You are on page 1of 17

ITEM

DESCRIPTION

UNIT

TOTAL

1.1.1 Connection cable PV modules

Supply and installation of cable flexible electrolytic copper, tin, class 5 according to IEC 60228, type
TECSUN solar (PV) S1ZZ-F or similar, ethylene propylene rubber insulated high modulus HEPR
120 C, 120 EVA sheathed C, the rated voltage 0. 6 / 1 kV, length of 0.5 meters complete with
connectors of the same type as that of the PV module. Including the connection to the PV modules.
Including all parts and accessories for the connections.
Unipolar cross section of 4 mm2.

Ud

65.100

1.1.2 Connecting PV modules

Connection of photovoltaic modules have already been placed, by means of solar cable and
connector supplied with the module.
Including UV bands for fixing cables and all parts and accessories for giving the finished work in a
workmanlike manner.

Ud

56.420

1.1.3 Connection cable for DC.

Supply and installation of flexible cable, type FG7R isolated ethylene-propylene rubber with high
modulus sheat PVC, rated voltage 0.6 / 1 kV, fire retardant for connecting parallel boards with
pictures of cutting, and the inverter .
Including all parts and accessories for the connections.
Unipolar section of 50 mm2.

mt

36.400

mt

3.255

1.1 CONNECTIONS

1.1.4 Earthing system.

Supply and installation of flexible cable type N07V-k rubber insulated with quality E14 sheat
polychloroprene quality EM2, rated voltage 450/750 V, yellow-green, to connect the structure to the
ground collector, including charges and supplies for the connection to the earth.
Unipolar cross section of 6 mm2.

1.1.5 Earthing system.

Supply and installation of flexible cable type N07V-k rubber insulated with quality E14 sheat
polychloroprene quality EM2, rated voltage 450/750 V, yellow-green, to connect the structure to the
ground collector, including charges and supplies for the connection to the earth.
Unipolar section of 50 mm2.

mt

3.000

1.1.6 Earthing system.

Supply and installation of flexible cable type N07V-k rubber insulated with quality E14 sheat
polychloroprene quality EM2, rated voltage 450/750 V, yellow-green, to connect the structure to the
ground collector, including charges and supplies the connection to the ground network.
Unipolar cross section of 35 mm2.

mt

800

Ud

224

Ud

14

1.2 DC ELECTRICAL BOXES IN OPEN FIELD

1.2.1 Electric string boxes. (QSCi)

Supply and installation of electric box with double insulation, high structural strength, made of
polymer-based thermosetting polyester reinforced with glass fiber non-hygroscopic, with solid door
equipped with lock, corrosion resistant, with degree of protection IP -65 and dielectric strength
greater than 5.000 V, including mounting brackets and the bottom plate, containing the following
connected and wired equipment, as per the design specifications attached:
-20 10x38 fuses 16 A 900V (AC / DC). As per attached specifications.
-20 Fuse disconnectors type dfelectric or similar, with a nominal voltage of 1000 V (DC).
-2 Copper busbar systems for positive and negative, in accordance with the attached
specifications.
-40 Terminals for DIN rail polyamide for cables up to 10 mm2.
-2 Terminals for DIN rail polyamide, the reinforced type for the connection of cables up to 95 mm2.
-40 Polyamide cable glands, IP-66, cable 0.6 / 1 kV section of 6 mm2.
-2 Polyamide cable glands, IP-66, cable 0.6 / 1 kV cross section of 25-95mm2.
-1 Multipole surge arrester type 2 rated voltage of 1000 V dc DEHN brand or similar.
-Duct cable cover.
Completely wired, including the identification of each cable, fuses and all other parts and accessories
designed to make the finished work and working in a workmanlike manner.

1.3 DC ELECTRICAL BOXES IN CABIN INVERTER

1.3.1 Framework of isolation (D.C)

Supply and installation of the electrical isolation (dc) box with double insulation, high structural
strength, made of polymer-based thermosetting polyester reinforced with glass fiber nonhygroscopic, with solid door equipped with lock, corrosion resistant, with degree of protection IP-65
and dielectric strength greater than 5.000 V, provided with input and output cables from below, with
their glands.
Including mounting brackets and the bottom plate, containing the following connected and wired
devices, such as by design specifications attached:
-2 Disconnectors with a rated current of 125 A, rated voltage 550-650 Vdc maximum open circuit
voltage 800 Vdc, maximum cross section of 150 mm2 cables connected.
-2 Copper busbar systems for positive and negative, in accordance with the attached specifications.
Fully wired, including any other parts and accessories designed to make the finished work and
working in a workmanlike manner.

1.3.2 Connect Inverter 550 Kw

Installation of inverters SMA SMC 550HE-US to 550KW, including connections through terminal
bimetallic properly installed and all other parts and accessory designed arendere the finished work
and working in a workmanlike manner.

Ud

14

1.3.3 Photovoltaic Modules

Supply and installation of photovoltaic modules NA-E135G5

Ud

56.420

Price per
Unit

ITEM

DESCRIPTION

UNIT

TOTAL

mt

1.260

mt

3.360

mt

420

mt

1.000

mt

1.000

mt

75

mt

3.500

2.1 CONNECTIONS

2.1.1 Cables for AC connections.

2.1.2 Cables for AC connections.

2.1.3 Cables for AC connections.

2.1.4 Cables for AC connections.

2.1.5

Cables for AC connections.


Power CE UC

2.1.6 Check-in MV cable line

2.1.7 MV cable cabin transformation

Supply and installation of flexible cable type FG7R ethylene propylene rubber insulated high
modulus sheat PVC, rated voltage 0.6 / 1 kV, fire retardant, including the connections according to
the design specifications attached.
Including all parts and accessories for the connections.
Unipolar cross section of 400 mm2.
Supply and installation of flexible cable type FG7R ethylene propylene rubber insulated high
modulus sheat PVC, rated voltage 0.6 / 1 kV, fire retardant.
Including all parts and accessories for the connections according to the design specifications
attached.
Unipolar cross section of 300 mm2.
Supply and installation of flexible cable type FG7R ethylene propylene rubber insulated high
modulus sheat PVC, rated voltage 0.6 / 1 kV, fire retardant.
Including all parts and accessories for the connections according to the design specifications
attached.
Unipolar cross section of 35 mm2.
Supply and installation of flexible cable type FG7R ethylene propylene rubber insulated high
modulus sheat PVC, rated voltage 0.6 / 1 kV, fire retardant.
Including all parts and accessories for the connections, according to the design specifications
attached.
Unipolar cross section of 16 mm2.
Supply and installation of flexible cable type FG7R ethylene propylene rubber insulated high
modulus sheat PVC, rated voltage 0.6 / 1 kV, fire retardant.
Including all parts and accessories for the connections, according to the design specifications
attached.
Multipolar section and training, equal to 5G16 mm2.
Supply and installation of medium voltage single core cable for the type RG7H1R, round compact
core copper conductor, operating voltage 12/20 kV, including terminals, connections, and all other
parts and accessories to give the finished work perfectly workmanlike manner.
Unipolar cross section of 240 mm2.
Supply and installation of medium voltage single core cable for the type ARG7H1RX core with
Stranded Compact aluminum, operating voltage 12/20 kV, including terminals, connections, and all
other parts and accessories to give the finished work in workmanlike.
Unipolar cross section of 35 mm2.

Price per
Unit

ITEM

2.2
2.2.1

UNIT

TOTAL

n.

14

Fixed

Fixed

Fixed

16

Fixed

Fixed

16

AC ELECTRICAL PANELS
Three phase inverters SMA SMC500HE-US - IN OPTION -

Protection box in AC
2.2.2 According to the specs: ST QE
QCAB.1

2.2.3

Protection box in AC
According to the specs: ST QE CAP

2.2.4

Protection box in AC
According to the specs: ST QE QBT

Protection box in AC
2.2.5 According to the specs: ST QE
QCAB.2

2.2.5

DESCRIPTION

Framework auxiliary cabin


EC QSA / Qaux

Conversion assembly composed of the main component "inverter" and from a set of components
such as active filters and disconnecting device protection and control.
Among the devices on the market that found the three-phase inverters SMA SMC-500HE-US.
Including anything not specified, but should give the finished work in a workmanlike manner.
Supply and installation of the electrical low voltage distribution box in pre-galvanized steel sheet with
treatment sendzimir 15/10 thick, painted with epoxy powder a minimum thickness of 60 microns, with
fine textured semi-gloss finish, a form of segregation 3a, with outer door glass of dimensions as
design specifications attached, having a degree of protection IP41, with input and output cables from
below, with the following electrical characteristics:
- Rated operational voltage up to 1000 V;
- Rated insulation voltage up to 1000 V;
- Rated current: up to 3000 A;
- Short-time current: 50 kA 1 s;
containing wired and connected to the equipment as specified in the attached project.
Including wiring lines for input and output, accompanied by protective ground terminal, labels and
other not specified, but appropriate to give the finished work in a workmanlike manner.
Supply and installation of the electrical low voltage distribution box in pre-galvanized steel sheet with
treatment sendzimir 15/10 thick, painted with epoxy powder a minimum thickness of 60 microns, with
fine textured semi-gloss finish, a form of segregation 3a, with outer door glass of dimensions as
design specifications attached, having a degree of protection IP41, with input and output cables from
below, with the following electrical characteristics:
- Rated operational voltage up to 1000 V;
- Rated insulation voltage up to 1000 V;
- Rated current: up to 3000 A;
- Short-time current: 50 kA 1 s;
containing wired and connected to the equipment as specified in the attached project.
Including wiring lines for input and output, including wiring lines for input and output, accompanied
by protective ground terminal, labels and other not specified, but appropriate to give the finished
work in a workmanlike manner.
Supply and installation of electrical distribution box in low voltage insulating material having a
degree of protection IP65, with entrance and exit of cables, located in Cabin Inverter 1, with the
following characteristics:
- Rated operational voltage up to 1000 V;
- Rated insulation voltage up to 1000 V;
- Rated operational current up to 32 A;
- Short-time current: 25 kA 1 s;
containing wired and connected to the equipment and subject to space by 20% of departures.
Including wiring lines for input and output, accompanied by protective ground terminal, labels and
other not specified, but appropriate to give the finished work in a workmanlike manner.
Supply and installation of electrical distribution box in low voltage insulating material having a
degree of protection IP65, with entrance and exit of cables, located in Cabin Inverter 2, with the
following characteristics:
- Rated operational voltage up to 1000 V;
- Rated insulation voltage up to 1000 V;
- Rated operational current up to 32 A;
- Short-time current: 25 kA 1 s;
containing wired and connected to the equipment as specified in the attached project and subject to
space by 20% of departures.
Including wiring lines for input and output, accompanied by protective ground terminal, labels and
other not specified, but appropriate to give the finished work in a workmanlike manner.
Supply and installation of the electrical low voltage distribution box in pre-galvanized steel sheet with
treatment sendzimir 15/10 thick, painted with epoxy powder a minimum thickness of 60 microns, with
fine textured semi-gloss finish, a form of segregation 3a, with outer door glass to size, having a
degree of protection IP41, with input and output cables from below, with the following electrical
characteristics:
- Rated operational voltage up to 1000 V;
- Rated insulation voltage up to 1000 V;
- Rated current: up to 125 A;
containing wired and connected to the equipment as specified in the attached project.
Including wiring lines for input and output, including wiring lines for input and output, accompanied
by protective ground terminal, labels and other not specified, but appropriate to give the finished
work in a workmanlike manner.

Price per
Unit

ITEM

UNIT

TOTAL

3.1.1 Cabin Delivery

Supply and installation of cabin prefabricated in one piece in c.a.v. self-supporting without union
joints between walls and between these and the bottom, made
of concrete with high resistance
lightened with expanded clay reinforced with double welded mesh. Including tank prefabricated
foundation, doors and ventilation grilles in flame retardant self-extinguishing fiberglass.
The price includes all charges and plywood needed for the construction of electric lighting, motive
power and ground to specification and those set forth in the attached project.
The cabin will be green and has the following rooms (inner net):
see graphics.
Total external dimensions cm. 945x252x310.
Including any other parts and accessories designed to make the finished work and working in a
workmanlike manner.

3.1.2 Cabin Station

Supply and installation of cabin prefabricated in one piece in c.a.v. self-supporting without union
joints between walls and between these and the bottom, made
of concrete with high resistance
lightened with expanded clay reinforced with double welded mesh. Including tank prefabricated
foundation, doors and ventilation grilles in flame retardant self-extinguishing fiberglass.
The price includes all charges and plywood needed for the construction of electric lighting, motive
power and ground to specification and those set forth in the attached project.
The cabin will be green and has the following rooms (inner net):
see graphics.
Total external dimensions cm. 945x252x310.
Including any other parts and accessories designed to make the finished work and working in a
workmanlike manner.

3.1.3 Cabin Inverter "CAB-2"

F.p.o. cabin prefabricated in one piece in c.a.v. self-supporting without union joints between walls
and between these and the bottom, made
of concrete with high resistance lightened with
expanded clay reinforced with double welded mesh. Including tank prefabricated foundation, doors
and ventilation grilles in flame retardant self-extinguishing fiberglass.
The price includes all charges and plywood needed for the construction of electric lighting, motive
power and ground to specification and those set forth in the attached project.
The cabin will be green and has the following rooms (inner net):
see graphics.
Total external dimensions cm. 645x252x310.
Including any other parts and accessories designed to make the finished work and working in a
workmanlike manner.

3.1

DESCRIPTION

Prefabricated in c.

Supply and installation of cabin prefabricated in one piece in c.a.v. self-supporting without union
joints between the walls and between them and the bottom, made
of high-strength lightweight
concrete with expanded clay reinforced with double mesh Including a bath of prefabricated
foundation, doors and ventilation grilles in flame retardant self-extinguishing fiberglass.
The price includes all charges and plywood needed for the construction of electric lighting, motive
Cabin Transformation MV / LV "CABpower and ground to specification and those set forth in the attached project.
3.1.4
1"
The cabin will be green and has the following rooms (inner net):
see graphics.
Total external dimensions cm. 645x252x310.
Including any other parts and accessories designed to make the finished work and working in a
workmanlike manner.

Price per
Unit

ITEM

3.2

3.2.2 Medium voltage switchgear

3.2.4

3.2.5

3.2.6

UNIT

TOTAL

n.

14

Electrical fittings and various MT

3.2.1 Personal protection devices cabins

3.2.3

DESCRIPTION

Supply and installation of of accessories as described below:


panel for wiring diagram;
table instructions aid those affected by electricity;
indicator plates and tutorial staff;
n 1 CO2 fire extinguisher 5 kg;
gloves for operating voltage 20 kV - only in the cabins with the presence of MV equipments;
Supply and installation with electrical medium voltage protected version suitable for installation at
'interior.
Structural features:
Structure in steel cages composed of cold steel panels edged, powder coated RAL7035 after
appropriate surface treatments.
The magazines will be structurally divided into two main compartments separated by septa metal:
A) Upper compartment containing the busbars.
B) Lower compartment containing equipments.
Mechanical locks for excluding the possibility of exposure to live parts and the obligation of the
operator to make the 'exact sequence maneuvers.
Plant grounding realized with manifolds flat electrolytic copper from 60 mmq which heads all
connections rigid or flexible section of not less than 30 sq. mm.
Electrical characteristics:
Operating voltage: 20/15/10 kV
Isolation voltage at 50 Hz x 60 s: 50 kV
Isolation voltage Impulse: 125 kV
Voltage circuits aux control and signaling: 230 V ac
Voltage auxiliary circuits ill. internal and condensation: 230 V BC
Busbar rated current: 630 A
Short time current for 1 s: 16 kA rms.
Dynamic limit current: 40 kA peak
External Protection Degree: IP 3X
Degree of internal protection: IP 2X
Brand switches: ABB or similar
Brand disconnectors: Coet or similar
Ambient temperature: - 5 C to + 40 C
Max Relative Humidity: 95%
Development frameworks according to specific project attached.

Supply and installation of medium voltage compartment, with design features described in section
3.2.2, such as "incoming feeder with" consisting of:
support reggiterminale, sight glass, set of three capacitive shunt for indicating the presence of
Medium voltage switchgear
voltage in the network using neon lamps, earthing system.
"incoming feeder with"
Dimensions wxdxh: 700x975x1950 mm.
Including medium voltage cables and auxiliaries and all other parts and accessories designed to
make the finished work and working in a workmanlike manner.
Supply and installation of medium voltage compartment, with electrical characteristics as described
Medium voltage switchgear "General above, such as "general protection" consists of:
rotary isolator line 630 A 16 kA 24 kV, 16 kA lower earthing, mechanical interlock between
Protection Fault" car delivery
equipment
Supply and installation of medium voltage compartment, with electrical characteristics described in
Medium voltage switchgear
section 3.2.2, such as "compartment measures" includes:
rotary isolator line 630 A 16 kA 24 kV, 16 kA lower earthing, mechanical interlock between
"compartment measures"
equipment
Fpo of medium voltage compartment, with design features described in section 3.2.2, such as
"general protection" consists of:
rotary isolator line 630 A 16 kA 24 kV, 16 kA lower earthing, mechanical interlock between the
switching device and the access port.
Key lock on the line disconnector or earth
Tern of capacitive shunt with signaling box
Withdrawable vacuum circuit-breaker VD4 / R Abb Sace or similar 24kV 630A 12.5 kA complete
with shunt release, auxiliary contacts and key lock.
Equipment consisting of:
Protection relay with RS485, for protection functions 51S1-51S2-51N, complete with reducing
Medium voltage switchgear "General voltage and current;
Protection Fault" cabin camp
Protective relay with RS485 for protection functions voltmetric, model Thytronic SVF5740, or similar,
complete with n.03 reducers voltage 20kV: 1.73 / 100V: 3
50VA Cl. 6P - 20kV: 1.73 / 100V: 1.73
50VA Cl. 0.5, n.02 reducers voltage 20kV / 100V 50VA Cl. 0.5, antiferrorisonanza resistance.
Motorized control for vacuum switch / SF6 complete closing relay and lamp kit
messages and local command - remote to switch sottovuoto/SF6 type ABB VD4 / R - ABB HD4 / R
Casing holder of low voltage.
Dimensions wxdxh: 900x975x1950 mm.
Including any other parts and accessories designed to make the finished work
and running in a workmanlike manner.

Price per
Unit

ITEM

3.2.7

Medium-voltage transformer 1000


kVA

3.2.9 Medium-voltage transformer 50 kVA

3.2.10 Medium-voltage transformer 20 kVA

3.2.11 Group UPS 1000 VA

3.2.12 Ground node and Links EQP

DESCRIPTION

Supply and installation of three-phase transformer MV / LV windings cast, with the following
characteristics:
- Primary voltage: 20 kV;
- Secondary rated voltage: 300 V;
- Nominal power: 1000 kVA;
- Short circuit voltage: 6%;
- Operating frequency: 50 Hz;
- Wiring diagram windings MT: triangle;
- Wiring diagram windings bt: Star with neutral frankly landed;
- Group membership: Dyn11;
Complete with the following accessories:
- Insulators for connections MT;
- Switch for adjusting the transformation ratio of approximately 5%;
- Eyebolts for lifting;
- Cart with casters for motion of the machine in the longitudinal or lateral;
- Connections for towing;
- Ground terminals;
- Identifying license plates;
-consists of a temperature sensor resistance thermometers Pt100 Ohm in each column;
Dimensions LxWxH: 1540x1000x1850 mm.
Including the cost of the transformer connections to circuits MV / LV and auxiliaries, the correct
accommodation in the transformer box and all other parts and accessories designed to make the
finished work
and running in a workmanlike manner.
Supply and installation of medium voltage compartment, with design features described in section
3.2.2, such as "general protection" consists of:
rotary isolator line 630 A 16 kA 24 kV, 16 kA lower earthing, mechanical interlock between the
switching device and the access port.
Key lock on the line disconnector or earth
Tern of capacitive shunt with signaling box
Withdrawable vacuum circuit-breaker VD4 / R Abb Sace or similar 24kV 630A 12.5 kA complete
with shunt release, auxiliary contacts and key lock.
Equipment consisting of:
Protection relay with RS485, for protection functions 51S1-51S2-51N, complete with reducing
voltage and current;
Protective relay with RS485 for protection functions voltmetric, model Thytronic SVF5740, or similar,
complete with n.03 reducers voltage 20kV: 1.73 / 100V: 3
50VA Cl. 6P - 20kV: 1.73 / 100V: 1.73
50VA Cl. 0.5, n.02 reducers voltage 20kV / 100V 50VA Cl. 0.5, antiferrorisonanza resistance.
Motorized control to switch sottovuoto/SF6 complete closing relay and lamp kit
messages and local command - remote to switch sottovuoto/SF6 type ABB VD4 / R - ABB HD4 / R
Casing holder of low voltage.
Dimensions wxdxh: 900x975x1950 mm.
Including any other parts and accessories designed to make the finished work
and running in a workmanlike manner.

Supply and installation of three-phase transformer MV / LV windings cast, with the following
characteristics:
- Primary voltage: 20 kV;
- Secondary rated voltage: 300 V;
- Rated power: 400 kVA;
- Short circuit voltage: 6%;
- Operating frequency: 50 Hz;
- Wiring diagram windings MT: triangle;
- Wiring diagram windings bt: Star with neutral frankly landed;
- Group membership: Dyn11;
Complete with the following accessories:
- Insulators for connections MT;
- Switch for adjusting the transformation ratio of approximately 5%;
- Eyebolts for lifting;
- Cart with casters for motion of the machine in the longitudinal or lateral;
- Connections for towing;
- Ground terminals;
- Identifying license plates;
-consists of a temperature sensor resistance thermometers Pt100 Ohm in each column;
Dimensions LxWxH: 1540x1000x1850 mm.
Including the cost of the transformer connections to circuits MV / LV and auxiliaries, the correct
accommodation in the transformer box and all other parts and accessories designed to make the
finished work
and running in a workmanlike manner.
Supply and installation of on-line UPS high performance of the rated power of 1000 VA, with the
following characteristics:
-input voltage 230 V;
-nominal frequency 50 Hz;
-distortion of output voltage <2%;
autonomy-> 2h;
Complete with sealed batteries of the type VLRA lead, maintenance, auxiliary contacts for signaling
and fault funzionemento, links to overview and auxiliary, as well as all other parts and accessories
designed to make the finished work and working in a workmanlike .
Supply and installation of the electrical low voltage distribution structure in pre-galvanized steel
sheet with treatment sendzimir 15/10 thick, painted with epoxy powder a minimum thickness of 60
microns, with fine textured semi-gloss finish, a form of segregation 3a, with outer door glass of
dimensions as design specifications, having a degree of protection IP41, with input and output
cables from below, with the following electrical characteristics:
- Rated operational voltage up to 1000 V;
- Rated insulation voltage up to 1000 V;
- Rated current: up to 125 A;
containing wired and connected to the equipment as specified in the attached project.
Including wiring lines for input and output, including wiring lines for input and output, accompanied
by protective ground terminal, labels and other not
specified, but appropriate to give the finished work in a workmanlike manner.

UNIT

TOTAL

19

40

Price per
Unit

ITEM

DESCRIPTION

UNIT

TOTAL

4.1.1 CCTV system

CCTV SYSTEM CONSISTS OF CABINET RACK 19 "CABLE ENTRY FROM THE BOTTOM, WITH
PANEL SUPPLY AND CABLES, VIDEO MATRIX TO 32 IN, 8 OUT,
DISTRIBUTOR OF SERIAL
SIGNALS, TERMINAL IN / OUT, N. 2 EQUIPMENT INCOME TX-RX , KEYBOARD WITH JOYSTICK
TRIAXIAL REMOTE CONTROL

Ud

4.1.2 Control system PLC / SCADA

PLC SYSTEM CONSISTS OF CABINET RACK 19 "CABLE ENTRY FROM THE BOTTOM, WITH
POWER SUPPLY PANEL AND WIRING, PLC CONTROL OF VALUES MEASURED BY INVERTER
CABINS AND PROCESSING AND SYSTEM FOR COORDINATION OF PROTECTION OF PLANT ..
DISTRIBUTOR OF SIGNALS SERIAL, TERMINAL IN / OUT EQUIPMENT INCOME TX-RX,
MONITOR AND KEYBOARD REMOTE CONTROL.

Ud

4.1.3 DOME cameras

CCTV STATION COMPLETE DIGITAL CAMERA CCD COLOR PAL DAY & NIGHT, WITH
MOTORIZED OPTICAL ZOOM LENS 8-60mm, HOUSING AND PAN (PAN & TILT), RECEIVER.

Ud

16

mt

500

Ul

4.1 MONITORING AND CONTROL SYSTEM (CCTV)

4.1.4 Earthing
4.1.5 Patch-cord f.o.

FLEXIBLE SINGLE CORE CABLE FOR CONNECTION TO MAINS EARTH TYPE FIRE
RETARDANT. INSULATION COLOUR GREEN / YELLOW. TRAINING 1x6mmq, ONLY ACCORDING
TO SIZE CEI 20.22. RATED VOLTAGE 450/750V. CODE BN89, FR2OR.
HARNESS / PATCH-CORD FIBER OPTIC MULTIMODE DUPLEX WITH TERMINATION SC FOR
CERTIFICATION IN OPTICAL DRAWERS.
RG11 COAXIAL CABLE SHIELDED / CONCRETE-BLACK FOR VIDEO SIGNALS, OUTDOOR
INSTALLATION.
RG59 COAXIAL CABLE SHIELDED / CONCRETE-BLACK FOR VIDEO SIGNALS, OUTDOOR
INSTALLATION.
SERIAL CABLE UTP 4x2x24AWG CAT.5E SHIELDED / CONCRETE DATA SIGNALS FOR BLU485.
FIBER OPTIC MULTIMODE 62.5 / 125 MICRON DUPLEX WITH TERMINATION SC, ARMED FOR
UNDERGROUND INSTALLATION DIRECTLY.
Supply and installation of flexible cable type FG7R isolated ethylene-propylene rubber with high
modulus sottoguaina PVC, rated voltage 0.6 / 1 kV, fire retardant.
Multi-section and training, equal to 3G4 mm2.

mt

7.200

mt

100

mt

7.750

mt

3.600

mt

3.200

SUPPLY CONDUIT PIPE CARBON STEEL THREADED 4 "SUPPORT FOR CCTV AND RECEIVER.

mt

64

4.1.12 protection maccanica

SUPPLY CONDUIT PIPE CARBON STEEL THREADED 1 "FOR LAYING CABLE EQUIPMENT.

mt

8.000

4.1.13 scratch protection

HEAD PIPE "BUSHING" CARBON STEEL FROM 1 .

Ul

43

4.1.6 Coaxial cable RG11


4.1.7 RG59 coaxial cable
4.1.8 RS485 serial cable UTP
4.1.9 Cable f.o. multimode

4.1.10

Cables for AC connections.


CCTV Power

4.1.11 Support CCTV

Price per
Unit

ITEM

DESCRIPTION

5.1 MONITORING AND CONTROL SYSTEM (CCTV)


Bared conductor from 397.5 AWG in AAC (All Aluminium Conductor), for realizzazzione airline
phase to 13.2 kV, for the distribution of electricity.

UNIT

TOTAL

mt

2.850

5.1.2 support Terminal

Support terminus prepared with rising underground cables, shelf-terminated cables and insulators
and departure airline in anchoring. For details, see standard air line to 13.2 kV Type A, El Salvador.
13RH3: REMATE HORIZONTAL + 13AS3: ACOMETIDA subterranea

Ud

5.1.3 Support Line

Support complete line of brackets insulators and supports for attestation of bare conductors in triple
anchoring. For details, see standard air line to 13.2 kV Type A, El Salvador.
13CH3: COURT HORIZONTAL

Ud

5.1.4 Support Line

Support complete line of brackets insulators and supports for attestation of bare conductors in triple
double suspension. For details, see standard air line to 13.2 kV Type A, El Salvador.
13TD3: TANGENT DOBLE

Ud

5.1.5 Support Line

Support complete line of brackets insulators and supports for attestation of backhoe bare
conductors in simple suspension. For details, see standard air line to 13.2 kV Type A, El Salvador.
13TS3: TANGENT Sencilla

Ud

5.1.1 397.5 AWG bare conductor

Price per
Unit

ITEM

DESCRIPTION

UNIT

TOTAL

n.

1.085

n.

22.785

n.

22.786

mt

16.275

mt

36.400

mt

1.565

42

n.

Excavation excavation for any purpose, for work to be carried out within the suburban, performed
with mechanical means, even in the presence of water, including the removal of pavement and
stone walls still calculated as the volume of excavation, trees and stumps, including interventions by
hand for the regularization of the fund, the surfaces of the cutting and profiling of the walls, and the
paleggiamento, the load on the means of transport, the transport detected or backfill within the
same site and all other costs to give complete the work in a workmanlike manner.

m3

445

Supply and placement of copper conductors insulated with synthetic elastomer sheathed PVC
ethylene-propylene unipolar 3G6 applied within ducts in excavations or tunnels, underground pipes,
including any burden and teaching to give the complete work in a workmanlike manner.

ml

2.965

n.

250

n.

150

150

m3

22.000

m3

3.282

m3

507

650

6 SUPPORT STRUCTURES

6.1.1 Support structures for PV modules

Support structure for solar modules by 13 modules for string, as from the accompanying drawings.
The price includes all materials and accessories required for assembly and transport on site
Number 1085 for facilities

Fixing system to the ground, consisting in the realization of holes with a diameter of 30 cm by
means of a drill with consequent insertion of element galvanized steel of the type "U" SHAPE
NORMAL SERIES UNI 5680 - 80x45 and cast concrete Rck 300 and whatever else is necessary to
Realization of system of ground fixing give the finished work and working in a workmanlike manner. The material from the drilling will be
6.1.2
used as fill to level the ground. Materials required for each pole:
SOLUTION 1
Profile length: 2 meters;
cubic meters concrete: 0.28
length hole 3 to 4 meters.
Fixing system to the ground, consisting of the attachment element in the soil of galvanized steel of
type "U" SHAPE NORMAL SERIES UNI 5680 - 80x45 through mechanical hammering equipment
Realization of system of ground fixing and whatever else is necessary to give the finished work and working in a workmanlike manner.
6.1.3
Materials required for each pole:
SOLUTION 2
Profile length: 3 to 4 meters.;
6.2 CONDUITS UNDERGROUND

6.2.1 Corrugated tube 80 mm.

6.2.2 Corrugated pipe 120 mm.

6.2.3 Corrugated pipe 150 mm.

Supply and installation of conduit within excavation consists


average guy, with crushing strength of 450 N, used for the
including joints and whatever else is necessary to give the
workmanlike manner.
Supply and installation of conduit within excavation consists
average guy, with crushing strength of 450 N, used for the
including joints and whatever else is necessary to give the
workmanlike manner.
Supply and installation of conduit within excavation consists
average guy, with crushing strength of 450 N, used for the
including joints and whatever else is necessary to give the
workmanlike manner.

of corrugated polyethylene pipe


protection of electrical networks,
finished work and working in a
of corrugated polyethylene pipe
protection of electrical networks,
finished work and working in a
of corrugated polyethylene pipe
protection of electrical networks,
finished work and working in a

6.3 LIGHTING

6.3.1 Poles for lighting

6.3.2 Low voltage boxl

6.3.3

Excavation for laying conduits


lighting

6.3.4 Conductor cable for power supply

Supply and installation, pole whip (shelf) or post-top of luminaire. Cabled class 2 isolation. Housing
in light alloy cylinder block into two parts connected by a hinge. In work including electrical
connections, foundation works and all other costs and teaching to give the complete work in a
workmanlike manner at any height. Including any charges and teaching to give the complete work in
a workmanlike manner.
Supply and installation of the electrical low voltage distribution structure in pre-galvanized steel
sheet with treatment sendzimir 15/10 thick, painted with epoxy powder a minimum thickness of 60
microns, with fine textured semi-gloss finish, a form of segregation 3a, with outer door glass to size,
having a degree of protection IP41, with input and output cables from below, with the following
electrical characteristics:
- Rated operational voltage up to 1000 V;
- Rated insulation voltage up to 1000 V;
- Rated current: up to 125 A;
containing wired and connected to the equipment as specified in the attached project.
Including wiring lines for input and output, including wiring lines for input and output, accompanied
by protective ground terminal, labels and other not specified, but appropriate to give the finished
work in a workmanlike manner.

6.4 SYSTEM OF EARTH


6.4.1 Links rope bare copper
6.4.2 Manholes
6.4.3 Foundation earth

Supply and installation of flexible cable to connect the structure to the ground collector, including
charges and supplies for the connection to the earth.
Unipolar cross section of 35 mm2.
Training of cockpit concrete prefabricated guaranteed performance with characteristic compressive
strength of not less
Supply and installation of sink galvanized steel earthing of the length of 3m to the equipotential
earth.

6.5 OTHER CIVIL WORKS

6.5.1 Excavation for leveling

6.5.2 Excavation for laying conduits

6.5.3 Excavation ditches to drain

6.5.4 Inspection pits

Excavation for any purpose, for work to be performed in suburban area, performed with mechanical
means, even in the presence of water, including the removal of road superstructures and drywall still
be calculated as the volume of excavation, trees and stumps, including speeches by hand for
regularization of the bottom surface of the cuts and profiling of the walls, as well as the load on the
means of transport, the transport in detected or backfill within the same site and any other
consideration to make the work complete workmanlike.
Excavation for any purpose, for work to be performed in suburban area, performed with mechanical
means, even in the presence of water, including the removal of road superstructures and drywall still
be calculated as the volume of excavation, trees and stumps, including speeches by hand for
regularization of the bottom surface of the cuts and profiling of the walls, as well as the load on the
means of transport, the transport in detected or backfill within the same site and any other
consideration to make the work complete workmanlike.
Excavation for any purpose, for work to be performed in suburban area, performed with mechanical
means, even in the presence of water, including the removal of road superstructures and drywall still
be calculated as the volume of excavation, trees and stumps, including speeches by hand for
regularization of the bottom surface of the cuts and profiling of the walls, as well as the load on the
means of transport, the transport in detected or backfill within the same site and any other
consideration to make the work complete workmanlike.
Training of cockpit concrete prefabricated guaranteed benefit

Price per
Unit

ITEM

DESCRIPTION

UNIT

TOTAL

Excavation for any purpose, for work to be performed in suburban area, performed with mechanical
means, even in the presence of water, including the removal of road superstructures and drywall still
be calculated as the volume of excavation, trees and stumps, including speeches by hand for
regularization of the bottom surface of the cuts and profiling of the walls, as well as the load on the
means of transport, the transport in detected or backfill within the same site and any other
consideration to make the work complete workmanlike.

m3

310

Conglomerate for foundation works in an aggressive environment, including the vibration of the jets
6.5.6 Base concrete for prefabricated cabin and all other costs necessary to make the mix on site and the work done in a workmanlike manner.
- For works in foundation construction

m3

296

Conglomerate for foundation works in an aggressive environment, including the vibration of the jets
and all other costs necessary to make the mix on site and the work done in a workmanlike manner.
- For works in foundation construction

m3

m3

4.865

mt
mt

1.754
5

m3

750

Excavation for foundation


6.5.5
prefabricated cabin

6.5.7 Concrete weld rod to gate

6.5.8 Granular mixture stabilized


6.5.9 Fence
6.5.10 Entrance gate
PROTECTION GEOTECHNICAL
6.6
WORKS

Foundation road performed with mixed particle size having a maximum size of the elements not
exceeding 40 mm, passing to 2 mm between 20% and 40% and all other costs needed to give the
conglomerate in site and the work performed to perfect rule d 'art.
Perimeter road and connecting roads between the subfields
Supply and installation of metal fence type Orsogril as attached table.
Supply and installation of gate as the attached table.

Realization of gabionades protection along the banks of the river. The structures in gabions will be
modeled according of the slope of the ground below, so as to leave no empty spaces. Before the
installation of gabions the soil should be well compacted to prevent sagging over time. (ref.
R027MXP559950000100)
6.6.1 Protection structures against erosion
The structure gabions must have a cross section L-shaped composed of three blocks (1 x 1) m
minimum height of 2 m
minimum depth of 2 m
minimum length of 250 meters

Price per