TPC Daily Report

Period From : 00:00Hrs To 23:59Hrs

MIYAPUR PSS

Prepared by TPC: Hanuma Rajesh G

Date: 28/07/2016

1. Power Block Summary :

A.

Power Block Approved/


Issued

Power
Block

No.

Power
Block

No.

Part-A No.

16-4127

Part-B No.

16-4127

Part-B No.
B.

Remarks
Company

Power Block Burst


Details
NIL

C.

Power Block Not


Executed

NIL

PIC

Scheduled
Closure

Actual
Closure

Reason
(if any)

NIL

NIL

NIL

NIL

Part-A No.

Remarks

NIL

NIL

2. Service Affecting Failure/Accident/Incident/Near Misses


A.

Time : 00:00 to 00:00hrs

Location:

Description:

NIL

Root cause:

NIL

Resolution:

NIL

Miyapur Depot

3. Energy Consumption (MSS-Miyapur)


Feeder Name

Approved
Load

Maximum
Demand

Apparent
Power

Reactive
Power

Real Power

Power
Factor

132kV Summation Meter

2000 KVA

1212.5 KVA

17700 KVAH

(0) KVARH

17700 KWH

0.999

33kV Incomer-1

N/A

N/A

34638 KVAH

(0) KVARH

4375 KWH

0.126

33kV Incomer-2

N/A

N/A

35319 KVAH

(0) KVARH

10951 KWH

0.310

25kV Incomer-1

N/A

N/A

4504 KVAH

1977 KVARH

3029 KWH

0.673

25kV Incomer-2

N/A

N/A

0 KVARH

0 KWH

N/A

160728_OPE_DRE_001_TPC_MYP daily report

KVAH

4. Miscellaneous Remarks :
1. Since 15/06/2015 BS101 Interrupter when given close command goes to unknown state sometimes (AMS
No: 16-41225)
2. Since 7/10/2015 SS-121 Isolator is showing OPEN status in SCADA workstation even though CLOSED
in field (AMS No: 16-41227)
3. Since 30/11/2015 Minor oil Leakage from Traction Transformer -2 at secondary bushings inspection
chamber. (AMS No: 16-41228)
4. Since 16/2/2016 Battery charger displaying false alarm every time when any of the 25KV GIS breakers are
operated. (AMS No: 16-41230)
5. HVAC Unit-1 is not working at MYP-RSS Building (AMS No.16-41231)
6. SCADA communication is intermittently failing in RSS & TSS RTU (AMS 16-31777)
7. 33KV I/C-1 & I/C-2 Circuit Breaker Face plate showing Ready to close indication in SCADA workstation
even though closed in field (AMS 16-32145)
8. MYP-Depot ASS,HT Board-2 Trafo WTI fault operated showing TRUE status in SCADA workstation (AMS
16-32149)
9. MYP-Depot ASS, HT Board-1 Bus Voltage showing ZERO (0) in PINK colour value even though BUS
charged in SCADA workstation (AMS 16-32150)
10. MYP-Depot ASS Breakers (52-13,52-15,52-16) Face plate showing TRUE Status for both Service & Test
position at the same time in SCADA workstation (AMS 16-32151)
11. In detail view of 33KV RSS C.B (M B 52 010) is not showing MWH & MVAH readings in SCADA
workstation (AMS 16-32152)
12. Since 26/04/2016 SS-113 is not operating through SCADA but when operated locally feedback is true
(AMS 16-32156)
13. Since 01/05/2016 Isolator SS-111 are showing Unknown status in SCADA workstation (AMS 16-32551).
14. MYP-TT-2 abnormal sound observed at LT side (AMS 16-72566).
15. KPHB Circuit Breaker (52-33) not operating thru SCADA (AMS 16- 81626).
16. SR NAGAR Circuit Breaker (52-79) Showing Local Mode in SCADA, even it is in remote mode @ field
(AMS 16-81635)
17. BS-103 is showing unknown status in SCADA workstation when given OPEN/CLOSE command through
SCADA (AMS No. 16-82215)
18. JNTU Station CB 52-28 not closing thru SCADA (AMS-16-82858)
19. KUKATPALLY Station HT-Board-2 all breakers showing Spring discharge indication in SCADA Even
though spring charged in field (AMS-16-82870)
20. TSTRANSCO M.D recorded as 1212.5 KVA @ 10:30 hrs. On 26/07/2016.