Professional Documents
Culture Documents
H2
H3
x1
H1
x2
H2
x3
H3
Earth
point
FRAMIT3 Test lead
Page 1 of 2
6. Connect all the test leads according to the information shown in the new test procedure
dialogue box.
7. Begin the test by hitting the Start Test button. The program will perform the first Winding test.
At this point, the impulse generator will automatically provide the voltage injections. These
signals are used to set the data capture units input range. The program will automatically
generate the first Windings frequency response fingerprint as shown in the example below
(Figure 3):
Figure 3: FRAMIT Test Results
IMPORTANT: The INPUT Voltage graph appearing on your test-screen should be similar in
shape to the one shown above. The OUTPUT Voltage graph and the frequency response result
may however be different. It is extremely important that the tops of the INPUT VOLTAGE
signal and the OUTPUT VOLTAGE signal ARE NOT clipped.
8. Either Keep or Redo this Winding test.
9. Repeat the above steps for the remaining 5 winding tests.
10. Once all six-winding tests are complete, enter all the relevant
information into the Test Details tab as per the example shown in
Figure 4. It is important that the TEST NAME entered here is
meaningful for easy retrieval at a later date. Test details can be
edited again at a later stage if need be.
11. Save the test by clicking on the OK button.