Outdoor Site Extend Alarm Detail Desi

Detail Design_v1.1

Scenario: DBS3900 with TP48200A

326293227.xlsx

Security Level

1. BBU with UPEU and UEIU

1.1 UPEU

1. Insert in BBU slot 19


2. EXT_ALM0 support 4 Boolean alarm
3. EXT_ALM1 support 4 Boolean alarm
4. Extend alarm will be configured from EXT-ALM0, the

1.2 UEIU

1. Insert in BBU slot 18


2. EXT_ALM0 support 4 Boolean alarm
3. EXT_ALM1 support 4 Boolean alarm
4.First 7 alarms are designed for TP48200A system in s

2. SLPU with two USLP2

2.1 USLP2

1. insert in SLPU slot 2 and 3


2. OUT0&OUT1 connect with UPE

2.1.1 Input and output PIN relationship of USLP2

08/10/2016

HUAWEI Confidential

Page5of20

326293227.xlsx

Security Level

3. Monitoring unit subrack of TP48200A

3.1 UIM of "Monitoring unit subrack"


1. Dry contact output:
ALM1----> AC power failure
ALM2----> DC undervoltage
ALM3----> PSU fault
ALM4----> SPD fault
ALM5---->Fuse blown
ALM6---->Battery protection

2. Port "GATE" connect with door

4. Signal cable
4.1 Straight through Ethernet cable-From BBU UPEU/UEIU to SLPU USLP2

08/10/2016

HUAWEI Confidential

Page6of20

326293227.xlsx

Security Level

4.2 Signal cable from SLPU IN0/IN1/IN2/IN3 to alarm sensor output port

1. It can be one segment of Ether


2. It should be long enough
3. It should be labeled

08/10/2016

HUAWEI Confidential

Page7of20

326293227.xlsx

Security Level

ured from EXT-ALM0, then EXT-ALM1

or TP48200A system in scenario "DBS3900 with TP48200A"

n SLPU slot 2 and 3


OUT1 connect with UPEU/UEIU EXT-ALM1&EXT-ALM0 by signal cable--Straight through Ethernet cable

08/10/2016

HUAWEI Confidential

Page8of20

326293227.xlsx

Security Level

ntact output:
AC power failure
DC undervoltage

Battery protection

GATE" connect with door alarm sensor

08/10/2016

HUAWEI Confidential

Page9of20

326293227.xlsx

Security Level

be one segment of Ethernet cable or transmission cable without connecter


ld be long enough
ld be labeled

08/10/2016

HUAWEI Confidential

Page10of20

326293227.xlsx

Security Level

Scenario : DBS3900 with TP48200A


1. Internal cable connection

Go to alarm
Sensor
2. Extend cable connection--From USLP2 TO UIM

08/10/2016

HUAWEI Confidential

Page11of20

326293227.xlsx

08/10/2016

HUAWEI Confidential

Security Level

Page12of20

326293227.xlsx

Security Level

1. Use straight through Ethernet cable:


S1: UEIU EXT-ALM0<---->Slot2 USLP2 OUT1
S2: UEIU EXT-ALM1<---->Slot2 USLP2 OUT0
S3: UPEU EXT-ALM0<---->Slot3 USLP2 OUT1
S4: UPEU EXT-ALM1<---->Slot3 USLP2 OUT0
2. One EXT-ALM port supports 4 alarms
3. Connect IN0, IN1, IN2, IN3 to alarm sensor
4. On the port of IN: 1&2 are one pair, 3&4 are one pair
5. Seven of Sixteen extend alarms are designed for TP48200A system already
6. Only Nine extend alarms are left for Genset or other system
7. Detailed alarm ID/Name design will output after confirmation

Go to
UIM

alarm

1. TP48200A GATE alarm cable may directlly connect to 1&2 of IN3 if it's long enough

08/10/2016

HUAWEI Confidential

Page13of20

326293227.xlsx

08/10/2016

HUAWEI Confidential

Security Level

Page14of20

326293227.xlsx

Security Level

system already

08/10/2016

HUAWEI Confidential

Page15of20

326293227.xlsx

08/10/2016

HUAWEI Confidential

Security Level

Page16of20

326293227.xlsx

Security Level

Scenario : DBS3900 with TP48200A

Notes:
1. Slot 18 UEIU first 7 alarms designed to pass TP48200A system monitor alarm. So this scenario support 9 Boolean a
2. Suggest start from slot 3 USLP2 if extend alarm quantity no more than 8.

From BBU
Port
Name

Slot/Card

EXTALM_0

To USLP2
Signal
cable
code

S1

Port
Name

OUT1

Slot 18
UEIU

EXTALM_1

EXTALM_0

S2

S3

OUT0

OUT1

Slot 19
UPEU

EXTALM_1

08/10/2016

S4

OUT0

PIN

OUT1.1
OUT1.2
OUT1.4
OUT1.5
OUT1.3
OUT1.6
OUT1.7
OUT1.8
OUT0.1
OUT0.2
OUT0.4
OUT0.5
OUT0.3
OUT0.6
OUT0.7
OUT0.8
OUT1.1
OUT1.2
OUT1.4
OUT1.5
OUT1.3
OUT1.6
OUT1.7
OUT1.8
OUT0.1
OUT0.2
OUT0.4
OUT0.5
OUT0.3
OUT0.6
OUT0.7
OUT0.8

Slot

Connect to
Port
Name

IN0

IN1
Slot2
USLP2
IN2

IN3

IN0

IN1
Slot3
USLP2

HUAWEI Confidential

IN2

IN3

PIN

IN0.1
IN0.2
IN0.3
IN0.4
IN1.1
IN1.2
IN1.3
IN1.4
IN2.1
IN2.2
IN2.3
IN2.4
IN3.1
IN3.2
IN3.3
IN3.4
IN0.1
IN0.2
IN0.3
IN0.4
IN1.1
IN1.2
IN1.3
IN1.4
IN2.1
IN2.2
IN2.3
IN2.4
IN3.1
IN3.2
IN3.3
IN3.4

Position
UIM
UIM
UIM
UIM
UIM
UIM

Page17of20

326293227.xlsx

Security Level

this scenario support 9 Boolean alarms Max;

Connect to

Alarm Design

Sensor

PIN

Port No.

Alarm
ID

N/A

ALM1

65049

TP48200A AC power failure

LOW

N/A

ALM2

65050

TP48200A DC under voltage

LOW

N/A

ALM3

65051

TP48200A PSU fault

LOW

N/A

ALM4

65052

TP48200A Door alarm

HIGH

N/A

ALM5

65053

TP48200A Fuse blown

LOW

N/A

ALM6

65054

Temperature control unit fault

LOW

65040

AAAA

HIGH

65041

AAAA

HIGH

65042

AAAA

HIGH

65043

AAAA

HIGH

65044

AAAA

HIGH

65045

AAAA

HIGH

65046

AAAA

HIGH

65047

AAAA

HIGH

65048

AAAA

HIGH

08/10/2016

Alarm Name

HUAWEI Confidential

Alarm
Voltage

Page18of20

326293227.xlsx

Severity
Level

Alarm Type

Major

Power

Major

Power

Major

Power

Major

Envoronment

Major

Power

Major

Power

Major

Envoronment

Major

Envoronment

Major

Envoronment

Major

Envoronment

Major

Envoronment

Major

Envoronment

Major

Envoronment

Major

Envoronment

Major

Envoronment

08/10/2016

HUAWEI Confidential

Security Level

Page19of20

326293227.xlsx

Security Level

Scenario : DBS3900 with TP48200A


UEIU_Slot 18 of BBU

SET BTSENVALMPORT: IDTYPE=BYID, BTSID=1000, CN=0, SRN=0, SN=18, PN=0, SW=OPEN, AID=65049, PT=BOOL, AV
SET BTSENVALMPORT: IDTYPE=BYID, BTSID=1000, CN=0, SRN=0, SN=18, PN=1, SW=OPEN, AID=65050, PT=BOOL, AV
SET BTSENVALMPORT: IDTYPE=BYID, BTSID=1000, CN=0, SRN=0, SN=18, PN=2, SW=OPEN, AID=65051, PT=BOOL, AV
SET BTSENVALMPORT: IDTYPE=BYID, BTSID=1000, CN=0, SRN=0, SN=18, PN=3, SW=OPEN, AID=65052, PT=BOOL, AV
SET BTSENVALMPORT: IDTYPE=BYID, BTSID=1000, CN=0, SRN=0, SN=18, PN=4, SW=OPEN, AID=65053, PT=BOOL, AV
SET BTSENVALMPORT: IDTYPE=BYID, BTSID=1000, CN=0, SRN=0, SN=18, PN=5, SW=OPEN, AID=65054, PT=BOOL, AV
SET BTSENVALMPORT: IDTYPE=BYID, BTSID=1000, CN=0, SRN=0, SN=18, PN=6, SW=OPEN, AID=65055, PT=BOOL, AV
SET BTSENVALMPORT: IDTYPE=BYID, BTSID=1000, CN=0, SRN=0, SN=18, PN=7, SW=OPEN, AID=65040, PT=BOOL, AV
UPEU_Slot 19 of BBU

SET BTSENVALMPORT: IDTYPE=BYID, BTSID=1000, CN=0, SRN=0, SN=19, PN=0, SW=OPEN, AID=65041, PT=BOOL, AV
SET BTSENVALMPORT: IDTYPE=BYID, BTSID=1000, CN=0, SRN=0, SN=19, PN=1, SW=OPEN, AID=65042, PT=BOOL, AV
SET BTSENVALMPORT: IDTYPE=BYID, BTSID=1000, CN=0, SRN=0, SN=19, PN=2, SW=OPEN, AID=65043, PT=BOOL, AV
SET BTSENVALMPORT: IDTYPE=BYID, BTSID=1000, CN=0, SRN=0, SN=19, PN=3, SW=OPEN, AID=65044, PT=BOOL, AV
SET BTSENVALMPORT: IDTYPE=BYID, BTSID=1000, CN=0, SRN=0, SN=19, PN=4, SW=OPEN, AID=65045, PT=BOOL, AV
SET BTSENVALMPORT: IDTYPE=BYID, BTSID=1000, CN=0, SRN=0, SN=19, PN=5, SW=OPEN, AID=65046, PT=BOOL, AV
SET BTSENVALMPORT: IDTYPE=BYID, BTSID=1000, CN=0, SRN=0, SN=19, PN=6, SW=OPEN, AID=65047, PT=BOOL, AV
SET BTSENVALMPORT: IDTYPE=BYID, BTSID=1000, CN=0, SRN=0, SN=19, PN=7, SW=OPEN, AID=65048, PT=BOOL, AV