There are different contacts connected in series along a trip circuit of a electrical circuit breaker.
There must be some situation when the circuit breaker should not trip even a faulty current
passes through its power contacts. Such situations are low gas pressure in SF6 circuit breaker, low
air pressure in pneumatic operated circuit breaker etc. In this situation the trip coil of the CB must
not be energized to trip the CB. So there must be NO contacts associated with gas pressure and air
pressure relays, connected in series with breaker trip coil. Another scheme of trip coil is that it
should not be re energized once the circuit breaker is open. That is done by providing one NO
contact of breaker auxiliary switch in series with trip coil. In addition to that the trip circuit of a CB
has to pass through considerable numbers of intermediate terminal contacts in relay, control panel
and circuit breaker kiosk. So if any of the intermediate contacts is detached, the circuit breaker
fails to trip. Not only that, if dc supply to the trip circuit fails, the CB will not trip.
To overcome this abnormal situation, trip circuit supervision becomes very necessary. The figure
below shows the simplest form of trip circuit healthy scheme. Here one series combination of one
http://www.electrical4u.com/trip-circuit-supervision/
7/25/2016
Page 2 of 6
lamp, one push bottom and one resistor is connected across the protective relay contact as shown.
In healthy situation all the contacts except protective relay contact are in close position. Now if
push bottom (PB) is pressed, the trip circuit supervision network is completed and lamp glows
indicating that the breaker is ready for tripping.
The above scheme is for supervision while circuit breaker is closed. This scheme is called post close
supervision.
There is another supervision scheme which is called pre and post close supervision. This trip circuit
supervision scheme is also quite simple. The only difference is that here in this scheme, one NC
contact of same auxiliary switch is connected across the auxiliary NO contact of the trip circuit. The
auxiliary NO contact is closed when CB is closed and auxiliary NC contact is closed when CB is open
and vice versa. Hence, as shown in the figure below when the circuit breaker is closed the trip
circuit supervision network is completed via auxiliary NO contact but when the circuit breaker is
open the same supervision network is completed via NC contact. The resistor is used series with
the lamp for preventing unwanted tripping of circuit breaker due to internal short circuit caused by
failure of the lamp.
So far whatever we have discussed it is only for local controlled installation but for a distance
control installation, relay system is necessary. The figure below shows the trip circuit supervision
scheme wherever a remote signal is required.
http://www.electrical4u.com/trip-circuit-supervision/
7/25/2016
Page 3 of 6
When trip circuit is healthy and circuit breaker is closed, relay A is energized which closes the NO
contact A1 and hence relay C is energized. Energized relay C keeps NC contact in open position.
Now if the circuit breaker is open, relay B is energized which closes No contact B1 hence relay C is
energized. As C is energized, it keeps the NC contact C1 in open position. While CB is closed, if
there is any discontinuity in the trip circuit relay A is de-energized which opens contact A1 and
consequently relay C is de-energized and which make the NC contact C1 in close position and hence
alarm circuit is actuated. Trip circuit supervision is experienced by relay B with the circuit breaker
is open in a similar manner as relay A with the circuit breaker is closed. Relays A and C are timedelayed by copper slugs to prevent spurious alarms during tripping or closing operations. The
resistors are mounted separately from the relays and their values are chosen such that if any one
component is inadvertently short-circuited, a tripping operation will not take place.
The alarm circuit supply should be separated from main trip supply so that the alarm can be
actuated even the trip supply is fail.
http://www.electrical4u.com/trip-circuit-supervision/