Grid-Connected System: Simulation parameters


Project :

Grid-Connected Project at Bhagwanpur

Geographical Site

Bhagwanpur

Situation
Time defined as

Latitude
Legal Time
Albedo
Bhagwanpur

Meteo data:

Simulation variant :

Country
30.1N
Time zone UT+5.5
0.20
Synthetic - Solar GIS

Longitude
Altitude

India
77.8E
309 m

36 MWp SGIS
Simulation date

30/07/16 14h27

Simulation parameters
Azimuth
Summer Tilt

Coll. plane: Seasonal tilt adjustment

Models used

Transposition

Horizon

Free Horizon

Near Shadings

No Shadings

PV Array Characteristics
PV module

Si-poly
Model
Manufacturer

Original PVsyst database

Number of PV modules
Total number of PV modules
Array global power
Array operating characteristics (50C)
Total area

In series
Nb. modules
Nominal (STC)
U mpp
Module area
Model
Manufacturer
Operating Voltage

Inverter
Characteristics
Inverter pack

Nb. of inverters

0
5

Winter season
Winter Tilt

Perez

Diffuse

O-N-D-J-F-M
25
Erbs, Meteonorm

TP672P-310
Talesun Solar (Zhongli)
20 modules
116140
36003 kWp
646 V
225358 m

In parallel
Unit Nom. Power
At operating cond.
I mpp
Cell area

5807 strings
310 Wp
31987 kWp (50C)
49488 A
203483 m

1250KW_SOLAR PCS
HITACHI
525-900 V
Unit Nom. Power

1250 kWac

24 units

30000 kWac

Total Power

PV Array loss factors


Array Soiling Losses
Thermal Loss factor
Wiring Ohmic Loss

External transformer

PVsyst Licensed to Rays power infra pvt ltd Jaipur (India)

0.22 mOhm

Loss Fraction

1.5 % at STC

1 - bo (1/cos i - 1)

Loss Fraction
Loss Fraction
Loss Fraction
bo Param.

2.0 %
0.0 %
1.0 % at MPP
0.05

33 kV
9142 m
35484 W
0.1 mOhm

Loss Fraction
Loss Fraction
Loss Fraction

0.8 % at STC
0.1 % at STC
1.8 % at STC

Time fraction

2.0 %

Global array res.

IAM =

Grid Voltage
Wires: 3x700.0 mm
Iron loss (24H connexion)
Resistive/Inductive losses

Unavailability of the system

2.0 %
0.0 W/mK / m/s

29.0 W/mK

LID - Light Induced Degradation


Module Quality Loss
Module Mismatch Losses
Incidence effect, ASHRAE parametrization
System loss factors
AC loss, transfo to injection

Loss Fraction
Uv (wind)

Uc (const)

7.3 days, 3 periods

PVSYST V6.39

Rays power infra pvt ltd Jaipur (India)

30/07/16 Page 2/4

Grid-Connected System: Simulation parameters (continued)

User's needs :
Auxiliaries loss

PVsyst Licensed to Rays power infra pvt ltd Jaipur (India)

Unlimited load (grid)


Constant (fans)

0W

... from Poper thresh.

0.0 kW

PVSYST V6.39

Rays power infra pvt ltd Jaipur (India)

30/07/16 Page 3/4

Grid-Connected System: Main results


Project :

Grid-Connected Project at Bhagwanpur

Simulation variant :

36 MWp SGIS
System type
Seasonal tilt: summer/winter
Model
Nb. of modules
Model
Nb. of units
Unlimited load (grid)

Main system parameters


PV Field Orientation
PV modules
PV Array
Inverter
Inverter pack
User's needs
Main simulation results
System Production

Produced Energy
Performance Ratio PR

Grid-Connected
5/25
azimuth
TP672P-310
Pnom
116140
Pnom total
1250KW_SOLAR PCS
Pnom
24.0
Pnom total

55400 MWh/year
78.7 %

Specific prod.

Normalized productions (per installed kWp): Nominal power 36003 kWp

1539 kWh/kWp/year

Performance Ratio PR

1.0

PR : Performance Ratio (Yf / Yr) : 0.787

Lc : Collection Loss (PV-array losses)


0.9 kWh/kWp/day
Ls : System Loss (inverter, ...)
0.24 kWh/kWp/day
Yf : Produced useful energy (inverter output) 4.22 kWh/kWp/day

0
310 Wp
36003 kWp
1250 kW ac
30000 kW ac

Performance Ratio PR

Normalized Energy [kWh/kWp/day]

0.8
6

0.6

0.4

2
0.2
1

Jan

Feb

Mar

Apr

May

Jun

Jul

Aug

Sep

Oct

Nov

0.0

Dec

Jan

Feb

Mar

Apr

May

Jun

Jul

Aug

Sep

Oct

36 MWp SGIS
Balances and main results
GlobHor

T Amb

GlobInc

GlobEff

EArray

E_Grid

EffArrR

EffSysR

kWh/m

kWh/m

kWh/m

MWh

MWh

January

89.0

12.20

117.7

111.9

3758

3401

14.17

12.82

February

116.0

15.60

147.4

140.7

4609

4448

13.87

13.39

March

172.0

21.50

198.9

189.8

5984

5780

13.35

12.90

April

190.0

28.10

194.0

184.2

5635

4864

12.89

11.13

May

203.0

32.40

204.0

193.5

5807

5618

12.63

12.22

June

170.0

33.30

169.6

160.4

4862

4706

12.72

12.31

July

145.0

30.10

144.8

136.6

4245

4107

13.01

12.59

August

147.0

28.10

148.2

139.8

4389

4245

13.14

12.71

September

145.0

26.10

149.1

141.0

4430

4281

13.19

12.74

October

150.0

22.20

185.5

177.3

5581

5387

13.35

12.89

November

113.0

17.20

155.5

148.4

4829

4665

13.78

13.31

December

97.0

12.89

140.0

133.5

4440

3899

14.07

12.35

1737.0

23.34

1954.7

1857.2

58571

55400

13.30

12.58

Year
Legends:

GlobHor

Horizontal global irradiation

EArray

Effective energy at the output of the array

T Amb

Ambient Temperature

E_Grid

Energy injected into grid

GlobInc

Global incident in coll. plane

EffArrR

Effic. Eout array / rough area

GlobEff

Effective Global, corr. for IAM and shadings

EffSysR

Effic. Eout system / rough area

PVsyst Licensed to Rays power infra pvt ltd Jaipur (India)

Nov

Dec

PVSYST V6.39

Rays power infra pvt ltd Jaipur (India)

30/07/16 Page 4/4

Grid-Connected System: Loss diagram


Project :

Grid-Connected Project at Bhagwanpur

Simulation variant :

36 MWp SGIS

Main system parameters


PV Field Orientation
PV modules
PV Array
Inverter
Inverter pack
User's needs

System type
Seasonal tilt: summer/winter
Model
Nb. of modules
Model
Nb. of units
Unlimited load (grid)

Grid-Connected
5/25
azimuth
TP672P-310
Pnom
116140
Pnom total
1250KW_SOLAR PCS
Pnom
24.0
Pnom total

0
310 Wp
36003 kWp
1250 kW ac
30000 kW ac

Loss diagram over the whole year

1737 kWh/m

Horizontal global irradiation


+12.5% Global incident in coll. plane
-3.1%
-2.0%

efficiency at STC = 16.00%

PV conversion
-0.4%

Array nominal energy (at STC effic.)


PV loss due to irradiance level

-8.6%

PV loss due to temperature

66967324 kWh

-2.0%

LID - Light induced degradation

-1.0%

Module array mismatch loss

-1.0%

Ohmic wiring loss


Array virtual energy at MPP

58573016 kWh
-1.5%

Inverter Loss during operation (efficiency)

0.0%
0.0%
0.0%
0.0%

Inverter Loss over nominal inv. power


Inverter Loss due to power threshold
Inverter Loss over nominal inv. voltage
Inverter Loss due to voltage threshold
Available Energy at Inverter Output

0.0%

Auxiliaries (fans, other)

-2.1%

System unavailability

57698748 kWh

PVsyst Licensed to Rays power infra pvt ltd Jaipur (India)

Soiling loss factor


Effective irradiance on collectors

1857 kWh/m * 225358 m coll.

55400081 kWh

IAM factor on global

-0.4%

AC ohmic loss

-1.5%

External transfo loss


Energy injected into grid