Compact Controller for Stand-by and Parallel Operating Gen-sets

Inteli New Technology


Mains Supervision Controller
Mains Circuit Breaker and Master Generator Circuit Breaker
application SW configuration MCB, MGCB
IM-NT
Software version IM-NT-2.6, August 2010

Reference Guide

Copyright 2009 ComAp s.r.o.


ComAp, spol. s r.o.
Kundratka 2359/17, 180 00 Praha 8, Czech Republic
Tel: +420 246 012 111, Fax: +420 266 31 66 47
Technical support hotline: +420 246 012 666
E-mail: info@comap.cz, www.comap.cz

Table of Contents
Table of Contents ...............................................................................................................................................2
General guidelines..............................................................................................................................................3
What is described in this manual? .................................................................................................................3
General description ............................................................................................................................................5
Description of the controller system (with all options)....................................................................................5
Available related documentation ....................................................................................................................7
Functions ............................................................................................................................................................8
OFF-MAN-AUT mode ....................................................................................................................................8
Power management .....................................................................................................................................11
PLC functions ...............................................................................................................................................21
Multi language support.................................................................................................................................21
Protections and Alarm management ................................................................................................................22
Controller operation states ...............................................................................................................................25
Inputs and Outputs ...........................................................................................................................................26
Virtual and physical modules .......................................................................................................................26
Binary Inputs - Control .................................................................................................................................26
Binary inputs Status information ...............................................................................................................31
Binary outputs Breaker control..................................................................................................................32
Binary outputs Control loops .....................................................................................................................35
Binary outputs Status information .............................................................................................................35
Binary outputs Fixed protection outputs....................................................................................................37
Binary outputs Configurable prog. states..................................................................................................40
Binary outputs Default configurable protections .......................................................................................41
Binary outputs Power management..........................................................................................................41
Analog values...............................................................................................................................................43
Setpoints...........................................................................................................................................................44
ProcessControl.............................................................................................................................................44
Basic settings ...............................................................................................................................................51
Comms settings ...........................................................................................................................................54
ComProtSetting ............................................................................................................................................55
Analog protect ..............................................................................................................................................57
Mains protect................................................................................................................................................57
Bus protect ...................................................................................................................................................62
AMF settings ................................................................................................................................................63
Pwr management .........................................................................................................................................65
Sync/Load ctrl...............................................................................................................................................69
Volt/PF ctrl....................................................................................................................................................72
Force value...................................................................................................................................................73
Load shedding..............................................................................................................................................74
PLC settings .................................................................................................................................................75
Timer settings...............................................................................................................................................75
Act. calls/SMS ..............................................................................................................................................76
Date/Time.....................................................................................................................................................77
Controller configuration and monitoring ...........................................................................................................79
Direct connection to the PC .........................................................................................................................79
GenConfig functions.....................................................................................................................................79
InteliMonitor..................................................................................................................................................80
Modbus protocol...........................................................................................................................................80
Value and setpoint codes.............................................................................................................................80
Technical data ..............................................................................................................................................80

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

General guidelines
What is described in this manual?
This manual describes MCB and MGCB software configuration. The software configuration is designed
for multiple gen-sets operating in parallel to mains with control of mains circuit breaker or both mains circuit
breaker and master generator circuit breaker.
It is indicated where the applications MCB and MGCB differ.
What is the purpose of this manual?
This manual provides general information on how to configure the controller.
This manual is intended for use by:
Operators of gen-sets
Gen-set control panel builders
For everybody who is concerned with installation, operation and maintenance of the gen-set

!! Warnings !!
Remote control
The NT controller can be remotely controlled. In case that maintenance needs to be done, check the
following to effect safety.
Disconnect remote control via RS232 line
Disconnect input REMOTE START/STOP
The controller contains a large number of configurable setpoints, because of this it is impossible to describe
all of its functions. These are subject to change from SW version to SW version. This manual only describes
the product and is not guaranteed to be set for your application on arrival.

Text
PAGE
Break Return
Protections
REMOTE START/STOP

(Capital letters in the frame) buttons on the front panel


(Italic) set points
(Bold) Set point group
(Capital letters) binary inputs and outputs

Conformity declaration
Following described machine complies with the appropriate basic safety and health
requirement of the EC Low Voltage Directive No: 73/23 / EEC and EC
Electromagnetic Compatibility Directive 89/336 / EEC based on its design and type,
as brought into circulation by us.

Note:
ComAp believes that all information provided herein is correct and reliable and reserves the right to update
at any time. ComAp does not assume any responsibility for its use unless otherwise expressly undertaken.

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

WARNING VERY IMPORTANT !!!

Every time you want to disconnect following InteliMains controller


terminals:

Mains voltage measuring


and / or
Binary output for MCB control and / or
MCB feedback
Switch InteliMains to MAN mode.

!!! CAUTION !!!


Dangerous voltage
The terminals for voltage and current measurement should never be touched.
Properly connect the grounding terminals.
Do not disconnect the CT terminals for any reason.

Adjust setpoints
All setpoints are preadjusted to their typical values. But the set points in the Basic settings settings
group !!must!! be adjusted before the first startup of the controller.
!!! WRONG ADJUSTMENT OF BASIC PARAMETERS
CAN HARM THE EQUIPMENT !!!
The following instructions are for qualified personnel only. To avoid personal injury do
not perform any action not specified in this User guide !!!

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

General description
Description of the controller system (with all options)
IM-NT controller is comprehensive mains supervision controller for multiple generating sets operating in
parallel to the Mains. A modular construction allow upgrades to different levels of complexity in order to
provide the best solution for various customer applications.
NT Family controllers are equipped with a powerful graphic display showing icons, symbols and bar-graphs
for intuitive operation, which sets, together with high functionality, new standards in Gen-set controls.
The controller automatically connects the group of gen-sets to the Mains. It features mains failure detection
using integrated Mains protections, MCB and MGCB synchronizing, configuration level switches based on
Mains import or object consumption.
The key feature of the controller is its easy-to-use operation and installation. Predefined configurations for
typical applications are available as well as user-defined configurations for special applications.
Hint:
In versions below 2.6 the IM-NT controller does not accept an external bus supply (bus supply which is not
controlled by a ComAp controller).
Gensets have to be in AUTO mode to ensure proper MGCB function.

Features

Automatic gen-set start when the mains fails (BI Sys start/stop is closed)
MCB controlled by IM-NT
Break transfer on mains failure
MCB synchronizing after mains return
Pwr management (load dependent start and stop)
Sets priority can be defined manually or automatically based on running hours equalization or load
demand (most efficient combination)
Load sharing and VAR sharing
Gen-sets soft loading and unloading
Voltage matching
Reverse power protection
MGCB support

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

MCB
FEEDBACK

+24V
MCB
CLOSE / OPEN

IM-NT

SYS
START/STOP

3xUM

LOAD
3xIM

Ko2

CAN

3xUB

Ko1

REM
START/STOP

0V

CAN

MCB

3x

3x

GCB1

3x

G1
3xIG

3xU B

Ko1

3xUG

iG- AVRi
TRANS
CAN

iG-AVRi

MCB

AVRi

AVR

AVRi OUT

IG/IS-NT
Vout

SPEED
GOVERNOR

SYS START/STOP
MCB FEEDBACK

GCB2

3x

G2
3xIG

3xUG

3xUB

iG- AVRi
TRANS
CAN

iG- AVRi

AVR

AVRi OUT

AVRi

IG/IS-NT
SPEED
GOVERNOR

Vout

Ko2

SYS START/ STOP


MCB FEEDBACK

MCB

MGCB
CLOSE/ OPEN

IM-NT

SYS
START / STOP

3xUM

LOAD
3xIM

Ko3

MCB
CLOSE/ OPEN

3xUB

Ko1
Ko2

REM
START/STOP

MCB
FEEDBACK

+24V

MGCB
FEEDBACK

0V

CA N
CAN
3x

3x

GCB1

3xUB

+24V

G1

Ko1

3xIG

MGCB

3x

3xUG

MCB

CAN

IG-AVRi
TRANS

IG-AVRi

Ko2

MGCB

MCB

AVRi

AVR

AVRi OUT

IG/IS-NT
Vou t

SPEED
GOVERNOR

SYS START / STOP


MCB FEEDBACK
3x

3xIG

G2
3xUG

3xUB

GCB2

CAN

AVRi

IG-AVRi
TRANS
AVR
IG-AVRi
AVRi OUT

IG/IS-NT
Vout

Ko3

SPEED
GOVERNOR

SYS START/ STOP


MCB FEEDBACK

MCB MGCB

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

Available related documentation


PDF files
IGS-NT-2.4-Application guide.pdf
IGS-NT-2.4-Installation guide.pdf
IGS-NT Communication Guide 12-2009.pdf

Description
Application guide for IG/IS-NT and IM-NT
Installation guide for IG/IS-NT and IM-NT
Communication guide for IG/IS/IM-NT controllers

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

Functions
OFF-MAN-AUT mode
OFF mode
InteliMains NT has no influence at gen-set group.
If mains voltage is within limits and no mains alarm is active, MCB is closed after AMF settings:MCB close
del if AMF settings:MCB opens on = MAINS FAIL. If AMF settings:MCB opens on = GEN RUNNING, MCB
stays closed all the time, regardless of the mains condition.
MCB application - if the controller is switched to OFF mode while the gen-sets are running and there is
voltage on the bus, MCB is not closed before bus voltage disappears.
MGCB application if the controller is switched to OFF mode while the gen-sets are running and there is
voltage on the bus, MGCB is opened and after AMF settings:FwRet break MCB is closed (if there is Mains
voltage).
Binary output Sys start/stop is not active.

MAN mode
It is possible to close/open breakers manually under supervision of IM-NT controller which doesnt allow to
close simultaneously breakers without synchronizing (e.g. MCB and MGCB).
If the Mains fails, controller opens MCB if AMF settings:MCB opens on = MAINS FAIL. After the Mains
returns, MCB stays opened. Otherwise MCB is controlled manually by pressing MCB ON/OFF button or
closing MCBButton binary input.
MGCB application if the Mains fails, group of gen-sets is started and there is voltage on the bus, MGCB
can be closed anytime by pressing MGCB ON/OFF button.
Pressing of Start/Stop buttons closes/opens binary output Sys start/stop, i.e. cause start/stop of the gen-set
group.

AUT mode
Controller performs automatically sequences after Mains failure, closing/opening MCB and MGCB, Peak
shaving function, closing of Sys start/stop binary output.
MCB is opened according to setpoint AMF settings:MCB opens on after Mains failure or after the gen-sets
are running.
MGCB is closed after the start of gen-set group as soon as an appropriate load reserve is achieved (Syst res
OK binary output closed).
Controller reacts on binary input Rem start/stop if this input is closed, controller activates binary output Sys
start/stop in order to start gen-set group. In MGCB application MGCB can be closed before the output
activation (see also setpoint ProcessControl:MGCBparalClose).

TEST mode
MCB application
Test on load automatic start of the gen-sets (activation of binary output Sys start/stop), load takeover and
opening of MCB; if the Mains fails during test, load is transferred to the gen-sets
MGCB application
Engine Start Only start of the gen/sets and their synchronization on generator bus; after pressing MGCB
ON/OFF button, it is synchronized and load is transferred to gen-sets; after pressing MCB ON/OFF button
MCB is opened and MGCB stays closed, gen-sets running in Island
Test on load MGCB is closed, gen-sets synchronized to the bus, load transferred to gen-sets and MCB
opened
Return to Mains is influenced by setpoint AMF settings:ReturnTo mains:
DISABLED after the Mains return, load remains on the gen-sets
ENABLED after the Mains return, synchronizes MCB, transfers load to the Mains, MGCB opens and gensets keep running unloaded

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

Mains OK or Mains fail


Start is blocked

ON
ON
ON

Mains OK: possible paralel operation after gen-set controllers have synchronized;
MGCB application - only forward synchronization of MGCB (i.e. not if
ProcessControl:MGCBparalClose = NO);
MCB application after Mains fail opens MCB and stops gen-sets
Mains fail: Start is blocked
Mains OK: possible paralel operation after gen-set controllers have synchronized;
MGCB application both ProcessControl:MGCBparalClose = YES/NO possible
MCB application after Mains fail opens MCB and stops gen-sets
Mains fail: Start is blocked
Mains OK: possible paralel operation after gen-set controllers have synchronized;
MGCB application - only forward synchronization of MGCB (i.e. not if
ProcessControl:MGCBparalClose = NO);
MCB application after Mains fail opens MCB and stops gen-sets
Mains fail: Start is blocked
Mains OK: possible paralel operation after gen-set controllers have synchronized;
MGCB application both ProcessControl:MGCBparalClose = YES/NO possible
MCB application after Mains fail opens MCB and stops gen-sets
Mains fail: Start is blocked
Mains OK: Start is blocked
Mains fail: Starts and goes to Island operation (if ProcessControl:MFStart enable =
YES)
MCB application after Mains return opens Sys start/stop output and after last GCB
is opened waits AMF Settings:FwRet break to closing MCB (paralel operation is
not enabled)
MGCB application after Mains returns opens MGCB and Sys start/stop output and
waits AMF Settings:FwRet break efore closing MCB (paralel operation is not
enabled)
Mains OK: possible paralel operation after gen-set controllers have synchronized;
MGCB application - only forward synchronization of MGCB(i.e. not if
ProcessControl:MGCBparalClose = NO); if ProcessControl:Synchro enable is
ON then MGCBparalClose is not important
Mains fail: Starts and goes to Island operation (if ProcessControl:MFStart enable =
YES)
MCB application after Mains return opens Sys start/stop output and after last GCB
is opened waits AMF Settings:FwRet break to closing MCB (there is no way to get
in paralel operation)
MGCB application after Mains returns opens MGCB and Sys start/stop output and
waits AMF Settings:FwRet break before closing MCB (there is no way to get in
paralel operation)
Mains OK: possible paralel operation after gen-set controllers have synchronized;

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

SynchroEnable

RevSyncEnable

State description

ParallelEnable

IslandEnable

Overview of controller reactions in AUT mode when start command is issued (e.g. binary input Rem
start/stop is closed) with influence of some setpoints from ProcessControl group:

ON

ON

ON

ON

ON

ON

ON

ON

ON
ON
ON
ON

ON

ON
ON
ON

ON
ON

ON
ON

ON

ON

IM-NT-MCB-MGCB-2.6.PDF

ON

ON

ON

RevSyncEnable

SynchroEnable

MGCB application - only forward synchronization of MGCB(i.e. not if


ON
ProcessControl:MGCBparalClose = NO); if ProcessControl:Synchro enable is
ON then MGCBparalClose is not important
Mains fail: Starts and goes to Island operation (if ProcessControl:MFStart enable =
YES)
MCB application after Mains return synchronizes MCB; after MCB is closed opens
Sys start/stop output (which causes unloading of all gen-sets and their stop)
MGCB application after Mains returns MCB is synchronized and after it is closed
Sys start/stop is opened; after gen-set power falls under Sync/Load ctrl:MGCB
open leve (or Sync/Load ctrl:MGCB open del elapses) MGCB is opened

ParallelEnable

IslandEnable

State description

ON

ON

ON

Hint:
RevSynsEnable = ProcessControl:Synchro enable = REVERSE.
SynchroEnable = ProcessControl:Synchro enable = FORWARD/BOTH (MGCB application only).

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

10

Power management
Automatic gen-set start / stop function based on load changes and/or Running hours or Engine size.
Following functions are available:

Power management in kW
Guarantees adjustable load reserve (load step) in kW. Suitable for load demand-based optimization.
Activation: #Pwr mgmt mode = ABS (kW)

Power management in kVA

Gen3

Priority 3

#LdResStrt1

Priority 2

Gen2

#LdResStrt1

#LdResStp1

Gen1

#LdResStrt1
#LdResStp1

Priority 1

Actual power [ kW or kVA ]

Guarantees adjustable load reserve (load step) in kVA. Suitable for generator- or busbar dimensioningbased optimization.
Activation: #Pwr mgmt mode = ABS (kVA)

Time

#NextStrt del
Gen 3

Running

#NextStrt del
Gen 2

Running

#NextStp del
Unloading / Cooling

#NextStp del
Unloading / Cooling

Gen 1 = Running, Loaded


BO Syst res OK

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

11

Relative power management in %

Gen3

Priority 3

#%LdResStrt1
= 25%

#%LdResStrt1
= 25%

Priority 2

Gen2
Gen1

Priority 1

Actual power [ kW or kVA ]

Guarantees that the engines be not continuously loaded more than to a certain level, leaving less than
selected relative load reserve. Suitable for engine life-based optimization.
Activation: #Pwr mgmt mode = REL (%)

#%LdResStp1
=37%

#%LdResStrt1
= 25%

#%LdResStp1
=37%

Time

#NextStrt del
Gen 3

#NextStp del
Unloading / Cooling

Running

#NextStp del

#NextStrt del
Gen 2

Running

Unloading / Cooling

Gen 1 = Running, Loaded


BO Syst res OK

Start/Stop conditions in Power management


Reserve
Actual Reserve
Absolute
ARstrt = PgNom PgAct
kW / kVA ARstp = Pg*Nom PgAct
Relative
RRstrt = [(PgNom PgAct) / PgNom].100%
%
RRstp = [(Pg*Nom PgAct) / Pg*Nom].100%
Where
ARstrt
ARstp
RRstrt
RRstp
PgNom

Start condition
ARstrt < #LdResStrt

Stop condition
ARstp > #LdResStp

RRstrt < #%LdResStrt

RRstp > #%LdResStp

Actual Absolute reserve in kW or kVA - for engine start calculation.


Actual Absolute reserves in kW or kVA - for engine stop calculation.
Actual Relative reserve in % - for engine start calculation.
Actual Relative reserves in % - for engine stop calculation.
Sum of Nominal power of all gen-sets on the bus.

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

12

Pg*Nom Sum of Nominal power of all gen-sets on the bus apart of the one, which is going to be stopped.
Sum of Actual power of all gen-sets on the bus = system load.
PgAct
Hint:
Optional functions in absolute or relative Power management are:
- Running hours balancing (equalization),
- Load demand (different size) engines swap and
- Power management of two or more gen-set groups (bus tie support).

Running hours balancing


The gen-sets priorities are automatically swapped to balance engine running hours. Up to 32 controllers are
supported.
Activation: #PriorAutoSwap = RUN HOURS EQU
Important setpoints: RunHoursBase , #RunHrsMaxDiff

Different sized engines (Load demand) swap


Three running engines (priorities) are swapped based on load demand (one small engine runs on small
load and swaps to another one big engine that runs when load increases).
Activation: #PriorAutoSwap = LD DEMAND SWAP
Important setpoints: #PwrBandContr1, #PwrBandContr2, #PwrBandContr3, #PwrBandContr4,
#PwrBandChngDlUp, #PwrBandChngDlDn.

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

13

Pwr management of splitted group


Important setpoints: Control group, GroupLinkLeft, GroupLinkRight
When a Bus-tie disconnects the gen-set group the Power management can operate separately on each of
them.

Load shedding
All LOAD SHED outputs are activated (closed) to trip the unessential load when gen-set group goes to
island:
a) Before MGCB closes after mains fail and gen-set group is instructed to start in AUT mode (MGCB
application only).
b) Before first GCB closes after mains fail and gen-set group is instructed to start in AUT mode (MCB
application only).
c) When MCB opens from parallel to mains operation in AUT mode (transit to island parallel operation)
d) Before MCB is opened in MAN mode by button (transit to island parallel operation).
The load shedding function is active in all controller modes except OFF. Load shedding works based on
mains import value or the total gen-set group active power (setpoint LdShedBased on).
Load shedding has three steps and each step is linked with its own Load shed x binary output. There is only
one load shed level and delay for all three steps as well as recon level and delay. Load shed can only move
from one step to the next, e.g. No LoadShed to LdShed S1 to LdShed S2 to LdShed S3 and vice versa.
If manual reconnection of the load is desired, the AutoLd recon setpoint needs to be disabled (AutoLd recon
= DISABLED) and the MAN load recon binary input needs to be configured.
Rising edge on this input resets the controller to a lower stage, but only if the load is under the Ld recon level
at that moment.

Hint:
If no Load Shedding outputs are configured, there is no record to history and no scrren timer indication of the
activity of this function.

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

14

Mains import/Gen- sets power


Ld shed level

closed

BO LdShed stage 1
closed

BO LdShed stage 2
closed

BO LdShed stage 3

Ld shed
delay

Ld shed
delay

Ld shed
delay

Load reconnection automatic -> AutoLd recon = ENABLED

Mains import/Gen-sets power


Ld recon level

BO LdShed stage 1

opened

BO LdShed stage 2

opened

BO LdShed stage 3

opened

Ld recon
delay

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

Ld recon
delay

Ld recon
delay

IM-NT-MCB-MGCB-2.6.PDF

15

Load reconnection manual -> AutoLd recon = DISABLED

Mains import / Gen- sets power

Ld recon level

opened

BO L dShed stage 3

opened

BO L dShed stage 2

opened

BO L dShed stage1

BI ManLdRecon
no
action

Peak shaving

Actual power [ kW ]

The Peak shaving function is active only in AUTO mode. Peak shaving works on mains import value where
load consumption increased over defined level anad the gen-set group has to be started. Peak shaving
function has one common delay for activation/deactivation. Peak level start > stop level!

PeakLevelStart
PeakLevelStop

Time

Sys start/stop
PeakAutS/S del

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

PeakAutS/S del

IM-NT-MCB-MGCB-2.6.PDF

16

System load control modes


System load control modes are determined by setpoints ProcessControl:Mload ctrl PtM and SysLdCtrl PtM.

SYSBLD->LS
Following diagram shows the way of calculation of requested gen-set group power if ProcessControl:Mload
ctrl PtM = SYSBLD->LS.

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

17

ANEXSYSBLD->LS
Following diagram shows the way of calculation of requested gen-set group power if ProcessControl:Mload
ctrl PtM = ANEXSYSBLD->LS.

IMP/EXP
Following diagram shows the way of calculation of requested gen-set group power if ProcessControl:Mload
ctrl PtM = IMP/EXP.

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

18

ANEXT IMP/EXP
Following diagram shows the way of calculation of requested gen-set group power if ProcessControl:Mload
ctrl PtM = ANEXT IMP/EXP.

T BY PWR
Following diagram shows the way of calculation of requested gen-set group power if ProcessControl:Mload
ctrl PtM = T BY PWR.

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

19

System PF control modes


System PF control modes are determined by setpoints ProcessControl:MPF ctrl PtM and SysPFCtrl PtM.

PF IMP/EXP
Following diagram shows the way of calculation of requested gen-set group power if ProcessControl:MPF
ctrl PtM = PF IMP/EXP.

PF ANEXT IMP/EXP
Following diagram shows the way of calculation of requested gen-set group power if ProcessControl:MPF
ctrl PtM = PF ANEXT IMP/EXP.

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

20

PLC functions
Number of PLC functions is the same for IM-NT and IS-NT. See description in IGS-NT-Application guidex.y.pdf.

Multi language support


NT Family controllers support up to five Languages that is possible to switch during controller duty. Every
terminal (i.e. Remote display or PC-InteliMonitor) can be switched to different language. Use PC-GenConfig
- Translator tool to translate texts to another language.
Default application archives contain all texts in English only.

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

21

Protections and Alarm management


Protection groups
There are two groups of protections in the controller: fix and customer configurable.
Setpoint group
Analog protections
Configurable
Analog protect
Mains protections
Configurable
Mains protect
Fixed protections
Fix
Mains protect
Bus protect

Protection types
Level

Protection types

1
1
1

History record
Alarm only
Warning

Abbrevi
ation
Hst
Al
Wrn

Controller action

Record

none
none
none

History only
Alarmlist only
Alarmlist and
History
Alarmlist only
Alarmlist and
History
History only

1
1

AL indication
A+H indication

ALI
AHI

none
none

Mains protection

MP

Mains protection
with fault reset

MPR

Fail sensor

Fls

Controller opens MCB, no


fault reset needed after alarm
inactivation
Controller opens MCB, MCB
cannot be closed before
alarm inactivation and fault
reset
Can be indicated when
Analog input value is 6%
out of sensor characteristic
range. Fls can optionally
activate corresponding (e.g.
Sd) Analog input protection
as well.

Fault reset
needed
NO
YES
YES
NO
NO
NO

Alarmlist and
History

YES

Alarmlist and
History

Configurable

Default protections in MCB/MGCB applications


Fixed firmware based
Mains:
IDMT current
IDMT Active power

Protection

Corresponding setpoints

MPR
MPR

Vector shift
Mains voltage: Um1>, Um1<,
Um2>, Um2<, Um3>, Um3<
Mains frequency: fm<, fm>

MP

Mains protect: Mns2Inom prot;Mains2Inom del


Mains protect: Mns2POvrldProt; OverlStrtEval;
2POvrldStEvDel
Mains protect: VectorS prot; VectorS limit
Mains protect: Mains >V MP; Mains <V MP;
Mains V del
Mains protect: Mains >f; Mains <f; Mains f del

Bus:
Bus voltage
Bus frequency

Hst
Hst

Bus protect: Bus >V Hst; Bus <V Hst; Bus V del
Bus protect: Bus >f; Bus <f; Bus f del

Default - configurable:
Mains voltage unbalance
Mains current unbalance

MP
MP

Mains protect: Mains V unbal; Mains Vunb del


Mains protect: Mains I unbal; Mains Iunb del

MP
MP

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

22

Bus voltage unbalance


Batt <V, Batt >V

Hst
Wrn

Bus protect: Bus V unbal; Bus Vunb del


Analog protect: Batt >V; Batt <V; Batt volt del

Mains voltage and frequency protections - limits and indications


Basic settings:
VoltProtSelect = PHASE- NEUTRAL
Mains protect::
Mains >V MP
Mains <V MP
Mains V del
Mains >f
Mains <f
Mains f del

MP L1 under
MP L2 under
MP L3 under
MP L1 over
MP L2 over
MP L3 over
MP fm over
MP fm under

Basic settings:
VoltProtSelect = PHASE - PHASE
Mains protect::
Mains >V MP
Mains <V MP
Mains V del
Mains >f
Mains <f
Mains f del

MP L12 under
MP L23 under
MP L31 under
MP L12 over
MP L23 over
MP L31 over
MP fm over
MP fm under

Bus voltage and frequency protections - limits and indications


Basic settings
:
VoltProtSelect = PHASE- NEUTRAL
Bus protect::
Bus > V Hst
Bus < V Hst
Bus V del
Bus > f
Bus <f
Bus f del

Vb L 1 under
Vb L 2 under
Vb L 3 under
Vb L 1 over
Vb L 2 over
Vb L3 over
fbus over
fbus under

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

23

Basic settings
:
VoltProtSelect = PHASE- PHASE
Bus protect::
Bus > V Hst
Bus < V Hst
Bus V del
Bus > f
Bus <f
Bus f del

Vb L12 under
Vb L23 under
Vb L31 under
Vb L12 over
Vb L23 over
Vb L31 over
fbus over
fbus under

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

24

Controller operation states


Controller can operate in following states
MainsOper

MainsFlt
ValidFlt

IslOper

MainsRet

MCB off
Brks off
Synchro
RevSync

ParalOper

MCB application: MCB feedback is active, all GCB feedbacks are not active, Mains
parameters are within limits
MGCB application: MCB feedback is active, MGCB feedback is not active, Mains
parameters are within limits
MCB application: Mains parameters are not within limits
MGCB application: MGCB feedback is not active, Mains parameters are not within
limits
MCB application: Mains parameters are not within limits and AMF
settings:EmergStart del elapsed
MGCB application: MGCB feedback is not active, Mains parameters are not within
limits and AMF settings:EmergStart del elapsed
MCB application: MCB feedback is not active, at least one GCB feedback is active,
Mains parameters are not within limits
MGCB application: MCB feedback is not active, MGCB feedback is active, Mains
parameters are not within limits
MCB application: MCB feedback is not active, at least one GCB feedback is active,
Mains parameters are within limits
MGCB application: MCB feedback is not active, MGCB feedback is active, Mains
parameters are within limits
MCB application: MCB feedback is not active, all GCB feedbacks are not active
MGCB application: MCB and MGCB feedbacks are not active
MGCB application: MCB feedback is active, MGCB feedback is not active,
synchronization is allowed and started
MCB application: MCB feedback is not active, at least one GCB feedback is active,
reverse synchronization is allowed and started
MGCB application: MCB feedback is not active, MGCB feedback is active, reverse
synchronization is allowed and started
MCB application: MCB feedback is active, at least one GCB feedback is active
MGCB application: MCB and MGCB feedbacks are active

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

25

Inputs and Outputs


Virtual and physical modules

BIN

BOUT

AIN

AOUT

Number of I/O can be extended and project wiring can be reduced using the following extension and virtual
modules.

IM-NT controller
IGS-PTM
IS-AIN8
IS-BIN16/8
IGL-RA15
I-AOUT8

6
8
16
-

6
8
8
15
-

0
4
8
-

0
1
8

Controller I/O.
Standard I/O extension module.
Standard I/O extension module.
Standard I/O extension module.
15 Green, Red, Yellow LED panel.
8 Analog outputs

VPIO
SHBIN
SHBOUT
SHAIN
SHAOUT
PLC

8
8
x

8
8
x

4
x

4
x

Virtual periphery I/O module.


SHared (virtual) Binary INput module
SHared (virtual) Binary OUTput module
Shared (virtual) Analog Input module
Shared (virtual) Analog OUTput module
Programmable (internal) logic module.

Module name

Note

Hint:
For more details about Virtual peripherals (Shared and Internal virtual I/O periphery and PLC) see IGS-NTApplication guide-2.4.pdf.

Binary Inputs - Control


Rem start/stop
If the input closes (AUT mode only), the controller activates the binary output Sys start/stop in order to start
the gen-set group (to enable the start setpoint ProcessControl:ParallelEnable should not be set to NO). In
MGCB application, the MGCB can be closed before the output activation (see setpoint description
ProcessControl:MGCBparalClose).

AccessLock int
If the input is closed, no setpoints can be adjusted from the controller front panel.
Hint:
For IS-NT, this input is controlling the display #1, which is supposed to be attached to or close to the main
module.
As the controller mode (OFF-MAN-AUT-TEST) is one of the setpoints, not even that can be changed.
The START, STOP, FAULT RESET and other control buttons are disabled as well.

AccessLock D#2
If the input is closed, no setpoints can be adjusted and no commands can be issued from IG/IS-Display #2.
Hint:
It is not possible to start and stop the gen-set, change controller mode or control breaker.

AccessLock ext
If the input is closed, no setpoints can be adjusted and no commands can be issued from any external
terminal = via direct/modem/internet connection to the controller.
Hint:
IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

26

Use these inputs to lock out the selected terminals for setpoint changes and commands (statistic, password
and access code change). Such a terminal can only be used for monitoring.

Remote OFF
Active binary input forces the controller mode to OFF.
Hint:
Use this input to lock out the IM-NT control loops. The only active function (in MCB, MGCB applications) is
closing of the MCB if healthy mains voltage is sensed and there is no counter voltage on the gen-set side;
and vice versa, opening of the MCB if mains voltage fails (only if some other conditions are met).

Remote MAN
Active binary input forces the controller mode to MAN.

Remote AUT
Active binary input forces the controller mode to AUT.
Hint:
Use this input to switch the controller to automatic operation, e.g. using the external key switch.

Remote TEST
Active binary input forces the controller mode to TEST.
Hint:
Use this input for periodic gen-set group tests (in combination with Timer module). In this case the IM-NT
output Sys start/stop is activated, which on the other side should be connected to all gen-set controllers Sys
start/stop inputs to ensure their start for the test purposes.

Force block 1-3


Inputs for user-specific blocking of programmable protections. If the particular input is active, all the
protections with the corresponding Force block X block type are blocked.

Load res 2
Load res 3
Load res 4
If the input Load res X is closed, the setpoint set #LoadResStrt X + #LoadResStop X (#%LdResStrt X +
#%LdResStop X) will be selected. Higher index has higher priority when more these binary inputs are closed
together. When not configured or not active, setpoint set #LoadResStrt 1 + #LoadResStop 1(#%LdResStrt 1
+ #%LdResStop 1) is used.
Hint:
IM-NT uses these signals for display purposes only, i.e. for correct bargraph indication. Nevertheless, IM-NT
is a suitable controller to be the source of Load res X and MinRun power X signals for the rest of the system,
if a virtual periphery is used.
All controllers operating in Power management must have selected the same Load reserves.
It is possible to use Virtual periphery to share the signals between more controllers on the CAN bus. In this
case one controller is a server which physically has the signals connected and other controllers get these
signals via CAN bus.
Setpoint set selection depends on the #Pwr mgmt mode if set to ABS (kW or kVA), #LoadResStrt X type
setpoints are active, if set to REL (%), #%LdResStrt X type setpoints are active.

GroupLink
If this input is configured, the group linking function is active, i.e. this controller becomes the status server for
two groups of gen-sets and informs them about the BTB status.
If this input is closed, the controller reports BTB status as closed, if open, the controller reports open BTB
status.
Hint:
In MCB and MGCB application, this input is present from compatibility purposes only. It can report a BTB
status, however InteliMains will most likely not be the controller to control that breaker.
IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

27

In BTB application, on the other hand, this is one of the most important logical inputs, which should be
connected to the feedback of the controlled BTB. Knowing the state of its BTB, the controller can report this
state to all other gen-set controllers on the CAN bus in order to merge / split the logical CAN groups. See
also setpoints ControlGroup, GroupLinkLeft, GroupLinkRight.

Emerg. Manual
The controller behaves like when switched to OFF mode if this input is closed. Controller opens binary
outputs or stays inactive:
Binary outputs Power management (Sys start/stop, SysReady, Sys res OK, Sys res 1 OK, Sys res
2 OK, Sys res 3 OK, Sys res 4 OK),
Binary outputs Breaker control (MCB close/open, MCB ON coil, MCB OFF coil, MCB UV coil,
MGCB ON coil, MGCB OFF coil, MGCB UV coil, BTB close/open, BTB ON coil, BTB OFF coil, BTB
UV coil)
Binary outputs Fixed protection outputs (Horn, Alarm, Alarm flashing, Horn flashing, Common
Wrn, Common MPR, Common Fls, Common MP, Common Al, Common Hst, CommonActLev 1,(2),
CommonAlLev1,(2)).
The output terminals that are configured with inversion are closed. Voltage, current and power
measurement is active all the time, regardless of the actual state of the mains. It is possible to
influence breaker under IM-NT supervision without Wrn MCB fail or Wrn MGCB fail.
After the binary input EMERG. MANUAL is open again, the controller recovers to the previous mode
and behaves according to the actual situation. Function is active in any controller mode and
activation of this input is written to history.
Hint:
The function is intended especially for Marine gen-sets which are supposed to be started manually
while the controller has no power supply. To recover successfully from this state, only the signals
MCB ON/OFF coil should be used for mains and breaker control, as the other outputs are continuous
active during Mains operation and it is not possible to switch them between more control sources.
The full name of this function is emergency manual.
Be aware that all outputs related to PLC functions remain functional!

FaultResButton
Binary input has the same function as Fault reset button on the controller front panel.

HornResButton
Binary input has the same function as Horn reset button on the controller front panel.

StartButton
Binary input has the same function as START button on the controller front panel. It is active in MAN mode
only.

StopButton
Binary input has the same function as STOP button on the controller front panel. It is active in MAN mode
only.
Hint:
Start and Stop buttons (or inputs) in MAN mode toggle the gen-set group start command signal (BO Sys
start/stop) that is output from IM-NT.
Setpoint Basic settings: Local Button can influence button functionality.

MCBButton
Binary input has the same function as MCB button on the controller front panel. It is active in MAN and
TEST modes only. In TEST mode in some special cases only (see description TEST mode).

MGCBButton MGCB application only


Binary input has the same function as MGCB button on the controller front panel. It is active in MAN and
TEST modes only. In TEST mode in some special cases only (see description TEST mode).
IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

28

Hint:
All Binary inputs, which simulate controller front panel buttons, are edge (no level) sensitive, and they react
on the rising edge only.

ManualLdRecon
The rising edge on this input switches the controller to the lower Load Shedding stage when AutoLd recon =
DISABLED and the load is under Ld recon level.

Test on load
Affects the behavior in TEST mode. Before the activation of this function
1. adjust setpoint AMF settings: ReturnTo mains = DISABLED (MGCB application only)
2. adjust ProcessControl: MFStart enable = YES.
3. switch controller to Test on load mode (see drawing below)
Gen-set group starts and goes to load (in MGCB application, the MGCB is closed first; the gen-sets are
synchronized to the mains and close their GCBs) automatically when this input is closed even if Mains is OK.
Gen-set group stays running in parallel with mains during the soft load transfer from the mains to the gen-set
group until Import power = 0. When the load is bigger than the sum of Nominal power of all loaded gen-sets,
MCB stays closed, BO WrnTstOnLdFail is closed and warning message is issued (WrnTstOnLdFail).
MCB application:
When the controller is switched from Test on load mode (and Mains is OK), it synchronizes the MCB and
switches off the Sys start/stop output.
MGCB application:
When the controller is switched from Test on load mode (and Mains is OK), it synchronizes the MCB, stays
running in parallel for BreakerOverlap time (soft load transfer), opens MGCB and switches off the Sys
start/stop output.
During the load transfer from the gen-set group to the mains can the BreakerOverlap time be shortened due
to the influence of: Load ramp, MGCB open level, MGCB open del setpoints.

0V
batt

TestOnLoad

IM-NT

Remote TEST

AMF settings: ReturnTo


mains = DISABLED

Hint:
It is possible to configure both binary inputs (Remote TEST and Test on load) to only one controller physical
binary input internally.

MCB disable
The input blocks the MCB closing, even if all other conditions for its closing are fulfilled. Valid in all modes.

MGCB disable MGCB application only


The input blocks the MGCB closing, even if all other conditions for its closing are fulfilled. Valid in all modes.

Force sync MCB application only


The controller will react on this input only if it is in AUT ctrl (FOLLOW).
If the input is closed, controller will start to synchronize to the voltages measured at mains and bus terminals
(or BusLeft and BusRight for BTB application), regardless of the actual state of breaker feedbacks.
Hint:
The synchronization will start only if it is allowed by actual setting of Synchro enable.

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

29

Alt brightness
Active binary input switches controller display backlight to the alternative setting. Alternative intensity of the
backlight can be set independently using controller panel buttons.

ExtValue1 up
ExtValue2 up
ExtValue3 up
ExtValue4 up
Active binary input causes increasing of the corresponding ExtValueX value. The rate of change is given by
the setpoint ExtValueX rate. If the ExtValueX reaches the ExtValueXHiLim, the further input request is
ignored.

ExtValue1 down
ExtValue2 down
ExtValue3 down
ExtValue4 down
Active binary input causes decreasing of the corresponding ExtValueX value. The rate of change is given by
the setpoint ExtValueX rate. If the ExtValueX reaches the ExtValueXLoLim, the further input request is
ignored.
Hint:
If at least one of the inputs (ExtValueX up / ExtValueX down) is configured for the particular ExtValueX, the
external set commands to the same value are ignored.

ExtValue1reset
ExtValue2reset
ExtValue3reset
ExtValue4reset
Active binary input causes ExtValueX to be reset and held at its default value, given by the setpoint
ExtValueXdeflt.
Hint:
These inputs, if configured, do not block the external set commands (in contrast to ExtValueX up / ExtValueX
down inputs). However, if the reset input is activated, the corresponding ExtValueX is reset to its default
(ExtValueXdeflt) value. This default value is kept in ExtValueX until the reset input is deactivated, and the
external set commands received meanwhile are ignored.

PulseCounter 1
PulseCounter 2
PulseCounter 3
PulseCounter 4
The inputs are linked with corresponding counters, which integrate the pulses sensed at these inputs. Each
rising edge of the signal at input increases the internal counter value.
Hint:
Pulse width (both high/low levels) must be at least 100 ms in order to be correctly sensed!
Conversion ratio can be selected using the setpoints ConvCoefPulseX. The converted values are visible in
statistics values PulseCounter X. These values can be reset using Statistics window in InteliMonitor.
IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

30

IssueActCallC1
IssueActCallC2
IssueActCallC3
Rising edge on these binary inputs forces an active call to be issued via the corresponding channel.
Hint:
Can be used to send e.g. an SMS in the case of a special event, not covered with standard Active Calls.

Binary inputs Status information


MCB feedback
Mains Circuit Breaker positive feedback input (closed if MCB is closed). This is a primary source for the
controller about the status of the MCB.
Hint:
The controller decides based on this signal whether the gen-set group is running in mains parallel or in island
parallel operation. Obviously, in MGCB application this depends on the status of MGCB as well.

MCB fdb neg


Mains Circuit Breaker negative feedback input (closed if MCB is open). Additional signal, can be used if both
positive and negative feedback signals are available from the breaker.
Hint:
If both feedbacks are used and there is a mismatch between these signals, longer than 500 ms, a MCB fail
alarm is activated.

MGCB feedback MGCB application only


Master Generator Circuit Breaker positive feedback input (closed if MGCB is closed). This is a primary
source for the controller about the status of the MGCB.

MGCB fdb neg MGCB application only


Generator Circuit Breaker negative feedback input (closed if GCB is open). Additional signal, can be used if
both positive and negative feedback signals are available from the breaker.
Hint:
If both feedbacks are used and there is a mismatch between these signals, longer than 500 ms, a MGCB fail
alarm is activated.

ForceValueIn 1-16
If the particular input is active, the Force value function on that corresponding channel gets active, forcing an
alternative value to the selected setpoint.
Hint:
If ForceValue input is active then forced setpoint is marked with F on the controler screen and in
InteliMonitor is presented with violet color.

Timer block 1-16


Blocking inputs for particular timer module channels. The input can lock out its assigned channel if this
input is active, the channel wont activate its output (Timer active X) to e.g. start the engine.

Lang sel int A


Lang sel int B
Lang sel int C
Set of binary inputs for forcing alternative languages. This set of inputs is switching the controllers internal
terminal for IG-based controllers the front panel, for IS-based controllers the IS-Display with address #1.
IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

31

Encoding of binary inputs combinations:


Language index ->
given by display setting
1
2
3
4
5
6
7
Lang sel int A
0
1
0
1
0
1
0
1
Lang sel int B
0
0
1
1
0
0
1
1
Lang sel int C
0
0
0
0
1
1
1
1
Hint:
Warning each language change causes the restart of the respective display (not the whole controller), so
the displays control panel wont react until the restart has finished (~ 5s).
Value 0 in the table denotes that the corresponding input is not active or not configured.
If more than 7 languages are present in the controller, it is not possible to force languages with index higher
than 7 using these binary inputs.
The reaction on BI combination change is 1s delayed not to react on transient combinations if a rotary
selector switch is used.

Lang sel D#2 A


Lang sel D#2 B
Lang sel D#2 C
Set of binary inputs for forcing alternative languages. This set of inputs is switching the controllers external
terminal with address #2 for IG-based controllers the IG-Display, for IS-based controllers the IS-Display
with address #2.
Encoding of binary inputs combinations:
Language index ->
given by display setting
1
2
3
4
5
6
7
Lang sel D#2 A
0
1
0
1
0
1
0
1
Lang sel D#2 B
0
0
1
1
0
0
1
1
Lang sel D#2 C
0
0
0
0
1
1
1
1
Hint:
Warning each language change causes the restart of the respective display (not the whole controller), so
the displays control panel wont react until the restart has finished (~ 5s).
Value 0 in the table denotes that the corresponding input is not active or not configured.
If more than 7 languages are present in the controller, it is not possible to force languages with index higher
than 7 using these binary inputs.
The reaction on BI combination change is 1s delayed not to react on transient combinations if a rotary
selector switch is used.

CtrlHBeat sens
BI "CtrlHBeat sens" should be assigned to the output "CtrlHeartBeat" from the other controller. If input signal
does not correspond to right form (log 1 / log 0 - 500 ms / 500 ms; +/- 100 ms), BO: "CtrlHBeat FD" (Fail
Detect) is activated. This BO can be used for primary controller blocking (switching to Emerg. manual,
disconnecting BO, ...) and mainly for disconnecting of BI "Emerg. manual" of this (backup) controller. What
means that the backup controller assumes engine control.

Time stamp act


Binary input activates time stamp writing to history depending on Date/Time:Time stamp act and Time stamp
per setpoints.

Binary outputs Breaker control


MCB close/open
The output controls the mains circuit breaker. It is intended for contactors provides a continual active signal
if MCB should be closed.
Hint:
Use binary output inversion (in GenConfig during configuration) to achieve that closed output = breaker
opened. External relay logic can assure closed MCB in the case of controllers power supply loss.

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

32

MCB ON coil
The pulse output for MCB closing. If MCB synchronizing is enabled, the pulse length is 2s, if not, pulse
length is 5s.
Hint:
ON coil can only be closed if UV coil is already active for at least 1s.

MCB OFF coil


The pulse output for MCB opening. If MCB synchronizing is enabled, the pulse length is 2s, if not, pulse
length is 5s.

MCB UV coil
MCB undervoltage coil. Output is closed if mains values are within limits and MCB is ready to be closed. It is
opened if MCB should be open, and then closed again if mains electric values are in limits. If MCB
synchronizing is enabled, the opening pulse length is 2s, if not, pulse length is 5s.

MCB status
Intended for the indication of the MCB status. The information is based on MCB feedback and MCB fdb neg
signals except of situation of feedbacks mismatch.
Can be used for external indication of breaker status according to controllers information.

GCB disable MCB application only


This output can be used for MCB x GCBs interlock in the case of an MCB controlled from the 230 V. The
typical sequence after the mains fail, when GCB disable output is important, is shown below:
Mains fails, MCB cannot be opened as there is no voltage to open it (setpoint MCB opens on = GEN
RUNNING).
Output GCB disable is connected to inputs GCB disable in gen-set controllers to block their closing to a dead
bus with MCB still closed; virtual periphery can be used to distribute the GCB disable signal.
Output GCB disable gets active together with the Sys start/stop output (command from IM-NT to start the
gen-set group after the mains fail).
As soon as the gen-sets start, their voltage can be used to open the MCB; the GCB disable signal
deactivates (with a delay FwRet break after the MCB has been opened), enabling the GCB closing in genset controllers.

MGCBclose/open MGCB application only


The output controls the master generator circuit breaker. It is intended for contactors provides a continual
active signal if MGCB should be closed.

MGCB ON coil MGCB application only


The pulse output for MGCB closing. If MGCB synchronizing is enabled, the pulse length is 2s, if not, pulse
length is 5s.
Hint:
ON coil can only be closed if UV coil is already active for at least 1s.

MGCB OFF coil MGCB application only


The pulse output for MGCB opening. If MGCB synchronizing is enabled, the pulse length is 2s, if not, pulse
length is 5s.

MGCB UV coil MGCB application only


MGCB undervoltage coil. Output is closed if bus values are within limits (i.e. at least one GCB has been
closed) and MGCB is ready to be closed. It is opened if MGCB should be open, and then closed again if bus
electric values are in limits. If MGCB synchronizing is enabled, the opening pulse length is 2s, if not, pulse
length is 5s.

MGCB status MGCB application only


Intended for the indication of the MGCB status. The information is based on MGCB feedback and MGCB fdb
neg signals except of situation of feedbacks mismatch.
IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

33

Can be used for external indication of breaker status according to controllers information.

LdShed stage 1
LdShed stage 2
LdShed stage 3
Outputs for Load shedding. See description below:

Mains import/ Gen- sets power


Ld shed level

closed

BO LdShed stage 1
closed

BO LdShed stage 2
closed

BO LdShed stage 3

Ld shed
delay

Ld shed
delay

Ld shed
delay

Load reconnection automatic -> AutoLd recon = ENABLED

Mains import/Gen-sets power


Ld recon level

BO LdShed stage 1

opened

BO LdShed stage 2

opened

BO LdShed stage 3

opened

Ld recon
delay

Ld recon
delay

Ld recon
delay

Load reconnection manual -> AutoLd recon = DISABLED


Hint:
If no Load Shedding outputs are configured, there is no record to history and no scrren timer indication of the
activity of this function.

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

34

Mains import/Gen-sets power

Ld recon level

opened

BO LdShed stage 3

opened

BO LdShed stage 2

opened

BO LdShed stage 1

BI Man load recon


no
action

Binary outputs Control loops


RemoteControl1-8
These outputs are controlled remotely from InteliMonitor or other tool. The user selects the requested state
of these outputs via the buttons in this program.
Hint:
Outputs can be used to switch on/off some auxiliary devices in the control panel.

Binary outputs Status information


Ready for load MGCB application only
The output closes when the gen-set group is running (Sys start/stop is active) and output SystReady is
active (i.e. sufficient number of gen-sets in Power management is available).
The MGCB is already closed or is able to be closed.

ForwardSynchro MGCB application only


The output is closed during forward synchronizing and opens when MGCB status gets active (= MGCB was
closed). The output can be used for external synchronizing module control.

ReverseSynchro
The output is closed during reverse synchronizing (gen-set group with load) and opens when MCB status
gets active (= MCB was closed). The output can be used for external synchronizing module control.

Off mode
Man mode
Aut mode
Test mode
These outputs follow the actual controller mode.

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

35

MainsParams OK
The output is copy of mains status LED on controller front panel. The output is closed if mains electric values
are in limits.

Bus params OK
The output is copy of bus status LED on controller front panel. The output is closed if bus electric values are
in limits.

GSG params OK
The output is closed if bus electric values are in limits and there is a sufficient number of loaded gen-sets not
having 2nd level alarm active (when only 1st level alarm is active, the output is closed).
Hint:
Sufficient number = actual load < total nominal power of all loaded gen-sets not having 2nd level alarm active.
The output is deactivated if one of the loaded gen-sets starts to softly unload because it is having some
problems (Stp or BOC protection active), and there is no sufficient nominal power left on the bus. The output
is not deactivated during the waiting stage of the Stp protection (i.e. waiting for another gen-set to start and
replace the failing one).

In synchronism
The output closes during synchronizing if all matching conditions are fulfilled. It opens if corresponding
breaker is closed (xCB status output get active).
Hint:
Synchronizing matching conditions:
- Slip frequency < 0,25 Hz
- Bus to Mains voltage phase shift within Phase window (BusLeft and BusRight in the case of BTB
application)
- Bus and Mains voltages within Voltage window (BusLeft and BusRight in the case of BTB
application)
- Dwell time elapsed

StartButnEcho
Start button echo reflects START button pressing from the panel, binary input or remote command is issued
(from PC software, SMS, ...). Output is active for 1s.

StopButnEcho
Stop button echo reflects STOP button pressing from the the panel, binary input or remote command is
issued (from PC software, SMS, ...). Output is active for 1s.

FltResButnEcho
Fault Reset button echo reflects FAULT Reset button pressing from the panel, binary input or remote
command is issued (from PC software, SMS, ...). Output is active for 1s.

HrnResButnEcho
Horn Reset Button echo reflects HORN button pressing from the the panel, binary input or remote command
is issued (from PC software, SMS, ...). Output is active for 1s.

MCBButnEcho
MCB button echo reflects MCB button pressing from the the panel, binary input or remote command is
issued (from PC software, SMS, ...). Output is active for 1s.

MGCBButnEcho MGCB application only


MGCB button echo reflects MGCB button pressing from the the panel, binary input or remote command is
issued (from PC software, SMS, ...). Output is active for 1s.

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

36

CtrlHeartBeat
The output signalizes watchdog reset. In a healthy state it flashes at 500ms : 500ms rate. When the unit
reset occurs and the new start-up fails, it stops flashing.

CtrlHBeat FD
Output activates if signal on binary input CtrlHBeat sens does not correspond to the right form (log 1 / log 0 500 ms / 500 ms; +/- 100 ms) which indicates fault (watchdog) of the other controller. This output can be
used for primary controller blocking (switching to Emerg. manual, disconnecting BO, ...) and mainly for
disconnecting of BI "Emerg. manual" of this controller. What means that the backup controller assumes
engine control.

Logical 0
Constant value that can be configured to any output.

Logical 1
Constant value that can be configured to any output.

Reserved
These outputs are reserved for internal states. It is not recommended to use it in any configuration.

TimerAct 1-4
TimerAct 5-8
TimerAct 9-12
TimerAct 13-16
These outputs are active if at least one of their assigned timer module channels gets active. Timer module
channels are organized into groups of four.

TimerActiveCom
This output is a logical OR (Com = Common) of the outputs TimerAct 1-4, 5-8, 9-12, 13-16. It gets active if
any timer module channel is active.

EnginesSwapped
The output generates 100 ms pulse in case two gen-sets exchange their priorities due to diference between
Maximal running hours and Minimal running hours value (active when Pwr management:#PriorAutoSwap
set to RUN HOURS EQU).

Binary outputs Fixed protection outputs


Alarm
The output closes if any alarm comes up. It opens if FAULT RESET is pressed. The output closes again if a
new fault comes up.

Alarm flashing
If any alarm comes up, the output starts periodic closing/opening with period 1s/1s. It opens and stays open
if FAULT RESET is pressed.

Horn
The output closes if any alarm comes up. It opens if FAULT RESET or HORN RESET is pressed or if Horn
timeout has elapsed. The output closes again if a new fault comes up.

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

37

Horn flashing
If any alarm comes up, the output starts periodic closing/opening with period 1s/1s. It opens and stays open
if FAULT RESET or HORN RESET is pressed or if Horn timeout has elapsed.

Common Hst
The output closes if any History record-type alarm appears. The output opens after 1s.

Common Al
The output closes if any Alarm only-type alarm appears. The output opens, if no Alarm only-type alarm is
active and FAULT RESET has been pressed.

Common Wrn
The output closes if any Warning-type alarm appears. The output opens, if no Warning-type alarm is
active and FAULT RESET has been pressed.

Common MP
The output closes if any Mains protection-type alarm appears. The output opens, if no Mains protectiontype alarm is active. No FAULT RESET needed.

Common MPR
The output closes if any Mains protection with fault Reset-type alarm appears. The output opens, if no
Mains protection with fault Reset-type alarm is active and FAULT RESET has been pressed.

CommonActLev 1
The output is a logical OR of Common Al and Common Wrn outputs.

CommonAlLev 1
The output is active if at least one of the 1st level alarms (Al, Wrn) is active or not yet confirmed.
Hint:
See picture below with signal behaviour description. The same behaviour like for Warning-type alarm would
be for Alarm only.
The same behaviour, but with signals CommonActLev 2 and CommonAlLev 2 would be for Mains
protection and Mains protection with fault Reset-type alarms (in MCB and MGCB applications).
For BTB application, the signals CommonActLev 2 and CommonAlLev 2 are driven by Breaker Open and
Breaker Open with fault Reset protections.

Alarm activity (Wrn)


BO: CommonActLev 1

Fault reset
Alarm activity ended
before the reset.

BO: CommonAlLev 1
BO: Alarm

Alarm activity (Wrn)


BO: CommonActLev 1
BO: CommonAlLev 1
IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,
BO: Alarm

Fault reset
Alarm activity ended
after the reset.

IM-NT-MCB-MGCB-2.6.PDF

38

CommonActLev 2
The output is a logical OR of Common MP and Common MPR (MCB and MGCB applications).
The output is a logical OR of Common BOp and Common BOR (BTB application).

CommonAlLev 2
The output is active if at least one of the 2nd level alarms (MP, MPR / BOp, BOR) is active or not yet
confirmed.

Common Fls
The output closes if any Fail sensor-type alarm appears. The output opens, if no Fail sensor-type alarm is
active and FAULT RESET has been pressed.

Vmains <>
The output closes if the mains over/under voltage is detected.

Vbus <>
The output closes if the bus over/under voltage is detected.

fmains <>
The output closes if the mains over/under frequency is detected.

fbus <>
The output closes if the bus over/under frequency is detected.

Mains OK
The output is closed if healthy mains voltage is present. It opens immediately if mains voltage or frequency
gets out of the limits.

Bus OK
The output is closed if healthy bus voltage is present. It opens immediately if bus voltage or frequency gets
out of the limits.

Mains fail
The output is open if healthy mains voltage is present. It closes with a delay given by mains protections if
mains voltage or frequency gets out of the limits.

Bus fail
The output is open if healthy bus voltage is present. It closes with a delay given by bus protections if bus
voltage or frequency gets out of the limits.

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

39

Mains/Bus OK
faulty

Mains/Bus OK

Mains/Bus fail
Mains V del or
Mains f del or
Bus V del or
Bus f del

VectorShiftTrp
The output closes if the Vector shift protection gets active and the controller actually trips the selected
breaker. The output stays closed for 3s, then opens again.

MPR ImainsIDMT
The output closes if the mains IDMT Overcurrent alarm activates. The output opens, if the alarm is no more
active and FAULT RESET has been pressed.

MPR PmainsIDMT
The output closes if the mains IDMT Overload alarm activates. The output opens, if the alarm is no more
active and FAULT RESET has been pressed.

PeriphCommErr
Output closes if there is an error in the communication with any peripheral unit (e.g. IS-AIN8, IGS-PTM, ...).

CAN2 bus empty


Closes if the detection of empty CAN2 bus is active (setpoint CAN2emptDetect) and there are no other
controllers sensed on this bus.

Binary outputs Configurable prog. states


MCB fail
Output closes when MCB fail is detected.

MGCB fail MGCB application only


Output closes when MGCB fail is detected.

Sync timeout MGCB application only


The output is closed when the alarm Sync timeout is active.

RevSyncTimeout
The output is closed when the alarm RevSyncTimeout is active and Wrn Rsync fail is presented.

WrnTstOnLdFail
If Test on load function is activated (by closing corresponding BI), and there is not enough power to transfer
all the load from mains to generators, the output closes after the Load ramp delay elapses. Together with
that, the message WrnTstOnLdFail appears in Alarm list.
IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

40

UnivState 1 Univ state 15


Universal state 1 to Universal state 15 activity indication.

Binary outputs Default configurable protections


Batt volt <>
The output closes if battery over/under voltage alarm appears.

Binary outputs Power management


Sys start/stop
The output serves for easy interfacing with IG/IS-NT controllers. It can be directly connected to their Sys
start/stop inputs which serve to control a group of gen-sets.
The signal can get active:
a) If binary input Rem start/stop gets active (AUT mode only).
b) If AMF condition is sensed in IM-NT and the gen-set group should be started as stand-by power
source (AUT mode only).
c) If PeakShaving function senses that it is suitable to start the gen-set group in order to lower the
mains import (AUT mode only).
d) If Start button is pressed on IM-NT front panel or remotely (MAN mode only). The signal can be
deactivated by pressing the Stop button. If the controller is switched from AUT to MAN mode, the
internal status of the flip-flop circuit created by Start-Stop buttons is set to follow the previous state in
AUT mode. E.g. if the gen-set group has run in an AMF situation in AUT mode, switching to MAN will
not stop it (= Sys start/stop output stays active).
The signal can get inactive:
a) If binary inpu Rem start/stop gets inactive (AUT mode only)
b) If mains is recovered and after MCB is clossed (synchro enable). If Synchro enable = none than Sys
start/stop signal gets inactive after mains is recovered.
c) If required power is under PeakLevelStop during PeakAutS/S del Sys start/stop gets inactive.
d) If STOP button is pressed on IM-NT front panel or remotely (MAN mode only). Sys start/stop button
stayed in the previous state despite of mode changing.
Hint:
For MGCB application - in a) and c) cases, before the output Sys start/stop is activated, the MGCB close
command is issued. This makes it easier to bring the gen-sets to the mains-parallel operation.
If MGCB should stay open until all required gen-sets are synchronized on the generator bus (without load),
adjust the setpoint MGCBparalClose to NO.

SystReady
The output is closed when the system is able to reach (not reached !) requested power reserve.

Syst res OK
The output closes when selected system load reserve is achieved within the gen-set group.
PBNom > PAkt + Reserve
PBNom
PAkt
Reserve

Sum of the nominal power of all gen-sets in the gen-set logical group
System load
selected setpoint #LoadResStrt X

In relative mode, actual relative load reserve of the gen-sets is calculated and compared with required
relative load reserve (#%LdResStrt X).

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

41

Syst res 1 OK
Syst res 2 OK
Syst res 3 OK
Syst res 4 OK
The corresponding output X is closed when Pwr management: #LoadResStrt X (or #%LdResStrt X in
relative mode) is achieved, independent to which #LoadResStrt X (or #%LdResStrt X) reserve is selected.

AllAvailGS run
The output gets closed if all gen-sets available to take part in PMS are running and loaded. All gen-sets
having the same logical group (Pwr management: Control group) as this controller has are considered +
gen-sets from other logical groups if those are currently linked with controllers logical group (using
GroupLink feature).

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

42

Analog values
Value
EnginePriority

Description
Actual engine priority

Act Reserve

Actual load reserve

LoadRes start

Load reserve for start

LoadRes stop
ActRes rel
ResStart rel
ResStp rel

Load reserve for stop


Actual relative load reserve
Load reserve for start
Load reserve for stop

Dimension
kX = kW or
kVA
kX = kW or
kVA
kX = kW or
kVA
%
%
%

TotRunPact
Sum of active power
TotRunPnomAll Sum of nominal power of all loaded gen-sets
Sum of nominal power of all gen-sets available for power
TotAvlbPnom
management
TotRunPnom
Sum of nominal power of loaded gen-sets in power management

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

kW
kW
kW
kW

IM-NT-MCB-MGCB-2.6.PDF

43

Setpoints
Password protection
Any setpoint can be password protected - 7 levels of password is available. The password is a four-digit
number. Only setpoints associated with the entered password level can be modified.
Even though one level may have been set from the front panel, the affected setpoints are not
accessible from InteliMonitor (direct or Modem) until this level is set in IMON.
Setpoints opened from front panel are automatically closed 15 minutes after the last key has been
pressed or when wrong value of password is set.
Any password can be changed once that level password or higher has been entered. The controller
programming (configuration) requires the highest - password 7 level.

ProcessControl
#SysBaseLoad

[ kW ]

From this value, the requested gen-set load is calculated, according to the number of gen-sets running (to
split the load among them based on their nominal power). The complete system produces the power equal to
this value. Active only when SysLdCtrl PtM = BASELOAD.
Step:
1 kW
Range:
0 65000 kW
Hint:
Setpoints starting with # are shared among all the controllers on the CAN2 bus, so changing the value in
one controller causes its change in all controllers. These setpoints are mainly present in IM-NT from
compatibility purposes only and have no meaning. Others have different meaning than in IG/IS-NT
controllers.
If you set this setpoint to a higher value than the system is able to produce, the total produced power is
limited with the sum of Nomin power setpoints of all gen-sets in the system.
The same holds for the lower limit - the gen-set power is limited to Generator protect: Min power PtM, and
IM-NT cannot force the gen-set to go under this limit, even if set in #SysBaseLoad setpoint.

#SysPwrFactor

[ ]

Requested gen-set power factor when #SysPFCtrl PtM = BASEPF. Values 0,60 0,99 correspond to lagging
(inductive, L) PF, 1,01 1,20 correspond to leading (capacitive, C) PF.
Step:
0,01
Range:
0,60 - 1,20
Hint:
Active PF control loop in IG/IS-NT controllers only, not in IM-NT.

#SysLdCtrl PtM
BASELOAD

LDSHARING

[ BASELOAD / LDSHARING ]

The gen-set is a part of the System delivered power control (#SysBaseLoad) and produces
a certain part of it, according to the actual number of running gen-sets and self Nomin
power. This option is only active in parallel with mains, in island parallel operation the mode
is always internally set to LDSHARING.
The gen-set load is shared with other gen-sets according to the actual load. For IM-NT, this
means it is able to influence

Hint:
BASE LOAD mode means that IM-NT speed/power control loops are switched off and only the control loops
in IG/IS-NT controllers are active.

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

44

#SysPFCtrl PtM
BASEPF

[ BASEPF / VSHARING ]

The gen-set power factor is controlled to a preadjusted level Process control:


#SysPwrFactor. This option is only active in parallel with mains, in island parallel operation
the mode is always internally set to VSHARING.
The power factor is equalized with other gen-sets according to the actual reactive load.

VSHARING
Hint:
BASE PF mode means that IM-NT voltage/power factor control loops are switched off and only the control
loops in IG/IS-NT controllers are active.

Import load

[ kW ]

Requested power from / to mains when MLoad ctrl PtM = IMP/EXP or when Export limitation function is
active i.e. Export limit = ENABLED.
Step:
1 kW
Range:
-32000kW to +32000 kW

Import PF

[ ]

Requested power factor on the mains side when MPF ctrl PtM = IMP/EXP. Value bigger than 1.00 means
capacitive PF (leading) load character.
Step:
0.01
Range:
0.60 to 1.20

MLoad ctrl PtM

[ SYSBLD->LS / ANEXSYSBLD->LS / IMP/EXP / ANEXT


IMP/EXP / T BY PWR ]
(FV)

MLoad ctrl PtM selects control mode for parallel to mains operation. Any of modes listed below requires the
setpoint #SysLdCtrl PtM = LDSHARING.
SYSBLD->LS:
Gen-set group is loaded at preadjusted level given by ProcessControl:
#SysBaseLoad, but controlled via IM-NT power control loop and subsequently Load
Sharing line. This enables the Export limit function to be used in IM-NT.
ANEXSYSBLD->LS: Gen-set group is loaded according to the requested value given by an external device
via Analog input MLC:AnExSysBld (configured in IM-NT). This enables IM-NT to
control the gen-sets via the Load Sharing line. Optionally, Export limit function can be
used.
IMP/EXP:
Gen-set group is loaded according to imported/exported power from/to mains to
achieve ProcessControl: Import load. However, in some cases the requested value
would bring the gen-sets to overload or reverse power, so their requested power
would be limited and consequently Import load not matched.
ANEXT IMP/EXP:
Gen-set group is loaded according to imported/exported power from/to mains to
achieve the requested value given by an external device via Analog input
MLC:AnExI/E. However, in some cases the requested value would bring the gen-sets
to overload or reverse power, so their requested power would be limited and
consequently the value given by the analog input not matched.
T BY PWR:
Gen-set group power is changed to keep required temperature, measured via an
analog input (configured in IM-NT). Optionally, Export limit function can be used.

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

45

Soft Unload

[ STANDARD / AuxCTGen / AuxCTLoad ]

This setpoint defines the way of evaluation of unloaded state for MGCB opening. It is useful especially for
multimains systems where a group of gensets supplies more loads:
STANDARD: The MGCB is opened at the moment when TotRunPact value is lower than MGCB open lev
or after MGCB open del elapsed. In multimains systems this can lead to the situation when
loads are supplied from one Mains incomer while the gensets are unloaded and at the
moment when corresponding MGCB is opened the gensets receive jump load from other
loads. To avoid this situation there are two other modes of operation.
AuxCTGen:
Auxiliary current measurement (AUX CURRENT terminal) can be used to measure actual
current through MGCB to enable to regulate the incoming power from the Mains and from
the gensets in the way that gensets stop supplying respective load but continue supplying
other load in the system. The CT is expected to be placed between MGCB and bus. The
MGCB is opened when the power over MGCB counted from this auxiliary current and
voltage is lower than MGCB open lev or after MGCB open del elapsed.

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

46

AuxCTLoad:

Auxiliary current measurement (AUX CURRENT terminal) can be used to measure actual
current to the load to enable to regulate the incoming power from the Mains and from the
gensets in the way that gensets stop supplying respective load but continue supplying other
load in the system. The CT is expected to be placed on load connection. The MGCB is
opened when the power to the load counted from this auxiliary current and voltage is lower
than Mains import power plus MGCB open lev or after MGCB open del elapsed.

MPF ctrl PtM

[ IMP/EXP / ANEXT IMP/EXP ]

(FV)

MPF ctrl PtM selects control mode of power factor for parallel to mains operation. Any of modes listed below
requires the setpoint #SysPFCtrl PtM = VSHARING.
IMP/EXP:
Gen-set group power factor is controlled according to imported/exported power factor
at the mains side to achieve ProcessControl: Import PF. However, in some cases
the requested value would bring the gen-sets out of the range 0.6L 0.8C, so their
requested power factor would be limited and consequently Import PF not matched.
ANEXT IMP/EXP:
Gen-set group power factor is controlled according to imported/exported power factor
at the mains side to achieve the requested value given by an external device via
Analog input MPF:AnExI/E. However, in some cases the requested value would bring
the gen-sets out of the range 0.6L 0.8C, so their requested power factor would be
limited and consequently the value given by the analog input not matched.

I/E-Pm meas

[ NONE / CT INPUTS / ANALOG INPUT ]

Import / Export measurement selection when one of power I/E modes selected.
NONE:
No source for I/E active power measurement available. If selected (and setpoint
#SysLdCtrl PtM = LDSHARING), power control defaults to SysBaseLoad via LS.
IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

47

CT INPUTS:
ANALOG INPUT:

I/E-Qm meas

Mains I/E active power (Pm) is measured and calculated from controllers current
terminals.
Mains I/E active power is measured by an external device and the controller measures
this value via analog input MLC:I/E-Pm. In the case of a sensor fail at that analog
input, this setpoint is internally re-adjusted to NONE position.

[ NONE / CT INPUTS / ANALOG INPUT ]

Import / Export measurement selection when one of PF I/E modes selected.


NONE:
No source for I/E reactive power measurement available. If selected (and setpoint
#SysPFCtrl PtM = VSHARING), power factor control in IM-NT is internally switched to
keep the gen-set group at #SysPwrFactor value. This is to suppress uncontrolled
drifting of the gen-set group in parallel to the mains operation.
CT INPUTS:
Mains I/E reactive power (Qm) is measured and calculated from controllers current
terminals.
ANALOG INPUT:
Mains I/E reactive power is measured by an external device and the controller
measures this value via analog input MPF:I/E-Qm. In the case of a sensor fail at that
analog input, this setpoint is internally re-adjusted to NONE position.
Hint:
Setpoints I/E-Pm meas and I/E-Qm meas are internally interlocked. That means if at least one of them is set
to CT INPUTS, both Pm and Qm are measured using controllers CT inputs, regardless of the setting of the
other setpoint.
In other words, either CT INPUTS option is active for both measurements, or these combinations are
allowed: NONE+NONE, ANALOG INPUT+NONE, NONE+ANALOG INPUT, ANALOG INPUT+ANALOG
INPUT.

PeakLevelStart

[ kW ]

(FV)

Load consumption level the gen-set group has to start at. Function is active only for PeakAutS/S del <> OFF.
Gen-set start command is PeakAutS/S del delayed after the consumption of the Load exceeds the
PeakLevelStart limit.
Step:
1 kW
Range:
PeakLevelStop to 32000 kW
Hint:
The Peak start/stop function activates the common output signal Sys start/stop in IM-NT. The signal is
intended to be directly connected to Sys start/stop inputs of all gen-set controllers in the system, e.g. using
SHBIN/SHBOUT peripherals.
Example how it could be used is on page 14.

PeakLevelStop

[ kW ]

(FV)

Load consumption level the gen-set group has to stop at. Gen-set stop command is PeakAutS/Sdel delayed
after PeakLevelStop limit is reached. Load consumption is calculated (not directly measured) as a sum of all
gen-sets (Act power) and mains (P mains) active power.
Step:
1 kW
Range:
0 to PeakLevelStart kW

PeakAutS/S del

[s]

(FV)

Delay for automatic Peak start/stop function. Set to OFF to disable Peak aut start function.
Step:
1s
Range:
OFF, 1 3200 s

Export limit

[ DISABLED / ENABLED ]

(FV)

Protection against power export to the mains. The function limits gen-set group requested power to hold
import power higher or equal to the setpoint Import Load.
Hint:
This function can be used in MLoad ctrl PtM = SYSBLD->LS / ANEXSYSBLD->LS / T BY PWR modes only.

TempByPwr Treq

[ C ]

(FV)

Requested temperature value for temperature control by generator power.


Before use, you have to configure the analog input MLC:TByPwr.
IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

48

Step:
Range:

1 C
32000 C

TempByPwr gain

[%]

Gain factor for Temperature by generator power control loop.


Step:
0,01 %
Range:
0,00 100,0 %

TempByPwr int

[%]

Integration factor for Temperature by generator power control loop.


Step:
0,01 %
Range:
0,00 100,0 %

Overheat prot
ENABLED:

DISABLED:

Island enable
NO:
YES:

[ ENABLED / DISABLED ]

(FV)

If the temperature measured from analog input MLC:TbyPwr exceeds the value TbyPwr
Treq the gen-set group power is decreased gradually. Particular gen-sets finish the rampdown at their Min Power PtM levels. If the temperature decreases below TbyPwr Treq the
gen-set group power is increased gradually to the original requested value (SysBaseload,
Imp/Exp....).
Overheat protection function is disabled. No power change if the temperature measured from
analog input MLC:TbyPwr exceeds the value TbyPwr Treq.

[ NO / YES ]

(FV)

No gen-set is started and during mains failure no command for start stop is issued.
Allows to start gen-set in AUTO mode and cover the load during mains failure.

ParallelEnable

[ NO / YES ]

(FV)

NO:
No parallel operation is allowed.
YES:
A gen-set can be started and synchronized via his GCB or MGCB to the mains.
Hint:
Explanation of detailed behaviour is on page 7.

Synchro enable

[ NONE / REVERSE / FORWARD / BOTH ]

(FV)

MGCB application only


Enable or disable forward/reverse synchronization.
NONE:
No synchronizing is enabled.
FORWARD:
MGCB synchronizing is enabled.
REVERSE:
MCB synchronizing is enabled.
BOTH:
MGCB and MCB synchronizing are enabled.

Synchro enable

[ NONE / REVERSE ]

(FV)

MCB application only


Enable or disable reverse synchronization.
NONE:
No synchronizing is enabled.
REVERSE:
MCB synchronizing is enabled.

MFStart enable

[ NO / YES ]

(FV)

NO, YES:
Enables or disables automatic mains failure start command to gen-set group.
Hint:
The AMF function activates the common output signal Sys start/stop in IM-NT. The signal is intended to be
directly connected to Sys start/stop inputs of all gen-set controllers in the system, e.g. using
SHBIN/SHBOUT peripherals.

MGCBparalClose

[ NO / YES / MCB CLOSED] (FV)

MGCB application only


IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

49

NO, YES:

Enables or disables automatic MGCB closing in the case that the Sys start/stop output is
activated.
In AUT mode, if the gen-set group is about to be started to mains-parallel operation, it is
suitable to close the MGCB first. The gen-sets then synchronize with the generator bus and
directly with the mains (both MCB and MGCB are closed). If this is not desired (from
whatever reason), the function can be blocked by adjusting this setpoint to NO. In that case,
the gen-sets are synchronized on the generator bus first (without load), and only after that
the MGCB synchronizing starts.

MCB CLOSED: Enables automatic MGCB closing after MCB is closed with 5s delay (In AUTO mode). If
Mains fail MGCB is opened after MCB is opened. When Synchronizing is enabled group of
gen-set is synchronized via MCB to the healthy mains. MGCB is closed only if 0V is on genset bus bar and GCBs are opened. Return without synchronization follows with MGCB
opening running group of gen-set are stopped and MCB is closed.
Hint:
IM-NT cannot influence behavior of another control unit that is in MAN mode. It is dangerous to close
GCB on gen-set in MAN mode while parallel operation is disabled. IM-NT react on this with opening
MGCB but it could take short time till it received feedback from GCB and MGCB breaker is
automatically opened.
Connecting of a genset with non-ComAp controller to a common bus
In version 2.5 it was not possible to close MGCB in case that all ComAp genset controllers were switched off
and there was another (hire) genset supplying voltage to the bus bar.
From version 2.6 the IM-NT closes MGCB based on voltage present on the bus (provided that load reserve
is fulfilled) and is not checking the presence of IGS-NTs. For proper functionality in parallel to Mains
operation it is then necessary that the MGCBparalClose setpoint is set to YES.

MinPwr PtM

[%]

(FV)

Specifies the minimal power that must be exported to the Mains in percentage of the sum of nominals of all
running engines (TotRunPnom value).
Step:
1%
Range:
0 100 %

AUT ctrl mode

[ NORMAL / COX (FOLLOW) ]

NORMAL:

The controller in AUT mode works with all delays specified in setpoints and provides
automatic state transfers according to the settings.
COX (FOLLOW):The controller in AUT mode follows the states specified externally (e.g. breaker feedback
active or not) and reacts only on input command Force sync. According to the actual
controller state, the respective power control loop is active. This IM-NT behaviour is similar
to the behaviour of IG/IS-NT COX application.
Hint:
This setpoint is in MCB application only.

Mains coupling
ENABLED:

DISABLED:

[ ENABLED / DISABLED]

(FV)

The process of connecting a healthy mains to a bus, energized by another mains, provided
by IM-NT controller is allowed. The bus is energized either using another IM-NT controller,
connected by CAN bus to the IM-NT in charge. During mains coupling, it is possible that one
or more gen-sets are connected to the bus in parallel-to-mains operation, which can not be
affected by the IM-NT in charge. During mains coupling, the control of gen-set controllers
from IM-NT in charge by means of digital load sharing and VAr-sharing line is not used, and
only passive check of voltage-matching conditions is provided. In case that the voltagematching conditions are fulfilled (phase, slip frequency, voltage match, dwell time), the MCB
or MGCB, if appropriate, is closed.
The controller blocks the MCB or MGCB closing in this situation.

Hint:
General rules:
In OFF mode, the mains coupling functionality is disabled.
IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

50

Once the MCB or MGCB is closed using Mains coupling functionality and later the Process control:
Mains coupling is set to DISABLED, the breaker is not opened.
If the voltage on any side of the breaker gets out of protection limits during mains coupling, the
process is terminated automatically.
In case that at least one gen-set is connected to the generator bus, the limitations and rules of
interconnecting the generators and mains feeder are in effect as described in the manual on page 7,
regardless of whether the secondary mains is connected to the generator bus or not. This applies
e.g. to the setting of Process control: Island enable, ParallelEnable, Synchro enable, etc.
The controller can sense that a particular bus side is connected to the mains from the information provided
by other controllers at the same CAN bus.
In AUT mode, the process is fully automatic. In MAN mode, the controller will only react on the button
command if the transition based on this setpoint is allowed.

WatchedContr

[0-16]

The setpoint specifies which controller will be set as a master in redundant control operation. Control
unit follows all inputs and it is in the same state as the master unit. All binary outputs are opened,
CAN bus messages are not transmitted from slave unit and all other units know about this state.
Slave control unit does not work in power management (is removed from PWR management).
Setpoint is ignored till Emerg. Manual binary input is not activated.
Hint:
Activation of Emerg. Manual operation is possible only when Binary input Emerg. Manual is active
and WatchedContr is set to 0! Binary input Emerg. Man deactivation brings controller to the previous
operation mode (depends on actual state of feedbacks and inputs).
In the case when Binary input Emerg. Manual is activated and WatchedContr is differnet from 0 then
control units follows Master unit and receives all messages from the CAN bus.

Basic settings
Vm VT ratio

[ /1 ]

Mains Voltage Transformers ratio.


Step:
0,1 V / V
Range:
0,1 500,0 V / V
Hint:
Set Vm VT ratio to 1,0 if no Voltage Transformers are used.

Vm InpRangeSel

[ 277 V / 120 V ]

Mains voltage sensing inputs range selection.

Vb VT ratio

[ /1 ]

Bus Voltage Transformers ratio.


Step:
0,1 V / V
Range:
0,1 500,0 V / V
Hint:
Set Vb VT ratio to 1,0 if no Voltage Transformers are used.

Vb InpRangeSel

[ 277 V / 120 V ]

Bus voltage sensing inputs range selection.


Step:
1V
Range:
80 30000 V

MainsNomV

[ V ] (FV)

Nominal mains voltage (phase to neutral).


Step:
1V
Range:
80 34641 V
Hint:
The nominal value can be externally changed using Force value function. However, it is intended for
changes between standard nominal voltages only (230 / 120 V) using Force value X source setpoints.
IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

51

It is prohibited to use another controller values as a source for Force value in this case!!!

MainsNomVph-ph

[V]

Nominal mains voltage (phase to phase).


Step:
1V
Range:
130 60000 V
Hint:
Both Mains and Bus nominal voltages must be set to the same value when no PT is used.

BusNomV

[ V ] (FV)

Nominal bus voltage (phase to neutral).


Step:
1V
Range:
80 34641 V
Hint:
The nominal value can be externally changed using Force value function. However, it is intended for
changes between standard nominal voltages only (230 / 120 V) using Force value X source setpoints.
It is prohibited to use another controller values as a source for Force value in this case!!!

BusNomVph-ph

[V]

Nominal bus voltage (phase to phase).


Step:
1V
Range:
130 60000 V
Hint:
Both Mains and Bus nominal voltages must be set to the same value when no PT is used.

Nomin current

[ A ] (FV)

This is the current limit for the mains/bus bars. IDMT over current and short current protections are based on
this setpoint. See Mains protect: Mains2Inom del, MainsIshort setpoints. These protections can be used for
breaker built-in protections back-up.
Step:
1A
Range:
1 - 10000 A
!!! VERY IMPORTANT !!!

The maximum input current to the controller current terminals is 11 Amps. Higher value is
displayed as measured limit, e.g. 15 Amps from CT is measured and displayed as 11 Amps.
Take special care when selecting CTs. All available 5 Amp CTs do not have a range up to 11
Amps.

NominMainsImp

[ kW ]

(FV)

Nominal power of the mains incomer. IDMT over load protection is based on this setpoint, as well as some
control loops internal adjustments.
Step:
1 kW
Range:
1 32000 kW

MainsCTprim

[A]

Mains phases Current Transformers ratio primary side.


Step:
1A
Range:
1 15000 A

MainsCTsec

[ /5A / /1A ]

Mains phases Current Transformers ratio secondary side selection /5A or /1A.

AuxCurrCTprim

[A]

Auxiliaries Current Transformer ratio primary side.


Step:
1A
Range:
1 15000 A
IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

52

AuxCurrCTsec

[ /5A / /1A ]

Auxiliaries Current Transformer ratio secondary side selection /5A or /1A.

FixVoltProtSelect
PHASE-NEUTRAL:
PHASE-PHASE:

Nominal freq

[ PHASE-NEUTRAL / PHASE-PHASE ]

The mains/bus voltage protections are based on phase-to-neutral voltages.


The mains/bus voltage protections are based on phase-to-phase voltages.

[ Hz ] (FV)

Nominal mains/bus frequency (usually 50 or 60 Hz).


Step:
1Hz
Range:
45 65 Hz
Hint:
The nominal value can be externally changed using Force value function. However, it is intended for
changes between standard nominal frequencies only (50 / 60 Hz) using Force value X source setpoints.
It is prohibited to use another controller values as a source for Force value in this case!!!

ControllerMode

[ OFF / MAN / AUT / TEST ]

(FV)

Equivalent to Controller mode changes by MODE or MODE buttons.


Hint:
Mode change can be separately password protected.

Local buttons

[ PANEL / EXTBUTTONS / BOTH ]

PANEL:
Only the buttons on the controller front panel are enabled.
EXTBUTTONS: Only the external signals (copies of the panel buttons) are enabled.
BOTH:
Both controller buttons and external signals are enabled.
Hint:
This switch is valid for these signals: MCBButton / BTBButton, MGCBButton, FaultResButton,
HornResButton.

DispBaklightTO

[ min ]

(FV)

Timeout after which the display backlight is switched off.


OFF = the backlight is off all the time, NO TIMEOUT = the backlight is on all the time.
Step:
1 min
Range:
OFF, 1 240 min, NO TIMEOUT

ConvCoefPulse1

[ /X ] (FV)

ConvCoefPulse2

[ /X ] (FV)

ConvCoefPulse3

[ /X ] (FV)

ConvCoefPulse4

[ /X ] (FV)

The conversion ratio between incoming pulses at binary inputs PulseCounter X and output statistic values
PulseCounter X. The ratio defines how many pulses (rising edges) have to be sensed at the input in order to
increase the output value. Unfinished invisible parts are stored in the controller even in the case of power
supply failure. Physical unit of the output statistic value has to correspond to the ratio unit /X.
Step:
1 /X
Range:
1 65000 /X
Hint:
Pulse width (both high/low levels) must be at least 100 ms in order to be correctly sensed!
Conversion ratio can be selected using the setpoints ConvCoefPulseX. The converted values are visible in
statistics values PulseCounter X. These values can be reset using Statistics window in InteliMonitor.

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

53

Comms settings
ControllerName
User-defined name, used for controller identification at remote connections. ControllerName is max 15
characters long and has to be entered using PC software.
Hint:
The setpoint can be changed only using PC SW when configuring IM-NT.

LB/UART Log

[ DISABLED / ENABLED ]

(FV)

Enables history logging of local terminal and IG-IB connection.


Force value possibility: Yes
Hint:
If communication via IG-IB (I-LB,) is interrupted for more than 5s, it is automatically terminated. If it is
recovered again after this period, it is considered as a newly established communication and a new record
Terminal is done into history in case of LB/UART Log = ENABLED. This may cause overfilling of the history
in case of some monitoring tools, e.g. InteliSupervisor.
Access code change, password changed and password set is written into the history when LB/UART Log =
DISABLED.

Contr. addr

[ ]

Controller CAN bus and RS485 identification number. Each controller in the group has to have its own
unique number.
Step:
1
Range:
1 to 32
Hint:
When opening Direct or Modem connection to the controller (using PC monitoring/control SW), the Contr.
address has to correspond to the Gen-set setting in PC SW.

RS232(1) mode
[ DIRECT / MODEM (HW) / MODEM (SW) /
MODBUS-DIRECT / MODBUS-MDM(HW) ]
Communication protocol selection for RS232(1) line.
DIRECT:
Connection to a local PC running InteliMonitor. RS232 or RS485 (with internal or
external converter) lines can be used. Set this also for IG-IB connected via RS232 line.
MODEM (HW):
Analog/GSM/ISDN modem connection. Select this for standard modems with HW flow
control. If selected and no CTS signal is detected, communication may not work
correctly.
MODEM (SW):
Analog/GSM/ISDN modem connection. Select this for modems without HW flow control
controller will use SW flow control signals XOn, XOff, so only TxD and RxD signals
need to be connected between the controller and the modem.
MODBUS-DIRECT:Modbus protocol for direct connection to PLC / external SCADA terminal. Communication
speed can be selected via setpoint RS232(1)MBCSpd.
MODBUS-MDM(HW):Modbus protocol for modem (remote) connection to PLC / external SCADA terminal.
Communication speed can be selected via setpoint RS232(1)MBCSpd.
Hint:
Detail description of Modbus protocol see in Communication guide.

RS232(1)MBCSpd

[ 9600 bps / 19200 bps / 38400 bps / 57600 bps ]

Defines the communication speed on RS232(1) line when ModBus mode is selected.

RS232(1)MdmIni

[ ]

Auxiliary modem initialization string executed after the default modem initialization string. Used with
modem connected to the RS232(1) communication port.
Hint:
Applicable only for MODEM(HW), MODEM(SW) and MODBUS-MDM(HW) modes.
Use for special AT command setting of your modem if default string does not initiate the modem properly. AT
commands must be separated using semicolon ;, max. length 31 characters.
The setpoint can be changed only using PC SW when configuring IM-NT.
IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

54

RS485(1) conv.

[ DISABLED / ENABLED ]

If set to ENABLED, the communication RS232(1) port is redirected to the built-in RS485 converter. That
means the remote display RS485 line (for IG-Display connection) is blocked and the converter is used for
communication with superior system or ECU.
Available in all controllers except of IS-NT.
Hint:
Applicable only for DIRECT, MODBUS-DIRECT and ECU LINK modes.
This converter is not isolated!

CAN bus mode

[ 32C / 8C ]

CAN bus speed selection.


32C: High speed CAN (250 kbps) applicable up to 32 controllers, CAN bus length limited up to 200
meters.
8C:
Low speed CAN (50 kbps) applicable up to 8 controllers, CAN bus length limited up to 900 meters.
Hint:
Low speed use for long distance connection only. Set all connected controllers to the same speed.
If having problems with needed CAN bus length, see Communication guide / I-CR module.

CAN2emptDetect

[ DISABLED / ENABLED ]

(FV)

Enables the detection of missing intercontroller CAN connection. If enabled and no other controllers are
detected on the CAN bus (the complete bus, not only within the logical group), this protection activates.

SHxOcol Detect

[ DISABLED / ENABLED ]

This setpoint is dedicated for virtual peripheries; it can enable / disable error messages when more then one
master (source) is configured.

CANAddrSwitch1

[ MODEM / OTHER ]

This setpoint defines whether CAN address 122 is used for modem communication over ComAp I-LB
module or direct communication of another device:
MODEM: Default setting for modem communication
OTHER: Address 125 can be used by other devices to read data via CAN bus the same way as if using
addresses 123 and 124

CANAddrSwitch2

[ MODEM / OTHER ]

This setpoint defines whether CAN address 122 is used for modem communication over ComAp I-LB
module or direct communication of another device:
MODEM: Default setting for modem communication
OTHER: Address 122 can be used by other devices to read data via CAN bus the same way as if using
addresses 123 and 124

ComProtSetting
Horn timeout

[ s ] (FV)

The maximum amount of time the Binary output Horn is closed (horn, buzzer will sound). OFF = the output
wont be activated, NO TIMEOUT = the output stays closed until the alarm has been reset.
Step:
1s
Range:
OFF, 1 3600 s, NO TIMEOUT

BinInp delay 1

[s]

Binary input protection is activated when input is closed for longer time than BinInp delay 1. To use this
delay, Binary input must be configured in GenConfig for Property Delay = BinInp delay 1.
Step:
0,1s
Range:
0,0 600,0 s

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

55

BinInp delay 2

[s]

Binary input protection is activated when input is closed for longer time than BinInp delay 2. To use this delay
Binary input must be configured in GenConfig for Property Delay = BinInp delay 2.
Step:
0,1s
Range:
0,0 600,0 s

BinInp delay 3

[ s ] (FV)

Binary input protection is activated when input is closed for longer time than BinInp delay 3. To use this delay
Binary input must be configured in GenConfig for Property Delay = BinInp delay 3.
Step:
0,1s
Range:
0,0 600,0 s
Hint:
BinInp delay is active only for Binary inputs configured as protection.
If these setpoints are not used, default BI delay is 0,5s.
GenConfig: I/O, Property-Prot.active = Closed
BINARY INPUT
physical

BinInp delay

BINARY INPUT

no change

Internal value
closed

BINARY INPUT
physical

BinInp delay

BINARY INPUT

Internal value
GenConfig: I/O, Property-Prot.active = Opened
BINARY INPUT
physical

opened
BinInp delay

BINARY INPUT
Internal value

ForceBlockDel1

[s]

ForceBlockDel2

[s]

ForceBlockDel3

[ s ] (FV)

Delays for Force block protection activation after the corresponding Binary input Force block is opened.
Protection deactivation is without delay. Protection is activated/deactivated independent on engine running
or not running state it depends only on the corresponding Force block X input.
Step:
0,1s
Range:
0,0 60,0 s
closed
BINARY INPUT
Prot, block type = Force block
BINARY INPUT
FORCE BLOCK
Protection

active

closed
ForceBlock del
inactive

active

BinInpDelayX

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

56

ResetActAlarms

[ DISABLED / ENABLED ]

DISABLED:
If Fault reset is activated (from any source), only inactive (normally displayed) alarms are
reset. So only inactive alarms can be cleared from the Alarmlist.
ENABLED:
If Fault reset is activated (from any source), all currently present (including inverse displayed
= active) alarms are reset (asterisk in Alarmlist disappears for all present alarms). I.e. after an active (inverse
displayed) alarm later on becomes inactive (normally displayed), it is cleared automatically from the Alarmlist
if previously reset.
Hint:
ENABLED mode corresponds to the way that IG and IS controllers (classic line) handled the alarms.

Analog protect
The content depends on programmable protections settings. The protections defined in this group are
supposed general protections, not related to mains monitoring.
This list contains pre-set protections from default archives:

Batt >V

[V]

Warning level for battery over voltage.


Step:
0,1 V
Range:
8 40 V

Batt <V

[V]

Warning level for low battery voltage.


Step:
0,1 V
Range:
8 40 V

Batt volt del

[s]

Delay for battery voltage alarms.


Step:
1s
Range:
0 600,0 s

Mains protect
The content depends also on programmable protections settings. This list contains fixed protections, which
are always present:

Mns2POvrldProt

[ DISABLED / ENABLED ]

(FV)

Enables or disables the mains over load (IDMT) protection.

OverldStrtEval

[ % ] (FV)

Specifies the overload level, where the protection evaluation starts (see figure at 2PovrldStEvDel). Under
this level the protection is not active.
Step:
1 % of NominMainsImp
Range:
100 200 %

2POvrldStEvDel

[s]

IDMT curve shape selection. 2PovrldStEvDel is the Reaction time of IDMT protection for 200% overload
Pmains = 2* OverldStrtEval.
Step:
0,1 s
Range:
0,0 - 600,0 s
Protection: Mains protection with fault Reset.
IDMT is inverse proportional to the mains overload. The higher the overload gets the less time will elapse
before the protection activates.
When the IDMT protection is activated the MCB is opened and the event is recorded in the Alarmlist and
History. The further MCB closing is blocked until Fault Reset has been pressed to clear the alarm.
IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

57

2POvrldStEvDel * OverldStrtEval
Reaction time =
Pmains - OverldStrtEval
Where Reaction time is the amount of time from IDMT detection to the opening of the MCB.
Hint:
The maximum allowable Reaction time is 3600 sec.
Following example shows reaction times for OverldStrtEval = 100% in dependence on mains power and
setpoint 2PovrldStEvDel value:

Pmains [%] <=100


2POvrldStEvDel [s]
0,1
0,2
0,5
1,0
1,5
2,0
2,5
5,0
10,0
20,0
50,0

101

102

105

110

120

150

No action
10
No action
20
No action
50
No action
100
No action
150
No action
200
No action
250
No action
500
No action
1000
No action
2000
No action No action

5
10
25
50
75
100
125
250
500
1000
2500

2
4
10
20
30
40
50
100
200
400
1000

1
2
5
10
15
20
25
50
100
200
500

0,5
1
2,5
5
7,5
10
12,5
25
50
100
250

0,2
0,4
1
2
3
4
5
10
20
40
100

Following example shows reaction times for OverldStrtEval = 110% in dependence on mains power and
setpoint 2PovrldStEvDel value:
Pmains [%] <=110
2POvrldStEvDel [s]
0,1
0,2
0,5
1,0
1,5
2,0
2,5
5,0
10,0
20,0
50,0

111

112

115

120

150

200

No action
11
No action
22
No action
55
No action
110
No action
165
No action
220
No action
275
No action
550
No action
1100
No action
2200
No action No action

5,5
11
27,5
55
82,5
110
137,5
275
550
1100
2750

2,2
4,4
11
22
33
44
55
110
220
440
1100

1,1
2,2
5,5
11
16,5
22
27,5
55
110
220
550

0,275
0,55
1,375
2,75
4,125
5,5
6,875
13,75
27,5
55
137,5

0,123
0,245
0,612
1,223
1,834
2,445
3,056
6,112
12,223
24,445
61,112

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

58

Reaction time

OverldStrtEval
Maximal Reaction
time

2 POvrldStEvDel

Pmains
NominMainsImp
Mns2Inom prot

[ DISABLED / ENABLED ]

(FV)

Enables or disables the mains over current (IDMT) protection.

Mains2Inom del

[s]

IDMT curve shape selection. Mains2Inom del is the Reaction time of IDMT protection for 200% overcurrent
Imains = 2* Nomin current.
Step:
0,1 s
Range:
0,0 - 60,0 s
Protection:
Mains protection with fault Reset.
IDMT is inversely proportional to the mains overcurrent. The higher the overcurrent gets the less time will
elapse before the protection is activated.
When the IDMT protection is activated the MCB is opened, the event is recorded in the Alarmlist and History.
The further MCB closing is blocked until Fault Reset has been pressed to clear the alarm.

Mains2Inom del * Nomin current


Reaction time =
Imains -

Nomin current

Where Reaction time is the amount of time from IDMT detection to the opening of the MCB.
Hint:
The maximum allowable Reaction time is 900 sec.
Imains is the maximum current of the three phases of mains current.
IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

59

EXAMPLE of Reaction time for different over current levels.


Imains [%]
Mains2Inom del
0,1
0,2
0,5
1,0
2,0
5,0
10,0
20,0
50,0

<=100

101

102

105

110

120

150

200

No action
10
5
2
No action
20
10
4
No action
50
25
10
No action
100
50
20
No action
200
100
40
No action
500
250
100
No action No action
500
200
No action No action No action
400
No action No action No action No action

1
2
5
10
20
50
100
200
500

0,5
1
2,5
5
10
25
50
100
250

0,2
0,4
1
2
4
10
20
40
100

0,1
0,2
0,5
1
2
5
10
20
50

!!! VERY IMPORTANT !!!

Maximal Reaction time

Reaction time

The maximum input range of the controller current terminals is 11 Amps. Anything over this
value is displayed as measured limit, e.g. 15 Amps from CT is measured and displayed as 11
Amps.
Take special care when selecting CTs. All available 5 Amp CTs do not have a range up to 11
Amps.

Mains2Inom del

Imains
Nomin current

Mains >V MP

[%]

FV

Threshold for mains over voltage.


Step:
1%
Range:
Mains <V MP 150 %
Protection:
Mains protection.

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

60

Mains <V MP

[%]

FV

Threshold for mains under voltage.


Step:
1%
Range:
50 Mains >V MP %
Protection:
Mains protection.
Hint:
All three phases are checked for mains voltage protection. Minimum or maximum out of three is used.
For high voltage applications, the MainsNomVph-ph can be used for nominal voltage setting.

Mains V del

[s]

Delay for mains under and over voltage protection.


Step:
0,02 s
Range:
0,00 600,00 s

Mains >f

[%]

FV

[%]

FV

Threshold for mains over frequency.


Step:
0,1 %
Range:
Mains <f - 150,0 %
Protection:
Mains protection.

Mains <f

Threshold for mains under frequency.


Step:
0,1 %
Range:
50,0 Mains >f %
Protection:
Mains protection.
Hint:
The mains frequency is evaluated from the L3 phase.

Mains f del

[s]

Delay for mains under frequency and over frequency protection.


Step:
0,02 s
Range:
0,00 600,00 s

VectorS prot
DISABLED:
PARALLEL ONLY:

[ DISABLED / PARALLEL ONLY / ENABLED ] (FV)


Vector shift protection is disabled.
Vector shift protection is enabled only if at least one gen-set is running in parallel
with mains (= MCB+GCB status active; MGCB status in addition for MGCB
application).
Vector shift protection is enabled if MCB status is active.

ENABLED:
Force value: Yes
Hint:
If ENABLED is selected, it is likely that Vector shift protection will trip the MCB before other mains
protections. It senses the fast changes in mains voltage angle position, which occur with every mains failure,
even if the gen-set is not running in parallel with mains.

VectorS CB sel

[ MCB / MGCB ] (FV)

MGCB application only


MCB:
MCB is tripped if Vector shift protection gets active. The loaded gen-set group
passes to the island-parallel operation.
MGCB:
MGCB is tripped if Vector shift protection gets active.
Force value: Yes
Hint:
If MGCB is selected and mains failure comes up, it is likely that MCB trips as well later on because of other
mains protections.
Use MGCB option in the case that the gen-set group is not able to handle the island load and would get
overloaded.
IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

61

VectorS limit

[]

Vector shift protection threshold level.


Step:
1
Range:
1 45
Hint:
To be sure of proper adjusting of VectorS limit, check Max VectorS value on the controller or PC software
screen. Max VectorS value is set to zero when transiting to parallel, and then accumulates the maximum
reached value (positive only) during parallel operation. Thus, during the normal operation, only the
background noise is accumulated (usually max 3), and the protection level should be set to approximately
twice the value of this noise.

Mains V unbal

[%]

Threshold for Mains voltage unbalance alarm. The voltage unbalance is calculated as a maximum difference
between phase voltages.
Step:
1% of Nominal voltage
Range:
0 200% of Nominal voltage
Protection:
Mains protection.

Mains Vunb del

[s]

Delay for Mains voltage unbalance alarm.


Step:
0.1s
Range:
0 600.0 s

Mains I unbal

[%]

Threshold for Mains current asymmetry (unbalance). The current unbalance is calculated as a maximum
difference between phase currents.
Step:
1% of Nominal current
Range:
0 200% of Nominal current
Protection:
Mains protection.

Mains Iunb del

[s]

Delay for Mains current asymmetry (unbalance).


Step:
0.1 s
Range:
0 600.0 s

Bus protect
Hint:
If bus voltage is measured at the same point by IM-NT and by IGS-NT controllers then it is recommended to
set bus protection setpoints to same values in IM-NT and gen-set controllers. Otherwise it might happen that
there is discordance between evaluation of healthy bus and it can lead to situation that gen-set controllers
realize the bus as healthy but IM-NT prevents reverse synchronizing keeping Sys start/stop to gen-set
controllers active.

Bus >V Hst

[%]

(FV)

[%]

(FV)

Threshold for bus over voltage.


Step:
1%
Range:
Bus <V Hst 150 %
Protection:
History record.

Bus <V Hst

Threshold for bus under voltage.


Step:
1%
Range:
50 Bus >V Hst %
Protection:
History record.
Hint:
All three phases are checked for bus voltage detection. Minimum or maximum out of three is used.
IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

62

For high voltage applications, the BusNomVph-ph can be used for nominal voltage setting.

Bus V del

[s]

Delay for bus under and over voltage detection.


Step:
0,02 s
Range:
0,00 600,00 s

Bus >f

[%]

(FV)

[%]

(FV)

Threshold for bus over frequency.


Step:
0,1 %
Range:
Bus <f - 150,0 %
Protection:
History record.

Bus <f

Threshold for bus under frequency.


Step:
0,1 %
Range:
50,0 Bus >f %
Protection:
History record.
Hint:
The bus frequency is evaluated from the L3 phase.

Bus f del

[s]

Delay for bus under frequency and over frequency protection.


Step:
0,02 s
Range:
0,00 600,00 s

BusMeasError
DISABLED:
ENABLED:

[ DISABLED / ENABLED ]

(FV)

The protection is off.


Bus measure error is detected in MCB / MGCB application when the voltage on
controllers bus terminals is out of limits for 20 seconds under these conditions:

MCB application:
a) MCB (feedback) was closed in AUT mode.
b) Any GCB in power management group (on CAN bus) was closed. The alarm is activated after 20 s,
however the MCB closing is blocked immediately from safety reasons.
MGCB application:
a) MCB and MGCB (feedbacks) were closed in AUT mode.
b) Any GCB in power management group (on CAN bus) was closed. The alarm is activated after 20 s,
however the MGCB closing is blocked immediately from safety reasons.

Bus V unbal

[%]

Threshold for bus voltage unbalance alarm. The voltage unbalance is calculated as a maximum difference
between phase voltages.
Step:
1% of Nominal voltage
Range:
0 200% of Nominal voltage
Protection:
History record.

Bus Vunb del

[s]

Delay for bus voltage unbalance alarm.


Step:
0.1s
Range:
0 600.0 s

AMF settings
EmergStart del

[ s ] (FV)

Delay between the mains failure and the command to start the gen-set group, i.e. closing the binary output
Sys start/stop.
IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

63

Step:
1s
Range:
0 600 s
Hint:
Link the output Sys start/stop with the inputs Sys start/stop at the gen-set controllers to achieve the
automatic start. Gen-set controllers have to be in AUT mode in order to react on this input.

FwRet break

[ s ] (FV)

MGCB application: Delay between MGCB opening and MCB closing during the return to mains when reverse
synchronizing (or mains parallel run) is not enabled.
Delay between MCB opening and MGCB closing in TEST Mode, when ReturnTo mains = ENABLED and
power cut comes.
MCB application: Delay between last GCB opening (from CAN2 bus) and MCB closing during the return to
mains when reverse synchronizing (or mains parallel run) is not enabled.
Step:
0,1 s
Range: 0 60,0 s

MCB close del

[ s ] (FV)

Delay after mains return to MCB closing, if gen-sets are not running (output Sys start/stop not active).
Step:
0,1 s
Range:
0 60,0 s
Hint:
This setpoint is active in OFF and AUTO mode.

MCB opens on

[ MAINSFAIL / GEN RUNNING ]

(FV)

Adjusting of condition when MCB opens after Mains fail:


MAINSFAIL:
Controller opens the MCB when Mains fail is detected (24 VDC controlled circuit breaker or
contactor expected).
GEN RUNNING:
Controller opens the MCB only after at least one gen-set starts, i.e. the generator
voltage is present to open the MCB (230 VAC controlled breaker expected). In OFF
mode, this means MCB stays closed all the time, regardless of the mains condition.
Hint:
Link the output Sys start/stop with the inputs Sys start/stop at the gen-set controllers to achieve the
automatic start. Gen-set controllers have to be in AUT mode in order to react on this input.

ReturnWithIntr

[ ENABLED / DISABLED]

(FV)

ENABLED:

Enables break transfer of the load back to the mains, if reverse synchronizing is not
successful, opens GCB and after FwRet break delay close MCB.
DISABLED:
Gen-set stays running loaded in island when reverse synchronizing is not successful, even if
mains is OK again.
FORCE value possibility:Yes

BreakerOverlap

[ s ] (FV)

MGCB application only


When limited time of running in parallel with mains is required, BreakerOverlap defines max time of running
in parallel with mains. During this time soft transfer of load is activated. Used in AUT and TEST modes.
This setpoint is valid during transfer of load from gen-set to the Mains and also in TEST mode. During
TestOnLoad the gen-sets remain in parallel until imported power from Mains reaches 0 but minimum for
BreakerOverlap time.
Step:
0,1 s
Range: 0,0 300,0 s

RetFromIsland
MANUAL:

[ MANUAL / AUTO ]

(FV)

Up to version 2.5.1 - controller is automatically switched to MAN mode on each transition to


Island operation. To activate the load transfer back to mains, the controller must be switched
back to AUT mode.
From version 2.6 - controller remains in AUT mode and the manual return to Mains is done
via MCB button. In case that the gensets fail to supply the load, IM-NT automatically
transfers load to the Mains.

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

64

AUTO:
Load is automatically transferred in AUT mode after Mains return.
Hint:
Select RetFromIsland = MANUAL when it is important at what time the load is transferred back to the mains.
Setting to MANUAL might be important only for applications with break transfers (with synchronizing
disabled).

ReturnTo mains

[ DISABLED / ENABLED ]

(FV)

MGCB application only


The setpoint influences the behavior of the TEST mode. If mains fail occurs during test (or is simulated using
Test on load function), the controller opens the MCB and switches the load to generators.
DISABLED: Now if the mains recovers, the generators stay running loaded until TEST mode is abandoned,
typically to AUT mode where reverse synchronizing and soft unloading follows.
ENABLED:
After the mains recovers, the generators will be reverse synchronized back to the mains,
softly unloaded and remain running without load (MGCB opens) until TEST mode is
abandoned or another mains failure occurs.

Mains ret del

[ s ] (FV)

Delay after the mains return to the start of synchronizing of MCB.


Step:
1s
Range:
0 3600 s
Hint:
If synchronizing is disabled, a break transfer takes place after this delay elapses.

Pwr management
#Pwr mgmt mode
ABS (kW):
ABS (kVA):
REL (%):

[ ABS (kW) / ABS (kVA) / REL (%) ]

Setpoints #LoadResStrt X and #LoadResStop X are set in absolute values in kW.


Setpoints #LoadResStrt X and #LoadResStop X are set in absolute values in kVA. Nominal
kVA of each gen-set is calculated from Nomin current and Gen nom V setpoints.
Setpoints #%LdResStrt and #%LdResStop are set in relative values in %. Then % means
minimum allowable relative power reserve of all running gen-sets in % of Nomin power.

#PriorAutoSwap
DISABLED:
RUN HOURS EQU:

LD DEMAND SWAP:

Priority ctrl
DISABLED:
MASTER:

#SysAMFstrtDel

[ DISABLED / RUN HOURS EQU / LD DEMAND SWAP ]


IM-NT does not provide the AutoSwap functions for other controllers.
Running Hours Equalization mode. All gen-sets in the logical group are kept to
work approximately the same number of running hours. See also setpoints
RunHoursBase and #RunHrsMaxDiff. Up to 32 engines can cooperate in this
mode.
For different sized engines, this mode allows to optimally select the running
engines according to the actual site load. Up to 3 engines can cooperate in this
mode.

[ DISABLED / MASTER ]

(FV)

IM-NT does not provide the AutoSwap functions for other controllers.
At least one controller in the logical group has to be selected as MASTER if some
PriorityAuto Swapping mode is enabled. Only the controller with lowest CAN
address becomes an active master, the other are ignored by SLAVE controllers.
The MASTER controller evaluates the Priority changing for all other controllers in
the group and sends them the forced Priority values.

[s]

System start delay between input Sys start/stop closing and start of Power Management System. When
input Sys start/stop is controlled by mains decoupling relay, this setpoint adjusts the delay between the
mains failure and the emergency start of the gen-sets. If the MCB feedback is closed, Power management is
started with 1s delay after the input Sys start/stop closing - parallel operation with the mains.
Step:
1s
Range:
0 600 s
Hint:
IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

65

Descriptions of the following # setpoints are related mostly to the gen-set controllers and are included in
IM-NT from compatibility purposes only.

#SysAMFstopDel

[s]

System stop delay between input Sys start/stop opening and Power Management System deactivation.
When input Sys start/stop is controlled by mains decoupling relay, this is a delay between the end of mains
failure and opening of GCB. If the MCB feedback is closed, gen-sets are unloaded to mains prior to GCB
opening.
Step:
1s
Range:
0 600 s

#LoadResStrt 1 (2, 3, 4)

[ kX ]

Active if Pwr mgmt mode = ABS (kW) / ABS (kVA).


Required system load reserve, or in the other words load reserve defines the maximum allowable load jump.
The active set of load reserve setpoints 1, 2, 3, 4 is selectable via binary inputs Load reserve 2, 3, 4.
When the required load reserve is not achieved, another gen-set is started. The system can work with active
(kW) or apparent (kVA) power.
Step:
1 kX
Range:
-32000 #LoadResStop 1 (2,3,4) kX

#%LdResStrt 1 (2, 3, 4)

[%]

Active if Pwr mgmt mode = REL (%).


System reserve is defined by the maximum allowable relative load reserve of running gen-sets.
Step:
1%
Range:
0 #LoadResStop 1 (2,3,4) %
Hint:
Use load reserve sets to separate minimum initial power for start-up and necessary reserve in steady
running conditions.

#LoadResStop 1 (2, 3, 4)

[ kX ]

Active if Pwr mgmt mode = ABS (kW) / ABS (kVA).


The active set of load reserve setpoints 1, 2, 3, 4 is selectable via binary inputs Load reserve 2, 3, 4. When
#LoadResStop 1 (2, 3, 4) level is achieved, the gen-set with the lowest priority (highest setpoint Priority) is
stopped.
Next gen-set is stopped when:
PBNom > PAkt + Reserve
PBNom
PAkt
Reserve

Sum of the nominal power of all gen-sets on the bus apart of the one, which is going to be
stopped.
System load
#LoadResStop 1 or 2 or 3 or 4

Step:
1 kX
Range: #LoadResStrt 1 (2,3,4) 32000 kX

#%LdResStop 1 (2, 3, 4)

[%]

Active if Pwr mgmt mode = REL (%).


Next gen-set is stopped when:
[(PBNom - PAkt) / PBNom].100 > %Reserve
PBNom
PAkt
%Reserve

Sum of the nominal power of all gen-sets on the bus apart of the one, which is going to be
stopped.
System load
#%LdResStop 1 or 2 or 3 or 4

Step:
1%
Range: #%LdResStrt 1 (2,3,4) 110 %
Hint:

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

66

If additional Minimum Running Power system is used, the engine might not stop even if required by load
reserves. Yet another conditions must be fulfilled in this case.

!!! IMPORTANT !!!


Reserve for stop always has to be higher than corresponding reserve for start for all Power Management
modes !

#NextStrt del

[s]

The delay before next gen-set start-up in Pwr management. Delay is not used, when the first gen-set(s)
starts.
Step:
1s
Range:
0 3600 s

#OverldNextDel

[s]

The delay before next gen-set start-up in Pwr management when the system load is equal or higher than
nominal power of all gen-sets on the bus.
Delay is not used, when the first gen-set(s) starts. Delay is used only when in island parallel operation, not in
mains parallel.
Step:
1s
Range:
0 3600 s

#NextStopDel

[s]

The delay before next gen-set stopping in Pwr management. When delay is elapsed, the gen-set starts soft
unload, opens GCB, cools down and stops.
Step:
1s
Range:
0 36000 s

#SlowStopDel

[s]

When the Slow stop protection occurs, the controller announces to the rest of the system, that the engine is
no more ready.
a) If there are another sets ready to start and supply the load, the protection waits until the substitute engine
starts and connects to the bus. Then the engine with the active Slow stop protection softly unloads, cools
down and stops. The controller waits for substitute engine max for #SlowStopDel time.
b) If there is no other set to start, the protection activates immediately. If soft unload possible (another set is
running or MCB is closed) engine is softly unloaded, if not, GCB opens immediately.
As every protection it has to be reset by operator to get ready again.
Step:
1s
Range: 0 600 s

#MinRunPower 1 (2, 3)

[ kW ]

Following description is valid for gen-set controllers only and has informative character here:
It is minimum required power of gen-set group (sum of Nomin power of running gen-sets). When Binary input
Sys start/stop is closed, starts and stays running such a number of gen-sets to keep selected
#MinRunPower X value. This is independent on load reserves system, so even if there is high load reserve
that would allow to stop some engines, Minimum Running Power system may force them to keep running.
When binary input MinRunPower X is closed, the corresponding #MinRun power X value is selected. When
more binary inputs MinRunPower X are closed, the higher number has higher priority. When no input closed,
no #MinRunPower X is selected and minimum running power is zero, leaving only the load reserves system
to work.
Step:
1 kW
Range:
0 65000 kW
Hint:
An engine will be stopped only if the sum of remaining gen-sets nominal powers is higher or equal to
#MinRunPower X level.

#RunHrsMaxDiff

[h]

Maximum allowed Running hours difference between gen-sets. Conditions to take part in Running Hours
Equalization:
IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

67

Pwr management = ENABLED.


#PriorAutoSwap = RUN HOURS EQU
Binary input Sys start/stop is closed.
When a gen-set reaches #RunHrsMaxDiff value its Priority is automatically swapped with lowest priority genset that takes part in Running Hours Equalization.
Step:
1h
Range:
0 - 65000 h

#PwrBandContr 1
#PwrBandContr 2
#PwrBandContr 3
#PwrBandContr 4

[ 1 / 2 / 1+2 / 3 / 1+3 / 2+3 / 1+2+3 ]

According to selected controller addresses combination (controllers must have addresses 1-3), running gensets are selected based on the actual site load.
The limits of site power bands are given by nominal powers of particular gen-sets. The gen-sets that are
required to run in certain power band get the priorities 1, other gen-sets get the priority 32. This system does
not influence the setpoint Priority.
Example:
Gen-set 1 = 20 kW
Gen-set 2 = 50 kW
Gen-set 3 = 100 kW
#PwrBandContr1 = 1 (active if load under 20-#LoadResStrt X kW)
#PwrBandContr2 = 1+2 (active between 20 .. 70-#LoadResStrt X kW)
#PwrBandContr3 = 3 (active between 70 .. 100-#LoadResStrt X kW)
#PwrBandContr4 = 2+3 (active between 100 .. 150-#LoadResStrt X kW)
Above the last power band, all gen-sets will be instructed to run.

#PwrBandChngDlUp

[s]

Delay for #PwrBandContr X setpoints. The site load must stay in another power band for more than
#PwrBandChngDlUp to switch to this power band, i.e. select different gen-sets to run.
Step:
1s
Range:
0 3600 s

#PwrBandChngDlDn

[s]

Delay for #PwrBandContr X setpoints. The site load must stay in another power band for more than
#PwrBandChngDlDn to switch to this power band, i.e. select different gen-sets to run.
Step:
1s
Range:
0 3600 s

Control group

[ ]

Defines the logical group which links this IM-NT with other gen-sets on the CAN bus. The gen-sets in each
logical group make the Load Sharing and VAr Sharing independently on other groups, allowing more such
groups to be present on the CAN bus. IM-NT will influence the speed/power and voltage/PF of the gen-sets
that have the same group.
Groups can be linked together using GroupLink tools.
Step:
1
Range:
COMMON (=1), 2 32

GroupLinkLeft
GroupLinkRight

[ ]

These setpoints define the gen-set groups present to both sides of a special breaker (Bus-Tie Breaker). The
information about the breaker status is sent to all controllers via CAN bus and the affected controllers will
behave according to it.
Step:
1
IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

68

Range:
COMMON (=1), 2 32
Hint:
Example: if settings are GroupLinkLeft = 1 and GroupLinkRight = 2 and the special breaker is closed, a CAN
message is sent to notify all gen-sets in groups 1 and 2, that they should work together and make Load and
VAr Sharing not only within their groups, but together with the other group, too.
The message is sent if logical binary input GroupLink is active, and this signal should be linked to the
feedback of the special breaker (e.g. Bus-Tie).
Setpoints marked with # are over written when logical groups are interconnected. Disconected logical groups
have the same setpoints, no setpoint is automatically set to the previous value.

Sync/Load ctrl
Voltage window

[ % ] (FV)

Maximum difference between mains and bus voltage. In case of BTB application, the difference between
BusLeft and BusRight voltage.
Step:
0,1 % of MainsNomV / BusLNomV
Range:
0,0 100,0 % of MainsNomV / BusLNomV
Hint:
The limit type (MainsNomV or BusLNomV) depends on the application type MCB, MGCB / BTB.
See Voltage phases match indication on the controller Synchronizing screen.
Example 1.
Voltage match 1 2 3
1 1 0

Note:
Phase L3 is out of voltage window

Example 2.
Voltage match 1 2 3
1 1 1

Note:
All phases are in voltage window

[]

BtoM AngleReq

Requested phase difference between mains and bus voltage during synchronizing. Use this setpoint for
phase correction of potential transformers connection.
Step:
1
Range:
-45 to +45
Following is an example of the controller connection to a high voltage system.
T1 shifts phase +30 and no shift is on T2.
BtoM AngleReq = +30 for this example.
LOAD

MCB

T1
3x 230/ 400 VAC

GCB

3x 10kV

L1 ,L2 ,L3 ,N

T2

Vm Im

MCB

Vb

IM- NT

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

69

[]

Phase window

(FV)

Maximum phase angle (Mains x Bus voltage) difference between requested and actual angle for
synchronizing.
Step:
1
Range:
0 90
Hint:
The setpoint works as a window surrounding the BtoM AngleReq setpoint. E.g. for BtoM AngleReq = +30
and Phase window = 5, the breaker closure is allowed for phases +25 to +35.
If you want to lock out the breaker closing during synchronizing control loop test, set Phase window = 0. This
allows the control loop setpoints to be tuned while actual breaker closing is blocked.

Dwell time

[ s ] (FV)

The period of time that the phase angle must be within Phase window and voltage difference within Voltage
window before a breaker (MCB/MGCB/BTB) is closed.
Step:
0,1 s
Range:
0,0 25,0 s

Freq gain

[%]

Gain of frequency control loop.


Step:
0,1 %
Range:
0,0 % - 200,0 %

Freq int

[%]

Relative integration factor of frequency control loop.


Step:
1%
Range:
0 % 100 %
Hint:
Application
Freq gain and Freq int setpoints are active during:
MCB
reverse synchronization of the gen-set group back to the mains
MGCB
forward or reverse synchronization of the gen-set group to the mains
BTB
synchronization between left and right buses

Angle gain

[%]

Gain of angle control loop.


Step:
0,1%
Range:
0,0 % to +200,0 %

Load ramp

[ s ] (FV)

Increasing or decreasing load rate. In seconds / NominMainsImp (or NominBusLImp for BTB application).
Step:
1s
Range:
0 1800 s
Hint:
You can achieve more different load ramps using Force Value function. E.g. for soft load in parallel with
mains use longer ramp than for soft load in island parallel (multi-stand-by).
Speed of load ramping to the Mains depends on setting of Load ramp in IM-NT and also in gen-set
controllers.
The Mains import increase/decrease behaves according to following images:

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

70

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

71

Load gain

[%]

Gain of power control loop.


Step:
0,1 %
Range:
0 200,0 %

Load int

[%]

Relative integration factor of power control loop.


Step:
1%
Range:
0 100 %
Hint:
Application
Load gain and Load int setpoints are active during:
MCB,
parallel to mains operation in any mode where IM-NT load control loop is active (see
MGCB
setpoint MLoad ctrl PtM), including load ramps
BTB
BusLeft or BusRight BaseLoad control in any mode where IM-NT load control loop
is active (see setpoint MultiLoad ctrl), including load ramps

MGCB open lev

[%]

MGCB application only


Power level for opening the MGCB while soft unload is in progress. If this level isnt reached, the MGCB
opens after MGCB open del time.
Step:
% of NominMainsImp
Range:
0 to 100 %

MGCB open del

[ s ] (FV)

MGCB application only


The timeout to unload the gen-set group. Should the load ramp fail to bring the gen-set group power down to
MGCB open lev to allow the opening of MGCB, the breaker will open after MGCB open del.
Step:
1s
Range:
Load ramp 1800 s

Sync timeout

[s]

Maximum allowed time for forward or reverse synchronization.


Step:
1s
Range:
1 1800 s, NO TIMEOUT
Hint:
If the synchronizing does not succeed within (Sync timeout / 10, but minimum 60) s, the control loop is
restarted to try again. So if you set the Sync timeout to sufficiently high value, the synchronizing cycle can be
internally repeated up to 10 times.
If NO TIMEOUT is selected, the control loop is restarted every 1800 / 10 = 180 s.

Volt/PF ctrl
Voltage gain

[%]

Gain of voltage control loop.


Step:
0,1 %
Range:
0,0 to +200,0 %

Voltage int

[%]

Relative integration factor of voltage control loop. Increasing of integration value causes quicker response.
Step:
1%
Range:
0 100 %
Hint:
Application
Voltage gain and Voltage int setpoints are active during:
IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

72

MCB
MGCB
BTB

reverse synchronization of the gen-set group back to the mains


forward or reverse synchronization of the gen-set group to the mains
synchronization between left and right buses

PF gain

[%]

Gain of power factor control loop.


Step:
0,1 %
Range:
0,0 200,0 %

PF int

[%]

Relative integration factor of power factor control loop. Increasing of integration value causes quicker
response.
Step:
1%
Range:
0 100 %
Hint:
When any gain setpoint is set to zero, the corresponding control loop is switched OFF.
PF gain and PF int setpoints are active only when the gen-set runs parallel to mains.

Force value
Force value 1-16

[X]

Source setpoints containing the alternative values for selected target setpoints. The setpoint with index X
corresponds to the Force value Xth function.
Hint:
As the source for Force value channel can be used any compatible value in the controller (in general all
values and setpoints of types integer8,16,32). In that case the corresponding Force value X setpoint is
unused on that channel.

ExtValue1LoLim

[X]

ExtValue2LoLim

[X]

ExtValue3LoLim

[X]

ExtValue4LoLim

[X]

ExtValueX low limit. The value is not decreased under this limit, even if the request still exists (via binary
input ExtValueX down).
Step:
1X
Range:
-32000 ExtValueXHiLim X

ExtValue1HiLim

[X]

ExtValue2HiLim

[X]

ExtValue3HiLim

[X]

ExtValue4HiLim

[X]

ExtValueX high limit. The value is not increased above this limit, even if the request still exists (via binary
input ExtValueX up).
Step:
1X
Range: ExtValueXLoLim 32000 X

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

73

ExtValue1 rate

[ X/s ]

(FV)

ExtValue2 rate

[ X/s ]

(FV)

ExtValue3 rate

[ X/s ]

(FV)

ExtValue4 rate

[ X/s ]

(FV)

ExtValueX rate of change per second. If the binary input ExtValueX down or ExtValueX up is active, the
value is changed according to this rate.
Step:
1 X/s
Range:
1 10000 X/s
Hint:
If binary input ExtValueXreset is active, the corresponding ExtValueX is held at its default value, regardless
of the activity of inputs Up and Down and regardless of incoming external set commands.
Using this function in combination with Force value you can externally control selected setpoints values and
achieve some special behaviour of the controller.

ExtValue1deflt

[ X ] (FV)

ExtValue2deflt

[ X ] (FV)

ExtValue3deflt

[ X ] (FV)

ExtValue4deflt

[ X ] (FV)

ExtValueX default (starting) value. If ExtValueX is changed from this default value using Modbus command,
the new value is kept in ExtValueX until another command arrives or until the controller has been switched
off. If the binary input ExtValueXreset is active, the ExtValueX is held at this value regardless of other
conditions.
Step:
1X
Range:
ExtValueXLoLim ExtValueXHiLim X

Load shedding
All LOAD SHED outputs are activated (closed) to trip the unessential load when gen-set group goes to
island:
e) Before MGCB closes after mains fail and gen-set group is instructed to start in AUT mode (MGCB
application only).
f) Before first GCB closes after mains fail and gen-set group is instructed to start in AUT mode (MCB
application only).
g) When MCB opens from parallel to mains operation in AUT mode (to island-parallel operation).
h) Before MCB is opened in MAN mode by button (to island-parallel operation).
The load shedding function is active in all controller modes except OFF.
Load shedding has three steps and each step is linked with its own Load shed x binary output. There is only
one load shed level and delay for all three steps as well as recon level and delay. Load shed can only move
from one step to the next, e.g. No LoadShed to LdShed S1 to LdShed S2 to LdShed S3 and vice versa.
If manual reconnection of the load is desired, the AutoLd recon setpoint needs to be disabled (AutoLd recon
= DISABLED) and the MAN load recon binary input needs to be configured.
Rising edge on this input resets the controller to a lower stage, but only if the load is under the Ld recon level
at that moment.

LdShedBased on

[ MAINS IMPORT / GEN-SETS ]

(FV)

Selector between two available Load Shedding algorithms:


MAINS IMPORT:
Load Shedding based on measured mains import, relative to the NominMainsImp
setpoint. If the load consumption crosses the pre-selected level, some parts of it can
be tripped to reduce the mains import.
GEN-SETS:
A total gen-set group active power, relative to their nominal powers, is the basic
value for this mode. If the load consumption crosses the pre-selected level (no
IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

74

matter if in island-parallel or mains-parallel situation), some parts of it can be tripped


to reduce the gen-set group load.

Ld shed level

[ % ] (FV)

When mains import / gen-set group load exceeds this level for more than Ld shed delay time, controller
proceeds to the next Load shedding stage - the next binary output Load shed x is closed.
Step:
1 % of NominMainsImp / sum of gen-set Nomin powers
Range: Ld recon level - 200 % of NominMainsImp / sum of gen-set Nomin powers
Hint:
The limit type (NominMainsImp or sum of gen-set Nomin powers) depends on the setting of LdShedBased
on setpoint.

Ld shed delay

[ s ] (FV)

Time delay for Ld shed level limit.


Step:
0,1 s
Range:
0,0 600,0 s

Ld recon level

[ % ] (FV)

When mains import / gen-set group load drops under this level for more than Ld recon delay time, controller
proceeds to the lower Load shedding stage. The binary output for higher stage is opened (Load shed x).
Automatic load reconnection works only when AutoLd recon = ENABLED.
Step:
1 % of NominMainsImp / sum of gen-set Nomin powers
Range:
0 - Ld shed level
Hint:
The limit type (NominMainsImp or sum of gen-set Nomin powers) depends on the setting of LdShedBased
on setpoint.

Ld recon delay

[ s ] (FV)

The amount of time that the load has to be under Ld recon level before the next part of the load is
reconnected.
Step:
1s
Range:
0 - 600 s

AutoLd recon

[ DISABLED / ENABLED ]

(FV)

Switch between manual and automatic reconnection of shedded load:


DISABLED
Rising edge on the input ManualLdRecon resets controller to the lower stage, but only if the
load is under the Ld recon level. Ld recon delay is not important in this case.
ENABLED
Load reconnection is automatic and depends on setpoints Ld recon level and Ld recon
delay. Binary input ManualLdRecon has no function.

PLC settings
The content depends on actual PLC configuration. Contains all setpoints related to the configurable PLC
blocks. If this setpoint group is empty, it is not displayed.

Timer settings
TimerChannel 1-16
Defines the setting of particular timer channel.
There is 16 channels, each defines occurrence date and time (year, month, day, hour, minute), duration time
(in minutes, maximum is 24*60), repeating period (day, week, month, once). In case of week day of the
week selection, when should be executed + selection of repeating (every 1st, 2nd, 3rd or 4th week); In case of
month day of the month selection (e.g. every 3rd day or every 2nd Monday)
Every channel can be disabled by blocking input (physical input or logical output). If blocking input is active
then the timer is not activated.
The channels are divided into groups of 4. Every group has an independent binary output. There is also one
common output for all 16 channels.
IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

75

Act. calls/SMS
History record

[ DISABLED / ENABLED ]

(FV)

Enables or disables active calls/SMS/mails to selected phone, mobile or mail address when a History record
type protection occurs.
Hint:
If enabled for an SMS type active call, an empty Alarmlist would be sent, as this type of protection does not
appear there. So together with the Alarmlist content, the prefix of the History record (Hst in english) is sent
to indicate the reason for the active call (available in future SW versions).

Alarm only

[ DISABLED / ENABLED ]

(FV)

Enables or disables active calls/SMS/mails to selected phone, mobile or mail address when an Alarm only
type protection occurs.

Warning

[ DISABLED / ENABLED ]

(FV)

Enables or disables active calls/SMS/mails to selected phone, mobile or mail address when a Warning type
protection occurs.

Mains protect

[ DISABLED / ENABLED ]

(FV)

Enables or disables active calls/SMS/mails to selected phone, mobile or mail address when a Mains protect
type protection occurs.
Hint:
If enabled for an SMS type active call, an empty Alarmlist would be sent, as this type of protection does not
appear there. So together with the Alarmlist content, the prefix of the Mains protection (MP in english) is
sent to indicate the reason for the active call (available in future SW versions).

MainsP w/Reset

[ DISABLED / ENABLED ]

(FV)

Enables or disables active calls/SMS/mails to selected phone, mobile or mail address when a MainsP
w/Reset type protection occurs.

AcallCH1..3-Type(FV)
Up to three separate channels are available for any of the following types of messages:
DISABLED:
Channel is disabled.
DATA-ANA:
Standard analog modem connection to monitoring SW.
DATA-GSM:
Standard GSM modem connection to monitoring SW.
DATA-ISDN:
Standard ISDN modem connection to monitoring SW.
DATA-CDMA:
CDMA modem connection to monitoring SW.
SMS-GSM:
Channel sends SMS message via GSM network. Only with GSM modem connected.
SMS-CDMA:
Channel sends SMS message via CDMA network. Only with CDMA modem connected.
IB-E-MAIL:
Channel sends E-mail. Only when IG-IB connected.
IB-EML-SMS:
Channel sends E-mail in short format (SMS). Only when IG-IB connected.
An Email contains
- header with serial number and application info
- Alarm list contents
- latest 20 History records (reason, date, time)
Example of EML-SMS:
AL=(Sd Water Temp,Wrn Water Temp,!Emerg Stop,ActCallCH1Fail)
Hint:
GSM modem must be connected to controller for Active GSM call or SMS.
IG-IB does not support direct SMS, just as an email.
Connected device type (Analog / GSM / ISDN / CDMA modem) is recognized automatically.

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

76

AcallCH1..3-Addr
Address for channel 1...3 active call. Each above message type has either a phone number or an e-mail
address associated to it.
For more details see PC software guide chapter IG-IB Internet communication.
Hint:
To receive active call run InteliMonitor Type of connection = Active call. Active call window contains list of
received ANT files. Each list item contains Gen-set name, Date, Time, controller serial number.

NumberRings AA

[ ]

Number of rings prior to answering the modem connection from PC to controller.


Step:
1
Range:
1 30
Hint:
NumberRings AA change is not accepted immedately but after controller is switched on or when modem is
connected to controller.

ActCallAttempt

[ 1 to 250 ]

When an active call is issued, this setpoint defines the number of attempts to deliver the message.
Step:
1
Range:
1 to 250
Hint:
Timeout for connection is 90 sec and after 120 sec controller starts the next attempt. During the time the
controller is trying to issue an active call, incoming calls are blocked.

Acall+SMS lang

[ 1 to 7 ]

The setpoint specifies in which language the SMS and e-mail messages are issued in case of active call.
The adjusted number corresponds with order of language as configured in GenConfig. If the selected
number is out of range of possible languages of the controller, the first language is selected as default.

Date/Time
Time stamp act

[ DISABLED / CONDITION / ALWAYS ]

(FV)

Defines the activity of time stamp function:


DISABLED
No periodic records are made.
CONDITION
Records are made with period given by Time stamp per only if binary input Time
stamp act is active.
ALWAYS
Records are made with period given by Time stamp per regardless of any condition.

Time stamp per


Time interval for periodic history records.
Step:
1 min
Range:
1 - 240 min

#SummerTimeMod

[ DISABLED / WINTER / SUMMER,


WINTER-S, SUMMER-S ]

DISABLED:
Automatic switching between summer and wintertime is disabled.
WINTER (SUMMER) : Automatic switching between summer and wintertime is enabled and it is set to
winter (summer) season.
WINTER-S (SUMMER-S) : Modification for southern hemisphere.

#Time [HHMMSS]
Real time clock adjustment.
IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

77

#Date [DDMMYYYY]
Actual date adjustment.
Hint:
#Time and #Date setpoints are synchronized via CAN bus each hour with the lowest address controller.
#Time or #Date change in any controller changes Time or Date in all controllers on CAN bus.

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

78

Controller configuration and monitoring


IM-NT controller uses the same configuration and monitoring tools as IGS-NT controllers: GenConfig (GC)
and InteliMonitor (IMON).
GC and IMON are based on Windows 98/NT/ME/2000/XP or higher platform and require approximately 30
Mbyte of hard disc free space.

Direct connection to the PC


IGS-NT controller can be connected directly with PC via RS232 or USB interface. Use the crossed RS232 or
USB cable to connect PC with controller.
Hint:
Make sure the grounding system on controller and PC COM port (negative of the PC DC supply) are
identical before the first direct connection. There must not be any voltage between these two points
otherwise the internal PTC protection activates and interrupts RS232 communication. In such case
disconnect RS232 line, wait a minute for PTC recovery and try again. The simple solution is to assure that
the PC supply 240/20V is ground free (GND terminal is not connected).
PC

RS 232

2 - RxD
3 - TxD
5 - GND

RS232

RS232

230 VAC

CONTROLLER

2 - RxD
3 - TxD
5 - GND

0 VDC

Required the same


voltage potential
between GNDs

Battery

GenConfig functions

Extension modules addressing


All I/O function or protection configuration
Setpoints adjusting
Sensor characteristics modification
History record modification
Password level protection modification (password value must be changed in DriveMonitor)
Controller firmware (mhx file) upgrade
Controller application file Up/Down load
Language translator enables
o Create Dictionary between two languages (Dictionary can be used repeatedly)
o Translate current text in Controller (in any language)
o Add new language (up to five)

Configuration steps
Following configuration steps are available in GenConfig software:
Select Extension modules when more inputs and outputs are required
Configure Binary inputs as Protection or Function
Configure Binary outputs
Configure Analog inputs as Protection or Function
Configure History record
Configure password protection
Add/Translate the language

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF

79

InteliMonitor
Functions

On-line direct, Modem or Internet single or multiple engine monitoring


Active Modem or Internet call from engine to PC (activated by selected Alarm)
On-line or Off-line History record listing
Setpoints listing and adjusting (password protected)
Statistics value (e.g. kW hours)
Password and Access code change

Modbus protocol
Standard protocol enables receive/transmit any data or command from a Master system:
Direct connection: RS232, RS422, RS485
Modem connection
9600, 19200, 38400 or 57600 bps, 8 data bits, 1 stop bit, no parity
Transfer mode RTU
Function 3 (Read Multiply Registers)
Function 6 (Write Single Register)
Function 16 (Write Multiply Registers)
The response to an incoming message depends on the communication speed. The delay is not shorter
than the time needed to send/receive 3 and characters.
The complete description of Modbus communication protocol can be found in Modbus Protocol Reference
Guide PI-MBUS-300 and Open Modbus Specification Release 1.0. Both documents are available from web
site at http://www.modicon.com/openmbus/ .
Hint:
Detail Modbus command description see in ComAp Communication guide.

Value and setpoint codes


Hint:
It is possible to export actual values, setpoints and history file on-line from the controller or off-line from the
archive using InteliMonitor Monitor Export data function.

Technical data
Hint:
Technical data of the controller and extension modules find in the IGS-NT-Installation guide-x.y.pdf.

IM-NT MCB, MGCB, SW Version 2.6, ComAp May 2010,

IM-NT-MCB-MGCB-2.6.PDF