System:
Loop Number
Alarm Settings
Actual alarm values
Alarms needing reset
Post test statement
P&ID:
L=
L=
LL =
LL =
Project:
Description
H=
H=
Signed
MCC Room
Starters and push buttons
Lighting suitable
Accessibility of terminations
Fuse/breaker lock box available
Heating adequate
Cooling adequate
Cabinet air fan acceptable?
Labels on cabinet door correct
Wires labeled
Cables labelled
Other
HH =
HH =
YES
NO
YES
NO
OK N/A Instrument
Air Isolation correct
Accessible
Location correct per Loop diagram and P&ID
Input continuity check
Calibration
Range check with Control system
Loop direct/reverse action
Serial number correct
State change OK on control system
mA =
mA =
mA =
mA =
mA =
Interlock tested
Documentation
Interlock data on loop and P&ID correct
All loop diagram data correct
Master copy red lines for final mark up
Control room has copy until as built issued
Motor
Megged/rating
Rotation
State change OK on control system
Date
Date