full bridge, LVDT
Noise at 25C [77F]
Butterworth/Bessel
1000 Hz/40 Hz
80 Hz/200 Hz
20 Hz/5 Hz
5 Hz/1.25 Hz
Linearity deviation

mV/V
mV/V
mV/V
mV/V

Operating temperature range

%
%
C [F]

Transducer connection
AP455i
AP455iS6
Width
*)
1)
2)
3)
4)

LVDT
< 140
< 28
< 14
< 6

< 0.02
Autocal on

Autocal off

< 0.01
< 0.005

< 0.03
< 0.01
20...+60 [4 ... +140]

4x15-pin Sub-D
6-pin LemoR FGG.1B.3064)
mm

The transducer type can be selected separately for each of the four subchannels
Use cable twisted and shielded in pairs with outer shield (e.g. HBM-no. 43301.0071)
Of measured value
Of fullscale value
HBM-order number 3-3312.0126

MGCplus with AB22A / AB32

Inductive
< 30
< 3
< 1.5
< 0.5

Effect of a 10Kchange of the ambient temperature


on sensitivity2)
on zero point3)

Strain-gage
< 3
< 0.5
< 0.2
< 0.1

20.3 (4 divs)

Specifications Multi-channel amplifier plug-in modules

J-35

Multichannel amplifier module ML455 and connection board AP455i


ML455
ML 455

AP455i

AP455iS6
AP455iS6

Subchannel 1

Subchannel 2

Subchannel 3

Subchannel 4

MGCplus with AB22A / AB32

Specifications Multi-channel amplifier plug-in modules

J-36

Multi-channel amplifier plug-in module ML460

ML460 + connection board


Accuracy class
Connectable transducers
HBM torque transducers2)
Frequency signal sources with square-wave or
sine-wave voltage, incremental transducers
Inductive rotation speed measuring devices (T-R coils)
using input filtering
Measuring ranges
Frequency measurement

Accuracy, related to fullscale value


Pulse counting
Maximum impulse rate when pulse counting
Precision
PWM carrier frequency
Precision
Pulse duration
Precision
Input frequency range
Mechanical
Nominal (rated) temperature range
Operating temperature range
Storage temperature range
Operating voltages

Max. number of amplifier modules per 19 housing


with battery operation (NT011T)
Card format
Width
Connections
Designation of suitable male connector
(Manufacturer LemoR)

1)
2)

AP460i
0.011)

kHz

T4WA-S3, T3...FN/FNA, T10F...KF1, T10F...SF1, T10F...


SU2
0.0001...500

kHz

0.5...200

kHz

0 ... 2
0... 20
0 ... 200
0 ... 500
0.01

Pulses
PPS
Kimp

100 ... 1 000 000


500 000
0.001

Hz
%
ms
ms
Hz

1 ... 10 000
0.05
0 ... 2500
0.001
0.25 ...10 000

_C
_C
_C
V

20 ...+ 60
20 ...+ 60
25 ... +70
+5 (<240 mA)
+16 (<100 mA)
+8 (<10 mA)
8 (<10 mA)

mm
mm

10
Europe 100 x 160
20.3 (4 divs)
LemoR 1B 10pin EXG.1B.310.HLN
Fixed plug (1st letter in model desig.) : F
Key (3rd letter in model desig.) : G
Series: 1B
Type: 310
Example: FGG.1B.310.CLAD62
(Bold characters must be selected)

0.05 in the case of PWM


These torque transducers are not supplied via the connection plate AP460i

MGCplus with AB22A / AB32

Specifications Multi-channel amplifier plug-in modules

J-37

Channel properties
Number of subchannels

Class accuracy

0.01

Signals per subchannel


F1
F2
Zero index
Electrical separation of all inputs from one another and
from MGC ground
Input frequency range

Frequency, pulse or PWM signal


90 phase shift relative to F1 (direction detection)
For detection of zero position in pulse counting
V

Typically 500V

kHz

0...500

MGCplus with AB22A / AB32

Specifications Multi-channel amplifier plug-in modules

J-38

Input signals
Direct inputs, difference signals
Input voltage range

VPP

0.4 ... 30

VPP

0.4 ... 30

V
ms

5...30
3

Direct inputs, bipolar


Input voltage range
Direct inputs, unipolar
Input voltage range
Minimum pulse width
Input for inductive transducer, filtered (F1 signals only)
Required minimum input voltage (peak-to-peak)
500 Hz
1 kHz
10 kHz
25 kH
50 kHz
75 kHz
100 kHz
125 kHz
150 kHz
175 kHz
200 kHz
Maximum input voltage
Input resistance F1 signal

50 mV
100 mV
750 mV
1V
1.5V
2V
2.5V
3V
4V
5V
7V
V

30

approx. 6

Transducer excitation
Maximum current per module
5V
8V
16V

MGCplus with AB22A / AB32

16 modules/device
10mA
62.5mA
62.5mA

1 module/device
160mA
1A
1A

Specifications Multi-channel amplifier plug-in modules

Measuring frequency range

J-39

Nom. val. fc 1dB


(Hz)

Without filter
LowPass with ButterworthCharacteristic

LowPass with BesselCharacteristic

3dB Phase del. Rise time

(Hz)

(Hz)

740

1750

<0.6

500
250
80
40
20
10
5

450
250
83
41
20
9
5

550
290
99
49.5
25.5
12.4
6.5

1.5
2.5
5
7.5
12
25
46

1
2.1
6.2
13
24
50
100

9.4
12
8.5
7.8
7
4.7
4.7

Nom. val. fc 1dB


(Hz)
400
200
100*)
40
20
10
5
2.5
1.25
0.5
0.2
0.1
0.05

(Hz)
380
235
125
43
24
11
4
2.6
1.35
0.7
0.17
0.08
0.04

(ms)

(ms)

Over
shoot
%

3dB Phase del. Rise time


(Hz)
650
380
210
70
40
18
10
4.8
2.4
1.2
0.3
0.15
0.075

(ms)
1.4
1.5
2.6
5.2
7.4
15.7
27
53
104
195
730
1480
3000

(ms)
1
1.75
3
7.5
15
31
55
125
210
450
2000
3700
7500

Over
shoot
%
1
1
2
1
1
0
0
0
0
0
0
0
0

MGCplus with AB22A / AB32

Specifications Multi-channel amplifier plug-in modules

J-40

ML460 multi-channel amplifier module and AP460i connection board


ML460
ML460

ERROR
O
V
E
RL
O
A
D

AP460i
AP460i

CHAN
1
2

Subchannel 1

3
4
1

S
I
GN
A
L

2
3

Subchannel 2

Subchannel 3

Subchannel 4

MGCplus with AB22A / AB32

Specifications Multi-channel amplifier plug-in modules

J-41

Multi-channel amplifier plug-in module ML801B

AP8011)

ML801B + connection board


Accuracy class

AP8092)

Width

Thermocouples
Type K, J, T, E,
N, S, B, R

mm

Maximum sampling rate per channel

0.05

Thermocouples
Type K, J, T, E,
N, S, B, R, Individual inputs
electrically isolated

Pt100
4wire circuit

20.3 (4divs)

values/s

2400

Measuring frequency range

kHz

0 ... 1

Effective resolution

Bit

Max. permissible input voltage and common-mode voltage

Absolute calibration deviation

with cold junction

2)
3)
4)

0.2

8
10V
symmetrical

Transducers

1)

AP8354)

0.05

Number of measuring points

Filter

AP4093)

20
50

10

50

0.05

Butterworth low pass

0.5

Nom. val fc

fg max
1dB

3dB

(Hz)
1000
500
250
200
80
1000
500
250
200
80
250
200
80
40
20
10
5

(Hz)
1189
523
253
203
78
1206
613
255
203
78
312
226
82
41
21
10
5.3

(Hz)
1518
691
322
265
103
1516
816
327
264
102
413
300
109
54
27
13
7

Internal
sampling rate
9600
9600
9600
9600
9600
4800
4800
4800
4800
4800
2400
2400
2400
1200
600
300
150

Connection plug on customer side: e. g. Phoenix Contact MC1.5/3-ST-3.5; Art. No. 1840379
(Connection plug for AP801S6: LemoR FFA0B.304 CLAD52)
No line break recognition
Two AP409 can be operated with one ML801B
Connection plug on customer side: LemoR FFA.0S.304.CLA

MGCplus with AB22A / AB32

J-42

ML801B + connection board

Specifications Multi-channel amplifier plug-in modules

AP801

Low pass Bessel

AP409

Nom. val fc

fg max
1dB

3dB

(Hz)
200
100
40
20
10
5
2.5
1
0.5
0.2
0.1
0.05

(Hz)
259
102
41
20
10
5
2.5
1
0.5
0.21
0.1
0.051

(Hz)
448
184
75
36
18
9
4.5
1.8
0.9
0.38
0.19
0.094

Nom. val fc

fg max
1dB

3dB

(Hz)
1000
500
250
200
80
40
20
10
5

(Hz)
1076
596
279
214
78.9
38.7
19.5
9.36
4.37

(Hz)
1282
798
345
266
103
51.8
27.2
13.2
6.4

Low pass Butterworth compatible

MGCplus with AB22A / AB32

AP809

AP835

Internal
sampling rate
2400
2400
2400
2400
2400
1200
600
300
150
75
37.5
18.7
Internal
sampling rate
4800
4800
2400
2400
2400
2400
2400
2400
1200

Specifications Multi-channel amplifier plug-in modules

J-43

ML801B + connection board

AP801

AP809

AP409

Nom. val fc

fg max
1dB

3dB

(Hz)
200
100
40
20
10
5
2.5
1
0.5
0.2
0.1
0.05

(Hz)
322
125
41
21
11
5.5
2.7
1.36
0.68
0.186
0.093
0.047

(Hz)
571
216
70
37
19
9.6
4.8
2.4
1.2
0.186
0.158
0.079

Low pass Bessel compatible

AP835

Internal
sampling rate
2400
2400
2400
2400
2400
2400
1200
600
300
75
37.5
18.7

Input for voltage measurement


Input range
Zero offset

V
mV

10.5...+10.5

V
mV

10.5...+10.5

80...+80

80...+80

80...+80

80...+80

Internal resistance of the voltage source

Input resistance symmetric/asymmetric

500/250

2000/1000

1000

mVSS

< 50

< 0.5

<2

mV

0.8/1.5

0.01/0.02

0.02/0.05

<0.03;
typ. 0.01

<0.03;
typ. 0.01

<0.06;
typ. 0.03

V
mA

8/16
50

Noise voltage rel. to input at 1.25 Hz filter


Longterm drift over 48 hours with/without autocalibration
Linearity deviation
Transducer excitation5) (only AP801S6)
Supply voltage for transducers (can only be selected collectively for all channels)
Max. output current for external transducers

< 1.0

5) A total of max. 2 A for transducers supply may be withdrawn from the MGC

MGCplus with AB22A / AB32

Specifications Multi-channel amplifier plug-in modules

J-44

ML801B + connection board

AP801

AP809

AP409

AP835

< 0.06

< 0.25 (K, J, T, E, N)

< 0.6 (S, B, R)

NiCrNi (K)

158...+1414

191...+1414

FeCuNi (J)

167...+1192

190...+1192

CuCuNi (T)

210...+393

237...+393

NiCrCuNi (E)

161...+1005

205...+1005

NiCrSiNiSi (N)

186...+1300

219...+1300

Pt10RhPt (S)

+181...+1755

50...+1755

Pt30RhPt6Rh (B)

+570...+1814

+160...+1814

Pt13RhPt (R)

+178...+1769

50...+1769

Type K, J, T, E, N

0.2/0.4

0.5/1

Type S, B, R

1.0/2.0

2/3

Type K, J, T, E, N

< 0.1

< 0.1

Type S, B, R

< 0.3

< 0.3

Measuring range

500

Linearisation error

< 0.02

Input for thermocouples


Linearisation error

Linearisation range

Temperature range of cold junction

20...+60

Longterm drift over 48 h with/without autocalibration

Noise with 1.25Hz filter

Input for Pt100

Linearisation range
Noise voltage with 1.25Hz filter
Measuring current

200 ... +848

mpp

mA

0.5

Permissible cable length between transducer and amplifier

3006)

Linearity deviation

0.1

< 30

Longterm drift over 48h with autocalibration

6) 100 m max. distance between connection board and TID/TEDS module

MGCplus with AB22A / AB32

Specifications Multi-channel amplifier plug-in modules

J-45

ML801B + Connection board

AP401

Accuracy class

0.1

Measuring range

10

Max. common mode input voltage (to housing/ground)

45

70

MW

20

Max. differential input voltage


Input impedance
Commonmode rejection
(with 50 Hz, 20 VPP)
(with DC 10 V)

typ. 75
min. 100

Measurement frequency range

Hz

1000 (1 dB)

Linearity deviation

0.03

%
%

max. 0.02
max. 0.05

%
%

max. 0.02
max. 0.05

ESD resistance channel to housing/ground

V (DC)

400

ESD resistance channel to channel

V (DC)

400

Effect of a 10Kchange of the ambient temperature


on zero point (related to full scale)
Autocal on
Autocal off
on sensitivity
Autocal on
Autocal off

4pole female connector, compatible to LemoR Serie S, Size 0,


contact arragement 304,
fitting connector: e.g. FFA 05 304 CLAC52 (LemoR)

Transducer connection

Width
Operating temperature range

mm

20.3 (4 divs)

C [F]

20...+60 [4...+140]

MGCplus with AB22A / AB32

Specifications Multi-channel amplifier plug-in modules

J-46

ML801B + Connection board


Accuracy class

AP418i
%

Connectable transducers*)

1
4 currentfed piezoelectric transducer (e.g. Deltatront)

Transducer identification
Transducer excitation

T-ID and TEDS compatible


mA

Input voltage range

2 ... 20

Measuring ranges

0.05; 0.5; 5

Measurement frequency range

Hz

1000 (1 dB)

Lower limit frequency (3 dB)

Hz

0.72

Linearity deviation

0.05

VPP
VPP
VPP

5 Hz Bessel/500 Hz Butterworth
< 25 m/< 60 m
< 25 m/< 0.35 m
< 100 m/< 3.5 m

Noise
Filter characteristics
Measuring range 0.05 V
Measuring range 0.5 V
Measuring range 5 V

Measuring range 0.05 V

Measuring range 0.5 V und 5


V

0.1

0.03

Effect of a 10Kchange of the ambient temperature


on zero point (related to full scale)
Width
Operating temperature range
*)

%
mm

20.3 (4 TE)

C [F]

20...+60 [4...+140]

If the transducer connection cable is used outside of closed rooms, please regard the advices on page B-55.

MGCplus with AB22A / AB32

Specifications Multi-channel amplifier plug-in modules

J-47

ML801B + Connection board


Accuracy class

AP810
%

0.1

Transducers that can be connected

8 S.G. half or full bridges

Excitation voltage (DC)

Transducer resistance at UB
Rmin (full bridge)
Rmax

10; 5; 2.5; 0.5


10V
330

5V
160

2.5V
120

0.5V
120

4000

Measuring ranges

mV/V

4 (VB=10V)
8 (VB=5V)
16 (VB=2.5V)
80 (VB=0.5V)

Control signal (Shunt)

mV/V

approx. 1 (with 350 S.G. full bridge)


approx. 0.5 (with 350 S.G. half bridge)

Noise at 350 W
Filter characteristics
Filter frequency
UB=10V
UB=5V
UB=2.5V
UB=0.5V

Hz
mm/m
mm/m
mm/m
mm/m

Transducer connection
Permissible cable length between transducer and
connection board

1.25/5
<0.025
<0.05
<0.1
<0.4

Bessel/Butterworth
40/80
<0.15
<0.3
<0.6
<3
D25 female receptacle

200

mm

20.3 (4 divs)

Linearity deviation

0.05

Measurement frequency range

Hz

500 (1dB)

Effect of a 10Kchange of the ambient temperature on


zero point (related to full scale)
on sensitivity

%
%

0.05
0.1

C [F]

20...+60 [4...+140]

Width

Operating temperature range

200/500
<1.8
<3.5
<7

MGCplus with AB22A / AB32

Specifications Multi-channel amplifier plug-in modules

J-48

ML801B + connection board


Accuracy class

AP814Bi

Transducers that can be connected


Internal completion resistors
Excitation voltage (DC)

0.1 7)

8 S.G. quarter bridges in three wire technique

120, 350, 700, 1000 8)

5; 2.5; 1; 0.5

Measuring ranges

mV/V

8 (UB=5V)
16 (UB=2.5V)
40 (UB=1V)
80 (UB=0.5V)

Control signal (shunt)

mV/V

approx. 1 (at 350 )

Noise at 350 W
Filter characteristics
Filter frequency
UB=5V
UB=2.5V
UB=1V
UB=0.5V

Hz
mm/m
mm/m
mm/m
mm/m

Transducer connection
Permissible cable length between transducer and
connection board
Width

1.25/5
<0.05
<0.1
<0.25
<0.45

Bessel/Butterworth
40/80
<0.3
<0.65
<1.5
<3.5
D25 female receptable

2009)10)

mm

20.3 (4 divs)

Linearity variation

0.05

Measurement frequency range

Hz

500 (1dB)

Effect of 10K change in ambient temperature


on the zero point (related to the fullscale value)
on sensitivity

0.1
0.1

%
Operating temperature range
7)

The error influence caused by asymmetrical cable resistances, is not included in the accuracy class.
8) Option
9) Use connection cable with wire cross section 0.25 mm2!
10) 100 m max. distance between connection board and TID/TEDS modul

MGCplus with AB22A / AB32

20...+60

200/500
<2.5
<6.5
<13

Specifications Multi-channel amplifier plug-in modules

J-49

ML801B + Connection board


Accuracy class

AP815i

Transducers that can be connected

8 S.G. full bridges in six wire technique or


8 S.G. half bridges in six wire technique or
8 S.G. half bridges in five wire technique or
8 S.G. quarter bridges in four wire technique or
2 S.G. rosettes

Internal completion resistors

120, 350, 700, (optional 1000)

Excitation voltage (DC)

5; 2.5; 1; 0.5

Measuring ranges

mV/V

8 (VB=5V)
16 (VB=2.5V)
40 (VB=1V)
80 (VB=0.5V)

Control signal (Shunt)

mV/V

1.0078  0.1% (at 350)

Noise at 350 W
Filter characteristics
Filter frequency
VB=5V
VB=2.5V
VB=1V
VB=0.5V

Hz
mm/m
mm/m
mm/m
mm/m

Transducer connection
Permissible cable length between transducer and
connection board
Width

11)
12)
13)

0.111)12)

1.25/5
<0.1
<0.2
<0.5
<1

Bessel/Butterworth
40/80
<0.6
<1.2
<3
<6

200/500
<4
<8
<20
<40

2 D25 female receptacle


m

20013)

mm

20.3 (4 divs)

Linearity deviation

0.05

Measurement frequency range

Hz

500 (1dB)

Effect of a 10K-change of the ambient temperature on


zero point (related to full scale)
on sensitivity

%
%

0.112)
0.1

Operating temperature range

20...+60

0.2 with irradiation according to EN 610043:1996 + A1:1998


0.2 with 5 Vexcitation
100 m max. distance between connection board and TID/TEDS modul

MGCplus with AB22A / AB32

Specifications Multi-channel amplifier plug-in modules

J-50

ML801B + Connection board


Accuracy class

AP836
%

0.1

Transducers that can be connected

8 potentiometric Transducers

Excitation voltage (DC)

Transducer resistance
Rmin
Rmax

190
5000

Measuring range
Noise
Filter characteristics
Filter frequency

mV/V

500

Hz
mV/V

Bessel/Butterworth
40/80
<0.05

Transducer connection
Permissible cable length between transducer and
connection board
Width

1.25/5
<0.01

D25 female receptacle


m

200 (100 m max. distance between connection board and


TID/TEDS modul)

mm

20.3 (4 divs)

Linearity deviation

0.05

Measuring frequency range

Hz

500 (1dB)

Effect of a 10K-change of the ambient temperature on


zero point (related to full scale)
on sensitivity

%
%

0.05
0.1

Operating temperature range

20...+60

MGCplus with AB22A / AB32

200/500
<0.5

Specifications Multi-channel amplifier plug-in modules

J-51

Multichannel amplifier connection boards

AP801
for 8 DC voltage sources

AP801S6

AP809

for 8 voltage sources

for 8 thermocouples

with voltage supply 8V/16V


AP801S6

AP409

AP835

AP836

for 4 thermocouples

for 8 RTD Pt100

for 8 potentiometric
Transducers

13

13

14

25

14

25

MGCplus with AB22A / AB32

Specifications Multi-channel amplifier plug-in modules

J-52

Multichannel amplifier connection boards

AP810

AP814Bi

AP815i

for 8 S.G. half or full bridges

for 8 S.G. quarter bridges


in three wire technique

for 8 S.G. quarter, halfor full bridges

13

13

14

25

13

14

25

13

14

25

13

AP401

AP418i

for 4 DCvoltage supplies


(electrically isolated)

for 4 currentfed piezoelectric transducers


(compatible with T-ID and TEDS)

MGCplus with AB22A / AB32

14

25

14

25

Specifications Multi-channel amplifier plug-in modules

J-53

Programmable plugin module ML70B

Analogue outputs
Max. number of analog outputs

2 (10 with AP78)

Analogue outputs update rate

Hz

2400

Nominal (rated) voltage

 10V asymmetrical

>5

Permissible load resistance

<5

mVPP

< 12

Long-term drift (over 48h)

mV

<3

Effect of ambient temperature at 10_K:


Sensitivity
Zero point

%
mV

< 0.08 typically 0.04


< 3 typically 2

Internal resistance
Residual carrier voltage (76.6 kHz)

Programming
Programming language

IEC611313

Data program memory (volatile)

kByte

224

Data program memory (non-volatile)

kByte

16

Code program memory (volatile)


(2 x available for online change)

kByte

2 x 160

Code program memory (non-volatile)

kByte

160

Memory for project sources (non-volatile)

kByte

192

Hz

2400, synchronized with MGCplus measured-value processing

Call frequency of the IEC program


Number of subchannels
Effective computer output

1...128 (set by user)


75,000 float operations/s
or 300,000 integer operations/s

MGCplus with AB22A / AB32

Specifications Multi-channel amplifier plug-in modules

J-54

Mechanical
Nominal (rated) temperature range

_C [F]

20 ...+ 60 [4 ...+140]

Operating temperature range

_C [F]

20 ...+ 60 [4 ...+140]

Storage temperature range

_C [F]

25 ... +70 [13 ...+158]

+14.6 ... +17.0 (<90 mA)


14.6 ... 17.0 (<100 mA)
7 ... 9 (<10 mA)

Card format

mm

Europe 100 x 160

Width

mm

20.3 (4 divs)

Operating voltages

Connector

DIN 41612 indirectly

Supported connection boards


Number of controllable connection boards

0, 1 or 2

Supported connection board types

AP71 (2 CAN interfaces)


AP72 (2 serial interfaces)
AP75 (8 Digital-In, 8 Digital-Out, 24V level)
AP78 (8 analog outputs)

AP72 Connection board


Interfaces
Baudrate
Electrical isolation

kBaud
V

Connector

9.6; 19.2; 38.4; 57.6; 115.2


Typ. 500
9pol.SubD female receptacle

Mechanics
Nominal (rated) temperature range

_C

20 ... +60

Operating temperature range

_C

20 ... +60

Storage temperature range

_C

25 ... +70

+5 ... (< 100 mA)

Nominal (rated) voltages


Card dimensions

mm

102 x 112

Width

mm

20.3 (4 division units)

MGCplus with AB22A / AB32

Specifications Multi-channel amplifier plug-in modules

J-55

ML70B Programmable module and AP72 Connection board


ML70B

AP72

MGCplus with AB22A / AB32

Specifications Multi-channel amplifier plug-in modules

J-56

Communication module ML71B/ML71BS6 with


AP71 Connection board (CANbus)

CAN interface
Number of CAN interfaces

Protocol

CAN 2.0B

Baud rate

Baud

Line length

10k

20k

50k

125k

250k

500k

1M

1000

1000

1000

500

250

100

25

Hardware bus link individually selectable for each CAN interface

Standard High Speed ISO 1189824V


Fault Tolerant Low Speed

Connection technique

2x 9-pin DSUB, individual potential separation of supply and


ground

Measurement recording
max. 128 each CANport1)
Signals per second

Number of recordable signals

Max. number of signals (16-bit-signals with 4 signals per message


Database with parameter information on the CAN signals
Size of databases

50

100

400

1200

128

72

36

8 2)

1 ... 83)

2 (one database per CAN interface)


2x 100k

Database storage
Mechanical values
Nominal (rated) temperature range

_C [F]

20 ... +60 [4 ...+140]

Operating temperature range


Storage temperature range
Operating voltage

_C [F]
_C [F]
V

20 ... +60 [4 ...+140]


25 ... +70 [13 ...+158]
+14.6 ... +17.0 (< 90 mA)
14.6 ... 17.0 (< 100 mA)
7 ... 9 (< 10 mA)

mm
mm

Europe 100 x 160


20.3 (4 divs)

Card format
Width
Receptacle
1)
2)
3)

Byte

25

Maximum 256 channels per CP42


For operation with more than 8 subchannels
For 8channel operation

MGCplus with AB22A / AB32

non-volatile in ML71B flash memory

DIN 41612 indirectly

Specifications Multi-channel amplifier plug-in modules

J-57

Type

ML71B/ML71BS6

Analogue output
The analogue output can display one of the max. 128 input
signals at a time
V

10V asymmetrical

Permissible load resistance

>5

Internal resistance

<5

Nonlinearity

< 0.05

< 0.08 typ. 0.04

Nominal (rated) voltage

Effect of a 10K-change of the ambient temperature on the


sensitivity
Effect of a 10K-change of the ambient temperature on zero
point

mV
3 typ. 2

MGCplus with AB22A / AB32

Specifications Multi-channel amplifier plug-in modules

J-58

Communication module ML74 with AP74


connection board (CANHEAD)1)

CANinterface
Connection board
Protocol
Baud rate
Line length

AP74
CAN 2.0B
kBaud
m

250
250

Hardware bus link individually selectable for each CAN


interface
Maximum bus length (without branches) 2)

No. of CANHEAD
12
11
10
9
8
7
6
5
4
3
2
1
Measurement recording
Max. number of CANHEAD modules
Number of subchannels
CANHEAD power supply
Cut off current
Cutoff upon current to earth
Mechanical values
Nominal (rated) temperature range
Operating temperature range
Storage temperature range
Card format
Width
1)
2)
3)

120 Ohm; 2.5 V


P=1.8W/CANHEAD

90
100
110
120
135
155
180
220
250

140
155
170
190
215
250

12
10 ... 120 3)
A

0.1

_C

20 ... +60

_C
_C
mm
mm

20 ... +60
25 ... +70

Only with CP22 or CP42 (not with CP32B). The housing must be of type B or C.
Thin Media Cable (0.38 mm2) at ambient temperature of 45 C
Max. 256 channels each CP42

MGCplus with AB22A / AB32

ISO 11898
350 Ohm; 2.5 V
P=1.15W/CANHEAD

Europa 100 x 160


20.3 (4 TE)

700 Ohm; 2.5 V


1000 Ohm; 2.5 V
P=1.0W/CANHEAD
165
180
200
220
250

Specifications Multi-channel amplifier plug-in modules

J-59

Communication module ML77B with AP77


Connection board (Profibus DP)1)

Protocol
Baud rate

Profibus DP slave as per DIN 192453


Baud

Profibus ID number
Potential separation

9.6k ... 12M


04A9 (hexadecimal)

Connection technique

typ. 500
9pin DSUB

Measurement transmission
Supported formats

Transmission rate at Profibus


Float; 24 signals
Float; 48 signals
Integer 32 bit; 32 signals
Integer 16 bit; 48 signals
Integer 16 bit; 88 signals
Integer 16 bit; 120 signals

4 Byte Integer
2 Byte Integer
4 Byte Float (IEEE)
4 Byte Float (Siemens)
4 Byte raw values
2 Byte raw values
Hz
Hz
Hz
Hz
Hz
Hz

2400
1200
2400
2400
1200
800

Nominal (rated) temperature range

_C [F]

20 ... +60 [4...+140]

Service temperature range

_C [F]

20 ... +60 [4...+140]

Storage temperature range

_C [F]

25 ... +70 [13...+158]

Operating voltages

+14.6 ... +17.0 (< 200 mA)


14.6 ... 17.0 (< 200 mA)
+7 ... +9 (<10 mA)

Card format (Euro)

mm

100 x 160

Width

mm

20.3 (4 divs)

Mechanical values

Connector
Weight
1)

DIN 41612 indirectly


kg

approx. 0.3

Only in systems with CP42 or in systems without a communications processor.

MGCplus with AB22A / AB32

Specifications Multi-channel amplifier plug-in modules

J-60

10

Multi-channel I/O amplifier module ML78B

ML78B + connection board

AP78

AP75

10 (2 filterable outputs, 1 of which


is also accessible via the front
panel on the ML78B)

2 (both outputs filterable


1 also accessible via the front panel on the
ML78B)

Analogue outputs
Max. number of analogue outputs

Electrical isolation

Analogue outputs update rate

Hz

D/A conversion resolution

bit
V

2400
16

22)

Grounding systems
Nominal (rated) voltage

Typically 2001)

1, isolated from dig. grounding systems


10 asymmetrical

Permissible load resistance

Internal resistance

<5

Residual carrier voltage (76.6 kHz)

mVPP

< 12

Long-term drift (over 48h)

mV

<3

Effect of change in ambient temperature of


10K

%
mV

< 0.08; typically 0.04


< 3, typically 2

Digital inputs
8 (16)3)

Max. number of digital inputs


Input voltage range

0 ... 30 (nom. 0 ... 24V)

Electrical isolation

Typically 500

Low potential

<5

High potential

Grounding systems
Control functions for MGCplus channel groups

1)
2)
3)

>10
1, isolated from the digital output
Autocalibration on/off; Reset; Tare; Peak
value clear/hold; Synchronisation of internal curve generator

The filterable digital outputs are not electrically isolated!


1 grounding system for 2 digital filterable analogue outputs and 1 grounding system for the remaining 8 analogue outputs
When using 2 AP75 connection boards: 16 digital inputs and 16 digital outputs

MGCplus with AB22A / AB32

Specifications Multi-channel amplifier plug-in modules

J-61

Digital outputs
8 (16)4)

Max. number of digital outputs


Output voltage range

0 ... 30 (nom. 0 ... 24V)

Output current

0.5

Short-circuit current

1.5

Electrical isolation

Typically 500

ms

<4

Response time
Grounding systems
Excitation

1, isolated from the digital inputs


V

18 ... 30 (nom. 24); external

Possible function assignment for the outputs

Combine Limit Value for up to


120 MGCplus channels
Acknowledgement signal for input
Settings by means of an external
software command
Overflow message for groups of
measurement channels

Curve generator
Max. number of curves
Update rate (each channel adjustable)

10
Hz

1; 2; 5; 10; 20; 50; 100; 200; 600; 1200; 2400


128000, permanently storable in flash memory

Max. number of curve points


Mechanical
Nominal (rated) temperature range

C [F]

Operating temperature range

C [F]

20 ...+ 60 [4 ... +140]

Storage temperature range

C [F]

25 ...+ 70 [13 ... +158]

Operating voltages

+14.6 ... +17.0 (< 100 mA)/ 17.0 ... 14.6 (< 90 mA)/ 9.0 ... 7.0 (< 10 mA)

Card format / width

mm

Connection technique
Permissible connection board configurations
4)
5)

20 ...+ 60 [4 ... +140]

Euro 160 x 100 / 20.3 (4divs)


25pin SubD

Plug-in screw terminals

1 x AP78 / 1 x AP75 / 1 x AP78 and 1 x AP75 / 2 x AP755)

When using 2 AP75 connection boards: 16 digital inputs and 16 digital outputs
Analogue outputs VO1 and VO2 are both available on both connection boards

MGCplus with AB22A / AB32

Specifications Multi-channel amplifier plug-in modules

J-62

Connection boards for ML78B


AP75

MGCplus with AB22A / AB32

AP78

J-63

Specifications System devices

11

System devices

System devices MGCplus*)


Mains supply
Supply voltage
Max. input nominal (rated) current
Start-up current

V AC
A
A

115V/230V 25+15%
2.2/1.3
<20

Battery supply
Battery voltage
Max. input nominal (rated) current
Start-up current

V DC
A
A

12V/24V 25+15%
11.5/5.5
<30

Max. power consumption

Nominal (rated) temperature range


C [F]
Type of protection

150
1...16 slots, desktop housing
10 ... +55 [14 ... 131]

19 rack frame
10 ... +55 [14 ... 131]

desktop housing IP20

19 rack frame IP20

*) MGCplus COMPLIANCE OF STANDARDS: The MGCplus system is tested according to the harmonized European standards EN61326
and EN61010 Therefore it achieves the protection aims of EEC directive 89/336EEC in the field of electromagnetic compatibility and EEC directive 73/23/EEC in the field of electrical safety of low voltage equipment. Mechanical stress is tested according to European Standard
EN6006826 for vibrations and EN60068227 for shock. The equipment is exposed to an acceleration of 25 m/s2 within the frequency range
of 5...65 Hz in all 3 axes. Duration of this vibration test: 30min per axis. The shock test is performed with a rated value of 200 m/s2 acceleration
during 11 ms, half sine pulse shape, with 3 shocks in each of the 6 possible directions.

System devices MGCsplit


Power supply 1NT650
Input voltage (nominal/rated)

12, 24 and 42, onboard network (9 V to 58 V)

Ridethrough during startup

3 (0.1 s); 6 ... 9 (10 s)

Output voltage

28 10 %

Output current (continuous load)

> 3.5

Protection against operating errors

Protection against sustained shortcircuit and false polarity

Permissible relative humidity

100 (with dew point transition)

Degree of protection

IP65

Connections

Voltage supply: ODU Minisnap, Series B, Type S3, Size 2, 4 pole, 60 encoded, (matching
connector e. g. S32BFC-T04LPH0-6000)
CAN and On/Off control signal: ODU Minisnap, Series B, Type S3, Size 2, 6 pole, 30 encoded, (matching connector e. g. S32BAC-T06MPH0-6000)
Split-Line: ODU Minisnap, Series B, Type S3, Size 2, 16 pole, 0 encoded,
(matching connector e. g. S32B0C-T16PFG0-7500)

Startup from standby mode

CAN, digital control line

Status exchange with CPxx

I2C (load currents, errors)

Control elements

Contactor (push button)


MGCplus with AB22A / AB32

J-64

Specifications System devices

System devices MGCsplit (continued)


Modules *)

1SH400

Function
Degree of protection

*)

1SH650

Enclosure for one MLxx amplifier and max. two connection


boards (each 4 divs wide)

Operating temperature range

C [F]

Nominal (rated) temperature


range

C [F]

Permissible relative humidity

Supply voltage

Connections

1SH400CP
Enclosure for the communication processor

IP40

IP65

IP40

30 ... +70 [22 ... +158]

30 ... +70 [22 ... +158]

20 ... +60 [4 ... +140]

20 ... +60 [4 ... +140]


95 at 40 C [104 F]

100

S SplitLine Input/Output
S As on the resp. connection
boards

S SplitLine Input/Output
S ODU connectors (LemoR
compatible)

95 at 40 C [104 F]

18 ...32

Weight without amplifier and


connection board, approx.

kg

1.6

Dimensions (W x H x D)

mm

104 x 146 x 205

S Connection for ABX22A


S With CP22 and CP42:
100 Mbit-Ethernet; USB;
RS-232-C

See MGCplus system specifications for measurement properties of amplifier modules.


Split-Line
Total length

25 (from 1SH400CP through last module)

Max. number of measurement


modules

16

Meas./s

307,200; 4byte format (like MGCplus)

Connected automatically

Baud rate
Bus termination

MGCplus with AB22A / AB32

J-65

Specifications System devices

CP42 Communication processor


Width

mm

Interfaces
RS-232-C
USB1) (master/slave)
Ethernet
Data transfer rate
Ethernet (128 channels/sampling rate 2400 Hz)
USB (32 channels/sampling rate 2400 Hz)
PC card harddisk
approx. 109 channels/sampling rate 2400 Hz
128 channels/sampling rate 2400 Hz

Measured
values/s
Measured
values/s
Measured
values/s
Measured
values/s

60.9 (12 divs)


Potential separation

Connection
technique

Baud rate

typ. 500V

9-pin Dsub
female connector

115.2 kBaud

No

USB female
connector

12 MBaud (fastmode)

typ. 500V

RJ45

100 MBaud

307 200 (4byte format)


76 800 (4byte format)

262144 (4byte format)


307200 (2byte format)

Nominal (rated) temperature range

C [F]

10 ... +55 [+14 ... +131]

Operating temperature range

C [F]

10 ... +55 [+14 ... +131]

Storage temperature range

C [F]

25 ... +70[13 ... +158]

kg

approx. 0.6

Weight
Extension (optional)

PC card harddisk, up to 5 GByte, ATA standard

I/O contacts
Potential separation

V DC

Connection technique 2 x In, 2 x Out, 24 V, GND

Screw terminals (line less than 30 meters long)

Input voltage level LOW

0 ... 5

Input voltage range HIGH

10 ... 24

Input current, typically, high level = 24 V

mA

12

Input current, typically, high level = 10 V

mA

Output level active high at 0 A

3
Level supply minus 0.7 V

Output level active high at 0.5 A

Level supply minus 3 V

Power supply (external)

24 (11 V ... 30 V)

Output current, max.

0.5

Short-circuit current, typically

Short-circuit period
1)

500

0.8
unlimited

Cable length  5 m; Cable extensions are not permissible.


MGCplus with AB22A / AB32

J-66

Specifications System devices

CP22 Communication processor


Width
Interfaces

mm
Potential separation

40.6 (8 divs)
Connection technique

Baud rate

RS-232-C

No

9-pin Dsub female connector

38.4 kBaud

USB2) (master/slave)

No

USB female connector

12 MBaud (fast
mode)

Ethernet

Yes

RJ45

10/100 MBaud

Data transfer rate


Ethernet (64 channels/4byte measured values/sampling
rate 2400 Hz)

Measured
values/s

153 600

Measured
values/s

57 600

Nominal (rated) temperature range

C [F]

20 ... +65 [4 ... +149]

Operating temperature range

C [F]

20 ... +65 [4 ... +149]

Storage temperature range

C [F]

25 ... +70 [13 ... +158]

kg

approx. 0.6

USB (24 channels/4byte measured values/sampling


rate 2400 Hz)

Weight
I/O contacts
Potential separation

V DC

Connection technique 1 x In, 1 x Out, 24 V, GND


Input voltage level LOW
Input voltage range HIGH

0 ... 5

10 ... 24

Input current, typically, high level = 24 V

mA

12

Input current, typically, high level = 10 V

mA

Output level active high at 0 A

Level supply minus 0.7 V

Output level active high at 0.5 A

Level supply minus 3 V

Power supply (external)

24 (11 V ... 30 V)

Output current, max.

0.5

Short-circuit current, typically

0.8

Short-circuit period
2)

500
Screw terminals (line less than 30 meters long)

Cable length  5 m; Cable extensions are not permissible.

MGCplus with AB22A / AB32

unlimited

J-67

Specifications System devices

RM001 Relay module


Input voltage

0/5

Resistance

12

Response time

ms

maximum 5

Release time

ms

maximum 25

V
A
VA

42
1
30

+8; 8

Relay breaking capacity

max. voltage
max current
max. power

Operating voltage
Power consumption

mA

34

Switching
cycles
Switching
cycles

50 x 106
100 x 103

kg

0.1

Input voltage

10 ... +10

Input resistance

12.5

Relay-module life

mechanical
electrical (at nominal (rated) load)

Weight, approx

EM001 Output stage module


Input

Output
Impressed voltage

Impressed current

mA

20 / 4 ... 20

maximum 500

Load resistance
Measuring frequency range

10 ... +10
minimum 0

kHz

10

+16; 16

Power consumption

mA

35

Weight, approx

kg

0.1

Operating voltage

MGCplus with AB22A / AB32

J-68

Specifications System devices

Mobile display and control unit ABX22A


Illuminated display

No

Front width

mm

Current consumption (8V)

mA

20

1.5

Length of cable (6-wire)


Connector type

111.8 (22 divs)

Linkage connector, in accordance with DIN 45326, Series 723, 8-pin,


No.09-0171-15-08

Display and control panel AB22A/AB32


Display

AB22A

Backlit LCD display, resolution 192x64 pixels

AB32

Vacuum-fluorescent display (VFD), resolution 192x64 pixels

Key panel

Keypad (alphanumeric), 4 function keys, cursor keys and 5 dialogue keys. All keys
are touch-sensitive with real keys beneath.

Password

There is a facility for protecting certain operating levels with


a password.

Dialogue

Menu languages: German/English/French

Display formats
Weight, approx

MGCplus with AB22A / AB32

1, 3, 6 values; ty graph, xy graph; Status limit switch


kg

0.5

K-1

Index

MGCplus with AB22A / AB32

K-2

MGCplus with AB22A / AB32

K-3

Index

AB22A, control elements, D-3

battery connection, desktop housing, B-4

AB22A/AB32
display, measuring mode, D-6
first display, D-5
menus, D-13
save setup, D-17
selection menus, D-18
setup mode, D-11

battery operation, B-4

AB32, control elements, D-4


absolute/relativ to base, G-8
ABX22A, J-68
connecting, B-8

blank plate, B-8


bridge resistance, B-49
button, D-19 , D-22 , I-4

C
calling up menus, D-13
CANHEAD, connecting, B-96
channel names, G-27

activation fields, D-19 , I-4

channel number, D-9

adaptation to the transducer


current and voltage measurement, E-52E-55
inductive transducer, E-31
piezoelectric transducer, E-66E-69
piezoresistive transducer, E-78E-81
potentiometric transducer, E-83E-86
resistance temperature detector, E-55E-57
resistors, E-58E-61
rotation speed, E-45E-49
SG transducer, E-20
thermocouples, E-49E-51

channel selection in measuring mode, D-15


channel selection in setup mode, D-16
Combine limit switches, F-12
commissioning, C-3
Communication module ML71B/ML71BS6, J-56
Communication module ML74, J-58
Communication module ML77, J-59
Communications processor CP22/CP42, insert, A-17

amplifier
first measurement, E-18
setting up, E-4

compensating resistor, B-19 , E-21 , E-29

angle of rotation measurement, B-38

computer, connecting, B-99

AP74 connection board, B-98

conditioning, E-13

auto start, H-30

conditions on site, A-35

Completion resistor, B-20

autocal, F-24
MGCplus with AB22A/AB32

K-4

Conformity, L-1

Index

connecting, A-1 , B-1 , C-1 , D-1 , E-1 , F-1 , G-1 ,


H-1 , J-1

data acquisition, D-7 , G-3 , G-22

Connecting separate TEDS modules, B-13

data acquisition comment, G-22 , H-25H-29

Connecting transducer, LVDT, B-17

data acquisition parameter, H-15 , H-17 , H-23 , H-24


, H-25 , H-26 , H-30 , H-31 , I-8

connecting transducers, B-12


DC power source, B-48
DC voltage sources, B-44
frequency generator, B-51 , B-52
impulse transducer, B-53
inductive full bridge, B-14 , B-15 , B-18 , E-6
inductive half bridge, B-16
piezoelectric transducers, B-55
piezoresistive transducers, B-56
potentiometric transducers, B-57
resistors, Pt10,100, 1000, B-49
SG full bridge, B-14 , B-15 , B-18 , E-6
SG half bridge, B-16
shunt resistor, B-100
single strain gage, B-19B-21
thermocouples, B-42
torque flange, T10FSF1, T10FSU2, B-26
torque measurement shaft, T4WAS3, B-38
torque transducer
T1A, T4A/WAS3, T5, TB1A, B-37
T3...FN/FNA, T10FKF1, B-33

data acquisition parameter set, H-30


data acquisition program, H-17 , H-19
data storage, D-17
DC power source, connecting, B-48
DC voltage source, connecting, B-44
define trigger, H-18
device structure, A-15
dialogue boxes, D-19
direct input, D-15
display
channel names, G-27
display format, G-3
Fkeys, G-23
display format, G-3
distributor board VT810/815i, connect, B-60

Connection board, AP460i, Pin assignment, B-28

Distributor board VT814i, connecting, B-59

connection board
AP02, B-111
AP07/1, B-113
AP74, B-98
AP77, B-119

documentation, A-8

connection boards, J-26


AP01i... AP18i, connecting, B-105
connector pin assignment, AP17, B-109
current value, F-20
MGCplus with AB22A/AB32

Rotation speed measurement, T10FSSF1,


T10FSSU2 (symmetrical signals), B-31

E
earthing switch, B-3 , B-4 , B-5
edit field, D-19 , D-21 , I-4
envelope curve, F-21

K-5

Index

error messages, D-10

Greenline, B-11

Evaluate F2 signal, E-64

guidelines, A-9

Extended functions, E-64

external trigger, H-21


External triggering, B-108

F
Fkeys, G-23

housing, MGCplus desktop housing, A-13


hysteresis, F-8

factory settings, of remotes, AP01i...AP14, B-108

impulse counting, B-53

feedback circuits, B-37

impulse transducer, connecting, B-53

file name, G-22 , H-24

inductive full bridge, connecting, B-14

filter
high pass, E-15
low pass, E-15

inductive half bridge, connecting, B-16

final stage module, B-115


AP01i and AP03i, B-120
AP07/1, B-121
AP08/14/17/18i, B-122
AP09 and AP11i, B-124
AP13i, B-116
format, H-25H-29
fourwire connection, B-12 , B-21 , B-37 , B-49
frequency generator, connecting, B-51 , B-52
frequency measurement, without direction of rotation
signal, B-51 , B-52

input, letters and numbers, D-21


Inputs and outputs, CP22/CP42, B-101 , B-104
integration, F-4 , F-18

L
language, H-38
desktop device, C-6
level, H-22
limit switch
delay time, F-9
setting up, F-8

Frequency quadrupling, E-64

limit switches, F-7 , F-11


setting up, F-6

fuse, B-4 , B-5

LVDT, connecting, B-17

Glitch filter, E-44 , E-48 , E-64

mains connection, desktop housing, B-3

graphic display, G-17

maintenance and cleaning, A-36


MGCplus with AB22A/AB32

K-6

Measurement, Torque transducer, E-37


measurement band, H-20
measurement of, impulses/frequencies, E-61E-64

Index

AP17, B-88
AP401, B-78
AP409, B-77
AP460i, B-80
AP815i, B-79

measurement with, piezoresistive transducers,


E-75E-78

ML38B, Extended functions, E-7

measuring rate trigger, H-17 , H-18

ML74 communication module, B-97

measuring with, inductive transducer, E-31E-35

mode, H-19 , H-22

menu, pullup menu, D-13


menu structure, I-1 , I-3

Multichannel amplifier connection boards, J-51 ,


J-52

menus, exiting, D-14

Multichannel amplifier module ML455, J-34

MGC Compact, C-5

Multichannel amplifier plugin module ML460, J-36

MGCsplit
CAN bus connection, AP71, B-89
Connecting, B-62 , B-75
Connecting to MGCplus systems, A-27
Enclosure dimensions, A-32
Enclosure versions, A-20
Inputs/outputs
AP13i, B-81 , B-82 , B-83
AP17, B-85 , B-86 , B-87
AP75, B-93 , B-94 , B-95
AP78, B-90 , B-91 , B-92
ML/AP module, B-76
LED display, A-24
ADDRESS, A-26
ERROR, A-24
LINK, A-24
Rx/Tx, A-24
SYNC, A-24
Measurement module IP40, A-21
Measurement module IP65, A-22
Power supply units NT650/NT651, B-63
Processor module, A-23
Transducer connection
AP13i, B-84

Multichannel amplifier plugin module ML70B, J-53

MGCplus with AB22A/AB32

Multichannel amplifier plugin module ML801B,


J-41
Multichannel I/O module ML78, J-60
multichannel module, D-9
multiplier, B-115

N
number, G-6

O
onechannel amplifier plugin modules, general
data, J-3
onechannel amplifier plug-in module ML01B, J-5
onechannel amplifier plug-in module ML10B, J-8
onechannel amplifier plug-in module ML30B, J-11
onechannel amplifier plug-in module ML35B, J-13

K-7

Index

onechannel amplifier plug-in module ML38, J-15

potentiometric transducer, connecting, B-57

onechannel amplifier plug-in module ML50B, J-17

potentiometric transducers, E-83


connecting, B-58

onechannel amplifier plug-in module ML55B, J-19


onechannel amplifier plug-in module ML55BS6,
J-21

Pre trigger, H-23

onechannel amplifier plug-in module ML60B, J-24

printer, connecting, B-99

onechannel module, D-9

print, H-37

R
recording measurement series, H-14

parameter set, F-24

reduction factor, H-26

password, H-3

relay contacts, AP01i...AP14, B-111

peak value, F-19

relay module, B-111

peak value stores, F-15


combine, F-16
controlling, F-18
switch off, F-15 , F-22

remote, F-3

periods, G-22 , H-15


piezoelectric transducer, connecting, B-55
piezoelectric transducers, E-66
piezoresistive transducer, E-75
piezoresistive transducers, E-78
connecting, B-56
pin assignment
AP01i...AP14, B-107
AP01i/03i/08/09/11i/14/17/18i, B-106
AP02, B-111
AP07/1, B-113
AP13i, B-116 , B-119
PLC, connecting, B-99

remote contacts, F-3 , F-4


AP13i, B-118
remotes, B-101
assignment AP01i...AP14, B-108
factory setting, B-108
function, F-3
resistors, E-58
PT10, 100, 1000, connecting, B-49
RM001, B-111
rotation speed and angle of rotation measurement,
T4WAS3, B-38
rotation speed measurement
T10FSF1, T10FSU2 (symmetrical signals), B-29
T3...FN/FNA, T10FKF1 (asymmetrical signals),
B-35

Polynomial curve, cubic, E-7

MGCplus with AB22A/AB32

K-8

Index

Rotation speed measurement with inductive transducers, B-41

S
safety instructions, A-3
remaining dangers, A-3
save, H-9
security prompt, D-17
selection field, D-19 , I-4
selection fields, D-20
selection levels, D-18
serial interfaces, B-99
setup window, D-19

stop condition, H-24


stop trigger, H-17
switch, F-24
synchronization, CP22, B-6
system
language, H-38
password, H-3
print, H-37
save, H-9
time, H-39
system description, A-10
system devices, J-63

setting up, basic parameters, E-3

TEDS, Connection, B-13

setup menu, G-4

TEDS transducer, E-9

SG
full bridge, connecting, B-14 , B-15 , B-18 , E-6
half bridge, connecting, B-16
single strain gauge, connecting, B-19
transducer, connecting, B-12

thermocouples, E-49
connecting, B-42

shielding design, B-11

time stamp, H-16

shunt resistor, connecting, B-100

torque flange T10FSF1, T10FSU2, B-26

single strain gauge, connecting, B-19B-21

torque measurement
T10FSF1, T10FSU2, B-26
T1A, T4A/WAS3, T5, TB1A (slip ring or direct
cable connection), B-37
T3...FN/FNA, T10FKF1 (squarewave excitation
voltage), B-33

slot number, D-9


start condition, H-23
start trigger, H-17
status data acquisition, G-22
status limit switch, G-21
Status line, D-8
status line, G-7
MGCplus with AB22A/AB32

threewire connection, B-49


time, H-39

Torque transducer, E-37


torque transducers (T1A, T4A/WAS3, T5, TB1A),
connecting, B-37

K-9

Index

torque transducers (T3...FN/FNA, T10FKF1), B-33


transducer connection
distributor board VT814i, B-59
potentiometric transducers, B-58 , B-60
Transducer error input active, E-64
trigger, external, H-21
trigger condition, H-17 , H-22
trigger function, H-17
trigger level, H-22
type, G-6

V
version, F-23
voltage drop, B-5

Y
YTDiagram, G-17

Z
Zero index input active, E-64

MGCplus with AB22A/AB32

K-10

MGCplus with AB22A/AB32

Index

xxx

Modifications reserved.
All details describe our products in
general form only. They are not to be understood as express
warranty and do not constitute any liability whatsoever.

B0534-18.0 en

Hottinger Baldwin Messtechnik GmbH


Postfach 10 01 51, D-64201 Darmstadt
Im Tiefen See 45, D-64293 Darmstadt
Tel.: +49/61 51/8 03-0; Fax: +49/61 51/ 8039100
Email: support@hbm.com www.hbm.com

You might also like