Engineering Data

FXV Closed Circuit Cooling Towers

Engineering Data
Single Inlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Dual Air Inlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Structural Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

Engineering Data
Single Air Inlet Models

FXV Engineering Data

Motor HP
Model
Nominal
Number
Tons5
FXV-L421
30
FXV-L422
41
FXV-L423
46
FXV-L424
55
FXV-421
33
FXV-422
46
FXV-423
52
FXV-424
59
FXV-L431
53
FXV-L432
68
FXV-L433
75
FXV-L434
86
FXV-431
57
FXV-432
73
FXV-433
81
FXV-434
95
FXV-L441
83
FXV-L442
100
FXV-L443
110
FXV-L444
130
FXV-441
92
FXV-442
111
FXV-443
122
FXV-444
140
FXV-LQ440
79
FXV-LQ441
116
FXV-Q440
88
FXV-Q441
125
FXV-L641
126
FXV-L642
154
FXV-L643
169
FXV-L644
193
FXV-641
144
FXV-642
175
FXV-643
193
FXV-644
215
FXV-LT642
169
FXV-T642
192
FXV-LQ640
118
FXV-LQ641
168
FXV-Q640
134
FXV-Q641
186
FXV-L661
202
FXV-L662
234
FXV-L663
257
FXV-L664
297
FXV-661
231
FXV-662
267
FXV-663
295
FXV-664
331
FXV-LT662
263
FXV-T662
297
FXV-LQ660
189
FXV-LQ661
269
FXV-Q660
215
FXV-Q661
299

Fan
5
5
5
7.5
7.5
7.5
7.5
10
7.5
7.5
7.5
10
10
10
10
15
10
10
10
15
15
15
15
20
10
15
15
20
15
15
15
20
25
25
25
30
15
25
15
20
25
30
22.5
22.5
22.5
30
40
40
40
45
22.5
40
22.5
30
40
45

Weights (lbs)

Pump

1.5

7.5

Operating1
7,730
8,190
8,680
9,160
7,730
8,190
8,680
9,160
11,230
11,930
12,630
13,380
11,230
11,930
12,630
13,380
14,200
15,150
16,080
17,070
14,200
15,150
16,080
17,070
15,150
17,070
15,150
17,070
18,560
20,050
21,550
23,050
18,560
20,050
21,550
23,050
21,550
21,650
20,050
23,050
20,050
23,050
27,070
29,290
31,570
33,810
27,070
29,290
31,570
33,810
33,790
33,810
29,290
33,810
29,290
33,810

Shipping
5,050
5,370
5,710
6,050
5,050
5,370
5,710
6,050
7,160
7,650
8,140
8,680
7,160
7,650
8,140
8,680
8,760
9,410
10,060
10,770
8,760
9,410
10,060
10,770
9,410
10,770
9,410
10,770
10,890
11,930
12,980
14,040
10,890
11,930
12,980
14,040
12,980
13,080
11,930
14,040
11,930
14,040
15,510
17,070
18,670
20,280
15,510
17,070
18,670
20,280
20,260
20,280
17,070
20,280
17,070
20,280

Connection Sizes2,3

Dimensions
Heaviest
Section
L
W
H
A
2,900
3,220
3,560
3,900
6 1-1/4 8 5-1/4 13 2-3/4 6 3/4
2,900
3,220
3,560
3,900
4,240
4,730
5,220
5,760
9 1-1/4 8 5-1/4 13 2-3/4 6 3/4
4,240
4,730
5,220
5,760
5,120
5,770
6,420
7,130
5,120
5,770
12 1-1/4 8 5-1/4 13 2-3/4 6 3/4
6,420
7,130
5,770
7,130
5,770
7,130
6,730
7,770
8,820
9,880
6,730
7,770
8,820
12 1-1/4 11 10 15 10-3/4 8 8-3/4
9,880
8,820
8,920
7,770
9,880
7,770
9, 880
9,690
11,250
12,850
14,460
9,690
11,250
12,850
18 1-1/4 11 10 16 4-1/4 9 2-1/4
14,460
14,440
14,460
11,250
14,460
11,250
14,460

Make-Up
Water

Coil

Spray
Pump
(GPM)

1 3-3/4

1-1/2

190

1 4-1/4

1-1/2

290

1-1/2

1 8-1/4

500

1-1/2

1-1/2

1 8-3/4

715

1-1/2

1-1/2

2 3/8

900

1-1/2

Internal
Coil
Volume
(GAL)
46
60
74
88
46
60
74
88
69
90
112
133
69
90
112
133
91
120
149
178
91
120
149
178
124
182
124
182
146
192
238
284
146
192
238
284
284
284
194
286
194
286
218
288
358
429
218
288
358
429
429
429
299
439
299
439

Do not use for construction. Refer to factory certified dimensions.

Baltimore Aircoil Company


Copyright Baltimore Aircoil Comany 2009

Engineering Data
Dual Air Inlet Models

FXV Engineering Data

Motor HP

Model Number
FXV-288-31M
FXV-288-31N
FXV-288-31O
FXV-288-31P
FXV-288-31Q
FXV-288-31R
FXV-288-41M
FXV-288-41N
FXV-288-41O
FXV-288-41P
FXV-288-41Q
FXV-288-41R
FXV-288-2TM
FXV-288-2TN
FXV-288-2TO
FXV-288-2TP
FXV-288-2TQ
FXV-288-2TR
FXV-288-1QM
FXV-288-1QN
FXV-288-1QO
FXV-288-1QP
FXV-288-1QQ
FXV-288-1QR
FXV-364-31N
FXV-364-31O
FXV-364-31P
FXV-364-31Q
FXV-364-31R
FXV-364-31S
FXV-364-41N
FXV-364-41O
FXV-364-41P
FXV-364-41Q
FXV-364-41R
FXV-364-41S
FXV-364-2TN
FXV-364-2TO
FXV-364-2TP
FXV-364-2TQ
FXV-364-2TR
FXV-364-2TS
FXV-364-1QN
FXV-364-1QO
FXV-364-1QP
FXV-364-1QQ
FXV-364-1QR
FXV-364-1QS

Nominal
Tons6
344
367
386
419
445
468
364
389
412
448
478
502
349
372
392
424
449
470
325
347
365
394
418
439
442
463
496
525
550
579
464
489
530
561
589
624
443
463
498
526
549
574
420
442
472
499
522
550

Fan
20
25
30
40
50
60
20
25
30
40
50
60
20
25
30
40
50
60
20
25
30
40
50
60
25
30
40
50
60
75
25
30
40
50
60
75
25
30
40
50
60
75
25
30
40
50
60
70

Weights (lbs)

Pump

15

15

Operating
46,000
46,030
46,080
46,240
46,250
46,465
49,690
49,720
49,770
49,930
49,940
50,155
49,690
49,720
49,770
49,930
49,940
50,155
49,690
49,720
49,770
49,930
49,940
50,160
53,900
53,950
54,110
54,120
54,335
54,435
58,260
58,310
58,470
58,480
58,695
58,795
58,260
58,310
58,470
58,480
58,695
58,795
58,260
58,310
58,470
58,480
58,700
58,800

Shipping
27,680
27,710
27,760
27,920
27,930
28,145
30,440
30,470
30,520
30,680
30,690
30,905
30,440
30,470
30,520
30,680
30,690
30,905
30,440
30,470
30,520
30,680
30,690
30,910
31,630
31,680
31,840
31,850
32,065
32,165
34,910
34,960
35,120
35,130
35,345
35,445
34,910
34,960
35,120
35,130
35,345
35,445
34,910
34,960
35,120
35,130
35,350
35,450

Dimensions
Heaviest
Section
8,050
8,050
8,050
8,050
8,050
8,050
9,430
9,430
9,430
9,430
9,430
9,430
9,430
9,430
9,430
9,430
9,430
9,430
9,430
9,430
9,430
9,430
9,430
9,430
9,390
9,390
9,390
9,390
9,390
9,390
11,030
11,030
11,030
11,030
11,030
11,030
11,030
11,030
11,030
11,030
11,030
11,030
11,030
11,030
11,030
11,030
11,030
11,030

Spray
Pump
(GPM)

11 11

24 1/2

18 10-3/8

1,720

13 11-1/8

26 3-1/2

19 0-3/8

1,720

Internal Coil
Volume
(GAL)
600
600
600
600
600
600
712
712
712
712
712
712
712
712
712
712
712
712
706
706
706
706
706
706
696
696
696
696
696
696
828
828
828
828
828
828
828
828
828
828
828
828
862
862
862
862
862
862

Notes:
1. Operating weight is for the tower with the water level in the cold
water basin at the overflow.
2. The actual size of the inlet and outlet connection may vary with
the design flow rate. Consult unit print for dimensions.
3. Inlet and outlet connections are beveled for welding.
4. Standard make-up, drain and overflow connections are located
on the bottom of the unit. Make-up connection is 1-1/2 MPT
standpipe, drain is 2 FPT and overflow is 3 FPT. On single airinlet models, standard make-up, drain and overflow connections
are MPT.

5. Models shipped with an optional gear drive or low sound fan


may have heights up to 10.5" greater than shown. Models with
Whisper Quiet Fans may have heights up to 5-1/2 greater than
shown.
6. Nominal tons of cooling represents 3 GPM of water cooled
from 95F to 85F at a 78F entering wet-bulb temperature.
7. For FXV-44xx, the riser pipe diameter is 4. For FXV-6xx and all
dual air inlet models, the riser pipe is 6.
8. Dimensional reference drawings.

Baltimore Aircoil Company


Copyright Baltimore Aircoil Comany 2009

FXV Engineering Data

Dimensional Reference Drawings

3" OVERFLOW

2" DRAIN

Single Air Inlet Models

6" FLUID OUT

6" FLUID IN

Dual Air Inlet Models

Baltimore Aircoil Company


Copyright Baltimore Aircoil Comany 2009

Engineering Data:
Cold Weather Operation
FXV Engineering Data

FXV Heat Loss Data (BTUH)


Model
Number

Standard
Unit

Unit w/
PCD Hood

Unit w/ PCD
Hood & Insulation

FXV-421
FXV-422
FXV-423
FXV-424

68,400
87,100
105,200
122,400

43,500
47,100
50,500
54,000

30,100
32,300
34,700
37,000

FXV-431
FXV-432
FXV-433
FXV-434

102,800
131,200
158,000
183,000

60,800
65,600
70,600
74,900

43,200
46,500
49,600
52,800

FXV-441
FXV-442
FXV-443
FXV-444
FXV-Q440
FXV-Q441

135,700
172,900
208,000
241,000
172,900
241,000

76,700
82,100
87,600
92,900
82,100
92,900

55,200
59,100
62,900
66,500
59,100
66,500

FXV-641
FXV-642
FXV-643
FXV-644
FXV-T642
FXV-Q640
FXV-Q641

203,400
259,800
313,100
362,900
362,900
259,800
362,900

103,800
109,700
115,600
121,300
121,300
109,700
121,300

75,300
79,300
83,200
86,900
86,900
79,300
86,900

FXV-661
FXV-662
FXV-663
FXV-664
FXV-T662
FXV-Q660
FXV-Q661

304,500
387,500
404,700
536,900
536,900
387,500
536,900

158,200
165,500
172,400
179,100
179,100
165,500
179,100

118,000
123,000
127,600
132,200
132,200
123,000
132,200

FXV-288-31x
FXV-288-41x
FXV-288-2TX
FXV-288-1Qx

760,200
881,100
881,100
881,100

280,700
294,500
294,500
294,500

202,000
211,000
211,000
211,000

FXV-364-31x
FXV-364-41x
FXV-364-2TX
FXV-364-1Qx

894,000
1,036,200
1,036,200
1,036,200

330,100
346,400
346,400
346,400

237,600
248,100
248,100
248,100

Notes:
1 Heat loss based on 50F entering coil water and -10F ambient
with 45 MPH wind (fans and pump off).
2. One inch thick PVC nitrite rubber blend thermal insulation on both
the PCD hood and the casing panels surrounding the coil.

Dimensional Data of Positive Closure Damper Hood

Model
Number

Hood Ship.
Weight (lbs.)

Operating Weight Add


(lbs.)

Length
(L)

Width (W)

Hood Height
(Y)

Unit Height
(H)

FXV-42x

390

320

5 11-7/8

3 5-1/4

2 5-1/8

15 1-3/4

FXV-43x

540

430

8 11-7/8

3 5-1/4

2 5-1/8

15 1-3/4

FXV-44x

720

570

11 11-7/8

3 5-1/4

2 5-1/8

15 1-3/4

FXV-64x

1,160

920

11 11-7/8

5 3-1/2

2 5-1/8

17 9-3/4

FXV-66x

1,650

1,300

17 11-7/8

5 3-1/2

2 5-1/8

17 9-3/4

FXV-288-xxx

1,300

1,040

11 11

6 3-3/8

2 5-1/8

20 2-5/8

FXV-364-xxx

1,500

1,200

13 11-1/8

6 3-3/8

2 5-1/8

20 2-5/8

Notes:
1. Hood shipping weight
includes shipping skid
weight.

Baltimore Aircoil Company


Copyright Baltimore Aircoil Comany 2009

FXV Engineering Data

Structural Support
The recommended support arrangement for FXV Closed Circuit Cooling Towers consists of parallel
I-beams positioned as shown on the drawings. Besides providing adequate support, the steel also
serves to raise the unit above any solid foundation to assure access to the bottom of the tower.
Alternate steel support designs include a cantilevered plan as indicated by the optional minimum D
dimension in the table below. To support an FXV on columns or in an alternate arrangement not shown
here, consult your local BAC Representative.

Single Air Inlet

Optional
Minimum D*

Maximum
Deflection

FXV - 42x

8 3

5 9

3/16

FXV - 43x

8 3

5 9

5/16

FXV - 44x

8 3

5 9

3/8

FXV - 64x

11 7-3/4

8 0

3/8

FXV - 66x

11 7-3/4

8 0

1/2

Model Number

Air
Inlet

*When unit is supported with a cantilever plan, the side


opposite the air inlet shall be cantilevered.

Dual Air Inlet

Maximum
Deflection

FXV-288-xxx

23 9-1/8

1/2

FXV-364-xxx

26 0-5/8

1/2

Model Number

Air
Inlet

Air
Inlet

Notes:
1. Support steel and anchor bolts to be designed and furnished
by others.
2. All support steel must be level at the top.
3. Beams must be selected in accordance with accepted structural
practice. Maximum deflection of beam under unit to be 1/360
of span, not to exceed 1/2 inch.

4. If vibration isolation rails are to be used between the unit and


supporting steel, be certain to allow for the length of the vibration
rails (by others) when determining the length of the supporting
steel, as vibration rail length and mounting hole locations may
differ from those of the unit.
5. If point vibration isolation is used with multi-cell units, the isolators
must be located under the support steel, not between the support
steel and the closed circuit cooling towers.

Baltimore Aircoil Company


Copyright Baltimore Aircoil Comany 2009