Professional Documents
Culture Documents
Ambient Temperature
Tabulated ccc usually assumes ambient
temperature at 30oC
therefore at other ambient
temperatures, tabulated ccc need to be
modified
Tables of Correction Factors for
ambient temperatures (Ca) are used
Tables 4C1 and 4C2
6
Grouping
CCC of cables are affected when they
are grouped together in the same
enclosure
correction factor (Cg) is provided by
Table 4B
Thermal Insulation
The tables for ccc has provision for cable in
thermally insulated wall or ceiling but in contact
with a thermally conductive surface on one side
for cables likely to be totally enclosed in thermal
insulation, the ccc is taken as 0.5 times ccc for
that cable clipped direct to a surface and open
(Reference Method 1)
11
Other Frequencies
50 Hz used on land
400 Hz used in planes, result in smaller size
motors (weight reduction)
however ccc of cables may also be reduced by
50% in large multi-core cables
12
Sizing Cables
Protection of cable against overcurrent
overload
short circuit
Ib In IZ
I 2 1.45I Z
Ib In Iz
3kW
14
Test
Type
Test
Current
Initial
Condition
B, C,
D
1.13 IN
Cold*
No
tripping
B, C,
D
1.45 IN
Right after
Test 1
Tripping
B, C,
D
2.55 IN
Cold *
Tripping
3 IN
No
tripping
5 IN
t > 0.1 s
(i.e. Instantaneous tripping
does not occur)
10 IN
5 IN
10 IN
50 IN
Cold *
Cold *
Test Period
t < 0.1 s
(i.e. Instantaneous tripping
occurs)
Result
Tripping
16
In IZ
I n I t CaC g Ci
It
In
C aC g Ci
Eqn (i)
I 2 = FF I n = 2 I n
2 I n 1.45I
1.45
In
I or 0.725I z or 0 .725 I t C a C g C i
2 z
It
It
Eqn (ii)
0 .725 C a C g C i
17
It
Eqn (iii)
CaC g Ci
18
1
1 1 1
It I x
C a C g Ci C d
Ix
Ca
from
Cg
from
Cd
In
Table 4C2
Table 4B1
0.725
Short circuit
only
Ib
Table 4C1
Table 4B1
Short circuit
& overload
In
Table 4C1
Table 4B1
Short circuit
only
Ib
Table 4C1
Table 4B1
HBC fuses
(BS88)/
BS1361 or
MCBs
20
21
therefore Ib
= 3 x VI(cos)
= Pout/ Pin
= Pout/ (3 x V(cos) )
= 50 x 746/(3 x 400 x 0.88 x 0.95)
= 64.4A
22
I n2 + 0.48 I b2
(i )
( 1 C g2 )
C
2
g
( ii )
23
(i )
( 1 C g2 )
C
2
g
( ii )
24
Example 1
A heater rated at 230 V, 3 kW is to be installed using twinwith-earth pvc-insulated and sheathed cable clipped direct in
a roof space that has an ambient temperature of 400C. The
circuit is protected by a 15-A MCB. The cable is bundled with
four other twin-and-earth cables for a short distance as shown
below. Determine the minimum tabulated current rating of the
circuit and the size of the conductor.
MCB
15A
40 C
15m, clipped direct
3 kW
Heater
25
Solution to Example 1
The design current is :
3000
Ib =
= 13 A
230
In
15
It
=
= 28.74 A
Ca C g 0.87 0.6
From Table 4D2A, column 6, a 4 mm2 cable which has a tabulated
current rating of 36 A is selected.
26
Solution to Example 1
(if circuit is not liable to simultaneous overload)
The design current is :
3000
Ib =
= 13 A
230
27
Solution to Example 1
(if circuit is not liable to simultaneous overload)
It
Ib
13
=
= 24.9 A
Ca C g Ci 0.87 0.6
It
C a Ci
(i )
2
(
1
C
g )
2
I n2 + 0.48 I b
C g2
2
1
(
1
0
.
6
)
2
2
15 + 0.48 13
0 .6 2
0.87
22.1 A
( ii )
Example 2
Determine the minimum tabulated current rating of a multicore, pvc-insulated cable connected to a 3-phase motor rated at
400 V, 15 kW, 0.8 power factor and 90% efficiency. This
motor is subjected to frequent start/stop and is operating at an
ambient temperature of 350C as shown below.
MCB
35C
4C /Cu/PVC, trunking
15kW
0.8 p.f.
90% Eff.
29
Solution to Example 2
The design current is
15 1000
= 30.07 A
Ib =
0.8 0.9 3 400
It
42.10
0.94
= 44.79
Example 3
Q: The circuit is the same as that for Example 1, except that the
cable has to pass through a thermal insulation area over a
length of 3 m. Determine the minimum tabulated current
rating of the circuit and the size of conductor.
S: The minimum tabulated current rating for the circuit is :
IN
15
It
=
= 57.47 A
Ca Cg Ci 0.87 0.6 0.5
32
33
Voltage Drop
Only static voltage drop considered
Equipment will not function properly if incorrect
voltage is being supplied
e.g motors - at 10% being rated voltage output
power (torque) drop by 20%
34
35
230V
216 V
7V
38
40
TVD I b l
Vd =
volts
( simple approach)
1000
For circuits using conductors of 25mm2 or more:
Vd =
(TVD ) z I b l
1000
volts
( simple approach)
41
42
50 = 70
0.004/ C
20
70
95
115
160
-230 -200
-100
0 20
70 95 115
160
43
(for ambient temperature 300C but < 700C and not for fuse (BS3036)
((TVD)
((TVD)
Example 4
A 3-phase motor with a full load current of 102 A,
and a power factor of 0.8 is to be fed by four singlecore, pvc-insulated, copper conductor, non-armoured
cables, clipped direct on a non-metallic surface at 75metre run as shown below. Determine the size of
conductor if the permissible voltage drop from the
MCB to the motor terminal is 2%.
MCB
IFL = 102A
75m
0.8 p.f.
48
Solution to Example 4
Let the design current Ib be the motors full load current. From Table
4D1A, column 7, a 25 mm2 cable with a current rating of 104 A is
initially selected, and the line-to-line voltage drop is calculated as :
(assume Ct = 1) V = (( TVD )r cos + ( TVD ) sin ) I B length
d
1000
(1.5 0.8 + 0.175 0.6 ) 10275
=
1000
= 9.983 V or 2.496% of 400 V
1000
= 7.512 V or 1.88%
Example 5
Q:A single-phase circuit is wired in two-core armoured 25mm2
copper conductor XLPE insulated cable. If Ib = 120A and
length = 30m, what is the voltage drop if the power factor is
0.7 lagging?
S: From the Table 4E2B, column 3,
TVDr = 1.85 mV/A/m, TVDx = 0.16 mV/A/m, TVDz = 1.90 mV/A/m
cos = 0. 7, sin = (1 0.7) 0.5 = 0.714
Vd = ((1.85 x 0.7 + 0.16 x 0.714) x 120 x 30)/1000 = 5.07 V
If power factor has been ignored,
Vd = (1.90 x 120 x 30)/1000 = 6.84V
If oltage drop is limited to 2.5% for this circuit, this would be resulted in
a larger cable, ie 35mm2 , being specified.
50
Example 6
A single-phase circuit having Ib = 27A is run in single-core
700C PVC insulated non-sheathed non-armoured copper
conductor cables. It is enclosed in conduit on a wall with
five other similar circuits. It is protected against both
overload and short circuit by means of a 30A MCB.
If ta = 400C, length = 40m and the power factor = 0.8
lagging, what is the minimum conductor cross-sectional
area that can be used and what is the voltage drop?
52
Solution to Example 6
From Table 4B1, Cg = 0.57
From Table 4C1, Ca = 0.87, and Ci = 1
It In / Ca Cg = 30/(0.57 x 0.87) = 60.5A
From Table 4D1A, column 4,
choose 16mm2 cable which has an It of 76A.
From Table 4D1B, column 3, TVD = 2.8 mV/A/m.
53
I b2
2 )(tt 30 )
It
230+t p
230+70 ( 0.87 20.57 2
Vd
27 2
30 )
2 )( 70
76
230 + 70
300 ( 0.25 0.12 )( 40 )
=
= 0.98
300
((TVD)r .Ct .cos ) I B length
=
1000
( 2.8 0.98 0.8 27 40 )
=
1000
= 2.37V
54
k S I t
2
2
f
55
58
Example 7
A 10 mm2 PVC insulated copper cable is short-circuited
when connected to a 230 V supply. The impedance of the
short circuit path is 0.1 . Calculate the maximum
permissible disconnection time and show that 50 A type 2
MCB to BS 3871 will meet this requirement
V
=
Z
230
=
0 .1
= 2300 A
59
Solution to Example 7
For copper conductor and PVC insulation, Table 43A gives
a value for of 115. So
115 2 10 2
=
= 0.25s
2
2300
61
62
I F,3 =
VLL
(R S + R1 )2 + (X S + X1 )2
63
I F, LN =
VLL
(R S + R1 + R n )2 + (X S + X1 +
X n )2
I F, LL =
VLL
(2R S + 2 R1 )2 + (2X S + 2 X1 )2
66
67