You are on page 1of 2

Indcon Projects & Equipment Limited

Block B-1, Plot G-1, Mohan Co-operative Industrial Estate, Mathura Road, New Delhi-44
Tel. : 26959570/45, 26991255-57, 41678710-12 Fax : (91)-11-26959603/41678714
E-mail : indcon@del3.vsnl.net.in Website : www.indconprojects.com
IPE/3218-3/ENQ.

05.09.2007
M/S. EX- PROTECTA
H.O: 305 & 306, GIDC, VITHAL
UDYOGNAGAR 388121, ANAND,
GUJRAT,INDIA
Phone No. : (+91) 2692 231430 / 237823 / 235995
e-mail: exprotecta@exprotecta.com
KIND ATTN.:- MANAGER SALES
Dear sir,
SUB.: ENQUIRY FOR SUPPLY OF FLAMEPROOF FITTINGS.
For one of our ongoing project with Indian Oil Corpn. Ltd., Noida, we require following flameproof fittings and
request you to kindly send us your lowest offer for supply of the same;
1.

FLAMEPROOF LIGHT DISTRIBUTION BOARDS, SUITABLE FOR LOCATION IN ZONE-I,


GAS GROUP IIA & IIB, T-3, IP-55, CAST ALUMINIUM LM-6, DULY CERTIFIED BY CCOE.
a.

FLP Lighting distribution board for pump shed with 63A 4 pole RCCB
of 100 mA sensitivity rating as incomer and Outgoing as
8 Nos. 6A DP MCBs, 1 Nos. 20 A 4 P MCB, 1 Nos. 16A 4P MCB.
: 01 No.

b.

FLP Emergency Lighting distribution board for pump shed with 32A
4 pole RCCB of 100 mA sensitivity, rating as incomer and Outgoing
4 Nos. 6A DP MCBs,

c.
2.

b.

6 way junction boxes with DIN rail mounted terminals, rating 10 Amps.
For cable connection of 6 Nos. separate SPN circuits.

= 5 Nos.

8 way junction boxes with DIN rail mounted terminals, rating 10 Amps.
For cable connection of 8 Nos. separate SPN circuits for lighting at
Building top

= 3 Nos.

FLAME PROOF POWER SOCKETS & PLUGS SUITABLE FOR LOCATION IN ZONE-I, GAS
GROUP IIA & IIB, T-3, IP-55, CAST ALUMINIUM LM-6, DULY CERTIFIED BY CCOE.
a.
b.

4.

FLP Power distribution board with 1no, 40A, 4 pole MCCB, as incomer
& 2 no 15 A 4 P and 2 no. 6A DP isolators as outgoing.
: 01 No.

FLAMEPROOF JUNCTION BOXES WITH SUITABLE CABLE GLANDS FOR LOCATION IN


ZONE-I, GASGROUP IIA & IIB, T-3, IP-55, CAST ALUMINIUM LM-6, DULY CERTIFIED BY
CCOE.
a.

3.

: 01 No.

3 ph, 440 V plug & socket (5pin) with 40A, 4 pole switch unit
250 V plug & socket (3 pin) with 15A DP switch unit

= 1 No.
= 1 No.

FLAMEPROOF START / STOP PUSH BUTTONS, WITH 3 POSITION SELECTOR SWITCH,


TWO NOS. PUSH BUTTONS, COMPLETE WITH SUITABLE CABLE GLANDS & ENTERY
PLUGS, COPPER PLUGS, LOCATION IN ZONE-I, GAS GROUP IIA & IIB, T-3, IP-55, CAST
ALUMINIUM LM-6, DULYCERTIFIED BY CCOE.

a.
5.

= 6 Nos.

FLAMEPROOF WELL GLASS / FLOOD LIGHT FITTINGS WITH TOUGHNED GLASS


AND MESS SUITABLE FOR HPMV LAMPS WITH SEPARATE CONTROL GEAR BOX,
COMPLETE WITH SUITABLE CABLE GLANDS & PLUGS, FOR LOCATION IN ZONE-I,
GAS GROUP IIA & IIB, T-3, IP-55, CAST ALUMINIUM LM-6, DULY CERTIFIED BY CCOE.
a.
b.

6.

Push button station suitable for 4Cx2.5sqmm Control cable, stop


push button stay put type with locking arrangements

250 Watt HPMV well glass light fitting with lamp, fixers and control gears
125 Watt HPMV flood light fittings, with fixers and control gear etc.

= 25 Nos.
= 12 Nos.

FLAME PROOF EMERGENCY LIGHTS SUITABLE FOR LOCATION IN ZONE-I, GAS


GROUP IIA & IIB, T-3, IP-55, CAST ALUMINIUM LM-6, DULY CERTIFIED BY CCOE.
a.

Emergency light with 18 W CFL Lamp., single phase 230 V UPS,Connection of


the fitting with 2C X 2.5sqmm FRLS Cable from DB.
= 3 Nos.

we hereby attach the relevant IOCL specifications for your reference.


Kindly submit your competitive offer for all of above items. Please ensure that your offer reaches us latest by 12 th
September2007.
Thanking you,
Yours faithfully,
For INDCON PROJECTS & EQUIPMENT LTD.

G.S.BISHT
G.M. CONTRACTS
Enclosed: as above.