You are on page 1of 191

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.

C)
V300R001C01

Product Description
Issue

04

Date

2011-07-08

HUAWEI TECHNOLOGIES CO., LTD.

Copyright Huawei Technologies Co., Ltd. 2011. All rights reserved.


No part of this document may be reproduced or transmitted in any form or by any means without prior written
consent of Huawei Technologies Co., Ltd.

Trademarks and Permissions


and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective holders.

Notice
The purchased products, services and features are stipulated by the contract made between Huawei and the
customer. All or part of the products, services and features described in this document may not be within the
purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information,
and recommendations in this document are provided "AS IS" without warranties, guarantees or representations
of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute the warranty of any kind, express or implied.

Huawei Technologies Co., Ltd.


Address:

Huawei Industrial Base


Bantian, Longgang
Shenzhen 518129
People's Republic of China

Website:

http://www.huawei.com

Email:

support@huawei.com

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

About This Document

About This Document

Purpose
This document describes the configurations, functions, and specifications of the boards and
modules in APM30H Ver.C, TMC11H Ver.C, IBBS200D Ver.C, and IBBS200T Ver.C. It also
describes the classification of cables, specifications of connectors, and installation positions of
cables.
l

APM30H is short for advanced power module with heat exchanger.

TMC11H is short for transmission cabinet of 11 U high with heat exchanger.

IBBS200D is short for integrated battery backup system with direct cooling.

IBBS200T is short for integrated battery backup system with thermal electric cooling.

Product Version
The following table lists the product version related to this document.
Product Name

Product Version

APM30H Ver.C (referred to as APM30H in


this document)

V300R001C01

TMC11H Ver.C (referred to as TMC11H in


this document)
IBBS200D Ver.C (referred to as IBBS200D in
this document)
IBBS200T Ver.C (referred to as IBBS200T in
this document)

Intended Audience
l

Base station installation engineers

System engineers

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

iii

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

About This Document

Site maintenance engineers

Organization
1 Changes in the APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C) Product
Description
This chapter describes changes in the APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description.
2 APM30H Product Description
This chapter describes the exterior, functions, specifications, usage scenarios, structure,
components, and cables of the APM30H.
3 TMC11H Product Description
This chapter describes the exterior, functions, specifications, usage scenarios, structure,
components, and cables of the TMC11H.
4 IBBS200D Product Description
This chapter describes the exterior, functions, specifications, structure, components, and cables
of the IBBS200D.
5 IBBS200T Product Description
This chapter describes the exterior, functions, specifications, structure, components, and cables
of the IBBS200T.

Conventions
Symbol Conventions
The symbols that may be found in this document are defined as follows.
Symbol

Description
Indicates a hazard with a high level of risk, which if not
avoided, will result in death or serious injury.
Indicates a hazard with a medium or low level of risk, which
if not avoided, could result in minor or moderate injury.
Indicates a potentially hazardous situation, which if not
avoided, could result in equipment damage, data loss,
performance degradation, or unexpected results.
Indicates a tip that may help you solve a problem or save
time.
Provides additional information to emphasize or supplement
important points of the main text.

iv

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

About This Document

General Conventions
The general conventions that may be found in this document are defined as follows.
Convention

Description

Times New Roman

Normal paragraphs are in Times New Roman.

Boldface

Names of files, directories, folders, and users are in


boldface. For example, log in as user root.

Italic

Book titles are in italics.

Courier New

Examples of information displayed on the screen are in


Courier New.

Command Conventions
The command conventions that may be found in this document are defined as follows.
Convention

Description

Boldface

The keywords of a command line are in boldface.

Italic

Command arguments are in italics.

[]

Items (keywords or arguments) in brackets [ ] are optional.

{ x | y | ... }

Optional items are grouped in braces and separated by


vertical bars. One item is selected.

[ x | y | ... ]

Optional items are grouped in brackets and separated by


vertical bars. One item is selected or no item is selected.

{ x | y | ... }*

Optional items are grouped in braces and separated by


vertical bars. A minimum of one item or a maximum of all
items can be selected.

[ x | y | ... ]*

Optional items are grouped in brackets and separated by


vertical bars. Several items or no item can be selected.

GUI Conventions
The GUI conventions that may be found in this document are defined as follows.

Issue 04 (2011-07-08)

Convention

Description

Boldface

Buttons, menus, parameters, tabs, window, and dialog titles


are in boldface. For example, click OK.

>

Multi-level menus are in boldface and separated by the ">"


signs. For example, choose File > Create > Folder.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

About This Document

Keyboard Operations
The keyboard operations that may be found in this document are defined as follows.
Format

Description

Key

Press the key. For example, press Enter and press Tab.

Key 1+Key 2

Press the keys concurrently. For example, pressing Ctrl+Alt


+A means the three keys should be pressed concurrently.

Key 1, Key 2

Press the keys in turn. For example, pressing Alt, A means


the two keys should be pressed in turn.

Mouse Operations
The mouse operations that may be found in this document are defined as follows.

vi

Action

Description

Click

Select and release the primary mouse button without moving


the pointer.

Double-click

Press the primary mouse button twice continuously and


quickly without moving the pointer.

Drag

Press and hold the primary mouse button and move the
pointer to a certain position.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

Contents

Contents
About This Document...................................................................................................................iii
1 Changes in the APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C) Product
Description.....................................................................................................................................1-1
2 APM30H Product Description.................................................................................................2-1
2.1 Introduction to the APM30H...........................................................................................................................2-2
2.2 Specifications of the APM30H.......................................................................................................................2-5
2.3 Usage Scenarios of the APM30H....................................................................................................................2-9
2.4 Structure of the APM30H.............................................................................................................................2-11
2.5 APM30H Components..................................................................................................................................2-13
2.5.1 Fan Box................................................................................................................................................2-14
2.5.2 EPU......................................................................................................................................................2-24
2.5.3 Outer Air Circulation Cooling Component..........................................................................................2-39
2.5.4 Junction Box.........................................................................................................................................2-40
2.5.5 ELU......................................................................................................................................................2-42
2.5.6 Door Status Sensor...............................................................................................................................2-42
2.5.7 Filler Panel...........................................................................................................................................2-43
2.5.8 AC Heater (Optional)...........................................................................................................................2-44
2.5.9 SOU (Optional)....................................................................................................................................2-45
2.6 APM30H Cables...........................................................................................................................................2-46
2.6.1 Cables...................................................................................................................................................2-47
2.6.2 PGND Cables.......................................................................................................................................2-49
2.6.3 Equipotential Cable..............................................................................................................................2-50
2.6.4 Power Cables........................................................................................................................................2-50
2.6.5 Signal Cables........................................................................................................................................2-57

3 TMC11H Product Description.................................................................................................3-1


3.1 Introduction to the TMC11H...........................................................................................................................3-2
3.2 Specifications of the TMC11H.......................................................................................................................3-3
3.3 Usage Scenarios of the TMC11H....................................................................................................................3-6
3.4 Structure of the TMC11H...............................................................................................................................3-8
3.5 TMC11H Components..................................................................................................................................3-11
3.5.1 Fan Box................................................................................................................................................3-11
3.5.2 DCDU-11B and DCDU-11C...............................................................................................................3-21
Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

vii

Contents

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description
3.5.3 Outer Air Circulation Cooling Component..........................................................................................3-26
3.5.4 Filler Panel...........................................................................................................................................3-27
3.5.5 Junction Box.........................................................................................................................................3-28
3.5.6 ELU......................................................................................................................................................3-29
3.5.7 Door Status Sensor...............................................................................................................................3-30
3.5.8 AC Heater (Optional)...........................................................................................................................3-31

3.6 TMC11H Cables...........................................................................................................................................3-32


3.6.1 Cables...................................................................................................................................................3-32
3.6.2 Equipotential Cable..............................................................................................................................3-34
3.6.3 Power Cables........................................................................................................................................3-35
3.6.4 Signal Cables........................................................................................................................................3-39

4 IBBS200D Product Description...............................................................................................4-1


4.1 Introduction to the IBBS200D........................................................................................................................4-2
4.2 Specifications of the IBBS200D.....................................................................................................................4-3
4.3 Structure of the IBBS200D.............................................................................................................................4-4
4.4 IBBS200D Components..................................................................................................................................4-6
4.4.1 Fan Installation Module.........................................................................................................................4-7
4.4.2 Power Distribution Box..........................................................................................................................4-8
4.4.3 CMUE..................................................................................................................................................4-10
4.4.4 Storage Battery.....................................................................................................................................4-16
4.4.5 ELU......................................................................................................................................................4-17
4.4.6 Heating Film.........................................................................................................................................4-17
4.4.7 Door Status Sensor...............................................................................................................................4-18
4.4.8 Temperature Sensor for Storage Batteries............................................................................................4-19
4.5 IBBS200D Cables.........................................................................................................................................4-20
4.5.1 Cables...................................................................................................................................................4-21
4.5.2 PGND Cables.......................................................................................................................................4-23
4.5.3 Equipotential Cable..............................................................................................................................4-23
4.5.4 Power Cables........................................................................................................................................4-24
4.5.5 Signal Cables........................................................................................................................................4-29

5 IBBS200T Product Description................................................................................................5-1


5.1 Introduction to the IBBS200T.........................................................................................................................5-2
5.2 Specifications of the IBBS200T......................................................................................................................5-3
5.3 Structure of the IBBS200T..............................................................................................................................5-5
5.4 IBBS200T Components..................................................................................................................................5-6
5.4.1 TEC........................................................................................................................................................5-7
5.4.2 Power Distribution Box..........................................................................................................................5-9
5.4.3 CMUE..................................................................................................................................................5-11
5.4.4 Storage Battery.....................................................................................................................................5-17
5.4.5 ELU......................................................................................................................................................5-18
5.4.6 Door Status Sensor...............................................................................................................................5-18
5.4.7 Temperature Sensor for Storage Batteries............................................................................................5-19
viii

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

Contents

5.5 IBBS200T Cables..........................................................................................................................................5-20


5.5.1 Cables...................................................................................................................................................5-21
5.5.2 PGND Cables.......................................................................................................................................5-23
5.5.3 Equipotential Cable..............................................................................................................................5-23
5.5.4 Power Cables........................................................................................................................................5-24
5.5.5 Signal Cables........................................................................................................................................5-28

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

ix

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

Figures

Figures
Figure 2-1 APM30H.............................................................................................................................................2-2
Figure 2-2 Scenario where the APM30H is stacked with a battery cabinet and is used for a distributed base station
.............................................................................................................................................................................2-10
Figure 2-3 Scenario where the APM30H is used for an outdoor macro base station........................................2-11
Figure 2-4 Structure of the APM30H.................................................................................................................2-12
Figure 2-5 Fan box.............................................................................................................................................2-15
Figure 2-6 Fan....................................................................................................................................................2-15
Figure 2-7 Signal cable delivered with a fan......................................................................................................2-15
Figure 2-8 HPMI................................................................................................................................................2-17
Figure 2-9 Ports on the panel of the HPMI........................................................................................................2-17
Figure 2-10 CMUE.............................................................................................................................................2-20
Figure 2-11 Ports and indicators on a CMUE....................................................................................................2-20
Figure 2-12 Position of the DIP switch on the CMUE.......................................................................................2-23
Figure 2-13 DIP switch settings of the CMUE in different cabinets.................................................................2-23
Figure 2-14 EPU.................................................................................................................................................2-25
Figure 2-15 EPU03A-03....................................................................................................................................2-27
Figure 2-16 EPU03A-05....................................................................................................................................2-28
Figure 2-17 EPU03A-02....................................................................................................................................2-29
Figure 2-18 EPU03A-04....................................................................................................................................2-30
Figure 2-19 PMU................................................................................................................................................2-33
Figure 2-20 Ports, indicators, and switch on the front panel of the PMU..........................................................2-34
Figure 2-21 Rear panel of the PMU...................................................................................................................2-34
Figure 2-22 DIP switch on the right of the PMU...............................................................................................2-36
Figure 2-23 PSU.................................................................................................................................................2-37
Figure 2-24 PSU (AC/DC) panel.......................................................................................................................2-38
Figure 2-25 Outer air circulation cooling component........................................................................................2-40
Figure 2-26 Junction box....................................................................................................................................2-41
Figure 2-27 Structure of the junction box..........................................................................................................2-41
Figure 2-28 ELU................................................................................................................................................2-42
Figure 2-29 Magnet part of the door status sensor.............................................................................................2-43
Figure 2-30 Switch part of the door status sensor..............................................................................................2-43
Figure 2-31 filler panel.......................................................................................................................................2-44
Figure 2-32 AC heater........................................................................................................................................2-44
Figure 2-33 SOU................................................................................................................................................2-46
Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

xi

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

Figures

Figure 2-34 Different types of sockets...............................................................................................................2-46


Figure 2-35 PGND cable....................................................................................................................................2-49
Figure 2-36 Equipotential cable.........................................................................................................................2-50
Figure 2-37 Power cable connections for a distributed base station..................................................................2-51
Figure 2-38 Power cable connections for an outdoor macro base station..........................................................2-52
Figure 2-39 220 V AC single-phase input power cable.....................................................................................2-53
Figure 2-40 Power cable for the SOU................................................................................................................2-54
Figure 2-41 Power cable for the AC heater........................................................................................................2-55
Figure 2-42 Power cable for the fan box in the APM30H.................................................................................2-56
Figure 2-43 Input power cable for the junction box...........................................................................................2-56
Figure 2-44 Signal cable connections in the APM30H......................................................................................2-58
Figure 2-45 Signal cable for the ELU................................................................................................................2-58
Figure 2-46 APM30H door status monitoring cable..........................................................................................2-60
Figure 2-47 Monitoring signal cable for the fan on the front door....................................................................2-61
Figure 2-48 Environment monitoring signal cable.............................................................................................2-62
Figure 2-49 Monitoring signal transfer cable.....................................................................................................2-63
Figure 3-1 TMC11H.............................................................................................................................................3-2
Figure 3-2 Scenario where the TMC11H is used for a distributed base station...................................................3-7
Figure 3-3 Scenario where the TMC11H is used for an outdoor macro base station..........................................3-8
Figure 3-4 Internal structure of the TMC11H......................................................................................................3-9
Figure 3-5 Fan box.............................................................................................................................................3-12
Figure 3-6 Fan....................................................................................................................................................3-12
Figure 3-7 Signal cable delivered with a fan......................................................................................................3-12
Figure 3-8 HPMI................................................................................................................................................3-14
Figure 3-9 Ports on the panel of the HPMI........................................................................................................3-14
Figure 3-10 CMUE.............................................................................................................................................3-17
Figure 3-11 Ports and indicators on a CMUE....................................................................................................3-17
Figure 3-12 Position of the DIP switch on the CMUE.......................................................................................3-20
Figure 3-13 DIP switch settings of the CMUE in different cabinets.................................................................3-20
Figure 3-14 Front view of the DCDU-11B/DCDU-11C....................................................................................3-22
Figure 3-15 Rear view of the DCDU-11B/DCDU-11C.....................................................................................3-22
Figure 3-16 Ports on the panel of the DCDU-11B/DCDU-11C........................................................................3-24
Figure 3-17 Easy power receptacle (pressfit type) connector (1).......................................................................3-26
Figure 3-18 Easy power receptacle (pressfit type) connector (2).......................................................................3-26
Figure 3-19 Outer air circulation cooling component........................................................................................3-27
Figure 3-20 filler panel.......................................................................................................................................3-28
Figure 3-21 Junction box....................................................................................................................................3-28
Figure 3-22 Structure of the junction box..........................................................................................................3-29
Figure 3-23 ELU................................................................................................................................................3-30
Figure 3-24 Magnet part of the door status sensor.............................................................................................3-30
Figure 3-25 Switch part of the door status sensor..............................................................................................3-31
Figure 3-26 AC heater........................................................................................................................................3-31
xii

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

Figures

Figure 3-27 Equipotential cable.........................................................................................................................3-34


Figure 3-28 Power cable connections in the TMC11H......................................................................................3-35
Figure 3-29 Input power cable for the TMC11H (1)..........................................................................................3-36
Figure 3-30 Input power cable for the TMC11H (2)..........................................................................................3-37
Figure 3-31 Power cable for the fan box in the TMC11H.................................................................................3-37
Figure 3-32 Power cable for the AC heater........................................................................................................3-38
Figure 3-33 Signal cable connections in the TMC11H......................................................................................3-39
Figure 3-34 Signal cable for the ELU................................................................................................................3-40
Figure 3-35 Monitoring signal cable for the door status sensor.........................................................................3-40
Figure 3-36 Monitoring signal cable for the fan on the front door....................................................................3-41
Figure 4-1 IBBS200D..........................................................................................................................................4-2
Figure 4-2 Structure of the IBBS200D.................................................................................................................4-5
Figure 4-3 Fan installation module......................................................................................................................4-7
Figure 4-4 PDB....................................................................................................................................................4-8
Figure 4-5 External structure of a PDB..............................................................................................................4-10
Figure 4-6 CMUE...............................................................................................................................................4-12
Figure 4-7 Ports and indicators on a CMUE......................................................................................................4-12
Figure 4-8 Position of the DIP switch on the CMUE.........................................................................................4-14
Figure 4-9 DIP switch settings of the CMUE in different cabinets...................................................................4-15
Figure 4-10 Exterior of the 12 V 92 Ah storage battery.....................................................................................4-16
Figure 4-11 ELU................................................................................................................................................4-17
Figure 4-12 Heating film....................................................................................................................................4-18
Figure 4-13 Magnet part of the door status sensor.............................................................................................4-19
Figure 4-14 Switch part of the door status sensor..............................................................................................4-19
Figure 4-15 Position for installing a temperature sensor for storage batteries in the IBBS200D......................4-20
Figure 4-16 Position for installing a temperature sensor for storage batteries in the IBBS200T......................4-20
Figure 4-17 PGND cable....................................................................................................................................4-23
Figure 4-18 Equipotential cable.........................................................................................................................4-24
Figure 4-19 Power cable connections in the IBBS200D....................................................................................4-25
Figure 4-20 Input power cables for storage batteries.........................................................................................4-26
Figure 4-21 Power cables between the battery group and the copper bar in the junction box...........................4-26
Figure 4-22 Copper bar for inter-battery series connection...............................................................................4-26
Figure 4-23 Input power cables for the fan in the IBBS200D...........................................................................4-27
Figure 4-24 Power transfer cables for the fan in the IBBS200D.......................................................................4-28
Figure 4-25 Power cable for the heating film.....................................................................................................4-28
Figure 4-26 Signal cable connections in the IBBS200D....................................................................................4-29
Figure 4-27 Signal cable for the ELU................................................................................................................4-30
Figure 4-28 Monitoring signal cable for the door status sensor.........................................................................4-30
Figure 4-29 Monitoring signal cable for the storage battery cabinet.................................................................4-31
Figure 5-1 IBBS200T...........................................................................................................................................5-2
Figure 5-2 Structure of the IBBS200T.................................................................................................................5-5
Figure 5-3 TEC.....................................................................................................................................................5-8
Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

xiii

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

Figures

Figure 5-4 PDB....................................................................................................................................................5-9


Figure 5-5 External structure of a PDB..............................................................................................................5-10
Figure 5-6 CMUE...............................................................................................................................................5-12
Figure 5-7 Ports and indicators on a CMUE......................................................................................................5-13
Figure 5-8 Position of the DIP switch on the CMUE.........................................................................................5-15
Figure 5-9 DIP switch settings of the CMUE in different cabinets................................................................... 5-15
Figure 5-10 Exterior of the 12 V 92 Ah storage battery.....................................................................................5-17
Figure 5-11 ELU................................................................................................................................................ 5-18
Figure 5-12 Magnet part of the door status sensor.............................................................................................5-19
Figure 5-13 Switch part of the door status sensor..............................................................................................5-19
Figure 5-14 Position for installing a temperature sensor for storage batteries in the IBBS200D......................5-20
Figure 5-15 Position for installing a temperature sensor for storage batteries in the IBBS200T...................... 5-20
Figure 5-16 PGND cable....................................................................................................................................5-23
Figure 5-17 Equipotential cable.........................................................................................................................5-23
Figure 5-18 Power cable connections in the IBBS200T....................................................................................5-25
Figure 5-19 Input power cables for storage batteries.........................................................................................5-26
Figure 5-20 Power cables between the battery group and the copper bar in the junction box...........................5-26
Figure 5-21 Copper bar for inter-battery series connection............................................................................... 5-26
Figure 5-22 Input power cable for the TEC....................................................................................................... 5-27
Figure 5-23 Power transfer cable for the TEC................................................................................................... 5-28
Figure 5-24 Signal cable connections in the IBBS200T....................................................................................5-29
Figure 5-25 Signal cable for the ELU................................................................................................................5-29
Figure 5-26 Monitoring signal cable for the door status sensor.........................................................................5-30
Figure 5-27 Monitoring signal cable for the storage battery cabinet................................................................. 5-31

xiv

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

Tables

Tables
Table 2-1 Functions of the APM30H...................................................................................................................2-2
Table 2-2 DC power distribution functions of the APM30H...............................................................................2-3
Table 2-3 Electrical specifications of the APM30H.............................................................................................2-5
Table 2-4 Engineering specifications of the APM30H........................................................................................2-7
Table 2-5 Surge protection specifications of the APM30H.................................................................................2-8
Table 2-6 Environmental specifications of the APM30H....................................................................................2-9
Table 2-7 Pin assignment...................................................................................................................................2-16
Table 2-8 Technical specifications of the fan.....................................................................................................2-16
Table 2-9 Specifications of the ports on the panel of the HPMI........................................................................2-17
Table 2-10 Functions of the CMUE...................................................................................................................2-19
Table 2-11 Functions of the ports and indicators on a CMUE...........................................................................2-21
Table 2-12 Indicators on a CMUE.....................................................................................................................2-22
Table 2-13 Specifications of the CMUE............................................................................................................2-23
Table 2-14 Types and usage scenarios of the EPU............................................................................................2-26
Table 2-15 DC power distribution functions of the EPU in the APM30H used for a distributed base station
.............................................................................................................................................................................2-31
Table 2-16 DC power distribution functions of the EPU in the APM30H used for an outdoor macro base station
.............................................................................................................................................................................2-31
Table 2-17 Specifications of the EPU................................................................................................................2-32
Table 2-18 Ports and switch on the PMU...........................................................................................................2-35
Table 2-19 Indicators on the PMU.....................................................................................................................2-35
Table 2-20 Indicators on a PSU (AC/DC) panel................................................................................................2-38
Table 2-21 Specifications of the heat exchanger core........................................................................................2-40
Table 2-22 Technical specifications of the SOU................................................................................................2-45
Table 2-23 Power cables, PGND cables, and equipotential cable......................................................................2-47
Table 2-24 Signal cables.....................................................................................................................................2-48
Table 2-25 PGND cables....................................................................................................................................2-49
Table 2-26 Specifications of the equipotential cable..........................................................................................2-50
Table 2-27 Specifications of an AC input power cable......................................................................................2-53
Table 2-28 Pin assignment for the wires of the power cable for the SOU.........................................................2-54
Table 2-29 Pin assignment for the wires of the power cable for the AC heater.................................................2-55
Table 2-30 Specifications of the power cable for the fan box in the APM30H.................................................2-56
Table 2-31 Pin assignment for the wires of the input power cable for the junction box....................................2-57
Table 2-32 Pin assignment for the wires of the signal cable for the ELU..........................................................2-59
Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

xv

Tables

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description
Table 2-33 Pin assignment for the wires of the monitoring signal cable for the fan on the front door..............2-61
Table 2-34 Pin assignment for the wires of the environment monitoring signal cable......................................2-62
Table 2-35 Pin assignment for the wires of the monitoring signal transfer cable..............................................2-64
Table 3-1 Functions of the TMC11H...................................................................................................................3-2
Table 3-2 Electrical specifications of the TMC11H.............................................................................................3-3
Table 3-3 Engineering specifications of the TMC11H........................................................................................3-4
Table 3-4 Surge protection specifications of the TMC11H.................................................................................3-4
Table 3-5 Environmental specifications of the TMC11H....................................................................................3-5
Table 3-6 Pin assignment................................................................................................................................... 3-13
Table 3-7 Technical specifications of the fan.....................................................................................................3-13
Table 3-8 Specifications of the ports on the panel of the HPMI........................................................................3-14
Table 3-9 Functions of the CMUE.....................................................................................................................3-16
Table 3-10 Functions of the ports and indicators on a CMUE...........................................................................3-18
Table 3-11 Indicators on a CMUE..................................................................................................................... 3-19
Table 3-12 Specifications of the CMUE............................................................................................................ 3-20
Table 3-13 DC power distribution functions of the DCDU-11B/DCDU-11C...................................................3-23
Table 3-14 Specifications of the ports on the panel of the DCDU-11B/DCDU-11C........................................ 3-24
Table 3-15 Specifications of the heat exchanger core........................................................................................3-27
Table 3-16 Power cables and equipotential cables.............................................................................................3-32
Table 3-17 Signal cables.....................................................................................................................................3-33
Table 3-18 Specifications of the equipotential cable..........................................................................................3-35
Table 3-19 Specifications of the input power cable for the TMC11H (1)..........................................................3-36
Table 3-20 Specifications of the input power cable for the TMC11H (2)..........................................................3-37
Table 3-21 Specifications of the power cable for the fan box in the TMC11H................................................. 3-38
Table 3-22 Pin assignment for the wires of the power cable for the AC heater.................................................3-38
Table 3-23 Pin assignment for the wires of the signal cable for the ELU..........................................................3-40
Table 3-24 Pin assignment for the wires of the monitoring signal cable for the fan on the front door..............3-41
Table 4-1 Functions of the IBBS200D.................................................................................................................4-2
Table 4-2 Electrical specifications of the IBBS200D..........................................................................................4-3
Table 4-3 Engineering specifications of the IBBS200D......................................................................................4-3
Table 4-4 Environmental specifications of the IBBS200D..................................................................................4-4
Table 4-5 Ports on the PDB..................................................................................................................................4-8
Table 4-6 Functions of the CMUE.....................................................................................................................4-10
Table 4-7 Functions of the ports and indicators on a CMUE.............................................................................4-12
Table 4-8 Indicators on a CMUE....................................................................................................................... 4-14
Table 4-9 Specifications of the CMUE.............................................................................................................. 4-15
Table 4-10 Technical specifications of the 12 V 92 Ah storage battery............................................................ 4-17
Table 4-11 Power cables, PGND cables, and equipotential cable......................................................................4-21
Table 4-12 Signal cables.....................................................................................................................................4-22
Table 4-13 PGND cables....................................................................................................................................4-23
Table 4-14 Specifications of the equipotential cable..........................................................................................4-24
Table 4-15 Specifications of the input power cable for the fan in the IBBS200D.............................................4-27

xvi

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

Tables

Table 4-16 Specifications of the power transfer cable for the fan in the IBBS200D.........................................4-28
Table 4-17 Pin assignment for the wires of the signal cable for the ELU..........................................................4-30
Table 4-18 Pin assignment for the wires of the monitoring signal cable for the storage battery cabinet...........4-31
Table 5-1 Functions of the IBBS200T.................................................................................................................5-2
Table 5-2 Electrical specifications of the IBBS200T...........................................................................................5-3
Table 5-3 Engineering specifications of the IBBS200T.......................................................................................5-3
Table 5-4 Environmental specifications of the IBBS200T..................................................................................5-4
Table 5-5 Ports on the PDB..................................................................................................................................5-9
Table 5-6 Functions of the CMUE.....................................................................................................................5-11
Table 5-7 Functions of the ports and indicators on a CMUE.............................................................................5-13
Table 5-8 Indicators on a CMUE.......................................................................................................................5-14
Table 5-9 Specifications of the CMUE..............................................................................................................5-16
Table 5-10 Technical specifications of the 12 V 92 Ah storage battery............................................................5-17
Table 5-11 Power cables, PGND cables, and equipotential cable......................................................................5-21
Table 5-12 Signal cables.....................................................................................................................................5-22
Table 5-13 PGND cables....................................................................................................................................5-23
Table 5-14 Specifications of the equipotential cable..........................................................................................5-24
Table 5-15 Specifications of the input power cable for the TEC.......................................................................5-27
Table 5-16 Specifications of the power transfer cable for the TEC...................................................................5-28
Table 5-17 Pin assignment for the wires of the signal cable for the ELU..........................................................5-30
Table 5-18 Pin assignment for the wires of the monitoring signal cable for the storage battery cabinet...........5-31

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

xvii

1 Changes in the
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

Changes in the

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.C) Product Description
This chapter describes changes in the APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description.

04 (2011-07-08)
This is the fourth commercial release.
Compared with issue 03 (2011-06-10), no information is added.
Compared with issue 03 (2011-06-10), this issue incorporates the following changes:
Topic

Change Description

2.4 Structure of the APM30H

Changed the maximum quantity of filler panels


configured in the APM30H to 3.

4.3 Structure of the IBBS200D

Added the description of the heating film.

Compared with issue 03 (2011-06-10), no information is deleted.

03 (2011-06-10)
This is the third commercial release.
Compared with issue 02 (2011-05-30), no information is added.
Compared with issue 02 (2011-05-30), this issue incorporates the following changes:

Issue 04 (2011-07-08)

Topic

Change Description

3.5.2 DCDU-11B and


DCDU-11C

Modified the components controlled by the DC output


terminals.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

1-1

1 Changes in the
APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

Compared with issue 02 (2011-05-30), no information is deleted.

02 (2011-05-30)
This is the second commercial release.
Compared with issue 01 (2011-04-30), no information is added.
Compared with issue 01 (2011-04-30), this issue incorporates the following changes:
Topic

Change Description

EPU

Added the description about short-circuiting bars.

2.6.2 PGND Cables

Deleted the description about the PGND cable for the


modules.

2.6.3 Equipotential Cable

Modified the cable specifications.

3.2 Specifications of the


TMC11H

Modified the maximum input current in the electrical


specifications of the TMC11H.

Compared with issue 01 (2011-04-30), no information is deleted.

01 (2011-04-30)
This is the first commercial release.

1-2

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

APM30H Product Description

About This Chapter


This chapter describes the exterior, functions, specifications, usage scenarios, structure,
components, and cables of the APM30H.
2.1 Introduction to the APM30H
The APM30H, a power cabinet used for Huawei radio communication products outdoors,
provides direct current (DC) power supply for distributed base stations and outdoor macro base
stations used outdoors. It can house a BBU and transmission devices and features small footprint
and ease-of-transportation.
2.2 Specifications of the APM30H
The specifications of an APM30H consist of electrical specifications, engineering specifications,
surge protection specifications, and environmental specifications.
2.3 Usage Scenarios of the APM30H
The APM30H can be used for a distributed or outdoor macro base station.
2.4 Structure of the APM30H
The APM30H has a modular design with high integrity. This improves the operability and
maintainability of the APM30H.
2.5 APM30H Components
APM30H components include the fan box, embedded power subrack unit (EPU), outer air
circulation cooling component, junction box, electronic labeling unit (ELU), door status sensor,
filler panel, AC heater (optional), and service outlet unit (SOU, optional).
2.6 APM30H Cables
This section describes the PGND cables, equipotential cables, power cables, and signal cables
in the APM30H.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-1

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

2.1 Introduction to the APM30H


The APM30H, a power cabinet used for Huawei radio communication products outdoors,
provides direct current (DC) power supply for distributed base stations and outdoor macro base
stations used outdoors. It can house a BBU and transmission devices and features small footprint
and ease-of-transportation.

Exterior of the APM30H


The dimensions (H x W x D) of an APM30H without a base are 700 mm x 600 mm x 480 mm
(27.56 in. x 23.62 in. x 18.90 in.).
Figure 2-1 shows an APM30H.
Figure 2-1 APM30H

Functions of the APM30H


Table 2-1 describes the functions of the APM30H.
Table 2-1 Functions of the APM30H

2-2

Item

Description

Installation space for


customer equipment

The dimensions (H x W x D) are 7 U x 19 in. x 380 mm.

Battery cabinet
connection

The APM30H can be connected to a single battery cabinet to support


a maximum of one 48 V 184 Ah battery group or to two stacked
battery cabinets to support a maximum of one 48 V 368 Ah battery
group.

Power supply unit


(PSU) built in the
APM30H

l It converts input AC mains power into 48 V DC power.

The dimensions are the space for installing customer equipment


after a 5 U AC/DC power subrack is installed.

l It is hot-swappable.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Item

Description

Power monitoring unit


(PMU) built in the
APM30H

l It manages PSUs and charges/discharges storage batteries.


l It provides RS485 communication and dry contact alarm ports
for remote monitoring.
l It provides battery low-voltage disconnection (BLVD) and load
low-voltage disconnection (LLVD) functions.
l It is hot-swappable.

Power input detection

When an AC/DC embedded power supply system is configured, the


APM30H supports 220 V AC single-phase, 220 V AC three-phase,
and 110/120 V AC dual-live-line power.

AC power distribution

After going through the embedded power subrack unit (EPU), an


AC power input is divided into two AC power outputs:
l One output provides AC power for the service outlet unit (SOU).
l One is connected to the junction box on the left of the cabinet,
and divided into four AC power outputs, which are then provided
for the heater or heating film.

DC power distribution

For details, see Table 2-2.

Surge protection for


power supply and
signal ports

Surge protection circuits are provided for external AC/DC power,


monitoring alarm, and communication ports to protect the APM30H
from electric and lightning-induced surges.

Heat dissipation

The APM30H uses the core of the heat exchanger and inner and
outer air circulation fans for heat dissipation and dust prevention.

Grounding

The ground cable for the cabinet and ground cables for equipment
are connected to the ground bar of the cabinet.

Automatic reporting of
the cabinet type

The APM30H automatically reports the cabinet type using the


electronic labeling unit (ELU).

Table 2-2 describes the DC power distribution functions of the APM30H.


Table 2-2 DC power distribution functions of the APM30H

Issue 04 (2011-07-08)

Output
Terminal
Label

Protecti
on
Compo
nent
Circuit
breaker

Usage
Scenar
io

DC
Outp
ut

Distrib
uted
base
station

Six
LLVD
output
s

RRU

RRU0RRU5

Nine
BLV

TMC

TMC

Power
Device

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Quantit
y

DC
Output
Termina
l Type

25 A

30 A

Easy
power
receptacl
e (pressfit
type)
connector

Specific
ation

2-3

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Usage
Scenar
io

DC
Outp
ut
D
output
s

Outdoo
r macro
base
station

2-4

Power
Device

Output
Terminal
Label

Protecti
on
Compo
nent

Quantit
y
Specific
ation

BBU

BBU_0
and
BBU_1

TM

LOAD0
and
LOAD1

TM

LOAD2

FAN/TEC
(battery
cabinet)

LOAD3

EMUA

LOAD4

FAN

LOAD5

Batter
y
power
backu
p

BAT

Circuit
breaker

160 A

PP175
connector
(gray)
with a
cable of
the crosssectional
area of 35
mm2

Two
LLVD
output
s

RFC1 and
RFC2

Circuit
breaker

125 A

PP120
connector
(blue)
with a 25
mm2
cable

Nine
BLV
D
output
s

TMC

TMC

30 A

BBU

BBU_0
and
BBU_1

25 A

TM

LOAD0
and
LOAD1

5A

Easy
power
receptacl
e (pressfit
type)
connector

TM

LOAD2

15 A

FAN/TEC
(battery
cabinet)

LOAD3

Fuse

Fuse

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

25 A

5A

15 A

DC
Output
Termina
l Type

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

Usage
Scenar
io

DC
Outp
ut

Batter
y
power
backu
p

Power
Device

2 APM30H Product Description

Output
Terminal
Label

Protecti
on
Compo
nent

Quantit
y
Specific
ation

EMUA

LOAD4

FAN

LOAD5

BAT

Circuit
breaker

160 A

DC
Output
Termina
l Type

PP175
connector
(gray)
with a 35
mm2
cable

2.2 Specifications of the APM30H


The specifications of an APM30H consist of electrical specifications, engineering specifications,
surge protection specifications, and environmental specifications.

Electrical Specifications of the APM30H


Table 2-3 describes the electrical specifications of the APM30H.
Table 2-3 Electrical specifications of the APM30H
Item
AC
input
featu
res

Specification
Typical
input
voltage

200 V AC to 240 V AC (220 V AC single-phase)


200/346 V AC to 240/415 V AC (220/380 V AC three-phase)
100/200 V AC to 120/240 V AC (110 V AC dual-live-wire)
120/208 V AC to 127/220 V AC (120 V AC dual-live-wire)

Operating
voltage
range

176 V AC to 290 V AC (220 V AC single-phase)


176/304 V AC to 290/500 V AC (220/380 V AC three-phase)
90/180 V AC to 135/270 V AC (110 V AC dual-live-wire)
105/176 V AC to 150/260 V AC (120 V AC dual-live-wire)

Issue 04 (2011-07-08)

Frequenc
y of the
input
voltage

45 Hz to 65 Hz

Rated
input
current

53 A (220 V AC single-phase)
23 A (220/380 V AC three-phase)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-5

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Item

Specification
55 A (110 V AC dual-live-wire)
52 A (120 V AC dual-live-wire)
l 220/380 V AC three-phase

Input
mode

l 110 V AC dual-live-wire
l 120 V AC dual-live-wire
l 220 V AC single-phase

AC input
power

It varies depending on AC loads.


l 9062.5 W when the power supply unit (PSU) is configured
l 10062.5 W when the PSU, heater, and heating film are configured
l 10562.5 W when the PSU, heater, heating film, and SOU are
configured

DC
outp
ut
featu
res

Prote
ction
featu
res

Output
voltage
range

43.2 V DC to 57 V DC

Output
current

0 A to 150 A

Typical
output
voltage

53.5 V DC

Number
of DC
outputs

The number of DC outputs varies depending on usage scenarios.

DC
output
power

8700 W (the maximum output power of a single module is 2900 W


when no PSU backup is available)

Input
protectio
n

l Overvoltage protection: An alarm is generated when the input voltage


is greater than a specified AC overvoltage alarm threshold (280 V by
default).

l 16 DC outputs for a distributed base station


l 12 DC outputs for an outdoor macro base station

l Undervoltage protection: An alarm is generated when the input


voltage is less than a specified AC undervoltage alarm threshold (180
V by default).
Output
protectio
n

l Overvoltage protection: An alarm is generated when the busbar


voltage is greater than a specified DC overvoltage alarm threshold (
58 V by default).
l Undervoltage protection: An alarm is generated when the busbar
voltage is less than a specified DC undervoltage alarm threshold (
45 V by default).
l Overcurrent and short circuit protection

2-6

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

Item

Specification

Permissible heat
consumption in
the cabinet

1050 W

2 APM30H Product Description

Engineering Specifications of the APM30H


Table 2-4 describes the engineering specifications of the APM30H.
Table 2-4 Engineering specifications of the APM30H
Item

Specification

Remarks

Weight

68 kg

Total weight of the equipment


l Including the cabinet frame, inner air
circulation fan box, outer air circulation fan
box, core of the heat exchanger, embedded
power subrack unit (EPU), and cables
l Excluding the baseband processing unit
(BBU), customer equipment, power
monitoring unit (PMU), and PSUs

87 kg

Weight of the cabinet in full configuration


l Including the cabinet, one PMU, three
PSUs, and one BBU
l Excluding customer equipment

Issue 04 (2011-07-08)

Cabinet
dimensions (H x
W x D)

700 mm x 600 mm x
480 mm

The base is not included.

Base dimensions
(H x W x D)

200 mm x 600 mm x
434 mm

Customer
equipment
dimensions (H x
W x D)

7 U x 19 in. x 380 mm

The depth consists of the rear (280 mm) and


front (100 mm) of the installation plane for
subrack mounting ears.

Space for cabling


and maintenance
in front of the
cabinet

70 mm

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-7

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Item

Specification

Remarks

Installation
option

The APM30H can be


installed on a floor,
wall, or pole. It can also
be stacked with the
radio frequency cabinet
(RFC), IBBS200D, or
IBBS200T.

The APM30H must be placed on the RFC,


IBBS200D, or IBBS200T in stacking mode.

Surge Protection Specifications of the APM30H


Table 2-5 describes the surge protection specifications of the APM30H.
Table 2-5 Surge protection specifications of the APM30H
Item

Specification

Surge protection for the AC


input port

Differential mode:
l Rated discharge current In (8/20 s): 30 kA
l Maximum discharge current Imax (8/20 s): 60 kA
Common mode:
l Rated discharge current In (8/20 s): 30 kA
l Maximum discharge current Imax (8/20 s): 60 kA

Surge protection for the DC


output port

l Differential mode (8/20 s): 10 kA


l Common mode (8/20 s): 20 kA
Loads corresponding to the DC output port are minor loads.
NOTE
The surge protection level of the shield layer of an RRU power cable
is 40 kA.

Surge protection for signal


ports

E1/T1 port:
l Differential mode (8/20 s): 3 kA
l Common mode (8/20 s): 5 kA
FE port:
l Differential mode (8/20 s): 3 kA
l Common mode (8/20 s): 5 kA

Environmental Specifications of the APM30H


The APM30H can be used outdoors. Table 2-6 describes the environmental specifications of
the APM30H.

2-8

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Table 2-6 Environmental specifications of the APM30H


Item

Specification

Remarks

Operating
temperatur
e

40C to +50C

A heater is required when the


operating temperature is below 20C.
A sun shield is required when the
operating temperature is above 50C.
NOTE
The operating temperature when a heater
is configured is obtained from the average
lowest temperature of all days in the
coldest month of a year.

Relative
humidity

5% RH to 100% RH

Altitude

60 m to 4000 m

Above the altitude of 1800 m, the


maximum operating temperature
decreases by 1C each time the altitude
increases by 220 m.

Wind
speed

67 m/s

Storage
temperatur
e

40C to +70C

Dustproof
and
waterproof
class

IP55

Noise level

61 dBA at 25C or 67 dBA at


45C when the total power
consumption is less than or equal to
700 W

Meeting the ETS 300 753 4.1E


standard (rural areas)

66 dBA at 25C or 76 dBA at


45C when the total power
consumption is greater than 700 W
and less than or equal to 1050 W

Meeting the ETS 300 753 4.1E


standard (urban areas)

2.3 Usage Scenarios of the APM30H


The APM30H can be used for a distributed or outdoor macro base station.

Used for a Distributed Base Station


When the APM30H is used for a distributed base station:

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-9

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

The APM30H provides 7 U-high space for installing the BBU and transmission equipment.
The embedded power supply system provides 48 V DC power to the distributed base
station and transmission equipment and charges battery groups in a battery cabinet.

When no mains are available, the battery groups in a battery cabinet provide 48 V DC
power to the distributed base station and transmission equipment.

Figure 2-2 shows a scenario where the APM30H is stacked with a battery cabinet and is used
for a distributed base station.
Figure 2-2 Scenario where the APM30H is stacked with a battery cabinet and is used for a
distributed base station

NOTE

When the APM30H is used for a distributed base station, the IBBS200D or IBBS200T can be selected.
Figure 2-2 uses the IBBS200D as an example.

Used for an Outdoor Macro Base Station


When the APM30H is used for an outdoor macro base station:
l

2-10

The APM30H provides 7 U-high space for installing the baseband processing unit (BBU)
and transmission equipment. The embedded power supply system provides 48 V DC
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

power to the BBU, radio frequency unit (RFU), and transmission equipment and charges
battery groups in a battery cabinet.
l

When no mains are available, the battery groups in a battery cabinet provide 48 V DC
power to the BBU, RFU, and transmission equipment.

The APM30H provides alarm reporting functions for radio frequency cabinet (RFC) fans,
door status sensor, direct current distribution unit (DCDU), and battery cabinet.

Figure 2-3 shows a scenario where the APM30H is used for an outdoor macro base station.
Figure 2-3 Scenario where the APM30H is used for an outdoor macro base station

NOTE

When the APM30H is used for an outdoor macro base station, the IBBS200D or IBBS200T can be
configured. Figure 2-3 uses the IBBS200D as an example.

2.4 Structure of the APM30H


The APM30H has a modular design with high integrity. This improves the operability and
maintainability of the APM30H.
Figure 2-4 shows the structure of the APM30H.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-11

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Figure 2-4 Structure of the APM30H

2-12

S
N

Name

Op
tio
nal
or
Ma
nd
ato
ry

Maxi
mum
Qua
ntity
Conf
igure
d in a
Singl
e
Cabi
net

Description

(1)

Fan box

Ma
nda
tor
y

The fan box is equipped with fans, a HERT power


monitoring interface unit (HPMI), and a central
monitoring unit type E (CMUE). It is used to dissipate
heat in the cabinet.

(2)

Door status
sensor

Ma
nda
tor
y

The door status sensor monitors the opening and closing


of the front door of the cabinet.

(3)

Electronic
labeling
unit (ELU)

Ma
nda
tor
y

The ELU reports the cabinet type automatically to


facilitate fault identification.

(4)

Embedded
power
subrack unit
(EPU)

Ma
nda
tor
y

The EPU converts AC power into DC power and supplies


power to the devices inside the cabinet. The EPU consists
of the EPU subrack, power monitoring unit (PMU), and
AC/DC power supply unit (PSU).

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

S
N

Name

Op
tio
nal
or
Ma
nd
ato
ry

Maxi
mum
Qua
ntity
Conf
igure
d in a
Singl
e
Cabi
net

Description

(5)

Filler panel

Ma
nda
tor
y

The filler panel is a 1 U-high plastic component that


prevents hot air recirculation in blank space of the BBU
subrack.

(6)

AC heater

Opt
ion
al

The AC heater is an optional component. It ensures that


the customer equipment in the cabinet works in a proper
temperature range when the ambient temperature is low.
It is installed in the 1 U space at the bottom of the cabinet.
If both the AC heater and service outlet unit (SOU) are
configured, the AC heater is installed in the 1 U space
above the SOU.

(7)

SOU

Opt
ion
al

The SOU is an optional component. It transfers AC


power supply to the customer equipment and is installed
in the 1 U space at the bottom of the cabinet.

(8)

Outer air
circulation
cooling
component

Ma
nda
tor
y

It is installed on the front door of the cabinet, dissipating


heat in the cabinet.

(9)

Junction
box

Ma
nda
tor
y

The junction box distributes one AC input to four


outputs. It is used in scenarios where an SOU and
multiple heating films or heaters are configured.

In the APM30H structure,


l

The 7 U space for customer equipment is available when no AC heater or SOU is installed
in the APM30H.

It take 1 U space for customer equipment when an AC heater or SOU is installed in the
APM30H.

2.5 APM30H Components


APM30H components include the fan box, embedded power subrack unit (EPU), outer air
circulation cooling component, junction box, electronic labeling unit (ELU), door status sensor,
filler panel, AC heater (optional), and service outlet unit (SOU, optional).

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-13

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

2.5.1 Fan Box


The fan box consists of the fan subrack, fan, HERT power monitoring interface unit (HPMI),
and central monitoring unit type E (CMUE).
2.5.2 EPU
The embedded power subrack unit (EPU) converts AC power into DC power and supplies power
to components in the cabinet.
2.5.3 Outer Air Circulation Cooling Component
The outer air circulation cooling component consists of the heat exchanger core and fan. The
heat exchanger core can speed up inner and outer air circulation to reduce the operating
temperature of the cabinet. It can also prevent dust from entering the cabinet. The fan dissipates
heat in the cabinet.
2.5.4 Junction Box
The junction box divides one AC input into four AC outputs. The AC outputs are used for the
SOU and multiple heating films or heaters.
2.5.5 ELU
The Electronic Label Unit (ELU) automatically reports the information about the cabinet type,
facilitating fast troubleshooting.
2.5.6 Door Status Sensor
The door status sensor monitors the opening and closing of the front door of the cabinet.
2.5.7 Filler Panel
The filler panel is a 1 U-high plastic component, which is made of polycarbonate. It is installed
in the blank space below the baseband unit (BBU) to dissipate heat in the cabinet.
2.5.8 AC Heater (Optional)
The AC heater is an optional component. It ensures that customer equipment in the APM30H
works in a proper temperature range when the ambient temperature is low.
2.5.9 SOU (Optional)
The Service Outlet Unit (SOU) feeds AC power to the customer equipment. The SOU is optional.

2.5.1 Fan Box


The fan box consists of the fan subrack, fan, HERT power monitoring interface unit (HPMI),
and central monitoring unit type E (CMUE).
Figure 2-5 shows a fan box.

2-14

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Figure 2-5 Fan box

(1) Fan subrack

(2) Fan

(3) CMUE

(4) HPMI

Fan
Fan is installed in the fan box of a cabinet, dissipating the heat in the cabinet. Signal cable is
delivered with fan.

Exterior
Figure 2-6 shows a fan.
Figure 2-6 Fan

Figure 2-7 shows the signal cable delivered with a fan.


Figure 2-7 Signal cable delivered with a fan

NOTE

The signal cable delivered with a fan feeds power into the fan and monitors the fan.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-15

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Pin Assignment
Table 2-7 describes the pin assignment for the wires of the signal cable delivered with a fan.
Table 2-7 Pin assignment
Wire

X1
End

Color

Description

W1

A.1

Red

Connects to the positive pole.

W2

A.2

Yello
w

Receives pulse-width modulation (PWM) speed-adjusting


signals.

W3

A.3

Blue

Receives alarm or speed signals.

W4

A.4

Black

Connects to the negative pole.

NOTE

The color of the signal cable delivered with a fan varies depending on manufacturers.

Specifications
Table 2-8 lists the technical specifications of a fan.
Table 2-8 Technical specifications of the fan

2-16

Item

Specification

Dimensions (diameter x
height)

175 mm x 69 mm

Length of the lead

600 mm

Rated voltage

48 V

Operating voltage range

36 V DC to 60 V DC

Rated current

1.3 A

Maximum current

2.1 A

Rated power

62 W

Maximum power

100 W

Rated traffic volume

697 m3/h

Rated speed

4000 r/min

Speed-adjusting mode

PWM mode

Operating temperature

25C to +70C

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

HPMI
The HERT power monitoring interface unit (HPMI) provides input and output ports for alarm
signals.

Exterior
Figure 2-8 shows an HPMI.
Figure 2-8 HPMI

Ports
Figure 2-9 shows the ports on the panel of the HPMI. Table 2-9 lists the specifications of the
ports on the panel of the HPMI.
Figure 2-9 Ports on the panel of the HPMI

Table 2-9 Specifications of the ports on the panel of the HPMI


Silkscreen

Issue 04 (2011-07-08)

Port Function

Port Relationship with the Related


Cabinet(1) (2)
APM30H

TMC11H

PMU_DB50

Connects to the PMU


and reports alarms
collected by the
HPMI to the BBU.

OUT0 and OUT1

Provides one
Boolean output at
each port.

Reserved

Reserved

IN0, IN1, and IN2

Provides one
Boolean input at each
port.

Reserved

Reserved

FUSE

Reserved for fuse


detection

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-17

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Silkscreen

Port Function

Port Relationship with the Related


Cabinet(1) (2)
APM30H

TMC11H

GATE

Connects to the door


status sensor and
receives door status
alarms.

Mandatory

Reserved

IN3, IN4

Provides one
Boolean input at each
port.

Reserved

Reserved

TEM_BAT1

Connects to the
temperature sensor
for storage batteries
in IBBS2.1 and
IBBS2.2 and
receives battery
temperature alarms.

Optional

Reserved

SMOKE

Connects to the
smoke sensor and
receives smoke
alarms.

Reserved

Reserved

WATER

Connects to the water


sensor and receives
water damage
alarms.

Reserved

Reserved

TEM_HUM

Connects to the
temperature and
humidity sensor and
receives temperature
and humidity alarms.

Reserved

Reserved

NOTE

(1) Mandatory monitoring devices and related monitoring signal cables are installed in a cabinet before the
cabinet is delivered. Optional devices are configured based on customer requirements, and related cables
must be installed onsite. For details about how to connect the cables, see the , , BTS3900A (Ver.C)
Installation Guide, , and .
(2) For details about the positions of devices monitored by the HPMI, see Structure of the BTS3900A
Cabinets.

CMUE
The central monitoring unit type E (CMUE) monitors the temperature of the fan box, heater,
and cabinet. The CMUE can be used for cabinets such as the AMP30H, RFC, TMC11H,
IBBS200D, and IBBS200T.

2-18

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Function
Table 2-10 describes the functions of the CMUE.
Table 2-10 Functions of the CMUE
Function

Description

Pulse-width
modulation
(PWM) speed
adjusting

Fan speeds can be adjusted based on temperature or controlled by the


baseband unit (BBU).

Fan speed query

Fan speeds can be queried by running a query command.

Full speed rotation


when a fan is faulty

When a fan in the fan subrack is faulty, other fans rotate at a full speed.

Full speed rotation


when the CPU is
faulty

Alarm reporting
when the fan box is
faulty

The alarms are as follows:


l Communication failure alarm
l Fan fault alarm
l Abnormal temperature alarm
l Smoke, water damage, or door status alarm
l Hardware fault alarm (related to the I2C fault)
The alarms are reported through an RS485 bus.

Issue 04 (2011-07-08)

Thermoelectric
cooling unit (TEC)
control and
detection

The CMUE controls the starting and stopping of the TEC and detects
its current and voltage.

Environment
monitoring

The CMUE detects the board temperature and air inlet temperature and
monitors the environment such as smoke, water damage, and door
status.

Boolean value
detection

The CMUE provides four Boolean inputs such as AC/DC surge


protector and door status sensor alarms.

Protection against
reverse connection

The CMUE provides protection against reverse connection.

Status indication

The CMUE provides one red indicator and one green indicator to
indicate the operating status of the board.

RS485 port
cascading and
extension

When a cabinet uses two fan subracks or cabinets are combined, the fan
box automatically identifies communication addresses.

Online loading

The CMUE supports online loading through an RS485 bus.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-19

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Function

Description

Surge protection

l The power socket provides surge protection of 1 kV in differential


mode and 2 kV in common mode.
l An RS485 bus supports surge protection of 250 A.
l IN0 and GATE Boolean inputs support surge protection of 250 A.
l IN1 and IN2 Boolean inputs support surge protection of 3 kA in
differential mode and 5 kA in common mode.

Electronic labeling

The CMUE supports electronic labeling for boards and external


cabinets.

Protection against
short-circuiting of
smoke, water, and
temperature
sensors

When short-circuiting occurs on a port, the CMUE provides currentlimiting protection based on positive temperature coefficient (PTC)
thermal resistance or other resistance.

Exterior
Figure 2-10 shows a CMUE.
Figure 2-10 CMUE

Ports
Figure 2-11 shows ports and indicators on a CMUE.
Figure 2-11 Ports and indicators on a CMUE

2-20

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Table 2-11 describes functions of the ports and indicators on a CMUE.


Table 2-11 Functions of the ports and indicators on a CMUE
S
N

Port or
Indicator

Description

(1)

TEMP2

Connects to a temperature sensor. The port is reserved.

(2)

WATER

Connects to a water sensor.

(3)

IFAN4

Connects to an inner air circulation fan.

(4)

IFAN3

Connects to an inner air circulation fan.

(5)

IFAN2

Connects to an inner air circulation fan.

(6)

IFAN1

Connects to an inner air circulation fan.

(7)

TEC

Connects to the TEC and receives alarms related to the TEC.

(8)

TEMP1

l Connects to the temperature sensor at the air inlet of an RFC and


receives temperature alarms.
l Connects to the battery temperature sensor in the IBBS200D or
IBBS200T and receives battery temperature alarms.

(9)

COM_OUT

This port is an RS485 signal port that connects to a lower-level port and
reports monitoring information.
l Connects to the power monitoring unit (PMU) in the APM30H.
l Connects to a lower-level CMUE in the RFC, TMC11H, IBBS200D,
or IBBS200T.

(10
)

COM_IN

This port is an RS485 signal port that connects to an upper-level port


and receives monitoring information.
l Connects to the baseband unit (BBU) in the APM30H.
l Connects to the BBU or an upper-level CMUE in the RFC or
TMC11H.
l Connects to the PMU or an upper-level CMUE in the IBBS200D or
IBBS200T.

Issue 04 (2011-07-08)

(11
)

RUN
indicator

Indicates the operating status of fans.

(12
)

ALM
indicator

Indicates the alarm status of fans.

(13
)

ELU

Connects to the electronic labeling unit (ELU) and reports the cabinet
type.

(14
)

GATE

Connects to the door status sensor. This port is a Boolean signal port.

(15
)

IN0, IN1,
IN2

This port is a reserved Boolean signal port.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-21

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

S
N

Port or
Indicator

Description

(16
)

SMOKE

Connects to the smoke sensor. This port is a Boolean signal port.

(17
)

EFAN1

Connects to an outer air circulation fan.

(18
)

EFAN2

Connects to an outer air circulation fan.

(19
)

PWR

Feeds DC power to boards. This is a power socket.

Indicators
Table 2-12 describes the indicators on a CMUE.
Table 2-12 Indicators on a CMUE
Label

Color

State

Description

RUN

Green

Blinking (on for 1s and


off for 1s)

The board is functional and communicates


with its upper-level device properly.

Blinking (on for 0.125s


and off for 0.125s)

The board is functional, but the


communication with its upper-level device
fails or the board is not registered.

Steady on

The board is in the power-on self-test state.

Off

The board is faulty.

Off

No alarm is reported.

Steady on

An alarm is generated, and the board needs to


be replaced.

Blinking (on for 1s and


off for 1s)

An alarm is generated, and the alarm may be


caused by an associated board or port fault.
Therefore, you must identify the fault before
replacing the board.

ALM

Red

DIP Switch
The CMUE has one dual in-line package (DIP) switch J18, which is used to set the working
mode of the CMUE based on the cabinet type. Figure 2-12 shows the position of the DIP switch
on the CMUE.

2-22

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Figure 2-12 Position of the DIP switch on the CMUE.

Figure 2-13 shows DIP switch settings of the CMUE in different cabinets.
Figure 2-13 DIP switch settings of the CMUE in different cabinets

NOTE

The red rectangles in Figure 2-13 indicate the positions for inserting jumper pins.

Specification
Table 2-13 describes the specifications of the CMUE.
Table 2-13 Specifications of the CMUE
Item

Specification

Description

Power
consumption

The following specifications are


described:

l The maximum power


consumption of the board circuit
is 3 W.
l The CMUE supports a
maximum of four fans and its
maximum power consumption
is 400 W.
l When the CMUE is connected
to a TEC, the maximum power
consumption is 750 W.
Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-23

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Item

Specification

Description

Input voltage
range

36 V DC to +60 V DC

Temperature
detection range

45C to 70C

The DS1820 digital temperature


sensor is used for temperature
detection.

Temperature
detection error

2C

Fan speed
adjustment

Four PWM signal outputs

A maximum of four fans are


supported. Each fan uses a separate
PWM signal output to control fan
speed and status detection in real
time.

Alarm reporting

Alarms reported to the main control


unit through an RS485 serial port.

The board supports one alarm


output through a bus.

Communication
port

Standard RS485 serial port

Operating
temperature
range

40C to 60C

Operating
altitude

4000 m

2.5.2 EPU
The embedded power subrack unit (EPU) converts AC power into DC power and supplies power
to components in the cabinet.
The EPU consists of the EPU subrack, power monitoring unit (PMU), and AC/DC power supply
unit (PSU).
Figure 2-14 shows an EPU.

2-24

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Figure 2-14 EPU

(1) PMU

(2) PSU

(3) Extraction tool

(4) Spare fuse box

(5) EPU subrack

(6) Output terminal for RFC1

(7) Output terminal for RFC2

(8) Output terminal for storage batteries

NOTE

The exterior of EPU for an outdoor macro base station is different from the EPU for a distributed base
station. Figure 2-14 takes the EPU for an outdoor macro base station as an example.

EPU
The APM30H supports four types of embedded power subrack units (EPUs), which are used for
a distributed or outdoor macro base station in the case of different AC inputs.

EPU Types
Table 2-14 describes the types and usage scenarios of the EPU in the AMP30H.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-25

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Table 2-14 Types and usage scenarios of the EPU


Type

Description

Usage Scenario

EPU03A
-02

The 5 U EPU supports three


4850 power supply units
(PSUs) and one power
monitoring unit (PMU). It
also supports DC large-power
and small-capacity power
distribution.

Outdoor macro base station in the case of 220 V


AC input

EPU03A
-03

The 5 U EPU supports three


4850 PSUs and one PMU. It
also supports DC large-power
and small-capacity power
distribution.

Distributed base station in the case of 220 V AC


input

EPU03A
-04

The 5 U EPU supports three


4850 PSUs and one PMU. It
also supports DC large-power
and small-capacity power
distribution.

Outdoor macro base station in the case of 110 V


AC input

EPU03A
-05

The 5 U EPU supports three


4850 PSUs and one PMU. It
also supports DC large-power
and small-capacity power
distribution.

Distributed base station in the case of 110 V AC


input

Exterior
The EPU03A-03 and EPU03A-05 are used for a distributed base station. Figure 2-15 and Figure
2-16 show the EPU03A-03 and EPU03A-05 respectively.

2-26

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Figure 2-15 EPU03A-03

(1) AC INPUT

(2) AC OUTPUT

(3) Circuit breakers for


PSU1 to PSU3

(4) Circuit breaker for AC


OUTPUT

(5) Circuit breaker for


storage batteries

(6) Circuit breaker for (7) Circuit breaker for


the TMC
BBU_0

(8) Circuit breaker for


BBU_1

(9) Circuit breakers for


RRU0 to RRU5

(10) Extraction tool

(11) Spare fuse box

(12) Output terminal for


storage batteries

(13) DC output terminal

(14) Fuse

(15) AC surge protector

(16) Short-circuiting bar(1)

NOTE

(1) A short-circuiting bar is configured on the AC INPUT wiring terminals of the EPU subrack supplied with
220 V AC power. This enables the AC INPUT wiring terminals labeled L1, L2, and L3 to be connected for 220
V AC single-phase power input. If no short-circuiting bar is configured, the EPU subrack is used for 220 V AC
three-phase power input.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-27

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Figure 2-16 EPU03A-05

(1) AC INPUT

(2) AC OUTPUT

(3) Circuit breaker for the


PSU

(4) Circuit breaker for AC


OUTPUT1

(5) Circuit breaker for AC (6) Circuit breaker for (7) Circuit breaker for the
OUTPUT2
storage batteries
TMC

(8) Circuit breaker for


BBU_0

(9) Circuit breaker for


BBU_1

(10) Circuit breakers


for RRU0 to RRU5

(11) Extraction tool

(12) Spare fuse box

(13) Output terminal for


storage batteries

(14) DC output
terminal

(15) Fuse

(16) AC surge protector

The EPU03A-02 and EPU03A-04 are used for an outdoor macro base station. Figure 2-17 and
Figure 2-18 show the EPU03A-02 and EPU03A-04 respectively.

2-28

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Figure 2-17 EPU03A-02

(1) AC INPUT

(2) AC OUTPUT

(5) Circuit breaker for


storage batteries

(6) Circuit breaker for the (7) Circuit breaker for


TMC
BBU_0

(8) Circuit breaker for


BBU_1

(9) Circuit breaker for


RFC1

(10) Circuit breaker for


RFC2

(11) Extraction tool

(12) Spare fuse box

(13) Output terminal for (14) Output terminal for


storage batteries
RFC2

(15) Output terminal for


RFC1

(16) DC output terminal

(17) Fuse

(19) Short-circuiting bar(1) -

(18) AC surge protector

(3) Circuit breakers for


PSU1 to PSU3

(4) Circuit breaker for AC


OUTPUT

NOTE

(1) A short-circuiting bar is configured on the AC INPUT wiring terminals of the EPU subrack supplied with
220 V AC power. This enables the AC INPUT wiring terminals labeled L1, L2, and L3 to be connected for 220
V AC single-phase power input. If no short-circuiting bar is configured, the EPU subrack is used for 220 V AC
three-phase power input.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-29

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Figure 2-18 EPU03A-04

(1) AC INPUT

(2) AC OUTPUT

(3) Circuit breaker for the (4) Circuit breaker for AC


PSU
OUTPUT1

(5) Circuit breaker for AC (6) Circuit breaker for


OUTPUT2
storage batteries

(7) Circuit breaker for the (8) Circuit breaker for


TMC
BBU_0

(9) Circuit breaker for


BBU_1

(10) Circuit breaker for


RFC1

(11) Circuit breaker for


RFC2

(13) Spare fuse box

(14) Output terminal for


storage batteries

(15) Output terminal for (16) Output terminal for


RFC2
RFC1

(17) DC output terminal

(18) Fuse

(19) AC surge protector -

(12) Extraction tool

Function
The EPU provides AC and DC power distribution functions.
l

The EPU provides the following AC power distribution functions:


Provides two AC outputs, one for the service outlet unit (SOU) and the other for the
junction box on the left of the cabinet. After the power distribution through the AC
power distribution box, four AC outputs are supplied to the heater or heating film.
Reports AC input surge protection alarms.

The EPU provides 16 or 12 DC outputs for a distributed or outdoor macro base station.

Table 2-15 describes the DC power distribution functions of the EPU in the APM30H used for
a distributed base station.

2-30

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Table 2-15 DC power distribution functions of the EPU in the APM30H used for a distributed
base station
DC Power
To...

DC
Output
Terminal

Protection
Compone
nt

Specificati
on

Quantity

DC Output
Terminal
Type

RRU

RRU0 to
RRU5

Circuit
breaker

25 A

TMC

TMC

30 A

Easy power
receptacle
(pressfit type)
connector

BBU

BBU_0 and
BBU_1

25 A

TM

LOAD0
and
LOAD1

5A

TM

LOAD2

15 A

FAN/TEC
(battery
cabinet)

LOAD3

EMUA

LOAD4

FAN

LOAD5

BAT

Fuse(1)

Circuit
breaker

160 A

PP175
connector
(gray) with a
35 mm2 cable

Table 2-16 describes the DC power distribution functions of the EPU in the APM30H used for
an outdoor macro base station.
Table 2-16 DC power distribution functions of the EPU in the APM30H used for an outdoor
macro base station

Issue 04 (2011-07-08)

DC Power
To...

DC Output
Terminal

Protection
Componen
t

Specificati
on

Quantity

DC Output
Terminal
Type

RFC1 and
RFC2

Circuit
breaker

125 A

PP120
connector
(blue) with a
25 mm2
cable

TMC

TMC

30 A

BBU

BBU_0 and
BBU_1

25 A

Easy power
receptacle
(pressfit

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-31

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

DC Power
To...

DC Output
Terminal

Protection
Componen
t

Specificati
on

Quantity

DC Output
Terminal
Type

TM

LOAD0 and
LOAD1

Fuse(2)

5A

type)
connector

TM

LOAD2

15 A

FAN/TEC
(battery
cabinet)

LOAD3

EMUA

LOAD4

FAN

LOAD5

BAT

Circuit
breaker

160 A

PP175
connector
(gray) with a
35 mm2
cable

NOTE

(1) and (2): The spare fuse box provides two types of fuse: 5 A and 15 A, which can be selected as required.

Specifications of the EPU


Table 2-17 describes specifications of the EPU.
Table 2-17 Specifications of the EPU
Name

Specification

Output voltage

44 V DC to 58 V DC

Rated voltage

53.5 V DC

Output current

0 A to 150 A

PMU
The power monitoring unit (PMU) provides the functions of power system and battery
management, power monitoring, and alarm reporting.

Function
The PMU performs the following functions:

2-32

Communicates with the baseband unit (BBU) through an RS485 serial port.

Manages the power system and charges and discharges the storage batteries.
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Checks and reports Boolean values of the door status sensor and standby sensor, and reports
the analog values of the temperature and humidity, battery temperature, and standby analog
value.

Monitors the power supply and reports alarms, including dry contact alarms.

Communicates with the battery cabinet through an RS485 serial port.

Exterior
Figure 2-19 shows a PMU.
Figure 2-19 PMU

Ports and Indicators


Figure 2-20 shows the ports, indicators, and switch on the front panel of the PMU. Figure
2-21 shows the rear panel of the PMU.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-33

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Figure 2-20 Ports, indicators, and switch on the front panel of the PMU

(1) Power supply unit (PSU) status indicator

(2) Power test port

(3) Control switch of storage batteries

(4) COM port

(5) COM_485 port

(6) COM_OUT port

(7) COM_IN port

Figure 2-21 Rear panel of the PMU

(1) Port on the rear panel

Table 2-18 describes the ports and switch on the PMU.


2-34

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Table 2-18 Ports and switch on the PMU


Port/Switch

Description

COM_IN

Connects to the BBU or upper-level device and reports alarms to


the BBU.

COM_OUT

Connects to lower-level devices such as the EMUA and collects


alarms from lower-level devices.

COM_485

Connects to the CMUE in the IBBS200D/IBBS200T and collects


alarms from the battery cabinet.

COM

Connects to the HPMI and collects alarms from the HPMI.

Control switch of
storage batteries

Powers on and powers off storage batteries through the ON and OFF
ports.
l Insert a round stick into the ON port and hold down it for 5s to
10s. When you hear a click, the storage batteries are connected
and the power-on operation is successful.
l Insert a round stick into the OFF port and hold it down for 5s to
10s. When you hear a click, the storage batteries are
disconnected and the power-off operation is successful.

Table 2-19 describes the indicators on the PMU.


Table 2-19 Indicators on the PMU

Issue 04 (2011-07-08)

Label

Color

State

Description

RUN

Green

Blinking (on for 1s and


off for 1s)

The PMU is functional and is communicating


with the BBU properly.

Blinking (on for 0.125s


and off for 0.125s)

The PMU is functional, but its


communication with the BBU fails. If the
PMU does not communicate with the BBU
for 1 minute, the communication is regarded
failed.

Steady on or off

The PMU is faulty (when it is not in the


power-on self-test state).

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-35

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Label

Color

State

Description

ALM

Red

Steady on

The base station reports at least one of the


following alarms:
l Mains failure alarm (including mains
phase loss)
l Mains power overvoltage or undervoltage
alarm
l Busbar overvoltage or undervoltage
alarm
l Charging overcurrent alarm
l Battery power-off alarm
l Battery group circuit failure alarm
l Environmental temperature alarm
l Ambient humidity alarm
l PSU alarm
l Load power-off alarm

Off

No alarm is generated.

NOTE

Within 3s to 5s after the PMU is powered on, the ALM and RUN indicators are on simultaneously for
about 3s.

DIP Switch
The DIP switch is located on the right of the PMU. The DIP switch has eight bits, where the
four least significant bits (1, 2, 3, and 4) define the monitoring address of the PMU, and the four
most significant bits (5, 6, 7, and 8) are not defined and are reserved for future use.
The ON position indicates 1, and the OFF position indicates 0. The default monitoring address
of the PMU is set to 3 before delivery, as shown in Figure 2-22.
Figure 2-22 DIP switch on the right of the PMU

2-36

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

NOTE

When two PMUs share the same RS485 bus in the case that two or more APM30Hs are configured in a base
station, the monitoring address of the second PMU is set to 4.

PSU
A power supply unit (PSU) converts 110 V AC or 220 V AC power into 48 V DC power.

Functions
A PSU (AC/DC) performs the following functions:
l

Converts 110 V AC or 220 V AC power into 48 V DC power, adjusts voltage and current,
and supports hot swap.

Monitors module fault alarms (such as output overvoltage, no output, and fan failure) and
module protection alarms (such as overtemperature, input overvoltage protection, and input
undervoltage protection).

Exterior
Figure 2-23 shows a PSU.
Figure 2-23 PSU

Indicators
Figure 2-24 shows a PSU (AC/DC) panel.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-37

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Figure 2-24 PSU (AC/DC) panel

(1) Running status indicator

(2) Protection indicator

(3) Fault indicator

Table 2-20 describes the indicators on a PSU (AC/DC) panel.


Table 2-20 Indicators on a PSU (AC/DC) panel
Indicator

Color

Status

Description

Running status
indicator

Green

Steady on

The PSU is operating


properly.

Off

l The PSU
experiences a
mains-supply
related fault (such
as no AC input,
AC input
overvoltage, or
AC input
undervoltage).
l The PSU has no
power output.
l The input fuse is
faulty.

Protection indicator

Yellow

Off

The PSU is operating


properly.

Steady on

A temperature alarm
is reported.
The protection
indicator is on when
the cabinet is in the
dormant state even if
no alarm is reported.

2-38

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Indicator

Color

Status

Description

Fault indicator

Red

Off

The PSU is operating


properly, or the PSU
has no power output
due to a mainssupplyrelated fault
(such as no AC input,
AC input
overvoltage, or AC
input undervoltage).

Steady on

l The PSU is
powered off due
to output
overvoltage
protection or
overtemperature
protection, fans
are faulty, or the
PSU is powered
off remotely.
l The PSU
experiences other
internal faults.
l The PSU has no
power output due
to a fault.

2.5.3 Outer Air Circulation Cooling Component


The outer air circulation cooling component consists of the heat exchanger core and fan. The
heat exchanger core can speed up inner and outer air circulation to reduce the operating
temperature of the cabinet. It can also prevent dust from entering the cabinet. The fan dissipates
heat in the cabinet.

Exterior
The outer air circulation cooling component is located on the inner side of the front door of the
APM30H. Figure 2-25 shows an outer air circulation cooling component.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-39

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Figure 2-25 Outer air circulation cooling component

(1) Heat exchanger core

(2) Fan

Heat Exchanger Core


Table 2-21 describes specifications of the heat exchanger core.
Table 2-21 Specifications of the heat exchanger core
Item

Specification

Dimensions (H x W x D)

415 mm x 390 mm x 89.5 mm

Heat dissipation capability

58.3 W/K

Fan
For details about specifications of the fan, see Fan.

2.5.4 Junction Box


The junction box divides one AC input into four AC outputs. The AC outputs are used for the
SOU and multiple heating films or heaters.

Exterior
The junction box is on the left inner side of the APM30H. Figure 2-26 shows the junction box.

2-40

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Figure 2-26 Junction box

Structure
Figure 2-27 shows the structure of the junction box.
Figure 2-27 Structure of the junction box

(1) L wiring terminals for four AC (2) N wiring terminals for four AC (3) PE wiring terminals for four AC
outputs
outputs
outputs
(4) Cable holes

Issue 04 (2011-07-08)

(5) N wiring terminals for the AC


input

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

(6) L wiring terminal for the AC


input

2-41

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

2.5.5 ELU
The Electronic Label Unit (ELU) automatically reports the information about the cabinet type,
facilitating fast troubleshooting.
The ELU is on the left inner side of the IBBS200D or IBBS200T or on the right inner side of
the APM30H, TMC11H, or RFC. Figure 2-28 shows the ELU.
Figure 2-28 ELU

(1) Housing

(2) RJ-45 port

2.5.6 Door Status Sensor


The door status sensor monitors the opening and closing of the front door of the cabinet.
The door status sensor consists of the magnet part and switch part.
Figure 2-29 shows the magnet part of the door status sensor.

2-42

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Figure 2-29 Magnet part of the door status sensor

Figure 2-30 shows the switch part of the door status sensor.
Figure 2-30 Switch part of the door status sensor

2.5.7 Filler Panel


The filler panel is a 1 U-high plastic component, which is made of polycarbonate. It is installed
in the blank space below the baseband unit (BBU) to dissipate heat in the cabinet.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-43

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Function
When the BBU is configured in the cabinet, the filler panel must be installed to prevent hot air
recirculation in the blank space of the BBU subrack.
NOTE

When no optional module is configured in the cabinet, three to five filler panels are delivered with the
cabinet by default. If the 5 U space needs to be used, remove the five filler panels. For details about how
to remove a filler panel, see the BTS3900A (Ver.C) Installation Guide.

Exterior
Figure 2-31 shows a filler panel.
Figure 2-31 filler panel

2.5.8 AC Heater (Optional)


The AC heater is an optional component. It ensures that customer equipment in the APM30H
works in a proper temperature range when the ambient temperature is low.

Exterior
The AC heater is 1 U high. Figure 2-32 shows an AC heater.
Figure 2-32 AC heater

Specifications
The technical specifications of the AC heater are as follows:
l

2-44

When the temperature in the cabinet is lower than +1C (with 6C offset considered), the
AC heater starts working. When the temperature in the cabinet is higher than +15C (with
3C offset considered), the AC heater stops working.
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

The rated heating power of the AC heater is 300 W.

2.5.9 SOU (Optional)


The Service Outlet Unit (SOU) feeds AC power to the customer equipment. The SOU is optional.

Technical Specifications
Table 2-22 describes the technical specifications of the SOU.
Table 2-22 Technical specifications of the SOU
Item

Specification

Dimensions (W x D x H)

482.6 mm x 91 mm x 55 mm

Weight

1.5 kg

Input voltage range

200 V AC to 240 V AC

Maximum input current

10 A

Output voltage range

200 V AC to 240 V AC

Maximum output current

10 A

Operating frequency

50 Hz or 60 Hz

Operating temperature

-40oC to + 55oC

Altitude

4,000 m
NOTE
Above the altitude of 3,000 m, the maximum
operating temperature decreases by 1oC each time
the altitude increases by 100 m.

Protection class

IP20

Exterior
Figure 2-33 shows the SOU.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-45

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Figure 2-33 SOU

(1) Power supply socket

(2) Breaker

(3) Socket (Europe)

The SOU can be used for different types of sockets in different countries. The types of sockets
that are supported are: North America, European standard, multi-standard, and UK types. Figure
2-34 shows the different types of sockets.
Figure 2-34 Different types of sockets

2.6 APM30H Cables


This section describes the PGND cables, equipotential cables, power cables, and signal cables
in the APM30H.
2.6.1 Cables
This section describes the PGND cables, equipotential cables, power cables, and signal cables
in the APM30H.
2.6.2 PGND Cables
A protection ground (PGND) cable ensures proper grounding of a cabinet by connecting the
cabinet to an onsite ground bar.
2.6.3 Equipotential Cable
Equipotent cables connect PGND terminals in different cabinets, ensuring equipotential
connections of the cabinets and safe operation of the base station.
2.6.4 Power Cables
This section describes the APM30H power cables and their connections.
2.6.5 Signal Cables
2-46

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

This section describes the APM30H signal cables and their connections.

2.6.1 Cables
This section describes the PGND cables, equipotential cables, power cables, and signal cables
in the APM30H.

Power Cables, PGND Cables, and Equipotential Cable


Table 2-23 lists the power cables, PGND cables, and equipotential cable.
Table 2-23 Power cables, PGND cables, and equipotential cable
Catego
ry

Cable

Cables
to be
installe
d onsite

Cables
installe
d before
deliver
y

Issue 04 (2011-07-08)

One End

The Other End

Connector

Installation
Position

Connector

Installation
Position

External AC
Input Power
Cable

OT terminal

AC INPUT
port on the
EPU

Reserved

External
power
equipment

2.6.2 PGND
Cables

OT terminal

Ground bar of OT terminal


the APM30H

Ground
busbar outside
the cabinet

2.6.3
Equipotential
Cable

OT terminal

Ground bar of OT terminal


the APM30H

Ground bar of
the lower
cabinet

Power Cable
for the Fan
Box in the
APM30H

Easy power
receptacle
(pressfit type)
connector

LOAD5 port
on the EPU in
the APM30H

3V3 power
connector

PWR port on
the fan box in
the APM30H

Power Cable
for the AC
Heater
(APM30H)

OT terminal

L0 and N0
terminals on
the junction
box and
ground bar of
the cabinet in
the APM30H

C13
connector

Power socket
on the AC
heater

Power Cable
for the SOU

OT terminal

M4 ground
screw and L2
and N2
terminals of
the AC
OUTPUT
port on the
EPU

C13
connector

AC INPUT
port on the
SOU

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-47

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Catego
ry

Cable

One End

Input Power
Cable for the
Junction Box
(APM30H)

The Other End

Connector

Installation
Position

Connector

Installation
Position

OT terminal

M4 ground
screw and L1
and N1
terminals of
the AC
OUTPUT
port on the
EPU

OT terminal

L and N
terminals on
the junction
box and
ground bar of
the cabinet in
the APM30H

NOTE

The installation mode of power cables for optional components varies depending on delivery modes. Table
2-23 uses a macro base station as an example.

Signal Cables
Table 2-24 lists the signal cables.
Table 2-24 Signal cables

2-48

Categ
ory

Cable

Cables
to be
install
ed
onsite
Cables
install
ed
before
deliver
y

One End

The Other End

Connecto
r

Installation
Position

Connect
or

Installation
Position

Environme
nt
Monitoring
Signal
Cable

DB50
male
connector

COM port on the


PMU

DB50
male
connector

PMU_DB50 port
on the HPMI of the
fan box in the
APM30H

Monitoring
Signal
Transfer
Cable

RJ45
connector

COM_IN port on
the PMU

RJ45
connector

COM_OUT port on
the CMUE of the
fan box in the
APM30H

Signal
Cable for
the ELU

RJ45
connector

ELU

RJ45
connector

ELU port on the


CMUE

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

Categ
ory

Cable

2 APM30H Product Description

One End

The Other End

Connecto
r

Installation
Position

Connect
or

Installation
Position

APM30H
Door Status
Monitoring
Cable

2-pin
connector

GATE port on the


HPMI

Bare wire

Door status sensor

Monitoring
Signal
Cable for
the Fan on
the Front
Door

4-pin
connector

Transfer box on
the front door of
the APM30H

4-pin
connector

FAN_EXT port on
the CMUE

2.6.2 PGND Cables


A protection ground (PGND) cable ensures proper grounding of a cabinet by connecting the
cabinet to an onsite ground bar.

Exterior
Figure 2-35 shows the PGND cable.
Figure 2-35 PGND cable

(1) OT terminal

Description
Table 2-25 describes the PGND cables.
Table 2-25 PGND cables

Issue 04 (2011-07-08)

Cable

Color

Cross-Sectional Area

PGND cable for the


cabinet

Yellow and green

16mm2, M6

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-49

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

2.6.3 Equipotential Cable


Equipotent cables connect PGND terminals in different cabinets, ensuring equipotential
connections of the cabinets and safe operation of the base station.

Exterior
Figure 2-36 shows an equipotential cable.
Figure 2-36 Equipotential cable

Description
Table 2-26 describes the equipotential cable.
Table 2-26 Specifications of the equipotential cable
Name

Color

Cross-Sectional Area

Equipotential cable for


the cabinet

Yellow and green

Specifications of the cable vary


depending on the installation mode of
cabinets.
l For stacked cabinets: 16mm2, M6
l For cabinets installed side-by-side:
25mm2, M6

2.6.4 Power Cables


This section describes the APM30H power cables and their connections.

Power Cable Connections in the APM30H


This section describes power cable connections in the APM30H.

Power Cable Connections for a Distributed Base Station


Figure 2-37 shows power cable connections when the APM30H is used for a distributed base
station.

2-50

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Figure 2-37 Power cable connections for a distributed base station

(1) Input power cable for the


junction box

(2) Power cable for the fan box in the (3) Input power cable for storage
APM30H
batteries

(4) Power cable for the SOU

(5) Power cable for the AC heater

(6) Transfer cable for the fan on the


front door

NOTE

The transfer cable for the fan on the front door is delivered with the fan. For details, see Exterior.

Power Cable Connections for an Outdoor Macro Base Station


Figure 2-38 shows power cable connections when the APM30H is used for an outdoor macro
base station.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-51

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Figure 2-38 Power cable connections for an outdoor macro base station

(1) Input power cable for the junction (2) Power cable for the fan box in the
box
APM30H

(3) Power cable for RFC2

(4) Power cable for RFC1

(5) Input power cable for storage


batteries

(6) Power cable for the SOU

(7) Power cable for the AC heater

(8) Transfer cable for the fan on the front door

NOTE

The transfer cable for the fan on the front door is delivered with the fan. For details, see Exterior.

External AC Input Power Cable


The external AC input power cable is used to feed external AC power to the power supply system
in the APM30H. The APM30H can use different power systems to receive 220 V AC singlephase, 220 V AC three-phase, and 110/120 V dual-live-wire power.

Exterior
Figure 2-39 shows a 220 V AC single-phase input power cable.

2-52

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Figure 2-39 220 V AC single-phase input power cable

(1) OT terminal

NOTE

Different types of AC input power cables consist of different numbers of internal wires. Figure 2-39 shows
the structure of the 220 V AC single-phase input power cable.

Specifications
Table 2-27 lists the specifications of an AC input power cable.
Table 2-27 Specifications of an AC input power cable
Cable

Wire

Wire Color

Cross-Sectional Area
of the Wire and
Aperture of the OT
Terminal

220 V AC threephase power cable

L1 wire

Brown

4 mm2, M6

L2 wire

Black

L3 wire

Gray

N wire

Blue

L wire

Brown

N wire

Blue

PE wire

Yellow and green

L1 wire

Black

L2 wire

Red

N wire

White

PE wire

Green

220 V AC singlephase power cable

110/120 V AC
dual-live-wire
power

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

16 mm2, M6

16 mm2, M6

2-53

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description


NOTE

The colors and structures of cables delivered by Huawei vary depending on the country and area. If cables
are purchased at local markets, the cables must comply with the local rules and regulations.

Power Cable for the SOU


The power cable for the service outlet unit (SOU) is used to feed AC power to the SOU through
the AC OUTPUT port on the embedded power subrack unit (EPU).

Exterior
Figure 2-40 shows a power cable for the SOU.
Figure 2-40 Power cable for the SOU

(1) C13 connector

(2) M4 OT terminal for cables with a cross-sectional area of 1.5 mm2

Pin Assignment
Table 2-28 describes the pin assignment for the wires of the power cable for the SOU.
Table 2-28 Pin assignment for the wires of the power cable for the SOU
Pin

Wire Color

Connector

Label

W1

Brown

OT terminal

W2

Yellow and
green

OT terminal

PE

W3

Blue

OT terminal

Power Cable for the AC Heater


The power cable for the AC heater is used to feed AC power from the junction box to the AC
heater.
2-54

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Exterior
Figure 2-41 shows a power cable for the AC heater.
Figure 2-41 Power cable for the AC heater

(1) C13 connector

(2) M4 OT terminal for cables with a cross-sectional area of 1.5 mm2

Pin Assignment
Table 2-29 describes the pin assignment for the wires of the power cable for the AC heater.
Table 2-29 Pin assignment for the wires of the power cable for the AC heater
Pin

Wire Color

Connector

Label

W1

Brown

OT terminal

W2

Yellow and
green

OT terminal

PE

W3

Blue

OT terminal

Power Cable for the Fan Box in the APM30H


The power cable for the fan box is used to feed 48 V DC power to the fan box in the APM30H.

Exterior
Figure 2-42 shows a power cable for the fan box in the APM30H.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-55

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Figure 2-42 Power cable for the fan box in the APM30H

(1) 3V3 power connector

(2) Easy power receptacle (pressfit type) connector

Cable Specifications
Table 2-30 describes the specifications of the power cable for the fan box in the APM30H.
Table 2-30 Specifications of the power cable for the fan box in the APM30H
Cable

Wire

Wire Color in Most


Area

Wire Color in Other Area

Power cable for the


fan box in the
APM30H

RTN(+)

Black

Blue

NEG(-)

Blue

Gray

Input Power Cable for the Junction Box


The input power cable for the junction box is used to feed AC power from the AC power supply
system to the junction box. After the power distribution through the AC power distribution box,
four AC outputs are supplied to the heater or heating film.

Exterior
Figure 2-43 shows the input power cable for the junction box.
Figure 2-43 Input power cable for the junction box

(1) OT terminal (1.5 mm2, M4)

2-56

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Pin Assignment
Table 2-31 describes the pin assignment for the wires of the input power cable for the junction
box.
Table 2-31 Pin assignment for the wires of the input power cable for the junction box
Pin

Wire Color

One End

The Other End

Label

W1

Brown

X1

X3

W2

Blue

X2

X4

2.6.5 Signal Cables


This section describes the APM30H signal cables and their connections.

Signal Cable Connections in the APM30H


This section describes the signal cable connections in the APM30H.
Figure 2-44 shows the signal cable connections.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-57

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Figure 2-44 Signal cable connections in the APM30H

(1) Environment monitoring signal


cable

(2) Monitoring signal cable for the (3) Monitoring signal transfer cable
door status sensor in the APM30H

(4) Signal cable for the ELU

(5) Monitoring signal cable for the fan on the front door of the cabinet

Signal Cable for the ELU


The signal cable for the electronic labeling unit (ELU) is used to report the cabinet type
information collected by the ELU to the central monitoring unit type E (CMUE).

Exterior
Figure 2-45 shows the signal cable for the ELU.
Figure 2-45 Signal cable for the ELU

(1) RJ45 connector

2-58

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Pin Assignment
Table 2-32 describes the pin assignment for the wires of the signal cable for the ELU.
Table 2-32 Pin assignment for the wires of the signal cable for the ELU
X1 End

X2 End

Wire Color

Wire Type

X1.1

X2.1

White

Twisted pair

X1.2

X2.2

Orange

X1.3

X2.3

White

X1.6

X2.6

Green

X1.5

X2.5

White

X1.4

X2.4

Blue

X1.7

X2.7

White

X1.8

X2.8

Brown

Twisted pair

Twisted pair

Twisted pair

APM30H Door Status Monitoring Cable


The APM30H door status monitoring cable transmits the alarm signals to the PMU through the
HPMI.

Exterior
Figure 2-46 shows the APM30H door status monitoring cable.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-59

2 APM30H Product Description

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

Figure 2-46 APM30H door status monitoring cable

The APM30H door status monitoring cable is described as follows:


l

The cable labeled 1 has a straight 2-pin connector at one end, which is connected to the
HPMI. The other end of the cable is a bare wire and a cord end terminal, which are connected
to the door status sensor and wiring terminal block respectively.

The cable labeled 2 has a bare wire at one end, which is connected to the door status sensor.
The other end of the cable is a cord end terminal, which is connected to the wiring terminal
block.

The cable labeled 3 has two cord end terminals at both ends, which are connected to two
ports in the wiring terminal block at a side.

Monitoring Signal Cable for the Fan on the Front Door


The monitoring signal cable for the fan on the front door is used to supply power to the fan on
the front door of the APM30H or TMC11H and reports fan monitoring signals to the central
monitoring unit type E (CMUE).

Exterior
Figure 2-47 shows the monitoring signal cable for the fan on the front door.

2-60

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Figure 2-47 Monitoring signal cable for the fan on the front door

Pin Assignment
Table 2-33 describes the pin assignment for the wires of the monitoring signal cable for the fan
on the front door.
Table 2-33 Pin assignment for the wires of the monitoring signal cable for the fan on the front
door
Wire

X1 End

X2 End

Color

W1

X1.1

X2.1

Black

W2

X1.2

X2.2

Black

W3

X1.3

X2.3

Black

W4

X1.4

X2.4

Black

Environment Monitoring Signal Cable


The environment monitoring signal cable connects the PMU to the HPMI. It reports the alarm
signals collected by the HPMI to the PMU.

Exterior
The environment monitoring signal cable between the PMU and the HEUA is black. It is 0.5 m
long, with a DB50 connector at each end.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-61

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Figure 2-48 Environment monitoring signal cable

(1) DB50 male connector

Pin Assignment
Table 2-34 describes the pin assignment for the wires of the environment monitoring signal
cable.
Table 2-34 Pin assignment for the wires of the environment monitoring signal cable

2-62

X1 End

X2 End

Description

Wire

Twisted pair

10

10

11

11

12

12

13

13

14

14

16

16

17

17

18

18

19

19

20

20
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd.

Twisted pair

Twisted pair

Twisted pair

Twisted pair

Twisted pair

Twisted pair

Twisted pair
Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

X1 End

X2 End

21

21

22

22

23

23

24

24

25

25

27

27

28

28

29

29

30

30

31

31

32

32

33

33

34

34

43

43

44

44

Description

Twisted pair

Twisted pair

Twisted pair

Twisted pair

Twisted pair

Twisted pair

Twisted pair

Monitoring Signal Transfer Cable


The monitoring signal transfer cable connects the power monitoring unit (PMU) and central
monitoring unit type E (CMUE). The RS485 signals collected by the PMU are transmitted to
the baseband unit (BBU) through the monitoring signal transfer cable.

Exterior
A monitoring signal transfer cable is black and 0.6 m long, with an RJ45 connector at each end,
as shown in Figure 2-49.
Figure 2-49 Monitoring signal transfer cable

(1) RJ45 connector

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

2-63

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

2 APM30H Product Description

Pin Assignment
Table 2-35 describes the pin assignment for the wires of the monitoring signal transfer cable.
Table 2-35 Pin assignment for the wires of the monitoring signal transfer cable

2-64

X1 End

X2 End

Pin Assignment

X1.1

X2.1

Twisted pair

X1.2

X2.2

X1.3

X2.3

X1.6

X2.6

X1.4

X2.4

X1.5

X2.5

X1.7

X2.7

X1.8

X2.8

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Twisted pair

Twisted pair

Twisted pair

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

TMC11H Product Description

About This Chapter


This chapter describes the exterior, functions, specifications, usage scenarios, structure,
components, and cables of the TMC11H.
3.1 Introduction to the TMC11H
The TMC11H is used for Huawei radio communication products outdoors. It provides DC power
distribution for distributed and outdoor macro base stations.
3.2 Specifications of the TMC11H
The technical specifications of the TMC11H consist of electrical specifications, engineering
specifications, Surge Protection Specifications and environmental specifications.
3.3 Usage Scenarios of the TMC11H
The TMC11H can be used for a distributed or outdoor macro base station.
3.4 Structure of the TMC11H
The TMC11H has a modular design with high integrity. This improves the operability and
maintainability of the TMC11H.
3.5 TMC11H Components
TMC11H components include the fan box, direct current distribution unit (DCDU), outer air
circulation cooling component, junction box, electronic labeling unit (ELU), door status sensor,
filler panel, and AC heater (optional).
3.6 TMC11H Cables
This section describes the PGND cables, equipotential cables, power cables, and signal cables
in the TMC11H.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

3-1

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

3.1 Introduction to the TMC11H


The TMC11H is used for Huawei radio communication products outdoors. It provides DC power
distribution for distributed and outdoor macro base stations.

Exterior of the TMC11H


The TMC11H has the same exterior as the APM30H but different internal modules.
The dimensions (H x W x D) of a TMC11H without a base are 700 mm x 600 mm x 480 mm.
Figure 3-1 shows a TMC11H.
Figure 3-1 TMC11H

Functions of the TMC11H


Table 3-1 shows functions of the TMC11H.
Table 3-1 Functions of the TMC11H
Item

Function

48 V DC
power supply

The TMC11H is equipped with the DCDU-11B or DCDU-11C, which


provides the following functions:
l Supports one 48 V DC input.
l Provides 10 (LOAD0 to LOAD9) 48 V DC outputs.

3-2

Space for
customer
equipment

l The TMC11H provides an 11 U-high space for the customer equipment.

Alarm
reporting

The TMC11H provides dry contact alarm ports for remote monitoring. One
dry contact alarm port is connected to the door status sensor.

Automatic
reporting of the
cabinet type

The TMC11H automatically reports the cabinet type using the electronic
labeling unit (ELU).

l The 1 U space for customer equipment is used when a heater is installed


in the TMC11H.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

3.2 Specifications of the TMC11H


The technical specifications of the TMC11H consist of electrical specifications, engineering
specifications, Surge Protection Specifications and environmental specifications.

Electrical Specifications of the TMC11H


Table 3-2 describes the electrical specifications of the TMC11H.
Table 3-2 Electrical specifications of the TMC11H
Item
DC input
features

Specification
Input voltage
range

38.4 V DC to 57 V DC

Typical input
voltage

48 V DC

Maximum input
current

The maximum input current varies depending on the


usage scenario of the BTS3900A.
l For distributed base station: 160 A
l For outdoor macro base station: 30 A (current
provided by the APM30H to the TMC11H)

DC output
features

Input mode

48 V DC input, M6 one-hole OT terminal

DC power
distribution

Ten 48 V DC outputs (LOAD0 to LOAD9) to customer


equipment

Typical output
voltage

48 V DC

Protection features

Overcurrent and short circuit protection

Permissible heat consumption in


the cabinet

1050 W (heat dissipation capability when the ambient


temperature is below 50C)

Engineering Specifications of the TMC11H


Table 3-3 describes the engineering specifications of the TMC11H.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

3-3

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

Table 3-3 Engineering specifications of the TMC11H


Item

Specification

Remarks

Weight

47 kg

Total weight of the equipment


l Including the cabinet frame, outer
air circulation component (heat
exchanger core and outer air
circulation fan), inner air
circulation fan box, direct current
distribution unit (DCDU), and
cables
l Excluding customer equipment

Cabinet dimensions
(H x W x D)

700 mm x 600 mm x 480 mm

The exterior and base of the TMC11H


are similar to those of the APM30H.

Base dimensions (H
x W x D)

200 mm x 600 mm x 434 mm

Customer
equipment
dimensions (H x W
x D)

11 U x 19 in. x 380 mm

The depth consists of the rear (280


mm) and front (100 mm) of the
installation plane for subrack
mounting ears.

Space for cabling


and maintenance in
front of the cabinet

70 mm

Installation option

The TMC11H can be


installed on a floor, wall, or
pole. It can also be stacked
with the radio frequency
cabinet (RFC), IBBS200D,
or IBBS200T.

The TMC11H must be placed on the


RFC, IBBS200D, or IBBS200T in
stacking mode.

Surge Protection Specifications of the TMC11H


Table 3-4 describes the surge protection specifications of the TMC11H.
Table 3-4 Surge protection specifications of the TMC11H

3-4

Item

Specification

Surge protection for the DC


input port

l Differential mode (8/20 s): 3 kA


l Common mode (8/20 s): 5 kA

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

Item

Specification

Surge protection for the DC


output port

l Differential mode (8/20 s): 10 kA


l Common mode (8/20 s): 20 kA
Loads corresponding to the DC output port are minor loads.
NOTE
The surge protection level of the shield layer of an RRU power cable
is 40 kA.

Environmental Specifications of the TMC11H


The TMC11H can be used outdoors. Table 3-5 describes the environmental specifications of
the TMC11H.
Table 3-5 Environmental specifications of the TMC11H
Item

Specification

Remarks

Operating
temperatur
e

40C to +50C

A heater is required when the operating


temperature is below 20C. A sun shield is
required when the operating temperature is
above 50C.
NOTE
The operating temperature when a heater is
configured is obtained from the average lowest
temperature of all days in the coldest month of a
year.

Issue 04 (2011-07-08)

Relative
humidity

5% RH to 100% RH

Altitude

60 m to 4000 m

Above the altitude of 1800 m, the maximum


operating temperature decreases by 1C each
time the altitude increases by 220 m.

Wind
speed

67 m/s

Storage
temperatur
e

40C to +70C

Dustproof
and
waterproof
class

IP55

Noise level

61 dBA at 25C or 67
dBA at 45C when the total
power consumption is less
than or equal to 700 W

Meeting the ETS 300 753 4.1E standard (rural


areas)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

3-5

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

Item

Specification

Remarks

66 dBA at 25C or 76
dBA at 45C when the total
power consumption is greater
than 700 W and less than or
equal to 1050 W

Meeting the ETS 300 753 4.1E standard (urban


areas)

3.3 Usage Scenarios of the TMC11H


The TMC11H can be used for a distributed or outdoor macro base station.

Used for a Distributed Base Station


When the TMC11H is used for a distributed base station:
l

48 V DC power is supplied.

The TMC11H is connected to remote radio units (RRUs).

The TMC11H is equipped with one direct current distribution unit-11B (DCDU-11B)
which supplies power to the RRUs, baseband unit (BBU), fan, and transmission equipment
in the TMC11H.

Figure 3-2 shows a scenario where the TMC11H is used for a distributed base station.

3-6

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

Figure 3-2 Scenario where the TMC11H is used for a distributed base station

Used for an Outdoor Macro Base Station


When the TMC11H is used for an outdoor macro base station:
l

48 V DC power is supplied.

The TMC11H is stacked with the radio frequency cabinet (RFC).

48 V DC power is supplied to a DC transfer box in the RFC and then distributed to the
DCDUs in the RFC and TMC11H.

Figure 3-3 shows a scenario where the TMC11H is used for an outdoor macro base station.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

3-7

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

Figure 3-3 Scenario where the TMC11H is used for an outdoor macro base station

3.4 Structure of the TMC11H


The TMC11H has a modular design with high integrity. This improves the operability and
maintainability of the TMC11H.
Figure 3-4 shows the internal structure of the TMC11H.

3-8

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

Figure 3-4 Internal structure of the TMC11H

Issue 04 (2011-07-08)

S
N

Name

Op
tio
nal
or
Ma
nd
ato
ry

(1)

Fan box

Ma
nda
tory

(2)

DCDU-1
1B or
DCDU-1
1C

Ma
nda
tory

Ma
xi
mu
m
Qu
ant
ity
Co
nfi
gur
ed
in
a
Sin
gle
Ca
bin
et

Description

The fan box is configured with the fan, HPMI, and CMUE,
dissipating heat in the cabinet.

The DCDU-11B or DCDU-11C is a 1 U-high direct current


distribution unit, which supplies power to each component in
the TMC11H. The useage Scenarios of DCDU-11B is
different with DCDU-11C's.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

3-9

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

S
N

Name

Op
tio
nal
or
Ma
nd
ato
ry

Ma
xi
mu
m
Qu
ant
ity
Co
nfi
gur
ed
in
a
Sin
gle
Ca
bin
et

Description

(3)

Electroni
c labeling
unit
(ELU)

Ma
nda
tory

The ELU reports the cabinet type automatically to facilitate


fault identification.

(4)

Door
status
sensor

Ma
nda
tory

The door status sensor monitors the opening and closing of


the front door of the cabinet.

(5)

Filler
panel

Opt
ion
al

The filler panel is a 1 U-high plastic component, which is


made of polycarbonate. It is optional when a baseband unit
(BBU) is installed in the DC power cabinet.

(6)

AC
heater

Opt
ion
al

The AC heater is an optional component. It ensures that the


customer equipment in the cabinet works in a proper
temperature range when the ambient temperature is low. It is
installed in the 1 U space at the bottom of the cabinet.

(7)

Outer air
circulatio
n cooling
compone
nt

Ma
nda
tory

It is installed on the front door of the cabinet, dissipating heat


in the cabinet.

(8)

Junction
box

Ma
nda
tory

The junction box provides AC power distribution (four


outputs). It is used in scenarios where an SOU and multiple
heating films or heaters are configured.

In the TMC11H,

3-10

The 11 U space for customer equipment is available when no filler panel or AC heater is
installed in the TMC11H.

An AC heater is preferentially installed in the 1 U space at the bottom of the TMC11H.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

3.5 TMC11H Components


TMC11H components include the fan box, direct current distribution unit (DCDU), outer air
circulation cooling component, junction box, electronic labeling unit (ELU), door status sensor,
filler panel, and AC heater (optional).
3.5.1 Fan Box
The fan box consists of the fan subrack, fan, HERT power monitoring interface unit (HPMI),
and central monitoring unit type E (CMUE).
3.5.2 DCDU-11B and DCDU-11C
The DCDU-11B and DCDU-11C are 1 U-high direct current distribution units, which supply
power to each component in the cabinet. They have the same exterior, engineering specifications,
and ports but different circuit breaker specifications and usage scenarios.
3.5.3 Outer Air Circulation Cooling Component
The outer air circulation cooling component consists of the heat exchanger core and fan. The
heat exchanger core can speed up inner and outer air circulation to reduce the operating
temperature of the cabinet. It can also prevent dust from entering the cabinet. The fan dissipates
heat in the cabinet.
3.5.4 Filler Panel
The filler panel is a 1 U-high plastic component, which is made of polycarbonate. It is installed
in the blank space below the baseband unit (BBU) to dissipate heat in the cabinet.
3.5.5 Junction Box
The junction box divides one AC input into four AC outputs. The AC outputs are used for the
SOU and multiple heating films or heaters.
3.5.6 ELU
The Electronic Label Unit (ELU) automatically reports the information about the cabinet type,
facilitating fast troubleshooting.
3.5.7 Door Status Sensor
The door status sensor monitors the opening and closing of the front door of the cabinet.
3.5.8 AC Heater (Optional)
The AC heater is an optional component. It ensures that customer equipment in the APM30H
works in a proper temperature range when the ambient temperature is low.

3.5.1 Fan Box


The fan box consists of the fan subrack, fan, HERT power monitoring interface unit (HPMI),
and central monitoring unit type E (CMUE).
Figure 3-5 shows a fan box.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

3-11

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

Figure 3-5 Fan box

(1) Fan subrack

(2) Fan

(3) CMUE

(4) HPMI

Fan
Fan is installed in the fan box of a cabinet, dissipating the heat in the cabinet. Signal cable is
delivered with fan.

Exterior
Figure 3-6 shows a fan.
Figure 3-6 Fan

Figure 3-7 shows the signal cable delivered with a fan.


Figure 3-7 Signal cable delivered with a fan

NOTE

The signal cable delivered with a fan feeds power into the fan and monitors the fan.

3-12

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

Pin Assignment
Table 3-6 describes the pin assignment for the wires of the signal cable delivered with a fan.
Table 3-6 Pin assignment
Wire

X1
End

Color

Description

W1

A.1

Red

Connects to the positive pole.

W2

A.2

Yello
w

Receives pulse-width modulation (PWM) speed-adjusting


signals.

W3

A.3

Blue

Receives alarm or speed signals.

W4

A.4

Black

Connects to the negative pole.

NOTE

The color of the signal cable delivered with a fan varies depending on manufacturers.

Specifications
Table 3-7 lists the technical specifications of a fan.
Table 3-7 Technical specifications of the fan

Issue 04 (2011-07-08)

Item

Specification

Dimensions (diameter x
height)

175 mm x 69 mm

Length of the lead

600 mm

Rated voltage

48 V

Operating voltage range

36 V DC to 60 V DC

Rated current

1.3 A

Maximum current

2.1 A

Rated power

62 W

Maximum power

100 W

Rated traffic volume

697 m3/h

Rated speed

4000 r/min

Speed-adjusting mode

PWM mode

Operating temperature

25C to +70C

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

3-13

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

HPMI
The HERT power monitoring interface unit (HPMI) provides input and output ports for alarm
signals.

Exterior
Figure 3-8 shows an HPMI.
Figure 3-8 HPMI

Ports
Figure 3-9 shows the ports on the panel of the HPMI. Table 3-8 lists the specifications of the
ports on the panel of the HPMI.
Figure 3-9 Ports on the panel of the HPMI

Table 3-8 Specifications of the ports on the panel of the HPMI


Silkscreen

3-14

Port Function

Port Relationship with the Related


Cabinet(1) (2)
APM30H

TMC11H

PMU_DB50

Connects to the PMU


and reports alarms
collected by the
HPMI to the BBU.

OUT0 and OUT1

Provides one
Boolean output at
each port.

Reserved

Reserved

IN0, IN1, and IN2

Provides one
Boolean input at each
port.

Reserved

Reserved

FUSE

Reserved for fuse


detection

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

Silkscreen

Port Function

3 TMC11H Product Description

Port Relationship with the Related


Cabinet(1) (2)
APM30H

TMC11H

GATE

Connects to the door


status sensor and
receives door status
alarms.

Mandatory

Reserved

IN3, IN4

Provides one
Boolean input at each
port.

Reserved

Reserved

TEM_BAT1

Connects to the
temperature sensor
for storage batteries
in IBBS2.1 and
IBBS2.2 and
receives battery
temperature alarms.

Optional

Reserved

SMOKE

Connects to the
smoke sensor and
receives smoke
alarms.

Reserved

Reserved

WATER

Connects to the water


sensor and receives
water damage
alarms.

Reserved

Reserved

TEM_HUM

Connects to the
temperature and
humidity sensor and
receives temperature
and humidity alarms.

Reserved

Reserved

NOTE

(1) Mandatory monitoring devices and related monitoring signal cables are installed in a cabinet before the
cabinet is delivered. Optional devices are configured based on customer requirements, and related cables
must be installed onsite. For details about how to connect the cables, see the , , BTS3900A (Ver.C)
Installation Guide, , and .
(2) For details about the positions of devices monitored by the HPMI, see Structure of the BTS3900A
Cabinets.

CMUE
The central monitoring unit type E (CMUE) monitors the temperature of the fan box, heater,
and cabinet. The CMUE can be used for cabinets such as the AMP30H, RFC, TMC11H,
IBBS200D, and IBBS200T.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

3-15

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

Function
Table 3-9 describes the functions of the CMUE.
Table 3-9 Functions of the CMUE
Function

Description

Pulse-width
modulation
(PWM) speed
adjusting

Fan speeds can be adjusted based on temperature or controlled by the


baseband unit (BBU).

Fan speed query

Fan speeds can be queried by running a query command.

Full speed rotation


when a fan is faulty

When a fan in the fan subrack is faulty, other fans rotate at a full speed.

Full speed rotation


when the CPU is
faulty

Alarm reporting
when the fan box is
faulty

The alarms are as follows:


l Communication failure alarm
l Fan fault alarm
l Abnormal temperature alarm
l Smoke, water damage, or door status alarm
l Hardware fault alarm (related to the I2C fault)
The alarms are reported through an RS485 bus.

3-16

Thermoelectric
cooling unit (TEC)
control and
detection

The CMUE controls the starting and stopping of the TEC and detects
its current and voltage.

Environment
monitoring

The CMUE detects the board temperature and air inlet temperature and
monitors the environment such as smoke, water damage, and door
status.

Boolean value
detection

The CMUE provides four Boolean inputs such as AC/DC surge


protector and door status sensor alarms.

Protection against
reverse connection

The CMUE provides protection against reverse connection.

Status indication

The CMUE provides one red indicator and one green indicator to
indicate the operating status of the board.

RS485 port
cascading and
extension

When a cabinet uses two fan subracks or cabinets are combined, the fan
box automatically identifies communication addresses.

Online loading

The CMUE supports online loading through an RS485 bus.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

Function

Description

Surge protection

l The power socket provides surge protection of 1 kV in differential


mode and 2 kV in common mode.
l An RS485 bus supports surge protection of 250 A.
l IN0 and GATE Boolean inputs support surge protection of 250 A.
l IN1 and IN2 Boolean inputs support surge protection of 3 kA in
differential mode and 5 kA in common mode.

Electronic labeling

The CMUE supports electronic labeling for boards and external


cabinets.

Protection against
short-circuiting of
smoke, water, and
temperature
sensors

When short-circuiting occurs on a port, the CMUE provides currentlimiting protection based on positive temperature coefficient (PTC)
thermal resistance or other resistance.

Exterior
Figure 3-10 shows a CMUE.
Figure 3-10 CMUE

Ports
Figure 3-11 shows ports and indicators on a CMUE.
Figure 3-11 Ports and indicators on a CMUE

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

3-17

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

Table 3-10 describes functions of the ports and indicators on a CMUE.


Table 3-10 Functions of the ports and indicators on a CMUE
S
N

Port or
Indicator

Description

(1)

TEMP2

Connects to a temperature sensor. The port is reserved.

(2)

WATER

Connects to a water sensor.

(3)

IFAN4

Connects to an inner air circulation fan.

(4)

IFAN3

Connects to an inner air circulation fan.

(5)

IFAN2

Connects to an inner air circulation fan.

(6)

IFAN1

Connects to an inner air circulation fan.

(7)

TEC

Connects to the TEC and receives alarms related to the TEC.

(8)

TEMP1

l Connects to the temperature sensor at the air inlet of an RFC and


receives temperature alarms.
l Connects to the battery temperature sensor in the IBBS200D or
IBBS200T and receives battery temperature alarms.

(9)

COM_OUT

This port is an RS485 signal port that connects to a lower-level port and
reports monitoring information.
l Connects to the power monitoring unit (PMU) in the APM30H.
l Connects to a lower-level CMUE in the RFC, TMC11H, IBBS200D,
or IBBS200T.

(10
)

COM_IN

This port is an RS485 signal port that connects to an upper-level port


and receives monitoring information.
l Connects to the baseband unit (BBU) in the APM30H.
l Connects to the BBU or an upper-level CMUE in the RFC or
TMC11H.
l Connects to the PMU or an upper-level CMUE in the IBBS200D or
IBBS200T.

3-18

(11
)

RUN
indicator

Indicates the operating status of fans.

(12
)

ALM
indicator

Indicates the alarm status of fans.

(13
)

ELU

Connects to the electronic labeling unit (ELU) and reports the cabinet
type.

(14
)

GATE

Connects to the door status sensor. This port is a Boolean signal port.

(15
)

IN0, IN1,
IN2

This port is a reserved Boolean signal port.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

S
N

Port or
Indicator

Description

(16
)

SMOKE

Connects to the smoke sensor. This port is a Boolean signal port.

(17
)

EFAN1

Connects to an outer air circulation fan.

(18
)

EFAN2

Connects to an outer air circulation fan.

(19
)

PWR

Feeds DC power to boards. This is a power socket.

Indicators
Table 3-11 describes the indicators on a CMUE.
Table 3-11 Indicators on a CMUE
Label

Color

State

Description

RUN

Green

Blinking (on for 1s and


off for 1s)

The board is functional and communicates


with its upper-level device properly.

Blinking (on for 0.125s


and off for 0.125s)

The board is functional, but the


communication with its upper-level device
fails or the board is not registered.

Steady on

The board is in the power-on self-test state.

Off

The board is faulty.

Off

No alarm is reported.

Steady on

An alarm is generated, and the board needs to


be replaced.

Blinking (on for 1s and


off for 1s)

An alarm is generated, and the alarm may be


caused by an associated board or port fault.
Therefore, you must identify the fault before
replacing the board.

ALM

Red

DIP Switch
The CMUE has one dual in-line package (DIP) switch J18, which is used to set the working
mode of the CMUE based on the cabinet type. Figure 3-12 shows the position of the DIP switch
on the CMUE.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

3-19

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

Figure 3-12 Position of the DIP switch on the CMUE.

Figure 3-13 shows DIP switch settings of the CMUE in different cabinets.
Figure 3-13 DIP switch settings of the CMUE in different cabinets

NOTE

The red rectangles in Figure 3-13 indicate the positions for inserting jumper pins.

Specification
Table 3-12 describes the specifications of the CMUE.
Table 3-12 Specifications of the CMUE
Item

Specification

Description

Power
consumption

The following specifications are


described:

l The maximum power


consumption of the board circuit
is 3 W.
l The CMUE supports a
maximum of four fans and its
maximum power consumption
is 400 W.
l When the CMUE is connected
to a TEC, the maximum power
consumption is 750 W.
3-20

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

Item

Specification

Description

Input voltage
range

36 V DC to +60 V DC

Temperature
detection range

45C to 70C

The DS1820 digital temperature


sensor is used for temperature
detection.

Temperature
detection error

2C

Fan speed
adjustment

Four PWM signal outputs

A maximum of four fans are


supported. Each fan uses a separate
PWM signal output to control fan
speed and status detection in real
time.

Alarm reporting

Alarms reported to the main control


unit through an RS485 serial port.

The board supports one alarm


output through a bus.

Communication
port

Standard RS485 serial port

Operating
temperature
range

40C to 60C

Operating
altitude

4000 m

3.5.2 DCDU-11B and DCDU-11C


The DCDU-11B and DCDU-11C are 1 U-high direct current distribution units, which supply
power to each component in the cabinet. They have the same exterior, engineering specifications,
and ports but different circuit breaker specifications and usage scenarios.

Exterior
Figure 3-14 and Figure 3-15 show the front and rear views of a DCDU-11B/DCDU-11C
respectively.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

3-21

3 TMC11H Product Description

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

Figure 3-14 Front view of the DCDU-11B/DCDU-11C

Figure 3-15 Rear view of the DCDU-11B/DCDU-11C

NOTE

The DCDU-11C does not use the equipotential connection point and ground point. The DCDU-11B uses
the equipotential connection point or ground point only in one of the following scenarios:
l Scenario 1: The DCDU-11B is placed in an open rack and is connected to the ground bar of the open
rack by using the equipotential connection point near the mounting ears.
l Scenario 2: The DCDU-11B is mounted on a wall to serve as an independent power distribution device,
which is connected to the ground bar in the equipment room by using the ground point at the rear of
the DCDU-11B.

Function
The DCDU-11B/DCDU-11C provides ten 48 V DC outputs. Different circuit breaker
configurations can meet power distribution requirements for a distributed or outdoor macro base
station.
Table 3-13 lists the DC power distribution functions of the DCDU-11B/DCDU-11C.

3-22

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

Table 3-13 DC power distribution functions of the DCDU-11B/DCDU-11C


DCDU
Type

DC
Output
Termina
l

Equipment

Circuit
Breaker
Specifica
tions

Circuit
Breaker

Description

DCDU-11
B

LOAD0
to
LOAD5

RRU0 to RRU5

25 A

SW0 to
SW5

Distributed or
mini base station

LOAD6

BBU or transmission
equipment

25 A

SW6

LOAD7

BBU or transmission
equipment

25 A

SW7

LOAD8

EMUA or
transmission
equipment

25 A

SW8

LOAD9

Fan box

25 A

SW9

LOAD0

Transmission
equipment

6A

SW0

LOAD1

Transmission
equipment

6A

SW1

LOAD2

Transmission
equipment

12 A

SW2

LOAD3

Transmission
equipment

12 A

SW3

LOAD4

Transmission
equipment

25 A

SW4

LOAD5

Transmission
equipment

25 A

SW5

LOAD6

BBU or transmission
equipment

25 A

SW6

LOAD7

BBU or transmission
equipment

25 A

SW7

LOAD8

EMUA or
transmission
equipment

25 A

SW8

LOAD9

Fan box

25 A

SW9

DCDU-11
C

48 V outdoor
macro base
station or
transmission
cabinet

Ports
Figure 3-16 shows the ports on the panel of the DCDU-11B/DCDU-11C.
Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

3-23

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

Figure 3-16 Ports on the panel of the DCDU-11B/DCDU-11C

Table 3-14 describes specifications of the ports on the panel of the DCDU-11B/DCDU-11C.
Table 3-14 Specifications of the ports on the panel of the DCDU-11B/DCDU-11C
S
N

Port

Label

Terminal and
Cable

Description

(1)

DC input
terminal

NEG(-)

M6 one-hole OT
terminal (two wires)
and a maximum
cross-sectional area
of 25 mm2.

Negative power input wiring


terminal

RTN(+)

3-24

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Positive power input wiring


terminal

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

S
N

Port

Label

Terminal and
Cable

Description

(2)

DC
output
terminal

LOAD0 to
LOAD9

DCDU-11B:

For details about DC output


specifications, see Table 3-13.

l Figure 3-17
shows an easy
power receptacle
(pressfit type)
connector
adapting to
LOAD0 to
LOAD5
terminals. The
maximum crosssectional area is
10 mm2.
l Figure 3-18
shows an easy
power receptacle
(pressfit type)
connector
adapting to
LOAD6 to
LOAD9
terminals. The
maximum crosssectional area is 4
mm2.
DCDU-11C: Figure
3-18 shows an easy
power receptacle
(pressfit type)
connector adapting to
LOAD0 to LOAD9
terminals. The
maximum crosssectional area is 4
mm2.

(3)

Issue 04 (2011-07-08)

Circuit
breaker

SW0 to SW9

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

The circuit breakers SW0 to


SW9 control the ports LOAD0
to LOAD9 respectively,
controlling the power supplies
to the BBU, fan box, DC heater,
and transmission equipment.

3-25

3 TMC11H Product Description

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

Figure 3-17 Easy power receptacle (pressfit type) connector (1)

Figure 3-18 Easy power receptacle (pressfit type) connector (2)

3.5.3 Outer Air Circulation Cooling Component


The outer air circulation cooling component consists of the heat exchanger core and fan. The
heat exchanger core can speed up inner and outer air circulation to reduce the operating
temperature of the cabinet. It can also prevent dust from entering the cabinet. The fan dissipates
heat in the cabinet.

Exterior
The outer air circulation cooling component is located on the inner side of the front door of the
APM30H. Figure 3-19 shows an outer air circulation cooling component.

3-26

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

Figure 3-19 Outer air circulation cooling component

(1) Heat exchanger core

(2) Fan

Heat Exchanger Core


Table 3-15 describes specifications of the heat exchanger core.
Table 3-15 Specifications of the heat exchanger core
Item

Specification

Dimensions (H x W x D)

415 mm x 390 mm x 89.5 mm

Heat dissipation capability

58.3 W/K

Fan
For details about specifications of the fan, see Fan.

3.5.4 Filler Panel


The filler panel is a 1 U-high plastic component, which is made of polycarbonate. It is installed
in the blank space below the baseband unit (BBU) to dissipate heat in the cabinet.

Function
When the BBU is configured in the cabinet, the filler panel must be installed to prevent hot air
recirculation in the blank space of the BBU subrack.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

3-27

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description


NOTE

When no optional module is configured in the cabinet, three to five filler panels are delivered with the
cabinet by default. If the 5 U space needs to be used, remove the five filler panels. For details about how
to remove a filler panel, see the BTS3900A (Ver.C) Installation Guide.

Exterior
Figure 3-20 shows a filler panel.
Figure 3-20 filler panel

3.5.5 Junction Box


The junction box divides one AC input into four AC outputs. The AC outputs are used for the
SOU and multiple heating films or heaters.

Exterior
The junction box is on the left inner side of the APM30H. Figure 3-21 shows the junction box.
Figure 3-21 Junction box

Structure
Figure 3-22 shows the structure of the junction box.
3-28

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

Figure 3-22 Structure of the junction box

(1) L wiring terminals for four AC (2) N wiring terminals for four AC (3) PE wiring terminals for four AC
outputs
outputs
outputs
(4) Cable holes

(5) N wiring terminals for the AC


input

(6) L wiring terminal for the AC


input

3.5.6 ELU
The Electronic Label Unit (ELU) automatically reports the information about the cabinet type,
facilitating fast troubleshooting.
The ELU is on the left inner side of the IBBS200D or IBBS200T or on the right inner side of
the APM30H, TMC11H, or RFC. Figure 3-23 shows the ELU.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

3-29

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

Figure 3-23 ELU

(1) Housing

(2) RJ-45 port

3.5.7 Door Status Sensor


The door status sensor monitors the opening and closing of the front door of the cabinet.
The door status sensor consists of the magnet part and switch part.
Figure 3-24 shows the magnet part of the door status sensor.
Figure 3-24 Magnet part of the door status sensor

3-30

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

Figure 3-25 shows the switch part of the door status sensor.
Figure 3-25 Switch part of the door status sensor

3.5.8 AC Heater (Optional)


The AC heater is an optional component. It ensures that customer equipment in the APM30H
works in a proper temperature range when the ambient temperature is low.

Exterior
The AC heater is 1 U high. Figure 3-26 shows an AC heater.
Figure 3-26 AC heater

Specifications
The technical specifications of the AC heater are as follows:
l

When the temperature in the cabinet is lower than +1C (with 6C offset considered), the
AC heater starts working. When the temperature in the cabinet is higher than +15C (with
3C offset considered), the AC heater stops working.

The rated heating power of the AC heater is 300 W.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

3-31

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

3.6 TMC11H Cables


This section describes the PGND cables, equipotential cables, power cables, and signal cables
in the TMC11H.
3.6.1 Cables
TMC11H cables include equipotential cables, power cables, and signal cables.
3.6.2 Equipotential Cable
Equipotent cables connect PGND terminals in different cabinets, ensuring equipotential
connections of the cabinets and safe operation of the base station.
3.6.3 Power Cables
This section describes the TMC11H power cables and their connections.
3.6.4 Signal Cables
This section describes the TMC11H signal cables and their connections.

3.6.1 Cables
TMC11H cables include equipotential cables, power cables, and signal cables.

Power Cables and Equipotential Cables


Table 3-16 describes the power cables and equipotential cables.
Table 3-16 Power cables and equipotential cables

3-32

Categ
ory

Cable

Cables
to be
install
ed
onsite

One End

The Other End

Connector

Installation
Position

Input Power
Cable for the
TMC11H (AC
cabinet)

Easy power
receptacle
(pressfit type)
connector

TMC terminal OT terminal


on the EPU

RTN(+) and
NEG(-)
terminals of
the INPUT
port on the
DCDU-11C

Input Power
Cable for the
Junction Box
(TMC11H)

OT terminal

L3 and N3
terminals on
the junction
box in the
APM30H

OT terminal

L and N
terminals on
the junction
box in the
TMC11H

Input Power
Cable for the
Junction Box
(48 V DC
cabinet)

C13
connector

Power socket
on the AC
heater

Reserved

External
power
equipment

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Connector

Installation
Position

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

Categ
ory

Cables
install
ed
before
deliver
y

Cable

3 TMC11H Product Description

One End

The Other End

Connector

Installation
Position

Connector

Installation
Position

3.6.2
Equipotential
Cable

OT terminal

Ground bar of
the upper
cabinet

OT terminal

Ground bar of
the lower
cabinet

Power Cable
for the Fan
Box in the
TMC11H

Easy power
receptacle
(pressfit type)
connector

LOAD9
terminal on
the
DCDU-11C

3V3 power
connector

PWR port on
the fan box in
the TMC11H

Power Cable
for the AC
Heater

OT terminal

L0 and N0
terminals on
the junction
box and
ground bar of
the cabinet in
the TMC11H

C13
connector

Power socket
on the AC
heater

Input Power
Cable for the
TMC11H (48
V DC cabinet)

OT terminal

DC transfer
box in the
RFC

OT terminal

RTN(+) and
NEG(-)
terminals of
the INPUT
port on the
DCDU-11C

NOTE

The installation mode of power cables for optional components varies depending on delivery modes. Table
3-16 uses a macro base station as an example.

Signal Cables
Table 3-17 describes the signal cables.
Table 3-17 Signal cables

Issue 04 (2011-07-08)

Categ
ory

Cable

Cables
to be
install
ed
onsite

One End

The Other End

Connecto
r

Installation
Position

Connect
or

Installation
Position

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

3-33

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

Categ
ory

Cable

Cables
install
ed
before
deliver
y

One End

The Other End

Connecto
r

Installation
Position

Connect
or

Installation
Position

Signal
Cable for
the ELU

RJ45
connector

ELU

RJ45
connector

ELU port on the


CMUE

Monitoring
Signal
Cable for
the Door
Status
Sensor

2-pin
connector

GATE port on the


CMUE

Bare wire

Door status sensor

Monitoring
Signal
Cable for
the Fan on
the Front
Door

4-pin
connector

Transfer box on
the front door of
the APM30H

4-pin
connector

FAN_EXT port on
the CMUE

3.6.2 Equipotential Cable


Equipotent cables connect PGND terminals in different cabinets, ensuring equipotential
connections of the cabinets and safe operation of the base station.

Exterior
Figure 3-27 shows an equipotential cable.
Figure 3-27 Equipotential cable

Description
Table 3-18 describes the equipotential cable.

3-34

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

Table 3-18 Specifications of the equipotential cable


Name

Color

Cross-Sectional Area

Equipotential cable for


the cabinet

Yellow and green

Specifications of the cable vary


depending on the installation mode of
cabinets.
l For stacked cabinets: 16mm2, M6
l For cabinets installed side-by-side:
25mm2, M6

3.6.3 Power Cables


This section describes the TMC11H power cables and their connections.

Power Cable Connections in the TMC11H


This section describes power cable connections in the TMC11H.
Figure 3-28 shows the power cable connections in the TMC11H.
Figure 3-28 Power cable connections in the TMC11H

(1) Power cable for the fan box in the TMC11H

(2) Power cable for the AC heater

(3) Input power cable for the TMC11H

(4) Transfer cable for the fan on the front door

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

3-35

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description


NOTE

The transfer cable for the fan on the front door is delivered with the fan. For details, see Exterior.

Input Power Cable for the TMC11H


The input power cable for the TMC11H varies depending on power inputs.

Input Power Cable for the TMC11H (1)


In an AC input scenario, the TMC11H obtains power from the APM30H. Figure 3-29 shows
the input power cable for the TMC11H in this scenario.
Figure 3-29 Input power cable for the TMC11H (1)

(1) Easy power receptacle (pressfit type) connector

(2) OT terminal

Table 3-19 describes the specifications of the input power cable for the TMC11H (1).
Table 3-19 Specifications of the input power cable for the TMC11H (1)
Cable

Wire

Wire Color for


Most Area

Wire Color for


Other Area

Cross-Sectional
Area of the Wire
and Aperture of
the OT Terminal

Input power
cable for the
TMC11H (1)

RTN
(+)

Black

Blue

4 mm2, M6

NEG
(-)

Blue

Gray

Input Power Cable for the TMC11H (2)


In a 48 V DC input scenario, the TMC11H obtains power from the DC transfer box in the radio
frequency cabinet (RFC). Figure 3-30 shows the input power cable for the TMC11H in this
scenario.

3-36

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

Figure 3-30 Input power cable for the TMC11H (2)

(1) OT terminal

Table 3-20 describes the specifications of the input power cable for the TMC11H (2).
Table 3-20 Specifications of the input power cable for the TMC11H (2)
Cable

Wire

Color for Most


Area

Color for Other


Area

Cross-Sectional
Area of the Wire
and Aperture of
the OT Terminal

Input power
cable for the
TMC11H (2)

RTN
(+)

Black

Blue

25 mm2, M6

NEG
(-)

Blue

Gray

Power Cable for the Fan Box in the TMC11H


The power cable for the fan box in the TMC11H is used to supply 48 V DC power from the
DCDU-11C to the fan box in the TMC11H.

Exterior
Figure 3-31 shows a power cable for the fan box in the TMC11H.
Figure 3-31 Power cable for the fan box in the TMC11H

(1) 3V3 power connector

Issue 04 (2011-07-08)

(2) Easy power receptacle (pressfit type) connector

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

3-37

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

Cable Specifications
Table 3-21 describes the specifications of the power cable for the fan box in the TMC11H.
Table 3-21 Specifications of the power cable for the fan box in the TMC11H
Cable

Wire

Wire Color in Most


Area

Wire Color in Other Area

Power cable for


the fan box in the
TMC11H

RTN(+)

Black

Blue

NEG(-)

Blue

Gray

Power Cable for the AC Heater


The power cable for the AC heater is used to feed AC power from the junction box to the AC
heater.

Exterior
Figure 3-32 shows a power cable for the AC heater.
Figure 3-32 Power cable for the AC heater

(1) C13 connector

(2) M4 OT terminal for cables with a cross-sectional area of 1.5 mm2

Pin Assignment
Table 3-22 describes the pin assignment for the wires of the power cable for the AC heater.
Table 3-22 Pin assignment for the wires of the power cable for the AC heater

3-38

Pin

Wire Color

Connector

Label

W1

Brown

OT terminal

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

Pin

Wire Color

Connector

Label

W2

Yellow and
green

OT terminal

PE

W3

Blue

OT terminal

3.6.4 Signal Cables


This section describes the TMC11H signal cables and their connections.

Signal Cable Connections in the TMC11H


This section describes the signal cable connections in the TMC11H.
Figure 3-33 shows the signal cable connections in the TMC11H.
Figure 3-33 Signal cable connections in the TMC11H

(1) Monitoring signal cable for the fan (2) Signal cable for the ELU (3) Monitoring signal cable for the door
on the front door of the cabinet
status sensor

Signal Cable for the ELU


The signal cable for the electronic labeling unit (ELU) is used to report the cabinet type
information collected by the ELU to the central monitoring unit type E (CMUE).

Exterior
Figure 3-34 shows the signal cable for the ELU.
Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

3-39

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

Figure 3-34 Signal cable for the ELU

(1) RJ45 connector

Pin Assignment
Table 3-23 describes the pin assignment for the wires of the signal cable for the ELU.
Table 3-23 Pin assignment for the wires of the signal cable for the ELU
X1 End

X2 End

Wire Color

Wire Type

X1.1

X2.1

White

Twisted pair

X1.2

X2.2

Orange

X1.3

X2.3

White

X1.6

X2.6

Green

X1.5

X2.5

White

X1.4

X2.4

Blue

X1.7

X2.7

White

X1.8

X2.8

Brown

Twisted pair

Twisted pair

Twisted pair

Monitoring Signal Cable for the Door Status Sensor


The monitoring signal cable for the door status sensor is used to inform the central monitoring
unit type E (CMUE) of the door status that is obtained from the door status sensor in the
TMC11H, radio frequency cabinet (RFC), IBBS200D, or IBBS200T.

Exterior
The monitoring signal cable for the door status sensor has two black bare wires, as shown in
Figure 3-35.
Figure 3-35 Monitoring signal cable for the door status sensor

3-40

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

3 TMC11H Product Description

Monitoring Signal Cable for the Fan on the Front Door


The monitoring signal cable for the fan on the front door is used to supply power to the fan on
the front door of the APM30H or TMC11H and reports fan monitoring signals to the central
monitoring unit type E (CMUE).

Exterior
Figure 3-36 shows the monitoring signal cable for the fan on the front door.
Figure 3-36 Monitoring signal cable for the fan on the front door

Pin Assignment
Table 3-24 describes the pin assignment for the wires of the monitoring signal cable for the fan
on the front door.
Table 3-24 Pin assignment for the wires of the monitoring signal cable for the fan on the front
door

Issue 04 (2011-07-08)

Wire

X1 End

X2 End

Color

W1

X1.1

X2.1

Black

W2

X1.2

X2.2

Black

W3

X1.3

X2.3

Black

W4

X1.4

X2.4

Black

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

3-41

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

4 IBBS200D Product Description

IBBS200D Product Description

About This Chapter


This chapter describes the exterior, functions, specifications, structure, components, and cables
of the IBBS200D.
4.1 Introduction to the IBBS200D
The IBBS200D uses fans for heat dissipation and provides power backup for the APM30H.
4.2 Specifications of the IBBS200D
The specifications of the IBBS200D consist of electrical specifications, engineering
specifications, and environmental specifications.
4.3 Structure of the IBBS200D
The IBBS200D has a modular design with high integrity. The power distribution equipment is
installed on the right of the cabinet, and the monitoring equipment is installed on the cabinet
door.
4.4 IBBS200D Components
IBBS200D components include the fan installation module, central monitoring unit type E
(CMUE), power distribution box (PDB), storage batteries, electronic labeling unit (ELU), door
status sensor, temperature sensor for storage batteries, and heating film.
4.5 IBBS200D Cables
This section describes the PGND cables, equipotential cables, power cables, and signal cables
in the IBBS200D.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

4-1

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

4 IBBS200D Product Description

4.1 Introduction to the IBBS200D


The IBBS200D uses fans for heat dissipation and provides power backup for the APM30H.

Exterior of the IBBS200D


The dimensions (H x W x D) of an IBBS200D without a base are 700 mm x 600 mm x 480 mm.
Figure 4-1 shows an IBBS200D.
Figure 4-1 IBBS200D

Functions of the IBBS200D


Table 4-1 describes functions of the IBBS200D.
Table 4-1 Functions of the IBBS200D

4-2

Item

Function

Power backup

The IBBS200D is equipped with 48 V 92 Ah battery groups and provides


DC power backup of 48 V 92 Ah or 48 V 184 Ah (two battery groups).

Automatic
reporting of the
cabinet type

The IBBS200D automatically reports the cabinet type using the electronic
labeling unit (ELU).

Built-in fans

The fans speed up the inner and outer circulation to ensure that the cabinet
works in a proper temperature range.

Centralized
monitoring

Alarm signals collected from the door status sensor, smoke sensor, fans,
and temperature sensor for storage batteries are transmitted to the central
monitoring unit type E (CMUE) and are together reported to the base station.
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

4 IBBS200D Product Description

NOTE

Two battery cabinets can be stacked to provide 48 V 368 Ah power backup.

4.2 Specifications of the IBBS200D


The specifications of the IBBS200D consist of electrical specifications, engineering
specifications, and environmental specifications.

Electrical Specifications of the IBBS200D


Table 4-2 describes electrical specifications of the IBBS200D.
Table 4-2 Electrical specifications of the IBBS200D
Item

Specification

Input voltage range

38.4 V DC to 57 V DC

Maximum battery capacity

48 V 184 Ah

Heat dissipation in the cabinet

A rise of the temperature in the cabinet is 5C less than the


ambient temperature.

Engineering Specifications of the IBBS200D


Table 4-3 describes engineering specifications of the IBBS200D.
Table 4-3 Engineering specifications of the IBBS200D
Item

Specification

Remarks

Weight

40 kg

The weight involves the


monitoring board, power
distribution box, and cables and
does not involve batteries.

Battery weight

12 V 92 Ah storage battery cell:


33.5 kg

By combining two 48 V 92 Ah
battery groups in parallel, users can
use 48 V 184 Ah batteries in a
cabinet.

NOTE
The weight of the preceding storage
battery cell is based on a common
battery cell. The actual weight of a
battery cell may vary depending on the
manufacturer.

Cabinet
dimensions (H x
W x D)

Issue 04 (2011-07-08)

700 mm x 600 mm x 480 mm

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

4-3

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

4 IBBS200D Product Description

Item

Specification

Base dimensions
(H x W x D)

200 mm x 600 mm x 434 mm

Remarks

Installation option The IBBS200D can be installed on


a floor or stacked with the
TMC11H or APM30H.

The IBBS200D must be placed


under the TMC11H or APM30H in
stacking mode.

Environmental Specifications of the IBBS200D


The IBBS200D can be used outdoors. Table 4-4 describes environmental specifications of the
IBBS200D.
Table 4-4 Environmental specifications of the IBBS200D
Item

Specification

Remarks

Operating
temperatur
e

40C to +40C

A heating film is required.

Relative
humidity

5% RH to 100% RH

Altitude

60 m to 4000 m

Above the altitude of 1800 m, the


maximum operating temperature
decreases by 1C each time the altitude
increases by 220 m.

Wind
speed

67 m/s

Storage
temperatur
e

40C to +70C

Dustproof
and
waterproof

IP35

Noise

Meeting the ETS 300 753 4.1E


standard (rural areas)

4.3 Structure of the IBBS200D


The IBBS200D has a modular design with high integrity. The power distribution equipment is
installed on the right of the cabinet, and the monitoring equipment is installed on the cabinet
door.
Figure 4-2 shows the structure of the IBBS200D.
4-4

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

4 IBBS200D Product Description

Figure 4-2 Structure of the IBBS200D

Issue 04 (2011-07-08)

S
N

Name

Option
al or
Manda
tory

Maxi
mum
Quan
tity
Confi
gured
in a
Singl
e
Cabi
net

Description

(1
)

Fan
installation
module

Mandat
ory

The fan installation module is installed on the


front door of the cabinet and is equipped with the
fans and central monitoring unit type E (CMUE).

(2
)

CMUE

Mandat
ory

The CMUE provides the functions of temperature


control, Boolean alarm detection, and ELU
identification of the cabinet.

(3
)

Electronic
labeling unit
(ELU)

Mandat
ory

The ELU reports the cabinet type automatically


to facilitate fault identification.

(4
)

Storage battery

Mandat
ory

The storage batteries provide long-duration


backup power for the base station.

(5
)

Door status
sensor

Mandat
ory

The door status sensor monitors the opening and


closing of the front door of the cabinet.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

4-5

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

4 IBBS200D Product Description

S
N

Name

Option
al or
Manda
tory

Maxi
mum
Quan
tity
Confi
gured
in a
Singl
e
Cabi
net

Description

(6
)

Power
distribution
box

Mandat
ory

The power distribution box is installed at the


upper right of the cabinet, implementing
conversion and distribution of power supply to the
fan or TEC and to the storage batteries.

(7
)

Junction box
for the input
power cable
for the heating
film

Mandat
ory

The junction box feeds power to the heating film.

(8
)

Heating film

Optiona
l

The heating film is configured only for the


IBBS200D that is used in cold area.

NOTE

For details about the position of the temperature sensor for storage batteries, see 4.4.8 Temperature Sensor
for Storage Batteries.

4.4 IBBS200D Components


IBBS200D components include the fan installation module, central monitoring unit type E
(CMUE), power distribution box (PDB), storage batteries, electronic labeling unit (ELU), door
status sensor, temperature sensor for storage batteries, and heating film.
4.4.1 Fan Installation Module
The fan installation module is installed on the front door of the cabinet and is equipped with the
fans and central monitoring unit type E (CMUE).
4.4.2 Power Distribution Box
The power distribution box (PDB) is installed at the upper right of the cabinet, controlling two
battery groups and DC power supply of the fan or thermoelectric cooling unit (TEC).
4.4.3 CMUE
The central monitoring unit type E (CMUE) monitors the temperature of the fan box, heater,
and cabinet. The CMUE can be used for cabinets such as the AMP30H, RFC, TMC11H,
IBBS200D, and IBBS200T.
4.4.4 Storage Battery
This section provides the exterior of storage batteries and describes technical specifications and
configuration of storage batteries.
4-6

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

4 IBBS200D Product Description

4.4.5 ELU
The Electronic Label Unit (ELU) automatically reports the information about the cabinet type,
facilitating fast troubleshooting.
4.4.6 Heating Film
This section describes the exterior, functions, and technical specifications of the heating film.
The heating film is optional.
4.4.7 Door Status Sensor
The door status sensor monitors the opening and closing of the front door of the cabinet.
4.4.8 Temperature Sensor for Storage Batteries
A temperature sensor for storage batteries monitors the temperature in a battery cabinet in real
time and reports the temperature to the central monitoring unit type E (CMUE).

4.4.1 Fan Installation Module


The fan installation module is installed on the front door of the cabinet and is equipped with the
fans and central monitoring unit type E (CMUE).

Exterior
Figure 4-3 shows a fan installation module.
Figure 4-3 Fan installation module

Function
The functions of the fan installation module are described as follows:
l

Issue 04 (2011-07-08)

The fans speed up the inner and outer circulation to ensure that the cabinet works in a proper
temperature range.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

4-7

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

4 IBBS200D Product Description

Alarm signals collected from the door status sensor, temperature sensor for storage
batteries, smoke sensor, and fans are transmitted to the CMUE and are together reported
to the power monitoring unit (PMU) through the RS485 signal cable.

4.4.2 Power Distribution Box


The power distribution box (PDB) is installed at the upper right of the cabinet, controlling two
battery groups and DC power supply of the fan or thermoelectric cooling unit (TEC).

Exterior
Figure 4-4 shows a PDB.
Figure 4-4 PDB

Ports
Table 4-5 describes ports on the PDB.
Table 4-5 Ports on the PDB

4-8

SN

Label

Name

Description

(1)

BAT_CON_B
OLT

Power input port


for storage
batteries

The M8 one-hole OT terminal supports a 35


mm2 cable.

(2)

FAN/
TEC_CON_B
OLT

Power input port


for the fan or
TEC

M4 one-hole OT terminal

(3)

BAT_SWO

Circuit breaker
for the upper
storage batteries

This circuit breaker controls cable connections


of the upper storage batteries, and its
specification is 160 A.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

4 IBBS200D Product Description

SN

Label

Name

Description

(4)

BAT_SW1

Circuit breaker
for the lower
storage batteries

This circuit breaker controls cable connections


of the lower storage batteries, and its
specification is 160 A.

(5)

FAN/
TEC_SW2

Circuit breaker
for the fan or
TEC

The specification is 15 A.

(6)

FAN/
TEC_CON_B
OLT

Power input port


for the fan or
TEC

M4 one-hole OT terminal

(7)

BAT_CON_B
OLT

Power input port


for storage
batteries

The M8 one-hole OT terminal supports a 35


mm2 cable.

NOTE

The PDB provides two power input ports for storage batteries and two power input ports for the fan or
TEC. Users can select the ports as required.
1. When the APM30H and IBBS200D or IBBS200T are installed in stacking mode, the input power cables
for storage batteries and the fan or TEC are connected to the upper ports on the PDB.
2. When the APM30H and IBBS200D or IBBS200T are installed in side-by-side mode, the input power
cables for storage batteries and the fan or TEC are connected to the lower ports on the PDB.

External Structure
Figure 4-5 shows the external structure of a PDB.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

4-9

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

4 IBBS200D Product Description

Figure 4-5 External structure of a PDB

(1) RTN(+) cable for the batteries in (2) Power transfer cable for the fan (3) 48 V cable for the batteries in
the upper part
or TEC
the lower part
(4) 48 V cable for the batteries in (5) RTN(+) cable for the batteries in the upper part
the lower part

4.4.3 CMUE
The central monitoring unit type E (CMUE) monitors the temperature of the fan box, heater,
and cabinet. The CMUE can be used for cabinets such as the AMP30H, RFC, TMC11H,
IBBS200D, and IBBS200T.

Function
Table 4-6 describes the functions of the CMUE.
Table 4-6 Functions of the CMUE

4-10

Function

Description

Pulse-width
modulation
(PWM) speed
adjusting

Fan speeds can be adjusted based on temperature or controlled by the


baseband unit (BBU).

Fan speed query

Fan speeds can be queried by running a query command.

Full speed rotation


when a fan is faulty

When a fan in the fan subrack is faulty, other fans rotate at a full speed.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

Function

Description

Full speed rotation


when the CPU is
faulty

Alarm reporting
when the fan box is
faulty

The alarms are as follows:

4 IBBS200D Product Description

l Communication failure alarm


l Fan fault alarm
l Abnormal temperature alarm
l Smoke, water damage, or door status alarm
l Hardware fault alarm (related to the I2C fault)
The alarms are reported through an RS485 bus.

Thermoelectric
cooling unit (TEC)
control and
detection

The CMUE controls the starting and stopping of the TEC and detects
its current and voltage.

Environment
monitoring

The CMUE detects the board temperature and air inlet temperature and
monitors the environment such as smoke, water damage, and door
status.

Boolean value
detection

The CMUE provides four Boolean inputs such as AC/DC surge


protector and door status sensor alarms.

Protection against
reverse connection

The CMUE provides protection against reverse connection.

Status indication

The CMUE provides one red indicator and one green indicator to
indicate the operating status of the board.

RS485 port
cascading and
extension

When a cabinet uses two fan subracks or cabinets are combined, the fan
box automatically identifies communication addresses.

Online loading

The CMUE supports online loading through an RS485 bus.

Surge protection

l The power socket provides surge protection of 1 kV in differential


mode and 2 kV in common mode.
l An RS485 bus supports surge protection of 250 A.
l IN0 and GATE Boolean inputs support surge protection of 250 A.
l IN1 and IN2 Boolean inputs support surge protection of 3 kA in
differential mode and 5 kA in common mode.

Issue 04 (2011-07-08)

Electronic labeling

The CMUE supports electronic labeling for boards and external


cabinets.

Protection against
short-circuiting of
smoke, water, and
temperature
sensors

When short-circuiting occurs on a port, the CMUE provides currentlimiting protection based on positive temperature coefficient (PTC)
thermal resistance or other resistance.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

4-11

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

4 IBBS200D Product Description

Exterior
Figure 4-6 shows a CMUE.
Figure 4-6 CMUE

Ports
Figure 4-7 shows ports and indicators on a CMUE.
Figure 4-7 Ports and indicators on a CMUE

Table 4-7 describes functions of the ports and indicators on a CMUE.


Table 4-7 Functions of the ports and indicators on a CMUE

4-12

S
N

Port or
Indicator

Description

(1)

TEMP2

Connects to a temperature sensor. The port is reserved.

(2)

WATER

Connects to a water sensor.

(3)

IFAN4

Connects to an inner air circulation fan.

(4)

IFAN3

Connects to an inner air circulation fan.

(5)

IFAN2

Connects to an inner air circulation fan.


Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

4 IBBS200D Product Description

S
N

Port or
Indicator

Description

(6)

IFAN1

Connects to an inner air circulation fan.

(7)

TEC

Connects to the TEC and receives alarms related to the TEC.

(8)

TEMP1

l Connects to the temperature sensor at the air inlet of an RFC and


receives temperature alarms.
l Connects to the battery temperature sensor in the IBBS200D or
IBBS200T and receives battery temperature alarms.

(9)

COM_OUT

This port is an RS485 signal port that connects to a lower-level port and
reports monitoring information.
l Connects to the power monitoring unit (PMU) in the APM30H.
l Connects to a lower-level CMUE in the RFC, TMC11H, IBBS200D,
or IBBS200T.

(10
)

COM_IN

This port is an RS485 signal port that connects to an upper-level port


and receives monitoring information.
l Connects to the baseband unit (BBU) in the APM30H.
l Connects to the BBU or an upper-level CMUE in the RFC or
TMC11H.
l Connects to the PMU or an upper-level CMUE in the IBBS200D or
IBBS200T.

Issue 04 (2011-07-08)

(11
)

RUN
indicator

Indicates the operating status of fans.

(12
)

ALM
indicator

Indicates the alarm status of fans.

(13
)

ELU

Connects to the electronic labeling unit (ELU) and reports the cabinet
type.

(14
)

GATE

Connects to the door status sensor. This port is a Boolean signal port.

(15
)

IN0, IN1,
IN2

This port is a reserved Boolean signal port.

(16
)

SMOKE

Connects to the smoke sensor. This port is a Boolean signal port.

(17
)

EFAN1

Connects to an outer air circulation fan.

(18
)

EFAN2

Connects to an outer air circulation fan.

(19
)

PWR

Feeds DC power to boards. This is a power socket.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

4-13

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

4 IBBS200D Product Description

Indicators
Table 4-8 describes the indicators on a CMUE.
Table 4-8 Indicators on a CMUE
Label

Color

State

Description

RUN

Green

Blinking (on for 1s and


off for 1s)

The board is functional and communicates


with its upper-level device properly.

Blinking (on for 0.125s


and off for 0.125s)

The board is functional, but the


communication with its upper-level device
fails or the board is not registered.

Steady on

The board is in the power-on self-test state.

Off

The board is faulty.

Off

No alarm is reported.

Steady on

An alarm is generated, and the board needs to


be replaced.

Blinking (on for 1s and


off for 1s)

An alarm is generated, and the alarm may be


caused by an associated board or port fault.
Therefore, you must identify the fault before
replacing the board.

ALM

Red

DIP Switch
The CMUE has one dual in-line package (DIP) switch J18, which is used to set the working
mode of the CMUE based on the cabinet type. Figure 4-8 shows the position of the DIP switch
on the CMUE.
Figure 4-8 Position of the DIP switch on the CMUE.

Figure 4-9 shows DIP switch settings of the CMUE in different cabinets.

4-14

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

4 IBBS200D Product Description

Figure 4-9 DIP switch settings of the CMUE in different cabinets

NOTE

The red rectangles in Figure 4-9 indicate the positions for inserting jumper pins.

Specification
Table 4-9 describes the specifications of the CMUE.
Table 4-9 Specifications of the CMUE
Item

Specification

Description

Power
consumption

The following specifications are


described:

l The maximum power


consumption of the board circuit
is 3 W.
l The CMUE supports a
maximum of four fans and its
maximum power consumption
is 400 W.
l When the CMUE is connected
to a TEC, the maximum power
consumption is 750 W.

Issue 04 (2011-07-08)

Input voltage
range

36 V DC to +60 V DC

Temperature
detection range

45C to 70C

The DS1820 digital temperature


sensor is used for temperature
detection.

Temperature
detection error

2C

Fan speed
adjustment

Four PWM signal outputs

A maximum of four fans are


supported. Each fan uses a separate
PWM signal output to control fan
speed and status detection in real
time.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

4-15

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

4 IBBS200D Product Description

Item

Specification

Description

Alarm reporting

Alarms reported to the main control


unit through an RS485 serial port.

The board supports one alarm


output through a bus.

Communication
port

Standard RS485 serial port

Operating
temperature
range

40C to 60C

Operating
altitude

4000 m

4.4.4 Storage Battery


This section provides the exterior of storage batteries and describes technical specifications and
configuration of storage batteries.
NOTE

The exterior and technical specifications of the storage battery may vary according to manufacturer. The
following description is based on common 12 V 92 Ah storage batteries.

Exterior
Figure 4-10 shows the exterior of the 12 V 92 Ah storage battery.
Figure 4-10 Exterior of the 12 V 92 Ah storage battery

Technical Specifications
Table 4-10 describes the technical specifications of the 12 V 92 Ah storage battery.
4-16

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

4 IBBS200D Product Description

Table 4-10 Technical specifications of the 12 V 92 Ah storage battery


Type

Dimensions (W x H x D)

Weight

12 V 92 Ah

105 mm x 287 mm x 390 mm

33.5 kg

108 mm x 287 mm x 393 mm

35 kg

Configuration
The cabinet supports two types of storage battery packs: 48 V 92 Ah and 48 V 184 Ah.
l

The upper and lower 48 V 92 Ah storage battery packs can be connected in parallel to
provide 48 V 184 Ah power.

Each storage battery pack contains four single storage batteries.

4.4.5 ELU
The Electronic Label Unit (ELU) automatically reports the information about the cabinet type,
facilitating fast troubleshooting.
The ELU is on the left inner side of the IBBS200D or IBBS200T or on the right inner side of
the APM30H, TMC11H, or RFC. Figure 4-11 shows the ELU.
Figure 4-11 ELU

(1) Housing

(2) RJ-45 port

4.4.6 Heating Film


This section describes the exterior, functions, and technical specifications of the heating film.
The heating film is optional.
Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

4-17

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

4 IBBS200D Product Description


NOTE

The IBBS200D has two heating films, which are installed on the upper and lower baffle plates.

Exterior
Figure 4-12 shows the heating film.
Figure 4-12 Heating film

Functions
The heating film ensures that the storage batteries are stored and function at the proper
temperature when the ambient temperature is low. When the ambient temperature is lower than
the normal working temperature of the storage battery, the battery capacity decreases. In this
case, the heating film is required to guarantee the best performance of the storage batteries.

Technical Specifications
The technical specifications of the heating film are as follows:
l

The heating film works with the rated voltage of 220 V AC, and the rated heating power
is 100 W.

When the ambient temperature is lower than +1oC (with 6oC offset considered), the
heating film starts working; when the ambient temperature is higher than 15oC (with
3oC offset considered), the heating film stops working.

4.4.7 Door Status Sensor


The door status sensor monitors the opening and closing of the front door of the cabinet.
The door status sensor consists of the magnet part and switch part.
Figure 4-13 shows the magnet part of the door status sensor.

4-18

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

4 IBBS200D Product Description

Figure 4-13 Magnet part of the door status sensor

Figure 4-14 shows the switch part of the door status sensor.
Figure 4-14 Switch part of the door status sensor

4.4.8 Temperature Sensor for Storage Batteries


A temperature sensor for storage batteries monitors the temperature in a battery cabinet in real
time and reports the temperature to the central monitoring unit type E (CMUE).

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

4-19

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

4 IBBS200D Product Description

Installation Position
Figure 4-15 and Figure 4-16 show the position for installing a temperature sensor for storage
batteries in the IBBS200D and IBBS200T respectively.
Figure 4-15 Position for installing a temperature sensor for storage batteries in the IBBS200D

Figure 4-16 Position for installing a temperature sensor for storage batteries in the IBBS200T

4.5 IBBS200D Cables


This section describes the PGND cables, equipotential cables, power cables, and signal cables
in the IBBS200D.
4-20

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

4 IBBS200D Product Description

4.5.1 Cables
This section describes the PGND cables, equipotential cables, power cables, and signal cables
in the IBBS200D.
4.5.2 PGND Cables
A protection ground (PGND) cable ensures proper grounding of a cabinet by connecting the
cabinet to an onsite ground bar.
4.5.3 Equipotential Cable
Equipotent cables connect PGND terminals in different cabinets, ensuring equipotential
connections of the cabinets and safe operation of the base station.
4.5.4 Power Cables
This section describes the IBBS200D power cables and their connections.
4.5.5 Signal Cables
This section describes the IBBS200D signal cables and their connections.

4.5.1 Cables
This section describes the PGND cables, equipotential cables, power cables, and signal cables
in the IBBS200D.

Power Cables, PGND Cables, and Equipotential Cable


Table 4-11 lists the power cables, PGND cables, and equipotential cable.
Table 4-11 Power cables, PGND cables, and equipotential cable

Issue 04 (2011-07-08)

Categ
ory

Cable

Cables
to be
install
ed
onsite

Power Cables
for Storage
Batteries

Fan Power
Cables in the
IBBS200D

One End
Connector

The Other End


Installation
Position

Connector

Installation
Position

Power series
Power series
175 connector 175 connector
(gray)
(gray) of the
EPU

OT terminal

RTN(+) and
NEG(-)
terminals of
BAT on the
power
distribution
box in the
IBBS200D or
IBBS200T

Easy power
receptacle
(pressfit type)
connector

OT terminal

RTN(+) and
NEG(-)
terminals of
the TEC or fan
on the power
distribution
box in the
IBBS200D

LOAD3 or
LOAD4
terminal (1) on
the EPU

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

4-21

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

4 IBBS200D Product Description

Categ
ory

Cables
install
ed
before
deliver
y

Cable

One End

The Other End

Connector

Installation
Position

Connector

Installation
Position

Power Cable
for the
Heating Film

OT terminal

L1 and N1 or
L2 and N2
terminals on
the junction
box in the
APM30H

OT terminal

L and N
terminals of
the power
cable for the
heating film in
the IBBS200D

4.5.2 PGND
Cables

OT terminal

Ground bar of
the cabinet

OT terminal

Ground busbar
outside the
cabinet

4.5.3
Equipotential
Cable

OT terminal

Ground bar of
the upper
cabinet

OT terminal

Ground bar of
the lower
cabinet

NOTE

(1) LOAD4 is preferentially used. If LOAD4 is already used, use LOAD3.

Signal Cables
Table 4-12 lists the signal cables.
Table 4-12 Signal cables

4-22

Categ
ory

Cable

Cables
to be
install
ed
onsite
Cables
install
ed
before

One End

The Other End

Connecto
r

Installation
Position

Connect
or

Installation
Position

Monitoring
Signal
Cable for
the Storage
Battery
Cabinet

RJ45
connector

COM_IN port on
the CMUE in the
IBBS200D or
IBBS200T

RJ45
connector

COM_485 port on
the PMU

Signal
Cable for
the ELU

RJ45
connector

ELU

RJ45
connector

ELU port on the


CMUE

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

Categ
ory

Cable

deliver
y

Monitoring
Signal
Cable for
the Door
Status
Sensor

4 IBBS200D Product Description

One End

The Other End

Connecto
r

Installation
Position

Connect
or

Installation
Position

2-pin
connector

GATE port on the


CMUE

Bare wire

Door status sensor

4.5.2 PGND Cables


A protection ground (PGND) cable ensures proper grounding of a cabinet by connecting the
cabinet to an onsite ground bar.

Exterior
Figure 4-17 shows the PGND cable.
Figure 4-17 PGND cable

(1) OT terminal

Description
Table 4-13 describes the PGND cables.
Table 4-13 PGND cables
Cable

Color

Cross-Sectional Area

PGND cable for the


cabinet

Yellow and green

16mm2, M6

4.5.3 Equipotential Cable


Equipotent cables connect PGND terminals in different cabinets, ensuring equipotential
connections of the cabinets and safe operation of the base station.
Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

4-23

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

4 IBBS200D Product Description

Exterior
Figure 4-18 shows an equipotential cable.
Figure 4-18 Equipotential cable

Description
Table 4-14 describes the equipotential cable.
Table 4-14 Specifications of the equipotential cable
Name

Color

Cross-Sectional Area

Equipotential cable for


the cabinet

Yellow and green

Specifications of the cable vary


depending on the installation mode of
cabinets.
l For stacked cabinets: 16mm2, M6
l For cabinets installed side-by-side:
25mm2, M6

4.5.4 Power Cables


This section describes the IBBS200D power cables and their connections.

Power Cable Connections in the IBBS200D


This section describes power cable connections in the IBBS200D.
Figure 4-19 shows the power cable connections in the IBBS200D.

4-24

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

4 IBBS200D Product Description

Figure 4-19 Power cable connections in the IBBS200D

(1) Power cable between the


(2) Input power cable for the fan in (3) Input power cable for storage
battery group and the copper bar in the IBBS200D
batteries
the junction box
(4) Power cable between the
(5) Power cable for the heating film (6) Power transfer cable for the fan in
battery group and the copper bar in
the IBBS200D
the junction box

Power Cables for Storage Batteries


This section describes input power cables for storage batteries, power cables between the battery
group and the copper bar in the junction box, and a copper bar for inter-battery series connection.

Exterior
Figure 4-20 shows input power cables for storage batteries.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

4-25

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

4 IBBS200D Product Description

Figure 4-20 Input power cables for storage batteries

(1) Power series 175 connector

(2) OT terminal (35 mm2, M8)

Figure 4-21 shows power cables between the battery group and the copper bar in the junction
box.
Figure 4-21 Power cables between the battery group and the copper bar in the junction box

(1) OT terminal (35 mm2, M8)

(2) OT terminal (35 mm2, M6)

NOTE

The M6 OT terminal is connected to the battery end, and the M8 OT terminal is connected to the power
distribution box (PDB) end.

Copper bars for inter-battery series connection are delivered with storage batteries. Figure
4-22 shows a copper bar for inter-battery series connection.
Figure 4-22 Copper bar for inter-battery series connection

4-26

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

4 IBBS200D Product Description

Specifications
l

The RTN(+) cable of input power cables for storage batteries is a red cable with a crosssectional area of 35 mm2, and the NEG(-) cable is a black cable with a cross-sectional area
of 35 mm2.

The RTN(+) cable of power cables between the battery group and the copper bar in the
junction box is a red cable with a cross-sectional area of 35 mm2, and the NEG(-) cable is
a black cable with a cross-sectional area of 35 mm2.

Fan Power Cables in the IBBS200D


Fan power cables in the IBBS200D are classified into input power cables for the fan and power
transfer cables for the fan.

Input Power Cable for the Fan in the IBBS200D


Figure 4-23 shows the input power cables for the fan in the IBBS200D.
Figure 4-23 Input power cables for the fan in the IBBS200D

(1) Easy power receptacle (pressfit type) connector

(2) OT terminal

Table 4-15 describes the specifications of the input power cable for the fan in the IBBS200D.
Table 4-15 Specifications of the input power cable for the fan in the IBBS200D
Cable

Wire

Wire Color in
Most Area

Wire Color in
Other Area

Cross-Sectional
Area of the Wire
and Aperture of
the OT Terminal

Input power
cable for the
fan in the
IBBS200D

RTN
(+)

Black

Blue

2.5 mm2, M4

NEG
(-)

Blue

Gray

Power Transfer Cable for the Fan in the IBBS200D


Figure 4-24 shows the power transfer cables for the fan in the IBBS200D.
Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

4-27

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

4 IBBS200D Product Description

Figure 4-24 Power transfer cables for the fan in the IBBS200D

(1) 3V3 power connector (2) OT terminal (1.5 mm2, (3) OT terminal (6 mm2,
M6)
M4)

(4) OT terminal (1.5 mm2,


M4)

Table 4-16 describes the specifications of the power transfer cable for the fan in the IBBS200D.
Table 4-16 Specifications of the power transfer cable for the fan in the IBBS200D
Cable

Wire

Wire Color in Most


Area

Wire Color in Other Area

Power transfer
cable for the fan in
the IBBS200D

W1

Blue

Gray

W2

Black

Blue

Power Cable for the Heating Film


The power cable for the heating film is used to connect the output terminal on the junction box
and the AC input terminal for the heating film on the left of the APM30H.

Exterior
Figure 4-25 shows a power cable for the heating film.
Figure 4-25 Power cable for the heating film

(1) M4 OT terminal with a cross-sectional area of 1.5 (2) M4 OT terminal with a cross-sectional area of 1.5
mm2 on the APM30H side
mm2 on the battery cabinet side

Specifications
The power cable for the heating film is a black cable with a cross-sectional area of 1.5 mm2 and
blue and brown wires.
4-28

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

4 IBBS200D Product Description

4.5.5 Signal Cables


This section describes the IBBS200D signal cables and their connections.

Signal Cable Connections in the IBBS200D


This section describes the signal cable connections in the IBBS200D.
Figure 4-26 shows the signal cable connections in the IBBS200D.
Figure 4-26 Signal cable connections in the IBBS200D

(1) Monitoring signal cable for the door


status sensor

(2) Signal for the ELU (3) Monitoring signal cable for the battery
cabinet

Signal Cable for the ELU


The signal cable for the electronic labeling unit (ELU) is used to report the cabinet type
information collected by the ELU to the central monitoring unit type E (CMUE).

Exterior
Figure 4-27 shows the signal cable for the ELU.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

4-29

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

4 IBBS200D Product Description

Figure 4-27 Signal cable for the ELU

(1) RJ45 connector

Pin Assignment
Table 4-17 describes the pin assignment for the wires of the signal cable for the ELU.
Table 4-17 Pin assignment for the wires of the signal cable for the ELU
X1 End

X2 End

Wire Color

Wire Type

X1.1

X2.1

White

Twisted pair

X1.2

X2.2

Orange

X1.3

X2.3

White

X1.6

X2.6

Green

X1.5

X2.5

White

X1.4

X2.4

Blue

X1.7

X2.7

White

X1.8

X2.8

Brown

Twisted pair

Twisted pair

Twisted pair

Monitoring Signal Cable for the Door Status Sensor


The monitoring signal cable for the door status sensor is used to inform the central monitoring
unit type E (CMUE) of the door status that is obtained from the door status sensor in the
TMC11H, radio frequency cabinet (RFC), IBBS200D, or IBBS200T.

Exterior
The monitoring signal cable for the door status sensor has two black bare wires, as shown in
Figure 4-28.
Figure 4-28 Monitoring signal cable for the door status sensor

4-30

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

4 IBBS200D Product Description

Monitoring Signal Cable for the Storage Battery Cabinet


The monitoring signal cable for the storage battery cabinet collects and transmits the monitoring
signals of the IBBS200D or IBBS200T to the PMU.

Exterior
Figure 4-29 shows the monitoring signal cable for the storage battery cabinet.
Figure 4-29 Monitoring signal cable for the storage battery cabinet

(1) RJ45 connector

Pin Assignment
Table 4-18 describes the pin assignment for the wires of the monitoring signal cable for the
storage battery cabinet.
Table 4-18 Pin assignment for the wires of the monitoring signal cable for the storage battery
cabinet

Issue 04 (2011-07-08)

X1 End

X2 End

Wire Color

Type

X1.1

X2.1

White

Twisted pair

X1.2

X2.2

Orange

X1.3

X2.3

White

X1.6

X2.6

Green

X1.5

X2.5

White

X1.4

X2.4

Blue

X1.7

X2.7

White

X1.8

X2.8

Brown

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Twisted pair

Twisted pair

Twisted pair

4-31

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

5 IBBS200T Product Description

IBBS200T Product Description

About This Chapter


This chapter describes the exterior, functions, specifications, structure, components, and cables
of the IBBS200T.
5.1 Introduction to the IBBS200T
The IBBS200T provides power backup for the APM30H.
5.2 Specifications of the IBBS200T
The specifications of the IBBS200T consist of electrical specifications, engineering
specifications, and environmental specifications.
5.3 Structure of the IBBS200T
The IBBS200T has a modular design with high integrity. The power distribution equipment is
installed on the right of the cabinet, and the monitoring equipment is installed on the cabinet
door.
5.4 IBBS200T Components
IBBS200T components include the thermoelectric cooling unit (TEC), central monitoring unit
type E (CMUE), power distribution box (PDB), storage batteries, electronic labeling unit (ELU),
door status sensor, and temperature sensor for storage batteries.
5.5 IBBS200T Cables
This section describes the PGND cables, equipotential cables, power cables, and signal cables
in the IBBS200T.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

5-1

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

5 IBBS200T Product Description

5.1 Introduction to the IBBS200T


The IBBS200T provides power backup for the APM30H.
The IBBS200T uses aluminum plates and orange powder coating on the surface to prevent solar
radiation, corrosion, humidity, and mildew. The thermoelectric cooling unit (TEC) is used in
the IBBS200T, and the sticking rate of the heat insulation foam reaches 75%, which improves
the cooling capability of the TEC.

Exterior of the IBBS200T


The dimensions (H x W x D) of an IBBS200T without a base are 700 mm x 600 mm x 480 mm.
Figure 5-1 shows an IBBS200T.
Figure 5-1 IBBS200T

Functions of the IBBS200T


Table 5-1 describes functions of the IBBS200T.
Table 5-1 Functions of the IBBS200T

5-2

Item

Function

Power backup

The IBBS200T is equipped with 48 V 92 Ah battery groups and provides


DC power backup of 48 V 92 Ah or 48 V 184 Ah (two battery groups).

Automatic
reporting of the
cabinet type

The IBBS200T automatically reports the cabinet type using the electronic
labeling unit (ELU).

Built-in TEC

The TEC ensures that the cabinet works in a proper temperature range.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

5 IBBS200T Product Description

Item

Function

Centralized
monitoring

Alarm signals collected from the door status sensor, smoke sensor, fans,
and temperature sensor for storage batteries are transmitted to the central
monitoring unit type E (CMUE) and are together reported to the base station.

NOTE

Two battery cabinets can be stacked to provide 48 V 368 Ah backup power.

5.2 Specifications of the IBBS200T


The specifications of the IBBS200T consist of electrical specifications, engineering
specifications, and environmental specifications.

Electrical Specifications of the IBBS200T


Table 5-2 describes electrical specifications of the IBBS200T.
Table 5-2 Electrical specifications of the IBBS200T
Item

Specification

Input voltage range

38.4 V DC to 57 V DC

Maximum battery capacity

48 V 184 Ah

Cooling capability

l When the ambient temperature is less than or equal to


45C, the inner air circulation temperature at the air
outlet is less than or equal to 35C.
l When the ambient temperature is greater than 45C and
less than or equal to 50C, the inner air circulation
temperature at the air outlet is less than or equal to 45
C.

Engineering Specifications of the IBBS200T


Table 5-3 describes engineering specifications of the IBBS200T.
Table 5-3 Engineering specifications of the IBBS200T

Issue 04 (2011-07-08)

Item

Specification

Remarks

Weight

45 kg

The weight involves the


monitoring board, power
distribution box, and cables and
does not involve batteries.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

5-3

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

5 IBBS200T Product Description

Item

Specification

Remarks

Battery weight

12 V 92 Ah storage battery cell:


33.5 kg

By combining two 48 V 92 Ah
battery groups in parallel, users can
use 48 V 184 Ah batteries in a
cabinet.

NOTE
The weight of the preceding storage
battery cell is based on a common
battery cell. The actual weight of a
battery cell may vary depending on the
manufacturer.

Cabinet
dimensions (H x
W x D)

700 mm x 600 mm x 480 mm

Base dimensions
(H x W x D)

200 mm x 600 mm x 434 mm

Installation option The IBBS200T can be installed on


a floor or stacked with the
TMC11H or APM30H.

The IBBS200T must be placed


under the TMC11H or APM30H in
stacking mode.

Environmental Specifications of the IBBS200T


The IBBS200T can be used outdoors. Table 5-4 describes environmental specifications of the
IBBS200T.
Table 5-4 Environmental specifications of the IBBS200T

5-4

Item

Specification

Remarks

Operating
temperatur
e

20C to +50C

A sun shield is required when the


operating temperature is above 50C.

Relative
humidity

5% RH to 100% RH

Altitude

60 m to 4000 m

Above the altitude of 1800 m, the


maximum operating temperature
decreases by 1C each time the altitude
increases by 220 m.

Wind
speed

67 m/s

Storage
temperatur
e

40C to +70C

Dustproof
and
waterproof
class

IP35

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

5 IBBS200T Product Description

Item

Specification

Remarks

Noise level

Meeting the ETS 300 753 4.1E


standard (rural areas)

5.3 Structure of the IBBS200T


The IBBS200T has a modular design with high integrity. The power distribution equipment is
installed on the right of the cabinet, and the monitoring equipment is installed on the cabinet
door.
Figure 5-2 shows the structure of the IBBS200T.
Figure 5-2 Structure of the IBBS200T

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

5-5

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

5 IBBS200T Product Description

S
N

Name

Option
al or
Manda
tory

Max
imu
m
Qua
ntit
y
Con
figu
red
in a
Sin
gle
Cab
inet

Description

(1)

TEC

Mandat
ory

The TEC is installed in the protecting hood for the TEC


on the front door of the cabinet. The TEC consists of
the TEC module, inner air circulation fan, outer air
circulation fan, heat-dissipation piece, and monitoring
board.

(2)

CMUE

Mandat
ory

The CMUE provides the functions of temperature


control, Boolean alarm detection, and ELU
identification of the cabinet.

(3)

Electronic
labeling
unit (ELU)

Mandat
ory

The ELU reports the cabinet type automatically to


facilitate fault identification.

(4)

Storage
battery

Mandat
ory

The storage batteries provide long-duration backup


power for the base station.

(5)

Door status
sensor

Mandat
ory

The door status sensor monitors the opening and


closing of the front door of the cabinet.

(6)

Power
distributio
n box

Mandat
ory

The power distribution box is installed at the upper


right of the cabinet, implementing conversion and
distribution of power supply to the fan or TEC and to
the storage batteries.

NOTE

For details about the position of the temperature sensor for storage batteries, see 5.4.7 Temperature Sensor
for Storage Batteries.

5.4 IBBS200T Components


IBBS200T components include the thermoelectric cooling unit (TEC), central monitoring unit
type E (CMUE), power distribution box (PDB), storage batteries, electronic labeling unit (ELU),
door status sensor, and temperature sensor for storage batteries.
5.4.1 TEC
5-6

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

5 IBBS200T Product Description

The thermoelectric cooling unit (TEC) is installed in the protecting hood for the TEC on the
front door of the cabinet. The TEC consists of the TEC module, inner air circulation fan, outer
air circulation fan, heat-dissipation piece, and monitoring board.
5.4.2 Power Distribution Box
The power distribution box (PDB) is installed at the upper right of the cabinet, controlling two
battery groups and DC power supply of the fan or thermoelectric cooling unit (TEC).
5.4.3 CMUE
The central monitoring unit type E (CMUE) monitors the temperature of the fan box, heater,
and cabinet. The CMUE can be used for cabinets such as the AMP30H, RFC, TMC11H,
IBBS200D, and IBBS200T.
5.4.4 Storage Battery
This section provides the exterior of storage batteries and describes technical specifications and
configuration of storage batteries.
5.4.5 ELU
The Electronic Label Unit (ELU) automatically reports the information about the cabinet type,
facilitating fast troubleshooting.
5.4.6 Door Status Sensor
The door status sensor monitors the opening and closing of the front door of the cabinet.
5.4.7 Temperature Sensor for Storage Batteries
A temperature sensor for storage batteries monitors the temperature in a battery cabinet in real
time and reports the temperature to the central monitoring unit type E (CMUE).

5.4.1 TEC
The thermoelectric cooling unit (TEC) is installed in the protecting hood for the TEC on the
front door of the cabinet. The TEC consists of the TEC module, inner air circulation fan, outer
air circulation fan, heat-dissipation piece, and monitoring board.

Exterior
Figure 5-3 shows a TEC.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

5-7

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

5 IBBS200T Product Description

Figure 5-3 TEC

Function
The TEC provides the following functions:

5-8

The TEC obtains 48 V DC power from the embedded power subrack unit (EPU) in the
APM30H.

When the ambient temperature is 50C without solar radiation and the storage batteries are
in the float charging state, the temperature in the cabinet is not greater than 40C. If the
storage batteries are in the boost charging state, the temperature is not greater than 45C.

When the ambient temperature is 50C with solar radiation (1120 W/m2, without sun
shields) considered, and the storage batteries are in the float charging state, the temperature
in the cabinet is not greater than 45C. If the storage batteries are in the boost charging
state, the temperature is not greater than 50C.

When the ambient temperature is 32C and the temperature offset between the cool and
hot air inlets of the TEC is 0C, the cooling power of the TEC is not less than 190 W (10%)
and the coefficient of performance (COP) is not less than 0.5.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

5 IBBS200T Product Description

5.4.2 Power Distribution Box


The power distribution box (PDB) is installed at the upper right of the cabinet, controlling two
battery groups and DC power supply of the fan or thermoelectric cooling unit (TEC).

Exterior
Figure 5-4 shows a PDB.
Figure 5-4 PDB

Ports
Table 5-5 describes ports on the PDB.
Table 5-5 Ports on the PDB

Issue 04 (2011-07-08)

SN

Label

Name

Description

(1)

BAT_CON_B
OLT

Power input port


for storage
batteries

The M8 one-hole OT terminal supports a 35


mm2 cable.

(2)

FAN/
TEC_CON_B
OLT

Power input port


for the fan or
TEC

M4 one-hole OT terminal

(3)

BAT_SWO

Circuit breaker
for the upper
storage batteries

This circuit breaker controls cable connections


of the upper storage batteries, and its
specification is 160 A.

(4)

BAT_SW1

Circuit breaker
for the lower
storage batteries

This circuit breaker controls cable connections


of the lower storage batteries, and its
specification is 160 A.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

5-9

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

5 IBBS200T Product Description

SN

Label

Name

Description

(5)

FAN/
TEC_SW2

Circuit breaker
for the fan or
TEC

The specification is 15 A.

(6)

FAN/
TEC_CON_B
OLT

Power input port


for the fan or
TEC

M4 one-hole OT terminal

(7)

BAT_CON_B
OLT

Power input port


for storage
batteries

The M8 one-hole OT terminal supports a 35


mm2 cable.

NOTE

The PDB provides two power input ports for storage batteries and two power input ports for the fan or
TEC. Users can select the ports as required.
1. When the APM30H and IBBS200D or IBBS200T are installed in stacking mode, the input power cables
for storage batteries and the fan or TEC are connected to the upper ports on the PDB.
2. When the APM30H and IBBS200D or IBBS200T are installed in side-by-side mode, the input power
cables for storage batteries and the fan or TEC are connected to the lower ports on the PDB.

External Structure
Figure 5-5 shows the external structure of a PDB.
Figure 5-5 External structure of a PDB

(1) RTN(+) cable for the batteries in (2) Power transfer cable for the fan (3) 48 V cable for the batteries in
the upper part
or TEC
the lower part

5-10

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

5 IBBS200T Product Description

(4) 48 V cable for the batteries in (5) RTN(+) cable for the batteries in the upper part
the lower part

5.4.3 CMUE
The central monitoring unit type E (CMUE) monitors the temperature of the fan box, heater,
and cabinet. The CMUE can be used for cabinets such as the AMP30H, RFC, TMC11H,
IBBS200D, and IBBS200T.

Function
Table 5-6 describes the functions of the CMUE.
Table 5-6 Functions of the CMUE
Function

Description

Pulse-width
modulation
(PWM) speed
adjusting

Fan speeds can be adjusted based on temperature or controlled by the


baseband unit (BBU).

Fan speed query

Fan speeds can be queried by running a query command.

Full speed rotation


when a fan is faulty

When a fan in the fan subrack is faulty, other fans rotate at a full speed.

Full speed rotation


when the CPU is
faulty

Alarm reporting
when the fan box is
faulty

The alarms are as follows:


l Communication failure alarm
l Fan fault alarm
l Abnormal temperature alarm
l Smoke, water damage, or door status alarm
l Hardware fault alarm (related to the I2C fault)
The alarms are reported through an RS485 bus.

Issue 04 (2011-07-08)

Thermoelectric
cooling unit (TEC)
control and
detection

The CMUE controls the starting and stopping of the TEC and detects
its current and voltage.

Environment
monitoring

The CMUE detects the board temperature and air inlet temperature and
monitors the environment such as smoke, water damage, and door
status.

Boolean value
detection

The CMUE provides four Boolean inputs such as AC/DC surge


protector and door status sensor alarms.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

5-11

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

5 IBBS200T Product Description

Function

Description

Protection against
reverse connection

The CMUE provides protection against reverse connection.

Status indication

The CMUE provides one red indicator and one green indicator to
indicate the operating status of the board.

RS485 port
cascading and
extension

When a cabinet uses two fan subracks or cabinets are combined, the fan
box automatically identifies communication addresses.

Online loading

The CMUE supports online loading through an RS485 bus.

Surge protection

l The power socket provides surge protection of 1 kV in differential


mode and 2 kV in common mode.
l An RS485 bus supports surge protection of 250 A.
l IN0 and GATE Boolean inputs support surge protection of 250 A.
l IN1 and IN2 Boolean inputs support surge protection of 3 kA in
differential mode and 5 kA in common mode.

Electronic labeling

The CMUE supports electronic labeling for boards and external


cabinets.

Protection against
short-circuiting of
smoke, water, and
temperature
sensors

When short-circuiting occurs on a port, the CMUE provides currentlimiting protection based on positive temperature coefficient (PTC)
thermal resistance or other resistance.

Exterior
Figure 5-6 shows a CMUE.
Figure 5-6 CMUE

Ports
Figure 5-7 shows ports and indicators on a CMUE.

5-12

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

5 IBBS200T Product Description

Figure 5-7 Ports and indicators on a CMUE

Table 5-7 describes functions of the ports and indicators on a CMUE.


Table 5-7 Functions of the ports and indicators on a CMUE
S
N

Port or
Indicator

Description

(1)

TEMP2

Connects to a temperature sensor. The port is reserved.

(2)

WATER

Connects to a water sensor.

(3)

IFAN4

Connects to an inner air circulation fan.

(4)

IFAN3

Connects to an inner air circulation fan.

(5)

IFAN2

Connects to an inner air circulation fan.

(6)

IFAN1

Connects to an inner air circulation fan.

(7)

TEC

Connects to the TEC and receives alarms related to the TEC.

(8)

TEMP1

l Connects to the temperature sensor at the air inlet of an RFC and


receives temperature alarms.
l Connects to the battery temperature sensor in the IBBS200D or
IBBS200T and receives battery temperature alarms.

(9)

COM_OUT

This port is an RS485 signal port that connects to a lower-level port and
reports monitoring information.
l Connects to the power monitoring unit (PMU) in the APM30H.
l Connects to a lower-level CMUE in the RFC, TMC11H, IBBS200D,
or IBBS200T.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

5-13

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

5 IBBS200T Product Description

S
N

Port or
Indicator

Description

(10
)

COM_IN

This port is an RS485 signal port that connects to an upper-level port


and receives monitoring information.
l Connects to the baseband unit (BBU) in the APM30H.
l Connects to the BBU or an upper-level CMUE in the RFC or
TMC11H.
l Connects to the PMU or an upper-level CMUE in the IBBS200D or
IBBS200T.

(11
)

RUN
indicator

Indicates the operating status of fans.

(12
)

ALM
indicator

Indicates the alarm status of fans.

(13
)

ELU

Connects to the electronic labeling unit (ELU) and reports the cabinet
type.

(14
)

GATE

Connects to the door status sensor. This port is a Boolean signal port.

(15
)

IN0, IN1,
IN2

This port is a reserved Boolean signal port.

(16
)

SMOKE

Connects to the smoke sensor. This port is a Boolean signal port.

(17
)

EFAN1

Connects to an outer air circulation fan.

(18
)

EFAN2

Connects to an outer air circulation fan.

(19
)

PWR

Feeds DC power to boards. This is a power socket.

Indicators
Table 5-8 describes the indicators on a CMUE.
Table 5-8 Indicators on a CMUE

5-14

Label

Color

State

Description

RUN

Green

Blinking (on for 1s and


off for 1s)

The board is functional and communicates


with its upper-level device properly.

Blinking (on for 0.125s


and off for 0.125s)

The board is functional, but the


communication with its upper-level device
fails or the board is not registered.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

Label

ALM

Color

Red

5 IBBS200T Product Description

State

Description

Steady on

The board is in the power-on self-test state.

Off

The board is faulty.

Off

No alarm is reported.

Steady on

An alarm is generated, and the board needs to


be replaced.

Blinking (on for 1s and


off for 1s)

An alarm is generated, and the alarm may be


caused by an associated board or port fault.
Therefore, you must identify the fault before
replacing the board.

DIP Switch
The CMUE has one dual in-line package (DIP) switch J18, which is used to set the working
mode of the CMUE based on the cabinet type. Figure 5-8 shows the position of the DIP switch
on the CMUE.
Figure 5-8 Position of the DIP switch on the CMUE.

Figure 5-9 shows DIP switch settings of the CMUE in different cabinets.
Figure 5-9 DIP switch settings of the CMUE in different cabinets

NOTE

The red rectangles in Figure 5-9 indicate the positions for inserting jumper pins.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

5-15

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

5 IBBS200T Product Description

Specification
Table 5-9 describes the specifications of the CMUE.
Table 5-9 Specifications of the CMUE
Item

Specification

Description

Power
consumption

The following specifications are


described:

l The maximum power


consumption of the board circuit
is 3 W.
l The CMUE supports a
maximum of four fans and its
maximum power consumption
is 400 W.
l When the CMUE is connected
to a TEC, the maximum power
consumption is 750 W.

5-16

Input voltage
range

36 V DC to +60 V DC

Temperature
detection range

45C to 70C

The DS1820 digital temperature


sensor is used for temperature
detection.

Temperature
detection error

2C

Fan speed
adjustment

Four PWM signal outputs

A maximum of four fans are


supported. Each fan uses a separate
PWM signal output to control fan
speed and status detection in real
time.

Alarm reporting

Alarms reported to the main control


unit through an RS485 serial port.

The board supports one alarm


output through a bus.

Communication
port

Standard RS485 serial port

Operating
temperature
range

40C to 60C

Operating
altitude

4000 m

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

5 IBBS200T Product Description

5.4.4 Storage Battery


This section provides the exterior of storage batteries and describes technical specifications and
configuration of storage batteries.
NOTE

The exterior and technical specifications of the storage battery may vary according to manufacturer. The
following description is based on common 12 V 92 Ah storage batteries.

Exterior
Figure 5-10 shows the exterior of the 12 V 92 Ah storage battery.
Figure 5-10 Exterior of the 12 V 92 Ah storage battery

Technical Specifications
Table 5-10 describes the technical specifications of the 12 V 92 Ah storage battery.
Table 5-10 Technical specifications of the 12 V 92 Ah storage battery
Type

Dimensions (W x H x D)

Weight

12 V 92 Ah

105 mm x 287 mm x 390 mm

33.5 kg

108 mm x 287 mm x 393 mm

35 kg

Configuration
The cabinet supports two types of storage battery packs: 48 V 92 Ah and 48 V 184 Ah.
l

Issue 04 (2011-07-08)

The upper and lower 48 V 92 Ah storage battery packs can be connected in parallel to
provide 48 V 184 Ah power.
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd.

5-17

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

5 IBBS200T Product Description

Each storage battery pack contains four single storage batteries.

5.4.5 ELU
The Electronic Label Unit (ELU) automatically reports the information about the cabinet type,
facilitating fast troubleshooting.
The ELU is on the left inner side of the IBBS200D or IBBS200T or on the right inner side of
the APM30H, TMC11H, or RFC. Figure 5-11 shows the ELU.
Figure 5-11 ELU

(1) Housing

(2) RJ-45 port

5.4.6 Door Status Sensor


The door status sensor monitors the opening and closing of the front door of the cabinet.
The door status sensor consists of the magnet part and switch part.
Figure 5-12 shows the magnet part of the door status sensor.

5-18

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

5 IBBS200T Product Description

Figure 5-12 Magnet part of the door status sensor

Figure 5-13 shows the switch part of the door status sensor.
Figure 5-13 Switch part of the door status sensor

5.4.7 Temperature Sensor for Storage Batteries


A temperature sensor for storage batteries monitors the temperature in a battery cabinet in real
time and reports the temperature to the central monitoring unit type E (CMUE).

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

5-19

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

5 IBBS200T Product Description

Installation Position
Figure 5-14 and Figure 5-15 show the position for installing a temperature sensor for storage
batteries in the IBBS200D and IBBS200T respectively.
Figure 5-14 Position for installing a temperature sensor for storage batteries in the IBBS200D

Figure 5-15 Position for installing a temperature sensor for storage batteries in the IBBS200T

5.5 IBBS200T Cables


This section describes the PGND cables, equipotential cables, power cables, and signal cables
in the IBBS200T.
5-20

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

5 IBBS200T Product Description

5.5.1 Cables
This section describes the PGND cables, equipotential cables, power cables, and signal cables
in the IBBS200T.
5.5.2 PGND Cables
A protection ground (PGND) cable ensures proper grounding of a cabinet by connecting the
cabinet to an onsite ground bar.
5.5.3 Equipotential Cable
Equipotent cables connect PGND terminals in different cabinets, ensuring equipotential
connections of the cabinets and safe operation of the base station.
5.5.4 Power Cables
This section describes the IBBS200T power cables and their connections.
5.5.5 Signal Cables
This section describes the IBBS200T signal cables and their connections.

5.5.1 Cables
This section describes the PGND cables, equipotential cables, power cables, and signal cables
in the IBBS200T.

Power Cables, PGND Cables, and Equipotential Cable


Table 5-11 lists the power cables, PGND cables, and equipotential cable.
Table 5-11 Power cables, PGND cables, and equipotential cable

Issue 04 (2011-07-08)

Categ
ory

Cable

Cables
to be
install
ed
onsite

One End

The Other End

Connector

Installation
Position

Connector

Installation
Position

Power Cables
for Storage
Batteries

PP175
connector
(gray)

PP175
connector
(gray) on the
EPU

OT terminal

RTN(+) and
NEG(-)
terminals of
BAT on the
power
distribution
box in the
IBBS200D or
IBBS200T

Power Cables
for the TEC

Easy power
receptacle
(pressfit type)
connector

LOAD2 to
LOAD4
terminals (1)
on the EPU

OT terminal

RTN(+) and
NEG(-)
terminals of
the TEC or fan
on the power
distribution
box in the
IBBS200T

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

5-21

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

5 IBBS200T Product Description

Categ
ory

Cables
install
ed
before
deliver
y

Cable

One End

The Other End

Connector

Installation
Position

Connector

Installation
Position

5.5.2 PGND
Cables

OT terminal

Ground bar of
the cabinet

OT terminal

Ground busbar
outside the
cabinet

5.5.3
Equipotential
Cable

OT terminal

Ground bar of
the upper
cabinet

OT terminal

Ground bar of
the lower
cabinet

NOTE

(1) LOAD4 is preferentially used. If LOAD4 is already used, use LOAD3. IF there are two IBBS200Ts,
the second IBBS200T can use LOAD2.

Signal Cables
Table 5-12 lists the signal cables.
Table 5-12 Signal cables

5-22

Categ
ory

Cable

Cables
to be
install
ed
onsite
Cables
install
ed
before
deliver
y

One End

The Other End

Connecto
r

Installation
Position

Connect
or

Installation
Position

Monitoring
Signal
Cable for
the Storage
Battery
Cabinet

RJ45
connector

COM_IN port on
the CMUE in the
IBBS200D or
IBBS200T

RJ45
connector

COM_485 port on
the PMU

Signal
Cable for
the ELU

RJ45
connector

ELU

RJ45
connector

ELU port on the


CMUE

Monitoring
Signal
Cable for
the Door
Status
Sensor

2-pin
connector

GATE port on the


CMUE

Bare wire

Door status sensor

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

5 IBBS200T Product Description

5.5.2 PGND Cables


A protection ground (PGND) cable ensures proper grounding of a cabinet by connecting the
cabinet to an onsite ground bar.

Exterior
Figure 5-16 shows the PGND cable.
Figure 5-16 PGND cable

(1) OT terminal

Description
Table 5-13 describes the PGND cables.
Table 5-13 PGND cables
Cable

Color

Cross-Sectional Area

PGND cable for the


cabinet

Yellow and green

16mm2, M6

5.5.3 Equipotential Cable


Equipotent cables connect PGND terminals in different cabinets, ensuring equipotential
connections of the cabinets and safe operation of the base station.

Exterior
Figure 5-17 shows an equipotential cable.
Figure 5-17 Equipotential cable

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

5-23

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

5 IBBS200T Product Description

Description
Table 5-14 describes the equipotential cable.
Table 5-14 Specifications of the equipotential cable
Name

Color

Cross-Sectional Area

Equipotential cable for


the cabinet

Yellow and green

Specifications of the cable vary


depending on the installation mode of
cabinets.
l For stacked cabinets: 16mm2, M6
l For cabinets installed side-by-side:
25mm2, M6

5.5.4 Power Cables


This section describes the IBBS200T power cables and their connections.

Power Cable Connections in the IBBS200T


This section describes power cable connections in the IBBS200T.
Figure 5-18 shows the power cable connections in the IBBS200T.

5-24

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

5 IBBS200T Product Description

Figure 5-18 Power cable connections in the IBBS200T

(1) Power cable between the battery (2) Input power cable for the TEC (3) Input power cable for storage
group and the copper bar in the
batteries
junction box
(4) Power cable between the battery (5) Power transfer cable for the TEC group and the copper bar in the
junction box

Power Cables for Storage Batteries


This section describes input power cables for storage batteries, power cables between the battery
group and the copper bar in the junction box, and a copper bar for inter-battery series connection.

Exterior
Figure 5-19 shows input power cables for storage batteries.

Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

5-25

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

5 IBBS200T Product Description

Figure 5-19 Input power cables for storage batteries

(1) Power series 175 connector

(2) OT terminal (35 mm2, M8)

Figure 5-20 shows power cables between the battery group and the copper bar in the junction
box.
Figure 5-20 Power cables between the battery group and the copper bar in the junction box

(1) OT terminal (35 mm2, M8)

(2) OT terminal (35 mm2, M6)

NOTE

The M6 OT terminal is connected to the battery end, and the M8 OT terminal is connected to the power
distribution box (PDB) end.

Copper bars for inter-battery series connection are delivered with storage batteries. Figure
5-21 shows a copper bar for inter-battery series connection.
Figure 5-21 Copper bar for inter-battery series connection

5-26

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

5 IBBS200T Product Description

Specifications
l

The RTN(+) cable of input power cables for storage batteries is a red cable with a crosssectional area of 35 mm2, and the NEG(-) cable is a black cable with a cross-sectional area
of 35 mm2.

The RTN(+) cable of power cables between the battery group and the copper bar in the
junction box is a red cable with a cross-sectional area of 35 mm2, and the NEG(-) cable is
a black cable with a cross-sectional area of 35 mm2.

Power Cables for the TEC


The power cables for the thermoelectric cooling unit (TEC) are classified into input power cables
for the TEC and power transfer cables for the TEC.

Input Power Cable for the TEC


Figure 5-22 shows an input power cable for the TEC.
Figure 5-22 Input power cable for the TEC

(1) Easy power receptacle (pressfit type) connector

(2) OT terminal

Table 5-15 describes the specifications of the input power cable for the TEC.
Table 5-15 Specifications of the input power cable for the TEC
Cable

Wire

Wire Color in
Most Area

Wire Color in
Other Area

Cross-Sectional
Area of the Wire
and Aperture of
the OT Terminal

Input power
cable for the
TEC

RTN
(+)

Black

Blue

2.5 mm2, M4

NEG
(-)

Blue

Gray

Power Transfer Cable for the TEC


Figure 5-23 shows a power transfer cable for the TEC.
Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

5-27

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

5 IBBS200T Product Description

Figure 5-23 Power transfer cable for the TEC

(1) 3V3 power connector (2) OT terminal (1.5 mm2, (3) OT terminal (6 mm2,
M6)
M4)

(4) OT terminal (1.5 mm2,


M4)

Table 5-16 describes the specifications of the power transfer cable for the TEC.
Table 5-16 Specifications of the power transfer cable for the TEC
Cable

Wire

Wire Color in Most


Area

Wire Color in Other Area

Power transfer
cable for the TEC

W1

Blue

Gray

W2

Black

Blue

5.5.5 Signal Cables


This section describes the IBBS200T signal cables and their connections.

Signal Cable Connections in the IBBS200T


This section describes the signal cable connections in the IBBS200T.
Figure 5-24 shows the signal cable connections.

5-28

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

5 IBBS200T Product Description

Figure 5-24 Signal cable connections in the IBBS200T

(1) Monitoring signal cable for the battery (2) Monitoring signal cable for the door
cabinet
status sensor

(3) Signal for the ELU

Signal Cable for the ELU


The signal cable for the electronic labeling unit (ELU) is used to report the cabinet type
information collected by the ELU to the central monitoring unit type E (CMUE).

Exterior
Figure 5-25 shows the signal cable for the ELU.
Figure 5-25 Signal cable for the ELU

(1) RJ45 connector

Pin Assignment
Table 5-17 describes the pin assignment for the wires of the signal cable for the ELU.
Issue 04 (2011-07-08)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

5-29

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

5 IBBS200T Product Description

Table 5-17 Pin assignment for the wires of the signal cable for the ELU
X1 End

X2 End

Wire Color

Wire Type

X1.1

X2.1

White

Twisted pair

X1.2

X2.2

Orange

X1.3

X2.3

White

X1.6

X2.6

Green

X1.5

X2.5

White

X1.4

X2.4

Blue

X1.7

X2.7

White

X1.8

X2.8

Brown

Twisted pair

Twisted pair

Twisted pair

Monitoring Signal Cable for the Door Status Sensor


The monitoring signal cable for the door status sensor is used to inform the central monitoring
unit type E (CMUE) of the door status that is obtained from the door status sensor in the
TMC11H, radio frequency cabinet (RFC), IBBS200D, or IBBS200T.

Exterior
The monitoring signal cable for the door status sensor has two black bare wires, as shown in
Figure 5-26.
Figure 5-26 Monitoring signal cable for the door status sensor

Monitoring Signal Cable for the Storage Battery Cabinet


The monitoring signal cable for the storage battery cabinet collects and transmits the monitoring
signals of the IBBS200D or IBBS200T to the PMU.

Exterior
Figure 5-27 shows the monitoring signal cable for the storage battery cabinet.

5-30

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Issue 04 (2011-07-08)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.C)
Product Description

5 IBBS200T Product Description

Figure 5-27 Monitoring signal cable for the storage battery cabinet

(1) RJ45 connector

Pin Assignment
Table 5-18 describes the pin assignment for the wires of the monitoring signal cable for the
storage battery cabinet.
Table 5-18 Pin assignment for the wires of the monitoring signal cable for the storage battery
cabinet

Issue 04 (2011-07-08)

X1 End

X2 End

Wire Color

Type

X1.1

X2.1

White

Twisted pair

X1.2

X2.2

Orange

X1.3

X2.3

White

X1.6

X2.6

Green

X1.5

X2.5

White

X1.4

X2.4

Blue

X1.7

X2.7

White

X1.8

X2.8

Brown

Huawei Proprietary and Confidential